1. Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models Introduction
INTRODUCTION
OVERVIEW
The OSM15, OSM27 and OSM38 automatic The status of the recloser is also reflected
circuit reclosers incorporate vacuum interrupters by microswitches connected to the control
inside solid dielectric insulated poles which are electronics. The electronic circuit board where the
housed within the arc fault venting designed, microswitch is fitted has no active elements which
stainless steel tank. This ensures maximum life dramatically improves impulse immunity.
and reliability with a fully insulated arrangement
inside the long life housing. The main circuit bushings are manufactured
from UV stable silicone rubber, providing
Voltage is measured on all six (6) bushings for a high creepage distance silicone bushing
the three phase devices or on four (4) bushings extension, which is completed with optional
for the two phase device or on two (2) bushings termination accessories.
for the single phase device. Current is measured
on all three (3) phases or two (2) phase or single The magnetic actuators are operated from stored
phase using current transformers. energy charged capacitors located in the RC
control cubicle. There is a rating plate located
Each phase of the recloser mechanism is operated on the side of the tank that provides tank rating
by an individual magnetic actuator. In three phase details in accordance with the requirements of
and two phase operation the magnetic actuators ANSI C37.60. There is an earthing point on the
are mechanically interlocked to guarantee correct side of the tank.
operation. The device is latched in the closed
position by magnetic latching and each magnetic The OSM is supplied with tin plated brass
actuator uses a single coil. cable connectors on each bushing. The cable
connectors can be supplied in the form of tunnel
The recloser can be mechanically tripped using terminals to suit cable up to 260mm2 or 2 hole
the yellow mechanical hook stick operated lever NEMA cable palms.
in the base of the tank. The device Open/Close
indication, also located in the base of the tank, The cross sectional diagrams below detail the
uses a green ‘0’ to designate contacts are open OSM tank configuration and main components.
and a red ‘I’ to designate contacts closed.
The control cubicle has three (3) main modules: IP66/NEMA 4 VANDAL PROOF
■■ The operator panel module which provides CABLE HOUSING
There is space provided inside the control cubicle The battery provides power while there is loss
to install any communications equipment to be of auxiliary supply and allows the shutdown
connected to the in built RTU or I/O module. of the device in an orderly fashion if there is a
prolonged loss of AC. The user can carry out a
The equipment has been designed for the RC battery test manually or remotely at a regular
control cubicle to operate over a temperature configurable time interval.
range of -40oC to +55oC inside the IP66
sealed enclosure. iPhone, iPad, PC with CMS
GPS Radome
SmartPhone Software
OSM RC
Recloser Cubicle Panel
Phase Vacuum
CT
3 Phase HV Line CVT Interrupter CVT UPS & 3
Switchgear Digital
Relay
Control Inputs
Rechargeable RS232
Battery USB Ethernet Wi-Fi 4G
Trip/Close Auxiliary Ethernet
Coil switches
Comms.
SIM
RTU or I/O
Radio / modules
PSM modem
Control Cable
AC Power
Supply Remote SCADA/CMS/NOJA APP/Protocols
Power
Data
Control / Indication
Introduction Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models 4.
PROTECTION
The Control and Management Software (CMS) is Voltage is measured on each bushing and current
a software package that runs on a PC and is used is measured on each phase of the OSM recloser
to configure and interrogate the RC control cubicle using capacitively coupled voltage sensors and
both locally and remotely. CMS allows both local current transformers.
and remote download of settings to a device
Phase to Earth Voltage: Range 0.3-22.0kV,
including communication and protection settings.
Accuracy ± 1% or ± 0.1kV
A USB front panel interface is provided on the Phase to Phase Voltage: Range 0.5-38.0kV,
RC for local engineering access. Remote control Accuracy ± 2% or ± 0.1kV
systems such as CMS can connect to the RC Phase Current: Range 0-800A, Accuracy ± 1% or ± 4A
using a number of interfaces which include: Residual Current: Range 0-100A,
RS232, USB and Ethernet. Serial connections Accuracy ± 5% or ± 0.5A
offer 300-115200bps and both full and half Active, Reactive and Total Power:
duplex modes. USB ports can be configured for Range 10-800A, 4.5 - 38kV, Accuracy ± 2%
Serial, Wi-fi and LAN. The Ethernet port provides Active, Reactive and Energy: Range 10-800A, 4.5-
connection to 10/100BaseT networks and can be 38kV, Accuracy ± 2%
configured for Wi-Fi. In addition the RC15 cubicle Frequency: Range 46-55Hz, 55-65Hz
provides an inbuilt Wi-Fi access point. Accuracy ± 0.025Hz at dF/dT < 0.2Hz/s
Accuracy ± 0.05Hz at dF/dT < 0.5Hz/s
NOJA Power Recloser Application for mobile Power Factor: Range 0-1, Accuracy ± 0.02
devices is available for download from the
Android and Apple app store, it will run on DATA LOGS
Android phones, Android tablets, Apple iPhones
Close Open (CO) and Event Logs are accessible
and iPads to provide full local and remote control
from the LCD display. These include critical
of all products connected to the RC control and
operation data such as close open operations, fault
communication cubicle.
types, phase and peak level of fault current. Event
DNP3, 2179, IEC61850, IEC60870-5-101 and logs are time and date stamped to 1 ms resolution
104 communications protocols are provided in which provides additional information such as a
the standard product combined with our ability full log of all operational history including setting
to engineer new protocols to meet specified changes, operations and fault history. The fault
customer requests. The control cubicle has history logs include 50 cycles of pre-trip history to
space to mount a radio or modem. The onboard allow analysis of the fault propagation.
radio power supply is rated at 12V 20W. I/O
modules with eight (8) user configurable inputs LOAD PROFILE LOG
and eight (8) user configurable outputs can be
ordered as options in the RC control. Up to two The Load Profile is logged with a user configured
I/O modules can be fitted extending this to sixteen integration period of either 1, 2, 5, 10, 15, 30, 60
inputs and sixteen outputs. and 120 minutes.
INTEROPERABILITY
NOJA Power can supply accessories which The CMS configuration software is used to
are designed and tested to work within the RC create the logic expressions, program the I/O
specified temperature range of -40oC to +55oC. modules and the local inputs using available
control and indication signals. CMS is also
The RC controller functionality can be extended used to create a subset of data points available
by using internal logic expressions, local inputs for Protocol configuration.
on the Relay module and up to two optional Input/
Output Modules.
IO Module
Local Panel
RC10 RC15
RELAY MODULE RELAY MODULE
Remote Panel
(maximum length 120m)
CMS on Computer
RS485 RS232 Wireless Ethernet Radio Wi-Fi 4G Main 4G Diversity GPS SIM
Module Module Module Module Module Antenna Antenna Antenna Module Card
Introduction Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models 8.
FIELD SAFETY
The app is able to configure and retain the fixed current and phase-voltage (voltage on all six
IP address and port number for each recloser, bushings), frequency, power, power factor, power
which is then stored in a device list that identifies flow direction and energy measurements.
each unit with a name or code. The engineers
can then select, configure, control and interrogate In addition, the app also allows the field engineers
any recloser from the list providing connections to control recloser functionality such as Trip/Close,
via a fixed line, GPRS, WiMax or Wi-Fi. Local/Remote, Active Protection Group, Protection
On/Off, Auto Reclose On/Off, Live Line On/Off and
The engineers will be able to read three phase- Earth Fault On/Off among others.
NOJA POWER RECLOSER REMOTE APP NOJA POWER RECLOSER REMOTE APP SCREENS
9. Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models Introduction
Oscillography Data
The RC can capture an oscillogram of the
PQS HARMONIC CURRENT GRAPH
waveform when a specific event occurs such as a
trip or a close. The amount of waveform captured
prior to the trigger can be configured by the user. duration interruptions. This information is used
This ranges from 0 to 80% of the capture prior to to calculate SAIDI (System Average Interruption
the trigger point. The data can be used to analyse Duration Index), SAIFI (System Average Interruption
power quality fluctuations. Frequency Index) and MAIFI (Momentary Average
Interruption Frequency Index). Both long and short
Captured data can be stored on internal flash interruptions are based on the Loss of Supply
memory or external USB drive. Detection (LSD).
The captured Oscillography files are saved in the Collects long and short interruption information for
file system in the IEEE Std C37.111-1999 Comtrade calculating SAIDI, SAIFI and MAIFI.
Advance Programmable Logic binary.
Sag and Swell
Harmonics The RC records voltage variations (sags & swells)
The RC measures Total Harmonic Distortion occurring outside a user set period of time. Sags
(THD), Total Demand Distortion (TDD) and & Swell voltages are based on the phase to
Harmonics Voltages and Currents up to the earth voltages.
15th Harmonic (800A).
Harmonic data, long and short duration
Harmonic data is averaged over 64 cycles and is interruptions and sag/swell logs can be
made available every 32 cycles. transferred to a USB in IEEE P1159.3 PQDIF.
Long and Short Duration Interruption The PQS is available to all NOJA Power OSM range
The RC stores information relating to long and short ACR customers, free of charge.
Introduction Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models 10.
INSTALLATION
SINGLE PHASE POLE MOUNTING TERMINAL CONNECTORS THREE PHASE POLE MOUNTING ARRANGEMENT
ARRANGEMENT
1. A Switchgear model with matched CTs to provide 0.2A SEF sensitivity, is available for all 3 phase and 2 phase tanks.
2. OSM15-16-800-311, OSM27-12-800-311, OSM38-12-800-301, OSM38-16-800-301 (Single Phase Autorecloser) 1 x Current Transformers, 2x Voltage Screens
OSM15-16-800-312, OSM27-12-800-312, OSM38-12-800-302, OSM38-16-800-302 ( Two Phase Autorecloser) 2 x Current Transformers, 4 x Voltage Screens
3. OSM38-16-800 tested at 40.5kV for interruption
4. Altitudes above 1000m should be corrected in accordance with ANSI C37.60-2012
NOJA POWER AUSTRALIA NOJA POWER BRAZIL NOJA POWER CHILE NOJA POWER EUROPE NOJA POWER UK NOJA POWER USA
CORPORATE OFFICE & FACTORY OFFICE & FACTORY SALES OFFICE SALES OFFICE SALES OFFICE SALES OFFICE
NOJA Power Switchgear Pty Ltd NOJA Power do Brasil Ltda NOJA Power SpA NOJA Power Switchgear Pty Ltd NOJA Power Limited NOJA Power, LLC
16 Archimedes Place, Murarrie Avenida Pierre Simon de Laplace, Ramón Subercaseaux 1268, Sebastianstrasse 38, 53115 4 Stalyhill Drive, Stalybridge 5065 Timberbridge Ln.
Brisbane Qld 4172 764 Techno Park – Campinas – SP Of 1206, San Miguel, Poppesldorf, Bonn, Germany Cheshire SK 15 2TR Alpharetta, Georgia 30022
Australia CEP 13069-301, Brasil Santiago. Chile United Kingdom United States of America
Phone: +61 (7) 3907 8777 Phone: +55 (19) 3283 0041 Phone: +56 (2) 2897 9649 Phone: +49 (0) 228 8236 9408 Phone: +44 (0) 1457 764538 Phone: +1 (971) 404 9039
Fax: +61 (7) 3399 6777 Fax: +55 (19) 3283 0041 Email: sales@nojapower.cl Email: sales@nojapower.eu Email: sales@nojapower.co.uk Email: sales@nojapower.com
Email: sales@nojapower.com.au Email: vendas@nojapower.com.br Web: www.nojapower.cl Web: www.nojapower.eu Web: www.nojapower.co.uk Web: www.nojapower.com
Web: www.nojapower.com.au Web: www.nojapower.com.br
Distributor
Scan to view
NOJA Power
website
NOJA Power® and OSM® are registered trademarks of NOJA Power Switchgear Pty Ltd. This document is copyright and is intended for users and distributors of NOJA Power Switchgear product. It contains information that is the intellectual property of NOJA Power Switchgear and the document, or
any part thereof, should not be copied or reproduced in any form without written permission from NOJA Power Switchgear. NOJA Power® and OSM® are registered trademarks of NOJA Power Switchgear and should not be reproduced or used in any way without written authorization.
NOJA Power Switchgear applies a policy of ongoing development and reserves the right to change product without notice. NOJA Power Switchgear does not accept any responsibility for loss or damage incurred as a result of acting or refraining from action based on information in this User Manual.
NOJA-560-07