EEE3004
LAB ASSESSMENT 1
Slot :L21+22
AC-DC Conversion
AIM: To study the wave form for single phase full wave converter with R load
and RL load
APPARATUS REQUIRED:
Manual:
Simulink:
R – LOAD
RL - LOAD
RLD-LOAD
Tabulation:
With R and RLD load:
R = 10Ω
α(deg) Vo(avg) measured Vo(avg) calculated
0 204.4 206.9
30 191.1 193.04
60 153.8 155.17
90 102.4 103.45
180 0 0
With RL load:
R = 10Ω ; L =50mH
0 205 206.9
30 177.3 179.1
60 105.5 103.4
90 64.1 0
180 0 -206.9
Graphs: FOR R LOAD:
INFERENCE:
1) The output waveform of R and RLD load is same.
2) The RL load has 2 different modes of working(continuous and
discontinuous).
3) The output wave is fully rectified wave(2 pulse mode).
4) It have both rectifier and inverter modes for the given value of α
̒
Ex No:2 Date: 26-08-2021
APPARATUS REQUIRED:
Manual:
Simulink:
Symmetrical semi converter:
R-load
Rl-load
Rl-load
Tabulation:
a)Symmetrical:
With RL load:
R = 10Ω ; L =50mH (Continuous mode)
α Vo(avg) measured Vo(avg) calculated
0 204.8 206.9
30 191.4 193.04
60 153.3 155.1
90 101.6 103.4
120 50.04 51.76
150 12.23 13.8
180 0 0
b) ASymmetrical:
With R load: (Discontinuous mode)
R = 10Ω
α(deg) Vo(avg) measured Vo(avg) calculated
0 204.1 206.9
30 191.4 193.20
60 153.5 155.1
90 102.5 103.4
180 0 0
With RL load:
0 204.4 206.9
30 191.4 193.20
60 153.6 155.1
90 102.4 103.4
180 0 0
GRAPHS:
SYMMETRICAL and ASYMMETRICAL:
FOR R LOAD:
RL-LOAD:
Manual graph:
RESULT: Wave forms for single phase semi-converter with R and RL
load were plotted and observed by using MATLAB.
INFERENCE:
1) The semi-convertors are of 2 types symmetrical and asymmetrical.
2) The output voltage waveform is same for both symmetrical and
asymmetrical.
3) The output voltage waveform resembles the half wave converter
for R load and full wave convertor for R and RLD load.
Ex No: 3 Date: 02-09-2021
APPARATUS REQUIRED:
Manual:
Simulink:
R-Load:
RL-Load
RLD load
Tabulation: With R load: α ≤ 30° continuous mode;
R = 10Ω
α(deg) Vo(avg) measured Vo(avg) calculated
0 279.4 280.22
15 269 270.67
30 241.5 242.68
60 161.1 280.22
90 80.45 140.11
150 0 0
With RL load:
0 279.1 280.22
15 269.6 270.67
30 241.5 242.68
60 139.2 140.11
90 41.8 0
150 0 -242.68
GRAPHS:
FOR R LOAD: α = 0° (continuous mode)
INFERENCE:
For alpha less than 30, the output voltage and current is in continuous
mode. For alpha greater than 30,the output is in discontinuous mode.
For R load, when alpha is greater than 30; the output voltage and
current is discontinuous between A and C and voltage is zero.For RL
load, when alpha is greater than 30;the voltage is discontinuous
between A and C and the inductor discharges current during this period.