PART 1 GENERAL
1.1 SECTION INCLUDES
1.3 REFERENCES
D. ASTM A 82 / A 82M- Standard Specification for Steel Wire Plain for Concrete
Reinforcement.
02836-1
E. ASTM A 123 / A 123M - Standard Specification for Zinc (Hot Dip Galvanized)
Coatings on Iron and Steel Products.
F. ASTM A 185 - Standard Specification for Steel Welded Wire Reinforcement, Plain,
for Concrete Reinforcement.
I. ASTM D 1556 - Standard Test Method for Density of Soil in Place by the Sand-Cone
Method.
J. ASTM D 2167 - Standard Test Method for Density and Unit Weight of Soil in Place
by the Rubber Balloon Method.
K. ASTM D 2922 - Standard Test Method for Density of Soil and Soil-Aggregate in
Place by Nuclear Methods (Shallow Depth).
L. ASTM D 3017 - Standard Test Method for Water Content of Soil and Rock in Place
by Nuclear Methods (Shallow Depth).
N. ASTM D 4716 - Standard Test Method for Constant Head Hydraulic Transmissivity
(In-Plane Flow) of Geotextiles and Geotextile Related Products.
P. ASTM F 904 - Standard Test Method for Comparison of Bond Strength or Ply
Adhesion of Similar Laminates Made from Flexible Materials; 1991.
1.4 SUBMITTALS
02836-2
2. Manufacturer's certifications that the ultimate tensile strength and junction
strength of the geogrid are equal to or greater than those specified.
A. Design Requirements: Design retaining wall system in accordance with the local
codes and regulations and the design guidelines of AASHTO, NCMA or Tensar
International Corporation Design shall be by a professional engineer registered in
the state where the project is located and who is employed by a firm that has
designed at least five projects of similar construction and scope.
B. Prevent excessive mud, fluid concrete, epoxy, or other deleterious materials from
coming in contact with and affixing to retaining wall materials.
B. Do not place backfill during wet or freezing weather that prevents conformance with
specified compaction requirements.
PART 2 PRODUCTS
2.1 MANUFACTURERS
02836-3
A. Acceptable Manufacturer:
1. SierraScape Facing Unit, Diagonal Strut and Connection Rod Manufacturers
approved by Tensar International Corporation 5883 Glenridge Dr., Suite 200,
Atlanta, GA 30328. ASD. Tel: (404) 250-1290 (Intl.), Toll Free: (866) 472-
7161. Fax: 404-250-9185. Web Site: www.tensarcorp.com/A. E-mail:
info@tensarcorp.com.
2. Tensar Structural Geogrid: The Tensar Corporation, 1nc. 1210 Citizens
Parkway, Morrow, GA 30309.
2.2 MATERIALS
A. SierraScape Facing System: Steel welded wire mesh facing unit, bent 90 degrees
at long center line to form "L" shaped unit; vertical section as face to retain fill, and
horizontal leg extending into fill, with structural geogrid mechanically connected to
rear edge of horizontal leg and diagonal struts supporting top edge of vertical leg.
1. Wire Mesh Facing Unit: Galvanized, in accordance with ASTM A 82, ASTM A
185 and ASTM A 123 / A 123M.
2. Wire Strut Type: Galvanized, in accordance with ASTM A 641/641M.
3. Wire Mesh Facing Unit: Steel in accordance with ASTM A 82 and ASTM A
185.
4. Wire Strut Type: Steel in accordance with ASTM A 82.
5. Wire Mesh Spacing: 1.80 inches by 12.75 inches (45 mm by 324 mm)
(vertical x horizontal wires) unless otherwise indicated on the Drawings.
6. Wire Mesh Minimum Diameters: 0.192 inch (4.87 mm), vertical wires and
0.243 inches (6.17 mm) horizontal wire (before galvanizing).
7. Wire, Strut, Minimum Diameter: 0.243 inch (6.17 mm).
8. Tie wire or cable ties to connect vertical wires of adjacent facing units.
9. Method of Connecting Geogrid to Facing Unit: Inverted U or V-shaped loops
in wires of horizontal leg near rear edge fit through alternate apertures
between geogrid ribs and bear against transverse direction bars of geogrid,
forming mechanical connection to transfer load between facing unit and
geogrid. Connection secured by 3/4 inch (20 mm) by 54 inch (1.37 mm) long
SierraScape connection rod placed through loops and over geogrid ribs. Rods
formulated with 25 percent glass filled high density polyethylene (HDPE).
02836-4
1. Ultimate Tensile Strength: 4800 pounds per linear foot (70 kN/M), minimum
average roll value, when tested in accordance with ASTM D 6637.
2. Junction Strength: 4520 pounds per linear foot (66kN/m), minimum average
roll value, when tested in accordance with GRI-GG2.
I. Geogrid (Face Backing): Tensar BX1120: Polymeric grid formed by regular network
02836-5
of integrally connected tensile elements with apertures of sufficient size to retain a 1
inch to 2 inch (25 mm to 51 mm) Stone Face Fill.
1. Aperture Size: 1 inch by 1.3 inches (25 mm by 33 mm).
2. Carbon Black Content: 2.0 percent.
J. Stone Fill: Free draining, uniformly graded stone placed immediately behind the
face of the wire mesh facing unit.
1. 100 percent passing a 4-inch (102 mm) sieve.
2. 0 to 10 percent passing a 2-inch (51 mm) sieve.
3. 100 percent passing a 2-inch (51 mm) sieve.
4. 0 to 15 percent passing a 1-inch (25 mm) sieve.
K. Plantable Fill: Fine grained organic soil placed immediately behind the face of the
facing unit for the purpose of supporting vegetation.
1. 100 percent passing a No. 10 sieve.
2. 0 to 75 percent passing a No. 200 sieve.
3. LL < 50.
4. PI < 20.
2.3 ** NOTE TO SPECIFIER ** For use with plantable facing fill or reinforced backfill facing fill.
Delete if not required.
02836-6
2. Minimum Allowable Peel Strength of Geotextile from Polyethylene Net: Not
less than 1 pound per inch of width (4.45 Newtons per meter of width) when
tested in accordance with ASTM F 904.
PART 3 EXECUTION
3.1 PREPARATION
C. Excavation:
1. Excavate subgrade vertically to plan elevation and horizontally to designed
geogrid lengths.
2. Geotechnical Engineer will inspect foundation area to ensure proper bearing
strength.
3. Remove soils not meeting required strength and replace with Geotechnical
Engineer-approved materials.
3.2 CONSTRUCTION
A. Construct SierraScape wall system in accordance with approved shop drawings and
manufacturer's instructions.
02836-7
the loops extend up through every other aperture of the geogrid. Pull the
geogrid back such that the transverse bar is in contact with the connection
loops. Use two full widths of geogrid per facing unit. The two ribs on outer
edges of the geogrids should be positioned between the first two wires on the
edges of the facing unit. The two ribs on the opposite edges of the geogrid
should be positioned between the center wire and the wires adjacent to it.
Two ribs of geogrid shall be positioned between each pair of wires.
3. Where the transverse bar cannot engage the wire connection loop due to
misalignment of apertures and wire loops, cut the transverse bar midway
between the wire loops to allow the geogrid to be spread or overlapped
slightly to achieve correct alignment of grid apertures with connection loops.
The transverse bar will usually have to be cut at the ends of the third, fifth and
seventh apertures from both edges of the geogrid and occasionally at a few
apertures in the center section of the geogrid to achieve the correct alignment
with the wire connection loops.
4. Thread the SierraScape connection rods through the wire connection loops
over the geogrid ribs.
5. After placement of geogrid and any required face wrap, place seven wire
support struts on approximately 18-inch (475 mm) centers connecting the
upper horizontal wire on the face of facing unit to back wire behind the
connection loop. Place one of the support struts at each end of the facing unit
between the outer two wires.
D. Fill:
1. Pull connection tight and secure by placing facing fill over the connection prior
to placement of reinforced fill over rest of geogrid.
2. Stone Face Fill (2-inch to 4-inch): Place stone face fill over horizontal leg of
facing unit to dimensions shown on shop drawings and cover with geotextile
to separate from reinforced backfill. Compacted lift thickness: Maximum 9
inches (229 mm).
3. Stone Face Fill (1-inch to 2-inch): Place Tensar BX1120 Face Backing
geogrid inside facing unit and place stone fill over horizontal leg of facing unit
to dimensions shown on shop drawings and cover with geotextile to separate
from reinforced backfill. Compacted lift thickness: Maximum 9 inches (229
mm).
4. Plantable Face Fill: Place the Turf Reinforcement Mat inside facing unit and
place plantable fill in lifts to dimensions shown on shop drawings. Compacted
lift thickness: Maximum 9 inches (229 mm).
5. Soil Face Fill: Place geotextile inside facing unit and place reinforced backfill
as shown on shop drawings. Compacted lift thickness: Maximum 9 inches
(229 mm).
6. Backfill: Place reinforced backfill material in compacted lifts, maximum 9
inches (229 mm) deep. Compact to minimum of 95 percent Standard Proctor
Dry Density in accordance with ASTM D 698.
7. Use only hand-operated compaction equipment within 3 feet (914 mm) of
front face. Use a minimum of 3 passes to compact this zone.
8. Do not perform soil density testing within 3 feet (914 mm) of front face.
9. Smooth and level backfill to ensure geogrid lays flat.
E. Geogrid placement:
1. Unroll the geogrid on the compacted backfill and cut to the length indicated.
2. Pull the geogrid taut to remove slack in the geogrid and at the facing unit
connection.
02836-8
3. Stake or pin the geogrid near the end to maintain alignment and tension
during filling.
4. Place a minimum of 3 inches (75 mm) of fill between overlapping layers of
geogrid where overlapping occurs behind curves and corners of a wall.
5. Rubber tired vehicles may travel on the geogrid at low speeds, less than 5
miles per hour. Turning of vehicles should be avoided to prevent dislocation
or damage to the geogrid and the connected wall facing units.
6. Tracked vehicles shall not be operated directly on the geogrid. A minimum of
8 inches (200 mm) of fill cover over the geogrid is required for operation of
tracked construction vehicles in the reinforced zone.
7. Place geogrid shims on the front flange of all facing units connected to
geogrid as shown on the shop drawings or as shown in the Tensar
International Corporation Construction and Quality Control Manual.
A. Testing and Inspection will be provided by the Owner's Testing Agency as specified
in Section 01400 Testing and Inspection Services. Notify the Architect 72 hours in
advance of testing.
E. Frequency of Tests:
1. Subgrade Soil: A minimum of one test per 1000 SF (100 SM) of surface area.
2. Reinforced Backfill: Provide one test for every 50 CY (40 CM) of fill placed.
3.4 PROTECTION
END OF SECTION
02836-9