DEHNguard® M ...

CI 275 (FM)
• No additional backup fuse required due to arrester
backup fuse integrated in the protection module
• Prewired, modular surge arrester for 230/400 V
systems consisting of a base part and plug-in
protection modules

See page 69

DEHNguard® M YPV SCI ... FM


• Prewired, modular surge arrester for use in photovol-
taic systems consisting of a base part and plug-in
protection modules
• Combined disconnection and short-circuiting device
with safe electrical isolation in the protection module
prevents fire damage due to d.c. arcs
See page 104

Surge Protection DEHNguard® S CI 275 (FM)


• No additional backup fuse required due to arrester
backup fuse integrated in the protection module
• Universal surge arrester consisting of a base part
and a plug-in protection module with integrated
backup fuse

See page 75

BITZDUCTOR® XTU ML4 (2) BD 0-180


• New combined lightning current and surge arrester
with actiVsense technology
• Automatically detects the operating voltage of the
wanted signal
• Optimally adjusts the voltage protection level to the
signal voltage currently applied
See page 179

BXT ML4 BE C 12
• BXT combined lightning current and surge arrester
module with LifeCheck for protecting 2 pairs
• Specifically coordinated with applications with diode
circuit at the input, current loops (TTY) and opto-
coupler inputs

See page 191

BXT ML2 B 180


• TYPE 1 lightning current arrester module,
with LifeCheck monitoring system
• Two-pole device with direct shield earthing
• Suitable for almost all applications

See page 195

BXT ML2 BD HF EX 6
• BXT surge arrester module with LifeCheck for use in
hazardous areas
• For protecting one pair of intrinsically safe circuits
and RS485 bus systems
• Self-capacitance and self-inductance negligibly small

See page 316

DRC LC M3+ Test Device


• For fast testing of LifeCheck-equipped SPDs
• Handheld device, easy transport and operation
• With database function for the documentation
of results

See page 362

Catalogue 2010/2011
New Products
DEHNbloc® Maxi NH00 255 DEHNguard® M ... 150/320/385/440 (FM)
• Coordinated, spark-gap-based lightning current arres- • Prewired, modular surge arrester consisting of a base
ter with a discharge capacity up to 25 kA (10/350 μs) part and plug-in protection modules
• No tripping of 32 A gL/gG fuses up to short-circuit • New models with a max. continuous operating voltage
currents of 50 kArms of 150 V, 320 V, 385 V and 440 V

See page 49 See page 76

DEHNbloc® M 1 320 (FM) DK 25 Feed-Through Terminal


• Coordinated, spark-gap-based lightning current arres- • For changing the wiring level
ter with a max. continuous operating voltage of 320 V • Supports lightning-impulse-current-conform
and a discharge capacity up to 25 kA (10/350 μs) installation of SPD combinations
• No tripping of 32 A gL/gG fuses up to short-circuit
currents of 50 kArms

See page 46 (47) See page 145

DEHNguard® S VA (FM) IGA 10 V2 IP54


• Universal surge arrester consisting of a base part and • Enclosure for the installation of surge arresters,
a plug-in protection module tested with lightning impulse currents
• Leakage-current-free series connection of a varistor • Degree of protection of IP54
and a spark gap in the plug-in protection module • Sealable

See page 112 See page 146

BXT ML2 BD DL S 15 BITZDUCTOR® VT ALD 36


• BXT combined lightning current and surge arrester • Energy coordinated combined lightning current and
module with LifeCheck monitoring system surge arrester
• Specifically coordinated with the requirements for • For protecting earth-free d.c. supply systems up to
Dupline buses nominal currents of 4 A
• Terminals for direct and indirect shield earthing • Low voltage protection level, suitable for sensitive
terminal equipment
See page 198 See page 223

NET PRO 10X TC1 RST DEHNgate DGA LG 7 16 X


• Compact and cost-effective protective board with 10 • Coaxial surge arrester for HF technology
RJ45 ports for the protection of telecommunications • For multi-frequency applications with d.c. supply system
systems • Optionally available with self-extinguishing gas dischar-
• Input equipped with cage spring terminals which can ge capsule up to nominal currents of 2.5 A
be removed as a block for easy line measuring • Maximum transmission and PIM performance
• Integrated protection against power crossing
See page 252 See page 276

EG NET PRO 10X 19” DEHNpipe DPI CD HF EXD 5 M


• 19“ (482.6 mm) stainless steel enclosure for installati- • Flameproof surge arrester for use in hazardous areas
on into distribution cabinets • For protecting measuring circuits and bus systems
• For up to 5 NET PRO 10X TC1 RST protective boards • Easy installation on field devices with a spare cable
• Compact in design, protection of up to 50 ports over gland
a vertical module

See page 252 See page 309

EG NET PRO 10X 3HE DEHNpipe DPI CD EXD 230 24 M (N)


• Stainless steel enclosure, 3 vertical modules for instal- • Dual surge protection for 230 V power supply systems
lation in 19“ (482.6 mm) distribution cabinets and data interfaces
• For NET PRO 10X TC1 RST protective boards • Easy installation on field devices with a spare cable
• Ideally suited for small-sized distribution boards gland
• Approved for hazardous areas due to flameproof
enclosure
See page 252 See page 310

Pipe Clamp for Use in hazardous Areas DPRO 230 LAN100


for Diameters from 26.9 mm to 500 mm • Dual surge protection for power supply systems and
• For installation in potentially explosive atmospheres LAN interfaces
(hazardous zones 1 and 2 as well as 21 and 22) • Gigabit Ethernet protection (1000 Base-T) with an
• Tested according to explosion group IIB elegant design
• Considerably reduced installation time

See page 351 See page 341


Contents

100 th Anniversary of DEHN. 2


DEHN – Worldwide. 8
DEHN – Safety according to Specification. 10

Surge protection for


Power Supply Systems 15
SPDs for low-voltage installations and equipment
Contents 17

Surge protection for


Information Technology Systems 153
SPDs for IT installations and equipment
Contents 155

Surge protection for


Power Supply and Information Technology Systems 337
Combined adapters

Lightning Equipotential Bonding 343


Isolating spark gaps and components

Measuring and Test Devices 359

General information 367


Index 372

Valid from 1st April 2010


This catalogue replaces the Surge Protection Main Catalogue published in 2008. We reserve the right to introduce changes
in performance, dimensions and material in the course of technical progress. The figures shown are without obligation.
Misprints, errors and alterations excepted.
Reproduction in any form whatsoever is forbidden without our authorisation. Publication No. DS570/E/2010

1
...from a workshop to an
industrial enterprise 100th Anniversary of DEHN.
In our great-grandparents’ time
electricity was by no means a
matter of course. In the early
1910 1918
20th century sufficient illumina- Hans Dehn quite early deals with lightning pro-
tion used to be a luxury and a tection. His first patent in this field is granted
privilege of the upper class. in 1918.
Electricity was at best available
in large cities but rarely in rural
areas. The first long-distance
transmission of alternating cur-
rent took place in 1891.
At that time Oskar von Miller
succeeded in transporting elec-
trical energy for the first time On 21st January 1910 the electrician Hans Dehn
over a distance of 176 kilome- laid the foundation for today’s company when
tres from Lauffen / Neckar to registering an electrical installation business in
Frankfurt / Main via a high- Nuremberg.
voltage power line (20 kV). Since electric current had to be transported to the
This marked the breakthrough consumer, building installation and particularly
of the transmission of alternat- the construction of overhead lines were the main
ing current and was a signifi- fields of activity for DEHN electricians under the
cant step forward. But it was management of Hans Dehn.
still a long way to go before
the total population was effi-
ciently and reliably supplied
1923 Apart from overhead line
construction and building
with electricity. It was only in installation, the installation of lightning protec-
tion systems on buildings is an integral part of
the early 1920s that electricity
was made accessible to many 1921 our business activities. Hans Dehn also starts to
small towns for the first time. develop and manufacture lightning protection
During this eventful time, Hans and earthing components.
Dehn founded his electrical
installation company in Nurem-
berg on 21st January 1910.

Now, many years later, and yet


within a comparatively short
period of time, which was char-
acterised like no other by the
changeful history of Germany
and its people, success and set-
back, war, reconstruction and
economic crisis, DEHN celebrat-
ed its 100th anniversary on
21st January 2010. 1933
Starting as a small electrical
installation company, DEHN
became a globally operating
family-owned company.

The following pages show


some milestones in the com-
pany’s history of 100 years. The company grows year after year and Hans
Dehn’s sons Walter and Willy become partners.
After the first successful business years, a sub- From now on, the family-owned company oper-
sidiary is opened in Neumarkt i.d.Opf. located ates under the name of DEHN + SÖHNE. In
about 45 km southeast of Nuremberg to 1941 the youngest son Richard becomes a
advance electrification in Upper Palatinate. partner.
2
1939 – 1945 1952
In the post-war period, business
begins to pick up again:
DEHN + SÖHNE presents light-
ning protection and earthing
products at the Hanover trade
fair for the first time. The
increasing market demand
requires a further extension of
the production facilities in
Neumarkt.

The third product field besides


lightning and surge protection -
safety equipment - is launched.
The ball pin patented for DEHN
+ SÖHNE in 1953 significantly
influences the state of the art.

The Second World War inevitably slows down


business development. The premises in Nurem-
berg and Neumarkt are considerably damaged
during the war. Highly motivated, the family
starts reconstruction.
1953
DEHN seizes the opportunity to market its
The starting point for post-war activities in
products abroad: Austria becomes the first
Neumarkt was a warehouse built in the last
exporting country.
months of the war near Hans-Dehn-Straße
where our head office is located today.

1948

1954
The decision to build Due to our technical expert
a hot dip galvanising knowledge and entrepreneurial
plant in Neumarkt vision, we are the world’s first
paves the way for manufacturer to realise that
the extension of the external lightning protection
subsidiary to a pro- has to be combined with inter-
duction site. nal lightning protection.
The first generation of surge
protective devices is launched.
3
1956 1984
The KS connector is devel- The first lightning current carrying surge
oped to reliably connect arrester enters the market: VGA 280/4, also
circular conductors to flat known as DEHNventil. It globally becomes a
profiles. synonym for a new generation of surge
arresters. DEHN + SÖHNE captures a leading
position in the sector of surge protection.

1958
The pioneering innovation of the separable
earth rod considerably complements the range
of earthing components and is still in great
demand today.
1986
The success story of surge protection starts
DEHN + SÖHNE becomes well-known in the
with VM 280, the world’s first arrester with a
field of earthing technology.
modular width of 17.5 mm.

The universal MV clamp from our lightning


protection portfolio is launched.

1988
Foundation of DESITEK A/S in Denmark. It is
the first of today’s 10 sales companies in for-
eign countries.

1970 – 1980
The product range is continuously complement-
ed, especially in the field of surge protection.
New protective devices such as VA 280 and
BLITZDUCTOR are presented on the market.

1990 InELVATEC
Switzerland DEHN + SÖHNE participates in the
AG, which has been distributing DEHN
products on the Swiss market for several years.

4
1991 1996
Development and implementation of the master The new energy-coordinated Yellow/Line
plan DEHN 2000. arrester family for the protection of data tech-
A milestone in the company’s history: nology and automation systems, including the
DEHN+SÖHNE prepares for the future. key product BLITZDUCTOR CT, is another mile-
National and international success requires com- stone of our research and development.
prehensive restructuring, reorganisation and
reorientation.

The positive development in Spain requires new


distribution channels. DEHN IBERICA S.A. is found- 1992
ed in co-operation with our long-standing partner.

1993 1998
The new energy-coordinated Red/Line arrester family for low-voltage consumer‘s Foundation of DEHN & FILS in Strasbourg, later
installations is launched. renamed in DEHN FRANCE S.a.r.l.
Surge protective devices such as DEHNport and DEHNguard start their story of
success.
Red/Line becomes the general term for all protective devices for use in power
supply systems.

1999
In this year DEHN + SÖHNE is ready to make
the leap to America. DEHN Inc. is founded.

DEHN POLSKA Sp. z o.o. is founded in Warsaw


to serve the Polish market more efficiently.

In co-operation with our long-time partner on the Italian


market DEHN ITALIA S.p.A. is founded in Bozen.

2000
After almost 50 years on the Austrian market, a
subsidiary is founded, DEHN AUSTRIA GmbH.

1994
To intensify our activities in England DEHN (UK)
Ltd. is founded near Manchester.

5
2002 2004
The successful DEHNventil has a strong succes- 50 years of surge protection by
sor: The new DEHNventil. DEHN + SÖHNE.
It is a perfect all-in-one solution with complete In 1954 only few believed in the
devices for all system configurations success of surge protection.
(TN-C, TN-S, TT). Today surge protective devices
are an essential part of electrical
installations.

Moreover, the master plan is continued:


Move into new production facilities for surge
protective devices.

2005
DEHN Surge Protection
(Shanghai) Co.Ltd is founded in
Shanghai to service the Chinese
market, which has been worked
by an agent since 1992.

2003 2006
The HVI conductor is a milestone in external
lightning protection. Safe and functional arresters with a unique design. The new Red/Line and
The separation distance can be easily main- Yellow/Line product families are presented on international trade fairs in Hanover
tained even in case of challenging architectural and Frankfurt.
design by using the new, high-voltage-resistant
down conductor.

Completion of the new administration building


on Hans-Dehn-Straße.

In 2006 DEHN + SÖHNE was the first company


to obtain VdS certification for surge protective
devices.

6
2007 2009
Evolution of safety – DEHNguard
SCI is a surge protective device
for PV systems which combines
effective surge protection with
the protection of persons and
fire protection.
Completion of a new three-storey production
facility. It stands for a further big step forward
in the scope of the master plan and provides
the company with more space for production.

DEHN + SÖHNE BLITZDUCTOR XTU is the first


proves for the first arrester to automatically adjust its
time absence of nominal voltage. It does not have
ignition sparks a specified nominal voltage and
when lightning can thus be used for any voltage
current flows in the range from 0 to 180 V d.c.
through a pipe thanks to actiVsense technology.
clamp. The newly
developed pipe clamp for hazardous areas can
be installed in potentially explosive areas with
little effort.

2008
The new space-saving DEHNrecord MCM XT
condition monitoring system acts like an early 2010
warning system generating a fault message On 21st January 2010 DEHN + SÖHNE celebrates its 100th anniversary – a time
even in the event of imminent arrester over- for joy, pride and review.
load. During our history of 100 years, showing and pioneering new ways in the field of
Thus faults can be identified in advance and lightning protection has always been a major concern.
precise status messages support maintenance
staff in diagnosing these faults. We provide protection against lightning, surges and possible hazards of electricity –
a triumvirate of safety.

Lightning protection
Surge protection
Safety equipment

DEHN – your safety is our concern.

www.dehn.de

7
DEHN – Worldwide.

Algeria Netherlands
Argentina New Zealand
Australia Nicaragua
Austria Nigeria
Belgium Norway
Belize Oman
Bolivia Pakistan
Brazil Panama
Bulgaria Peru
Canada Poland
Cap Verde Portugal
Chile Romania
China Russia
Columbia Saudi Arabia
Costa Rica Serbia
Croatia Singapore
Cuba Slovakia
Czech Republic Slovenia
Denmark South Africa
El Salvador Spain
Estonia Sri Lanka
F.Y.R.O.M Sweden
Finland Switzerland
France Syria
Great Britain Taiwan
Greece Thailand
Guatemala Turkey
Honduras Uganda
Hungary United Arab Emirates
Iceland USA
India Venezuela
Iran
Ireland
We shall be pleased to name you
Israel
the right contact person of our
Italy
subsidiaries or representatives.
Japan
Latvia Please contact our Export
Lebanon Department under
Lithuania
Tel. +49 9181 906 462
Luxembourg
Fax +49 9181 906 444
Malaysia
Mauritius or send an e-mail to
Mexico export@dehn.de

8
9
DEHN – Safety according to Specification.
Lightning Protection Zones Concept
Failures of technical systems and installations are very unpleasant In case of a close or direct lightning strike, the surges (Fig. 3:
for the operators. These require faultless operation from the Case 1a) are caused by a voltage drop at the impulse earthing
equipment both under “normal“ conditions and in case of thun- resistance and the resulting potential rise of the structure towards
derstorms. Loss reports of insurance companies show clearly that the distant surroundings. This is the maximum load on electrical
there is a backlog demand both in the private (Fig. 1) and com- installations in structures.
mercial sector (Fig. 2). A comprehensive protection concept
would help to achieve this aim.
The characteristic parameters of flowing impulse currents (peak
The Lightning Protection Zones Concept enables designers, con-
value, rate of current rise, load, specific energy) can be described
structors and operators to plan, perform and control protection
measures. All relevant devices, installations and systems are thus with the impulse-current wave form 10/350 μs (Fig. 4) and are
reliably protected and furthermore with economically acceptable defined in international, European and national standards as test
efforts. currents for components and devices for protection against direct
lightning strokes.

Fire Theft In addition to the voltage drop at the impulse earthing resistance,
Water
5.6 %
4.6 % Vandalism surges arise in the electrical building installation and the systems
27.1 %
connected to it and equipment due to the induction effect of the
electromagnetic lightning field (Fig 3: Case 1b).
The power of these induced surges and the resulting impulse cur-
rents is considerably lower than the power of a direct lightning
impulse current and is therefore only described with the impulse
22.9 % current wave 8/20 μs (Fig. 4). Components and equipment, which
Negligence 15.3 % 0.8 % 23.7 % do not have to conduct currents from direct lightning strokes, are
Others Elemental Surges
(lightning discharges therefore tested with impulse currents of 8/20 μs.
switching operations)

Fig. 1: Causes of damage to electronic equipment, Protection philosophy


Analysis of 7370 damage claims Distant strokes are lightning strokes from a distance to the object
(Ref.: Württemberigsche Versicherung AG) to be protected, lightning strokes into the medium voltage over-
head line network or into its immediate surroundings or lightning
Others discharges from cloud to cloud (Fig. 3: Cases 2a, 2b and 2c).
41 %

In analogy to induced surges, the effects of distant lightning stro-


kes on the electrical system of a structure are controlled by devi-
ces and components, which are designed accordingly for impulse
current wave 8/20 μs.
Surges due to switching operations (SEMP) are caused by e.g.
14 % – switching off inductive loads
Unknown 45 %
Lightning/Surges (e.g. transformers, coils, motors),
– ignition and interruption of electric arcs
Fig. 2: Average damage causes during the last years
(e.g. arc welding device),
(Ref.: Gesamtverband der Deutschen Versicherungswirtschaft e.V.)
– tripping of fuses.

Sources of interference The effects of switching operations in electrical installations of


Surges arising due to thunderstorms are caused by direct or close structures can also be simulated with impulse currents of wave
lightning strokes or distant lightning strokes (Fig. 3). form 8/20 μs for testing purposes.
Direct or close lightning strokes are strokes into the lightning pro-
tection system of a structure, into its immediate surroundings or
into the conductive systems entering the structure (e.g. low-volta-
ge power supply, telecommunications lines and control lines...).
Due to their amplitudes and energy loads, the arising impulse cur-
rents and impulse voltages as well as the corresponding electro-
magnetic field (LEMP) represent a special risk for the system to
be protected.

10
To ensure continuous availability of complex power sup-
Direct/Close lightning strike:
Lightning strike into the external lightning ply and IT systems even in case of a direct lightning
1 protection system, process framework
(in industrial installations), cables etc. effect, further measures for surge protection of electrical
1a Voltage drop at the impulse earthing 2b
resistance Rst
1 2a and electronic installations are necessary based on a
1b Induced voltage in loops
20 kV building lightning protection system. Taking all causes of
L1
L2
L3 surges into consideration is very important. For this pur-
PEN
2c
pose, the Lightning Protection Zones Concept of IEC
Distant lightning strike 62305-4 is applied (Fig. 5).
Strike into medium volta-
1b
2a ge overhead lines A structure is subdivided in different risk zones. These
Surge travelling waves on
2b overhead lines due to
cloud-to-cloud lightning
zones help to define the necessary devices and compo-
1a
Rst
2c Fields of the lightning
channel
nents for lightning and surge protection.
IT system
low voltage power Part of an EMC-conform lightning protection zones con-
supply system
cept is an external lightning protection system (including
air-termination system, down-conductor system, earth-
Fig. 3: Causes of surges in case of lightning discharges
ing), equipotential bonding, spatial shielding and surge
protection for the power supply systems and IT systems.
(kA) 1 2 The lightning protection zones have to be defined
100 kA Wave form [μs] 10/350 8/20 according to Table 1.
imax [kA] 100 5
Q [As] 50 0.1
i 80 kA
W/R [J/Ω] 2.5 · 106 0.4 · 103 In correspondence with the requirements and loads on
Standard IEC 62305-1 EN 61000-4-5 surge protective devices with respect to their installation
60 kA
50 kA 1
sites, these are classified as lightning current arresters,
40 kA surge arresters and combined lightning current and
surge arresters.
20 kA The highest requirements for the discharge capacity are
2 made on lightning current and combined lightning cur-
200 μs 350 μs 600 μs 800 μs 1000 μs
rent and surge arresters used for the transition from
t (μs) Lightning Protection Zone 0A to 1 or 0A to 2.
Fig. 4: Test impulse current for Test impulse current for
1
lightning current arresters
2
surge arresters These SPDs must be able to conduct partial lightning
currents (wave form 10/350 μs) several times without
destruction in order to prevent the penetration of
air-termination system destructive partial lightning currents into the electrical
installation of a building.
At the boundary from LPZ 0B to 1 or downstream of the
spatial shield
lightning current arrester at the boundary from LPZ 1 to
ventilation terminal device 2 and higher, surge arresters are used for protection
against surges. Their function is to further reduce both
down-
conductor
system
the residual loads of the upstream protection levels and
limit the induced or own surges.

l.v. power
supply system The aforementioned lightning and surge protective
IT system
foundation earth electrode
measures at the boundaries of the lightning protection
steel reinforcement
zones apply to both power supply systems and IT sys-
Lightning equipotential bonding
Lightning current arrester (SPD Type 1)
Lightning equipotential bonding
Lightning current arrester
Lightning electro-
magnetic pulse
Lightning
protection zone tems to the same extent.
Local equipotential bonding Local equipotential bonding Switching electro-
Surge arrester (SPD Type 2, SPD Type 3) Surge arrester magnetic pulse All measures described in the EMC-conform Lightning
Fig. 5: EMC-based lightning protection zones concept Protection Zones Concept help to achieve a permanent
system availability of a modern infrastructure.
LEMP protection of structures with electrical and electronic systems
according to IEC 62305-4
Lightning Protection Zone Description
LPZ 0A Threat by direct lightning strokes, impulse currents up to complete lightning
currents and the entire lightning field.
LPZ 0B Protected against direct lightning strokes. Threat by impulse currents up to
partial lightning currents and the entire lightning field.
LPZ 1 Impulse currents are further limited by current distribution and SPDs situated
at the zone boundaries. The lightning field is mostly attenuated by spatial
shielding.
LPZ 2 Impulse currents are further limited by current distribution and SPDs situated
at the zone boundaries. The lightning field is mostly attenuated by spatial
shielding.

Table 1: Definition of lightning protection zones (LPZ)


11
DEHN – Technical Definitions.

Surge Protective Devices (SPD) Technical data of surge protective devices


Surge protective devices are items of equipment The technical data of surge protective devices
whose basic components are voltage-controlled comprise information defining the application
resistors (varistors, suppressor diodes) and/or conditions upon
spark gaps (discharge paths). The function of
– application
surge protective devices is to protect other elec-
trical equipment and installations against imper- (e.g. installation, mains conditions,
missibly high surges and/or to establish the temperature)
equipotential bonding. – performance in case of interference
Surge protective devices are classified (e.g. impulse current discharge capacity,
a) according to their application in follow current extinguishing capability,
– Surge protective devices for power sup- voltage protection level, response time)
ply systems and equipment – performance during operation
for nominal voltage ranges up to 1000 V (e.g. nominal current, attenuation,
• according to EN 61643-1:2001 as SPD Types insulation resistance)
1/2/3 – performance in case of failure
• according to IEC 61643-1:1998-02 as SPDs (e.g. backup fuse, disconnection device,
Class I / II / III fail-safe)
– Surge protective devices for IT systems
Categories according to IEC 61643-21: 2001
and equipment
(DIN VDE 0845 Part 3-1)
for protection of modern electronic systems in
telecommunications and signal-processing net- For testing the current carrying capability and
works with nominal voltages up to 1000 V a.c. voltage limitation under influences of impulses,
(root-mean-square value (rms)) and 1500 V a variety of impulse voltages and impulse cur-
d.c. against indirect and direct effects of light- rents is described in IEC 61643-21:2001 (DIN
ning strokes and other transients. VDE 0845 Part 3-1). They are sorted in Table 3
and provide preferred values. In table 2 of IEC
• according to IEC 61643-21:2000 + Corrigen- 61643-22 (DIN VDE 0845-3-2) the source of
dum:2001, EN 61643-21:2001 and DIN VDE transients is assigned to the different impulse
0845 Part 3-1. categories according to the coupling mechanism.
– Isolating spark gaps for earth-termina- Category C2 includes inductive couplings
tion systems or for equipotential bond- (surges), category D1 galvanic couplings (light-
ing ning currents). The relevant category is specified
in the technical data.
b) according to their impulse current dis-
charge capacity and their protective effect Cut-off frequency fG
in
defines the frequency-dependent performance
– Lightning current arresters / of an SPD. Cut-off frequencies are frequencies
Coordinated lightning current arresters causing an insertion loss (aE) of 3 dB under cer-
tain test conditions (see EN 61643-21:2001).
for interference due to direct or close light-
If no other value is indi-
ning strokes for protection of installations
cated, the frequency
and equipment (for use at the boundaries of
value refers to a 50 Ω
Lightning Protection Zones (LPZ) 0A and 1).
system.
– Surge arresters
for distant lightning strokes, switching over-
voltages as well as electrostatic discharges
for protection of installations, equipment and
terminal devices (for use at the boundaries
downstream of LPZ 0B).
– Combined lightning current and surge
arresters
for interference due to direct or close light-
ning strokes for protection of installations,
equipment and terminal devices (for use at
the boundaries between LPZ 0A and 1 as well
as 0A and 2).
12
DEHN + SÖHNE surge protective devices system availability, SPDs should therefore be
exceed the values indicated in the categories. subject to systematic tests. LifeCheck allows
The explicit value for the impulse current carry- for quick and easy SPD testing (refer also to
ing capability is therefore indicated by the page 177).
stated nominal discharge current (8/20 μs) and
lightning impulse current (10/350 μs). Lightning impulse current Iimp
is a standardised impulse current curve, with a
Combined impulse UOC wave form of 10/350 μs. Its parameters (peak
is generated by a hybrid generator (1.2/50 μs, value, charge, specific power) simulate the
8/20 μs) with a virtual impedance of 2 Ω. The loads of natural lightning currents.
open-circuit voltage of this generator is de- Lightning current and combined lightning
fined as UOC. UOC is especially indicated for current and surge arresters must be capable of
SPDs Type 3. discharging such lightning impulse currents
several times without consequential destruc-
Degree of protection tion of the equipment.
The degree of protection (IP) corresponds to
the subdivision into degrees of protection in Mains-side overcurrent protection /
accordance with DIN EN 60529 (VDE 0470 Backup fuse
Part 1). is an overcurrent protective device (e.g. fuse or
circuit breaker), which is installed outside of
Disconnecting time ta the surge arrester on the supply side to inter-
rupt the power-frequency follow currents, if
is the time passing until the automatic discon-
the breaking capacity of the surge protective
nection from power supply of the electrical device is exceeded.
circuit or equipment to be protected in case of
a failure. The disconnecting time is an applica- Max. continuous operating voltage UC
tion-specific value resulting from the intensity
is the root mean square (rms) value of the
of the fault current flowing and the character-
maximum voltage, which may be applied to
istics of the protective device. the correspondingly marked terminals of the
surge protective device during operation. It is
Disconnection capacity / Follow current the maximum voltage on the SPD in the
extinguishing capability Ifi defined non-conductive state, which ensures
The disconnection capacity is the uninterfered that this state is regained after response and
(prospective) rms value of the mains follow discharge.
current, which can automatically be extin- The value of UC shall be chosen in accordance
guished by the surge protective device at pres- with the nominal voltage of the system to be
ence of UC. It can be proven in the scope of an protected and the requirements of the installa-
operating duty test according to EN 61643-11. tion provisions (IEC 60364-5-534).

Frequency range Max. discharge current Imax


characterises the transmission band or let- is the maximum peak value of the impulse cur-
through frequency of an SPD according to rent (8/20 μs), which can be safely discharged
the described attenuation characteristics. by the device.

Insertion loss Max. transmission capacity


With an indicated frequency, the insertion loss defines the maximum RF capacity which can
of a surge protective device is defined by the be transmitted via a coaxial surge protective
relation of the voltage value at the installation device without interfering with the protective
site before and after installing the SPD. component.
If no other value is indicated, the value refers
to a 50 Ω system. Nominal discharge current In
is the peak value of an impulse current (wave
LifeCheck® form 8/20 μs), which the surge protective
device is rated for according to a certain test
Repeated discharges with values beyond the programme.
specifications of the device may overload SPDs
used in IT systems. In order to ensure a high

13
Nominal load current (nominal current) IL Shield attenuation
is the highest permissible operating current, Relation of the power fed into a coaxial cable to
which may be permanently conducted via the the power radiated through the cable from the
correspondingly marked terminals. phase conductor.

Nominal voltage UN Short-circuit withstand capability


corresponds to the nominal voltage of the sys- is the value of the prospective power-frequency
tem to be protected. The nominal voltage is short-circuit current controlled by the surge pro-
often indicated for surge protective devices used tective device if it is supplied with an upstream
in IT installations for type designation purposes. backup fuse.
For a.c. voltages it is indicated as rms value.
SPD class (Yellow / Line)
N-PE surge arresters All DEHN surge arresters for use in IT systems
are surge protective devices exclusively designed are assigned a Yellow/Line SPD Class and are
for installation between the N and PE conductor. marked correspondingly with a symbol in the
technical data sheet and on the rating plate
Operating temperature range TU (refer also to page 151).
indicates the range in which the devices can be
used. For devices without self-heating, it is equal Thermal disconnector
to the ambient temperature range. The tempera- Surge protective devices for use in power supply
ture rise of devices with self-heating must not systems, which are supplied with voltage-con-
exceed the maximum value indicated. trolled resistors (varistors), mostly have an inte-
grated disconnection device, which isolates the
surge protective device from mains in case of
Protective circuit overloads and indicates this operating state.
Protective circuits are multi-stage, cascaded pro- The disconnector reacts to the “joule heat“
tective devices. The individual protection stages generated by an overloaded varistor and discon-
can consist of discharge paths, varistors, semi- nects the surge protective device from mains, if
conductor elements. The energy coordination of a certain temperature is exceeded.
the individual protection stages is performed The disconnection device is designed to discon-
with decoupling elements. nect the overloaded surge protective device in
time to avoid a fire hazard. It is not designed to
Protective conductor current IPE ensure the protective measure of “protection
is the current flowing through the PE connection against indirect contact“.
when the surge protective device is connected to The function of these thermal disconnectors can
the maximum continuous operating voltage UC, be tested by simulated overloads/ageing of the
corresponding to the installation instructions SPD.
and without load-side consumers.
Voltage protection level Up
The voltage protection level of a surge protective
Response time tA
device is the maximum instantaneous value of
Response times generally characterise the the voltage on the terminals of a surge protec-
response performance of the individual protec- tive device, determined from the standardised
tion elements used in surge protective devices individual tests for
(refer also to page 371).
– Lightning impulse sparkover voltage
Depending on the steepness du/dt of the im-
1.2/50 μs (100%)
pulse voltage or di/dt of the impulse current, the
response times can change within certain limits. – Response voltage for a steepness of 1 kV/μs
– Residual voltage for nominal discharge
Return loss
current Ures
indicates for high-frequency applications, how
The voltage protection level characterises the
many rates of the “forward“ wave are reflected
capability of a surge protective device to limit
at the protective device (“transition point“).
surges to a residual level. If used in power sup-
It is a direct measure for rating the adjustment
ply systems, the voltage protection level defines
of the protective device to the surge impedance
the location of use by the overvoltage category
of the system.
according to DIN VDE 0110-1:2003-11 (DIN EN
60664-1, IEC 60664-1). For surge protective
Series impedance devices designed for protection of IT systems,
is the impedance in the direction of the signal the voltage protection level has to be adapted
flow between input and output of the SPD. to the immunity of the equipment to be protect-
ed (IEC 61000-4-5: 2001-12).
14
Surge protection for
POWER SUPPLY SYSTEMS
SPDs for low-voltage installations and equipment

www.dehn.de 15
16 www.dehn.de
Combined SPDs – Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS CONTENTS

Easy choice 18

Combined SPDs – Type 1 Combined SPDs – 31


Type 1

Lightning Current Arresters – Type 1 Lightning Current


45
Arresters – Type 1

N-PE Lightning Current Arresters – Type 1 N-PE Lightning Current 63


Arresters – Type 1

Surge Arresters – Type 2 Surge Arresters –


69
Type 2

Surge Arresters – Type 3 Surge Arresters –


119
Type 3

Accessories 145
Accessories

Measuring and Test Devices 365

www.dehn.de 17
Combined SPDs – Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

Easy Choice POWER SUPPLY SYSTEMS

Arrangement I Arrangement II Arrangement III


L1 L2 L3 N PE
SPD Type 3 SPD Type 3 SPD Type 3
(Surge arrester) (Surge arrester) (Surge arrester)

Socket Outlet
S-Schutz

DEHNflex

Cable leng 1 x DSA 230 LA Part No. 924 370 1 x DFL M 255 Part No. 924 396 1 x STC 230 Part No. 924 350
th ≥ 5 m
for cable ducts for flush-mounted systems for existing socket outlets

16 A

125 A 1 125 A 1

Subdistribution Board
L1 L2 L3 N L1 L2 L3 N

indication of interference
DEHNguard

DEHNguard

DEHNguard

DEHNguard

DEHNguard

DEHNguard

DEHNguard

DEHNguard
DG MOD 275

DG MOD 275

DG MOD 275

DG MOD 275

DG MOD 275

DG MOD 275

DG MOD 275

DG MOD 275

9 PE 9 PE

with remote signalling contact:


1 x DG M TNS 275 Part No. 952 400 1 x DG M TNS 275 FM Part No. 952 405

SPD Type 2 SPD Type 2


(Surge arrester) (Surge arrester)

DEHNbloc® M DEHNventil®
Coordinated to DEHNguard® Directly coordinated to
Cable length ≥ 15 m without additional cable length. Red/Line SPDs Type 2 and 3
without additional cable length.

For serial connection please see also page 21

SPD Type 1 SPD Type 1


SPD Type 1 (Coordinated lightning (Combined lightning current
(Lightning current arrester) current arrester) and surge arrester)
Main Distribution Board

315 A 1 315 A 1 315 A 1

L/N L/N L/N L1 L1‘ L2 L2‘ L3 L3‘


indication of interference

L1 L1’ L2 L2’ L3 L3’

DEHNbloc DB 3 255 H
DB M 1 255 FM

DB M 1 255 FM

DB M 1 255 FM

DEHNventil

DEHNventil

DEHNventil
DV MOD 255

DV MOD 255

DV MOD 255
DEHNbloc

DEHNbloc

DEHNbloc

N‘/PEN N/PEN

N/PE(N) N/PE(N) N/PE(N) 9 PEN

1 x DB 3 255 H Part No. 900 120 3 x DB M 1 255 FM Part No. 961 125 1 x DV M TNC 255 Part No. 951 300
1 x MVS 1 6 Part No. 900 815 alt. 1 x DV M TNC 255 FM Part No. 951 305
also available as
EBB alt. 3 x DB 1 255 H Part No. 900 222 alt. 3 x DB M 1 255 Part No. 961 120 1 x DV M TNS 255 Part No. 951 400
1 x MVS 1 6 Part No. 900 815 1 x MVS 1 6 Part No. 900 815 alt. 1 x DV M TNS 255 FM Part No. 951 405

1) Only required, if a fuse of the same or a lower nominal value is not already provided in the upstream power supply.

L1 L2 L3 PEN

TN systems: Office Building – Separation of the PEN in the main distribution board

18 www.dehn.de
Combined SPDs – Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS Easy Choice

Arrangement I Arrangement II Arrangement III


L1 L2 L3 N PE
SPD Type 3 SPD Type 3 SPD Type 3
(Surge arrester) (Surge arrester) (Surge arrester)

Socket Outlet
Überspannungsschutz

PROTECTOR

0
1
SFL-Protector

1 x NSM PRO EW Part No. 924 342 1 x DPRO 230 F Part No. 909 240 1 x SFL PRO Part No. 912 260
Cable leng 1 x DPRO 230 Part No. 909 230
th ≥ 5 m

16 A

125 A 1 125 A 1

Subdistribution Board
L1 L2 L3 L1 L2 L3

indication of interference
DEHNguard

DEHNguard

DEHNguard

DEHNguard

DEHNguard

DEHNguard
DG MOD 275

DG MOD 275

DG MOD 275

DG MOD 275

DG MOD 275

DG MOD 275
9 PEN 9 PEN

with remote signalling contact:


1 x DG M TNC 275 Part No. 952 300 1 x DG M TNC 275 FM Part No. 952 305

SPD Type 2 SPD Type 2


(Surge arrester) (Surge arrester)

DEHNbloc® M DEHNventil®
Coordinated to DEHNguard® Directly coordinated to
Cable length ≥ 15 m without additional cable length. Red/Line SPDs Type 2 and 3
without additional cable length.

For serial connection please see also page 21

SPD Type 1 SPD Type 1


SPD Type 1 (Coordinated lightning (Combined lightning current
(Lightning current arrester) current arrester) and surge arrester) Main Distribution Board
315 A 1 315 A 1 315 A 1

L/N L/N L/N L1 L1‘ L2 L2‘ L3 L3‘


indication of interference

L1 L1’ L2 L2’ L3 L3’

DEHNbloc DB 3 255 H
DEHNventil

DEHNventil

DEHNventil
DB M 1 255 FM

DB M 1 255 FM

DB M 1 255 FM

DV MOD 255

DV MOD 255

DV MOD 255
DEHNbloc

DEHNbloc

DEHNbloc

N‘/PEN N/PEN

N/PE(N) N/PE(N) N/PE(N) 9 PEN

1 x DB 3 255 H Part No. 900 120 3 x DB M 1 255 FM Part No. 961 125 1 x DV M TNC 255 Part No. 951 300
1 x MVS 1 6 Part No. 900 815
EBB alt. 3 x DB 1 255 H Part No. 900 222 alt. 3 x DB M 1 255 Part No. 961 120 alt. 1 x DV M TNC 255 FM Part No. 951 305
1 x MVS 1 6 Part No. 900 815 1 x MVS 1 6 Part No. 900 815

1) Only required, if a fuse of the same or a lower nominal value is not already provided in the upstream power supply.

L1 L2 L3 PEN

TN systems: Example: Office Building – Separation of the PEN in the subdistribution board

www.dehn.de 19
Combined SPDs – Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

Easy Choice POWER SUPPLY SYSTEMS

Arrangement I Arrangement II Arrangement III


L1 L2 L3 N PE
SPD Type 3 25 A also
SPD Type 3 SPD Type 3
(Surge arrester) permissible
without NF 10
(Surge arrester) 25 A 1 (Surge arrester)
3A 1 10 A 1

Switchgear / Machine
3 9 4

L1 L2 L3 N 9
L L 9 9 N N
IN

99 / IN function

indication of interference
DR M 2P 255 FM

DEHNrail
DEHN SPD NETZFILTER
SPS PRO electronic
SPS SPS equipment

DR M 4P 255 FM
DEHNrail
OUT / FM OUT
L’ L’ 9 9 N’ N’

1 9 2

L1 L2 L3 N 9

Cable leng 1 x SPS PRO Part No. 912 253 1 x DR M 2P 255 FM Part No. 953 205 1 x DR M 4P 255 FM Part No. 953 405
th ≥ 5 m 1 x NF 10 Part No. 912 254 alt. 1 x DR M 4P 255 Part No. 953 400

32 A
125 A 1

Subdistribution Board
L1 L2 L3

V NH V NH V NH
V NH00 280 V NH00 280 V NH00 280
DEHNguard

DEHNguard

DEHNguard
2
DG MOD 275

DG MOD 275

DG MOD 275

9 PEN

3 x V NH00 280 Part No. 900 261 1 x DG M TNC 275 Part No. 952 300
or with remote signalling contact:
1 x DG M TNC 275 FM Part No. 952 305

SPD Type 2 SPD Type 2


(Surge arrester) (Surge arrester)

DEHNbloc® M DEHNventil®
Coordinated to DEHNguard® Directly coordinated to
without additional cable length. Red/Line SPDs Type 2 and 3
without additional cable length.

For serial connection please see also page 21

SPD Type 1 SPD Type 1 SPD Type 1


(Coordinated lightning (Coordinated lightning (Combined lightning current
current arrester) current arrester) and surge arrester)
Main Distribution Board

315 A 1 315 A 1 315 A 1

L/N L/N L/N L1 L1‘ L2 L2‘ L3 L3‘


indication of interference

indication of interference

DEHNbloc Maxi DEHNbloc Maxi DEHNbloc Maxi


DBM NH00 255 DBM NH00 255 DBM NH00 255
DEHNventil

DEHNventil

DEHNventil
DB M 1 255 FM

DB M 1 255 FM

DB M 1 255 FM

DV MOD 255

DV MOD 255

DV MOD 255
DEHNbloc

DEHNbloc

DEHNbloc

N/PE(N) N/PE(N) N/PE(N) 9 PEN

3 x DBM NH00 255 Part No. 900 255 3 x DB M 1 255 FM Part No. 961 125 1 x DV M TNC 255 FM Part No. 951 305
1 x MVS 1 6 Part No. 900 815
EBB alt. 3 x DB M 1 255 Part No. 961 120 alt. 1 x DV M TNC 255 Part No. 951 300
1 x MVS 1 6 Part No. 900 815

1) Only required, if a fuse of the same or a lower nominal value is not already provided in the upstream power supply.
2) Without separate backup fuse in case of earth-fault- and short-circuit-proof installation.
L1 L2 L3 PEN

TN systems: Example: Industry – Separation of the PEN in the subdistribution board

20 www.dehn.de
Combined SPDs – Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS Easy Choice

L1 L2 L3 N PE
SPD Type 3 SPD Type 3
(Surge arrester) (Surge arrester)

Heating Control
1 9 2

Socket Outlet
heating

DR M 2P 255 FM
DEHNrail

PROTECTOR
Cable leng
th ≥ 5 m
1 x DPRO 230 Part No. 909 230
1 x DPRO 230 F Part No. 909 240
1 x DR M 2P 255 Part No. 953 200 1 x SFL PRO Part No. 912 260

16 A

Subdistribution Board
KW h

Central Main and


SPD Type 1 Note:
PEN
(Combined lightning current As an alternative, surge arresters can also be
used downstream of meter panels
L1 DEHNventil ZP
DV ZP TNC 255
and surge arrester) (e.g. DG M TNC 275 Part No. 952 300),
if no
L2
– lightning protection system,
L3 1 x DV ZP TNC 255 Part No. 900 390 – electrical power supply by the service entry mast,
– antenna of the roof
9 PEN also available for 5-wire systems is available.
1 x DV ZP TT 255 Part No. 900 391

315 A EBB

L1 L2 L3 PEN

TN systems: Example: Single-family house

L1 L2 L3 N PE
SPD Type 3 SPD Type 3
(Surge arrester) (Surge arrester)
Heating Control

1 9 2

Socket Outlet
heating
DR M 2P 255 FM
DEHNrail

DEHNflex

Cable leng
th ≥ 5 m

1 x DR M 2P 255 Part No. 953 200 1 x DFL M 255 Part No. 924 396

16 A
RCD
Subdistribution Board

SPD Type 1 Note:


Central Main and

(Combined lightning current As an alternative, surge arresters can also be


used downstream of meter panels
L1 L2 L3 N
and surge arrester) (e.g. DG M TT 275 Part No. 952 310),
if no
– lightning protection system,
– electrical power supply by the service entry mast,
DEHNventil
DEHNventil

DEHNventil

DEHNventil

– antenna of the roof


DV MOD NPE
DV MOD 255

DV MOD 255

DV MOD 255

50

is available.

9 PE
1 x DV M TT 255 Part No. 951 310
25 A

EBB

L1 L2 L3 N

TT system: Example: Single-family house

www.dehn.de 21
Combined SPDs – Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

Easy Choice POWER SUPPLY SYSTEMS

Arrangement I Arrangement II Arrangement III


L1 L2 L3 N PE
SPD Type 3 SPD Type 3 SPD Type 3
(Surge arrester) (Surge arrester) (Surge arrester)

Socket Outlet
S-Schutz

DEHNflex

Cable leng
th ≥ 5 m
1 x DSA 230 LA Part No. 924 370 1 x DFL M 255 Part No. 924 396 1 x STC 230 Part No. 924 350
for cable ducts for flush-mounted systems for existing socket outlets

16 A
RCD

125 A 1 125 A 1

Subdistribution Board
L1 L2 L3 N L1 L2 L3 N

indication of interference
DEHNguard
DEHNguard

DEHNguard

DEHNguard
DEHNguard
DEHNguard

DEHNguard

DEHNguard

DG MOD NPE
DG MOD NPE

DG MOD 275

DG MOD 275

DG MOD 275
DG MOD 275

DG MOD 275

DG MOD 275

9 PE 9 PE

with remote signalling contact:


1 x DG M TT 275 Part No. 952 310 1 x DG M TT 275 FM Part No. 952 315

SPD Type 2 SPD Type 2


(Surge arrester) (Surge arrester)

DEHNbloc® M
DEHNventil®
Coordinated to DEHNguard®
Directly coordinated to
Cable length ≥ 15 m without additional cable length.
Red/Line SPDs Type 2 and 3
without additional cable length.

For serial connection please see also page 21

SPD Type 1 SPD Type 1


SPD Type 1 (Coordinated lightning (Combined lightning current
Main Distribution Board

(Lightning current arrester) current arrester) and surge arrester)


315 A 1 315 A 1 315 A 1

L/N L/N L/N PE 9 L1 L1‘ L2 L2‘ L3 L3‘ N N‘

L1 L1’ L2 L2’ L3 L3’

DEHNgap B/n
DEHNbloc DB 3 255 H DGP BN 255
Feed-Through

DV MOD NPE 50
DEHNventil

DEHNventil

DEHNventil

DEHNventil
DV MOD 255

DV MOD 255

DV MOD 255
DEHNbloc

DEHNbloc

DEHNbloc

DEHNgap
DB M 1 255

DB M 1 255

DB M 1 255

DGP M 255
Terminal
DK25

N‘/PEN N/PEN

N/PE(N) N/PE(N) N/PE(N) N 9 PE

1x DB 3 255 H Part No. 900 120 indication of interference


alt. 3 x DB 1 255 H Part No. 900 222
1x DGP BN 255 Part No. 900 132 3 x DB M 1 255 Part No. 961 120 1 x DV M TT 255 FM Part No. 951 315
EBB 1x DK 25 Part No. 952 699 1 x DGP M 255 Part No. 961 101
1x MVS 1 2 Part No. 900 617 1 x MVS 1 8 Part No. 900 611 alt. 1 x DV M TT 255 Part No. 951 310

1) Only required, if a fuse of the same or a lower nominal value is not already provided in the upstream power supply.

L1 L2 L3 N

TT systems: Example: Office Building

22 www.dehn.de
Combined SPDs – Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS Easy Choice

Arrangement I Arrangement II Arrangement III


L1 L2 L3 N PE
SPD Type 3 25 A also SPD Type 3 SPD Type 3
permissible
(Surge arrester) without NF 10 (Surge arrester) 25 A 1 (Surge arrester)
3A 1 10 A 1

Switchgear / Machine
3 9 4

L1 L2 L3 N 9
L L 9 9 N N
IN

99 / IN function

indication of interference
DEHNrail
DR M 2P 255 FM
DEHN SPD NETZFILTER
SPS PRO

SPS SPS electronic

DR M 4P 255 FM
equipment

DEHNrail
OUT / FM OUT
L’ L’ 9 9 N’ N’

1 9 2

L1 L2 L3 N 9

Cable leng
th ≥ 5 m
1 x SPS PRO Part No. 912 253 1 x DR M 2P 255 FM Part No. 953 205 1 x DR M 4P 255 FM Part No. 953 405
1 x NF 10 Part No. 912 254 alt. 1 x DR M 4P 255 Part No. 953 400
32 A
RCD

125 A 1 125 A 1

Subdistribution Board
L1 L2 L3 N L1 L2 L3 N

indication of interference
DEHNguard

DEHNguard
DEHNguard

DEHNguard

DEHNguard

DEHNguard

DEHNguard

DEHNguard
DG MOD NPE

DG MOD NPE
DG MOD 275

DG MOD 275

DG MOD 275

DG MOD 275

DG MOD 275

DG MOD 275

9 PE 9 PE

with remote signalling contact:


1 x DG M TT 275 Part No. 952 310 1 x DG M TT 275 FM Part No. 952 315

SPD Type 2 SPD Type 2


(Surge arrester) (Surge arrester)

DEHNbloc® M DEHNventil®
Coordinated to DEHNguard® Directly coordinated to
Cable length ≥ 15 m without additional cable length. Red/Line SPDs Type 2 and 3
without additional cable length.

For serial connection please see also page 21

SPD Type 1 SPD Type 1


SPD Type 1 (Coordinated lightning (Combined lightning current
(Lightning current arrester) current arrester) and surge arrester) Main Distribution Board
315 A 1 315 A 1 315 A 1

L/N L/N L/N PE 9 L1 L1‘ L2 L2‘ L3 L3‘ N N‘


indication of interference

DEHNbloc NH DEHNbloc NH DEHNbloc NH DEHNgap B NH


DB NH00 255 H DB NH00 255 H DB NH00 255 H DGP B NH00 N 255
DV MOD NPE 50
DB M 1 255 FM

DB M 1 255 FM

DB M 1 255 FM

DEHNventil
DGP M 255 FM

DEHNventil

DEHNventil

DEHNventil
DV MOD 255

DV MOD 255

DV MOD 255
DEHNbloc

DEHNbloc

DEHNbloc

DEHNgap

N/PE(N) N/PE(N) N/PE(N) N 9 PE

indication of interference
3 x DB NH00 255 H Part No. 900 273 3 x DB M 1 255 FM Part No. 961 125 1 x DV M TT 255 FM Part No. 951 315
EBB 1 x DGP B NH00 N 255 Part No. 900 269 1 x DGP M 255 FM Part No. 961 105
1 x MVS 1 8 Part No. 900 611 alt. 1 x DV M TT 255 Part No. 951 310

1) Only required, if a fuse of the same or a lower nominal value is not already provided in the upstream power supply.

L1 L2 L3 N

TT systems: Example: Industry

www.dehn.de 23
Combined SPDs – Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

Easy Choice POWER SUPPLY SYSTEMS

L1 L2 L3 PEN L1 L2 L3 PE
SPD Type 2 SPD Type 2

indication of interference
(Surge arrester) (Surge arrester)
125 A 100 A aM

indication of interference
DEHNguard DEHNguard DEHNguard
DG 1000 FM DG 1000 FM DG 1000 FM
DEHNguard

DEHNguard

DEHNguard
DG S 440 FM

DG S 440 FM

DG S 440 FM

3 x DG S 440 FM Part No. 952 095 3 x DG 1000 FM Part No. 950 112
1 x MVS 1 3 Part No. 900 615 1 x EB DG 1000 1 3 Part No. 900 411

SPD Type 1 SPD Type 1


(Coordinated lightning (Coordinated lightning
current arrester) current arrester)
250 A 250 A

L L L L L L
DBM 1 440 FM

DBM 1 440 FM

DBM 1 760 FM

DBM 1 760 FM

DBM 1 760 FM
440 FM
DEHNbloc

DEHNbloc

DEHNbloc

DEHNbloc

DEHNbloc
DEHNbloc

DBM 1 760
Maxi

Maxi

Maxi

Maxi

Maxi
Maxi

indication of interference

indication of interference
N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN

3 x DBM 1 440 FM Part No. 961 145 3 x DBM 1 760 FM Part No. 961 175
1 x EB DG 1000 1 3 Part No. 900 411 1 x EB DG 1000 1 3 Part No. 900 411
EBB EBB

alt. 3 x DBM 1 440 Part No. 961 140


1 x EB DG 1000 1 3 Part No. 900 411

L1 L2 L3 PEN L1 L2 L3 PE

TN systems: Industry TN-C 400/690 V IT systems: Industry IT 690 V, without integrated neutral conductor

24 www.dehn.de
Combined SPDs – Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS Easy Choice

L1 L2 L3 N PE L1 L2 L3 N PE
SPD Type 3 SPD Type 3
(Surge arrester) (Surge arrester)

Socket Outlet

Socket Outlet
Cable leng
DEHNflex th ≥ 5 m DEHNflex
Cable leng
th ≥ 5 m

1 x DFL M 255 Part No. 924 396 16 A 1 x DFL M 255 Part No. 924 396
for flush-mounted systems RCD for flush-mounted systems
16 A

Subdistribution Board

Subdistribution Board
L1 L2 L3 N

L1 L2 L3 N
indication of interference

indication of interference
DEHNguard

DEHNguard

DEHNguard

DEHNguard

DG MOD 275
DG MOD CI

DG MOD CI

DG MOD CI

DEHNguard
DEHNguard

DEHNguard

DEHNguard
275

275

275

DG MOD NPE
DG MOD CI

DG MOD CI

DG MOD CI
275

275

275
9 PE

9 PE

with remote signalling contact: with remote signalling contact:


1 x DG M TNS CI 275 FM Part No. 952 406 1 x DG M TT CI 275 FM Part No. 952 327

SPD Type 2 SPD Type 2


(Surge arrester) (Surge arrester)

DEHNbloc® M DEHNbloc® M
Coordinated to DEHNguard® Coordinated to DEHNguard®
without additional cable length. without additional cable length.

SPD Type 1 SPD Type 1


(Coordinated lightning (Coordinated lightning
Main Distribution Board

Main Distribution Board


current arrester) current arrester)
315 A 1
315 A 1

L/N L/N L/N


L/N L/N L/N PE 9
indication of interference
DB M 1 255 FM

DB M 1 255 FM

DB M 1 255 FM
DEHNbloc

DEHNbloc

DEHNbloc

DEHNbloc

DEHNbloc

DEHNbloc

DEHNgap
DB M 1 255

DB M 1 255

DB M 1 255

DGP M 255

N/PE(N) N/PE(N) N/PE(N)


N/PE(N) N/PE(N) N/PE(N) N

3 x DB M 1 255 FM Part No. 961 125


1 x MVS 1 6 Part No. 900 815
3 x DB M 1 255 Part No. 961 120
EBB alt. 3 x DB M 1 255 Part No. 961 120 EBB 1 x DGP M 255 Part No. 961 101
1 x MVS 1 6 Part No. 900 815 1 x MVS 1 8 Part No. 900 611

1) Only required, if a fuse of the same or a 1) Only required, if a fuse of the same or a
L1 L2 L3 PEN lower nominal value is not already L1 L2 L3 N lower nominal value is not already
IK ≤ 25 kA provided in the upstream power supply. IK ≤ 25 kA provided in the upstream power supply.

TN systems TT systems

www.dehn.de 25
Combined SPDs – Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

Easy Choice of SPDs for Use in Photovoltaic Systems

d.c. arresters
1 Modular surge arrester as complete unit for use in
max. PV voltage unearthed / functionally earthed
photovoltaic systems
up to 600 V d.c. Part No. 952 511 (952 516)
DG M YPV SCI 600 Part No. 952 511
DG M YPV SCI 600 FM Part No. 952 516 up to 1000 V d.c. Part No. 952 510 (952 515)
DG M YPV SCI 1000 Part No. 952 510 up to 1200 V d.c. Part No. 952 512 (952 517)
DG M YPV SCI 1000 FM Part No. 952 515
DG M YPV SCI 1200 Part No. 952 512
DG M YPV SCI 1200 FM Part No. 952 517

5 Type 1 combined lightning current


and surge arrester for use in photo-
voltaic systems
DLM PV 1000 Part No. 900 330

a.c. arresters
2 Modular surge arrester for use in single-phase 2 Modular surge arrester for use in single-phase
230 V TN power supply systems 230 V TT power supply systems
DG M TN 275 Part No. 952 200 DG M TT 2P 275 Part No. 952 110
DG M TN 275 FM Part No. 952 205 DG M TT 2P 275 FM Part No. 952 115

3 Multipole combined lightning current and surge


arrester for use in three-phase power supply sys-
tems
DV M TNC 255 Part No. 951 300
DV M TNC 255 FM Part No. 951 305
DV M TNS 255 Part No. 951 400
DV M TNS 255 FM Part No. 951 405
DV M TT 255 Part No. 951 310
DV M TT 255 FM Part No. 951 315

4 Modular combined lightning current and surge 4 Modular combined lightning current and surge
arrester for use in single-phase TN power supply arrester for use in single-phase TT and TN-S power
systems supply systems
DV M TN 255 Part No. 951 200 DV M TT 2P 255 Part No. 951 110
DV M TN 255 FM Part No. 951 205 DV M TT 2P 255 FM Part No. 951 115

6 Modular multipole surge arrester for use in three-


phase power supply systems
DG M TNC 275 Part No. 952 300
DG M TNC 275 FM Part No. 952 305
DG M TNS 275 Part No. 952 400
DG M TNS 275 FM Part No. 952 405
DG M TT 275 Part No. 952 310
DG M TT 275 FM Part No. 952 315

26 www.dehn.de
Combined SPDs – Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

Easy Choice of SPDs for Use in Photovoltaic Systems

PV system on a building with external lightning protection system.

a) if the separation distance s is observed b) if the separation distance s is not observed

<s
separation s separation <s
distance OK distance

s
not OK
<s
≥s 6 2
~
1 3 4
~
5
a.c. d.c. input a.c. d.c. input
= output =
output

3 3
meter/ kWh kWh meter/ kWh kWh
distribution board distribution board

power supply power supply


SEB SEB

PV system on a building without external lightning protection system.

c)

6 2 1
~
a.c. = d.c. input
output

6
meter/ kWh kWh
distribution board

power supply
SEB

Equipotential bonding
For lightning and surge protection reasons, it is strongly recommended to
connect the PV frame as follows to the equipotential bonding system:
• Defined connection with at least 16 mm2 copper at the PV frame (b).
• Defined connection with at least 6 mm2 copper at the PV frame
(a + c).
• Electrically conductive connection of the PV frames has to be ensured.
• The earth conductor is connected to the main earthing busbar of the
building on ground level.
• The earth conductor has to be installed in parallel and in close proxi-
mity to the d.c. and a.c. cables / lines and accessory.

www.dehn.de 27
Combined SPDs – Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

Power Supply Systems Worldwide POWER SUPPLY SYSTEMS

International system configurations* according to IEC 60364-1 (DIN VDE 0100-100)

L1 TN-C system TN-S system


L1
L2
L2
L3
L3
PEN PE
N

RB
RB

TN-C system 230 / 400 V TN-C-S system 230 / 400 V

L1 L1 L1
L2 L2 L2
L3 L3 L3
N N
PE
PE PE

RB RB RA RA

TN-S system 230 / 400 V TT system 230 / 400 V IT system 230 V, 400 V, 500 V, 690 V

Further system configurations* used worldwide

L L1 L1 L1 L1

N N L2
N
G L2 L2 L3
L2 L3 L3 N
G G G G

single-phase; 3 conductors single-phase; 4 conductors 3-phase; 4 conductors 3-phase; 5 conductors 3-phase; 5 conductors
Split Phase or Edison Delta ”Highleg“
(1 Ph, 2 W + G) (1 Ph, 3 W + G) (3 Ph Y, 3 W + G) (3 Ph Y, 4 W + G) (3 Ph Δ, 4 W + G)
110 V 120 V / 240 V 480 V 120 V / 208 V 120 V / 240 V
120 V 277 V / 480 V
220 V
240 V

L1 L1

L2 L2 R R
L3 L3 200 V 100 V
G G T N

3-phase; 4 conductors 3-phase; 4 conductors single-phase; 2 conductors single-phase; 2 conductors


Delta ”Ungrounded“ Delta ”Grounded Corner“
(3 Ph Δ, 3 W + G) (3 Ph Δ, 3 W + G) (1 Ph, 2 W) (1 Ph, 2 W)
240 V 240 V 200 V 100 V
480 V 480 V

R R R
200 V 100 V 200 V
200 V 200 V S
N
T 200 V 200 V 100 V
100 V N
200 V 100 V
T S T

single-phase; 3 conductors 3-phase; 3 conductors 3-phase; single-phase;


+
(1 Ph, 3 W) (3 Ph, 3 W) 3 conductors 3 conductors
100 V / 200 V 200 V 100 V / 200 V; 200 V

* System according to earth connection (according to DIN VDE 0100-100)

28 www.dehn.de
Combined SPDs – Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS Cross-reference


Discontinued Products Alternatives Discontinued Products Alternatives
Part No. Type Part No. Type Part No. Type Part No. Type

Combined SPDs – Type 1 900 625 DG 320 FM 952 093 DG S 320 FM


900 370 DV 2P TT 255 951 110 DV M TT 2P 255 or 900 627 DG 440 FM 952 095 DG S 440 FM
951 115 DV M TT 2P 255 FM 900 641 DG T 385 952 074 DG S 385
900 371 DV 2P TN 255 951 200 DV M TN 255 or 900 650 DG T 275 952 070 DG S 275
951 205 DV M TN 255 FM
900 651 DG T 600 952 076 DG S 600
900 373 DV TNC 255 951 300 DV M TNC 255 or
900 652 DG T 320 952 073 DG S 320
951 305 DV M TNC 255 FM
900 653 DG T 150 952 072 DG S 150
900 374 DV TNS 255 951 400 DV M TNS 255 or
951 405 DV M TNS 255 FM 900 654 DG T 75 952 071 DG S 75
900 375 DV TT 255 951 310 DV M TT 255 or 900 655 DG T 440 952 075 DG S 440
951 315 DV M TT 255 FM 900 659 DG T 275 VA 952 082 DG S 275 VA
Coordinated Lightning Current Arresters – Type 1 900 667 DG T 75 VA 952 080 DG S 75 VA
900 015 DBM 1 135 961 110 DB M 1 150 or 900 680 DG T 275 FM 952 090 DG S 275 FM
961 115 DB M 1 150 FM 900 681 DG T 600 FM 952 096 DG S 600 FM
900 016 DBM 1 320 961 130 DB M 1 320 or 900 682 DG T 320 FM 952 093 DG S 320 FM
961 135 DB M 1 320 FM 900 683 DG T 150 FM 952 092 DG S 150 FM
900 025 DBM 1 255 961 120 DB M 1 255 900 684 DG T 75 FM 952 091 DG S 75 FM
900 026 DBM 1 255 L 961 125 DB M 1 255 FM 900 685 DG T 440 FM 952 095 DG S 440 FM
900 044 DBM 440 961 140 DBM 1 440 or 900 689 DG T 275 VA FM 952 087 DG S 275 VA FM
961 145 DBM 1 440 FM
900 691 DG T 385 FM 952 094 DG S 385 FM
900 055 DGPM 255 961 101 DGP M 255 or
961 105 DGP M 255 FM 900 692 DG T 75 VA FM 952 085 DG S 75 VA FM
901 000 VAV 1000 950 102 DG 1000 or
Lightning Current Arresters – Type 1 950 112 DG 1000 FM
900 100 DP 255 961 120 DB M 1 255 or 902 375 VA NH00 280 3 IG FM –
900 222 DB 1 255 H
902 376 VA NH00 280 4 IG FM –
900 101 DP 440 961 140 DBM 1 440 or
902 385 VA NH00 280 3 IG –
900 159 DB 1 440
902 386 VA NH00 280 4 IG –
900 110 DB 3 255 900 120 DB 3 255 H
950 220 DG T 48 952 078 DG S 48
900 111 DB 1 255 900 222 DB 1 255 H
950 225 DG T 48 FM 952 098 DG S 48 FM
900 260 DB NH00 255 900 273 DB NH00 255 H
Surge Arresters – Type 3
Surge Arresters – Type 2
901 100 DR 230 FML 953 205 DR M 2P 255 FM or
900 133 DGP C T 255 952 030 DGP C S or
953 200 DR M 2P 255
952 035 DGP C S FM
901 101 DR 120 FML 953 209 DR M 2P 150 FM or
900 265 V NH1 3 900 270 V NH1 280
953 204 DR M 2P 150
900 266 VA NH1 3 900 271 VA NH1 280
901 102 DR 60 FML 953 208 DR M 2P 75 FM or
900 506 DG TN 230 952 200 DG M TN 275 953 203 DR M 2P 75
900 507 DG TN 230 FM 952 205 DG M TN 275 FM 901 103 DR 48 FML 953 207 DR M 2P 60 FM or
900 508 DG TT 230 952 110 DG M TT 2P 275 953 202 DR M 2P 60
900 509 DG TT 230 FM 952 115 DG M TT 2P 275 FM 901 104 DR 24 FML 953 206 DR M 2P 30 FM or
900 510 DG TNC 230 400 952 300 DG M TNC 275 953 201 DR M 2P 30
900 516 DG IT 500 952 302 DG M WE 600 901 130 DR 230 3N FML 953 405 DR M 4P 255 FM or
953 400 DR M 4P 255
900 517 DG Y PV 1000 952 510 DG M YPV SCI 1000
952 511 DG M YPV SCI 600 909 820 SF PRO 909 240 DPRO 230 F
2x 950 500 2x DG PV 500 SCP 909 821 S PRO 909 230 DPRO 230
900 520 DG TT 230 400 952 310 DG M TT 275 Mains Connection Boxes
900 530 DG TNS 230 400 952 400 DG M TNS 275 900 964 NAK 63A 4 951 400 DV M TNS 255
900 540 DG TNC 230 400 FM 952 305 DG M TNC 275 FM 900 965 NAK 63A 3 951 300 DV M TNC 255
900 546 DG IT 500 FM 952 307 DG M WE 600 FM 900 966 NAK 35A 4 951 400 DV M TNS 255
900 547 DG Y PV 1000 FM 952 515 DG M YPV SCI 1000 FM 900 967 NAK 35A 3+1 951 310 DV M TT 255
952 516 DG M YPV SCI 600 FM
2x 950 505 2x DG PV 500 SCP FM 900 968 NAK 35A 3 951 300 DV M TNC 255
900 550 DG TT 230 400 FM 952 315 DG M TT 275 FM 900 969 NAK 63A 3+1 951 310 DV M TT 255
900 560 DG TNS 230 400 FM 952 405 DG M TNS 275 FM 902 492 NAK TAB 3 900 390 DV ZP TNC 255
900 600 DG 275 952 070 DG S 275 902 493 NAK TAB 3+1 900 391 DV ZP TT 255
900 601 DG 600 952 076 DG S 600 902 494 NAK TAB 4 900 391 DV ZP TT 255
900 602 DG 385 952 074 DG S 385 Accessories
900 603 DG 150 952 072 DG S 150 900 309 IGA 10 IP54 902 315 IGA 10 V2 IP54
900 604 DG 75 952 071 DG S 75 902 480 IGA 10 IP55 902 315 IGA 10 V2 IP54
900 605 DG 320 952 073 DG S 320 900 121 DBR 35 –
900 607 DG 440 952 075 DG S 440 900 122 DBR 63 –
900 620 DG 275 FM 952 090 DG S 275 FM 900 699 DK 35 952 699 DK 25
900 621 DG 600 FM 952 096 DG S 600 FM Isolating Spark Gaps
900 622 DG 385 FM 952 094 DG S 385 FM 923 070 EXFS C1 923 100 EXFS 100
900 623 DG 150 FM 952 092 DG S 150 FM 923 071 EXFS C1 KU 923 101 EXFS 100 KU
900 624 DG 75 FM 952 091 DG S 75 FM

www.dehn.de 29
Combined SPDs – Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS

30 www.dehn.de
Combined SPDs– Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNventil® modular


COMBINED SPDs – TYPE 1 Multipole modular combined lightning current and
SPD Type 1 according to EN 61643-11
SPD Class I according to IEC 61643-1
surge arrester

Combined SPDs Type 1


• Prewired spark-gap-based combined lightning
current and surge arrester, consisting of a base
part and plug-in protection modules
• Maximum system availability due to RADAX
Flow follow current limitation
• No tripping of 20 A gL/gG fuses up to short-cir-
cuit currents of 50 kArms
• Discharge capacity up to 100 kA (10/350 μs)
• Protection of terminal devices
• Operating state/fault indication by indicator
flag in the inspection window
• Easy replacement of protection modules with-
out tools due to module locking system with
module release button
For protecting low-voltage consumer´s installations against surges and • Vibration- and shock-tested according to EN
even direct lightning strikes. For installation in conformity with the light-
ning protection zones concept at the boundaries from 0A – 2.
60068-2

DEHNventil M TNC 255: Modular combined lightning current and surge arrester for use in TN-C systems
DEHNventil M TNS 255: Modular combined lightning current and surge arrester for use in TN-S systems
DEHNventil M TT 255: Modular combined lightning current and surge arrester for use in TT and TN-S systems
(”3+1” circuit)
DEHNventil M TN 255: Modular combined lightning current and surge arrester for use in single-phase TN systems
DEHNventil M TT 2P 255: Modular combined lightning current and surge arrester for use in single-phase TT and TN systems
(”1+1” circuit)
DEHNventil M ... FM: With remote signalling contact for monitoring device (floating changeover contact)

With their functional Red/Line design, the devices of the modular MVS 3 8 6 and MVS 4 11 8 can be
DEHNventil family combine safety and innovation. Designed for ”all-in- used. The right DEHNventil devices
one installation”, the SPDs integrate lightning equipotential bonding and can be easily chosen according to
protection against surges in a single device. This function is particularly of the system configuration of the
advantage in compact electrical installations. The design of the SPDs low-voltage consumer´s installa-
according to energy coordination criteria even allows protection of termi- tion and type designation of the
nal devices if they are close to the consumers ( ) 5 m). With their light- device.
ning current discharge capacity up to 100 000 A, the SPDs ensure high
availability of the electrical installation to be protected. Even for expand- The patented RADAX Flow technol-
ed electrical installations, the modular DEHNventil devices offer various ogy ensures follow current limita-
application possibilities. Red/Line surge arresters installed at the bound- tion and extinction as well as max-
aries of the individual lightning protection zones are already energy-coor- imum system availability of electri-
dinated with DEHNventil devices. By using encapsulated creepage dis- cal installations to be protected. Even in case of short-circuit currents as
charge spark gaps, combined with a compact design, DEHNventil units high as 50 kArms, mains follow currents are reduced in such a way that
are well suited for use in switchgear installations or distribution boards. there is a selectivity to lower fuse values, i.e. upstream fuses will not trip
A special feature of the new modular DEHNventil family is its functional due to arising mains follow currents.
design. The module release button is a key element. It ensures reliable fix-
ation of the protection module to keep the safe connection to the base The operating state/fault indication of each protective circuit immediate-
part even in case of maximum loads. If protection modules have to be ly provides information on the operating state of the surge arrester even
replaced, the module is released without tools and can be removed easi- if no operating current is present. Apart from the standard green and red
ly. The devices incorporate double terminals which are suitable for all con- indicator, DEHNventil M ... FM devices feature a three-pole terminal for
ductors, allowing series connection in a space- and cost-effective way remote signalling. With their floating changeover contact, the remote sig-
according to IEC 60364-5-53 requirements for nominal currents up to nal can be used as a break or make contact according to the particular cir-
125 A. For connecting further DIN rail mounted devices, busbars of type cuit concept.

www.dehn.de 31
Combined SPDs– Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNventil® modular POWER SUPPLY SYSTEMS


951 300 DV M
TNC 255

DEHNventil M TNC (FM) COMBINED SPDs – TYPE 1


951 305 DV M
TNC 255 FM

L1 L1´ L2 L2´ L3 L3´


Combined SPDs Type 1

DV M TNC 255
951 300
DV M TNC 255 FM
951 305

12
11
14

PEN

Basic circuit diagram DV M TNC 255 FM Dimension drawing DV M TNC 255 (FM)

DV M TNC 255 (FM): Modular combined lightning current and surge arrester for protecting TN-C
systems against surges

DV M TNC 255 DV M TNC 255 FM


SPD according to EN 61643-11 / ... IEC 61643-1 Type 1 / Class I Type 1 / Class I
Energy-coordinated protection effect with
regard to the terminal equipment Type 1 + Type 2 Type 1 + Type 2
Energy-coordinated protection effect with
regard to the terminal equipment ( ) 5m) Type 1 + Type 2 + Type 3 Type 1 + Type 2 + Type 3
Nominal a.c. voltage UN 230 / 400 V 230 / 400 V
Max. continuous operating a.c. voltage UC 255 V 255 V
Lightning impulse current (10/350 μs) [L1+L2+L3-PEN] Itotal 75 kA 75 kA
Lightning impulse current (10/350 μs) [L-PEN] Iimp 25 kA 25 kA
Nominal discharge current (8/20 μs) In 25 / 75 kA 25 / 75 kA
Voltage protection level UP ) 1.5 kV ) 1.5 kV
Follow current extinguishing capability a.c. Ifi 50 kArms 50 kArms
Follow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.) no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA ) 100 ns ) 100 ns
Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG 315 A gL/gG
Max. backup fuse (L) for IK > 50 kArms 200 A gL/gG 200 A gL/gG
Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG
Temporary overvoltage (TOV) UT 440 V / 5 sec. 440 V / 5 sec.
TOV characteristics withstand withstand
Operating temperature range [parallel]/[continuity] TU -40°C...+80°C / -40°C...+60°C -40°C...+80°C / -40°C...+60°C
Operating state/fault indication green / red green / red
Cross-sectional area (L1, L1´, L2, L2´, L3, L3´, PEN, 9) min. 10 mm2 solid/flexible 10 mm2 solid/flexible
Cross-sectional area (L1, L2, L3, PEN) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible
Cross-sectional area (L1´, L2´, L3´, 9) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 6 mods., DIN 43880 6 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL, VdS KEMA, VDE, UL, VdS
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DV M TNC 255 DV M TNC 255 FM
Part No. 951 300 951 305
Packing unit 1 pc(s). 1 pc(s).

Accessory part for DEHNventil® modular


951 001
255
DV MOD

Spark-gap-based protection module


PU Part
DV MOD 255
951 001
Type pc(s). No.
DV MOD 255 1 951 001

32 www.dehn.de
Combined SPDs– Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNventil® modular


951 400 DV M TNS
255

COMBINED SPDs – TYPE 1 DEHNventil M TNS (FM)


951 405 DV M TNS
255 FM

L1 L1´ L2 L2´ L3 L3´ N N´

Combined SPDs Type 1


DV M TNS 255
951 400
DV M TNS 255 FM
951 405

12
11
14

PE

Dimension drawing DV M TNS 255 (FM) Basic circuit diagram DV M TNS 255 FM

DV M TNS 255 (FM): Modular combined lightning current and surge arrester for protecting TN-S
systems against surges

DV M TNS 255 DV M TNS 255 FM


SPD according to EN 61643-11 / ... IEC 61643-1 Type 1 / Class I Type 1 / Class I
Energy-coordinated protection effect with
regard to the terminal equipment Type 1 + Type 2 Type 1 + Type 2
Energy-coordinated protection effect with
regard to the terminal equipment ( ) 5m) Type 1 + Type 2 + Type 3 Type 1 + Type 2 + Type 3
Nominal a.c. voltage UN 230 / 400 V 230 / 400 V
Max. continuous operating a.c. voltage UC 255 V 255 V
Lightning impulse current (10/350 μs) [L1+L2+L3+N-PE] Itotal 100 kA 100 kA
Lightning impulse current (10/350 μs) [L, N-PE] Iimp 25 kA 25 kA
Nominal discharge current (8/20 μs) In 25 / 100 kA 25 / 100 kA
Voltage protection level [L-PE]/[N-PE] UP ) 1.5 kV / ) 1.5 kV ) 1.5 kV / ) 1.5 kV
Follow current extinguishing capability a.c. Ifi 50 kArms 50 kArms
Follow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.) no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA ) 100 ns ) 100 ns
Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG 315 A gL/gG
Max. backup fuse (L) for IK > 50 kArms 200 A gL/gG 200 A gL/gG
Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG
Temporary overvoltage (TOV) [L-N] UT 440 V / 5 sec. 440 V / 5 sec.
TOV characteristics withstand withstand
Operating temperature range [parallel]/[continuity] TU -40°C...+80°C / -40°C...+60°C -40°C...+80°C / -40°C...+60°C
Operating state/fault indication green / red green / red
Cross-sectional area (L1, L1´, L2, L2´, L3, L3´, N, N´, PE, 9) min. 10 mm2 solid/flexible 10 mm2 solid/flexible
Cross-sectional area (L1, L2, L3, N, PE) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible
Cross-sectional area (L1´, L2´, L3´, N´, 9) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 8 mods., DIN 43880 8 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL, VdS KEMA, VDE, UL, VdS
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DV M TNS 255 DV M TNS 255 FM
Part No. 951 400 951 405
Packing unit 1 pc(s). 1 pc(s).

Accessory part for DEHNventil® modular


Spark-gap-based protection module
951 001
255
DV MOD

PU Part
Type
DV MOD 255
Ableiter-Schutzmodul
Kombi-
951 001
pc(s). No.
DV MOD 255 1 951 001

www.dehn.de 33
Combined SPDs– Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNventil® modular POWER SUPPLY SYSTEMS


951 310 DV M TT
255

DEHNventil M TT (FM) COMBINED SPDs – TYPE 1


951 315 DV M TT
255 FM

L1 L1´ L2 L2´ L3 L3´ N N´


Combined SPDs Type 1

DV M TT 255
951 310
DV M TT 255 FM
951 315

12
11
14 NPE

PE

Basic circuit diagram DV M TT 255 FM Dimension drawing DV M TT 255 (FM)

DV M TT 255 (FM): Modular combined lightning current and surge arrester for protecting TT and
TN-S systems (”3+1” circuit) against surges
DV M TT 255 DV M TT 255 FM
SPD according to EN 61643-11 / ... IEC 61643-1 Type 1 / Class I Type 1 / Class I
Energy-coordinated protection effect with
regard to the terminal equipment Type 1 + Type 2 Type 1 + Type 2
Energy-coordinated protection effect with
regard to the terminal equipment ( ) 5m) Type 1 + Type 2 + Type 3 Type 1 + Type 2 + Type 3
Nominal a.c. voltage UN 230 / 400 V 230 / 400 V
Max. continuous operating a.c. voltage UC 255 V 255 V
Lightning impulse current (10/350 μs) [L1+L2+L3+N-PE] Itotal 100 kA 100 kA
Lightning impulse current (10/350 μs) [L-N]/[N-PE] Iimp 25 / 100 kA 25 / 100 kA
Nominal discharge current (8/20 μs) In 25 / 100 kA 25 / 100 kA
Voltage protection level [L-N]/[N-PE] UP ) 1.5 kV / ) 1.5 kV ) 1.5 kV / ) 1.5 kV
Follow current extinguishing capability [L-N]/[N-PE] Ifi 50 kArms / 100 Arms 50 kArms / 100 Arms
Follow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.) no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA ) 100 ns ) 100 ns
Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG 315 A gL/gG
Max. backup fuse (L) for IK > 50 kArms 200 A gL/gG 200 A gL/gG
Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG
Temporary overvoltage (TOV) [L-N] UT 440 V / 5 sec. 440 V / 5 sec.
Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms
TOV characteristics withstand withstand
Operating temperature range [parallel]/[continuity] TU -40°C...+80°C / -40°C...+60°C -40°C...+80°C / -40°C...+60°C
Operating state/fault indication green / red green / red
Cross-sectional area (L1, L1´, L2, L2´, L3, L3´, N, N´, PE, 9) min. 10 mm2 solid/flexible 10 mm2 solid/flexible
Cross-sectional area (L1, L2, L3, N, PE) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible
Cross-sectional area (L1´, L2´, L3´, N´, 9) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 8 mods., DIN 43880 8 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL, VdS KEMA, VDE, UL, VdS
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DV M TT 255 DV M TT 255 FM
Part No. 951 310 951 315
Packing unit 1 pc(s). 1 pc(s).

Accessory part for DEHNventil® modular Accessory part for DEHNventil® modular
951 001
255
DV MOD

Spark-gap-based protection module 951 050


951 100
DV MOD NPE 50
DV MOD NPE 100
N-PE spark-gap-based protection module
PU Part PU Part
DV MOD 255
Ableiter-Schutzmodul
Kombi-
951 001
Type pc(s). No. DV MOD NPE 50
951 050
Type pc(s). No.
DV MOD NPE 100

DV MOD 255 1 951 001 951 100


DV MOD NPE 100 1 951 100

34 www.dehn.de
Combined SPDs– Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNventil® modular


951 200 DV M TN
255

COMBINED SPDs – TYPE 1 DEHNventil M TN (FM)


951 205 DV M TN
255 FM

L L´ N N´

Combined SPDs Type 1


DV M TN 255
951 200
DV M TN 255 FM
951 205

12
11
14

PE

Dimension drawing DV M TN 255 (FM) Basic circuit diagram DV M TN 255 FM

DV M TN 255 (FM): Modular combined lightning current and surge arrester for protecting single-
phase TN systems against surges
DV M TN 255 DV M TN 255 FM
SPD according to EN 61643-11 / ... IEC 61643-1 Type 1 / Class I Type 1 / Class I
Energy-coordinated protection effect with
regard to the terminal equipment Type 1 + Type 2 Type 1 + Type 2
Energy-coordinated protection effect with
regard to the terminal equipment ( ) 5m) Type 1 + Type 2 + Type 3 Type 1 + Type 2 + Type 3
Nominal a.c. voltage UN 230 V 230 V
Max. continuous operating a.c. voltage UC 255 V 255 V
Lightning impulse current (10/350 μs) [L+N-PE] Itotal 50 kA 50 kA
Lightning impulse current (10/350 μs) [L, N-PE] Iimp 25 kA 25 kA
Nominal discharge current (8/20 μs) In 25 / 50 kA 25 / 50 kA
Voltage protection level [L-PE]/[N-PE] UP ) 1.5 kV / ) 1.5 kV ) 1.5 kV / ) 1.5 kV
Follow current extinguishing capability a.c. Ifi 50 kArms 50 kArms
Follow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.) no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA ) 100 ns ) 100 ns
Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG 315 A gL/gG
Max. backup fuse (L) for IK > 50 kArms 200 A gL/gG 200 A gL/gG
Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG
Temporary overvoltage (TOV) [L-N] UT 440 V / 5 sec. 440 V / 5 sec.
TOV characteristics withstand withstand
Operating temperature range [parallel]/[continuity] TU -40°C...+80°C / -40°C...+60°C -40°C...+80°C / -40°C...+60°C
Operating state/fault indication green / red green / red
Cross-sectional area (L, L´, N, N´, PE, 9) min. 10 mm2 solid/flexible 10 mm2 solid/flexible
Cross-sectional area (L, N, PE) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible
Cross-sectional area (L´, N´, 9) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 4 mods., DIN 43880 4 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL, VdS KEMA, VDE, UL, VdS
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DV M TN 255 DV M TN 255 FM
Part No. 951 200 951 205
Packing unit 1 pc(s). 1 pc(s).

Accessory part for DEHNventil® modular


Spark-gap-based protection module
951 001
255
DV MOD

PU Part
Type
DV MOD 255
Ableiter-Schutzmodul
Kombi-
951 001
pc(s). No.
DV MOD 255 1 951 001

www.dehn.de 35
Combined SPDs– Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNventil® modular POWER SUPPLY SYSTEMS


951 110 DV M TT
2P 255

DEHNventil M TT 2P (FM) COMBINED SPDs – TYPE 1


951 115 DV M TT
2P 255 FM

L L´ N N´
Combined SPDs Type 1

DV M TT 2P 255
951 110
DV M TT 2P 255 FM
951 115

12
11
14 NPE

PE

Basic circuit diagram DV M TT 2P 255 FM Dimension drawing DV M TT 2P 255 (FM)

DV M TT 2P 255 (FM): Modular combined lightning current and surge arrester for protecting
single-phase TT and TN systems (”1+1” circuit) against surges
DV M TT 2P 255 DV M TT 2P 255 FM
SPD according to EN 61643-11 / ... IEC 61643-1 Type 1 / Class I Type 1 / Class I
Energy-coordinated protection effect with
regard to the terminal equipment Type 1 + Type 2 Type 1 + Type 2
Energy-coordinated protection effect with
regard to the terminal equipment ( ) 5m) Type 1 + Type 2 + Type 3 Type 1 + Type 2 + Type 3
Nominal a.c. voltage UN 230 V 230 V
Max. continuous operating a.c. voltage UC 255 V 255 V
Lightning impulse current (10/350 μs) [L+N-PE] Itotal 50 kA 50 kA
Lightning impulse current (10/350 μs) [L-N]/[N-PE] Iimp 25 / 50 kA 25 / 50 kA
Nominal discharge current (8/20 μs) In 25 / 50 kA 25 / 50 kA
Voltage protection level [L-N]/[N-PE] UP ) 1.5 kV / ) 1.5 kV ) 1.5 kV / ) 1.5 kV
Follow current extinguishing capability [L-N]/[N-PE] Ifi 50 kArms / 100 Arms 50 kArms / 100 Arms
Follow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.) no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA ) 100 ns ) 100 ns
Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG 315 A gL/gG
Max. backup fuse (L) for IK > 50 kArms 200 A gL/gG 200 A gL/gG
Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG
Temporary overvoltage (TOV) [L-N] UT 440 V / 5 sec. 440 V / 5 sec.
Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms
TOV characteristics withstand withstand
Operating temperature range [parallel]/[continuity] TU -40°C...+80°C / -40°C...+60°C -40°C...+80°C / -40°C...+60°C
Operating state/fault indication green / red green / red
Cross-sectional area (L, L´, N, N´, PE, 9) min. 10 mm2 solid/flexible 10 mm2 solid/flexible
Cross-sectional area (L, N, PE) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible
Cross-sectional area (L´, N´, 9) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94-V-0 thermoplastic, red, UL 94-V-0
Degree of protection IP 20 IP 20
Capacity 4 mods., DIN 43880 4 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL, VdS KEMA, VDE, UL, VdS
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DV M TT 2P 255 DV M TT 2P 255 FM
Part No. 951 110 951 115
Packing unit 1 pc(s). 1 pc(s).

Accessory part for DEHNventil® modular Accessory part for DEHNventil® modular
951 001
255
DV MOD

Spark-gap-based protection module 951 050 DV MOD NPE 50

N-PE spark-gap-based protection module


PU Part PU Part
DV MOD 255
Ableiter-Schutzmodul
Kombi-
951 001
Type pc(s). No. DV MOD NPE 50
Ableiter-Schutzmodul N-PE 50 kA
Kombi-
951 050
Type pc(s). No.
DV MOD 255 1 951 001 DV MOD NPE 50 1 951 050

36 www.dehn.de
Combined SPDs– Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS Protection Module for DEHNventil® modular


COMBINED SPDs – TYPE 1
SPD Type 1 according to EN 61643-11
SPD Class I according to IEC 61643-1

Combined SPDs Type 1


• High discharge capacity due to powerful creep-
age discharge spark gap
• Maximum system availability due to RADAX
Flow follow current limitation
• With module release button for replacing pro-
tection modules without tools
• Operating state/fault indication by green/red
indicator flag in the inspection window
• The plug-in protection module can be replaced
without the need to de-energise and without
removing the cover plate of the distribution
board

For protecting low-voltage consumer´s installations against surges and


even direct lightning strikes. For installation in conformity with the light-
ning protection zones concept at the boundaries from 0A – 2.

DV MOD 255: Spark-gap-based protection module


DV MOD NPE 50: 50 kA N-PE spark-gap-based protection module
DV MOD NPE 100: 100 kA N-PE spark-gap-based protection module

The spark-gap-based protection modules of the modular DEHNventil The module locking device ensures safe fixation of the protection modules
series combine safety and innovation. Apart from the encapsulated in the base part. The protection modules are easily removed without the
RADAX Flow spark gap technology, the compact protection components use of tools by simply pressing the module release button.
incorporate the complete monitoring circuit for controlling the energy
flow of the spark gap, monitoring device and operating state/fault indica-
tor.

The mechanical coding of the protection module prevents unintended


interchanging of the N-PE protection modules with the spark-gap-based
module for the phase conductors.

www.dehn.de 37
Combined SPDs– Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

Protection Module for DEHNventil® modular POWER SUPPLY SYSTEMS


951 001 DV MOD
255

Spark-gap-based protection module COMBINED SPDs – TYPE 1


Combined SPDs Type 1

DV MOD 255
951 001

Basic circuit diagram DV MOD 255 Dimension drawing DV MOD 255

DV MOD 255: Spark-gap-based protection module

DV MOD 255
Max. continuous operating a.c. voltage UC 255 V
Lightning impulse current (10/350 μs) Iimp 25 kA
Follow current extinguishing capability [L-N] a.c. Ifi 50 kArms
Follow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)

Ordering information
Type DV MOD 255
Part No. 951 001
Packing unit 1 pc(s).

951 050 DV MOD


NPE 50

N-PE spark-gap-based protection module


951 100 DV MOD
NPE 100

DV MOD NPE 50
951 050
DV MOD NPE 100
951 100

NPE

Basic circuit diagram DV MOD NPE ... Dimension drawing DV MOD NPE ...

DV MOD NPE 50: 50 kA N-PE spark-gap-based protection module


DV MOD NPE 100: 100 kA N-PE spark-gap-based protection module

DV MOD NPE 50 DV MOD NPE 100


Max. continuous operating a.c. voltage UC 255 V 255 V
Lightning impulse current (10/350 μs) Iimp 50 kA 100 kA
Follow current extinguishing capability [N-PE] a.c. Ifi 100 Arms 100 Arms

Ordering information
Type DV MOD NPE 50 DV MOD NPE 100
Part No. 951 050 951 100
Packing unit 1 pc(s). 1 pc(s).

38 www.dehn.de
Combined SPDs– Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNventil® ZP


COMBINED SPDs – TYPE 1 Multipole combined lightning current and
SPD Type 1 according to EN 61643-11
SPD Class I according to IEC 61643-1
surge arrester for primary power systems

Combined SPDs Type 1


• Combined lightning current and surge arrester based on RADAX
Flow spark gap technology
• Fully compliant with all requirements of the national VDN*
Directive on the use of SPDs upstream of the meter
• Quick and easy installation by snapping the SPD onto 40 mm bus-
bar systems
• Test for correct operation by pressing the button with light indi-
cator
• No tripping of fuses from 32 A gL/gG up to short-circuit currents
of 25 kArms
• Discharge capacity up to 100 kA (10/350 μs)
• Protection of terminal equipment
• Maximum system availability

DEHNventil ZP TNC 255: Three-pole combined lightning current and surge


arrester for TN-C systems for use in primary power sys-
For protecting low-voltage consumer´s installa-
tems
tions against surges and even direct lightning
strikes. For installation in conformity with the DEHNventil ZP TT 255: Four-pole combined lightning current and surge
lightning protection zones concept at the arrester for TT and TN-S systems for use in primary
boundaries from 0A – 2. power systems

The DEHNventil ZP combined lightning current


and surge arrester is specifically designed for
connection to busbar panels of supply meters. It
can be snapped directly onto the busbar system
without the need for tools. Its reduced size
leaves enough space for connecting cables from
the service entrance box (SEB), even if three
selective main circuit breakers are installed.
The operating state of the SPD is indicated by a
light indicator which is controlled by a button.
Both with this kind of operating state control
and due to its design as a spark-gap-based SPD,
the DEHNventil ZP device has no leakage and
operating currents.
The RADAX Flow spark gap technology allows
the required selectivity for follow currents even
for small-sized fuses in the service entrance
box. Unwanted interruptions of the power sup-
ply due to tripping of main fuses are thus avoid-
ed.
The dimensioning of the parameters as well as
the complete concept of the device are fully
compliant with all requirements of the new
German VDN* Directive on the use of surge protective devices in primary power systems.

* VDN ... Verband der Netzbetreiber VDN e. V. at BDEW


[Association of German network operators]

www.dehn.de 39
Combined SPDs– Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNventil® ZP POWER SUPPLY SYSTEMS


900 390 DV ZP
TNC 255

DEHNventil ZP TNC COMBINED SPDs – TYPE 1

PEN
Combined SPDs Type 1

DV ZP TNC 255
900 390

L1

&
L2

L3

PEN

Basic circuit diagram DV ZP TNC 255 Dimension drawing DV ZP TNC 255

DV ZP TNC 255: Combined lightning current and surge arrester for TN-C systems for use in primary
power systems (”3-0” circuit)

DV ZP TNC 255
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Energy-coordinated protection effect with regard to the terminal equipment Type 1 + Type 2
Energy-coordinated protection effect with regard to the terminal equipment ( ) 5m) Type 1 + Type 2 + Type 3
Nominal a.c. voltage UN 230 / 400 V
Max. continuous operating a.c. voltage UC 255 V
Lightning impulse current (10/350 μs) [L1+L2+L3-PEN] Itotal 75 kA
Lightning impulse current (10/350 μs) [L-PEN] Iimp 25 kA
Nominal discharge current (8/20 μs) In 25 / 75 kA
Voltage protection level UP ) 1.5 kV
Follow current extinguishing capability a.c. Ifi 25 kArms
Follow current limitation/Selectivity no tripping of a 32 A gL/gG fuse up to 25 kArms (prosp.)
Response time tA ) 100 ns
Max. backup fuse up to I = 25 kArms 315 A gL/gG
Max. backup fuse for IK > 25 kArms 200 A gL/gG
Temporary overvoltage (TOV) UT 335 V / 5 sec.
TOV characteristics withstand
Operating temperature range TU -40°C...+80°C
Function control button with light indicator
Cross-sectional area (PEN, 9) 10-35 mm2 flexible/50 mm2 stranded
For mounting on 40 mm busbar system
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IP 20
Capacity 3 mods., DIN 43880
Certifications, Approvals VDE

Ordering information
Type DV ZP TNC 255
Part No. 900 390
Packing unit 1 pc(s).

40 www.dehn.de
Combined SPDs– Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNventil® ZP


900 391 DV ZP TT
255

COMBINED SPDs – TYPE 1 DEHNventil ZP TT

Combined SPDs Type 1


DV ZP TT 255
900 391

L1

L2
&
L3

PE*
* in case of existing
PE busbar
PE

Dimension drawing DV ZP TT 255 Basic circuit diagram DV ZP TT 255

DV ZP TT 255: Combined lightning current and surge arrester for TT and TN-S systems for use in
primary power systems (”3+1” circuit)

DV ZP TT 255
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Energy-coordinated protection effect with regard to the terminal equipment Type 1 + Type 2
Energy-coordinated protection effect with regard to the terminal equipment ( ) 5m) Type 1 + Type 2 + Type 3
Nominal a.c. voltage UN 230 / 400 V
Max. continuous operating a.c. voltage UC 255 V
Lightning impulse current (10/350 μs) [L1+L2+L3+N-PE] Iimp 100 kA
Lightning impulse current (10/350 μs) [L-N] Iimp 25 kA
Lightning impulse current (10/350 μs) [N-PE] Iimp 100 kA
Nominal discharge current (8/20 μs) In 25 / 100 kA
Voltage protection level [L-N] UP ) 1.5 kV
Voltage protection level [N-PE] UP ) 1.5 kV
Follow current extinguishing capability [L-N] a.c. Ifi 25 kArms
Follow current extinguishing capability [N-PE] a.c. Ifi 100 Arms
Follow current limitation/Selectivity no tripping of a 32 A gL/gG fuse up to 25 kArms (prosp.)
Response time tA ) 100 ns
Max. backup fuse up to I = 25 kArms 315 A gL/gG
Max. backup fuse for IK > 25 kArms 200 A gL/gG
Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec.
Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms
TOV characteristics withstand
Operating temperature range TU -40°C...+80°C
Function control button with light indicator
Cross-sectional area (PE, 9) 10-35 mm2 flexible/50 mm2 stranded
For mounting on 40 mm busbar system
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IP 20
Capacity 3 mods., DIN 43880
Certifications, Approvals VDE

Ordering information
Type DV ZP TT 255
Part No. 900 391
Packing unit 1 pc(s).

www.dehn.de 41
Combined SPDs– Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNlimit PV 1000 POWER SUPPLY SYSTEMS


Type 1 combined lightning current and COMBINED SPDs – TYPE 1
surge arrester for use in photovoltaic systems SPD Type 1 classification according to EN 61643-11
SPD Class I classification according to IEC 61643-1
Combined SPDs Type 1

• Prewired combined lightning current and surge


arrester for use in photovoltaic generator cir-
cuits
• For use in photovoltaic installations up to
1000 V UCPV
• High lightning current discharge capacity due
to approved spark gap technology
• Maximum system availability due to spark gap
technology with d.c. current extinction

For protecting photovoltaic inverters against surges and even direct light-
ning strikes. For use in accordance with IEC 60364-7-712:2002-05
(Installation of photovoltaic power supply systems).

DEHNlimit PV 1000: Combined lightning current and surge arrester for use in photovoltaic power supply systems up to
1000 V d.c.

The combined lightning current and surge arrester of type DEHNlimit PV The d.c. extinction by the spark gap is a unique feature of DEHNlimit PV
1000 was specifically developed for use in photovoltaic power supply sys- 1000. Potential short-circuit currents up to 100 A caused by a tripping
tems. The approved encapsulated creepage discharge spark gap technol- spark gap are interrupted within only a fraction of a second in case of a
ogy allows reliable protection of photovoltaic generators and inverters photovoltaic voltage up to 1000 V d.c.
even in the event of direct lightning impulse currents. It is the voltage pro-
tection level of DEHNlimit PV 1000 and reduction of the impulse time due The combination of lightning current carrying capability, protection capa-
to the spark gap technology that allow for coordination of the SPD with bility and follow current extinction provides maximum availability of the
the equipment to be protected. PV system protected by DEHNlimit PV 1000.

42 www.dehn.de
Combined SPDs– Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNlimit PV 1000


900 330 DLM PV
1000

COMBINED SPDs – TYPE 1 DEHNlimit PV 1000


L+ L–

Combined SPDs Type 1


DLM PV 1000
900 330

d.c. control bypass

(8 mods.)

Dimension drawing DLM PV 1000 Basic circuit diagram DLM PV 1000

DLM PV 1000: Combined lightning current and surge arrester for use in photovoltaic power
supply systems up to 1000 V d.c.

DLM PV 1000
SPD classification according to EN 61643-11 Type 1
SPD classification according to IEC 61643-1 Class I
Max. PV voltage [UCPV ] of the PV generator 1000 V
Max. continuous operating d.c. voltage Umax dc 1000 V
Min. continuous operating d.c. voltage Umin dc 100 V
Follow current extinguishing capability d.c. Ifi dc 100 A
Nominal discharge current (8/20 μs) In 100 kA
Lightning impulse current (10/350 μs) [L+/L- -> PE] Iimp 50 kA
Lightning impulse current (10/350 μs) [L+ -> L-] Iimp 25 kA
Voltage protection level [L+ -> L-] Up ) 3.3 kV
Voltage protection level [(L+/L-) -> PE] Up ) 4 kV
Operating current IIN dc ) 5 mA
Response time [L+ -> L-] tA ) 20 ns
Protective conductor current IPE ) 1 μA
Operating temperature range Tu -40°C...+60°C
Cross-sectional area (min.) 10 mm2 solid/flexible
Cross-sectional area (max.) 50 mm2 stranded/ 35 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IP 20
Capacity 8 mods., DIN 43880

Ordering information
Type DLM PV 1000
Part No. 900 330
Packing unit 1 pc(s).

www.dehn.de 43
Combined SPDs– Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS


COMBINED SPDs – TYPE 1
Combined SPDs Type 1

44 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNbloc® M


LIGHTNING CURRENT ARRESTERS – TYPE 1 Single-pole modular coordinated
SPD Type 1 according to EN 61643-11
SPD Class I according to IEC 61643-1
lightning current arrester

• Coordinated spark-gap-based lightning current


arrester consisting of a base part and plug-in
protection module
• Maximum system availability due to RADAX
Flow follow current limitation
• No tripping of 32 A gL/gG fuses up to short-cir-

Lightn. Curr. Arr. Type 1


cuit currents of 50 kArms
• Discharge capacity up to 50 kA (10/350 μs)
• Directly coordinated with DEHNguard surge
protective devices without additional cable
length
• Low voltage protection level
• Operating state/fault indication by indicator
flag in the inspection window
For protecting low-voltage consumer´s installations against surges and • Easy replacement of protection modules with-
even direct lightning strikes. For installation in conformity with the light-
ning protection zones concept at the boundaries from 0A – 1.
out tools due to module locking system with
module release button

DEHNbloc M 1 ...: Single-pole modular coordinated lightning current arrester with high follow current limitation
DEHNbloc M 1 ... FM: With remote signalling contact for the monitoring system (floating changeover contact)

The modular devices of the DEHNbloc M product family are coordinated during transport or operation or
lightning current arresters with a functional design. enormous mechanical impulse
loads resulting from discharges do
Energy coordination with Type 2 surge arresters of the DEHNguard fami- not affect the module locking sys-
ly is ensured without additional cable lengths or decoupling coils. This is tem which ensures safe fixation
one of the most important characteristics of the Red/Line product family. both for the base part and protec-
tion module. Nevertheless, the pro-
The DEHNbloc M devices stand for performance and user friendliness in a tection modules can be easily
concise form. Their electrical parameters were rated for maximum require- replaced without tools by simply
ments for lightning and surge protection systems. DEHNbloc M is the ideal pressing the user-friendly module
device for use in main distribution boards of low-voltage consumer´s release button. In order to avoid
installations of a building. Equipped with the latest RADAX Flow spark incorrect insertion by the installer
gap technology, the most important goal of DEHNbloc M is to ensure pro- or user when replacing the modules, both the base part and protection
tection and availability of electrical installations. module are mechanically coded. DEHNbloc M devices incorporate double
terminals which are suitable for all conductors, allowing series connection
Due to the unique follow current limitation and follow current extinction, of the SPDs in a space- and cost-saving way according to IEC 60364-5-53
a follow current breaking selectivity is ensured even for small-sized fuses requirements for nominal currents up to 125 A.
in installations. DEHNbloc M is leakage-current-free and has a mechani-
cal operating state indication, allowing the device to be installed even The operating state/fault indication of DEHNbloc M immediately provides
upstream of meter panels in low-voltage consumer´s installations. information on the availability of the device even if no operating current
is present. Apart from the standard red and green indicator, DEHNbloc M
When installing this modular arrester, the user of DEHNbloc M has all ... FM devices have an additional remote signalling output. With their
safety characteristics and features this design has to offer. The vibration- floating changeover contact, the remote signal can be used as a break or
proof module locking system, for example, is unique. Shock or vibration make contact according to the particular circuit concept.

www.dehn.de 45
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNbloc® M POWER SUPPLY SYSTEMS


961 110 DB M 1
150

DEHNbloc M 1 ... LIGHTNING CURRENT ARRESTERS – TYPE 1


961 120 DB M 1
255
961 130 DB M 1
320

L/N
DB M 1 150
961 110
DB M 1 255
961 120
DB M 1 320
961 130

(2 mods.)
Lightn. Curr. Arr. Type 1

N/PE(N)

Basic circuit diagram DB M 1 ... Dimension drawing DB M 1 ...

DB M 1 ...: Single-pole, modular, coordinated lightning current arrester with high follow current
limitation

DB M 1 150 DB M 1 255 DB M 1 320


SPD according to EN 61643-11 Type 1 Type 1 Type 1
SPD according to IEC 61643-1 Class I Class I Class I
Max. continuous operating a.c. voltage UC 150 V 255 V 320 V
Lightning impulse current (10/350 μs) Iimp 35 kA 50 kA 25 kA
Nominal discharge current (8/20 μs) In 35 kA 50 kA 25 kA
Voltage protection level UP 1.5 kV 2.5 kV 2.5 kV
Follow current extinguishing capability a.c. Ifi 50 kArms 50 kArms 50 kArms
Follow current limitation/Selectivity no tripping of a 32 A gL/gG no tripping of a 32 A gL/gG no tripping of a 32 A gL/gG
fuse up to 50 kArms (prosp.) fuse up to 50 kArms (prosp.) fuse up to 50 kArms (prosp.)
Response time tA ) 100 ns ) 100 ns ) 100 ns
Max. backup fuse (L) up to IK = 50 kArms (ta ) 0.2 s) 500 A gL/gG 500 A gL/gG 315 A gL/gG
Max. backup fuse (L) up to IK = 50 kArms (ta ) 5 s) 315 A gL/gG 315 A gL/gG 315 A gL/gG
Max. backup fuse (L) for IK > 50 kArms 200 A gL/gG 200 A gL/gG 200 A gL/gG
Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG 125 A gL/gG
Temporary overvoltage (TOV) UT 200 V / 5 sec. 440 V / 5 sec. 440 V / 5 sec.
TOV characteristics withstand withstand withstand
Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C -40°C...+80°C
Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C -40°C...+60°C
Operating state/fault indication green / red green / red green / red
Cross-sectional area (L/N, L´/N´, N/PE (N)) min. 10 mm2 solid/flexible 10 mm2 solid/flexible 10 mm2 solid/flexible
Cross-sectional area (L/N, N/PE(N)) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible
Cross-sectional area (L´/N´) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20
Capacity 2 mods., DIN 43880 2 mods., DIN 43880 2 mods., DIN 43880
Test standards — VDE, KEMA —

Ordering information
Type DB M 1 150 DB M 1 255 DB M 1 320
Part No. 961 110 961 120 NEW 961 130
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNbloc® M


961 001
MOD 150
961 002
MOD 255
961 003
DB M

DB M

DB M
DB M spark-gap-based protection module
MOD 320

PU Part
DB M MOD 150
961 001
Type pc(s). No.
DB M MOD 255
961 002
DB M MOD 320
961 003
DB M MOD 150 1 961 001
DB M MOD 255 1 961 002
DB M MOD 320 1 961 003

46 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNbloc® M


961 115 DB M 1
150 FM

LIGHTNING CURRENT ARRESTERS – TYPE 1 DEHNbloc M 1 ... FM


961 125 DB M 1
255 FM
961 135 DB M 1
320 FM

L/N
DB M 1 150 FM
961 115
DB M 1 255 FM
961 125
DB M 1 320 FM
961 135

12
11
14

(2 mods.)

Lightn. Curr. Arr. Type 1


N/PE(N)

Dimension drawing DB M 1 ... FM Basic circuit diagram DB M 1 ... FM

DB M 1 ... FM: Single-pole, modular, coordinated lightning current arrester with high follow cur-
rent limitation; with remote signalling contact for the monitoring system (floating
changeover contact)

DB M 1 150 FM DB M 1 255 FM DB M 1 320 FM


SPD according to EN 61643-11 Type 1 Type 1 Type 1
SPD according to IEC 61643-1 Class I Class I Class I
Max. continuous operating a.c. voltage UC 150 V 255 V 320 V
Lightning impulse current (10/350 μs) Iimp 35 kA 50 kA 25 kA
Nominal discharge current (8/20 μs) In 35 kA 50 kA 25 kA
Voltage protection level UP 1.5 kV 2.5 kV 2.5 kV
Follow current extinguishing capability a.c. Ifi 50 kArms 50 kArms 50 kArms
Follow current limitation/Selectivity no tripping of a 32 A gL/gG no tripping of a 32 A gL/gG no tripping of a 32 A gL/gG
fuse up to 50 kArms (prosp.) fuse up to 50 kArms (prosp.) fuse up to 50 kArms (prosp.)
Response time tA ) 100 ns ) 100 ns ) 100 ns
Max. backup fuse (L) up to IK = 50 kArms (ta ) 0.2 s) 500 A gL/gG 500 A gL/gG 315 A gL/gG
Max. backup fuse (L) up to IK = 50 kArms (ta ) 5 s) 315 A gL/gG 315 A gL/gG 315 A gL/gG
Max. backup fuse (L) for IK > 50 kArms 200 A gL/gG 200 A gL/gG 200 A gL/gG
Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG 125 A gL/gG
Temporary overvoltage (TOV) UT 200 V / 5 sec. 440 V / 5 sec. 440 V / 5 sec.
TOV characteristics withstand withstand withstand
Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C -40°C...+80°C
Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C -40°C...+60°C
Operating state/fault indication green / red green / red green / red
Cross-sectional area (L/N, L´/N´, N/PE (N)) min. 10 mm2 solid/flexible 10 mm2 solid/flexible 10 mm2 solid/flexible
Cross-sectional area (L/N, N/PE(N)) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible
Cross-sectional area (L´/N´) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20
Capacity 2 mods., DIN 43880 2 mods., DIN 43880 2 mods., DIN 43880
Test standards — VDE, KEMA —
Type of remote signalling contact changeover contact changeover contact changeover contact
Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information
Type DB M 1 150 FM DB M 1 255 FM DB M 1 320 FM
Part No. 961 115 961 125 961 135 NEW
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNbloc® M


DB M spark-gap-based protection module
961 001
MOD 150
961 002
MOD 255
961 003
DB M

DB M

DB M
MOD 320

PU Part
Type
DB M MOD 150
für DB M, 150 V
ÜS-Modul
961 001
pc(s). No.
DB M MOD 255 ÜS-Modul

DB M MOD 150
für DB M, 255 V
DB M MOD 320
für DB M, 320 V
961 002
ÜS-Modul
961 003
1 961 001
DB M MOD 255 1 961 002
DB M MOD 320 1 961 003

www.dehn.de 47
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

Protection Module for DEHNbloc® M POWER SUPPLY SYSTEMS


LIGHTNING CURRENT ARRESTERS – TYPE 1
SPD Type 1 according to EN 61643-11
SPD Class I according to IEC 61643-1

• High discharge capacity due to powerful creep-


age discharge spark gap
• Maximum system availability due to RADAX
Flow follow current limitation
• With module release button for replacing pro-
tection modules without tools
Lightn. Curr. Arr. Type 1

• Operating state / fault indication by green / red


indicator flag in the inspection window
• The plug-in protection module can be replaced
without the need to de-energise and removing
the vertical cover

For protecting low-voltage consumer´s installations against surges and


even direct lightning strikes. For installation in conformity with the light-
DB M MOD ...: Spark-gap-based mains protection module ning protection zones concept at the boundaries from 0A – 1.

The spark-gap-based protection modules for DEHNbloc M devices provide In order to avoid incorrect insertion when replacing the protection mod-
the complete protective circuit including RADAX Flow spark gap and ules, every protection module is mechanically coded.
monitoring circuit for controlling the energy flow.
The spark gap monitoring system and operating state and fault indication Like with all modular protective devices, protection modules are easily
are also integrated in the protection module. replaced without tools by simply pressing the module release button.

961 001 DB M
MOD 150
961 002 DB M
MOD 255
961 003 DB M
MOD 320

DB M MOD 150
961 001
DB M MOD 255
961 002
DB M MOD 320
961 003

Basic circuit diagram DB M MOD ... Dimension drawing DB M MOD ...

DB M MOD ...: Spark-gap-based mains protection module

DB M MOD 150 DB M MOD 255 DB M MOD 320


Max. continuous operating a.c. voltage UC 150 V 255 V 320 V
Lightning impulse current (10/350 μs) Iimp 35 kA 50 kA 25 kA
Follow current extinguishing capability a.c. Ifi 50 kArms 50 kArms 50 kArms
Follow current limitation/Selectivity no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)

Ordering information
Type DB M MOD 150 DB M MOD 255 DB M MOD 320
Part No. 961 001 961 002 961 003
NEW
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

48 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNbloc® Maxi


LIGHTNING CURRENT ARRESTERS – TYPE 1 Coordinated lightning current arrester
SPD Type 1 according to EN 61643-11
SPD Class I according to IEC 61643-1

• Encapsulated RADAX Flow spark gap with high


follow current limitation
• No tripping of 32 A gL/gG fuses up to short-cir-
cuit currents of 50 kArms
• High discharge capacity of lightning currents

Lightn. Curr. Arr. Type 1


• Directly coordinated with DEHNguard ... or V(A)
NH ... surge protective devices without addi-
tional cable length
• ”NH00” versions
• Low voltage protection level

For protecting low voltage consumer’s installations against surges and


even direct lightning strikes. For installation in conformity with the light-
ning protection zones concept at the boundaries from 0A – 1.

DBM NH00 255: Coordinated single-pole lightning current arrester in NH design size 00 with high follow current limitation
for UC = 255 V

The coordinated DEHNbloc Maxi ... lightning current arrester adapts to


every kind of application. Be it in exposed locations or harsh industrial
environments: DEHNbloc Maxi ... always offers the adequate solution. The
single-pole device is coordinated with the approved DEHNguard or V(A)
NH surge arresters of the Red/Line family. Independent of cable lengths
and without the need for additional decoupling coils, the surge protection
concept can be individually adapted to all operating conditions of the
installation.

DEHNbloc Maxi uses the patented technologies of encapsulated creepage


discharge spark gaps and RADAX Flow follow current limitation. There is
no need for installers to worry about safety distances from busbars or
equipment. This arrangement also eliminates the risk of tripped backup
fuses resulting from the lack of selectivity between the protective device
and any overcurrent protection systems that may be in place, ensuring the
highest possible system availability.

DEHNbloc Maxi NH00 255 was specifically designed for use in industrial
distribution boards and supply systems and can be easily installed in size
00 NH fuse holders or NH disconnectors in a compact and space-saving
way.

www.dehn.de 49
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNbloc® Maxi POWER SUPPLY SYSTEMS


900 255 DBM NH00 255

DEHNbloc Maxi NH00 255 LIGHTNING CURRENT ARRESTERS – TYPE 1

NEW DBM NH00 255


900 255
Lightn. Curr. Arr. Type 1

Basic circuit diagram DBM NH00 255 Dimension drawing DBM NH00 255

DBM NH00 255: Coordinated single-pole lightning current arrester in NH design, size 00, with
high follow current limitation for UC = 255 V

DBM NH00 255


SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Max. continuous operating a.c. voltage UC 255 V
Lightning impulse current (10/350 μs) Iimp 25 kA
Nominal discharge current (8/20 μs) In 25 kA
Voltage protection level UP ) 2.5 kV
Follow current extinguishing capability a.c. Ifi 50 kArms
Follow current limitation / Selectivity no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA ) 100 ns
Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG
Temporary overvoltage (TOV) UT 440 V / 5 sec.
TOV characteristics withstand
Operating temperature range (parallel connection) TUP -40°C...+80°C
For mounting on NH fuse holder size 00
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IPX4W

Ordering information
Type DBM NH00 255
Part No. 900 255
Packing unit 1 pc(s).

50 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNbloc® Maxi 440 / 760


LIGHTNING CURRENT ARRESTERS – TYPE 1 Coordinated lightning current arrester
SPD Type 1 according to EN 61643-11
SPD Class I according to IEC 61643-1
for nominal voltages 400 V and 690 V

• Encapsulated non-exhausting spark gap


• High follow current extinguishing capability
and follow current limitation due to RADAX
Flow technology
• Directly coordinated with DEHNguard surge
protective devices without additional cable

Lightn. Curr. Arr. Type 1


length
• Operating state/fault indication by indicator
flag in window

For protecting low-voltage consumer´s installations against surges and


even direct lightning strikes. For installation in conformity with the light-
ning protection zones concept at the boundaries from 0A – 1.

DEHNbloc Maxi 1 440: Coordinated single-pole lightning current arrester with high follow current limitation for
UC = 440 V
DEHNbloc Maxi 1 440 FM: With remote signalling contact for the monitoring system (floating changeover contact)
DEHNbloc Maxi 1 760 FM: Coordinated single-pole lightning current arrester with high follow current limitation for
UC = 760 V; with remote signalling contact for the monitoring system (floating changeover con-
tact)

The coordinated DEHNbloc Maxi 440 and 760 lightning current arresters devices even if no operating current is present. Apart from the standard
were specifically designed for higher system voltages. visual green and red indication, DEHNbloc Maxi 1 ... FM features a three-
This allows to reliably protect a variety of industrial applications against pole remote signalling terminal. With its floating changeover contact, the
direct and indirect lightning currents. remote signal can be used as a break or make contact according to the
Be it in a wind turbine or isolated low-voltage installation of an industri- particular circuit concept.
al enterprise, DEHNbloc Maxi devices excellently meet all requirements.

Both the design of the protective circuit and the enclosure specifically
designed for this type of devices are particularly adapted to high system
voltages.
The core of the coordinated DEHNbloc Maxi 440 and 760 lightning cur-
rent arresters is the approved RADAX Flow technology. Their capability of
considerably limiting mains-frequency follow currents and extinguishing
them within a matter of milliseconds places these devices in a special
position.
The patented RADAX Flow follow current limitation allows a follow cur-
rent breaking selectivity, even for small-sized fuses in installations.
Its capability to discharge lightning currents without damage and to sup-
press mains follow currents without tripping of upstream overcurrent pro-
tective devices ensures high availability of electrical installations.
The operating state/fault indication of the coordinated lightning current
arresters immediately provides information on the availability of the

www.dehn.de 51
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNbloc® Maxi 440 / 760 POWER SUPPLY SYSTEMS


961 140 DBM 1 440
961 145 DBM 1 440 FM

DEHNbloc Maxi 1 440 (FM) LIGHTNING CURRENT ARRESTERS – TYPE 1


L L´
DBM 1 440
961 140
DBM 1 440 FM
961 145

12
11
14

( 2 mods.)
Lightn. Curr. Arr. Type 1

N/PEN

Basic circuit diagram DBM 1 440 FM Dimension drawing DBM 1 440 FM

DBM 1 440 (FM): Coordinated, single-pole lightning current arrester with high follow current lim-
itation for UC = 440 V

DBM 1 440 DBM 1 440 FM


SPD according to EN 61643-11 Type 1 Type 1
SPD according to IEC 61643-1 Class I Class I
Max. continuous operating a.c. voltage UC 440 V 440 V
Lightning impulse current (10/350 μs) Iimp 35 kA 35 kA
Nominal discharge current (8/20 μs) In 35 kA 35 kA
Voltage protection level UP ) 2.5 kV ) 2.5 kV
Follow current extinguishing capability a.c. Ifi 50 kArms 50 kArms
Follow current limitation / Selectivity no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.) no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA ) 100 ns ) 100 ns
Max. backup fuse (L) up to IK = 50 kArms (ta ) 0.2 s) 500 A gL/gG 500 A gL/gG
Max. backup fuse (L) up to IK = 50 kArms (ta ) 5 s) 250 A gL/gG 250 A gL/gG
Max. backup fuse (L) for IK > 50 kArms 160 A gL/gG 160 A gL/gG
Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG
Temporary overvoltage (TOV) UT 690 V / 5 sec. 690 V / 5 sec.
TOV characteristics withstand withstand
Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C
Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C
Operating state/fault indication green / red green / red
Cross-sectional area (L, L´, N/PEN) min. 10 mm2 solid/flexible 10 mm2 solid/flexible
Cross-sectional area (L, N/PEN) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible
Cross-sectional area (L´) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 2 mods., DIN 43880 2 mods., DIN 43880
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DBM 1 440 DBM 1 440 FM
Part No. 961 140 961 145
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNbloc® Maxi 440 / 760 Accessory Part for DEHNbloc® Maxi 440 / 760
EB DG, 3-pole, single-phase 900 411
1000 1 3
EB DG

Earthing Clip, 4-pole, single-phase 900 417 EB 1 4 9

Earthing clip for earth-side jumpering of e.g. 3 Type 1 SPDs in a 2- Earthing clip for earth-side jumpering of e.g. 4 Type 1 SPDs in a 2-
module enclosure with multifunctional terminal EB DG 1000 1 3
900 411
module enclosure with multifunctional terminal EB 1 4 9
900 417

PU Part PU Part
Type Dimension Terminal pc(s). No. Type Dimension Terminal pc(s). No.
EB DG 1000 1 3 34 x 112 x 3 mm up to 25 mm2 1 900 411 EB 1 4 9 34 x 148 x 3 mm up to 25 mm2 1 900 417

52 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNbloc® Maxi 440 / 760


961 175 DBM 1 760 FM

LIGHTNING CURRENT ARRESTERS – TYPE 1 DEHNbloc Maxi 1 760 FM


L
DBM 1 760 FM
961 175

12
11
14
9

( 2 mods.)

Lightn. Curr. Arr. Type 1


Dimension drawing DBM 1 760 FM Basic circuit diagram DBM 1 760 FM

DBM 1 760 FM: Single-pole, coordinated lightning current arrester with high follow current
limitation for UC = 760 V

DBM 1 760 FM
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Max. continuous operating a.c. voltage UC 760 V
Lightning impulse current (10/350 μs) Iimp 25 kA
Nominal discharge current (8/20 μs) In 25 kA
Voltage protection level UP ) 4 kV
Follow current extinguishing capability a.c. Ifi 25 kArms
Follow current limitation / Selectivity no tripping of a 32 A gL/gG fuse up to 25 kArms (prosp.)
Response time tA ) 100 ns
Max. backup fuse (L) up to IK = 25 kArms (ta ) 5 s) 250 A gL/gG
Max. backup fuse (L) up to IK > 25 kArms 100 A gL/gG
Max. backup fuse (L-L´) 125 A gL/gG
Short-circuit withstand capability for max. mains-side overcurrent protection 25 kArms
Temporary overvoltage (TOV) UT 1000 V / 5 sec.
TOV characteristics withstand
Operating temperature range (parallel connection) TUP -40°C...+80°C
Operating temperature range (series connection) TUS -40°C...+60°C
Operating state/fault indication green / red
Cross-sectional area (L, L´, 9) min. 10 mm2 solid/flexible
Cross-sectional area (L, 9) max. 50 mm2 stranded/35 mm2 flexible
Cross-sectional area (L´) max. 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IP 20
Capacity 2 mods., DIN 43880
Type of remote signalling contact changeover contact
Switching capacity a.c. 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible

Ordering information
Type DBM 1 760 FM
Part No. 961 175
Packing unit 1 pc(s).

Accessory Part for DEHNbloc® Maxi 440 / 760 Accessory Part for DEHNbloc® Maxi 440 / 760
Earthing Clip, 4-pole, single-phase 900 411
1000 1 3
EB DG

EB DG, 3-pole, single-phase 900 417 EB 1 4 9

Earthing clip for earth-side jumpering of e.g. 4 Type 1 SPDs in a 2- Earthing clip for earth-side jumpering of e.g. 3 Type 1 SPDs in a 2-
module enclosure with multifunctional terminal EB DG 1000 1 3
Erdungsbügel 1-phasig, 3-polig, 8 TE 900 411
module enclosure with multifunctional terminal EB 1 4 9
Erdungsbügel 1-phasig, 4-polig, 9 TE 900 417

PU Part PU Part
Type Dimension Terminal pc(s). No. Type Dimension Terminal pc(s). No.
EB 1 4 9 34 x 148 x 3 mm up to 25 mm2 1 900 417 EB DG 1000 1 3 34 x 112 x 3 mm up to 25 mm2 1 900 411

www.dehn.de 53
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNbloc® Maxi S POWER SUPPLY SYSTEMS


Coordinated lightning LIGHTNING CURRENT ARRESTERS – TYPE 1
current arrester for busbars SPD Type 1 according to EN 61643-11
SPD Class I according to IEC 61643-1

• Combination of spark gap and integrated back-


up fuse
• For mounting directly onto PEN/N busbars
• Low voltage protection level UP ) 2.5 kV
(80 cm connecting cable included)
Lightn. Curr. Arr. Type 1

• Directly coordinated with DEHNguard surge


protective device without additional cable
length
• Short-circuit withstand capability of 100 kArms
(220 kApeak)
• High follow current extinguishing capability
and follow current limitation due to RADAX
Flow technology
• High lightning current discharge capacity
• With optical-fibre interface for monitoring the For protecting low voltage consumer´s installations against surges. For
installation in conformity with the lightning protection zones concept at
SPD the boundaries from 0A – 1.

DEHNbloc Maxi 1 255 S: Coordinated lightning current arrester with integrated backup fuse for busbars

DEHNbloc Maxi S allows to better integrate surge protective devices into DEHNbloc Maxi S also features the patented RADAX Flow follow current
application environments of a low-voltage switchgear installation or dis- limitation thus allowing selectivity, even for small-sized fuses.
tribution board. The capability of conducting lightning impulse currents without damage
Due to its unique mechanical design, the coordinated DEHNbloc Maxi S and suppressing mains follow currents without tripping upstream over-
lightning current arrester can be mounted directly onto the PEN/N busbar current protective devices ensures the availability of the switchgear
of a switchgear installation without requiring additional adapters. installation in case of a lightning strike and considerably reduces the risk
With the backup fuse integrated into the device, no further separate back- of arc formation in the installation.
up fuses need to be installed. Combined with the DEHNsignal remote signalling system, the availability
Installing the DEHNbloc Maxi S devices directly into the terminal panel of of DEHNbloc Maxi S devices can be monitored at any time.
the switchgear installation upstream of the circuit breaker ensures short An optical fibre transmission to the DEHNsignal E 3 receiver module,
cable lengths of the SPDs and a low voltage protection level for the instal- which is easy to perform, ensures
lation. safe electrical isolation between
With a discharge capacity of 25 kA (10/350 μs) DEHNbloc Maxi S fulfils the power circuit and the remote
the most stringent requirements of national and international lightning signalling circuit.
protection standards for all three-phase current applications in TN and TT
systems.
For “3+1“ circuits, DEHNgap Maxi S provides a powerful creepage dis-
charge spark gap with a discharge capacity of 100 kA (10/350 μs).

*) DEHbloc Maxi S
DBM 1 255 S main circuit bre main circuit bre
aker aker
**) DEHNgap Maxi S
DGPM 1 255 S TN-C
optical fibre optical fibr DSI E 3
L1
LWL DSI plastic TT / TN-S
DSI E 3 L1
LWL DSI plastice power supply
L2 L3 max. 6 m power supply L2 L3 max. 6 m
S N L
S N L *) DEHbloc Maxi S
DBM 1 255 S
without with
wire wire
**) jumper N L
*) *) jumper
N L *) *) S/N (PEN)
N busbar *) S/N *)
PEN busbar

N' N L
N' N L

PE busbar DEHNgap Maxi S


DGPM 1 255 S equipoten
tial bond
ing
power supply
equipoten F 230 V~ F power
L max. 16 A gl/gG L 230 V~supply
tial bond
ing
N (C 16 A) ! N max. 16 A gl/g
! All three optical fibres
(C 16 A)
G

All three optical fibres must be connected!


must be connected!

Application in a TT / TN-S system Application in a TN-C system

54 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNbloc® Maxi S


900 220 DBM 1 255 S

LIGHTNING CURRENT ARRESTERS – TYPE 1 DEHNbloc Maxi 1 255 S


DBM 1 255 S
900 220

optical fibre

N/PEN

Lightn. Curr. Arr. Type 1


Dimension drawing DBM 1 255 S Basic circuit diagram DBM 1 255 S

DBM 1 255 S: Coordinated single-pole lightning current arrester with integrated backup fuse for
busbars

DBM 1 255 S
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Max. continuous operating a.c. voltage UC 255 V
Lightning impulse current (10/350 μs) Iimp 25 kA
Nominal discharge current (8/20 μs) In 25 kA
Voltage protection level UP ) 2.5 kV (includes 80 cm connecting cable)
Follow current extinguishing capability a.c. Ifi 50 kArms
Follow current limitation / Selectivity no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA ) 100 ns
Short-circuit withstand capability 100 kArms (220 kApeak)
Temporary overvoltage (TOV) UT 335 V / 5 sec.
TOV characteristics withstand
Operating temperature range TU -40°C...+80°C
For mounting on PEN / N busbar min. 35 mm2
Connection type cable lug min. 35 mm2/max. 50 mm2
Enclosure material thermoplastic, red, UL 94 V-0
Dimension (W x H x D) 72 x 89 x 100 mm
Operating state indication by optical fibres via DSI E 3

Ordering information
Type DBM 1 255 S
Part No. 900 220
Packing unit 1 pc(s).

Accessory Part for DEHNbloc® Maxi S Accessory Part for DEHNbloc® Maxi S
LWL ST DSI
910 641
DSI
LWL ST

DEHNsignal E 3
910 631 DSI E 3

Plug for plastic optical fibres DSI E 3: Receiver module for optical fibre transmission for selective
LWL ST DSI
Optical Fibre
Plug for
910 641
operating state indication / centralised fault indication of 3 coordina-
DSI E 3
910 631

PU Part
Type Diameter pc(s). No.
ted DEHNbloc Maxi S and, if required, DEHNgap Maxi S lightning cur-
LWL ST DSI 2.2 mm 1 910 641
rent arresters in 5-conductor systems
PU Part
Type pc(s). No.
LWL DSI 18M
910 642
18M
LWL DSI

DSI E 3 1 910 631


18 metres of plastic optical fibre, preferably for use with DEHNbloc
Maxi S
LWL DSI 18M
910 642

PU Part
Type Diameter Length pc(s). No.
LWL DSI 18M 2.2 mm 18 m 1 910 642

www.dehn.de 55
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNsignal POWER SUPPLY SYSTEMS


Remote signalling and receiver module ACCESSORIES FOR SPDs TYPE 1
EN 61010-1; EN 61010-1/A2

• Operating state indication of the surge protec-


tive device connected to it
• Indication of phase failures
• Floating changeover contact
• Selective operating state indication
Lightn. Curr. Arr. Type 1

• Centralised fault indication

Receiver module for optical fibre transmission for DEHNbloc Maxi S and
DEHNgap Maxi S protective devices with floating changeover contact.

DEHNsignal E 3: Receiver module for optical fibre transmission for selective operating state indication / centralised fault
indication of three coordinated lightning current arresters of type DEHNbloc Maxi S and DEHNgap Maxi S,
if any, in 5-conductor systems

The receiver module for opti- Considering the special installation environment of the surge protective
cal fibre transmission of type devices in a switchgear installation, communication via optical fibre cable
DEHNsignal E 3 transmits between the protective devices and the DEHNsignal E 3 receiver module
remote signals of DEHNbloc is a considerable benefit in terms of safety.
Maxi S and DEHNgap Maxi S The readiness for operation of the individual SPDs is transmitted to the
surge protective devices. DEHNsignal E 3 receiver module in the form of a visual signal via EMC-
safe plastic optical fibre cables. The visual signals are evaluated in the
The receiver module for opti- DEHNsignal E 3 receiver module and are converted into an electrical sig-
cal fibre transmission of type nal. The signal of the operating states can be directly read out at the
DEHNsignal E 3 is particular- DEHNsignal E 3 receiver module or is provided via a floating changeover
ly adapted to the place of contact. The DEHNsignal E 3 receiver module features a green indicator
installation of the coordinat- lamp to check its operating state. In addition to the function indication,
ed DEHNbloc Maxi S and the three indicator lamps of the selective operating state indication show
DEHNgap Maxi S surge pro- that the assigned protective devices are ready for operation. The receiver
tective devices. module indicates if a protective device of a phase fails. The surge protec-
The receiver module for opti- tive devices and the DEHNsignal E 3 receiver module are easily connect-
cal fibre transmission is able ed via optical fibre cable by using the accessory parts described.
to telemonitor three DEHN-
bloc Maxi S SPDs and, if
required, the N-PE protective
circuit via optical fibre cables.

56 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNsignal


910 631 DSI E 3

ACCESSORIES FOR SPDs TYPE 1 DEHNsignal E 3

DSI E 3
red
910 631
L1
LWL 1
red
L2
LWL 2
red
L3
LWL 3
signal
evaluation green
L 12
S N L 14
N

S 11

Note:
Change of contacts in case of present

Lightn. Curr. Arr. Type 1


voltage and optical fibre signal!

Dimension drawing DSI E 3 Basic circuit diagram DSI E 3

DSI E 3: Receiver module for optical fibre transmission for selective operating state indication /
centralised fault indication of 3 coordinated DEHNbloc Maxi S and, if required, DEHNgap
Maxi S lightning current arresters in 5-conductor systems

DSI E 3
Supply a.c. voltage UN 230 V
Power input P < 550 mW
Backup fuse for supply voltage 16 A gL/gG or C 16 A
Operating temperature range -40°C...+80°C
Signal input 3x via optical fibre plug-in system (LWL ST DSI)
Operating state indication green LED
Selective operating state indication 3 x red LEDs (L1, L2, L3)
For mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IP 20
Capacity 1.5 mods., DIN 43880
Type of remote signalling contact floating changeover contact
Switching capacity a.c. 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area min. 0.5 mm2 solid/flexible; max. 4 mm2 solid/flexible
Max. distance with LWL DSI 18M 6m
Test standards EN 61010-1:1993 and EN 61010-1/A2:1995

Ordering information
Type DSI E 3
Part No. 910 631
Packing unit 1 pc(s).

Accessory Part for DEHNsignal Accessory Part for DEHNsignal


LWL ST DSI
910 641
DSI
LWL ST

LWL DSI 18M


910 642
18M
LWL DSI

Plug for plastic optical fibres 18 metres of plastic optical fibre, preferably for use with DEHNbloc
Maxi S
LWL ST DSI Plug for LWL DSI 18M
Optical Fibre 910 641 910 642

PU Part
Type Diameter pc(s). No. PU Part
LWL ST DSI 2.2 mm 1 910 641 Type Diameter Length pc(s). No.
LWL DSI 18M 2.2 mm 18 m 1 910 642

www.dehn.de 57
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNbloc® POWER SUPPLY SYSTEMS


Lightning current arrester LIGHTNING CURRENT ARRESTERS – TYPE 1
SPD Type 1 according to EN 61643-11
SPD Class I according to IEC 61643-1

• Encapsulated, non-exhausting creepage dis-


charge spark gap
• DEHNbloc ... H: RADAX Flow spark gap technol-
ogy with high follow current limitation
• Energy-coordinated within the Red/Line pro-
duct family
Lightn. Curr. Arr. Type 1

• High insulation resistance allows installation


even upstream of meter panels
• Multifunctional terminal for connecting con-
ductors and busbars
• Single-pole and three-pole version (lightning
impulse currents up to 100 kA according to the
system configuration)
• ”NH00” version also available
For protecting low voltage consumer’s installations against surges and
even direct lightning strikes. For installation in conformity with the light-
ning protection zones concept at the boundaries from 0A – 1.

DEHNbloc 1 255 H: Single-pole lightning current arrester with high follow current limitation
DEHNbloc 3 255 H: Three-pole lightning current arrester with high follow current limitation
DEHNbloc NH00 H: Lightning current arrester, NH 00 design, with high follow current limitation
DEHNbloc 1 440: Single-pole lightning current arrester for UC = 440 V

The spark gaps of the DEHNbloc lightning current arresters allow for a But the concept of the DEHNbloc H family also stands out due to other
compact structure of low-voltage distribution boards. Using pressurised product features: With its phase-side and earth-side double terminals, the
encapsulated creepage discharge spark gaps, safety distances from elec- single-pole device of type DEHNbloc 1 255 H offers a wide range of appli-
trical busbars and special flameproof enclosures are not required. cation possibilities.

With a lightning current discharge capacity up to 50 kA (10/350 μs) per DEHNbloc incorporates double terminals which are suitable for all con-
pole, DEHNbloc devices fulfil the most stringent requirements of national ductors, allowing a series connection of three-pole DEHNbloc 3 255 H
and international lightning protection and application standards. SPDs in a space- and cost-saving way according to IEC 60364-5-53
requirements for nominal currents up to 125 A.
The consistent development of the integration concept has made the
DEHNbloc devices even more powerful: With the product designation For application with other DIN rail mounted devices, multifunctional ter-
DEHNbloc ... H, the groundbreaking RADAX Flow spark gap technology minals are ideally suited for providing connection for conductors and bus-
for follow current extinction and follow current limitation was integrated bars.
into the DEHNbloc family.
DEHNbloc NH00 255 H was
The RADAX Flow technology prevents operational interruptions caused by especially developed for use
tripping conductor protection due to responding SPDs. In times where all in industrial distribution
systems increasingly depend on a functioning electrical infrastructure, this boards and in power supply
is an indispensable product feature. Due to the patented RADAX Flow systems. It can be installed
principle, even the amplitudes of short circuits in installations up to 50 into size 00 NH fuse holders
kArms can be limited to approx. 500 A and extinguished after approx. 5 ms. or NH disconnectors accor-
This performance allows a breaking selectivity of the SPD even in case of ding to the particular sys-
small-sized fuses. tem.

DEHNbloc 1 440 is suitable


for rated voltages of 440 V.

DB NH00 255 H in a busbar connection


panel of a meter system

58 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNbloc®


900 222 DB 1 255
H

LIGHTNING CURRENT ARRESTERS – TYPE 1 DEHNbloc ... 255 H


900 120 DB 3 255
H

DB 1 255 H
DEHNbloc/1 900 222
L L´ L1 L2 L3
DB 3 255 H
DEHNbloc/3 900 120

N´/PEN N/PEN N/PEN

Lightn. Curr. Arr. Type 1


Dimension drawing DB 1 255 H / DB 3 255 H Basic circuit diagram DB 1 255 H / DB 3 255 H

DB ... 255 H: Single-pole and three-pole lightning current arrester with high follow current limita-
tion

DB 1 255 H DB 3 255 H
SPD according to EN 61643-11 Type 1 Type 1
SPD according to IEC 61643-1 Class I Class I
Nominal a.c. voltage UN 230 V 230/400 V
Max. continuous operating a.c. voltage UC 255 V 255 V
Lightning impulse current (10/350 μs) Iimp 50 kA —
Lightning impulse current (10/350 μs) [L-N/PEN] Iimp — 50 kA
Lightning impulse current (10/350 μs) [L1+L2+L3-N/PEN] Itotal — 100 kA
Nominal discharge current (8/20 μs) In 50 kA 50 / 100 kA
Voltage protection level UP ) 4 kV ) 4 kV
Follow current extinguishing capability a.c. Ifi 50 kArms 50 kArms
Follow current limitation / Selectivity no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.) no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA ) 100 ns ) 100 ns
Max. backup fuse up to IK = 50 kArms (ta ) 0.2 s) 500 A gL/gG 500 A gL/gG
Max. backup fuse up to IK = 50 kArms (ta ) 5 s) 315 A gL/gG 315 A gL/gG
Max. backup fuse for IK > 50 kArms 200 A gL/gG 200 A gL/gG
Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG
Temporary overvoltage (TOV) UT 335 V / 5 sec. 335 V / 5 sec.
TOV characteristics withstand withstand
Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C
Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C
Cross-sectional area (L, L´, N/PEN, N´/PEN) min. 10 mm2 solid/flexible —
Cross-sectional area (L, N/PEN) max. 50 mm2 stranded/35 mm2 flexible —
Cross-sectional area (L´, N´/PEN) max. 35 mm2 stranded/25 mm2 flexible —
Cross-sectional area (L1, L1´, L2, L2´, L3, L3´, N/PEN, N´/PEN) — 10 mm2 solid/flexible
Cross-sectional area (L1, L2, L3, N/PEN) — 50 mm2 stranded/35 mm2 flexible
Cross-sectional area (L1´, L2´, L3´, N´/PEN) — 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 2 mods., DIN 43880 6 mods., DIN 43880
Approvals, Certifications KEMA KEMA

Ordering information
Type DB 1 255 H DB 3 255 H
Part No. 900 222 900 120
Packing unit 1 pc(s). 1 pc(s).

www.dehn.de 59
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNbloc® POWER SUPPLY SYSTEMS


900 273 DB NH00 255 H

DEHNbloc NH00 255 H LIGHTNING CURRENT ARRESTERS – TYPE 1

DB NH00 255 H
900 273
Lightn. Curr. Arr. Type 1

Basic circuit diagram DB NH00 255 H Dimension drawing DB NH00 255 H

DB NH00 255 H: Single-pole lightning current arrester in NH design, size 00, with high follow cur-
rent limitation

DB NH00 255 H
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Max. continuous operating a.c. voltage UC 255 V
Lightning impulse current (10/350 μs) Iimp 25 kA
Nominal discharge current (8/20 μs) In 25 kA
Voltage protection level UP ) 4 kV
Follow current extinguishing capability a.c. Ifi 50 kArms
Follow current limitation / Selectivity no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA ) 100 ns
Max. backup fuse up to IK = 50 kArms (ta ) 0.2 s) 315 A gL/gG
Max. backup fuse up to IK = 50 kArms (ta ) 5 s) 200 A gL/gG
Max. backup fuse for IK > 50 kArms 125 A gL/gG
Temporary overvoltage (TOV) UT 440 V / 5 sec.
TOV characteristics withstand
Operating temperature range TU -40°C...+80°C
For mounting on NH fuse holder, size 00
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IPX4W

Ordering information
Type DB NH00 255 H
Part No. 900 273
Packing unit 1 pc(s).

60 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNbloc®


900 159 DB 1 440

LIGHTNING CURRENT ARRESTERS – TYPE 1 DEHNbloc 1 440

DB 1 440 DEHNbloc/1
900 159

Lightn. Curr. Arr. Type 1


Dimension drawing DB 1 440 Basic circuit diagram DB 1 440

DB 1 440: Single-pole lightning current arrester with high discharge capacity for UC = 440 V

DB 1 440
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Max. continuous operating a.c. voltage UC 440 V
Lightning impulse current (10/350 μs) Iimp 50 kA
Nominal discharge current (8/20 μs) In 50 kA
Voltage protection level UP ) 4 kV
Follow current extinguishing capability a.c. Ifi 1.5 kArms
Response time tA ) 100 ns
Max. mains-side overcurrent protection 160 A gL/gG
Short-circuit withstand capability for max. mains-side overcurrent protection 50 kArms
Temporary overvoltage (TOV) TN system UT 580 V / 5 sec.
Temporary overvoltage (TOV) IT system UT 1200 V + U0 / 200 ms
TOV characteristics withstand
Operating temperature range TU -40°C...+80°C
Cross-sectional area (min.) 10 mm2 solid/flexible
Cross-sectional area (max.) 50 mm2 stranded/35 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IP 20
Capacity 2 mods., DIN 43880

Ordering information
Type DB 1 440
Part No. 900 159
Packing unit 1 pc(s).

www.dehn.de 61
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS


LIGHTNING CURRENT ARRESTERS – TYPE 1
Lightn. Curr. Arr. Type 1

62 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNgap


N-PE LIGHTNING CURRENT ARRESTERS N-PE lightning current arrester
SPD Type 1 according to EN 61643-11
SPD Class 1 according to IEC 61643-1

• Discharge capacity up to 100 kA (10/350 μs)


• Total current arrester specifically designed for
installation in ”3+1” and ”1+1” circuits of TT
systems according to IEC 60364-5-53 between
neutral conductor N and protective earth con-
ductor PE
• Creepage discharge spark gap technology
• DEHNgap M model available with operating
state/fault indication in the inspection window

N-PE Arresters Type 1


For protecting low voltage consumer’s installations against surges and
even direct lightning strikes. For installation in conformity with the light-
ning protection zones concept at the boundaries from 0A – 1 with 3+1 cir-
cuits.

DEHNgap M 255 (FM): Coordinated, single-pole, modular N-PE lightning current arrester
DEHNgap Maxi 1 255 S: Coordinated, single-pole N-PE lightning current arrester for busbars
DEHNgap BN 255: Single-pole N-PE lightning current arrester
DEHNgap B NH00 N 255: Single-pole N-PE lightning current arrester in NH design
DEHNgap Maxi 440 (FM): Coordinated, single-pole N-PE lightning current arrester for UC = 440 V a.c.

Being total current arresters between neutral and protective conductors connecting conductors
in TT systems, the single-pole N-PE lightning current arresters DEHNgap and busbars, allowing
M, DEHNgap Maxi, DEHNgap Maxi S, DEHNgap BN and DEHNgap B NH wiring with other DIN
are designed to meet the requirements for the protection of persons and rail mounted terminals.
material assets in ”3+1 circuits”. The creepage discharge spark gaps were The functional Red/Line
specifically developed to meet this challenge. With a discharge capacity design of DEHNgap M
up to 100 kA (10/350 μs) they fulfil the highest requirements specified in offers many features for
national and international lightning protection standards. The leakage- safe and easy handling.
current-free spark gap design allows the devices to be used upstream of The mechanical operat-
the meter according to national regulations (e.g. German VDN Directive). ing state and fault indi-
Being coordinated N-PE lightning current arresters, DEHNgap M, cation, for example,
DEHNgap Maxi and DEHNgap Maxi S are different from other total cur- stands for fulfilling the high safety requirements, just like the module lock-
rent arresters. Due to their response performance, they can be coordinat- ing device which is unique for use with surge arresters. It fixes the protec-
ed directly with N-PE surge arresters of the DEHNguard M family and tion modules and the base part of the device firmly in place. Neither vibra-
DEHNgap S surge arresters without additional decoupling coil. If lightning tion nor shock during transport nor the enormous electromagnetic forces
current and surge arresters have to be installed together at one site, no of lightning discharge can loosen the protection modules. Nevertheless,
additional DEHNgap S is required thanks to the low voltage protection they can be easily replaced without tools by pressing the user-friendly
levels of DEHNgap M and DEHNgap Maxi. module release button of the protection module. Each protection module
The design and installation of DEHNgap Maxi S are adapted to the spe- is mechanically coded to avoid incorrect insertion by the installer or user.
cial characteristics of low voltage switchgear installations and entirely Apart from the standard visual indication of DEHNgap M, DEHNgap M ...
complement the application of DEHNbloc Maxi S. FM features a three-pole remote signalling terminal. With its floating
DEHNgap B NH was specifically developed for industrial plants as well as changeover contact, the remote signal can be used as a break or make
for supply systems. This SPD can be easily integrated into existing size 00 contact according to the particular circuit concept.
NH fuse holders. The multifunctional terminals of the DIN rail mounted
devices DEHNgap M, DEHNgap Maxi and DEHNgap BN are suitable for

www.dehn.de 63
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNgap POWER SUPPLY SYSTEMS


961 101 DGP M
255

DEHNgap M 255 (FM) N-PE LIGHTNING CURRENT ARRESTERS


961 105 DGP M
255 FM

PE
DGP M 255
PE 9
961 101
DGP M 255 FM
961 105

12
11
14 NPE
N

(2 mods.)

Basic circuit diagram DGP M 255 FM Dimension drawing DGP M 255 FM

DGP M 255 (FM): Single-pole, modular, coordinated N-PE lightning current arrester for UC = 255 V;
also available with remote signalling contact for the monitoring system (floating
changeover contact)
N-PE Arresters Type 1

DGP M 255 DGP M 255 FM


SPD according to EN 61643-11 Type 1 Type 1
SPD according to IEC 61643-1 Class I Class I
Max. continuous operating a.c. voltage UC 255 V 255 V
Lightning impulse current (10/350 μs) Iimp 100 kA 100 kA
Nominal discharge current (8/20 μs) In 100 kA 100 kA
Voltage protection level UP ) 1.5 kV ) 1.5 kV
Follow current extinguishing capability a.c. Ifi 100 Arms 100 Arms
Response time tA ) 100 ns ) 100 ns
Temporary overvoltage (TOV) 1200 V / 200 ms 1200 V / 200 ms
TOV characteristics withstand withstand
Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C
Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C
Operating state/fault indication green / red green / red
Cross-sectional area (N, PE, 9) min. 10 mm2 solid/flexible 10 mm2 solid/flexible
Cross-sectional area (N, PE) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible
Cross-sectional area (9) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 2 mods., DIN 43880 2 mods., DIN 43880
Approvals, Certifications VDE, KEMA VDE, KEMA
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DGP M 255 DGP M 255 FM
Part No. 961 101 961 105
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNgap


961 010
MOD 255
DGP M

DGP M – 100 kA N-PE spark-gap-based protection


module
DGP M MOD ...: 100 kA N-PE spark-gap-based protection module for
DGP M MOD 255
961 010

use with all modular DEHNgap M devices


PU Part
Type pc(s). No.
DGP M MOD 255 1 961 010

64 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNgap


900 050 DGPM 1 255 S

N-PE LIGHTNING CURRENT ARRESTERS DEHNgap Maxi 1 255 S


PE
DGPM 1 255 S
900 050

S
NPE
(DSI E 3)

N/PEN

Dimension drawing DGPM 1 255 S Basic circuit diagram DGPM 1 255 S

DGPM 1 255 S: Coordinated single-pole N-PE lightning current arrester for busbars

N-PE Arresters Type 1


DGPM 1 255 S
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Max. continuous operating a.c. voltage UC 255 V
Lightning impulse current (10/350 μs) Iimp 100 kA
Nominal discharge current (8/20 μs) In 100 kA
Voltage protection level UP ) 2.5 kV (includes 80 cm connecting cable)
Follow current extinguishing capability a.c. Ifi 100 Arms
Response time tA ) 100 ns
Temporary overvoltage (TOV) 1200 V / 200 ms
TOV characteristics withstand
Operating temperature range TU -40°C...+80°C
For mounting on N busbar min. 35 mm2
Connection via cable lug min. 35 mm2/max. 50 mm2
Operating state control via DEHNsignal DSI E 3
Connection for DSI E 3 (S) min. 1 mm2 solid/flexible
Connection for DSI E 3 (S) max. 2.5 mm2 solid/flexible
Enclosure material thermoplastic, red, UL 94 V-0
Dimension (W x H x D) 72 x 89 x 100 mm

Ordering information
Type DGPM 1 255 S
Part No. 900 050
Packing unit 1 pc(s).

www.dehn.de 65
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNgap POWER SUPPLY SYSTEMS


900 132 DGP BN
255

DEHNgap BN 255 N-PE LIGHTNING CURRENT ARRESTERS

DGP BN 255 DEHNgap


B/n 900 132

Basic circuit diagram DGP BN 255 Dimension drawing DGP BN 255

DGP BN 255: Single-pole N-PE lightning current arrester


N-PE Arresters Type 1

DGP BN 255
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Max. continuous operating a.c. voltage UC 255 V
Lightning impulse current (10/350 μs) Iimp 100 kA
Nominal discharge current (8/20 μs) In 100 kA
Voltage protection level UP ) 4 kV
Follow current extinguishing capability a.c. Ifi 100 Arms
Response time tA ) 100 ns
Temporary overvoltage (TOV) 1200 V / 200 ms
TOV characteristics withstand
Operating temperature range TU -40°C...+80°C
Operating state/fault indication green / red
Cross-sectional area (min.) 10 mm2 solid/flexible
Cross-sectional area (max.) 50 mm2 stranded/35 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IP 20
Capacity 2 mods., DIN 43880

Ordering information
Type DGP BN 255
Part No. 900 132
Packing unit 1 pc(s).

66 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNgap


900 269 DGP B
NH00 N 255

N-PE LIGHTNING CURRENT ARRESTERS DEHNgap B NH00

DGP B NH00 N 255 DEHNgap


B/NH/n 900 269

Dimension drawing DGP B NH00 N 255 Basic circuit diagram DGP B NH00 N 255

DGP B NH00 N 255: Single-pole N-PE lightning current arrester, NH design, size 00

N-PE Arresters Type 1


DGP B NH00 N 255
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Max. continuous operating a.c. voltage UC 255 V
Lightning impulse current (10/350 μs) Iimp 50 kA
Nominal discharge current (8/20 μs) In 50 kA
Voltage protection level UP ) 4 kV
Follow current extinguishing capability a.c. Ifi 100 Arms
Response time tA ) 100 ns
Temporary overvoltage (TOV) 1200 V / 200 ms
TOV characteristics withstand
Operating temperature range TU -40°C...+80°C
For mounting on NH fuse holder, size 00
Enclosure material thermoplastic, red, UL 94 V-0

Ordering information
Type DGP B NH00 N 255
Part No. 900 269
Packing unit 1 pc(s).

www.dehn.de 67
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNgap POWER SUPPLY SYSTEMS


961 160 DGPM
440

DEHNgap Maxi 440 (FM) N-PE LIGHTNING CURRENT ARRESTERS


961 165 DGPM
440 FM

PE PE 9

DGPM 440
961 160
DGPM 440 FM
961 165

12
11
14
N

( 2 mods.)

Basic circuit diagram DGPM 440 FM Dimension drawing DGPM 440

DGPM 440 (FM): Coordinated, single-pole N-PE lightning current arrester for UC = 440 V
N-PE Arresters Type 1

DGPM 440 DGPM 440 FM


SPD according to EN 61643-11 Type 1 Type 1
SPD according to IEC 61643-1 Class I Class I
Max. continuous operating a.c. voltage UC 440 V 440 V
Lightning impulse current (10/350 μs) Iimp 100 kA 100 kA
Nominal discharge current (8/20 μs) In 100 kA 100 kA
Voltage protection level UP ) 2.5 kV ) 2.5 kV
Follow current extinguishing capability a.c. Ifi 100 Arms 100 Arms
Response time tA ) 100 ns ) 100 ns
Temporary overvoltage (TOV) 1200 V / 200 ms 1200 V / 200 ms
TOV characteristics withstand withstand
Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C
Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C
Operating state/fault indication green / red green / red
Cross-sectional area (N, PE, 9) min. 10 mm2 solid/flexible 10 mm2 solid/flexible
Cross-sectional area (N, PE) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible
Cross-sectional area (9) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 2 mods., DIN 43880 2 mods., DIN 43880
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DGPM 440 DGPM 440 FM
Part No. 961 160 961 165
Packing unit 1 pc(s). 1 pc(s).

68 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® modular CI


SURGE ARRESTERS – TYPE 2 Modular surge arrester
SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1
with integrated backup fuse

• Arrester backup fuse integrated in the protec-


tion module
• Prewired complete unit consisting of a base
part and plug-in protection modules
• Energy coordination within the Red/Line pro-
duct family
• High discharge capacity
• High reliability due to ”Thermo Dynamic
Control” SPD monitoring device
• Easy replacement of protection modules with-
out tools due to module locking system with
module release button

For protecting low-voltage consumer’s installations against surges. For


use in conformity with the lightning protection zones concept at the
boundaries from 0B – 1 and higher.

Surge Arresters Type 2


DEHNguard M TNC CI 275: modular surge arrester with integrated backup fuse for TN-C systems
DEHNguard M TNS CI 275: with integrated backup fuse for TN-S systems
DEHNguard M TT CI 275: with integrated backup fuse for TT and TN-S systems (”3+1” circuits)
DEHNguard M TN CI 275: with integrated backup fuse for 230 V TN systems
DEHNguard M TT 2P CI 275: with integrated backup fuse for 230 V TT and TN systems (”1+1” circuits)
DEHNguard S CI 275: single-pole, modular surge arrester with integrated backup fuse
DEHNguard M ... CI 275 FM: with remote signalling contact for the monitoring device (floating changeover contact)

The modular surge arresters of the DEHNguard M ... CI family with their Apart from the mechanical operating state/fault indication, the ...FM ver-
functional Red/Line design combine short-circuit protection and surge sion of the DEHNguard M ...CI devices features a three-pole remote sig-
protection in a single protection module. This sets new standards for user- nalling terminal. With its floating changeover contact, the remote signal
friendly surge and short-circuit protection. can be used as break or make contact according to the particular circuit
The protective circuit with the arrester backup fuse integrated in the pro- concept.
tection module and the heavy-duty zinc oxide varistor in combination
with the dual Thermo Dynamic Control monitoring device offer the advan- All benefits of the modular design of the DEHNguard M family were com-
tage of easy installation and minimum space requirements. pletely integrated into the new DEHNguard M ... CI family.
Due to the integrated arrester backup fuse the user does not have to The system-configuration-specific product designation as well as the
worry about arrester-specific dimensioning requirements such as backup ”Thermo Dynamic Control“ monitoring device reflect the high safety
protection in case of short-circuits and impulse current carrying capacity. requirements.
The unique module locking system prevents the protection modules from
The user has the possibility to implement space-saving surge protection becoming loose due to shock during transport or due to the enormous
measures in installations up to short-circuit currents of 25 kArms which forces of discharge. Nevertheless, the protection modules can be easily
cover all functions specified in the IEC 60364-5-53 installation standard. replaced without tools, the need to de-energise and removing the cover
All circuits including the N-PE circuit feature an operating state indication of the distribution board by simply pressing the user-friendly module
required in accordance with the IEC 60364-5-53 standard. release button of the protection modules. To prevent incorrect insertion by
The ”Thermo Dynamic Control“ monitoring device does not only evaluate the installer or user, every protective circuit of the multipole and single-
the surface temperature of the heavy-duty varistor but also the intensity pole SPDs and every protection module is mechanically coded.
of the discharge current. The mechanical visual indication with green and
red flags, which is free of operating currents, shows if every protective cir- The surge arresters of the mutlipole modular DEHNguard M ... CI family
cuit is ready for operation. The visual indication indicates the activation of feature multifunctional terminals on a standardised spacing of 1 module
the ”Thermo Dynamic Control“ monitoring device and the integrated for connecting conductors and busbars, allowing easy wiring with other
arrester backup fuse. DIN rail mounted devices. Thus, a variety of applications can be easily con-
nected in series in accordance with IEC 60364-5-53 for optimal protec-
tion.

www.dehn.de 69
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® modular with integrated backup fuse POWER SUPPLY SYSTEMS


952 304 DG M TNC CI 275
952 309 DG M TNC CI 275 FM

DEHNguard M TNC CI 275 (FM) SURGE ARRESTERS – TYPE 2


L1 L2 L3
NEW DG M TNC CI 275
952 304
DG M TNC CI 275 FM
952 309

12
11
14

9 PEN

Basic circuit diagram DG M TNC CI 275 FM Dimension drawing DG M TNC CI 275 FM

DG M TNC CI 275 (FM): Modular surge arrester with integrated backup fuses for TN-C systems

DG M TNC CI 275 DG M TNC CI 275 FM


SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Nominal a.c. voltage UN 230/400 V 230/400 V
Max. continuous operating a.c. voltage UC 275 V 275 V
Nominal discharge current (8/20 μs) In 12.5 kA 12.5 kA
Max. discharge current (8/20 μs) Imax 25 kA 25 kA
Voltage protection level UP ) 1.5 kV ) 1.5 kV
Surge Arresters Type 2

Voltage protection level at 5 kA UP ) 1 kV ) 1 kV


Response time tA ) 25 ns ) 25 ns
Max. mains-side overcurrent protection not required not required
Short-circuit withstand capability 25 kArms 25 kArms
Temporary overvoltage (TOV) UT 335 V / 5 sec. 335 V / 5 sec.
TOV characteristics withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 3 mods., DIN 43880 3 mods., DIN 43880
Approvals, Certifications KEMA KEMA
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DG M TNC CI 275 DG M TNC CI 275 FM
Part No. 952 304 952 309
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular with integrated backup fuse


Varistor-based protection module for 952 020
CI 275
DG MOD

NEW DEHNguard M CI
DG MOD CI 275: Protection module for DEHNguard M ... CI 275 com-
DG MOD CI 275
952 020

prising a varistor connected in series with the integrated backup fuse


PU Part
Type pc(s). No.
DG MOD CI 275 1 952 020

70 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® modular with integrated backup fuse


952 401 DG M TNS CI 275
952 406 DG M TNS CI 275 FM

SURGE ARRESTERS – TYPE 2 DEHNguard M TNS CI 275 (FM)

DG M TNS CI 275
L1 L2 L3 N NEW
952 401
DG M TNS CI 275 FM
952 406

12
11
14

9 PE

Dimension drawing DG M TNS CI 275 FM Basic circuit diagram DG M TNS CI 275 FM

DG M TNS CI 275 (FM): Modular surge arrester with integrated backup fuses for TN-S systems

DG M TNS CI 275 DG M TNS CI 275 FM


SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Nominal a.c. voltage UN 230/400 V 230/400 V
Max. continuous operating a.c. voltage UC 275 V 275 V
Nominal discharge current (8/20 μs) In 12.5 kA 12.5 kA
Max. discharge current (8/20 μs) Imax 25 kA 25 kA
Voltage protection level UP ) 1.5 kV ) 1.5 kV

Surge Arresters Type 2


Voltage protection level at 5 kA UP ) 1 kV ) 1 kV
Response time tA ) 25 ns ) 25 ns
Max. mains-side overcurrent protection not required not required
Short-circuit withstand capability 25 kArms 25 kArms
Temporary overvoltage (TOV) UT 335 V / 5 sec. 335 V / 5 sec.
TOV characteristics withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 4 mods., DIN 43880 4 mods., DIN 43880
Approvals, Certifications KEMA KEMA
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DG M TNS CI 275 DG M TNS CI 275 FM
Part No. 952 401 952 406
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular with integrated backup fuse Accessory Part for DEHNguard® modular with integrated backup fuse
Varistor-based protection module for N-PE circuits
952 010
275
DG MOD

Varistor-based protection module for 952 020


CI 275
DG MOD

NEW
DG MOD ...: Varistor-based protection module for DEHNguard M ... and DEHNguard M CI
DEHNguard S ... surge arresters
DG MOD 275
952 010
DG MOD CI 275: Protection module for DEHNguard M ... CI 275 com-
DG MOD CI 275
952 020

PU Part prising a varistor connected in series with the integrated backup fuse
Type pc(s). No. PU Part
DG MOD 275 1 952 010 Type pc(s). No.
DG MOD CI 275 1 952 020

www.dehn.de 71
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® modular with integrated backup fuse POWER SUPPLY SYSTEMS


952 322 DG M TT CI 275
952 327 DG M TT CI 275 FM

DEHNguard M TT CI 275 (FM) SURGE ARRESTERS – TYPE 2


L1 L2 L3 N
NEW DG M TT CI 275
952 322
DG M TT CI 275 FM
952 327

12
11
14

9 PE

Basic circuit diagram DG M TT CI 275 FM Dimension drawing DG M TT CI 275 FM

DG M TT CI 275 (FM): Modular surge arrester with integrated backup fuses for TT and TN-S sys-
tems (”3+1” circuits)

DG M TT CI 275 DG M TT CI 275 FM
SPD according to EN 61643-11 / ... IEC 61643-1 Type 2 / Class II Type 2 / Class II
Nominal a.c. voltage UN 230/400 V 230/400 V
Max. continuous operating a.c. voltage [L-N] UC 275 V 275 V
Max. continuous operating a.c. voltage [N-PE] UC 255 V 255 V
Nominal discharge current (8/20 μs) [L-N] In 12.5 kA 12.5 kA
Nominal discharge current (8/20 μs) [N-PE] In 20 kA 20 kA
Max. discharge current (8/20 μs) [L-N] Imax 25 kA 25 kA
Max. discharge current (8/20 μs) [N-PE] Imax 40 kA 40 kA
Lightning impulse current (10/350 μs) [N-PE] Iimp 12 kA 12 kA
Surge Arresters Type 2

Voltage protection level [L-N] UP ) 1.5 kV ) 1.5 kV


Voltage protection level [L-N] at 5 kA UP ) 1 kV ) 1 kV
Voltage protection level [N-PE] UP ) 1.5 kV ) 1.5 kV
Follow current extinguishing capability [N-PE] Ifi 100 Arms 100 Arms
Response time [L-N] tA ) 25 ns ) 25 ns
Response time [N-PE] tA ) 100 ns ) 100 ns
Max. mains-side overcurrent protection not required not required
Short-circuit withstand capability 25 kArms 25 kArms
Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec.
Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms
TOV characteristics withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 4 mods., DIN 43880 4 mods., DIN 43880
Approvals, Certifications KEMA KEMA
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DG M TT CI 275 DG M TT CI 275 FM
Part No. 952 322 952 327
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular with integrated backup fuse Accessory Part for DEHNguard® modular with integrated backup fuse
Varistor-based protection module for 952 020
CI 275
DG MOD

N-PE spark-gap-based protection module for 952 050


NPE
DG MOD

DEHNguard M CI DEHNguard M TT ...


NEW DG MOD NPE
952 050

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 com- DG MOD NPE: N-PE spark-gap-based protection module for two- and
DG MOD CI 275
952 020

prising a varistor connected in series with the integrated backup fuse four-pole DEHNguard DG M TT ... surge arresters
PU Part PU Part
Type pc(s). No. Type pc(s). No.
DG MOD CI 275 1 952 020 DG MOD NPE 1 952 050
72 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® modular with integrated backup fuse


952 173 DG M TN CI 275
952 178 DG M TN CI 275 FM

SURGE ARRESTERS – TYPE 2 DEHNguard M TN CI 275 (FM)

DG M TN CI 275
L N NEW
952 173
DG M TN CI 275 FM
952 178

12
11
14

9 PE

Dimension drawing DG M TN CI 275 FM Basic circuit diagram DG M TN CI 275 FM

DG M TN CI 275 (FM): Modular surge arrester with integrated backup fuse for single-phase
230 V TN systems

DG M TN CI 275 DG M TN CI 275 FM
SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Nominal a.c. voltage UN 230 V 230 V
Max. continuous operating a.c. voltage UC 275 V 275 V
Nominal discharge current (8/20 μs) In 12.5 kA 12.5 kA
Max. discharge current (8/20 μs) Imax 25 kA 25 kA
Voltage protection level UP ) 1.5 kV ) 1.5 kV
Voltage protection level at 5 kA UP ) 1 kV ) 1 kV
Response time tA ) 25 ns ) 25 ns

Surge Arresters Type 2


Max. mains-side overcurrent protection not required not required
Short-circuit withstand capability 25 kArms 25 kArms
Temporary overvoltage (TOV) UT 335 V / 5 sec. 335 V / 5 sec.
TOV characteristics withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 2 mods., DIN 43880 2 mods., DIN 43880
Approvals, Certifications KEMA KEMA
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DG M TN CI 275 DG M TN CI 275 FM
Part No. 952 173 952 178
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular with integrated backup fuse Accessory Part for DEHNguard® modular with integrated backup fuse
Varistor-based protection module for N-PE circuits
952 010
275
DG MOD

Varistor-based protection module for 952 020


CI 275
DG MOD

NEW
DG MOD ...: Varistor-based protection module for DEHNguard M ... and DEHNguard M CI
DEHNguard S ... surge arresters
DG MOD 275
für DG M und DG S, 275 V
ÜS-Modul
952 010
DG MOD CI 275: Protection module for DEHNguard M ... CI 275 com-
DG MOD CI 275
952 020

PU Part prising a varistor connected in series with the integrated backup fuse
Type pc(s). No. PU Part
DG MOD 275 1 952 010 Type pc(s). No.
DG MOD CI 275 1 952 020

www.dehn.de 73
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® modular with integrated backup fuse POWER SUPPLY SYSTEMS


952 171 DG M TT 2P CI 275
952 176 DG M TT 2P CI 275 FM

DEHNguard M TT 2P CI 275 (FM) SURGE ARRESTERS – TYPE 2


L N
NEW DG M TT 2P CI 275
952 171
DG M TT 2P CI 275 FM
952 176

12
11
14

9 PE

Basic circuit diagram DG M TT 2P CI 275 FM Dimension drawing DG M TT 2P CI 275 FM

DG M TT 2P CI 275 (FM): Modular surge arrester with integrated backup fuse for single-phase
230 V TT and TN systems (”1+1” circuits)

DG M TT 2P CI 275 DG M TT 2P CI 275 FM
SPD according to EN 61643-11 / ... IEC 61643-1 Type 2 / Class II Type 2 / Class II
Nominal a.c. voltage UN 230 V 230 V
Max. continuous operating a.c. voltage [L-N] UC 275 V 275 V
Max. continuous operating a.c. voltage [N-PE] UC 255 V 255 V
Nominal discharge current (8/20 μs) [L-N] In 12.5 kA 12.5 kA
Nominal discharge current (8/20 μs) [N-PE] In 20 kA 20 kA
Max. discharge current (8/20 μs) [L-N] Imax 25 kA 25 kA
Max. discharge current (8/20 μs) [N-PE] Imax 40 kA 40 kA
Lightning impulse current (10/350 μs) [N-PE] Iimp 12 kA 12 kA
Surge Arresters Type 2

Voltage protection level [L-N] UP ) 1.5 kV ) 1.5 kV


Voltage protection level [L-N] at 5 kA UP ) 1 kV ) 1 kV
Voltage protection level [N-PE] UP ) 1.5 kV ) 1.5 kV
Follow current extinguishing capability [N-PE] Ifi 100 Arms 100 Arms
Response time [L-N] tA ) 25 ns ) 25 ns
Response time [N-PE] tA ) 100 ns ) 100 ns
Max. mains-side overcurrent protection not required not required
Short-circuit withstand capability 25 kArms 25 kArms
Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec.
Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms
TOV characteristics withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 2 mods., DIN 43880 2 mods., DIN 43880
Approvals, Certifications KEMA KEMA
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DG M TT 2P CI 275 DG M TT 2P CI 275 FM
Part No. 952 171 952 176
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular with integrated backup fuse Accessory Part for DEHNguard® modular with integrated backup fuse
Varistor-based protection module for 952 020
CI 275
DG MOD

N-PE spark-gap-based protection module for 952 050


NPE
DG MOD

NEW DEHNguard M CI DEHNguard M TT ... DG MOD NPE ÜS-Modul


N-PE für DG M TT 952 050

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 com- DG MOD NPE: N-PE spark-gap-based protection module for two- and
DG MOD CI 275
952 020

prising a varistor connected in series with the integrated backup fuse four-pole DEHNguard DG M TT ... surge arresters
PU Part PU Part
Type pc(s). No. Type pc(s). No.
DG MOD CI 275 1 952 020 DG MOD NPE 1 952 050
74 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® modular with integrated backup fuse


952 079 DG S CI 275
952 099 DG S CI 275 FM

SURGE ARRESTERS – TYPE 2 DEHNguard S CI 275 (FM)

DG S CI 275
NEW
952 079
DG S CI 275 FM
952 099

12
11
14

Dimension drawing DG S CI 275 FM Basic circuit diagram DG S CI 275 FM

DG S CI 275 (FM): Single-pole, pluggable surge arrester consisting of a base part and plug-in pro-
tection module; with integrated backup fuse; optionally available with floating
remote signalling contact

DG S CI 275 DG S CI 275 FM
SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Max. continuous operating a.c. voltage UC 275 V 275 V
Nominal discharge current (8/20 μs) In 12.5 kA 12.5 kA
Max. discharge current (8/20 μs) Imax 25 kA 25 kA
Voltage protection level UP ) 1.5 kV ) 1.5 kV
Voltage protection level at 5 kA UP ) 1 kV ) 1 kV

Surge Arresters Type 2


Response time tA ) 25 ns ) 25 ns
Max. mains-side overcurrent protection not required not required
Short-circuit withstand capability 25 kArms 25 kArms
Temporary overvoltage (TOV) UT 335 V / 5 sec. 335 V / 5 sec.
TOV characteristics withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 1 mod., DIN 43880 1 mod., DIN 43880
Approvals, Certifications KEMA KEMA
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DG S CI 275 DG S CI 275 FM
Part No. 952 079 952 099
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular with integrated backup fuse


Varistor-based protection module for 952 020
CI 275
DG MOD

NEW
DEHNguard M CI
DG MOD CI 275: Protection module for DEHNguard M ... CI 275 com-
DG MOD CI 275
952 020

prising a varistor connected in series with the integrated backup fuse


PU Part
Type pc(s). No.
DG MOD CI 275 1 952 020

www.dehn.de 75
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® modular POWER SUPPLY SYSTEMS


Multipole, modular surge arrester SURGE ARRESTERS – TYPE 2
SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1

• Prewired complete unit consisting of a base


part and plug-in protection modules
• Energy coordination within the Red/Line pro-
duct family
• High discharge capacity due to heavy-duty zinc
oxide varistors/spark gaps
• High reliability due to ”Thermo Dynamic
Control” SPD monitoring device
• Easy replacement of protection modules due to
module locking system with module release
button
• Vibration- and shock-tested according to EN
60068-2

For protecting low-voltage consumer´s installations against surges. For


installation in conformity with the lightning protection zones concept at
the boundaries from 0B – 1 and higher.
Surge Arresters Type 2

DEHNguard M TNC ...: Modular surge arrester for use in TN-C systems
DEHNguard M TNS ...: Modular surge arrester for use in TN-S systems
DEHNguard M TT ...: Modular surge arrester for use in TT and TN-S systems (”3+1” circuit)
DEHNguard M TN ...: Modular surge arrester for use in single-phase TN systems
DEHNguard M TT 2P ...: Modular surge arrester for use in single-phase TT and TN systems (”1+1” circuit)
DEHNguard M WE ...: Modular surge arrester especially for use in wind turbines
DEHNguard M ... FM: With remote signalling contact for the monitoring device (floating changeover contact)

The modular DEHNguard M ... surge arresters with their functional The dual Thermo Dynamic Control monitoring device was not only devel-
Red/Line family design set new standards in terms of safety and user- oped on the basis of national and international product standards, but it
friendliness. The approved protective circuit with heavy-duty zinc oxide also stands for experience of decades in the international use of surge
varistors in combination with the dual Thermo Dynamic Control monitor- protective devices and considers many fields of application where SPDs
ing device characterise the DEHNguard technology. might be damaged. Like with all DEHN surge arresters with Thermo
Dynamic Control, evaluation is based on the intensity of the discharge
Many features of the device show that both safe surge protection and current and the surface temperature of the heavy-duty varistor. The green
reliability of the devices are the key element of the new modular and red indicator shows if each protective circuit is ready for operation.
DEHNguard. The application-oriented product designation, which makes Apart from this standard visual indication, DEHNguard M ... FM devices
the choice of the adequate devices considerably easier, as well as the feature a three-pole terminal for remote signalling.
module locking device, which is unique for use with surge protective
devices, stand for fulfilling stringent safety requirements. It fixes the pro- With their floating changeover contact, the remote signal can be used as
tection modules and the base part of the device firmly in place. Neither a make or break contract according to the particular circuit concept. The
vibration during transport nor the enormous electromagnetic forces of surge arresters of the multipole modular DEHNguard M family feature
discharge can loosen the protection modules. Nevertheless, they can be multifunctional terminals on a standardised spacing of 1 module for the
easily replaced without tools by simply pressing the user-friendly module connection of conductors
release button of the protection modules. In order to avoid incorrect inser- and busbars, allowing
tion by the installer or user when replacing the modules, each protective easy wiring with other
circuit of the multipole surge arresters and each protection module are DIN rail mounted devices.
mechanically coded. Thus a variety of applica-
tions can be connected in
series according to IEC
60364-5-53 for optimal
protection.

76 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® modular


952 313 DG M TNC 150
952 300 DG M TNC 275

SURGE ARRESTERS – TYPE 2 DEHNguard M TNC ...


952 314 DG M TNC 385
952 303 DG M TNC 440

L1 L2 L3
DG M TNC 150
952 313
DG M TNC 275
952 300
DG M TNC 385
952 314
DG M TNC 440
952 303

9 PEN

Dimension drawing DG M TNC ... Basic circuit diagram DG M TNC ...

DG M TNC ... : Modular surge arrester for TN-C systems

DG M TNC 150 DG M TNC 275 DG M TNC 385 DG M TNC 440


SPD according to EN 61643-11 Type 2 Type 2 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II Class II Class II
Nominal a.c. voltage UN 120/240 V 230/400 V 230/400 V 400/690 V
Max. continuous operating a.c. voltage UC 150 V 275 V 385 V 440 V
Nominal discharge current (8/20 μs) In 15 kA 20 kA 20 kA 20 kA
Max. discharge current (8/20 μs) Imax 40 kA 40 kA 40 kA 40 kA
Voltage protection level UP ) 0.7 kV ) 1.25 kV ) 1.75 kV ) 2 kV

Surge Arresters Type 2


Voltage protection level at 5 kA UP ) 0.55 kV ) 1 kV ) 1.35 kV ) 1.7 kV
Response time tA ) 25 ns ) 25 ns ) 25 ns ) 25 ns
Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG
Short-circuit withstand capability
for max. mains-side overcurrent protection 50 kArms 50 kArms 25 kArms 25 kArms
Temporary overvoltage (TOV) UT 175 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec. 580 V / 5 sec.
TOV characteristics withstand withstand withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20 IP 20
Capacity 3 mods., DIN 43880 3 mods., DIN 43880 3 mods., DIN 43880 3 mods., DIN 43880
Approvals, Certifications — KEMA, VDE, UL, VdS — —

Ordering information
Type DG M TNC 150 DG M TNC 275 DG M TNC 385 DG M TNC 440
Part No. 952 313 NEW 952 300 952 314 NEW 952 303
Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular


Varistor-based protection module
952 012
150
952 010
275
952 013
DG MOD

DG MOD

DG MOD
320
952 014 DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


385
952 015
440
DG MOD

DEHNguard S ... surge arresters


DG MOD 150
952 012
DG MOD 275
952 010
DG MOD 320
952 013
DG MOD 385
952 014
DG MOD 440
PU Part
952 015

Type pc(s). No.


DG MOD 150 1 952 012
DG MOD 275 1 952 010
DG MOD 385 1 952 014
DG MOD 440 1 952 015

www.dehn.de 77
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® modular POWER SUPPLY SYSTEMS


952 318 DG M TNC 150 FM
952 305 DG M TNC 275 FM

DEHNguard M TNC ... FM SURGE ARRESTERS – TYPE 2


952 319 DG M TNC 385 FM
952 308 DG M TNC 440 FM

L1 L2 L3
DG M TNC 150 FM
952 318
DG M TNC 275 FM
952 305
DG M TNC 385 FM
952 319
DG M TNC 440 FM
952 308

12
11
14

9 PEN

Basic circuit diagram DG M TNC ... FM Dimension drawing DG M TNC ... FM

DG M TNC ... FM: Modular surge arrester for TN-C systems; with floating remote signalling contact

DG M TNC 150 FM DG M TNC 275 FM DG M TNC 385 FM DG M TNC 440 FM


SPD according to EN 61643-11 Type 2 Type 2 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II Class II Class II
Nominal a.c. voltage UN 120/240 V 230/400 V 230/400 V 400/690 V
Max. continuous operating a.c. voltage UC 150 V 275 V 385 V 440 V
Nominal discharge current (8/20 μs) In 15 kA 20 kA 20 kA 20 kA
Max. discharge current (8/20 μs) Imax 40 kA 40 kA 40 kA 40 kA
Voltage protection level UP ) 0.7 kV ) 1.25 kV ) 1.75 kV ) 2 kV
Surge Arresters Type 2

Voltage protection level at 5 kA UP ) 0.55 kV ) 1 kV ) 1.35 kV ) 1.7 kV


Response time tA ) 25 ns ) 25 ns ) 25 ns ) 25 ns
Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG
Short-circuit withstand capability
for max. mains-side overcurrent protection 50 kArms 50 kArms 25 kArms 25 kArms
Temporary overvoltage (TOV) UT 175 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec. 580 V / 5 V / 5 sec.
TOV characteristics withstand withstand withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20 IP 20
Capacity 3 mods., DIN 43880 3 mods., DIN 43880 3 mods., DIN 43880 3 mods., DIN 43880
Approvals, Certifications — KEMA, VDE, UL, VdS — —
Type of remote signalling contact changeover contact changeover contact changeover contact changeover contact
Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible

Ordering information
Type DG M TNC 150 FM DG M TNC 275 FM DG M TNC 385 FM DG M TNC 440 FM
Part No. NEW 952 318 952 305 N W 952 319
E 952 308
Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular


952 012
150
952 010
275
952 013
DG MOD

DG MOD

DG MOD
Varistor-based protection module
320
952 014 DG MOD
385
952 015
440
DG MOD
DG MOD ...: Varistor-based protection module for DEHNguard M ... and
DG MOD 150
952 012
DG MOD 275
952 010
DEHNguard S ... surge arresters
DG MOD 320
952 013
DG MOD 385
952 014
DG MOD 440
PU Part
952 015

Type pc(s). No.


DG MOD 150 1 952 012
DG MOD 275 1 952 010
DG MOD 385 1 952 014
DG MOD 440 1 952 015

78 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® modular


952 403 DG M TNS 150
952 400 DG M TNS 275

SURGE ARRESTERS – TYPE 2 DEHNguard M TNS ...


952 404 DG M TNS 385

L1 L2 L3 N
DG M TNS 150
952 403
DG M TNS 275
952 400
DG M TNS 385
952 404

9 PE

Dimension drawing DG M TNS ... Basic circuit diagram DG M TNS ...

DG M TNS ... : Modular surge arrester for TN-S systems

DG M TNS 150 DG M TNS 275 DG M TNS 385


SPD according to EN 61643-11 Type 2 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II Class II
Nominal a.c. voltage UN 120/240 V 230/400 V 230/400 V
Max. continuous operating a.c. voltage UC 150 V 275 V 385 V
Nominal discharge current (8/20 μs) In 15 kA 20 kA 20 kA
Max. discharge current (8/20 μs) Imax 40 kA 40 kA 40 kA
Voltage protection level UP ) 0.7 kV ) 1.25 kV ) 1.75 kV

Surge Arresters Type 2


Voltage protection level at 5 kA UP ) 0.55 kV ) 1 kV ) 1.35 kV
Response time tA ) 25 ns ) 25 ns ) 25 ns
Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG
Short-circuit withstand capability
for max. mains-side overcurrent protection 50 kArms 50 kArms 25 kArms
Temporary overvoltage (TOV) UT 175 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.
TOV characteristics withstand withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20
Capacity 4 mods., DIN 43880 4 mods., DIN 43880 4 mods., DIN 43880
Approvals, Certifications KEMA, UL KEMA, VDE, UL, VdS KEMA, UL

Ordering information
Type DG M TNS 150 DG M TNS 275 DG M TNS 385
Part No. 952 403 NEW 952 400 952 404 NEW
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular


Varistor-based protection module
952 012
150
952 010
275
952 013
DG MOD

DG MOD

DG MOD
320
952 014 DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


385
952 015
440
DG MOD

DEHNguard S ... surge arresters


DG MOD 150
952 012
DG MOD 275
952 010
DG MOD 320
952 013
DG MOD 385
952 014
DG MOD 440
PU Part
952 015

Type pc(s). No.


DG MOD 150 1 952 012
DG MOD 275 1 952 010
DG MOD 385 1 952 014

www.dehn.de 79
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® modular POWER SUPPLY SYSTEMS


952 408 DG M TNS 150 FM
952 405 DG M TNS 275 FM

DEHNguard M TNS ... FM SURGE ARRESTERS – TYPE 2


952 409 DG M TNS 385 FM

L1 L2 L3 N
DG M TNS 150 FM
952 408
DG M TNS 275 FM
952 405
DG M TNS 385 FM
952 409

12
11
14

9 PE

Basic circuit diagram DG M TNS ... FM Dimension drawing DG M TNS ... FM

DG M TNS ... FM: Modular surge arrester for TN-S systems; with floating remote signalling contact

DG M TNS 150 FM DG M TNS 275 FM DG M TNS 385 FM


SPD according to EN 61643-11 Type 2 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II Class II
Nominal a.c. voltage UN 120/240 V 230/400 V 230/400 V
Max. continuous operating a.c. voltage UC 150 V 275 V 385 V
Nominal discharge current (8/20 μs) In 15 kA 20 kA 20 kA
Max. discharge current (8/20 μs) Imax 40 kA 40 kA 40 kA
Voltage protection level UP ) 0.7 kV ) 1.25 kV ) 1.75 kV
Voltage protection level at 5 kA UP ) 0.55 kV ) 1 kV ) 1.35 kV
Surge Arresters Type 2

Response time tA ) 25 ns ) 25 ns ) 25 ns
Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG
Short-circuit withstand capability
for max. mains-side overcurrent protection 50 kArms 50 kArms 25 kArms
Temporary overvoltage (TOV) UT 175 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.
TOV characteristics withstand withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20
Capacity 4 mods., DIN 43880 4 mods., DIN 43880 4 mods., DIN 43880
Approvals, Certifications KEMA, UL KEMA, VDE, UL, VdS KEMA, UL
Type of remote signalling contact changeover contact changeover contact changeover contact
Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information
Type DG M TNS 150 FM DG M TNS 275 FM DG M TNS 385 FM
Part No. 952 408 952 405 952 409
NEW NEW
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular


952 012
150
952 010
275
952 013
DG MOD

DG MOD

DG MOD
Varistor-based protection module
320
952 014 DG MOD
385
952 015
440
DG MOD
DG MOD ...: Varistor-based protection module for DEHNguard M ... and
DG MOD 150
952 012
DG MOD 275
952 010
DEHNguard S ... surge arresters
DG MOD 320
952 013
DG MOD 385
952 014
DG MOD 440
PU Part
952 015

Type pc(s). No.


DG MOD 150 1 952 012
DG MOD 275 1 952 010
DG MOD 385 1 952 014

80 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® modular


952 310 DG M TT 275
952 320 DG M TT 320

SURGE ARRESTERS – TYPE 2 DEHNguard M TT ...


952 311 DG M TT 385

DG M TT 275
L1 L2 L3 N
952 310
DG M TT 320
952 320
DG M TT 385
952 311

9 PE

Dimension drawing DG M TT ... Basic circuit diagram DG M TT ...

DG M TT ... : Modular surge arrester for TT and TN-S systems (”3+1” circuits)

DG M TT 275 DG M TT 320 DG M TT 385


SPD according to EN 61643-11 Type 2 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II Class II
Nominal a.c. voltage UN 230/400 V 230/400 V 230/400 V
Max. continuous operating a.c. voltage [L-N] UC 275 V 320 V 385 V
Max. continuous operating a.c. voltage [N-PE] UC 255 V 255 V 255 V
Nominal discharge current (8/20 μs) In 20 kA 20 kA 20 kA
Max. discharge current (8/20 μs) Imax 40 kA 40 kA 40 kA
Lightning impulse current (10/350 μs) [N-PE] Iimp 12 kA 12 kA 12 kA

Surge Arresters Type 2


Voltage protection level [L-N] UP ) 1.25 kV ) 1.5 kV ) 1.75 kV
Voltage protection level [L-N] at 5 kA UP ) 1 kV ) 1.2 kV ) 1.35 kV
Voltage protection level [N-PE] UP ) 1.5 kV ) 1.5 kV ) 1.5 kV
Follow current extinguishing capability [N-PE] Ifi 100 Arms 100 Arms 100 Arms
Response time [L-N] tA ) 25 ns ) 25 ns ) 25 ns
Response time [N-PE] tA ) 100 ns ) 100 ns ) 100 ns
Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG
Short-circuit withstand capability
for max. mains-side overcurrent protection 50 kArms 25 kArms 25 kArms
Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.
Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms 1200 V / 200 ms
TOV characteristics withstand withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20
Capacity 4 mods., DIN 43880 4 mods., DIN 43880 4 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL, VdS KEMA KEMA

Ordering information
Type DG M TT 275 DG M TT 320 DG M TT 385
Part No. 952 310 952 320 NEW 952 311 NE
W
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular Accessory Part for DEHNguard® modular
N-PE spark-gap-based protection module for
952 050
NPE
DG MOD

Varistor-based protection module


952 012
150
952 010
275
952 013
DG MOD

DG MOD

DG MOD

DEHNguard M TT ... 320


952 014 DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


385
952 015
440
DG MOD

DG MOD NPE: N-PE spark-gap-based protection module for two- and


DG MOD NPE
952 050
DEHNguard S ... surge arresters
DG MOD 150
952 012
DG MOD 275
952 010
DG MOD 320

four-pole DEHNguard DG M TT ... surge arresters 952 013


DG MOD 385
952 014
DG MOD 440
PU Part
952 015

PU Part Type pc(s). No.


Type pc(s). No. DG MOD 275 1 952 010
DG MOD NPE 1 952 050 DG MOD 320 1 952 013
DG MOD 385 1 952 014

www.dehn.de 81
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® modular POWER SUPPLY SYSTEMS


952 315 DG M TT 275 FM
952 325 DG M TT 320 FM

DEHNguard M TT ... FM SURGE ARRESTERS – TYPE 2


952 316 DG M TT 385 FM

L1 L2 L3 N
DG M TT 275 FM
952 315
DG M TT 320 FM
952 325
DG M TT 385 FM
952 316

12
11
14

9 PE

Basic circuit diagram DG M TT ... FM Dimension drawing DG M TT ... FM

DG M TT ... FM: Modular surge arrester for TT and TN-S systems (”3+1” circuits); with floating
remote signalling contact

DG M TT 275 FM DG M TT 320 FM DG M TT 385 FM


SPD according to EN 61643-11 / ... IEC 61643-1 Type 2 / Class II Type 2 / Class II Type 2 / Class II
Nominal a.c. voltage UN 230/400 V 230/400 V 230/400 V
Max. continuous operating a.c. voltage [L-N] UC 275 V 320 V 385 V
Max. continuous operating a.c. voltage [N-PE] UC 255 V 255 V 255 V
Nominal discharge current (8/20 μs) In 20 kA 20 kA 20 kA
Max. discharge current (8/20 μs) Imax 40 kA 40 kA 40 kA
Lightning impulse current (10/350 μs) [N-PE] Iimp 12 kA 12 kA 12 kA
Voltage protection level [L-N] UP ) 1.25 kV ) 1.5 kV ) 1.75 kV
Voltage protection level [L-N] at 5 kA UP ) 1 kV ) 1.2 kV ) 1.35 kV
Surge Arresters Type 2

Voltage protection level [N-PE] UP ) 1.5 kV ) 1.5 kV ) 1.5 kV


Follow current extinguishing capability [N-PE] Ifi 100 Arms 100 Arms 100 Arms
Response time [L-N] tA ) 25 ns ) 25 ns ) 25 ns
Response time [N-PE] tA ) 100 ns ) 100 ns ) 100 ns
Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG
Short-circuit withstand capability
for max. mains-side overcurrent protection 50 kArms 25 kArms 25 kArms
Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.
Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms 1200 V / 200 ms
TOV characteristics withstand withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20
Capacity 4 mods., DIN 43880 4 mods., DIN 43880 4 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL, VdS KEMA KEMA
Type of remote signalling contact changeover contact changeover contact changeover contact
Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information
Type DG M TT 275 FM DG M TT 320 FM DG M TT 385 FM
Part No. 952 315 N W 952 325
E W 952 316
NE
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular Accessory Part for DEHNguard® modular
952 012
150
952 010
275
952 013
DG MOD

DG MOD

DG MOD
Varistor-based protection module 952 050
NPE
DG MOD

N-PE spark-gap-based protection module for


320
952 014
385
952 015
440
DG MOD

DG MOD
DG MOD ...: Varistor-based protection module for DEHNguard M ... and DEHNguard M TT ...
DG MOD 150
952 012
DG MOD 275
952 010
DEHNguard S ... surge arresters DG MOD NPE
952 050
DG MOD NPE: N-PE spark-gap-based protection module for two- and
DG MOD 320
952 013
DG MOD 385
952 014
DG MOD 440
PU Part four-pole DEHNguard DG M TT ... surge arresters
952 015

Type pc(s). No. PU Part


DG MOD 275 1 952 010 Type pc(s). No.
DG MOD 320 1 952 013 DG MOD NPE 1 952 050
DG MOD 385 1 952 014

82 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® modular


952 201 DG M TN 150
952 200 DG M TN 275

SURGE ARRESTERS – TYPE 2 DEHNguard M TN ...


L N
DG M TN 150
952 201
DG M TN 275
952 200

9 PE

Dimension drawing DG M TN ... Basic circuit diagram DG M TN ...

DG M TN ... : Modular surge arrester for single-phase TN systems

DG M TN 150 DG M TN 275
SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Nominal a.c. voltage UN 120 V 230 V
Max. continuous operating a.c. voltage UC 150 V 275 V
Nominal discharge current (8/20 μs) In 15 kA 20 kA
Max. discharge current (8/20 μs) Imax 40 kA 40 kA
Voltage protection level UP ) 0.7 kV ) 1.25 kV
Voltage protection level at 5 kA UP ) 0.55 kV ) 1 kV
Response time tA ) 25 ns ) 25 ns

Surge Arresters Type 2


Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG
Short-circuit withstand capability for max. mains-side overcurrent protection 50 kArms 50 kArms
Temporary overvoltage (TOV) UT 175 V / 5 sec. 335 V / 5 sec.
TOV characteristics withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 2 mods., DIN 43880 2 mods., DIN 43880
Approvals, Certifications — KEMA, VDE, UL, VdS

Ordering information
Type DG M TN 150 DG M TN 275
Part No. 952 201 NEW 952 200
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular


Varistor-based protection module
952 010
275
952 012
150
952 013
DG MOD

DG MOD

DG MOD
320
952 014 DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


385
952 015
440
DG MOD

DEHNguard S ... surge arresters


DG MOD 275
für DG M und DG S, 275 V
DG MOD 150
für DG M und DG S, 150 V
ÜS-Modul
952 010
ÜS-Modul
952 012
DG MOD 320 ÜS-Modul
für DG M und DG S, 320 V 952 013
DG MOD 385
für DG M und DG S, 385 V
DG MOD 440
ÜS-Modul
952 014
ÜS-Modul
PU Part
für DG M und DG S, 440 V 952 015

Type pc(s). No.


DG MOD 150 1 952 012
DG MOD 275 1 952 010

www.dehn.de 83
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® modular POWER SUPPLY SYSTEMS


952 206 DG M TN 150 FM
952 205 DG M TN 275 FM

DEHNguard M TN ... FM SURGE ARRESTERS – TYPE 2


L N
DG M TN 150 FM
952 206
DG M TN 275 FM
952 205

12
11
14

9 PE

Basic circuit diagram DG M TN ... FM Dimension drawing DG M TN ... FM

DG M TN ... FM: Modular surge arrester for single-phase TN systems; with floating remote sig-
nalling contact

DG M TN 150 FM DG M TN 275 FM
SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Nominal a.c. voltage UN 120 V 230 V
Max. continuous operating a.c. voltage UC 150 V 275 V
Nominal discharge current (8/20 μs) In 15 kA 20 kA
Max. discharge current (8/20 μs) Imax 40 kA 40 kA
Voltage protection level UP ) 0.7 kV ) 1.25 kV
Voltage protection level at 5 kA UP ) 0.55 kV ) 1 kV
Response time tA ) 25 ns ) 25 ns
Surge Arresters Type 2

Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG


Short-circuit withstand capability for max. mains-side overcurrent protection 50 kArms 50 kArms
Temporary overvoltage (TOV) UT 175 V / 5 sec. 335 V / 5 sec.
TOV characteristics withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 2 mods., DIN 43880 2 mods., DIN 43880
Approvals, Certifications — KEMA, VDE, UL, VdS
Type of remote signalling contact changeover contact changeover contact
Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information
Type DG M TN 150 FM DG M TN 275 FM
Part No. N W 952 206
E 952 205
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular


952 010
275
952 012
150
952 013
DG MOD

DG MOD

DG MOD
Varistor-based protection module
320
952 014 DG MOD
385
952 015
440
DG MOD
DG MOD ...: Varistor-based protection module for DEHNguard M ... and
DG MOD 275
für DG M und DG S, 275 V
DG MOD 150
für DG M und DG S, 150 V
ÜS-Modul
952 010
ÜS-Modul
952 012
DEHNguard S ... surge arresters
DG MOD 320 ÜS-Modul
für DG M und DG S, 320 V 952 013
DG MOD 385
für DG M und DG S, 385 V
DG MOD 440
ÜS-Modul
952 014
ÜS-Modul
PU Part
für DG M und DG S, 440 V 952 015

Type pc(s). No.


DG MOD 150 1 952 012
DG MOD 275 1 952 010

84 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® modular


952 110 DG M TT 2P 275
952 130 DG M TT 2P 320

SURGE ARRESTERS – TYPE 2 DEHNguard M TT 2P ...


952 111 DG M TT 2P 385

L N
DG M TT 2P 275
952 110
DG M TT 2P 320
952 130
DG M TT 2P 385
952 111

9 PE

Dimension drawing DG M TT 2P ... Basic circuit diagram DG M TT 2P ...

DG M TT 2P ... : Modular surge arrester for single-phase TT and TN systems (”1+1” circuits)

DG M TT 2P 275 DG M TT 2P 320 DG M TT 2P 385


SPD according to EN 61643-11 Type 2 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II Class II
Nominal a.c. voltage UN 230 V 230 V 230 V
Max. continuous operating a.c. voltage [L-N] UC 275 V 320 V 385 V
Max. continuous operating a.c. voltage [N-PE] UC 255 V 255 V 255 V
Nominal discharge current (8/20 μs) In 20 kA 20 kA 20 kA
Max. discharge current (8/20 μs) Imax 40 kA 40 kA 40 kA
Lightning impulse current (10/350 μs) [N-PE] Iimp 12 kA 12 kA 12 kA
Voltage protection level [L-N] UP ) 1.25 kV ) 1.5 kV ) 1.75 kV

Surge Arresters Type 2


Voltage protection level [L-N] at 5 kA UP ) 1 kV ) 1.2 kV ) 1.35 kV
Voltage protection level [N-PE] UP ) 1.5 kV ) 1.5 kV ) 1.5 kV
Follow current extinguishing capability [N-PE] Ifi 100 Arms 100 Arms 100 Arms
Response time [L-N] tA ) 25 ns ) 25 ns ) 25 ns
Response time [N-PE] tA ) 100 ns ) 100 ns ) 100 ns
Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG
Short-circuit withstand capability
for max. mains-side overcurrent protection 50 kArms 25 kArms 25 kArms
Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.
Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms 1200 V / 200 ms
TOV characteristics withstand withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20
Capacity 2 mods., DIN 43880 2 mods., DIN 43880 2 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL, VdS KEMA KEMA

Ordering information
Type DG M TT 2P 275 DG M TT 2P 320 DG M TT 2P 385
Part No. 952 110 952 130 NEW 952 111 NEW
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular Accessory Part for DEHNguard® modular
N-PE spark-gap-based protection module for
952 050
NPE
DG MOD

Varistor-based protection module


952 010
275
952 012
150
952 013
DG MOD

DG MOD

DG MOD

DEHNguard M TT ... 320


952 014 DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


385
952 015
440
DG MOD

DG MOD NPE: N-PE spark-gap-based protection module for two- and


DG MOD NPE
952 050
DEHNguard S ... surge arresters
DG MOD 275
für DG M und DG S, 275 V
DG MOD 150
für DG M und DG S, 150 V
ÜS-Modul
952 010
ÜS-Modul
952 012
DG MOD 320 ÜS-Modul

four-pole DEHNguard DG M TT ... surge arresters für DG M und DG S, 320 V


DG MOD 385
für DG M und DG S, 385 V
DG MOD 440
952 013
ÜS-Modul
952 014
ÜS-Modul
VPE
für DG M und DG S, 440 V 952 015

PU Part Typ Stk. Art.-Nr.


Type pc(s). No. DG MOD 275 1 952 010
DG MOD NPE 1 952 050 DG MOD 320 1 952 013
DG MOD 385 1 952 014

www.dehn.de 85
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® modular POWER SUPPLY SYSTEMS


952 115 DG M TT 2P 275 FM
952 135 DG M TT 2P 320 FM

DEHNguard M TT 2P ... FM SURGE ARRESTERS – TYPE 2


952 116 DG M TT 2P 385 FM

L N
DG M TT 2P 275 FM
952 115
DG M TT 2P 320 FM
952 135
DG M TT 2P 385 FM
952 116

12
11
14

9 PE

Basic circuit diagram DG M TT 2P ... FM Dimension drawing DG M TT 2P ... FM

DG M TT 2P ... FM: Modular surge arrester for single-phase TT and TN systems (”1+1” circuit);
with floating remote signalling contact

DG M TT 2P 275 FM DG M TT 2P 320 FM DG M TT 2P 385 FM


SPD according to EN 61643-11 / ... IEC 61643-1 Type 2 / Class II Type 2 / Class II Type 2 / Class II
Nominal a.c. voltage UN 230 V 230 V 230 V
Max. continuous operating a.c. voltage [L-N] UC 275 V 320 V 385 V
Max. continuous operating a.c. voltage [N-PE] UC 255 V 255 V 255 V
Nominal discharge current (8/20 μs) In 20 kA 20 kA 20 kA
Max. discharge current (8/20 μs) Imax 40 kA 40 kA 40 kA
Lightning impulse current (10/350 μs) [N-PE] Iimp 12 kA 12 kA 12 kA
Voltage protection level [L-N] UP ) 1.25 kV ) 1.5 kV ) 1.75 kV
Voltage protection level [L-N] at 5 kA UP ) 1 kV ) 1.2 kV ) 1.35 kV
Surge Arresters Type 2

Voltage protection level [N-PE] UP ) 1.5 kV ) 1.5 kV ) 1.5 kV


Follow current extinguishing capability [N-PE] Ifi 100 Arms 100 Arms 100 Arms
Response time [L-N] tA ) 25 ns ) 25 ns ) 25 ns
Response time [N-PE] tA ) 100 ns ) 100 ns ) 100 ns
Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG
Short-circuit withstand capability
for max. mains-side overcurrent protection 50 kArms 25 kArms 25 kArms
Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.
Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms 1200 V / 200 ms
TOV characteristics withstand withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20
Capacity 2 mods., DIN 43880 2 mods., DIN 43880 2 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL, VdS KEMA KEMA
Type of remote signalling contact changeover contact changeover contact changeover contact
Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information
Type DG M TT 2P 275 FM DG M TT 2P 320 FM DG M TT 2P 385 FM
Part No. 952 115 NEW 952 135 NEW 952 116
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular Accessory Part for DEHNguard® modular
952 010
275
952 012
150
952 013
DG MOD

DG MOD

DG MOD
Varistor-based protection module 952 050
NPE
DG MOD

N-PE spark-gap-based protection module for


320
952 014
385
952 015
440
DG MOD

DG MOD
DG MOD ...: Varistor-based protection module for DEHNguard M ... and DEHNguard M TT ...
DG MOD 275
für DG M und DG S, 275 V
DG MOD 150
für DG M und DG S, 150 V
ÜS-Modul
952 010
ÜS-Modul
952 012
DEHNguard S ... surge arresters DG MOD NPE
952 050
DG MOD NPE: N-PE spark-gap-based protection module for two- and
DG MOD 320 ÜS-Modul
für DG M und DG S, 320 V
DG MOD 385
für DG M und DG S, 385 V
DG MOD 440
952 013
ÜS-Modul
952 014
ÜS-Modul
VPE four-pole DEHNguard DG M TT ... surge arresters
für DG M und DG S, 440 V 952 015

Typ Stk. Art.-Nr. PU Part


DG MOD 275 1 952 010 Type pc(s). No.
DG MOD 320 1 952 013 DG MOD NPE 1 952 050
DG MOD 385 1 952 014

86 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® modular


952 302 DG M WE 600
952 307 DG M WE 600 FM

SURGE ARRESTERS – TYPE 2 DEHNguard M WE ... (FM)


L1 L2 L3
DG M WE 600
952 302
DG M WE 600 FM
952 307

12
11
14

9 PEN

Dimension drawing DG M WE ... FM Basic circuit diagram DG M WE ... FM

DG M WE ... (FM): Three-pole modular surge arrester for use in wind turbines with a rated voltage
of the varistor Umov = 750 V a.c.; FM version with floating remote signalling
contact

DG M WE 600 DG M WE 600 FM
SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Nominal a.c. voltage UN 600 V 600 V
Max. continuous operating a.c. voltage UC 600 V 600 V
Rated voltage of varistor Umov 750 V 750 V
Nominal discharge current (8/20 μs) In 15 kA 15 kA
Max. discharge current (8/20 μs) Imax 25 kA 25 kA
Voltage protection level UP ) 3 kV ) 3 kV

Surge Arresters Type 2


Voltage protection level at 5 kA UP ) 2.5 kV ) 2.5 kV
Response time tA ) 25 ns ) 25 ns
Max. mains-side overcurrent protection 100 A gL/gG 100 A gL/gG
Short-circuit withstand capability for max. mains-side overcurrent protection 25 kArms 25 kArms
Temporary overvoltage (TOV) UT 900 V / 5 sec. 900 V / 5 sec.
TOV characteristics withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 3 mods., DIN 43880 3 mods., DIN 43880
Approvals, Certifications KEMA, UL, VdS KEMA, UL, VdS
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DG M WE 600 DG M WE 600 FM
Part No. 952 302 952 307
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular


Varistor-based protection module for DEHNguard 952 017
750
DG MOD

M (S) WE DG MOD 750


952 017

DG MOD 750: Varistor-based protection module for DEHNguard M WE


... and DEHNguard S WE ... surge arresters with a rated varistor voltage
Umov = 750 V a.c.
PU Part
Type pc(s). No.
DG MOD 750 1 952 017

www.dehn.de 87
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® S / DEHNguard® S FM POWER SUPPLY SYSTEMS


Single-pole, pluggable surge arrester SURGE ARRESTERS – TYPE 2
SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1

• Multi-purpose surge arrester consisting of a


base element and plug-in protection module
• High discharge capacity due to heavy-duty zinc
oxide varistor
• High reliability due to ”Thermo Dynamic
Control” SPD monitoring device
• Energy coordination within the Red/Line pro-
duct family
• Narrow (modular) design acc. to DIN 43880
• Multifunctional terminals for connecting con-
ductors and busbars
• Easy replacement of protection modules due to
module locking system with module release
button
• Vibration- and shock-tested according to EN For protecting low-voltage consumer´s installations against surges. For
installation in conformity with the lightning protection zones concept at
60068-2 the boundaries from 0B – 1 and higher.
Surge Arresters Type 2

DEHNguard S ...: Pluggable surge arrester consisting of a base part and plug-in protection module
DEHNguard S ... FM: With remote signalling contact for the monitoring device (floating changeover contact)

The universal features are characteristic of the single-pole devices of the Like with all DEHNguard surge arresters, the users of DEHNguard S can
DEHNguard S product family. Be it as a single device or in combination rely on the dual Thermo Dynamic Control SPD monitoring device. This
with other devices – DEHNguard S surge arresters always provide the ensures maximum reliability of the devices, even under unfavourable
right protective circuit. The modern Red/Line family design and its univer- environmental conditions. The green and red indicator shows if
sal features ensure safety and user-friendliness. The module release but- DEHNguard S is ready for operation. Apart from the standard visual indi-
ton and the approved Thermo Dynamic Control SPD monitoring device cator, DEHNguard S ... FM features a three-pole terminal for remote sig-
with dual tripping performance characterise the devices of the nalling. With its floating changeover contact, the remote signal can be
DEHNguard S series. used as a break or make contact according to the particular circuit con-
cept. The multifunctional terminals of DEHNguard S surge arresters are
Experience of decades in the international use of surge arresters has fur- suitable for connecting conductors and busbars, allowing an easy connec-
ther improved the latest DEHNguard generation compared to the previous tion to other DIN rail mounted devices. Series connection according to IEC
types. 60364-5-53 for optimal protection is therefore possible for a wide range
of applications.
The module locking system, which is unique for use with surge protective
devices, fixes the protection module and the base part firmly in place.
Neither vibration during transport nor the enormous electromagnetic
forces of discharge can loosen this connection. Nevertheless, the modules
can be easily replaced without tools by simply pressing the user-friendly
module release button of the protection modules.

In order to avoid incorrect insertion by the installer or user when replac-


ing the protection modules, every base part and protection module is
mechanically coded by the manufacturer.

88 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® S / DEHNguard® S FM


952 078 DG S 48
952 071 DG S 75

SURGE ARRESTERS – TYPE 2 DEHNguard S ...


952 072 DG S 150
952 070 DG S 275
952 073 DG S 320
952 074 DG S 385
952 075 DG S 440
952 076 DG S 600

DG S 48
952 078
DG S 75
952 071
DG S 150
952 072
DG S 275
952 070
DG S 320
952 073
DG S 385
952 074
DG S 440
952 075
DG S 600
952 076

Dimension drawing DG S ... Basic circuit diagram DG S ...

DG S ...: Single-pole, pluggable surge arrester consisting of a base part and plug-in protection
module

DG S 48 DG S 75 DG S 150 DG S 275 DG S 320 DG S 385 DG S 440 DG S 600


SPD according to EN 61643-11 Type 2 Type 2 Type 2 Type 2 Type 2 Type 2 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II Class II Class II Class II Class II Class II Class II
Max. continuous operat. a.c. volt. UC 48 V 75 V 150 V 275 V 320 V 385 V 440 V 600 V
Max. continuous operat. d.c. volt. UC 60 V 100 V 200 V 350 V 420 V 500 V 585 V 600 V
Nominal discharge current (8/20 μs) In 10 kA 10 kA 15 kA 20 kA 20 kA 20 kA 20 kA 15 kA
Max. discharge current (8/20 μs) Imax 25 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 30 kA
Voltage protection level UP ) 0.3 kV ) 0.4 kV ) 0.7 kV ) 1.25 kV ) 1.5 kV ) 1.75 kV ) 2 kV ) 2.5 kV
Voltage protection level at 5 kA UP ) 0.25 kV ) 0.35 kV ) 0.55 kV ) 1 kV ) 1.2 kV ) 1.35 kV ) 1.7 kV ) 2 kV
Response time tA ) 25 ns ) 25 ns ) 25 ns ) 25 ns ) 25 ns ) 25 ns ) 25 ns ) 25 ns

Surge Arresters Type 2


Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG 100 A gL/gG
Short-circuit withstand capability for max.
mains-side overcurrent protection 50 kArms 50 kArms 50 kArms 50 kArms 25 kArms 25 kArms 25 kArms 25 kArms
Temporary overvoltage (TOV) UT 70 V / 5 sec. 90 V / 5 sec. 175 V / 5 sec. 335 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec. 580 V / 5 sec. 600 V / 5 sec.
TOV characteristics withstand withstand withstand withstand withstand withstand withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red green / red green / red green / red green / red green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20
Capacity 1 mod., DIN 43880
Approvals, Certifications — KEMA, VDE, KEMA, VDE, KEMA, VDE, KEMA, VDE, KEMA, VDE, KEMA, VDE, KEMA, VDE,
UL, CSA UL, VdS, CSA UL, VdS, CSA UL, VdS, CSA UL, VdS, CSA UL, VdS, CSA UL, VdS, CSA

Ordering information
Type DG S 48 DG S 75 DG S 150 DG S 275 DG S 320 DG S 385 DG S 440 DG S 600
Part No. 952 078 952 071 952 072 952 070 952 073 952 074 952 075 952 076
Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® S / DEHNguard® S FM


Varistor-based protection module
952 018
48
952 011
75
952 012
DG MOD

DG MOD

DG MOD
150
952 010 DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


275
952 013
320
952 014
DG MOD

DG MOD

DEHNguard S ... surge arresters


385
DG
952MOD
015 48 DG MOD
952
440 018
DG
952MOD
016 75 DG MOD
952
600 011
DG MOD 150
952 012
DG MOD 275
952 010
DG MOD 320
PU Part
952 013

Type
DG MOD 385
952 014
DG MOD 440
pc(s). No.
952 015

DG MOD 48
DG MOD 600
952 016
1 952 018
DG MOD 75 1 952 011
DG MOD 150 1 952 012
DG MOD 275 1 952 010
DG MOD 320 1 952 013
DG MOD 385 1 952 014
DG MOD 440 1 952 015
DG MOD 600 1 952 016

www.dehn.de 89
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® S / DEHNguard® S FM POWER SUPPLY SYSTEMS


952 098 DG S 48
FM

DEHNguard S ... FM SURGE ARRESTERS – TYPE 2


952 091 DG S 75
FM
952 092 DG S 150
FM
952 090 DG S 275
FM
952 093 DG S 320
FM
952 094 DG S 385
FM
952 095 DG S 440
FM
952 096 DG S 600
FM

DG S 48 FM
952 098
DG S 75 FM
952 091
DG S 150 FM
952 092
DG S 275 FM
952 090
DG S 320 FM
952 093
DG S 385 FM
952 094
DG S 440 FM
952 095
DG S 600 FM
12 952 096

11
14

Basic circuit diagram DG S ... FM Dimension drawing DG S ... FM

DG S ... FM: Single-pole, pluggable surge arrester consisting of a base part and plug-in protection
module; with floating remote signalling contact

DG S 48 FM DG S 75 FM DG S 150 FM DG S 275 FM DG S 320 FM DG S 385 FM DG S 440 FM DG S 600 FM


SPD according to EN 61643-11 Type 2 Type 2 Type 2 Type 2 Type 2 Type 2 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II Class II Class II Class II Class II Class II Class II
Max. continuous operat. a.c. volt. UC 48 V 75 V 150 V 275 V 320 V 385 V 440 V 600 V
Max. continuous operat. d.c. volt. UC 60 V 100 V 200 V 350 V 420 V 500 V 585 V 600 V
Nominal discharge current (8/20 μs) In 10 kA 10 kA 15 kA 20 kA 20 kA 20 kA 20 kA 15 kA
Max. discharge current (8/20 μs) Imax 25 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 30 kA
Voltage protection level UP ) 0.3 kV ) 0.4 kV ) 0.7 kV ) 1.25 kV ) 1.5 kV ) 1.75 kV ) 2 kV ) 2.5 kV
Voltage protection level at 5 kA UP ) 0.25 kV ) 0.35 kV ) 0.55 kV ) 1 kV ) 1.2 kV ) 1.35 kV ) 1.7 kV ) 2 kV
Response time tA ) 25 ns ) 25 ns ) 25 ns ) 25 ns ) 25 ns ) 25 ns ) 25 ns ) 25 ns
Surge Arresters Type 2

Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG 100 A gL/gG
Short-circuit withstand capability for max.
mains-side overcurrent protection 50 kArms 50 kArms 50 kArms 50 kArms 25 kArms 25 kArms 25 kArms 25 kArms
Temporary overvoltage (TOV) UT 70 V / 5 sec. 90 V / 5 sec. 175 V / 5 sec. 335 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec. 580 V / 5 sec. 600 V / 5 sec.
TOV characteristics withstand withstand withstand withstand withstand withstand withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red green / red green / red green / red green / red green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20
Capacity 1 mod., DIN 43880
Approvals, Certifications — KEMA, VDE, KEMA, VDE, KEMA, VDE, KEMA, VDE, KEMA, VDE, KEMA, VDE, KEMA, VDE,
UL, CSA UL, VdS, CSA UL, VdS, CSA UL, VdS, CSA UL, VdS, CSA UL, VdS, CSA UL, VdS, CSA
Type of remote signalling contact changeover contact
Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible

Ordering information
Type DG S 48 FM DG S 75 FM DG S 150 FM DG S 275 FM DG S 320 FM DG S 385 FM DG S 440 FM DG S 600 FM
Part No. 952 098 952 091 952 092 952 090 952 093 952 094 952 095 952 096
Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).
952 018
48
952 011
75
952 012
DG MOD

DG MOD

DG MOD
Varistor-based protection module
150
952 010 DG MOD
275
952 013
320
952 014
DG MOD

DG MOD
DG MOD ...: Varistor-based protection module for DEHNguard M ... and
385
DG
952MOD
952
015 48
440 018
DG
952MOD
952
016 75
600 011
DG MOD

DG MOD
DEHNguard S ... surge arresters
DG MOD 150
952 012
DG MOD 275
952 010
DG MOD 320
PU Part
952 013
DG MOD 385
952 014
DG MOD 440
Type pc(s). No.
952 015
DG MOD 600
952 016
DG MOD 48 1 952 018
DG MOD 75 1 952 011
DG MOD 150 1 952 012
DG MOD 275 1 952 010
DG MOD 320 1 952 013
DG MOD 385 1 952 014
DG MOD 440 1 952 015
DG MOD 600 1 952 016

90 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® S / DEHNguard® S FM


952 077 DG S WE
600

SURGE ARRESTERS – TYPE 2 DEHNguard S WE 600 (FM)


952 097 DG S WE
600 FM

DG S WE 600
952 077
DG S WE 600 FM
952 097

12
11
14

Dimension drawing DG S WE 600 FM Basic circuit diagram DG S WE 600 FM

DG S WE 600 (FM): Single-pole, pluggable surge arrester with a rated varistor voltage Umov = 750 V
a.c., consisting of base part and plug-in protection module; FM version with
floating remote signalling contact

DG S WE 600 DG S WE 600 FM
SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Max. continuous operating a.c. voltage UC 600 V 600 V
Rated varistor voltage a.c. Umov 750 V 750 V
Nominal discharge current (8/20 μs) In 15 kA 15 kA
Max. discharge current (8/20 μs) Imax 25 kA 25 kA
Voltage protection level UP ) 3 kV ) 3 kV

Surge Arresters Type 2


Voltage protection level at 5 kA UP ) 2.5 kV ) 2.5 kV
Response time tA ) 25 ns ) 25 ns
Max. mains-side overcurrent protection 100 A gL/gG 100 A gL/gG
Short-circuit withstand capability for max. mains-side overcurrent protection 25 kArms 25 kArms
Temporary overvoltage (TOV) UT 900 V / 5 sec. 900 V / 5 sec.
TOV characteristics withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 1 mod., DIN 43880 1 mod., DIN 43880
Approvals, Certifications UL, CSA UL, CSA
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DG S WE 600 DG S WE 600 FM
Part No. 952 077 952 097
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® S / DEHNguard® S FM


Varistor-based protection module for
952 017
750
DG MOD

DEHNguard M (S) WE
DG MOD 750: Varistor-based protection module for DEHNguard M WE
DG MOD 750
952 017

... and DEHNguard S WE ... with a rated varistor voltage Umov = 750 V
a.c.
PU Part
Type pc(s). No.
DG MOD 750 1 952 017

www.dehn.de 91
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNgap C S POWER SUPPLY SYSTEMS


N-PE surge arrester SURGE ARRESTERS – TYPE 2
SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1

• Specifically designed for use in ”3+1” and


”1+1” circuits of TT systems acc. to IEC 60364-
5-53 between neutral conductor N and protec-
tive earth conductor PE
• High discharge capacity
• Two-part unit consisting of a base part and
spark-gap-based plug-in protection module
• Energy coordination within the Red/Line pro-
duct family
• Operating state/fault indication by indicator
flag in the inspection window
• With remote signalling contact for SPD moni-
toring device
• Easy replacement of protection modules with-
out tools due to module release button For protecting low-voltage consumer´s installations against surges. For
installation in conformity with the lightning protection zones concept at
• Vibration- and shock-tested according to EN the boundaries from 0B – 1 and higher.
60068-2
Surge Arresters Type 2

DEHNgap C S: N-PE surge arrester consisting of a base part and plug-in protection module
DEHNgap C S FM: With remote signalling contact for monitoring device (floating changeover contact)

The N-PE surge arrester DEHNgap C S ideally complements the single-pole Monitoring of the arrester temperature and an integrated disconnector,
DEHNguard S surge protective devices. Being a total current arrester which is connected in series to the surge arrester, further increase the
between neutral conductor and protective conductor in TT systems, its safety of DEHNgap C S.
function is to ensure that the requirements for protection of persons and
material assets in so-called ”3+1” and ”1+1” circuits are fulfilled. The green and red indicator shows if DEHNgap C S is ready for operation.

With the modern Red/Line design, DEHNgap C S provides safety and per- Apart from the standard visual indicator, DEHNgap C S ... FM incorporates
formance just like the DEHNguard S devices. The module locking system, a three-pole terminal for remote signalling. With its floating changeover
which is unique for use with surge protective devices, combines the spark- contact, the remote signal can be used as a break or make contact accord-
gap-based module and base part to a powerful unit. Neither vibration ing to the particular circuit concept. The N-PE surge arrester DEHNgap C
during transport nor the enormous electromagnetic forces of discharge S features multifunctional terminals for connection of conductors and
can loosen the protection module. Nevertheless, the protection modules busbars, allowing easy wiring with other DIN rail mounted devices. Series
can be easily replaced without tools by simply pressing the module connection according to IEC 60364-5-53 for optimal protection is there-
release button of the protection module. The mechanical coding at the fore possible for a wide range of applications.
protection module and base part prevents incorrect insertion by the
installer or user.

92 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNgap C S


952 030 DGP C S
952 035 DGP C S

SURGE ARRESTERS – TYPE 2 DEHNgap C S (FM)


FM

DGP C S
952 030
DGP C S FM
952 035

12
11
14

Dimension drawing DGP C S FM Basic circuit diagram DGP C S FM

DGP C S (FM): N-PE surge arrester; FM version with floating remote signalling contact

DGP C S DGP C S FM
SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Max. continuous operating a.c. voltage UC 255 V 255 V
Nominal discharge current (8/20 μs) In 20 kA 20 kA
Max. discharge current (8/20 μs) Imax 40 kA 40 kA
Follow current extinguishing capability Ifi 100 Arms 100 Arms
Lightning impulse current (10/350 μs) Iimp 12 kA 12 kA

Surge Arresters Type 2


Voltage protection level UP ) 1.5 kV ) 1.5 kV
Response time tA ) 100 ns ) 100 ns
Temporary overvoltage (TOV) UT 1200 V / 200 ms 1200 V / 200 ms
TOV characteristics withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 1 mod., DIN 43880 1 mod., DIN 43880
Approvals, Certifications KEMA, VDE, UL, VdS KEMA, VDE, UL, VdS
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DGP C S DGP C S FM
Part No. 952 030 952 035
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNgap C S


N-PE spark-gap-based protection module for
952 060
MOD
DGP C

DEHNgap C S
DGP C MOD: N-PE spark-gap-based protection module for single-pole
DGP C MOD
952 060

N-PE surge arresters of type DEHNgap DGP C S ...


PU Part
Type pc(s). No.
DGP C MOD 1 952 060

www.dehn.de 93
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

Protection Module POWER SUPPLY SYSTEMS


for DEHNguard® M, ... S and DEHNgap C S SURGE ARRESTERS – TYPE 2
SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1

• High discharge capacity due to heavy-duty zinc


oxide varistors/spark gaps
• High reliability due to ”Thermo Dynamic
Control” SPD monitoring device
• Energy coordination within the Red/Line pro-
duct family
• Operating state/fault indication by indicator
flag in the inspection window
• Easy replacement of protection modules with-
out tools by module locking system with mod-
ule release button
• The plug-in protection module can be replaced
without the need to de-energise and without
removing the cover plate of the distribution
board
For protecting low-voltage consumer´s installations against surges. For
• Vibration- and shock-tested according to EN installation in conformity with the lightning protection zones concept at
60068-2 the boundaries from 0B – 1 and higher.
Surge Arresters Type 2

DEHNguard MOD ...: Varistor-based protection module for DEHNguard M ... and DEHNguard S
DEHNguard MOD 750: Varistor-based protection module for DEHNguard M WE 600 and DEHNguard S WE 600
DEHNguard MOD NPE: N-PE spark-gap-based protection module for two- and four-pole DEHNguard M TT ... surge
arresters
DEHNgap C MOD: N-PE spark-gap-based protection module for single-pole DEHNgap C S ... N-PE surge arresters
DEHNguard MOD CI 275: Varistor-based protection module for DEHNguard M CI
DEHNguard MOD ... VA: Varistor- and spark-gap-based protection module for DEHNguard S ... VA
DEHNguard MOD PV SCI ...: Varistor-based protection module for DEHNguard M YPV SCI

The varistor- and spark-gap-based protection modules of the DEHNguard In order to avoid incorrect insertion by the installer or user when replac-
M, DEHNguard S and DEHNgap C S devices distinguish themselves ing the modules, all protection modules are mechanically coded. The pro-
through their outstanding performance and sophistication. tection modules can be easily replaced without tools by simply pressing
The compact protection modules include the complete protective circuit the user-friendly module release button.
as well as the monitoring device and disconnector.
The green flag in the window indicates if the protection modules are
ready for operation.

94 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS Prot. Mod. f. DEHNguard® M, ... S and DEHNgap C S


952 018 DG MOD
48

SURGE ARRESTERS – TYPE 2 Varistor-based protection module


952 011 DG MOD
75
952 012 DG MOD
150
952 010 DG MOD
275
952 013 DG MOD
320
952 014 DG MOD
385
952 015 DG MOD
440
952 016 DG MOD
600

DG MOD 48
952 018
DG MOD 75
952 011
DG MOD 150
952 012
DG MOD 275
952 010
DG MOD 320
952 013
DG MOD 385
952 014
DG MOD 440
952 015
DG MOD 600
952 016

Dimension drawing DG MOD varistor-based Basic circuit diagram DG MOD varistor-based


protection module protection module
DG MOD ...: Varistor-based protection module for DEHNguard M ... and DEHNguard S ... surge
arresters

DG MOD 48 DG MOD 75 DG MOD 150 DG MOD 275 DG MOD 320 DG MOD 385 DG MOD 440 DG MOD 600
Nominal discharge current (8/20 μs) In 10 kA 10 kA 15 kA 20 kA 20 kA 20 kA 20 kA 15 kA
Max. discharge current (8/20 μs) Imax 25 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 30 kA
Max. continuous op. a.c. voltage UC 48 V 75 V 150 V 275 V 320 V 385 V 440 V 600 V
Max. continuous op. d.c. voltage UC 60 V 100 V 200 V 350 V 420 V 500 V 585 V 600 V

Ordering information
Type DG MOD 48 DG MOD 75 DG MOD 150 DG MOD 275 DG MOD 320 DG MOD 385 DG MOD 440 DG MOD 600
Part No. 952 018 952 011 952 012 952 010 952 013 952 014 952 015 952 016
Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Surge Arresters Type 2


952 017 DG MOD
750

Varistor-based protection module for DEHNguard M (S) WE

DG MOD 750
952 017

Dimension drawing DG MOD 750 varistor-based Basic circuit diagram DG MOD 750 varistor-based
protection module protection module
DG MOD 750: Varistor-based protection module for DEHNguard M WE ... and DEHNguard S WE ...
surge arresters with a rated varistor voltage Umov = 750 V a.c.

DG MOD 750
Nominal discharge current (8/20 μs) In 15 kA
Max. discharge current (8/20 μs) Imax 25 kA
Max. continuous operating a.c. voltage UC 600 V
Max. continuous operating d.c. voltage UC 600 V
Rated varistor voltage Umov 750 V

Ordering information
Type DG MOD 750
Part No. 952 017
Packing unit 1 pc(s).

www.dehn.de 95
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

Prot. Mod. f. DEHNguard® M, ... S and DEHNgap C S POWER SUPPLY SYSTEMS


952 050 DG MOD
NPE

N-PE spark-gap-based protection module SURGE ARRESTERS – TYPE 2


for DEHNguard M TT ...
DG MOD NPE
952 050

Basic circuit diagram DG MOD NPE Dimension drawing DG MOD NPE

DG MOD NPE: N-PE spark-gap-based protection module for two- and four-pole DEHNguard DG M
TT ... surge arresters

DG MOD NPE
Nominal discharge current (8/20 μs) In 20 kA
Max. discharge current (8/20 μs) Imax 40 kA
Max. continuous operating a.c. voltage UC 255 V

Ordering information
Type DG MOD NPE
Part No. 952 050
Packing unit 1 pc(s).
Surge Arresters Type 2

952 060 DGP C


MOD

N-PE spark-gap-based protection module for DEHNgap C S

DGP C MOD
952 060

Basic circuit diagram DGP C MOD Dimension drawing DGP C MOD

DGP C MOD: N-PE spark-gap-based protection module for single-pole N-PE surge arresters of
type DEHNgap DGP C S ...

DGP C MOD
Nominal discharge current (8/20 μs) In 20 kA
Max. discharge current (8/20 μs) Imax 40 kA
Max. continuous operating a.c. voltage UC 255 V

Ordering information
Type DGP C MOD
Part No. 952 060
Packing unit 1 pc(s).

96 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS Prot. Mod. f. DEHNguard® M, ... S and DEHNgap C S


952 053 DG MOD PV SCI 300
952 051 DG MOD PV SCI 500

SURGE ARRESTERS – TYPE 2 Varistor-based protection module


952 054 DG MOD PV SCI 600

for DEHNguard M YPV SCI


DG MOD PV SCI 300
952 053
DG MOD PV SCI 500
952 051
DG MOD PV SCI 600
952 054

Dimension drawing DG MOD PV SCI Basic circuit diagram DG MOD PV SCI

DG MOD PV SCI ...: Protection module for DEHNguard M YPV SCI ... comprising a varistor con-
nected in parallel with a short-circuiting device with integrated back-up fuse

DG MOD PV SCI 300 DG MOD PV SCI 500 DG MOD PV SCI 600


Nominal discharge current (8/20 μs) In 12.5 kA 12.5 kA 12.5 kA
Max. discharge current (8/20 μs) Imax 25 kA 25 kA 25 kA
Max. continuous operating d.c. voltage UC 300 V 500 V 600 V

Ordering information
Type DG MOD PV SCI 300 DG MOD PV SCI 500 DG MOD PV SCI 600
Part No. 952 053 952 051 952 054
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Surge Arresters Type 2


952 025 DG MOD 75 VA
952 027 DG MOD 275 VA

Varistor-and spark-gap-based protection module for DEHNguard S ... VA


952 029 DG MOD 385 VA

DG MOD 75 VA
952 025
DG MOD 275 VA
952 027
DG MOD 385 VA
952 029

Dimension drawing DG MOD ... VA Basic circuit diagram DG S ... VA

DG MOD ... VA: Protection module for DEHNguard S ... VA comprising a varistor connected in
series with a spark gap

DG MOD 75 VA DG MOD 275 VA DG MOD 385 VA


Nominal discharge current (8/20 μs) In 10 kA 10 kA 10 kA
Max. discharge current (8/20 μs) Imax 20 kA 20 kA 20 kA
Max. continuous operating a.c. voltage UC 75 V 275 V 385 V
Max. continuous operating d.c. voltage UC 100 V 350 V 500 V

Ordering information
Type DG MOD 75 VA DG MOD 275 VA DG MOD 385 VA
Part No. 952 025 952 027 952 029
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

www.dehn.de 97
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

Prot. Mod. f. DEHNguard® M, ... S and DEHNgap C S POWER SUPPLY SYSTEMS


952 020 DG MOD CI 275

Varistor-based protection module SURGE ARRESTERS – TYPE 2


for DEHNguard M CI
DG MOD CI 275
952 020

Basic circuit diagram DG MOD CI 275 Dimension drawing DG MOD CI 275

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 comprising a varistor connected
in series with the integrated backup fuse

DG MOD CI 275
Nominal discharge current (8/20 μs) In 12.5 kA
Max. discharge current (8/20 μs) Imax 25 kA
Max. continuous operating a.c. voltage UC 275 V

Ordering information
Type DG MOD CI 275
Part No. 952 020
Surge Arresters Type 2

Packing unit 1 pc(s).

98 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® ... H LI


SURGE ARRESTERS – TYPE 2 Multipole surge arrester with
SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1 ‘’Pro-Active Thermo Control’’
• Prewired complete unit for standard system
configurations consisting of a base part and
plug-in protection modules
• Clear operating state indication due to 3-stage
visual service life indicator <GREEN-YELLOW-
RED> with linked remote signalling function
• ”Pro-Active Thermo Control” SPD monitoring
device
• Recommends the user to replace the protection
module <YELLOW> before the SPD is threat-
ened by overloads
• Energy coordination within the Red/Line pro-
duct family

For protecting low-voltage consumer´s installations against surges. For


installation in conformity with the lightning protection zones concept at
the boundaries from 0B – 1 and higher.

Surge Arresters Type 2


DEHNguard TNC H LI: Multipole surge arrester with service life indicator for use in TN-C systems
DEHNguard TNS H LI: Multipole surge arrester with service life indicator for use in TN-S systems
DEHNguard TT H LI: Multipole surge arrester with service life indicator for use in TT and TN-S systems (”3+1” circuit)
DEHNguard T H LI: Single-pole surge arrester with service life indicator

The single-pole and multipole surge arresters of the DEHNguard ... H LI the triple monitoring device of each circuit with Pro-Active Thermo
family provide maximum safety and user-friendliness and set new stan- Control and the coding of the pluggable protection modules characterise
dards in surge protection. the maximum degree of safety of the devices. Damage caused by incor-
With the Pro-Active Thermo Control concept, they are the first ”intelli- rect subsequent insertion by the installer or the user is very unlikely.
gent” surge arresters to warn the user of failures of the surge protection With DEHNguard T H LI, the user is also provided with a single-pole device
system in due time. With this technique, this new SPD monitoring device for universal use.
meets the steadily increasing requirements on the availability of electrical All types of DEHNguard ... H LI feature a three-pole terminal for remote
systems in industrial, commercial and domestic environments. The 3-stage signalling. With their floating changeover contact, the remote signal can
visual indicator along with a floating changeover contact for remote sig- be used as a make or break con-
nalling always informs the user on the operating state of the SPD. If there tact according to the particular
is a risk that the varistor might be irreversibly damaged due to an circuit concept. All surge arresters
increased energy load, the user is informed by the yellow indicator and of the DEHNguard ... H LI family
the remote signalling function that the surge protection module should be incorporate multifunctional ter-
replaced – before the installation is unprotected! minals for the connection of con-
Like the well-known multipole DEHNguard family, the application-based ductors and busbars, allowing
type designation makes the choice of products of the prewired complete easy wiring with other DIN rail
units considerably easier. Less installation errors and saving of installation mounted devices.
work at the same time are unbeatable advantages for the customer. Both

Yellow indicator flag: Replacement of


the protection module recommended

www.dehn.de 99
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® ... H LI POWER SUPPLY SYSTEMS


950 160 DG TNC
H230 400 LI

DEHNguard TNC H LI SURGE ARRESTERS – TYPE 2

PEN DG TNC H230 400 LI


950 160

12
11
14

L1 L2 L3

Basic circuit diagram DG TNC H230 400 LI Dimension drawing DG TNC H230 400 LI

DG TNC H LI: Multipole surge arrester for use in TN-C systems with ”Pro-Active Thermo Control”
SPD monitoring device with 3-stage visual indicator.

DG TNC H230 400 LI


SPD according to EN 61643-11 Type 2
SPD according to IEC 61643-1 Class II
Nominal a.c. voltage 230/400 V
Max. continuous operating a.c. voltage UC 275 V
Nominal discharge current (8/20 μs) In 20 kA
Max. discharge current (8/20 μs) Imax 65 kA
Voltage protection level UP ) 1.25 kV
Surge Arresters Type 2

Voltage protection level at 5 kA UP ) 1 kV


Response time tA ) 25 ns
Max. mains-side overcurrent protection 160 A gL/gG
Short-circuit withstand capability for max. mains-side overcurrent protection 20 kArms
Temporary overvoltage (TOV) UT 335 V / 5 sec.
TOV characteristics withstand
Operating temperature range -40°C...+55°C
Indication of disconnector green-yellow-red
Cross-sectional area (min.) 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IP 20
Capacity 3 mods., DIN 43880
Approvals, Certifications KEMA
Type of remote signalling contact changeover contact
Switching capacity a.c. 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible

Ordering information
Type DG TNC H230 400 LI
Part No. 950 160
Packing unit 1 pc(s).

Accessory Part for DEHNguard® ... H LI


Varistor-based protection module with Pro-Active
950 130
950 131
T H 275 LI
T H 385 LI

Thermo Control
PU
T H 275 LI
950 130
T H 385 LI
Part
950 131
Type pc(s). No.
T H 275 LI 1 950 130

100 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® ... H LI


950 170 DG TNS
H230 400 LI

SURGE ARRESTERS – TYPE 2 DEHNguard TNS H LI

DG TNS H230 400 LI


PE
950 170

12
11
14

L1 L2 L3 N

Dimension drawing DG TNS H230 400 LI Basic circuit diagram DG TNS H 230 400 LI

DG TNS H LI: Multipole surge arrester for use in TN-S systems with ”Pro-Active Thermo Control”
SPD monitoring device with 3-stage visual indicator

DG TNS H230 400 LI


SPD according to EN 61643-11 Type 2
SPD according to IEC 61643-1 Class II
Nominal a.c. voltage 230/400 V
Max. continuous operating a.c. voltage UC 275 V
Nominal discharge current (8/20 μs) In 20 kA
Max. discharge current (8/20 μs) Imax 65 kA
Voltage protection level UP ) 1.25 kV

Surge Arresters Type 2


Voltage protection level at 5 kA UP ) 1 kV
Response time tA ) 25 ns
Max. mains-side overcurrent protection 160 A gL/gG
Short-circuit withstand capability for max. mains-side overcurrent protection 20 kArms
Temporary overvoltage (TOV) UT 335 V / 5 sec.
TOV characteristics withstand
Operating temperature range -40°C...+55°C
Indication of disconnector green-yellow-red
Cross-sectional area (min.) 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IP 20
Capacity 4 mods., DIN 43880
Approvals, Certifications KEMA
Type of remote signalling contact changeover contact
Switching capacity a.c. 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible

Ordering information
Type DG TNS H230 400 LI
Part No. 950 170
Packing unit 1 pc(s).

Accessory Part for DEHNguard® ... H LI


Varistor-based protection module with Pro-Active 950 130
950 131
T H 275 LI
T H 385 LI

Thermo Control
PU Part T H 275 LI
950 130
T H 385 LI
950 131
Type pc(s). No.
T H 275 LI 1 950 130

www.dehn.de 101
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® ... H LI POWER SUPPLY SYSTEMS


950 150 DG TT
H230 400 LI

DEHNguard TT H LI SURGE ARRESTERS – TYPE 2


950 151 DG TT
H230 400 LI385

PE DG TT H230 400 LI
950 150
DG TT H230 400 LI385
950 151

12
11
14

L1 L2 L3 N

Basic circuit diagram DG TT H230 400 LI Dimension drawing DG TT H230 400 LI

DG TT H LI: Multipole surge arrester with ”Pro-Active Thermo Control” SPD monitoring device
with 3-stage visual indicator for use in TT and TN-S systems (”3+1” circuit)

DG TT H230 400 LI DG TT H230 400 LI385


SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Nominal a.c. voltage 230/400 V 230/400 V
Max. continuous operating a.c. voltage [L-N] 275 V 385 V
Max. continuous operating a.c. voltage [N-PE] 255 V 255 V
Max. discharge current (8/20 μs) [L-N] Imax 65 kA 65 kA
Max. discharge current (8/20 μs) [N-PE] 65 kA 65 kA
Lightning impulse current (10/350 μs) [N-PE] 12 kA 12 kA
Voltage protection level [L-N] ) 1.25 kV ) 1.75 kV
Surge Arresters Type 2

Voltage protection level [L-N] at 5 kA ) 1 kV ) 1.35 kV


Voltage protection level [N-PE] ) 1.5 kV ) 1.5 kV
Follow current extinguishing capability [N-PE] 100 Arms 100 Arms
Response time [L-N] ) 25 ns ) 25 ns
Response time [N-PE] ) 100 ns ) 100 ns
Max. mains-side overcurrent protection 160 A gL/gG 160 A gL/gG
Short-circuit withstand capability for max. mains-side overcurrent protection 20 kArms 20 kArms
TOV characteristics withstand withstand
Temporary overvoltage (TOV) [L-N] 335 V / 5 sec. 385 V / 5 sec.
Temporary overvoltage (TOV) [N-PE] 1200 V / 200 ms 1200 V / 200 ms
Operating temperature range -40°C...+55°C -40°C...+55°C
Indication of disconnector green-yellow-red green-yellow-red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 4 mods., DIN 43880 4 mods., DIN 43880
Approvals, Certifications KEMA KEMA
Type of remote signalling contact changeover contact changeover contact
Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information
Type DG TT H230 400 LI DG TT H230 400 LI385
Part No. 950 150 950 151
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® ... H LI Accessory Part for DEHNguard® ... H LI
Varistor-based protection module with Pro-Active 950 130
950 131
T H 275 LI
T H 385 LI
900 216 T C H 255

N-PE spark-gap-based protection module


Thermo Control PU Part
PU
T H 275 LI
950 130
T H 385 LI
Part T C H 255
900 216
Type pc(s). No.
950 131
Type pc(s). No. T C H 255 1 900 216
T H 275 LI 1 950 130
T H 385 LI 1 950 131

102 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® ... H LI


950 120 DG T H
275 LI

SURGE ARRESTERS – TYPE 2 DEHNguard T H LI


950 121 DG T H
385 LI

DG T H 275 LI
950 120
DG T H 385 LI
950 121

12
11
14

Dimension drawing DG T H ... LI Basic circuit diagram DG T H ... LI

DG T H LI: Single-pole, pluggable surge arrester with ”Pro-Active Thermo Control” SPD monitor-
ing device with 3-stage visual indicator

DG T H 275 LI DG T H 385 LI
SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Nominal a.c. voltage 230 V 230 V
Max. continuous operating a.c. voltage UC 275 V 385 V
Nominal discharge current (8/20 μs) In 20 kA 20 kA
Max. discharge current (8/20 μs) Imax 65 kA 65 kA
Voltage protection level UP ) 1.25 kV ) 1.75 kV
Voltage protection level at 5 kA UP ) 1 kV ) 1.35 kV
Response time tA ) 25 ns ) 25 ns

Surge Arresters Type 2


Max. mains-side overcurrent protection 160 A gL/gG 160 A gL/gG
Short-circuit withstand capability for max. mains-side overcurrent protection 20 kArms 20 kArms
Temporary overvoltage (TOV) UT 335 V / 5 sec. 385 V / 5 sec.
TOV characteristics withstand withstand
Operating temperature range -40°C...+55°C -40°C...+55°C
Indication of disconnector green-yellow-red green-yellow-red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 1 mods., DIN 43880 1 mods., DIN 43880
Approvals, Certifications KEMA KEMA
Type of remote signalling contact changeover contact changeover contact
Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information
Type DG T H 275 LI DG T H 385 LI
Part No. 950 120 950 121
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® ... H LI


Varistor-based protection module with Pro-Active 950 130
950 131
T H 275 LI
T H 385 LI

Thermo Control
PU Part T H 275 LI
950 130
T H 385 LI
950 131
Type pc(s). No.
T H 275 LI 1 950 130
T H 385 LI 1 950 131

www.dehn.de 103
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® M YPV SCI ... (FM) POWER SUPPLY SYSTEMS


Multipole arrester for use in photovoltaic systems SURGE ARRESTERS – TYPE 2
with three-step d.c. switching device SPD Type 2 classification according to EN 61643-11
SPD Class II classification according to IEC 61643-1

• Prewired modular complete unit for use in pho-


tovoltaic systems consisting of a base part and
plug-in protection modules
• Combined disconnection and short-circuiting
device with safe electrical isolation in the pro-
tection module prevents fire damage due to
d.c. arcs
• Approved fault-resistant Y circuit prevents
damage to the surge protective devices in case
of insulation faults in the generator circuit
• Safe replacement of protection modules with-
out arc formation due to integrated d.c. fuse
• Suitable for all PV systems in accordance with
IEC 60364-7-712

For protecting low-voltage consumer’s installations against surges. For


use in accordance with IEC 60364-7-712:2002-05 (installation of photo-
voltaic power supply systems)
Surge Arresters Type 2

DEHNguard M YPV SCI 600: Multipole, modular surge arrester with three-step d.c. switching device; for use in photo-
voltaic systems up to 600 V
DEHNguard M YPV SCI 1000: For photovoltaic systems up to 1000 V
DEHNguard M YPV SCI 1200: For photovoltaic systems up to 1200 V
DEHNguard M YPV SCI ... FM: With remote signalling contact for a monitoring device (floating changeover contact)

The modular surge arresters of type DEHNguard M YPV SCI ... (FM) were photovoltaic systems was integrated into the short-circuit path to ensure
specifically designed for protecting equipment in photovoltaic systems. safe electrical isolation in case of a faulty surge protection module, allow-
The innovative three-step d.c. switching device makes these arresters ing de-energised replacement of the protection module without arc for-
especially safe so that they fulfil the requirements for modern photovolta- mation in case of a faulty surge protection module. This unique design
ic systems. combines surge protection, fire protection and the protection of persons.
The application features of the modular Red/Line family design are simi- DEHNguard M YPV SCI ... (FM) can be used in all low-, medium- and high-
larly unique as the three-step d.c. switching device. The module locking performance photovoltaic systems without backup fuse due to this inno-
system firmly fixes the protection modules in the base part of the arrester. vative and unique design.
Neither shock nor vibration nor the enormous forces of discharge affect
the safe connection to the protection module. Nevertheless, the protec- The green and red indicator flags show if every protective circuit is ready
tion modules can be easily replaced without tools by simply pressing the for operation. Apart from this standard visual indication, DEHNguard M
user-friendly module release button of the protection modules. Every pro- YPV SCI ... (FM) arresters also feature a three-pole terminal for remote
tective circuit of the DEHNguard M YPV SCI ... (FM) and every protection signalling. With their floating changeover contact, the remote signal can
module is mechanically coded to avoid incorrect insertion by the installer be used as make or break contact according to the particular circuit con-
or user. cept. Like all surge arresters of the modular DEHNguard M family,
To fulfil the specific requirements for photovoltaic systems, the approved DEHNguard M YPV SCI ... (FM) arresters incorporate multifunctional ter-
safety philosophies of the fault-resistant Y circuit consisting of three pro- minals on a standardised spacing of 1 module for connecting conductors
tective circuits of the varistor and the combined disconnection and short- and busbars, allowing easy wiring with other DIN rail mounted devices.
circuiting device were integrated in a single device.
This synergy reduces the probability of an arrester failure in case of oper- Switching stages:
ating and fault states which have to be considered in photovoltaic sys- 1. 2. 3.
tems. This ensures that the arrester is protected in case of overload with- Original state Response of the Arc extinction Safe electrical
disconnection device isolation
out presenting a fire risk to the system. Even in case of voltages up to
1200 V d.c. an arc, which is likely to occur in the surge protective device
if a conventional disconnection device is activated, is extinguished imme-
diately and without risk. Fire protection is the top priority of the
DEHNguard M YPV SCI ... (FM) arrester. A fuse particularly developed for

SCI SCI SCI SCI

104 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® M YPV SCI ... (FM)


952 511 DG M YPV SCI 600
952 510 DG M YPV SCI 1000

SURGE ARRESTERS – TYPE 2 DEHNguard M YPV SCI ...


952 512 DG M YPV SCI 1200

DG M YPV SCI 600


DC+/– 9 DC–/+ NEW
952 511
DG M YPV SCI 1000
952 510
DG M YPV SCI 1200
952 512
DC+/– 9 DC–/+

Dimension drawing DG M YPV SCI ... Basic circuit diagram DG M YPV SCI ...

DG M YPV SCI ...: Multipole, modular surge arrester with three-step d.c. switching device for use
in PV systems.

DG M YPV SCI 600 DG M YPV SCI 1000 DG M YPV SCI 1200


SPD classification according to EN 61643-11 Type 2 Type 2 Type 2
SPD classification according to IEC 61643-1 Class II Class II Class II
Max. PV voltage UCPV ) 600 V ) 1000 V ) 1200 V
Max. continuous operating d.c. voltage [(DC+/DC-) —> PE] UC 300 V 500 V 600 V
Total discharge current (8/20 μs) Itotal 40 kA 40 kA 30 kA
Nominal discharge current (8/20 μs) [(DC+/DC-) —> PE] In 12.5 kA 12.5 kA 12.5 kA
Max. discharge current (8/20 μs) [(DC+/DC-) —> PE] Imax 25 kA 25 kA 25 kA

Surge Arresters Type 2


Voltage protection level UP ) 2.5 kV ) 4 kV ) 4.5 kV
Voltage protection level at 5 kA UP ) 2 kV ) 3.5 kV ) 4 kV
Response time tA ) 25 ns ) 25 ns ) 25 ns
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C
Breaking capacity of the integrated fuse 30 kA / 1000 V d.c. 30 kA / 1000 V d.c. 30 kA / 1200 V d.c.
Operating state/fault indication green / red green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20
Capacity 3 mod(s)., DIN 43880 3 mod(s)., DIN 43880 3 mod(s)., DIN 43880
Approvals, Certifications UL UL —

Ordering information
Type DG M YPV SCI 600 DG M YPV SCI 1000 DG M YPV SCI 1200
Part No. 952 511 952 510 952 512
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® M YPV SCI ... (FM) Accessory Part for DEHNguard® M YPV SCI ... (FM)
Varistor-based protection module
952 010
275
952 015
440
952 016
DG MOD

DG MOD

DG MOD
Varistor-based protection module for M YPV SCI
952 053
PV SCI 300
952 051
PV SCI 500
952 054
DG MOD

DG MOD

DG MOD
600 PV SCI 600

PU Part DG MOD PV SCI ...: Protection module for DEHNguard M YPV SCI ...
Type
DG MOD 275
952 010
pc(s). No. comprising a varistor connected in parallel with a short-circuiting
DG MOD PV SCI 300
952 053
DG MOD 440 DG MOD PV SCI 500

DG MOD 275
952 015
DG MOD 600
952 016
1 952 010 952 051

device with integrated back-up fuse


DG MOD PV SCI 600
952 054

DG MOD 440 1 952 015


PU Part
DG MOD 600 1 952 016 Type pc(s). No.
DG MOD PV SCI 300 1 952 053
DG MOD PV SCI 500 1 952 051
DG MOD PV SCI 600 1 952 054

www.dehn.de 105
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® M YPV SCI ... (FM) POWER SUPPLY SYSTEMS


952 516 DG M YPV SCI 600 FM
952 515 DG M YPV SCI 1000 FM

DEHNguard M YPV SCI ... FM SURGE ARRESTERS – TYPE 2


952 517 DG M YPV SCI 1200 FM

NEW DC+/– 9 DC–/+ DG M YPV SCI 600 FM


952 516
DG M YPV SCI 1000 FM
DC+/– 9 DC–/+ 952 515
DG M YPV SCI 1200 FM
952 517

12
11
14

Basic circuit diagram DG M YPV SCI ... FM Dimension drawing DG M YPV SCI ... FM

DG M YPV SCI ... FM: Multipole, modular surge arrester with three-step d.c. switching device for
use in PV systems with remote signalling contact (floating changeover
contact).

DG M YPV SCI 600 FM DG M YPV SCI 1000 FM DG M YPV SCI 1200 FM


SPD classification according to EN 61643-11 Type 2 Type 2 Type 2
SPD classification according to IEC 61643-1 Class II Class II Class II
Max. PV voltage UCPV ) 600 V ) 1000 V ) 1200 V
Max. continuous operating d.c. voltage [(DC+/DC-) —> PE] UC 300 V 500 V 600 V
Total discharge current (8/20 μs) Itotal 40 kA 40 kA 30 kA
Nominal discharge current (8/20 μs) [(DC+/DC-) —> PE] In 12.5 kA 12.5 kA 12.5 kA
Max. discharge current (8/20 μs) [(DC+/DC-) —> PE] Imax 25 kA 25 kA 25 kA
Surge Arresters Type 2

Voltage protection level UP ) 2.5 kV ) 4 kV ) 4.5 kV


Voltage protection level at 5 kA UP ) 2 kV ) 3.5 kV ) 4 kV
Response time tA ) 25 ns ) 25 ns ) 25 ns
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C
Breaking capacity of the integrated fuse 30 kA / 1000 V d.c. 30 kA / 1000 V d.c. 30 kA / 1200 V d.c.
Operating state/fault indication green / red green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20
Capacity 3 mod(s)., DIN 43880 3 mod(s)., DIN 43880 3 mod(s)., DIN 43880
Approvals, Certifications UL UL —
Type of remote signalling contact changeover contact changeover contact changeover contact
a.c. switching capacity 250 V/0.1 A 250 V/0.1 A 250 V/0.1 A
d.c. switching capacity 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information
Type DG M YPV SCI 600 FM DG M YPV SCI 1000 FM DG M YPV SCI 1200 FM
Part No. 952 516 952 515 952 517
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® M YPV SCI ... (FM) Accessory Part for DEHNguard® M YPV SCI ... (FM)
952 053
PV SCI 300
952 051
PV SCI 500
952 054
DG MOD

DG MOD

DG MOD
Varistor-based protection module for M YPV SCI 952 010
275
952 015
440
952 016
DG MOD

DG MOD

DG MOD
Varistor-based protection module
PV SCI 600 600

DG MOD PV SCI ...: Protection module for DEHNguard M YPV SCI ... PU Part
DG MOD PV SCI 300
952 053
comprising a varistor connected in parallel with a short-circuiting DG MOD 275
952 010
Type pc(s). No.
DG MOD PV SCI 500 DG MOD 440
952 051
DG MOD PV SCI 600
952 054
device with integrated back-up fuse
952 015
DG MOD 600
952 016
DG MOD 275 1 952 010
DG MOD 440 1 952 015
PU Part
Type pc(s). No. DG MOD 600 1 952 016
DG MOD PV SCI 300 1 952 053
DG MOD PV SCI 500 1 952 051
DG MOD PV SCI 600 1 952 054

106 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® PV ... SCP (FM)


SURGE ARRESTERS – TYPE 2 Single-pole arrester for use in
SPD Type 2 classification according to EN 61643-11
SPD Class II classification according to IEC 61643-1 photovoltaic systems with short-circuiting device
• For use in all types of PV systems in accordance
with IEC 60364-7-712
• High discharge capacity due to heavy-duty zinc
oxide varistor
• No fire risk in case of overload due to com-
bined disconnection and short-circuiting device
• Continuous current carrying capacity of the
short-circuiting device of 80 A d.c.
• Indication of overload by red flag in the inspec-
tion window and remote signalling function

For protecting photovoltaic installations against surges. For use in accor-


dance with IEC 60364-7-712:2002-05 (Installation of photovoltaic power
supply systems).

Surge Arresters Type 2


DG PV ... SCP: Single-pole surge arrester with combined disconnection and short-circuiting device for use in photovoltaic
generator circuits
DG PV ... SCP FM: With remote signalling contact for the monitoring device (floating changeover contact)

Single-pole surge arresters of type DEHNguard PV ... SCP (FM) are specif- Apart from the standard green and red indi-
ically designed for use in photovoltaic power supply systems. cation, DEHNguard PV ... SCP FM devices fea-
ture a three-pole remote signalling terminal.
Even the external design of the surge arresters (width of 2 modules) is With their floating changeover contact, the
completely adapted to the safety requirements of modern photovoltaic remote signal can be used as a break or make
systems with their high system voltages. contact according to the particular circuit
concept.
The approved dual ”Thermo Dynamic Control” monitoring and disconnec-
tion device of the DEHNguard PV ... SCP (FM) Type 2 surge arresters was
combined with an additional short-circuiting device. This two-step d.c.
switching device ensures safe operation, even in case of overloaded
devices, e.g. due to an insulation fault in the photovoltaic generator cir-
cuit, without presenting a fire risk to the installation. The combined dis-
connection and short-circuiting device is capable of conducting the indi-
cated short-circuit current independently until the PV installation is main-
tained.

Switching stages:
1. 2.
Original state Response of the Arc extinction
disconnection device

SCP SCP SCP

www.dehn.de 107
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® PV ... SCP (FM) POWER SUPPLY SYSTEMS


950 500 DG PV 500 SCP
950 501 DG PV 700 SCP

DEHNguard PV ... SCP SURGE ARRESTERS – TYPE 2


950 502 DG PV 1200 SCP

DG PV 500 SCP
950 500
DG PV 700 SCP
950 501
DG PV 1200 SCP
950 502

Basic circuit diagram DG PV ... SCP Dimension drawing DG PV ... SCP

DG PV ... SCP: Single-pole surge arrester with combined disconnection and short-circuiting device
for use in photovoltaic generator circuits

DG PV 500 SCP DG PV 700 SCP DG PV 1200 SCP


SPD classification according to EN 61643-11 Type 2 Type 2 Type 2
SPD classification according to IEC 61643-1 Class II Class II Class II
PV voltage of earth-free PV systems (2 x DG PV ...) UCPV ) 1000 V ) 1400 V ) 1400 V
PV voltage of functionally earthed PV systems (thin film) UCPV ) 500 V ) 700 V ) 1200 V
Max. continuous operating d.c. voltage UC 500 V 700 V 1200 V
Nominal discharge current (8/20 μs) In 20 kA 15 kA 15 kA
Max. discharge current (8/20 μs) Imax 30 kA 30 kA 30 kA
Surge Arresters Type 2

Voltage protection level for In UP ) 2 kV ) 2.5 kV ) 4.2 kV


Voltage protection level at 5 kA UP ) 1.7 kV ) 2 kV ) 3.5 kV
Response time tA ) 25 ns ) 25 ns ) 25 ns
Permanent short-circuit withstand capability IK 80 A d.c. 80 A d.c. 80 A d.c.
Reverse current withstand capability Ipmax 50 kA / 5 ms 50 kA / 5 ms 50 kA / 5 ms
Max. protection of the main d.c. line at the inverter 315 A gR 315 A gR 315 A gR
Operating temperature range TU -40°C...+65°C -40°C...+65°C -40°C...+65°C
Operating state/fault indication green / red green / red green/red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20
Capacity 2 mods., DIN 43880 2 mods., DIN 43880 2 mods., DIN 43880

Ordering information
Type DG PV 500 SCP DG PV 700 SCP DG PV 1200 SCP
Part No. 950 500 950 501 950 502
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

108 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® PV ... SCP (FM)


950 505 DG PV 500 SCP FM
950 506 DG PV 700 SCP FM

SURGE ARRESTERS – TYPE 2 DEHNguard PV ... SCP FM


950 507 DG PV 1200 SCP FM

DG PV 500 SCP FM
950 505
DG PV 700 SCP FM
950 506
DG PV 1200 SCP FM
950 507

12
11
14

Dimension drawing DG PV ... SCP FM Basic circuit diagram DG PV ... SCP FM

DG PV ... SCP FM: Single-pole surge arrester with combined disconnection and short-circuiting
device for use in photovoltaic generator circuits; with floating remote sig-
nalling contact

DG PV 500 SCP FM DG PV 700 SCP FM DG PV 1200 SCP FM


SPD classification according to EN 61643-11 Type 2 Type 2 Type 2
SPD classification according to IEC 61643-1 Class II Class II Class II
PV voltage of earth-free PV systems (2 x DG PV ...) UCPV ) 1000 V ) 1400 V ) 1400 V
PV voltage of functionally earthed PV systems (thin film) UCPV ) 500 V ) 700 V ) 1200 V
Max. continuous operating d.c. voltage UC 500 V 700 V 1200 V
Nominal discharge current (8/20 μs) In 20 kA 15 kA 15 kA
Max. discharge current (8/20 μs) Imax 30 kA 30 kA 30 kA

Surge Arresters Type 2


Voltage protection level for In UP ) 2 kV ) 2.5 kV ) 4.2 kV
Voltage protection level at 5 kA UP ) 1.7 kV ) 2 kV ) 3.5 kV
Response time tA ) 25 ns ) 25 ns ) 25 ns
Permanent short-circuit withstand capability IK 80 A d.c. 80 A d.c. 80 A d.c.
Reverse current withstand capability Ipmax 50 kA / 5 ms 50 kA / 5 ms 50 kA / 5 ms
Max. protection of the main d.c. line at the inverter 315 A gR 315 A gR 315 A gR
Operating temperature range TU -40°C...+65°C -40°C...+65°C -40°C...+65°C
Operating state/fault indication green / red green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20
Capacity 2 mods., DIN 43880 2 mods., DIN 43880 2 mods., DIN 43880
Type of remote signalling contact changeover contact changeover contact changeover contact
Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information
Type DG PV 500 SCP FM DG PV 700 SCP FM DG PV 1200 SCP FM
Part No. 950 505 950 506 950 507
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

www.dehn.de 109
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard® 1000 (FM) POWER SUPPLY SYSTEMS


Single-pole, compact surge arrester SURGE ARRESTERS – TYPE 2
SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1

• High discharge capacity due to heavy-duty zinc


oxide varistor
• Quick response
• High reliability due to ”Thermo Dynamic
Control” disconnector
• Fault indication by red indicator flag in the
inspection window
• Specifically designed for high system voltages

For protecting low voltage consumer´s installations against surges. For


installation in conformity with the lightning protection zones concept at
the boundaries from 0B – 1 and higher.
Surge Arresters Type 2

DEHNguard 1000: Single-pole, compact surge arrester with a rated voltage UC = 1000 V a.c.
DEHNguard ... FM: With remote signalling contact for the monitoring device (floating changeover contact)

The compact and powerful DEHNguard ... 1000 (FM) surge arresters are Especially the DEHN-specific ”Thermo Dynamic Control” disconnector
designed for rated voltages of 1000 V. These single-pole devices can be ensures that the arresters change to a safe isolated operating state even
used for a wide range of applications. in case of extreme overload. Apart from the surface temperature of the
heavy-duty varistor, also the intensity of the discharge current is evaluat-
It is not only the flexibility that characterises the DEHNguard family, but ed.
especially the striking performance parameters, setting trends worldwide:
High discharge capacity, low voltage protection level and dual ”Thermo Also the external design of the device is completely adapted to the field
Dynamic Control” monitoring and disconnection device stand for maxi- of application. DEHNguard 1000 (FM), with a width of 2 modules, entire-
mum reliability. ly fulfils all mechanical requirements resulting from the high system volt-
ages.

Apart from the standard green and red indication, DEHNguard ... FM fea-
tures a three-pole terminal for remote signalling. With its floating
changeover contact, the remote signal can be used as a break or make
contact according to the particular circuit concept.

For earth-sided installation of DEHNguard (FM) devices, earthing brackets


of type EB DG 1000 1 3 and EB 1 4 9 can be used.

110 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard® 1000 (FM)


950 102 DG 1000
950 112 DG 1000 FM

SURGE ARRESTERS – TYPE 2 DEHNguard 1000 (FM)

DG 1000 DEHNguard, 1000 V


950 102
DG 1000 FM DEHNguard FM, 1000 V
950 112

12
11
14

Dimension drawing DG 1000 FM Basic circuit diagram DG 1000 FM

DG 1000 (FM): Single-pole, compact surge arrester with a rated voltage UC = 1000 V a.c.; FM ver-
sion with floating remote signalling contact

DG 1000 DG 1000 FM
SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Max. continuous operating a.c. voltage UC 1000 V 1000 V
Max. continuous operating d.c. voltage UC 1000 V 1000 V
Nominal discharge current (8/20 μs) In 15 kA 15 kA
Max. discharge current (8/20 μs) Imax 30 kA 30 kA
Voltage protection level Up ) 4.2 kV ) 4.2 kV

Surge Arresters Type 2


Voltage protection level at 5 kA UP ) 3.5 kV ) 3.5 kV
Response time tA ) 25 ns ) 25 ns
Max. overcurrent protection 100 A aM 100 A aM
Max. overcurrent protection for U ) 690 V a.c. 125 A gL/gG 125 A gL/gG
Short-circuit withstand capability for max. backup fuse 25 kArms 25 kArms
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 2 mods., DIN 43880 2 mods., DIN 43880
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DG 1000 DG 1000 FM
Part No. 950 102 950 112
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® 1000 (FM) Accessory Part for DEHNguard® 1000 (FM)
EB DG, 3-pole, single-phase
900 411
1000 1 3
EB DG

Earthing Clip, 4-pole, single-phase


900 417 EB 1 4 9

Earthing clip for earth-side jumpering of 3 DEHNguard 1000 (FM) surge Earthing clip for earth-side jumpering of 4 DEHNguard 1000 (FM) surge
arresters
EB DG 1000 1 3
900 411
arresters
EB 1 4 9
900 417

PU Part PU Part
Type Dimension Terminal pc(s). No. Type Dimension Terminal pc(s). No.
EB DG 1000 1 3 34 x 112 x 3 mm up to 25 mm2 1 900 411 EB 1 4 9 34 x 148 x 3 mm up to 25 mm2 1 900 417

www.dehn.de 111
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard S® ... VA (FM) POWER SUPPLY SYSTEMS


Single-pole, pluggable varistor- and SURGE ARRESTERS – TYPE 2
spark-gap-based arrester SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1

• All-purpose surge arrester consisting of a base


part and plug-in protection module
• Leakage-current-free series connection of a
varistor and a spark gap in the pluggable pro-
tection module
• High reliability due to ”Thermo Dynamic
Control” SPD monitoring device
• Energy coordination within the Red/Line pro-
duct family
• Easy replacement of protection modules with-
out tools due to module locking system with
module release button
• Narrow (modular) design in accordance with
DIN 43880
• Multifunctional terminal for connecting con- For protecting low-voltage consumer’s installations against overvoltage.
ductors and busbars For installation in conformity with the lightning protection zones concept
at the boundaries from 0B – 1 and higher.
Surge Arresters Type 2

DEHNguard S ... VA: Modular, single-pole surge arrester with a varistor and a spark gap connected in series in the plug-
gable protection module
DEHNguard S ... VA FM: With remote signalling contact for the monitoring device (floating changeover contact)

The single-pole DEHNguard S ... VA surge arresters complement the tried Particularly the DEHN-specific Thermo Dynamic Control disconnection
and tested DEHNguard product families. The special series connection of device ensures that the arresters enter a safe, isolated state even in case
a spark gap and a varistor module in the protection module opens up new of extreme overload. For this purpose, the intensity of the discharge cur-
fields of application. It is advisable to use DEHNguard S ... VA devices e.g. rent is evaluated together with the surface temperature of the heavy-duty
in systems with permanent insulation monitoring and in e.g. railroad sys- varistor. In addition to the standard red and green indicator, the
tems for protecting the power supply of signal lines which have to be free DEHNguard S VA ... FM devices feature a three-pole remote signalling ter-
of leakage currents. DEHNguard S ... VA arresters are also suited for pro- minal. With their floating changeover contact, the remote signal can be
tecting power line communication applications. used as break or make contact according to the particular protection con-
cept.
The multifunctional terminals allow almost unlimited flexibility in terms of
connection among one another, but also with other DIN rail mounted
devices in a distribution board. The DEHNguard S ... VA line is not only
characterised by flexibility. It are rather the distinctive performance
parameters which set standards worldwide:
A high discharge capacity, complete absence of leakage currents, a low
voltage protection level and the dual Thermo Dynamic Control monitoring
and disconnection device describe the high degree of reliability.

112 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNguard S® ... VA (FM)


952 080 DG S 75 VA
952 082 DG S 275 VA

SURGE ARRESTERS – TYPE 2 DEHNguard S VA


952 084 DG S 385 VA

DG S 75 VA
NEW
952 080
DG S 275 VA
952 082
DG S 385 VA
952 084

Dimension drawing DG S ... VA Basic circuit diagram DG S ... VA

DG S ... VA: Modular, single-pole surge arrester comprising a varistor and a spark gap connected
in series in the pluggable protection module

DG S 75 VA DG S 275 VA DG S 385 VA
SPD according to EN 61643-11 Type 2 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II Class II
Max. continuous operating a.c. voltage UC 75 V 275 V 385 V
Max. continuous operating d.c. voltage UC 100 V 350 V 500 V
Nominal discharge current (8/20 μs) In 10 kA 10 kA 10 kA
Max. discharge current (8/20 μs) Imax 20 kA 20 kA 20 kA
Voltage protection level UP ) 1.1 kV ) 1.5 kV ) 1.75 kV

Surge Arresters Type 2


Response time tA ) 100 ns ) 100 ns ) 100 ns
Max. supply side overcurrent protection 100 A gL/gG 100 A gL/gG 100 A gL/gG
Short-circuit withstand capability for
max. supply side overcurrent protection 25 kArms 25 kArms 25 kArms
Temporary overvoltage (TOV) UT 75 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.
TOV characteristics withstand withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20
Capacity 1 mod., DIN 43880 1 mod., DIN 43880 1 mod., DIN 43880

Ordering information
Type DG S 75 VA DG S 275 VA DG S 385 VA
Part No. 952 080 952 082 952 084
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard S® ... VA (FM)


Varistor-and spark-gap-based protection module
952 025
75 VA
952 027
275 VA
952 029
DG MOD

DG MOD

DG MOD

for DEHNguard S ... VA


385 VA

DG MOD ... VA: Protection module for DEHNguard S ... VA comprising a


DG MOD 75 VA
952 025
DG MOD 275 VA
952 027
DG MOD 385 VA

varistor connected in series with a spark gap


952 029

NEW
PU Part
Type pc(s). No.
DG MOD 75 VA 1 952 025
DG MOD 275 VA 1 952 027
DG MOD 385 VA 1 952 029

www.dehn.de 113
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNguard S® ... VA (FM) POWER SUPPLY SYSTEMS


952 085 DG S 75 VA FM
952 087 DG S 275 VA FM

DEHNguard S VA FM SURGE ARRESTERS – TYPE 2


952 089 DG S 385 VA FM

NEW DG S 75 VA FM
952 085
DG S 275 VA FM
952 087
DG S 385 VA FM
952 089

12
11
14

Basic circuit diagram DG S ... VA FM Dimension drawing DG S ... VA FM

DG S ... VA FM: Modular, single-pole surge arrester with a varistor and a spark gap connected in
series in the pluggable protection module; with floating remote signalling contact

DG S 75 VA FM DG S 275 VA FM DG S 385 VA FM
SPD according to EN 61643-11 Type 2 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II Class II
Max. continuous operating a.c. voltage UC 75 V 275 V 385 V
Max. continuous operating d.c. voltage UC 100 V 350 V 500 V
Nominal discharge current (8/20 μs) In 10 kA 10 kA 10 kA
Max. discharge current (8/20 μs) Imax 20 kA 20 kA 20 kA
Voltage protection level UP ) 1.1 kV ) 1.5 kV ) 1.75 kV
Surge Arresters Type 2

Response time tA ) 100 ns ) 100 ns ) 100 ns


Max. supply side overcurrent protection 100 A gL/gG 100 A gL/gG 100 A gL/gG
Short-circuit withstand capability for
max. supply side overcurrent protection 25 kArms 25 kArms 25 kArms
Temporary overvoltage (TOV) UT 75 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.
TOV characteristics withstand withstand withstand
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red green / red
Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20
Capacity 1 mod., DIN 43880 1 mod., DIN 43880 1 mod., DIN 43880
Type of remote signalling contact changeover contact changeover contact changeover contact
Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information
Type DG S 75 VA FM DG S 275 VA FM DG S 385 VA FM
Part No. 952 085 952 087 952 089
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard S® ... VA (FM)


952 025
75 VA
952 027
275 VA
952 029
DG MOD

DG MOD

DG MOD
Varistor-and spark-gap-based protection module
385 VA

for DEHNguard S ... VA


NEW
DG MOD 75 VA
952 025
DG MOD 275 VA DG MOD ... VA: Protection module for DEHNguard S ... VA comprising a
952 027
DG MOD 385 VA
952 029
varistor connected in series with a spark gap
PU Part
Type pc(s). No.
DG MOD 75 VA 1 952 025
DG MOD 275 VA 1 952 027
DG MOD 385 VA 1 952 029

114 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS V NH / VA NH


SURGE ARRESTERS – TYPE 2 NH Surge arresters
SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1

• Surge arrester for use in size 00 and 1 NH fuse


holders
• Zinc oxide varistor with monitoring device, dis-
connector and integrated backup fuse (VA NH
with additional spark gap connected in series)
• Energy coordination within the Red/Line prod-
uct family
• Fault indication by tripping indicator

For protecting low voltage consumer´s installations against surges. For


installation in conformity with the lightning protection zones concept at
the boundaries from 0B – 1 and higher. German patented design.

Surge Arresters Type 2


V(A) NH00 280: Surge arrester for use in size 00 NH fuse holders
V(A) NH1 280: Surge arrester for use in size 1 NH fuse holders
V(A) NH00 280 FM: With fault indicator for remote signalling; allows for use of NH fuse holders with microswitch (tripping
distance of fault indicator max. 7 mm)

The single-pole V NH and VA NH surge arresters show that surge protec-


tive devices do not necessarily have to be designed exclusively for DIN
rails or socket outlets. Being adapted to the conditions in industrial sub-
circuit distribution boards, V NH and VA NH devices are designed in the
form of an NH fuse holder. This allows for easy integration into busbar sys-
tems, as often applied in zones belonging to the operators of power sup-
ply systems or in industrial installations. Thus, the advantages of busbar
systems such as easy installation, less installation time and reduced
wiring also apply to surge protection. The idea of such a busbar system is
consistently continued with SPDs in NH design. V NH and VA NH surge
arresters can be installed and removed by means of a fuse switch discon-
nector and a fuse handle. This makes it considerably easier to measure the
isolation of the installation as the SPD does not have to be disconnected
any more.

Another considerable advan-


tage of the V NH / VA NH fam- case of type VA NH, a spark gap was connected in series to the heavy-duty
ily is the already integrated zinc oxide varistor with thermal monitoring and disconnection device of
backup fuse. If SPDs are the V NH devices. VA NH devices provide reliable protection especially for
installed in an earth fault- and large-scale systems with permanent isolation control. Apart from the
short-circuit-proof way, this standard visual indication by a fault indicator, V(A) NH ... FM devices pro-
considerably saves space and vide a microswitch integrated into the NH fuse holder for remote sig-
costs in distribution boards. In nalling.

www.dehn.de 115
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

V NH / VA NH POWER SUPPLY SYSTEMS


900 261 V NH00
280

V NH00 (FM) SURGE ARRESTERS – TYPE 2


900 263 V NH00
280 FM

V NH00 280 VNH


Surge Arrester, Size 00 900 261
V NH00 280 FM VNH FM
Surge Arrester, Size 00 900 263

Basic circuit diagram V NH00 (FM), V NH1 Dimension drawing Dimension drawing
V NH1 V NH00 (FM)
V NH00 (FM): Surge arrester for use in size 00 NH fuse holders; optionally available with indicator
for remote signalling
V NH1: Surge arrester for use in size 1 NH fuse holders

V NH00 280 V NH00 280 FM


SPD according to EN 61643-11 / ... IEC 61643-1 Type 2 / Class II Type 2 / Class II
Max. continuous operating a.c. voltage UC 280 V 280 V
Nominal discharge current (8/20 μs) In 15 kA 15 kA
Max. discharge current (8/20 μs) Imax 30 kA 30 kA
Voltage protection level UP ) 1.25 kV ) 1.25 kV
Voltage protection level at 5 kA UP ) 1 kV ) 1 kV
Response time tA ) 25 ns ) 25 ns
Surge Arresters Type 2

Max. mains-side overcurrent protection not required not required


Short-circuit withstand capability 25 kArms 25 kArms
Temporary overvoltage (TOV) UT 335 V / 5 sec. 335 V / 5 sec.
TOV characteristics withstand withstand
Indication of the disconnector red fault indicator red fault indicator (tripping distance 7 mm)
Operating temperature range TU -40°C...+80°C -40°C...+80°C
For mounting on size 00 NH fuse holder size 00 NH fuse holder
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IPX4W —

Ordering information
Type V NH00 280 V NH00 280 FM
Part No. 900 261 900 263
Packing unit 1 pc(s). 1 pc(s).

V NH1 280
SPD according to EN 61643-11 / ... IEC 61643-1 Type 2 / Class II
Max. continuous operating a.c. voltage UC 280 V
900 270 V NH1

Nominal discharge current (8/20 μs) In 15 kA 280

Max. discharge current (8/20 μs) Imax 30 kA


Voltage protection level UP ) 1.25 kV V NH1 280
Surge Arrester, Size 1
VNH
900 270

Voltage protection level at 5 kA UP ) 1 kV


Response time tA ) 25 ns
Max. mains-side overcurrent protection not required
Short-circuit withstand capability 25 kArms
Temporary overvoltage (TOV) UT 335 V / 5 sec.
TOV characteristics withstand
Indication of the disconnector red fault indicator
Operating temperature range TU -40°C...+80°C
For mounting on size 1 NH fuse holder
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IPX4W

Ordering information
Type V NH1 280
Part No. 900 270
Packing unit 1 pc(s).

116 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS V NH / VA NH


900 262 VA NH00
280

SURGE ARRESTERS – TYPE 2 VA NH00 (FM)


900 264 VA NH00
280 FM

VA NH00 280 VANH


Surge Arrester, Size 00 900 262
VA NH00 280 FM VANH FM
Surge Arrester, Size 00 900 264

Dimension drawing Dimension drawing Basic circuit diagram VA NH00 (FM), V NH1
VA NH00 (FM) VA NH1
VA NH00 FM: Surge arrester with a varistor and a spark gap connected in series; for use in size 00
NH fuse holders, optionally available with indicator for remote signalling
VA NH1: Surge arrester with a varistor and a spark gap connected in series; for use in size 1
NH fuse holders
VA NH00 280 VA NH00 280 FM
SPD according to EN 61643-11 / ... IEC 61643-1 Type 2 / Class II Type 2 / Class II
Max. continuous operating a.c. voltage UC 280 V 280 V
Nominal discharge current (8/20 μs) In 10 kA 10 kA
Max. discharge current (8/20 μs) Imax 20 kA 20 kA
Voltage protection level UP ) 1.5 kV ) 1.5 kV
Response time tA ) 100 ns ) 100 ns
Max. mains-side overcurrent protection not required not required

Surge Arresters Type 2


Short-circuit withstand capability 25 kArms 25 kArms
Temporary overvoltage (TOV) UT 335 V / 5 sec. 335 V / 5 sec.
TOV characteristics withstand withstand
Indication of the disconnector red fault indicator red fault indicator (tripping distance 7 mm)
Operating temperature range TU -40°C...+80°C -40°C...+80°C
For mounting on size 00 NH fuse holder size 00 NH fuse holder
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IPX4W IPX4W

Ordering information
Type VA NH00 280 VA NH00 280 FM
Part No. 900 262 900 264
Packing unit 1 pc(s). 1 pc(s).

VA NH1 280
SPD according to EN 61643-11 / ... IEC 61643-1 Type 2 / Class II
Max. continuous operating a.c. voltage UC 280 V
900 271 VA NH1
280
Nominal discharge current (8/20 μs) In 10 kA
Max. discharge current (8/20 μs) Imax 20 kA
VA NH1 280
280, Size 1
VANH
900 271
Voltage protection level UP ) 1.5 kV
Response time tA ) 100 ns
Max. mains-side overcurrent protection not required
Short-circuit withstand capability 25 kArms
Temporary overvoltage (TOV) UT 335 V / 5 sec.
TOV characteristics withstand
Indication of the disconnector red fault indicator
Operating temperature range TU -40°C...+80°C
For mounting on size 1 NH fuse holder
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IPX4W

Ordering information
Type VA NH1 280
Part No. 900 271
Packing unit 1 pc(s).

www.dehn.de 117
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS – TYPE 2
Surge Arresters Type 2

118 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNrail modular


SURGE ARRESTERS – TYPE 3 Two-pole, pluggable surge arrester
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

• Two-pole surge arrester consisting of a base


part and plug-in protection module
• High discharge capacity due to heavy-duty zinc
oxide varistor/spark gap combination
• Energy coordination within the Red/Line pro-
duct family
• Operating state/fault indication by indicator
flag in the inspection window
• Narrow (modular) design according to DIN
43880
• Easy replacement of protection modules due to
module locking system with module release
button
• Vibration- and shock-tested according to EN
For protection of the power supply circuit of industrial electronics equip- 60068-2
ment against transient surges in switchboards. For installation according
to the lightning protection zones concept at the boundaries from 1 – 2
and higher.

DEHNrail M 2P ...: Two-pole surge arrester consisting of a base element and plug-in protection module
DEHNrail M 2P ... FM: With remote signalling contact for the monitoring device (floating changeover contact)

Surge Arresters Type 3


The modular devices of the DEHNrail M product family stand out due to The new module locking system of the DEHNrail M product family is
their high performance parameters and new straightforward Red/Line unique for surge protective devices. It fixes the surge protection module
design. The devices combine safety and user-friendliness in a single mod- and the base part of the SPD firmly in place. Neither vibration during
ule. The low voltage protection level and comprehensive common and dif- transport nor the electromagnetic forces of discharge can loosen the con-
ferential mode protection are ideally suited for the protection of terminal nection.
devices in industrial electronic environments. The design of the devices
with input and output terminals for series connection and the protective If the protective circuit is overloaded despite of the powerful characteris-
circuit designed for high load currents underline this concept. tics of the devices, the module release button allows quick replacement
of the protection modules without tools.
Compact in design, DEHNrail M surge arresters feature a distinctive Y pro-
tection circuit and a combined SPD monitoring device and disconnection In addition to the standard green
mechanism. and red indication, DEHNrail M ...
FM devices feature a three-pole
The base part and protection module are coded thus preventing incorrect terminal for remote signalling. With
insertion by the installer or user. their floating changeover contact,
the remote signal can be used as a
break or make contact according to
the particular circuit concept.

www.dehn.de 119
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNrail modular POWER SUPPLY SYSTEMS


953 201 DR M 2P
30

DEHNrail M 2P ... SURGE ARRESTERS – TYPE 3


953 202 DR M 2P
60
953 203 DR M 2P
75
953 204 DR M 2P
150
953 200 DR M 2P
255

1 2 DR M 2P 30
953 201
DR M 2P 60
953 202
DR M 2P 75
953 203
DR M 2P 150
953 204
DR M 2P 255
953 200

3 4

Basic circuit diagram DR M 2P ... Dimension drawing DR M 2P ...

DR M 2P ...: Two-pole surge arrester consisting of a base element and plug-in protection module

DR M 2P 30 DR M 2P 60 DR M 2P 75 DR M 2P 150 DR M 2P 255
SPD according to EN 61643-11 / ... IEC 61643-1 Type 3 / Class III Type 3 / Class III Type 3 / Class III Type 3 / Class III Type 3 / Class III
Nominal a.c. voltage UN 24 V 48 V 60 V 120 V 230 V
Max. continuous operating a.c. voltage UC 30 V 60 V 75 V 150 V 255 V
Max. continuous operating d.c. voltage UC 30 V 60 V 75 V 150 V 255 V
Nominal load current a.c. IL 25 A 25 A 25 A 25 A 25 A
Nominal discharge current (8/20 μs) In 1 kA 1 kA 2 kA 2 kA 3 kA
Total discharge current (8/20 μs) [L+N-PE] Itotal 2 kA 2 kA 4 kA 4 kA 5 kA
Combined impulse UOC 2 kV 2 kV 4 kV 4 kV 6 kV
Combined impulse [L+N-PE] UOC total 4 kV 4 kV 8 kV 8 kV 10 kV
Voltage protection level [L-N] UP ) 180 V ) 350 V ) 400 V ) 640 V ) 1250 V
Voltage protection level [L/N-PE] UP ) 630 V ) 730 V ) 730 V ) 800 V ) 1500 V
Response time [L-N] tA ) 25 ns ) 25 ns ) 25 ns ) 25 ns ) 25 ns
Response time [L/N-PE] tA ) 100 ns ) 100 ns ) 100 ns ) 100 ns ) 100 ns
Max. mains-side overcurrent protection 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A
Short-circuit withstand capability for
mains-side overcurrent protection with 25 A gL/gG 6 kArms 6 kArms 6 kArms 6 kArms 6 kArms
Temporary overvoltage (TOV) [L-N] UT — — — — 335 V / 5 sec.
Surge Arresters Type 3

Temporary overvoltage (TOV) [L/N-PE] UT — — — — 400 V / 5 sec.


Temporary overvoltage (TOV) [L+N-PE] UT — — — — 1200 V + U0 / 200 ms
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red green / red green / red green / red
Cross-sectional area (min.) 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible
Cross-sectional area (max.) 4 mm2 solid/2.5 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20 IP 20 IP 20
Capacity 1 mod., DIN 43880 1 mod., DIN 43880 1 mod., DIN 43880 1 mod., DIN 43880 1 mod., DIN 43880
Approvals, Certifications KEMA, VDE, UL, VdS, CSA

Ordering information
Type DR M 2P 30 DR M 2P 60 DR M 2P 75 DR M 2P 150 DR M 2P 255
Part No. 953 201 953 202 953 203 953 204 953 200
Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNrail modular


953 011
30
953 012
60
953 013
DR MOD

DR MOD

DR MOD
Protection module for DEHNrail M 2P
75
953 014 DR MOD
150
953 010
255
DR MOD
DR MOD ...: Protection module with integrated Y protection circuit
DR MOD 30
953 011
DR MOD 60
953 012
DR MOD 75
953 013
PU Part
DR MOD 150
953 014
DR MOD 255
953 010
Type pc(s). No.
DR MOD 30 1 953 011
DR MOD 60 1 953 012
DR MOD 75 1 953 013
DR MOD 150 1 953 014
DR MOD 255 1 953 010

120 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNrail modular


953 206 DR M 2P
30 FM

SURGE ARRESTERS – TYPE 3 DEHNrail M 2P ... FM


953 207 DR M 2P
60 FM
953 208 DR M 2P
75 FM
953 209 DR M 2P
150 FM
953 205 DR M 2P
255 FM

DR M 2P 30 FM
953 206
1 2
DR M 2P 60 FM
953 207
DR M 2P 75 FM
953 208
DR M 2P 150 FM
953 209
DR M 2P 255 FM
953 205

12
11
14

3 4

Dimension drawing DR M 2P ... FM Basic circuit diagram DR M 2P ... FM

DR M 2P ... FM: Two-pole surge arrester consisting of a base element and plug-in protection mod-
ule; with floating remote signalling contact

DR M 2P 30 FM DR M 2P 60 FM DR M 2P 75 FM DR M 2P 150 FM DR M 2P 255 FM
SPD according to EN 61643-11 / ... IEC 61643-1 Type 3 / Class III Type 3 / Class III Type 3 / Class III Type 3 / Class III Type 3 / Class III
Nominal a.c. voltage UN 24 V 48 V 60 V 120 V 230 V
Max. continuous operating a.c. voltage UC 30 V 60 V 75 V 150 V 255 V
Max. continuous operating d.c. voltage UC 30 V 60 V 75 V 150 V 255 V
Nominal load current a.c. IL 25 A 25 A 25 A 25 A 25 A
Nominal discharge current (8/20 μs) In 1 kA 1 kA 2 kA 2 kA 3 kA
Total discharge current (8/20 μs) [L+N-PE] Itotal 2 kA 2 kA 4 kA 4 kA 5 kA
Combined impulse UOC 2 kV 2 kV 4 kV 4 kV 6 kV
Combined impulse [L+N-PE] UOC total 4 kV 4 kV 8 kV 8 kV 10 kV
Voltage protection level [L-N] UP ) 180 V ) 350 V ) 400 V ) 640 V ) 1250 V
Voltage protection level [L/N-PE] UP ) 630 V ) 730 V ) 730 V ) 800 V ) 1500 V
Response time [L-N] tA ) 25 ns ) 25 ns ) 25 ns ) 25 ns ) 25 ns
Response time [L/N-PE] tA ) 100 ns ) 100 ns ) 100 ns ) 100 ns ) 100 ns
Max. mains-side overcurrent protection 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A
Short-circuit withstand capability for
mains-side overcurrent protection with 25 A gL/gG 6 kArms 6 kArms 6 kArms 6 kArms 6 kArms
Temporary overvoltage (TOV) [L-N] UT — — — — 335 V / 5 sec.

Surge Arresters Type 3


Temporary overvoltage (TOV) [L/N-PE] UT — — — — 400 V / 5 sec.
Temporary overvoltage (TOV) [L+N-PE] UT — — — — 1200 V + U0 / 200 ms
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red green / red green / red green / red
Cross-sectional area (min.) 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible
Cross-sectional area (max.) 4 mm2 solid/2.5 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20 IP 20 IP 20 IP 20
Capacity 1 mod., DIN 43880 1 mod., DIN 43880 1 mod., DIN 43880 1 mod., DIN 43880 1 mod., DIN 43880
Approvals, Certifications KEMA, VDE, UL, VdS, CSA
Type of remote signalling contact changeover contact changeover contact changeover contact changeover contact changeover contact
Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible

Ordering information
Type DR M 2P 30 FM DR M 2P 60 FM DR M 2P 75 FM DR M 2P 150 FM DR M 2P 255 FM
Part No. 953 206 953 207 953 208 953 209 953 205
Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).
Protection module for DEHNrail M 2P
953 011
30
953 012
60
953 013
DR MOD

DR MOD

DR MOD
75
953 014 DR MOD

DR MOD ...: Protection module with integrated Y protection circuit


150
953 010
255
DR MOD

DR MOD 30 ÜS-Modul
DEHNrail, 2-polig, 30 V 953 011
DR MOD 60 ÜS-Modul
DEHNrail, 2-polig, 60 V
DR MOD 75
DEHNrail, 2-polig, 75 V
953 012
ÜS-Modul
953 013
PU Part
DR MOD 150 ÜS-Modul
Type
DEHNrail, 2-polig, 150 V
DR MOD 255
DEHNrail, 2-polig, 255 V
953 014
ÜS-Modul
953 010
pc(s). No.
DR MOD 30 1 953 011
DR MOD 60 1 953 012
DR MOD 75 1 953 013
DR MOD 150 1 953 014
DR MOD 255 1 953 010

www.dehn.de 121
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNrail modular, multipole POWER SUPPLY SYSTEMS


Four-pole, pluggable surge arrester SURGE ARRESTERS – TYPE 3
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

• Four-pole surge arrester consisting of a base


element and plug-in protection module
• High discharge capacity due to heavy-duty zinc
oxide varistor/spark gap combination
• Energy coordination within the Red/Line pro-
duct family
• Operating state/fault indication by indicator
flag in the inspection window
• Easy replacement of protection modules with-
out the use of tools due to module locking sys-
tem with module release button
• Nominal load currents up to 25 A
• Vibration- and shock-tested in accordance with
EN 60068-2
For protecting the power supply circuit of industrial electronics equipment
against transient surges in switchgear cabinets. For installation in con-
formity with the lightning protection zones concept at the boundaries
from 1 – 2 and higher.

DEHNrail M 4P ...: Four-pole surge arrester consisting of a base element and plug-in protection module
DEHNrail M 4P ... FM: With remote signalling contact for the monitoring device (floating changeover contact)

The four-pole, modular DEHNrail M 4P ... (FM) surge arrester was specifi- The base part and protection module of the device are coded thus pre-
cally developed for protecting three-phase industrial electronics terminal venting incorrect insertion by the installer or user.
equipment. Adapted to this kind of environment, the SPD with the new
Red/Line design is suitable for 35 mm DIN rails. The low voltage protec- The new module locking system of the DEHNrail M family is unique for
Surge Arresters Type 3

tion level and the comprehensive common and differential mode protec- surge protective devices. It fixes the surge protection modules and the
tion are characteristic of DEHNrail M 4P ... (FM). In order to provide opti- base part of the SPD firmly in place. Neither vibrations during transport
mal low voltage protection levels for the terminal equipment to be pro- nor the electrodynamic forces of discharge can loosen the connection.
tected, the device features input and output terminals for series connec-
tion. DEHNrail M 4P ... (FM) devices ideally adapt to the cable run If the protective circuits, which are rated for high load currents up to
upstream of the terminal equipment therefore not requiring additional 25 A, are overloaded despite of the powerful characteristics of the device,
terminal blocks for outgoing cables. The very compact design of DEHNrail the protection modules can be easily replaced without tools by simply
M 4P ... (FM) already incorporates the tried and tested disconnector. It dis- pressing the module release button.
connects an overloaded SPD circuit from the mains without interrupting
the supply circuit. Apart from the standard green and red visual indication, DEHNrail M 4P
... FM devices feature a three-pole remote signalling terminal. With their
floating changeover contact, the remote signal can be used as a break or
make contact according to the particular circuit concept.

122 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNrail modular, multipole


953 400 DR M 4P
255

SURGE ARRESTERS – TYPE 3 DEHN rail M 4P ... (FM)


953 405 DR M 4P
255 FM

L1 L1 L2 L2 L3 L3
DR M 4P 255
953 400
DR M 4P 255 FM
953 405

12
11
14

PE PE N N

Dimension drawing DR M 4P ... FM Basic circuit diagram DR M 4P ... FM

DR M 4P ... (FM): Four-pole surge arrester consisting of a base element and plug-in protection
module; also available with floating remote signalling contact

DR M 4P 255 DR M 4P 255 FM
SPD according to EN 61643-11 Type 3 Type 3
SPD according to IEC 61643-1 Class III Class III
Nominal a.c. voltage UN 230/400 V 230/400 V
Max. continuous operating a.c. voltage UC 255/440 V 255/440 V
Nominal load current a.c. IL 25 A 25 A
Nominal discharge current (8/20 μs) In 3 kA 3 kA
Total discharge current (8/20 μs) [L1+L2+L3+N-PE] Itotal 8 kA 8 kA
Combined impulse UOC 6 kV 6 kV
Combined impulse [L1+L2+L3+N-PE] UOC total 16 kV 16 kV
Voltage protection level [L-N] UP ) 1000 V ) 1000 V
Voltage protection level [L/N-PE] UP ) 1500 V ) 1500 V
Response time [L-N] tA ) 25 ns ) 25 ns
Response time [L/N-PE] tA ) 100 ns ) 100 ns
Max. mains-side overcurrent protection 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A
Short-circuit withstand capability for
mains-side overcurrent protection with 25 A gL/gG 6 kArms 6 kArms
Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec.

Surge Arresters Type 3


Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec. 400 V / 5 sec.
Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Operating state/fault indication green / red green / red
Cross-sectional area (min.) 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible
Cross-sectional area (max.) 4 mm2 stranded/2.5 mm2 flexible 4 mm2 solid/2.5 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0
Degree of protection IP 20 IP 20
Capacity 2 mods., DIN 43880 2 mods., DIN 43880
Approvals, Certifications KEMA KEMA
Type of remote signalling contact — changeover contact
Switching capacity a.c. — 250 V/0.5 A
Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information
Type DR M 4P 255 DR M 4P 255 FM
Part No. 953 400 953 405
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNrail modular, multipole


Protection module for DEHNrail M 4P
953 020
4P 255
DR MOD

DR MOD 4P ...: 4-pole protection module with integrated protective


circuit
DR MOD 4P 255
953 020

PU Part
Type pc(s) No.
DR MOD 4P 255 1 953 020

www.dehn.de 123
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

Protection Module for DEHNrail modular POWER SUPPLY SYSTEMS


Plug-in protection module for SPDs Type 3 SURGE ARRESTERS – TYPE 3
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

• The plug-in protection module can be replaced


without the need to de-energise and without
removing the covering plate from the distribu-
tion board
• Operating state and fault indication by indica-
tor flag in the inspection window
• Easy replacement of the protection modules
due to module locking system with module
release button

DEHNrail MOD ...: For all types of two-pole DEHNrail M


For protection of the power supply circuit of industrial electronics equip-
2P ... surge arresters
ment against surges in switchboards. For installation in conformity with
DEHNrail MOD 4P...: For all types of four-pole DEHNrail M the lightning protection zones concept at the boundaries from 1 – 2 and
4P ... surge arresters higher.

Protection module for DEHNrail M 2P

953 011 DR MOD


30
953 012 DR MOD
60
953 013 DR MOD
75

DR MOD ...: Protection module with integrated Y protection circuit 953 014
150
953 010
255
DR MOD

DR MOD

Basic circuit diagram Dimension drawing


DR MOD protection module DR MOD protection module DR MOD 30
953 011
DR MOD 60
953 012
DR MOD 75
953 013
DR MOD 150
953 014
DR MOD 255

DR MOD 30 DR MOD 60 DR MOD 75 DR MOD 150 DR MOD 255


Surge Arresters Type 3

953 010

Nominal discharge current (8/20 μs) In 1 kA 1 kA 2 kA 2 kA 3 kA


Total discharge current (8/20 μs) [L+N-PE] Itotal 2 kA 2 kA 4 kA 4 kA 5 kA
Max. continuous operating a.c. / d.c. voltage UC 30 V 60 V 75 V 150 V 255 V

Ordering information
Type DR MOD 30 DR MOD 60 DR MOD 75 DR MOD 150 DR MOD 255
Part No. 953 011 953 012 953 013 953 014 953 010
Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Protection module for DEHNrail M 4P

DR MOD 4P ...: Four-pole protection module with integrated protective 953 020
4P 255
DR MOD

circuit
Basic circuit diagram Dimension drawing DR MOD 4P 255
953 020

DR MOD 4P protection module DR MOD 4P protection module

DR MOD 4P 255
Nominal discharge current (8/20 μs) In 3 kA
Total discharge current (8/20 μs) [L+N-PE] Itotal 8 kA
Max. continuous operating a.c. / d.c. voltage UC 255 V

Ordering information
Type DR MOD 4P 255
Part No. 953 020
Packing unit 1 pc(s).

124 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS Mains Filter


SURGE ARRESTERS – TYPE 3 NF 10

• Protection of sensitive industrial electronics


equipment against balanced and unbalanced
high-frequency interferences
• Completes surge protection,
e.g. DEHNrail M 2P 255
• Easy installation on DIN rails in switchgears

The NF 10 mains filter is the ideal completion of surge protection for interferences. The separate input and output terminals of the mains filter
industrial terminal equipment. Being a DIN rail mounted device, the mains ensure that an optimal protective effect of the device is provided for the
filter is ideally suited for installation downstream of surge protective equipment to be protected. This also allows to meet electromagnetic com-
devices (e.g. DEHNrail M 2P 255). In addition to surge protection, this patibility requirements for constructing control systems and installations
ensures protection against balanced and unbalanced high-frequency which do not relate to surge protection.

912 254 NF 10

NF 10 Mains
Filter 10 A 912 254

L1 L1

mains SPD

N N
PE PE

Surge Arresters Type 3


Dimension drawing NF 10 Basic circuit diagram NF 10

NF 10: Mains filter for protection against balanced and unbalanced interferences

NF 10
Nominal a.c. voltage UN 230 V
Nominal load current a.c. IL 10 A
Nominal frequency fN 50...60 Hz
Discharge current (for UN) ) 3.5 mA
Attenuation for f = 1 MHz, balanced > 64 dB
Attenuation for f = 1 MHz, unbalanced > 69 dB
Total circuit capacitance [L-N] 660 nF
Total circuit capacitance [L (N)-PE] 66 nF
Total circuit inductance 1.8 mH per line
Backup fuse 10 A gL/gG
Operating temperature range -25°C...+40°C
Cross-sectional area min. 2.5 mm2 stranded, max. 4 mm2 flexible
For mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic GF (polycarbonate)
Degree of protection IP 20
Dimension 110 x 45 x 75 mm

Ordering information
Type NF 10
Part No. 912 254
Packing unit 1 pc(s).

www.dehn.de 125
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

SPS Protector POWER SUPPLY SYSTEMS


Two-pole surge arrester with filter SURGE ARRESTERS – TYPE 3
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

• Combination of surge protection and filter


• Surge protection with monitoring device and
disconnector
• Interference suppressor filter for protecting
sensitive industrial electronics equipment
against balanced and unbalanced high-frequen-
cy interference
• Installed into a shielded enclosure
• Visual operating state indication (green) and
floating remote signalling contact (break con-
tact) for fault indication

For protecting the power supply circuit of industrial electronics equipment


(e.g. programmable logic controls/PLCs) against surges and high-frequen-
cy interference voltages. For installation in conformity with the lightning
protection zones concept at the boundaries from 1 – 2 and higher.

SPS Protector: Two-pole surge arrester with interference suppressor filter

The SPS Protector combines surge protection and interference suppressor the device to be protected. The metal enclosure of the SPS Protector
filter in one compact device. This makes the device ideal for protecting ensures that high-frequency interferences are discharged without interfer-
sensitive terminal equipment in industrial automation systems (e.g. pro- ing with other devices close to the installation. The compact design of the
grammable logic controls ”PLCs”). The coordinated surge protection and SPS Protector already incorporates the approved disconnector. In case of
filter functions complement one another and prevent core saturation of overload, it disconnects the SPD from the mains without interrupting the
Surge Arresters Type 3

the filter in the event of high-energy transients. The separate input and supply circuit. Apart from the green light, standard SPS Protector devices
output terminals ensure that an optimal protective effect is provided for can also be used for remote signalling.

126 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS SPS Protector


912 253 SPS PRO

SURGE ARRESTERS – TYPE 3 SPS Protector


FM
SPS PRO SPS-
11 12
Protector 912 253

L L'

N N'

PE PE

Dimension drawing SPS PRO Basic circuit diagram SPS PRO

SPS PRO: Surge arrester with interference suppressor filter

SPS PRO
SPD according to EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Nominal a.c. voltage UN 230 V
Max. continuous operating a.c. voltage UC 255 V
Nominal load current a.c. IL 3A
Nominal discharge current (8/20 μs) In 3 kA
Total discharge current (8/20 μs) [L+N-PE] Itotal 5 kA
Combined impulse UOC 6 kV
Combined impulse [L+N-PE] UOC total 10 kV
Voltage protection level [L-N] UP ) 0.8 kV
Voltage protection level [L/N-PE] UP ) 1.0 kV
Response time [L-N] tA ) 25 ns
Response time [L/N-PE] tA ) 100 ns
Short-circuit withstand capability for max. mains-side overcurrent protection 6 kArms
Fault indication green light off

Surge Arresters Type 3


Operating state indication green light
Operating temperature range TU -10°C...+40°C
Cross-sectional area (min.) 0.14 mm2 solid/stranded/flexible
Cross-sectional area (max.) 2.5 mm2 solid/stranded/flexible
For mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material aluminium, red powder coating
Degree of protection IP 20
Capacity 7 mods., DIN 43880
Type of remote signalling contact break contact
Switching capacity a.c. 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible
Mains filter acc. to DIN VDE 0565 Part 3
Attenuation for f = 1 MHz, balanced * 73 dB
Attenuation for f = 1 MHz, unbalanced * 45 dB

Ordering information
Type SPS PRO
Part No. 912 253
Packing unit 1 pc(s).

www.dehn.de 127
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNsafe POWER SUPPLY SYSTEMS


Surge arrester for use in cable ducts SURGE ARRESTERS – TYPE 3
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

• Two-pole surge protective device for 230 V ter-


minal devices
• For use in flush-type boxes and cable ducts
• Enhanced safety due to distinctive Y protection
circuit
• Multiple visual operating state indication
• Programmable acoustic function
• Terminals for series connection
• Independent from the design of socket outlets

For protecting electronic devices against surges. For installation into elec-
trical installation systems, e.g. cable ducts or flush-type boxes. For instal-
lation in conformity with the lightning protection zones concept at the
boundaries from 1 – 2 anf higher.

DEHNsafe 230 LA: Surge protective device for use in cable ducts

The DEHNsafe surge arrester particularly stands out due to its flexible A triple TAE cover plate of any switch pro-
application options. DEHNsafe is a two-pole surge protective device for gramme manufacturer can be used for covering
230 V terminal equipment which can be installed into cable ducts, but it. Thus, DEHNsafe adapts ideally to any socket
also into flat flush-type boxes due to the minimal installation depth of outlet design.
only 31 mm. DEHNsafe incorporates a monitoring device and a thermal The two available terminals for L, N and PE allow
Surge Arresters Type 3

disconnector. In addition to a visual operating state indication, the device for series connection to ensure that the surge
features a programmable acoustic fault indication. With such an acoustic protection is situated in parallel to the circuit to
signal, the fault indication can be programmed for three different operat- be protected. If DEHNsafe surge arresters are
ing states: overloaded, the surge protective device does not necessarily interrupt the
– Acoustic fault indication, circuit to be protected. DEHNsafe surge arresters feature a green and red
LED for visual indication of the protective device.
– Test function,
– Muting of the acoustic signal.

128 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNsafe


924 370 DSA 230
LA

SURGE ARRESTERS – TYPE 3 DEHNsafe

DSA 230 LA DEHNsafe


924 370

L PE N

Dimension drawing DSA 230 LA Basic circuit diagram DSA 230 LA

DSA 230 LA: Surge protective device for use in cable ducts and flush-type boxes

DSA 230 LA
SPD according to EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Nominal a.c. voltage UN 230 V
Max. continuous operating a.c. voltage UC 255 V
Nominal load current IL 16 A
Nominal discharge current (8/20 μs) In 3 kA
Total discharge current (8/20 μs) [L+N-PE] Itotal 5 kA
Combined impulse UOC 6 kV
Combined impulse [L+N-PE] UOC total 10 kV
Voltage protection level [L-N] UP ) 1.25 kV
Voltage protection level [L/N-PE] UP ) 1.5 kV
Response time [L-N] tA ) 25 ns
Response time [L/N-PE] tA ) 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
Short-circuit withstand capability for mains-side overcurrent protection with 16 A gL/gG 6 kArms
Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec.
Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec.

Surge Arresters Type 3


Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms
Fault indication red light + acoustic signal
Operating state indication green light
Switch function test / acoustic signal off
Operating temperature range TU -25°C...+40°C
Cross-sectional area (min.) 0.5 mm2 solid/stranded/flexible
Cross-sectional area (max.) 2.5 mm2 solid/stranded/flexible
For mounting on supporting ring (Ø60 mm) for installing into switch boxes, depth of 40 mm
Enclosure material thermoplastic, grey, UL 94 V-2
Degree of protection IP 20
Cover TAE

Ordering information
Type DSA 230 LA
Part No. 924 370
Packing unit 1 pc(s).

Accessory Part for DEHNsafe Accessory Part for DEHNsafe


Central covering plate
924 329 ZAP STW

Covering frame
924 328 AR1 STW

Single unit, alpha exclusive Single unit, alpha exclusive


ZAP STW Central AR1 STW Covering
Covering Plate for DEHNsafe 924 329 Frame for DEHNsafe, studio white 924 328

PU Part PU Part
Type Colour pc(s). No. Type Colour pc(s). No.
ZAP STW studio white 1 924 329 AR1 STW studio white 1 924 328

www.dehn.de 129
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

STC Module POWER SUPPLY SYSTEMS


Surge arrester for earthed socket outlets SURGE ARRESTERS – TYPE 3
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

• Two-pole surge arrester with monitoring device


and disconnector
• Enhanced safety due to distinctive Y protection
circuit
• Acoustic fault indication
• For installation in combination with standard
earthed socket outlets
• Independent from the design of the socket out-
lets
• Plastic supporting ring with latch for easy
installation on already mounted socket outlets

For protecting electronic devices against surges. For use with standard
earthed socket outlets. For installation in conformity with the lightning
protection zones concept at the boundaries from 1 – 2 and higher.

STC 230: Snap-on module for standard earthed socket outlets

The popular STC surge protection module can be installed inconspicuous- addition to a thermal disconnector, the protective device features an
ly. Being a two-pole surge arrester, the module can be installed on the rear acoustic fault indication. As the surge protection module is installed in
side of standard earthed socket outlets. The STC surge protection module parallel to the socket outlet, the power supply of the connected con-
thus adapts to every type of socket outlet. The plastic supporting ring with sumers remains uninterrupted, even if the surge arrester is overloaded.
latch allows easy installation even on already mounted socket outlets. In
Surge Arresters Type 3

130 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS STC Module


924 350 STC 230

SURGE ARRESTERS – TYPE 3 STC 230

STC 230
924 350

approx. 127

approx. 117

N PE L

Dimension drawing STC 230 Basic circuit diagram STC 230

STC 230: Two-pole surge arrester for snapping onto earthed socket outlets

STC 230
SPD according to EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Nominal a.c. voltage UN 230 V
Max. continuous operating a.c. voltage UC 255 V
Nominal discharge current (8/20 μs) In 3 kA
Total discharge current (8/20 μs) [L+N-PE] Itotal 5 kA
Combined impulse UOC 6 kV
Combined impulse [L+N-PE] UOC total 10 kV
Voltage protection level [L-N] UP ) 1.25 kV
Voltage protection level [L/N-PE] UP ) 1.5 kV
Response time [L-N] tA ) 25 ns
Response time [L/N-PE] tA ) 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
Short circuit withstand capability for mains-side overcurrent protection with 16 A gL/gG 6 kArms
Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec.

Surge Arresters Type 3


Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec.
Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms
Fault indication acoustic signal on
Operating temperature range TU -25°C...+40°C
Terminal wires 1 mm2, length: 120 mm
For mounting on common socket outlets with earth contact
Enclosure material thermoplastic, red, UL 94 V-2
Degree of protection of installed device IP 20
Dimension 53 x 53 x 32 mm
Indication of disconnector acoustic signal on

Ordering information
Type STC 230
Part No. 924 350
Packing unit 1 pc(s).

www.dehn.de 131
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNflex POWER SUPPLY SYSTEMS


Flexible protection of terminal equipment SURGE ARRESTERS – TYPE 3
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

• Two-pole surge arrester with monitoring device


and disconnector
• Enhanced safety due to distinctive Y protection
circuit
• Acoustic fault indication
• Compact design
• For use in flush-mounted systems, cable ducts
and flush-type boxes

For protecting electronic equipment against surges. For installation into


electrical installation systems, e.g. flush-mounted systems, cable ducts
and flush-type boxes. German utility patent for DEHNflex A / ... D. For
installation in conformity with the lightning protection zones concept at
the boundaries from 1 – 2 and higher.

DEHNflex M: More compact version; for use in cable duct systems and flush-mounted socket outlets
DEHNflex A: For use in any cable duct systems or flush-mounted socket outlets; with test function
DEHNflex D: Like DEHNflex A, but for series connection of several socket outlets

The name of the DEHNflex family refers to the nearly unlimited applica- The distinctive Y protection circuit always ensures safety even if the phase
Surge Arresters Type 3

tion possibilities of the devices. Being 2-pole surge arresters, the compact and neutral conductors cannot be identified. Apart from the powerful Y
modules are ideally suited for protecting electronic consumers in final cir- circuit, the compact enclosure also incorporates a disconnector and an
cuits. The design was adapted to the most common installation locations, acoustic fault indicator. In cable ducts, flush-mounted systems, branching
i.e. cable ducts and flush-type boxes. DEHNflex devices show that small boxes or device tubs – DEHNflex can always be installed in the right place
and compact sizes do not necessarily mean low-capacity performance. close to terminal equipment.

132 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNflex


924 396 DFL M
255

SURGE ARRESTERS – TYPE 3 DEHNflex M

DFL M 255 DEHNflex


M 924 396

N PE L

Dimension drawing DFL M Basic circuit diagram DFL M

DFL M: Surge arrester for use in all types of installation systems for terminal equipment; compact
dimensions

DFL M 255
SPD according to EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Nominal a.c. voltage UN 230 V
Max. continuous operating a.c. voltage UC 255 V
Nominal discharge current (8/20 μs) In 1.5 kA
Total discharge current (8/20 μs) [L+N-PE] Itotal 3 kA
Combined impulse UOC 3 kV
Combined impulse [L+N-PE] UOC total 6 kV
Voltage protection level [L-N] UP ) 1.25 kV
Voltage protection level [L/N-PE] UP ) 1.5 kV
Response time [L-N] tA ) 25 ns
Response time [L/N-PE] tA ) 100 ns
Max. mains-side overcurrent protection 32 A gL/gG or B 32 A
Short-circuit withstand capability for mains-side overcurrent protection with 32 A gL/gG 6 kArms
Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec.

Surge Arresters Type 3


Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec.
Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms
Fault indication acoustic signal on
Operating temperature range TU -25°C...+40°C
Terminal wires 1 mm2 , length: 120 mm
Enclosure material thermoplastic, red, UL 94 V-2
Degree of protection of installed device IP 20
Dimension 30 x 50 x 11 mm

Ordering information
Type DFL M 255
Part No. 924 396
Packing unit 1 pc(s).

www.dehn.de 133
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNflex POWER SUPPLY SYSTEMS


924 389 DFL A 255

DEHNflex A SURGE ARRESTERS – TYPE 3

DFL A 255 DEHNflex


L A 924 389

PE

Basic circuit diagram DFL A Dimension drawing DFL A

DFL A: Surge arrester for use in all types of installation systems for terminal equipment; with test
function

DFL A 255
SPD according to EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Nominal a.c. voltage UN 230 V
Max. continuous operating a.c. voltage UC 255 V
Nominal discharge current (8/20 μs) In 3 kA
Total discharge current (8/20 μs) [L+N-PE] Itotal 5 kA
Combined impulse UOC 6 kV
Combined impulse [L+N-PE] UOC total 10 kV
Voltage protection level [L-N] UP ) 1.25 kV
Voltage protection level [L/N-PE] UP ) 1.5 kV
Response time [L-N] tA ) 25 ns
Response time [L/N-PE] tA ) 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
Short-circuit withstand capability for mains-side overcurrent protection with 16 A gL/gG 6 kArms
Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec.
Surge Arresters Type 3

Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec.


Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms
Fault indication acoustic signal on
Operating temperature range TU -25°C...+40°C
Terminal wires 1 mm2 , length: 120 mm
Enclosure material thermoplastic, red, UL 94 V-2
Degree of protection of installed device IP 20
Dimension 36 x 62 x 19 mm

Ordering information
Type DFL A 255
Part No. 924 389
Packing unit 1 pc(s).

134 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNflex


924 395 DFL D 255

SURGE ARRESTERS – TYPE 3 DEHNflex D

DFL D 255 DEHNflex


D 924 395
L

PE

Dimension drawing DFL D Basic circuit diagram DFL D

DFL D: Surge arrester for use in all types of installation systems for terminal equipment; allows for
through-wiring; with test function

DFL D 255
SPD according to EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Nominal a.c. voltage UN 230 V
Max. continuous operating a.c. voltage UC 255 V
Nominal load current a.c. IL 16 A
Nominal discharge current (8/20 μs) In 3 kA
Total discharge current (8/20 μs) [L+N-PE] Itotal 5 kA
Combined impulse UOC 6 kV
Combined impulse [L+N-PE] UOC total 10 kV
Voltage protection level [L-N] UP ) 1.25 kV
Voltage protection level [L/N-PE] UP ) 1.5 kV
Response time [L-N] tA ) 25 ns
Response time [L/N-PE] tA ) 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
Short-circuit withstand capability for mains-side overcurrent protection with 16 A gL/gG 6 kArms

Surge Arresters Type 3


Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec.
Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec.
Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms
Fault indication acoustic signal on
Operating temperature range TU -25°C...+40°C
Terminal wires 2.5 mm2 , length: 120 mm
Enclosure material thermoplastic, red, UL 94 V-2
Degree of protection of installed device IP 20
Dimension 36 x 62 x 19 mm

Ordering information
Type DFL D 255
Part No. 924 395
Packing unit 1 pc(s).

www.dehn.de 135
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

NSM Protector POWER SUPPLY SYSTEMS


Surge protective socket outlet SURGE ARRESTERS – TYPE 3
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

• Surge protection with monitoring device and


disconnector
• Maximum safety due to distinctive Y protection
circuit
• Visual operating state (green) and fault indica-
tion (red)
• With supporting ring (dimension 60 mm) for
installation into switchboxes with a diameter of
60 mm and a depth of 40 mm

For protecting electronic equipment against surges. Earthed socket outlet


contact and surge protective circuit for installation into electrical installa-
tion systems. For installation according to the lightning protection zones
concept at the boundaries from 1 – 2 and higher. German utility patent.

NSM Protector: Earthed socket outlet with integrated surge protection

The devices of the NSM Protector family combine surge protection and the devices of the NSM Protector family. The distinctive Y protective cir-
earthed socket outlet in one single device. The two-pole surge arresters cuit ensures safety even if the phase and neutral conductors in final cir-
are specifically designed for protecting electronic consumers in final cir- cuits cannot be identified. The integrated disconnector makes a further
Surge Arresters Type 3

cuits. The very compact design of NSM Protector devices already includes contribution to the safety of devices and installations. The standard green
the approved disconnector. It isolates overloaded surge arresters without and red LEDs inform the user on the present operating state of the surge
interrupting the supply circuit. The low voltage protection level as well as protective devices.
the comprehensive common and differential mode protection is typical of

136 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS NSM Protector


924 335 NSM PRO
TW

SURGE ARRESTERS – TYPE 3 NSM PRO


924 337 NSM PRO
SI
924 339 NSM PRO
AZ
924 342 NSM PRO
EW

L/N L/N
NSM PRO TW NSM-
Protector DELTA profile, titan white 924 335
NSM PRO SI NSM-
Protector DELTA profile, silver 924 337
NSM PRO AZ NSM-
Protector DELTA profile, anthracite 924 339
NSM PRO EW NSM-
Protector DELTA profile, studio white 924 342

PE

Dimension drawing NSM PRO ... Basic circuit diagram NSM PRO ...

NSM PRO ...: Surge protective socket outlet

NSM PRO TW NSM PRO SI NSM PRO AZ NSM PRO EW


SPD according to EN 61643-11 Type 3 Type 3 Type 3 Type 3
SPD according to IEC 61643-1 Class III Class III Class III Class III
Nominal a.c. voltage UN 230 V 230 V 230 V 230 V
Max. continuous operating a.c. voltage UC 255 V 255 V 255 V 255 V
Nominal discharge current (8/20 μs) In 3 kA 3 kA 3 kA 3 kA
Total discharge current (8/20 μs) [L+N-PE] Itotal 5 kA 5 kA 5 kA 5 kA
Combined impulse UOC 6 kV 6 kV 6 kV 6 kV
Combined impulse [L+N-PE] UOC total 10 kV 10 kV 10 kV 10 kV
Voltage protection level [L-N] UP ) 1.25 kV ) 1.25 kV ) 1.25 kV ) 1.25 kV
Voltage protection level [L/N-PE] UP ) 1.5 kV ) 1.5 kV ) 1.5 kV ) 1.5 kV
Response time [L-N] tA ) 25 ns ) 25 ns ) 25 ns ) 25 ns
Response time [L/N-PE] tA ) 100 ns ) 100 ns ) 100 ns ) 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A 16 A gL/gG or B 16 A 16 A gL/gG or B 16 A 16 A gL/gG or B 16 A
Short-circuit withstand capability for mains-side
overcurrent protection with 16 A gL/gG 6 kArms 6 kArms 6 kArms 6 kArms
Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec. 335 V / 5 sec. 335 V / 5 sec.
Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec. 400 V / 5 sec. 440 V / 5 sec. 400 V / 5 sec.

Surge Arresters Type 3


Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms 1200 V + U0 / 200 ms 1200 V + U0 / 200 ms 1200 V + U0 / 200 ms
Fault indication red light red light red light red light
Operating state indication green light green light green light green light
Operating temperature range TU -25°C...+40°C -25°C...+40°C -25°C...+40°C -25°C...+40°C
Cross-sectional area screwless double terminals up to 2.5 mm2 each, also suitable for series connection
For mounting on supporting ring (Ø60 mm) for installation into switchboxes, depth of 32 mm
Enclosure material thermoplastic, UL 94 V-2 thermoplastic, UL 94 V-2 thermoplastic, UL 94 V-2 thermoplastic, UL 94 V-2
Degree of protection IP 20 IP 20 IP 20 IP 20
DELTA type profile, titanium white profile, silver profile, anthracite plus, studio white

Ordering information
Type NSM PRO TW NSM PRO SI NSM PRO AZ NSM PRO EW
Part No. 924 335 924 337 924 339 924 342
Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for NSM Protector


AR1 Covering Frame
924 336
924 338
924 340
924 343
AR1 TW
AR1 SI
AR1 AZ
AR1 EW

Single unit, suitable for NSM Protector


AR1 TW Protector
Cover, single-piece, titan white 924 336
AR1 SI Protector
Cover, single piece, silver
AR1 AZ
Cover, single piece, anthracite
924 338
Protector
924 340
PU Part
AR1 EW Protector
Type
Cover, single piece, studio white 924 343
Profile pc(s). No.
AR1 TW DELTA profile, titanium white 1 924 336
AR1 SI DELTA profile, silver 1 924 338
AR1 AZ DELTA profile, anthracite 1 924 340
AR1 EW DELTA plus, studio white 1 924 343

www.dehn.de 137
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNprotector POWER SUPPLY SYSTEMS


Surge protective adapter SURGE ARRESTERS – TYPE 3
Type 3 according to EN 61643-11
Class III according to EN 61643-1

• Surge protection with monitoring device and


disconnector
• Visual operating state (green) and fault indica-
tion (red)
• Mains filter (DEHNpro 230 F-Protector only)
• Enhanced safety due to distinctive Y protection
circuit

Adapters for protecting the power supply circuit of electronic devices


against transient overvoltages as well as high-frequency interference
voltages (DEHNpro 230 F-Protector). For installation in conformity with
the lightning protection zones concept at the boundaries from 1 – 2 and
higher.

DEHNpro 230: Protection for terminal devices


DEHNpro 230 F: Protection for terminal devices with mains filter

The surge protective adapters of the DEHNpro family provide surge pro- devices in final circuits. The distinctive Y protection circuit ensures protec-
tection for electronic consumers connected to final circuits. In the tion even if the phase and neutral conductors in standard earthed socket
Surge Arresters Type 3

DEHNpro 230 F-Protector, the powerful surge protective circuit of outlets cannot be identified. The integrated disconnector also contributes
DEHNpro 230 Protector was supplemented by an interference suppressor to the safety of devices and installations. The standard green and red LEDs
filter with a balancing and unbalancing effect. This combination of surge inform the user on the operating state of the surge protective devices.
protection and filter prevents a core saturation of the filter in case of high- The modern design of DEHNpro devices and the use of high-quality mate-
energy transients. The nominal current carrying capability of 16 A for rials ensure safety in a sophisticated appearance. The DEHNpro devices
DEHNpro 230 and 10 A for 230 F-Protector allows flexible use of these thus ideally adapt to the environment. They create the right technical
ambience already at the socket outlet for connecting the latest communi-
cation and multimedia systems. The curved enclosure surfaces and the
smooth surface structure ensure that the DEHNpro devices will not lose
their original properties even after several years of application.

138 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS DEHNprotector


909 230 DPRO 230

SURGE ARRESTERS – TYPE 3 DPRO 230 Protector

DPRO 230
909 230
L/N

red
L'/N'

PE green PE

N'/L'

N/L

Dimension drawing DPRO 230 Basic circuit diagram DPRO 230

DPRO 230: Surge protective adapter

DPRO 230 DPRO 230 SE


SPD according to EN 61643-11 Type 3 Type 3
SPD according to IEC 61643-1 Class III Class III
Nominal a.c. voltage UN 230 V 230 V
Max. continuous operating a.c. voltage UC 255 V 255 V
Nominal load current a.c. IL 16 A 16 A
Nominal discharge current (8/20 μs) In 3 kA 3 kA
Total discharge current (8/20 μs) [L+N-PE] Itotal 5 kA 5 kA
Combined impulse UOC 6 kV 6 kV
Combined impulse [L+N-PE] UOC total 10 kV 10 kV
Voltage protection level [L-N] UP ) 1.25 kV ) 1.25 kV
Voltage protection level [L/N-PE] UP ) 1.5 kV ) 1.5 kV
Response time [L-N] tA ) 25 ns ) 25 ns
Response time [L/N-PE] tA ) 100 ns ) 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A 16 A gL/gG or B 16 A
Short-circuit withstand capability for

Surge Arresters Type 3


mains-side overcurrent protection with 16 A gL/gG 6 kArms 6 kArms
Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec.
Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec. 400 V / 5 sec.
Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms 1200 V + U0 / 200 ms
Fault indication red LED red LED
Operating state indication green LED green LED
Operating temperature range TU -25°C...+40°C -25°C...+40°C
For mounting on plug-in system with earth contact centre earthing contact system
according to DIN 49440 / DIN 49441 according to CEE 7, standard sheet V
Enclosure material thermoplastic, pure white, UL 94 V-2 thermoplastic, pure white, UL 94 V-2
Degree of protection IP 20 IP 20
Dimension 128 x 71 x 40 mm 128 x 71 x 40 mm

Ordering information
Type DPRO 230 DPRO 230 SE
Part No. 909 230 909 235
Packing unit 1 pc(s). 1 pc(s).

www.dehn.de 139
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

DEHNprotector POWER SUPPLY SYSTEMS


909 240 DPRO 230
F

DPRO 230 F-Protector SURGE ARRESTERS – TYPE 3

DPRO 230 F

L/N 909 240

red
L'/N'

PE green PE

N'/L'

N/L

Basic circuit diagram DPRO 230 F Dimension drawing DPRO 230 F

DPRO 230 F: Surge protective adapter with integrated mains filter

DPRO 230 F DPRO 230 SE F


SPD according to EN 61643-11 Type 3 Type 3
SPD according to IEC 61643-1 Class III Class III
Nominal a.c. voltage UN 230 V 230 V
Max. continuous operating a.c. voltage UC 255 V 255 V
Nominal load current a.c. IL 10 A 10 A
Nominal discharge current (8/20 μs) In 3 kA 3 kA
Total discharge current (8/20 μs) [L+N-PE] Itotal 5 kA 5 kA
Combined impulse UOC 6 kV 6 kV
Combined impulse [L+N-PE] UOC total 10 kV 10 kV
Voltage protection level [L-N] UP ) 1.25 kV ) 1.25 kV
Voltage protection level [L/N-PE] UP ) 1.5 kV ) 1.5 kV
Response time [L-N] tA ) 25 ns ) 25 ns
Response time [L/N-PE] tA ) 100 ns ) 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A 16 A gL/gG or B 16 A
Short-circuit withstand capability for
Surge Arresters Type 3

mains-side overcurrent protection with 16 A gL/gG 6 kArms 6 kArms


Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec.
Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec. 400 V / 5 sec.
Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms 1200 V + U0 / 200 ms
Fault indication red light red light
Operating state indication green light green light
Operating temperature range TU -25°C...+40°C -25°C...+40°C
For mounting on plug-in system with earth contact centre earthing contact system
according to DIN 49440 / DIN 49441 according to CEE 7, standard sheet V
Enclosure material thermoplastic, pure white, UL 94 V-2 thermoplastic, pure white, UL 94 V-2
Degree of protection IP 20 IP 20
Dimension 128 x 71 x 40 mm 128 x 71 x 40 mm
Mains filter acc. to DIN VDE 0565 Part 3 acc. to DIN VDE 0565 Part 3
Attenuation for f = 1 MHz, balanced * 40 dB * 40 dB
Attenuation for f = 1 MHz, unbalanced * 30 dB * 30 dB

Ordering information
Type DPRO 230 F DPRO 230 SE F
Part No. 909 240 909 245
Packing unit 1 pc(s). 1 pc(s).

140 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS SFL Protector


SURGE ARRESTERS – TYPE 3 Surge protective multiple socket outlet with filter
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

• Surge protection with monitoring device and


disconnector
• Interference suppressor filter
• Enhanced safety due to distinctive Y protection
circuit
• Mains switch with operating state indication
• Visual fault indicator (red)

Multiple socket outlet for protecting the power supply circuit of electron-
ic devices against transient surges as well as high-frequency interference
voltages. For installation in conformity with the lightning protection zones
concept at the boundaries from 1 – 2 and higher.

SFL Protector: Surge protective multiple socket outlet with interference suppressor filter

The SFL Protector compelements the wide range of Red/Line surge protec- quency interferences. With a nominal current carrying capability of 16 A,
tive devices. The combination of surge protection and mains filter makes the SFL Protector can be used flexibly in final electrical circuits. The dis-
the 5-fold socket outlet a powerful device for protecting electronic con- tinctive Y protection circuit ensures protection even if the phase and neu-
sumers in final electrical circuits. The coordinated functions of surge pro- tral conductors in standard earthed socket outlets cannot be identified.
tection and filter complement one another and prevent a core saturation The standard green and red LEDs inform the user at a glance about the
of the filter in case of high-energy transients. The integrated mains filter present operating state of the surge protective device.
was optimised for protection against balanced and unbalanced high-fre-

Surge Arresters Type 3

www.dehn.de 141
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

SFL Protector POWER SUPPLY SYSTEMS


912 260 SFL PRO

SFL PRO SURGE ARRESTERS – TYPE 3

SFL PRO SFL-


Protector 912 260

L/N

PE approx.

N/L

Basic circuit diagram SFL PRO Dimension drawing SFL PRO

SFL PRO: Surge protective multiple socket outlet with mains filter

SFL PRO SFL PRO SE


SPD according to EN 61643-11 Type 3 Type 3
SPD according to IEC 61643-1 Class III Class III
Nominal a.c. voltage UN 230 V 230 V
Max. continuous operating a.c. voltage UC 255 V 255 V
Nominal load current a.c. IL 16 A 16 A
Nominal discharge current (8/20 μs) In 3 kA 3 kA
Total discharge current (8/20 μs) [L+N-PE] Itotal 5 kA 5 kA
Combined impulse UOC 6 kV 6 kV
Combined impulse [L+N-PE] UOC total 10 kV 10 kV
Voltage protection level UP ) 1.5 kV ) 1.5 kV
Response time [L-N] tA ) 25 ns ) 25 ns
Response time [L/N-PE] tA ) 100 ns ) 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A 16 A gL/gG or B 16 A
Short-circuit withstand capability for
mains-side overcurrent protection with 16 A gL/gG 1.5 kArms 1.5 kArms
Surge Arresters Type 3

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec.


Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec. 400 V / 5 sec.
Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms 1200 V + U0 / 200 ms
Fault indication red light red light
Operating state indication green light green light
Operating temperature range TU -25°C...+40°C -25°C...+40°C
Connecting cable length: 200 cm length: 200 cm
Number of socket outlets 5 5
For mounting on plug-in system with earth contact centre earthing contact system
according to DIN 49440 / DIN 49441 according to CEE 7, standard sheet V
Enclosure material black/anthracite thermoplastic, UL 94 V-2 black/anthracite thermoplastic, UL 94 V-2
Degree of protection IP 20 IP 20
Dimension 513 x 55 x 47 mm 513 x 55 x 47 mm
Mains filter according to DIN VDE 0565 Part 3 according to DIN VDE 0565 Part 3
Attenuation for f = 1 MHz, balanced * 54 dB * 54 dB
Attenuation for f = 1 MHz, unbalanced * 42 dB * 42 dB

Ordering information
Type SFL PRO SFL PRO
Part No. 912 260 912 261
Packing unit 1 pc(s). 1 pc(s).

142 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS VC 280 2


SURGE ARRESTERS – TYPE 3 Compact protection for terminal equipment
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

• Two-pole surge arrester with monitoring device


and disconnector
• Complete surge protective circuit for devices
with a.c. voltage power supply
• Enhanced safety due to distinctive Y protection
circuit
• Floating remote signalling contact (break con-
tact) with test option for fault indication
• For installation onto printed circuit boards

For protecting electronic equipment against surges. For installation into


the enclosure or directly into the device to be protected. For installation
in conformity with the lightning protection zones concept at the bound-
aries from 1 – 2 and higher. German utility patent.

VC 280 2: Surge protective mains module for installation into the terminal device to be protected

Surge arresters of type VC 280 2 are small-sized, but still feature all even feature an integrated test option for testing the fault indicator.
required characteristics. The two-pole module includes a distinctive Y pro- VC 280 2 reliably protects electronic equipment against surges. The solder

Surge Arresters Type 3


tection circuit, monitoring device and disconnector as well as a floating pins allow the SPD to be installed directly onto the PCBs of the device to
remote signalling contact ensuring maximum compact safety. The SPDs be protected.

www.dehn.de 143
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters– Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

VC 280 2 POWER SUPPLY SYSTEMS


900 471 VC 280 2

VC 280 2 SURGE ARRESTERS – TYPE 3


L/N L/N
VC 280 2 Mains
Surge Protection Module, 2-pole 900 471

11

12

Basic circuit diagram VC 280 2 Dimension drawing VC 280 2

VC 280 2: Surge protective mains module for installation into terminal devices to be protected

VC 280 2
SPD according to EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Nominal a.c. voltage UN 230 V
Max. continuous operating a.c. voltage UC 280 V
Nominal discharge current (8/20 μs) In 3 kA
Total discharge current (8/20 μs) [L+N-PE] Itotal 5 kA
Combined impulse UOC 6 kV
Combined impulse [L+N-PE] UOC total 10 kV
Voltage protection level [L-N] UP ) 1.25 kV
Voltage protection level [L/N-PE] UP ) 1.5 kV
Response time [L-N] tA ) 25 ns
Response time [L/N-PE] tA ) 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
Short-circuit withstand capability for mains-side overcurrent protection with 16 A gL/gG 6 kArms
Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec.
Surge Arresters Type 3

Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec.


Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms
Fault indication remote signalling contact
Operating temperature range UT -25°C...+40°C
For mounting on printed circuit board
Enclosure material thermoplastic, red, UL 94 V-2
Degree of protection IP 20
Dimension 32 x 24 x 15 mm
Type of remote signalling contact break contact
Switching capacity a.c. 250 V/0.5 A
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Ordering information
Type VC 280 2
Part No. 900 471
Packing unit 1 pc(s).

144 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS Wiring Accessories


ACCESSORIES DK 25 and STAK 2X16

• DK 25 allows to change the wiring level


• DK 25 supports lightning-impulse-current-con-
form installation of SPD combinations
• STAK 2X16 allows to clamp cross sections that
are smaller than the defined minimum clamp-
ing cross section of the surge protective device
• STAK 2X16 allows EMC-optimised series con-
nection according to IEC 60364-5-53

EMC-optimised series connection of lightning current and surge arresters


952 699 DK 25

according to IEC 60364-5-53 by means of STAK 2X16

DK 25
NEW
952 699

Dimension drawing DK 25 DK 25 STAK 2X16


900 589 STAK
2X16

DK 25: Feed-through terminal for busbar wiring


STAK 2X16: Pin-shaped terminal

STAK 2X16
900 589

DK 25 STAK 2X16
Accessories
Nominal a.c./d.c. voltage UN 500 V —
Nominal load current a.c. IL 100 A —
Test current according to EN 60947-7-1 100 A —
Lightning impulse current (10/350 μs) 100 kA —
Rated insulation voltage Ui 630 V —
Rated impulse withstand voltage Uimp 6 kV —
Operating temperature range TU -40°C...+80°C —
Cross-sectional area min. 1.5 mm2 solid/flexible, max. 25 mm2 stranded/16 mm2 flexible 2x min. 1.5 mm2, max. 16 mm2
For mounting on 35 mm DIN rail according to EN 60715 —
Type of connection — front (double terminal)
Enclosure material thermoplastic, red, UL 94 V-0 —
Degree of protection IP 20 —
Capacity 1 mod., DIN 43880 —

Ordering information
Type DK 25 STAK 2X16
Part No. 952 699 NEW 900 589
Packing unit 1 pc(s). 1 pc(s).

www.dehn.de 145
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

Insulating Enclosure POWER SUPPLY SYSTEMS


ACCESSORIES

• Enclosure for installing surge arresters tested


with lightning impulse currents

Application example: Modular DEHNventil® M TNC in


IGA 10 V2 IP54 insulating enclosure

902 315 IGA 10 V2 IP54

IGA 10 V2 IP54

NEW IGA 10 V2 IP54


902 315

Dimension drawing IGA 10 V2 IP54


Accessories

IGA 10 V2 IP54: Insulating enclosure for the installation of max. 10 modules; with membrane
flange for 5 cables Ø7-30 mm EPDM and 3 mounted membrane openings M20
with lock nut; ideally suited for through-wiring

IGA 10 V2 IP54
Degree of protection IP 54
Tested with lightning currents 3
Type of cover Transparent cover
Colour of enclosure grey
Quantity of cable entries 1 x for cables Ø7...10 mm; 2x for cables Ø10...14 mm or Ø15...30 mm each; 3 x for cables Ø8...13 mm
Available installation space 10 mods., DIN 43880
Dimension (W x H x D) 200 x 300 x 132 mm
Sealable 3

Ordering information
Type IGA 10 V2 IP54
Part No. 902 315
Packing unit 1 pc(s).

146 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS Insulating Enclosure


902 471 IGA 12
IP54

ACCESSORIES IGA 12 IP54

IGA 12 IP54
902 471

Dimension drawing IGA 12 IP54 Integrated plug-in terminal technology


for PE and N conductors
IGA 12 IP54: Insulating enclosure for max. 12 modules, for non-exhausting SPDs

IGA 12 IP54
Degree of protection IP 54
Type of cover transparent cover
Colour of enclosure grey, RAL 7035
Cable entry integrated, elastic sealing membrane for entering cables
PE/N Quantity x Cross section 3 x 25 mm2, 12 x 4 mm2, Cu
Available installation space 12 mods., DIN 43880
Dimension (W x H x D) 295 x 333 x 129 mm

Ordering information
Type IGA 12 IP54
Part No. 902 471
Packing unit 1 pc(s).

902 472 IGA 24


IP54

IGA 24 IP54

IGA 24 IP54
902 472

Dimension drawing IGA 24 IP54 Integrated plug-in terminal technology


Accessories
for PE and N conductors
IGA 24 IP54: Insulating enclosure for max. 2x 12 modules, for non-exhausting SPDs

IGA 24 IP54
Degree of protection IP 54
Type of cover transparent cover
Colour of enclosure grey, RAL 7035
Cable entry integrated, elastic sealing membrane for entering cables
PE/N Quantity x Cross section 6 x 25 mm2, 24 x 4 mm2, Cu
Available installation space 24 (2x 12) mods., DIN 43880
Dimension (W x H x D) 295 x 458 x 129 mm

Ordering information
Type IGA 24 IP54
Part No. 902 472
Packing unit 1 pc(s).

www.dehn.de 147
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

Insulating Enclosure POWER SUPPLY SYSTEMS


902 485 IGA 6
IP54

IGA 6 IP54 ACCESSORIES

IGA 6 IP54 Insulating


Enclosure 6 mods. 902 485

Dimension drawing IGA 6 IP54

IGA 6 IP54: Enclosure for non-exhausting SPDs for max. 6 modules

IGA 6 IP54
Degree of protection IP 54
Type of cover transparent cover
Colour of enclosure grey
Quantity of cable entries 2 plug-in glands EST 21 for cables Ø9 ... 21 mm
Available installation space 6 mods., DIN 43880
Dimension (W x H x D) 165 x 255 x 115 mm
Sealable 3

Ordering information
Type IGA 6 IP54
Part No. 902 485
Packing unit 1 pc(s).
Accessories

148 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS Busbars / Modular Wiring System


ACCESSORIES
• Allows for compact connection of SPDs with one
another and to other DIN rail mounted devices

MVS 1 2 MVS 2-pole, single-phase


Single-phase unit 3
Number of contact studs 2
900 617 MVS 1 2

Max. installation width 2 mods.


MVS 1 2
900 617
Nominal cross section 16 mm2

Ordering information
Type MVS 1 2
Part No. 900 617
Packing unit 1 pc(s).

MVS 1 3 MVS 3-pole, single-phase


Single-phase unit 3
Number of contact studs 3
900 615 MVS 1 3 Max. installation width 3 mods.
MVS 1 3
900 615
Nominal cross section 16 mm2

Ordering information
Type MVS 1 3
Part No. 900 615
Packing unit 1 pc(s).

900 610 MVS 1 4

MVS 1 4 MVS 4-pole, single-phase


Single-phase unit 3
MVS 1 4 Busbar
single-phase, 4-pole 900 610

Number of contact studs 4


Max. installation width 4 mods. Accessories
Nominal cross section 16 mm2

Ordering information
Type MVS 1 4
Part No. 900 610
Packing unit 1 pc(s).

MVS 1 6 MVS 6-pole, single-phase


Single-phase unit 3
Number of contact studs 6
Max. installation width 6 mods.
Nominal cross section 16 mm2
900 815 MVS 1 6

Ordering information
MVS 1 6
900 815 Type MVS 1 6
Part No. 900 815
Packing unit 1 pc(s).

www.dehn.de 149
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

Busbars / Modular Wiring System POWER SUPPLY SYSTEMS


ACCESSORIES

MVS 7-pole, single-phase MVS 1 7


Single-phase unit 3 900 848 MVS 1 7

Number of contact studs 7


Max. installation width 7 mods.
Nominal cross section 16 mm2 MVS 1 7
900 848

Ordering information
Type MVS 1 7
Part No. 900 848
Packing unit 1 pc(s).

MVS 8-pole, single-phase MVS 1 8 900 611 MVS 1 8

Single-phase unit 3
Number of contact studs 8 MVS 1 8
single-phase, 8-pole
Busbar
900 611

Max. installation width 8 mods.


Nominal cross section 16 mm2

Ordering information
Type MVS 1 8
Part No. 900 611
Packing unit 1 pc(s).

MVS 57-pole, single-phase MVS 1 57 900 612 MVS 1 57

Single-phase unit 3
Number of contact studs 57
Max. installation width 57 mods.
MVS 1 57 Busbar
single-phase, 57-pole 900 612

Nominal cross section 16 mm2

Ordering information
Type MVS 1 57
Part No. 900 612
Packing unit 1 pc(s).

MVS 6-pole, three-phase MVS 3 6


Three-phase unit 3
Number of contact studs 6
900 595 MVS 3 6

Max. installation width 6 mods.


Accessories

Nominal cross section 16 mm2 MVS 3 6


phase, 6-pole
Busbar 3-
900 595

Ordering information
Type MVS 3 6
Part No. 900 595
Packing unit 1 pc(s).

MVS 6-pole, three-phase MVS 3 6 8


Three-phase unit 3 900 813 MVS 3 6
8

Number of contact studs 6


Max. installation width 8 mods. MVS 3 6 8
phase, 8-pole
Busbar 3-
900 813

Nominal cross section 16 mm2

Ordering information
Type MVS 3 6 8
Part No. 900 813
Packing unit 1 pc(s).

150 www.dehn.de
Combined Lightning Current N-PE Lightning Current Surge Arresters – Surge Arresters –
Arresters – Type 1 Arresters – Type 1 Arresters – Type 1 Type 2 Type 3 Accessories

POWER SUPPLY SYSTEMS Busbars / Modular Wiring System


ACCESSORIES
900 814
11
MVS 4 8

MVS 4 8 11 MVS 8-pole, four-phase


MVS 4 8 11
phase, 11-pole
Busbar 4-
900 814 Four-phase unit 3
Number of contact studs 8
Max. installation width 11 mods.
Nominal cross section 16 mm2

Ordering information
Type MVS 4 8 11
Part No. 900 814
Packing unit 1 pc(s).

MVS 4 56 MVS 56-pole, four-phase


3
900 614 MVS 4 56

Four-phase unit
MVS 4 56 Busbar 4-
Number of contact studs 56
phase, 56-pole 900 614

Max. installation width 56 mods.


Nominal cross section 16 mm2

Ordering information
Type MVS 4 56
Part No. 900 614
Packing unit 1 pc(s).

900 411 EB DG
EB DG 1000 1 3 DG Earthing Clip, 3-pole,
single-phase
1000 1 3

Single-phase unit 3
EB DG 1000 1 3
900 411 Number of contact studs 3
Dimension 34 x 112 x 3 mm
Terminal up to 25 mm2

Ordering information
Type EB DG 1000 1 3
Part No. 900 411
Packing unit 1 pc(s).

EB 1 4 9 Earthing Clip, 4-pole,


900 417
49
EB 1 Single-phase unit 3 single-phase
Number of contact studs 4
EB 1 4 9
900 417
Dimension 34 x 148 x 3 mm
Terminal up to 25 mm2 Accessories

Ordering information
Type EB 1 4 9
Part No. 900 417
Packing unit 1 pc(s).

www.dehn.de 151
152 www.dehn.de
Surge protection for
INFORMATION
TECHNOLOGY SYSTEMS
SPDs for installations and equipment

www.dehn.de 153
Cross-reference INFORMATION TECHNOLOGY SYSTEMS

Discontinued Products Alternatives Discontinued Products Alternatives


Part No. Type Part No. Type Part No. Type Part No. Type

Pluggable SPDs for DIN rail mounting Pluggable SPDs for DIN rail mounting
BLITZDUCTOR CT BLITZDUCTOR XT BLITZDUCTOR CT BLITZDUCTOR XT
919 506 BCT BAS 920 300 BXT BAS 919 522 BCT MOD ME 15 920 222 BXT ML2 BE S 12 or
919 310 BCT MLC B 110 920 310 BXT ML4 B 180 920 322 BXT ML4 BE 12
919 320 BCT MLC BE 5 920 220 BXT ML2 BE S 5 or 919 523 BCT MOD ME 24 920 224 BXT ML2 BE S 24 or
920 320 BXT ML4 BE 5 920 324 BXT ML4 BE 24
919 321 BCT MLC BE 12 920 222 BXT ML2 BE S 12 or 919 524 BCT MOD ME 30 920 224 BXT ML2 BE S 24 or
920 322 BXT ML4 BE 12 920 324 BXT ML4 BE 24
919 322 BCT MLC BE 15 920 222 BXT ML2 BE S 12 or 919 525 BCT MOD ME 48 920 225 BXT ML2 BE S 48 or
920 322 BXT ML4 BE 12 920 325 BXT ML4 BE 48
919 323 BCT MLC BE 24 920 224 BXT ML2 BE S 24 or 919 526 BCT MOD ME 60 920 326 BXT ML4 BE 60
920 324 BXT ML4 BE 24 919 527 BCT MOD ME 110 920 327 BXT ML4 BE 180
919 324 BCT MLC BE 30 920 224 BXT ML2 BE S 24 or 919 560 BCT MOD ME C 5 ––
920 324 BXT ML4 BE 24 919 561 BCT MOD ME C 12 920 362 BXT ML4 BE C 12
919 325 BCT MLC BE 48 920 225 BXT ML2 BE S 48 or 919 562 BCT MOD ME C 24 920 364 BXT ML4 BE C 24
920 325 BXT ML4 BE 48 919 563 BCT MOD ME C 30 920 364 BXT ML4 BE C 24
919 326 BCT MLC BE 60 920 326 BXT ML4 BE 60 919 540 BCT MOD MD 5 920 240 BXT ML2 BD S 5 or
919 327 BCT MLC BE 110 920 327 BXT ML4 BE 180 920 340 BXT ML4 BD 5
919 360 BCT MLC BE C 5 –– 919 541 BCT MOD MD 12 920 242 BXT ML2 BD S 12 or
919 361 BCT MLC BE C 12 920 362 BXT ML4 BE C 12 920 342 BXT ML4 BD 12
919 362 BCT MLC BE C 24 920 364 BXT ML4 BE C 24 919 542 BCT MOD MD 15 920 242 BXT ML2 BD S 12 or
919 363 BCT MLC BE C 30 920 364 BXT ML4 BE C 24 920 342 BXT ML4 BD 12
919 340 BCT MLC BD 5 920 240 BXT ML2 BD S 5 or 919 543 BCT MOD MD 24 920 244 BXT ML2 BD S 24 or
920 340 BXT ML4 BD 5 920 344 BXT ML4 BD 24
919 341 BCT MLC BD 12 920 242 BXT ML2 BD S 12 or 919 544 BCT MOD MD 30 920 244 BXT ML2 BD S 24 or
920 342 BXT ML4 BD 12 920 344 BXT ML4 BD 24
919 342 BCT MLC BD 15 920 242 BXT ML2 BD S 12 or 919 545 BCT MOD MD 48 920 245 BXT ML2 BD S 48 or
920 342 BXT ML4 BD 12 920 345 BXT ML4 BD 48
919 343 BCT MLC BD 24 920 244 BXT ML2 BD S 24 or 919 546 BCT MOD MD 60 920 346 BXT ML4 BD 60
920 344 BXT ML4 BD 24 919 547 BCT MOD MD 110 920 247 BXT ML2 BD 180 or
919 344 BCT MLC BD 30 920 244 BXT ML2 BD S 24 or 920 347 BXT ML4 BD 180
920 344 BXT ML4 BD 24 919 549 BCT MOD MD 250 ––
919 345 BCT MLC BD 48 920 245 BXT ML2 BD S 48 or 919 570 BCT MOD MD HF 5 920 270 BXT ML2 BE HFS 5 or
920 345 BXT ML4 BD 48 920 370 BXT ML4 BE HF 5
919 346 BCT MLC BD 60 920 346 BXT ML4 BD 60 919 571 BCT MOD MD HFD 5 920 271 BXT ML2 BD HFS 5 or
919 347 BCT MLC BD 110 920 247 BXT ML2 BD 180 or 920 371 BXT ML4 BD HF 5
920 347 BXT ML4 BD 180 919 575 BCT MOD MD HFD 24 920 375 BXT ML4 BD HF 24
919 349 BCT MLC BD 250 –– 919 552 BCT MOD MD TC N ––
919 370 BCT MLC BD HF 5 920 270 BXT ML2 BE HFS 5 or 919 589 BCT MOD MY 250 920 389 BXT ML4 MY 250
920 370 BXT ML4 BE HF 5 919 502 GDT 90 ––
919 371 BCT MLC BD HFD 5 920 271 BXT ML2 BD HFS 5 or 919 504 BCT MOD PTS 920 309 BXT M4 T
920 371 BXT ML4 BD HF 5 919 505 EKS BCT 920 308 BXT M4 E
919 375 BCT MLC BD HFD 24 920 375 BXT ML4 BD HF 24
919 508 EFK BCT 920 395 SAK BXT LR
919 520 BCT MOD ME 5 920 220 BXT ML2 BE S 5 or
920 320 BXT ML4 BE 5
919 521 BCT MOD ME 12 920 222 BXT ML2 BE S 12 or
920 322 BXT ML4 BE 12

Accessories for compact SPDs for DIN rail mounting SPDs for coaxial connection
919 885 KB 5 DCO RK –– 929 041 DGA G 1.6 5.6 929 040 DGA F 1.6 5.6
919 888 KB 8 DCO RK –– 929 058 DGA G N 3 929 044 DGA G N
SPDs for LSA technology SPDs for terminal connection
907 209 GDT 230 G3 FS 907 217 GDT 230 G3 FSD 924 271 DSM TC 1 SK 924 272 DSM TC 2 SK
907 215 DPL 10 G3 110 FS 907 216 DPL 10 G3 110 FSD 924 273 DSM TC DK SK ––
SPDs for data cabinets 482.6 mm (19 inch) Accessories for screwable SPDs
929 067 NET PRO ISDN 929 100 DPA M CAT6 RJ45S 48 929 981 KV S M20 MS 13 ––
929 068 NET PRO ISDN LSA 929 100 DPA M CAT6 RJ45S 48 929 985 KV M20 MS 8 ––
929 069 NET PRO TC 1 929 071 NET PRO TC 2 SPDs for potentially explosive areas
929 070 NET PRO TC 1 LSA 929 072 NET PRO TC 2 LSA 919 507 BCT BAS EX 920 301 BXT BAS EX
SPDs for RJ connection 919 580 BCT MOD MD EX 24 920 381 BXT ML4 BD EX 24
929 027 DLI TC 1 I 929 028 DLI TC 2 I 919 581 BCT MOD MD EX 30 920 381 BXT ML4 BD EX 24
929 029 DLI TC DK –– 919 583 BCT MOD MD HFD EX 6 920 538 BXT ML2 BD HF EX 6
929 080 DLI TC ECO 929 028 DLI TC 2 I

154 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS CONTENTS

Easy choice according to Interface / Signal 156

Pluggable SPDs for DIN rail mounting 179

Compact SPDs for DIN rail mounting 209

SPDs for LSA technology 229


1 2 3 4 5 6 7 8 9 0

SPDs for data cabinets 482.6 mm (19 inch) 247

SPDs for RJ connection 253

SPDs for BT Jack connection 265

SPDs for coaxial connection 267

SPDs for D-Sub connection 281

SPDs for terminal connection 289

Screwable SPDs 297

SPDs for use in potentially explosive areas 301

Accessories for terminal block systems 325

Combined adapters 337

Measuring and test devices 359

155

www.dehn.de
Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS

Bus systems and measuring and control technology Page 156 – 165
Telecommunications, Telephony Page 166 – 169
Data networks Page 170 – 171
Antenna systems, Broadband systems,
Transmitting and receiving systems, Video systems Page 172 – 174

Bus systems and measuring and control technology


LifeCheck SPD
Protected class
Interface / Signal For mounting on Ex Connection system lines TYPE SPD Part No. Page

0-20 mA, 4-20 mA screw terminals 4 1 1 920 324 + 920 300 188
(also with HART)
screw terminals 2 1 1 920 224 + 920 300 197
J J
spring terminals 2 2 919 921 210
Joker
actiVsense®

J J
spring terminals 2 3 919 988 215

wires / terminals 2 2 929 921 293

4-20 mA screw terminals 4 1 1 920 344 + 920 300 189


(also with HART) acc.
to NAMUR recommen- screw terminals 2 1 1 920 244 + 920 300 196
dation NE 21 or acc. to 2
spring terminals 2 919 941 211
EN 61000-4-5, open-circuit
voltage 1 kV A-PG screw terminals 4 2 918 407 220
J J

Joker wires / terminals 2 2 929 941 292


actiVsense®

J J
1 907 401
LSA 20 + 907 498 + 907 442 232

3/4 conductor measuring screw terminals 4 1 1 920 354 + 920 300 190

ADVANT screw terminals 4 1 1 920 370 + 920 300 192

screw terminals 2 1 1 920 270 + 920 300 198

screw terminals 5 2 918 401 221

spring terminals 2 2 919 970 214

AS interface vampire taps 2 2 925 013 293

Binary signals screw terminals 4 1 1 920 320 – 327 + 920 300 188

screw terminals 2 1 1 920 220 – 225 + 920 300 197

spring terminals 2 2 919 920 – 923 210

spring terminals 2 3 919 987 – 990 215

1 907 401
LSA 20 + 907 498 + 907 422 232

Bitbus screw terminals 4 1 1 920 370 + 920 300 192

screw terminals 2 1 1 920 270 + 920 300 198

spring terminals 2 2 919 970 214

156 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal

Bus systems and measuring and control technology


LifeCheck SPD
Protected class
Interface / Signal For mounting on Ex Connection system lines TYPE SPD Part No. Page

BLN screw terminals 4 1 1 920 342 + 920 300 189


(Building Level network)
screw terminals 2 1 1 920 242 + 920 300 196

screw terminals 4 1 1 920 345 + 920 300 189

screw terminals 2 1 1 920 245 + 920 300 198

CAN Bus screw terminals 4 1 1 920 370 + 920 300 192


(data line only)
screw terminals 2 1 1 920 270 + 920 300 198
J J

Joker
actiVsense®
spring terminals 2 2 919 970 214
907 401
J J

LSA 20 1 232
+ 907 498 + 907 465

C Bus (Honeywell) screw terminals 4 1 1 920 370 + 920 300 192


J J

screw terminals 2 1 1 920 270 + 920 300 198


Joker
actiVsense®

J J
spring terminals 2 2 919 970 214

Control Net BNC 1 2 929 010 268

BNC 1 2 909 710 / 711 271

CP installations
Sensor circuit screw terminals 2 1 918 421 / 405 226

Anode circuit screw terminals 2 1 918 420 / 404 225

Data Highway Plus screw terminals 4 1 1 920 342 + 920 300 189
J J
screw terminals 2 1 1 920 242 + 920 300 196
Joker
actiVsense®

J J
spring terminals 2 2 919 940 214

d.c. power supply screw terminals 2 3 918 402 222


+24/30 V d.c.
screw terminals 2 1 918 408 223

Delta Net Peer Bus screw terminals 4 1 1 920 370 + 920 300 192

screw terminals 2 1 1 920 270 + 920 300 198

spring terminals 2 2 919 970 214

Device Net screw terminals 4 1 1 920 370 + 920 300 192


(data line only)
screw terminals 2 1 1 920 270 + 920 300 198
J J

Joker
actiVsense® spring terminals 2 2 919 970 214
J J

J J

Joker
actiVsense®

For further details please refer to page 174 J J

www.dehn.de 157
Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS

Bus systems and measuring and control technology


LifeCheck SPD
Protected class
Interface / Signal For mounting on Ex Connection system lines TYPE SPD Part No. Page

Dupline screw terminals 4 1 1 920 243 + 920 300 201


J J

Joker
actiVsense®

J J

E-Bus (Honeywell) screw terminals 4 1 1 920 345 + 920 300 189


J J
screw terminals 2 1 1 920 245 + 920 300 196
Joker
actiVsense®

J J

EIB screw terminals 4 1 1 920 310 + 920 300 187

screw terminals 2 1 1 920 211 + 920 300 200

wires 2 2 925 001 293

LSA 20 1 907 401 232

Electroacoustic screw terminals 4 1 1 920 327 + 920 300 188


system (ELA)
spring terminals 2 2 919 923 210

1 907 401
LSA 20 232
+ 907 498 + 907 445

ET 200 screw terminals 4 1 1 920 370 + 920 300 192

screw terminals 2 1 1 920 270 + 920 300 198

spring terminals 2 2 919 970 214

Ex(d) circuits
4-20 mA, NAMUR, wires 2 2 929 962 / 964 308
HART, PROFIBUS-PA, FF

Ex (i) circuits screw terminals 4 1 2 920 381 + 920 301 314

screw terminals 4 1 2 920 538 + 920 301 316

spring terminals 2 2 919 960 323

wires / terminals 2 2 929 960 303

wires 2 2 929 961 / 963 306

wires 2 2 929 971 309

screw terminals 4 1 2 989 408 321

Fieldbus Foundation screw terminals 4 1 1 920 344 + 920 300 189

screw terminals 2 1 1 920 244 + 920 300 196


J J

Joker
actiVsense® spring terminals 2 2 919 941 211
J J

wires / terminals 2 2 929 941 294

1 907 401
LSA 20 232
+ 907 498 + 907 442

158 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal

Bus systems and measuring and control technology


LifeCheck SPD
Protected class
Interface / Signal For mounting on Ex Connection system lines TYPE SPD Part No. Page

Fieldbus Foundation screw terminals 4 1 2 920 381 + 920 301 314


Ex (i)
screw terminals 4 1 2 920 538 + 920 301 316

spring terminals 2 2 919 960 323

wires / terminals 2 2 929 960 303

wires 2 2 929 961 / 963 306

wires 2 2 929 971 309

screw terminals 4 1 2 989 408 321

FIPIO / FIPWAY screw terminals 4 1 1 920 344 + 920 300 189

screw terminals 2 1 1 920 244 + 920 300 196

FIP I / O screw terminals 4 1 1 920 370 + 920 300 192

screw terminals 2 1 1 920 270 + 920 300 198

FSK screw terminals 4 1 1 920 371 + 920 300 193


J J
screw terminals 2 1 1 920 271 + 920 300 199
Joker
actiVsense®

J J
spring terminals 2 2 919 970 214

Genius I/O Bus screw terminals 4 1 1 920 342 + 920 300 189

screw terminals 2 1 1 920 242 + 920 300 196

IEC Bus (RS 485) screw terminals 4 1 1 920 370 + 920 300 192
J J
screw terminals 2 1 1 920 270 + 920 300 198
Joker
actiVsense®

J J spring terminals 2 2 919 970 214

1 907 401
Industrial Ethernet LSA 20 232
+ 907 498 + 907 470

RJ45 8 2 929 100 / 110 254

RJ45 8 2 929 121 255

RJ45, LSA / RJ45 8x8 3 929 035 / 036 249

RJ45 8x8 4 929 037 249

RJ45 4 2 909 321 337

INTERBUS INLINE (I/O) screw terminals 4 1 1 920 345 + 920 300 189
J J
screw terminals 4 1 1 920 325 + 920 300 188
Joker
actiVsense®

J J

J J

Joker
actiVsense®

For further details please refer to page 174 J J

www.dehn.de 159
Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS

Bus systems and measuring and control technology


LifeCheck SPD
Protected class
Interface / Signal For mounting on Ex Connection system lines TYPE SPD Part No. Page

INTERBUS Loop spring terminals 2 3 919 988 215

Interbus INLINE screw terminals 4 1 1 920 371 + 920 300 193


Long-distance bus
screw terminals 2 1 1 920 271 + 920 300 2199
J J

Joker
actiVsense®
screw terminals 5 2 918 401 221
J J

K Bus screw terminals 4 1 1 920 344 + 920 300 189

screw terminals 2 1 1 920 244 + 920 300 196

spring terminals 2 2 919 941 211

KBR Energy bus screw terminals 4 1 1 920 370 + 920 300 192

screw terminals 2 1 1 920 270 + 920 300 198

spring terminals 2 2 919 970 214

KNX Bus screw terminals 4 1 1 920 310 + 920 300 187

screw terminals 2 1 1 920 211 + 920 300 200

wires 2 2 925 001 291

LSA 20 1 907 401 232

LON
– TP/XF 78 screw terminals 4 1 1 920 340 + 920 300 189

screw terminals 2 1 1 920 240 + 920 300 196

–TP/FTT10 (up to 1 A) screw terminals 4 1 1 920 345 + 920 300 189


and TP/LPT10
(up to 1 A) screw terminals 2 1 1 920 245 + 920 300 196

(up to 1.7 A) spring terminals 2 2 919 942 212

1 907 401
(up to 0.4 A) LSA 20 232
+ 907 498 + 907 443

– TP/FTT 10 screw terminals 4 1 1 920 371 + 920 300 193

screw terminals 2 1 1 920 271 + 920 300 199

LUXMATE Bus screw terminals 4 1 1 920 344 + 920 300 189


J J
screw terminals 2 1 1 920 244 + 920 300 196
Joker
actiVsense®

J J

M Bus screw terminals 4 1 1 920 345 + 920 300 189

J J
screw terminals 2 1 1 920 245 + 920 300 196
Joker
actiVsense®
spring terminals 2 2 919 942 212
J J

1 907 401
LSA 20 + 907 498 + 907 443 232

160 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal

Bus systems and measuring and control technology


LifeCheck SPD
Protected class
Interface / Signal For mounting on Ex Connection system lines TYPE SPD Part No. Page

Melsec Net 2 BNC 1 2 929 010 268

BNC 1 2 909 710 / 711 271

MODBUS screw terminals 4 1 1 920 370 + 920 300 192

J J screw terminals 2 1 1 920 270 + 920 300 198


Joker
actiVsense®
spring terminals 2 2 919 970 214
J J

1 907 401
LSA 20 + 907 498 + 907 465 232

MPI Bus screw terminals 4 1 1 920 370 + 920 300 192


J J
screw terminals 2 1 1 920 270 + 920 300 198
Joker
actiVsense®

J J
spring terminals 2 2 919 970 214

N1 LAN screw terminals 4 1 1 920 371 + 920 300 193

screw terminals 2 1 1 920 271 + 920 300 199

screw terminals 4 1 1 920 370 + 920 300 192

screw terminals 2 1 1 920 270 + 920 300 198

spring terminals 2 2 919 970 214

BNC 1 2 909 710 / 711 271

N2 Bus (Johnson Controls, screw terminals 4 1 1 920 371 + 920 300 193
LON, FTT 10)
screw terminals 2 1 1 920 271 + 920 300 199

Optocoupler screw terminals 4 1 1 920 364 + 920 300 191


Interface
screw terminals 4 2 918 400 219

Procontic CS31 (RS 232) screw terminals 4 1 1 920 322 + 920 300 188

Procontic T200 (RS 422) screw terminals 4 1 1 920 371 + 920 300 193
J J
screw terminals 5 2 918 401 221
Joker
actiVsense®

J J

PROFIBUS DP/FMS screw terminals 4 1 1 920 370 + 920 300 192

screw terminals 2 1 1 920 270 + 920 300 198


J J

Joker D-Sub, 9-pole 4 4 924 017 282


actiVsense®

2
J J
spring terminals 2 919 970 214

1 907 401
LSA 20 + 907 498 + 907 465 232

J J

Joker
actiVsense®

For further details please refer to page 174 J J

www.dehn.de 161
Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS

Bus systems and measuring and control technology


LifeCheck SPD
Protected class
Interface / Signal For mounting on Ex Connection system lines TYPE SPD Part No. Page

PROFIBUS PA screw terminals 4 1 1 920 344 + 920 300 189

screw terminals 2 1 1 920 244 + 920 300 196


J J
spring terminals 2 2 919 941 211
Joker
actiVsense®

J J
wires / terminals 2 2 929 941 294

1 907 401
LSA 20 + 907 498 + 907 442 232

PROFIBUS PA Ex (i) screw terminals 4 1 2 920 381 + 920 301 314

screw terminals 4 1 2 920 538 + 920 301 316

spring terminals 2 2 919 960 323

wires / terminals 2 2 929 960 303

wires 2 2 929 961 / 963 306

wires 2 2 929 971 309

screw terminals 4 1 2 989 408 321

PROFIBUS SIMATIC NET screw terminals 4 1 1 920 370 + 920 300 192
J J

Joker screw terminals 2 1 1 920 270 + 920 300 198


actiVsense®

J J

PSM EG RS 422 screw terminals 4 1 1 920 371 + 920 300 193


J J
screw terminals 5 2 918 401 221
Joker
actiVsense®

J J

PSM EG RS 485 screw terminals 4 1 1 920 371 + 920 300 193


J J
screw terminals 2 1 1 920 271 + 920 300 199
Joker
actiVsense®

J J screw terminals 5 2 918 401 221

Rackbus (RS 485) screw terminals 4 1 1 920 371 + 920 300 193
J J
screw terminals 2 1 1 920 271 + 920 300 199
Joker
actiVsense®

J J screw terminals 5 2 918 401 221

R Bus screw terminals 4 1 1 920 340 + 920 300 189


J J
screw terminals 2 1 1 920 240 + 920 300 196
Joker
actiVsense®

J J
spring terminals 2 2 919 970 214

162 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal

Bus systems and measuring and control technology


LifeCheck SPD
Protected class
Interface / Signal For mounting on Ex Connection system lines TYPE SPD Part No. Page

RS 485 screw terminals 4 1 1 920 370 + 920 300 192

screw terminals 4 1 2 920 538 + 920 301 316


J J

Joker
actiVsense®
screw terminals 2 1 1 920 270 + 920 300 198
J J

screw terminals 5 2 918 401 221

spring terminals 2 2 919 970 214

1 907 401
LSA 20 + 907 498 + 907 442 232

wires 2 2 929 971 309

RS 422, V11 screw terminals 4 1 1 920 370 + 920 300 192

screw terminals 2 1 1 920 270 + 920 300 198

screw terminals 5 2 918 401 221


J J
spring terminals 2 2 919 970 214
Joker
actiVsense®

J J
D-Sub, 15-pole 6 2 924 051 287

D-Sub, 15-pole 6 4 924 016 284

1 907 401
LSA 20 + 907 498 + 907 465 232

S Bus screw terminals 4 1 1 920 370 + 920 300 192

screw terminals 2 1 1 920 270 + 920 300 198

spring terminals 2 2 919 970 214

SafetyBUS p screw terminals 4 1 1 920 370 + 920 300 192


J J
screw terminals 2 1 1 920 270 + 920 300 198
Joker
actiVsense®

J J spring terminals 2 2 919 970 214

SDLC screw terminals 4 1 1 920 370 + 920 300 192

screw terminals 2 1 1 920 270 + 920 300 198

spring terminals 2 2 919 970 214

SDLS RJ45, screw terminals 4 2 918 410 257

1 907 401
LSA 20 232
+ 907 498 + 907 470

J J

Joker
actiVsense®

For further details please refer to page 174 J J

www.dehn.de 163
Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS

Bus systems and measuring and control technology


LifeCheck SPD
Protected class
Interface / Signal For mounting on Ex Connection system lines TYPE SPD Part No. Page

Securilan LON Bus screw terminals 4 1 1 920 340 + 920 300 189
(LONWORKS Technology
screw terminals 2 1 1 920 240 + 920 300 196
Standard Bus based on
Echelon) 2
spring terminals 2 919 970 214

SIGMASYS screw terminals 4 1 1 920 345 + 920 300 189


(Siemens fire
screw terminals 2 1 1 920 245 + 920 300 196
alarm system)
screw terminals 4 1 1 920 325 + 920 300 188

screw terminals 2 1 1 920 225 + 920 300 197

1 907 401
LSA 20 232
+ 907 498 + 907 423

SINEC L1 screw terminals 4 1 1 920 370 + 920 300 192

screw terminals 2 1 1 920 270 + 920 300 198

SINEC L2 screw terminals 4 1 1 920 370 + 920 300 192

screw terminals 2 1 1 920 270 + 920 300 198

spring terminals 2 2 919 970 214

D-Sub, 9-pole 4 4 924 017 282

SS97 SIN/X (RS 232) screw terminals 4 1 1 920 322 + 920 300 188

screw terminals 2 1 1 920 222 + 920 300 197

SUCONET screw terminals 4 1 1 920 340 + 920 300 189


J J
screw terminals 2 1 1 920 240 + 920 300 196
Joker
actiVsense®

J J

Temperature screw terminals 4 1 1 920 350 + 920 300 190


measuring
screw terminals 4 1 1 920 354 + 920 300 190
PT 100, PT 1000
Ni 1000, NTC, PTC screw terminals 4 1 1 920 320 + 920 300 188

screw terminals 2 1 1 920 220 + 920 300 197

spring terminals 2 2 919 970 214

Temperature
measuring Ex (i) screw terminals 4 1 2 920 384 + 920 301 315
PT 100, PT 1000,
Ni 1000, NTC, PTC

164 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal

Bus systems and measuring and control technology


LifeCheck SPD
Protected class
Interface / Signal For mounting on Ex Connection system lines TYPE SPD Part No. Page

TTL screw terminals 4 1 1 920 322 + 920 300 188

screw terminals 2 1 1 920 222 + 920 300 197

spring terminals 2 2 919 920 210

D-Sub, 25-pole 4, 9 2 924 046 288

D-Sub, 9-pole 9 4 924 019 283

TTY screw terminals 4 1 1 920 364 + 920 300 191

screw terminals 2 1 1 920 362 + 920 300 191

screw terminals 4 2 918 400 219

TTY 4 – 20 mA screw terminals 4 1 1 920 324 + 920 300 188

screw terminals 2 1 1 920 224 + 920 300 197

spring terminals 2 2 919 921 210

spring terminals 2 3 919 988 215

wires / terminals 2 2 929 921 295

J J

Joker
actiVsense®

For further details please refer to page 174 J J

www.dehn.de 165
Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS

Telecommunications, Telephony
LifeCheck SPD-
Protected class
Interface / Signal For mounting on Ex Connection system lines TYPE SPD Part No. Page

1 907 401
a/b wires LSA 20 232
+ 907 498 + 907 430

J J
RJ45, LSA / RJ45 8x2 2 929 071 / 072 250
Joker
actiVsense®
screw terminals 4 1 1 920 347 + 920 300 189
J J

RJ45, screw terminals 2 2 918 411 258

TAE, RJ12 2 2 909 310 335

spring terminals / RJ45 2 2 929 230 252

BT jack 6 2 929 026 266

ADSL screw terminals 4 1 1 920 347 + 920 300 189

screw terminals 2 1 1 920 247 + 920 300 195

1 907 401
LSA 20 232
+ 907 498 + 907 430
J J
wires 2 2 924 272 289
Joker
actiVsense®

J J
TAE, RJ12 2 2 909 310 335

RJ45, LSA / RJ45 8x2 2 929 071 / 072 250

RJ45, screw terminals 2 2 918 411 258

spring terminals / RJ45 2 2 929 230 252

BT jack 6 2 929 026 266

1 907 401
ADSL 2+ LSA 20 232
+ 907 498 + 907 430
J J

screw terminals 4 1 1 920 347 + 920 300 189


Joker
actiVsense®

J J

Datex P screw terminals 4 1 1 920 375 + 920 300 193

E1 RJ45 8x2 2 929 100 / 110 254

1 907 401
LSA 20 232
+ 907 498 + 907 470

LSA / RJ45 8x4 2 929 075 251

screw terminals 4 1 1 920 375 + 920 300 193

G.703 koax 1.6/5.6 connector 1 3 929 040 273

insulation displacement
G.703 / G.704 2 2 907 214 240
terminal
LSA / RJ45 8x4 2 929 075 251

RJ45 8x2 2 929 100 / 110 254

1 907 401
LSA 20 232
+ 907 498 + 907 470

screw terminals 4 1 1 920 375 + 920 300 193

166 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal

Telecommunications, Telephony
LifeCheck SPD-
Protected class
Interface / Signal For mounting on Ex Connection system lines TYPE SPD Part No. Page

HDSL screw terminals 4 1 1 920 375 + 920 300 193


up to 30 dBm for 600 W 907 401
LSA 20 1 232
+ 907 498 + 907 470

RJ45 8x2 2 929 100 / 110 254

LSA / RJ45 8x4 2 929 075 251

ISDN S0 screw terminals 4 1 1 920 375 + 920 300 193

RJ45 4 2 929 024 262

1 907 401
LSA 20 232
J J + 907 498 + 907 470
Joker
actiVsense®
wires 4 2 924 270 288
J J

RJ45 4 2 909 320 336

RJ45 8x2 2 929 100 / 110 254

RJ45, screw terminals 4 2 918 410 257

RJ45, screw terminals 4 2 924 274 260

ISDN S2m / U2m screw terminals 4 1 1 920 375 + 920 300 193

1 907 401
LSA 20 232
J J + 907 498 + 907 470
Joker
actiVsense®
RJ45 8x2 2 929 100 / 110 254
J J

LSA / RJ45 8x4 2 929 075 251

ISDN UK0 / UP0 screw terminals 4 1 1 920 347 + 920 300 189

screw terminals 2 1 1 920 247 + 920 300 195

spring terminals 2 2 919 943 213


J J

Joker 1 907 401


actiVsense® LSA 20 232
J J
+ 907 498 + 907 430

RJ45, LSA / RJ45 8x2 2 929 071 / 072 250

TAE, RJ12 2 2 909 310 335

RJ45, screw terminals 2 2 918 411 258

spring terminals / RJ45 10 x 2 2 929 230 252

Modem M1 screw terminals 4 1 1 920 322 + 920 300 188

screw terminals 2 1 1 920 222 + 920 300 197

SDSL RJ45 8x2 2 929 100 / 110 254


J J

1 907 401
Joker LSA 20 232
actiVsense® + 907 498 + 907 470
J J

screw terminals 4 1 1 920 375 + 920 300 193

LSA / RJ45 8x4 2 929 075 251

J J

Joker
actiVsense®

For further details please refer to page 174 J J

www.dehn.de 167
Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS

Telecommunications, Telephony
LifeCheck SPD-
Protected class
Interface / Signal For mounting on Ex Connection system lines TYPE SPD Part No. Page

SHDSL screw terminals 4 1 1 920 371 + 920 300 193

screw terminals 4 1 1 920 375 + 920 300 193

RJ45 8x2 2 929 100 / 110 254


J J

Joker 1 907 401


actiVsense® LSA 20 232
J J
+ 907 498 + 907 470

screw terminals 4 1 1 920 310 + 920 300 187

screw terminals 2 1 1 920 211 + 920 300 200

LSA / RJ45 8x4 2 929 075 251

Telephony screw terminals 2 1 1 920 247 + 920 300 195


System Telephony
spring terminals 2 2 919 943 213
e. g. Siemens, HICOM,
Alcatel RJ45, RJ11 4 2 929 028 263

RJ12 2 2 929 081 264

1 907 401
LSA 20 232
+ 907 498 + 907 430
J J

1 907 401
Joker LSA 20 232
actiVsense® + 907 498 + 907 445
J J

wires 4 2 924 272 291

RJ45, LSA / RJ45 8x2 2 929 071 / 072 250

TAE, RJ12 2 2 909 310 335

RJ45, screw terminals 2 2 918 411 258

spring terminals / RJ45 10 x 2 2 929 230 252

T-DSL screw terminals 4 1 1 920 347 + 920 300 189

screw terminals 2 1 1 920 247 + 920 300 195

1 907 401
LSA 20 232
+ 907 498 + 907 430
J J

Joker wires 2 2 924 272 291


actiVsense®

2
J J
TAE, RJ12 2 909 310 335

RJ45, LSA / RJ45 8x2 2 929 071 / 072 248

RJ45, screw terminals 2 2 918 411 258

spring terminals / RJ45 10 x 2 2 929 230 252

1 907 401
Telecommunication LSA 20 232
+ 907 498 + 907 430
systems
RJ45, LSA / RJ45 8x2 2 929 071 / 072 250
J J
screw terminals 2 1 1 920 347 + 920 300 189
Joker
actiVsense®

J J RJ45, screw terminals 2 2 918 411 258

TAE, RJ12 2 2 909 310 335

spring terminals / RJ45 10 x 2 2 929 230 252

BT jack 6 2 929 026 266

168 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal

Telecommunications, Telephony
LifeCheck SPD-
Protected class
Interface / Signal For mounting on Ex Connection system lines TYPE SPD Part No. Page

Universal lightning screw terminals 4 1 1 920 310 + 920 300 187


equipotential bonding
screw terminals 2 1 1 920 211 + 920 300 200

LSA 20 1 907 400 231

LSA 20 1 907 401 232


insulation displacement
terminal 20 2 907 214 240
insulation displacement 2
20 907 216 240
terminal

VDSL LSA 20 1 907 401 232


J J
screw terminals 4 1 1 920 310 + 920 300 187
Joker
actiVsense®

J J screw terminals 4 1 1 920 211 + 920 300 200

J J

Joker
actiVsense®

For further details please refer to page 174 J J

www.dehn.de 169
Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS

Data networks
LifeCheck SPD-
Protected class
Interface / Signal For mounting on Connection system lines TYPE SPD Part No. Page

Arcnet BNC 1 2 929 010 268

BNC 1 2 909 710 / 711 271

ATM RJ45 8 2 929 100 / 110 254

RJ45 8 2 929 121 255

RJ45, LSA / RJ45 8x8 3 929 035 / 036 249

RJ45 8x8 4 929 037 249

RJ45 4 2 909 321 337

Ethernet 10/100/1000 RJ45 8 2 929 100 / 110 254

RJ45 8 2 929 121 255

RJ45, LSA / RJ45 8x8 3 929 035 / 036 249

RJ45 8x8 4 929 037 249

RJ45 4 2 909 321 337

10 Base T RJ45, screw terminals 4 2 924 274 260

RJ45 4 2 909 320 336

LSA 20 1 907 401 232


+ 907 498 + 907 470

FDDI, CDDI RJ45 8 2 929 100 / 110 254

RJ45 8 2 929 121 255

RJ45, LSA / RJ45 8x8 3 929 035 / 036 249

RJ45 8x8 4 929 037 249

RJ45 4 2 909 321 337

1 907 401
Industrial Ethernet LSA 20 232
+ 907 498 + 907 470

RJ45 8 2 929 100 / 110 254

RJ45 8 2 929 121 255

RJ45, LSA / RJ45 8x8 3 929 035 / 036 249

RJ45 8x8 4 929 037 249

RJ45 4 2 909 321 337

Power over Ethernet RJ45 8 2 929 100 / 110 254


PoV
RJ45 8 2 929 121 255

RJ45 8x8 4 929 037 249

170 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal

Data networks
LifeCheck SPD-
Protected class
Interface / Signal For mounting on Connection system lines TYPE SPD Part No. Page

1 907 401
Token Ring LSA 20 232
+ 907 498 + 907 470

RJ45 8 2 929 100 / 110 254

RJ45 8 2 929 121 255

RJ45, LSA / RJ45 8x8 3 929 035 / 036 249

RJ45 8x8 4 929 037 249

RJ45 4 2 909 321 337

V 24 (RS 232 C) screw terminals 4 1 1 920 322 + 920 300 188

spring terminals 2 2 919 921 210

1 907 401
LSA 20 232
+ 907 498 + 907 421

D-Sub 9-, 25-pole 4, 9 2 924 046 / 061 288

D-Sub 9-, 25-pole 9 4 924 018 / 019 283

VG AnyLAN RJ45 8 2 929 100 / 110 254

RJ45 8 2 929 121 255

RJ45, LSA / RJ45 8x8 3 929 035 / 036 249

RJ45 8x8 4 929 037 249

RJ45 4 2 909 321 337

Voice over IP RJ45 8 2 929 100 / 110 254

RJ45 8x8 4 929 037 249

RJ45 4 2 909 321 337

J J

Joker
actiVsense®

For further details please refer to page 174 J J

www.dehn.de 171
Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS

Antenna systems, Broadband systems, Transmitting and receiving systems, Video systems
SPD-
Protected Frequency class
Interface / Signal For mounting on Connection system lines range TYPE SPD Part No. Page

AMPS, NADAC BNC 1 d.c. – 4 GHz 2 929 042 274


(824 – 894 MHz)
BNC 1 d.c. – 1 GHz 1 929 043 275

N Connector 1 d.c. – 5.8 GHz 2 929 044 274

N Connector 1 d.c. – 2.5 GHz 1 929 045 275

7/16 Connector 1 d.c., 806 – 2200 MHz 1 929 046 276

7/16 Connector 1 d.c., 806 – 2200 MHz 1 929 446 276

7/16 Connector 1 880 – 2200 MHz 1 929 048 277

BWA (Broadband BNC 1 d.c. – 4 GHz 2 929 042 274


Wireless Access)
N Connector 1 d.c. – 5.8 GHz 2 929 044 274

N Connector 1 2.0 – 6.0 GHz 1 929 059 278

CATV F Connector 1 d.c., 5 – 2400 MHz 1 909 705 272

IEC / F Connector 1 d.c. – 2400 MHz 2 909 300 334

DCS 1800 B162 BNC 1 d.c. – 4 GHz 2 929 042 274


(1710 – 1880 MHz)
N Connector 1 d.c. – 5.8 GHz 2 929 044 274

N Connector 1 d.c. – 2.5 GHz 1 929 045 275

7/16 Connector 1 d.c., 806 – 2200 MHz 1 929 046 276

7/16 Connector 1 d.c., 806 – 2200 MHz 1 929 446 276

7/16 Connector 1 880 – 2200 MHz 1 929 048 277

DCF 77 BNC 1 d.c. – 4 GHz 2 929 042 274

BNC 1 d.c. – 1 GHz 1 929 043 275

GPS (1565 – 1585 MHz) BNC 1 d.c. – 4 GHz 2 929 042 274

N Connector 1 d.c. – 5.8 GHz 2 929 044 274

N Connector 1 d.c. – 2.5 GHz 1 929 045 275

7/16 Connector 1 d.c., 806 – 2300 MHz 1 929 046 276

7/16 Connector 1 d.c., 806 – 2200 MHz 1 929 446 276

7/16 Connector 1 880 – 2200 MHz 1 929 048 277

GSM 900, GSMR BNC 1 d.c. – 4 GHz 2 929 042 274


(876 – 960 MHz)
BNC 1 d.c. – 1 GHz 1 929 043 275

N Connector 1 d.c. – 5.8 GHz 2 929 044 274

N Connector 1 d.c. – 2.5 GHz 1 929 045 275

7/16 Connector 1 d.c., 806 – 2200 MHz 1 929 046 276

7/16 Connector 1 d.c., 806 – 2200 MHz 1 929 446 276

7/16 Connector 1 880 – 2200 MHz 1 929 048 277

172 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal

Antenna systems, Broadband systems, Transmitting and receiving systems, Video systems
SPD-
Protected Frequency class
Interface / Signal For mounting on Connection system lines range TYPE SPD Part No. Page

PCS 1900 BNC 1 d.c. – 4 GHz 2 929 042 274


(1850 – 1990 MHz)
N Connector 1 d.c. – 5.8 GHz 2 929 044 274

N Connector 1 d.c. – 2.5 GHz 1 929 045 275

7/16 Connector 1 d.c., 806 – 2200 MHz 1 929 046 276

7/16 Connector 1 d.c., 806 – 2200 MHz 1 929 446 276

7/16 Connector 1 880 – 2200 MHz 1 929 048 277

Radio systems BNC 1 d.c. – 4 GHz 2 929 042 274

BNC 1 d.c. – 1 GHz 1 929 043 275

N Connector 1 d.c. – 5.8 GHz 2 929 044 274

N Connector 1 d.c. – 2.5 GHz 1 929 045 275

7/16 Connector 1 d.c., 806 – 2200 MHz 1 929 046 276

7/16 Connector 1 d.c., 806 – 2200 MHz 1 929 446 276

U Connector 1 d.c. - 300 MHz 1 929 057 235

7/16 Connector 1 380 – 512 MHz 1 929 047 277

7/16 Connector 1 880 – 2200 MHz 1 929 048 277

N Connector 1 2,0 – 6,0 GHz 1 929 059 278

SAT F Connector 1 d.c., 5 – 2400 MHz 1 909 705 272

Sky DSL F Connector 1 d.c., 5 – 2400 MHz 1 909 705 272

TETRA, NMT 450 BNC 1 d.c. – 4 GHz 2 929 042 274


(380 – 512 MHz)
BNC 1 d.c. – 1 GHz 1 929 043 275

N Connector 1 d.c. – 5.8 GHz 2 929 044 274

N Connector 1 d.c. – 2.5 GHz 1 929 045 275

7/16 Connector 1 380 – 512 MHz 1 929 047 277

TV F Connector 1 d.c., 5 – 3000 MHz 3 909 703 272

F Connector 1 d.c. – 2400 MHz 1 909 704 272

F Connector 1 d.c., 5 – 2400 MHz 1 909 705 272

IEC / F Connector 1 d.c. – 2400 MHz 2 909 300 334

J J

Joker
actiVsense®

For further details please refer to page 174 J J

www.dehn.de 173
Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS

Antenna systems, Broadband systems, Transmitting and receiving systems, Video systems
SPD-
Protected Frequency class
Interface / Signal For mounting on Connection system lines range TYPE SPD Part No. Page

UMTS BNC 1 d.c. – 4 GHz 2 929 042 274

N Connector 1 d.c. – 5.8 GHz 2 929 044 274

N Connector 1 d.c. – 2.5 GHz 1 929 045 275

7/16 Connector 1 d.c., 806 – 2200 MHz 1 929 046 276

7/16 Connector 1 d.c., 806 – 2200 MHz 1 929 446 276

7/16 Connector 1 880 – 2200 MHz 1 929 048 277

WiMax N Connector 1 2.0 – 6.0 GHz 1 929 059 278

WLAN (2.4 GHz band) BNC 1 d.c. – 4 GHz 2 929 042 274

N Connector 1 d.c. – 5.8 GHz 2 929 044 274

WLAN (5 GHz band) N Connector 1 d.c. – 5.8 GHz 2 929 044 274

N Connector 1 2.0 – 6.0 GHz 1 929 059 278

Video (2-wire) screw terminals 4 d.c. – 100 MHz 1 920 370 + 920 300 192

RJ45 8 d.c. – 250 MHz 2 929 100 / 110 254

RJ45 8 d.c. – 250 MHz 2 929 121 255

screw terminals 2 d.c. – 100 MHz 1 920 270 + 920 300 198

RJ45 4 2 909 321 337

Video (coax) BNC 1 d.c. – 300 MHz 2 929 010 268

BNC 1 0 – 300 MHz 2 909 710 / 711 271

BLITZDUCTOR® XTU
J J Universal lightning current / surge arrester with actiVsense® technology
• Automatically detects the operating voltage
• Optimally adjusts the voltage protection level to the voltage currently applied
Joker
actiVsense® Application:
• Suitable fo the vast majority of applications in information technology systems
J J • Ideally suited for telecommunications systems, bus systems and measuring and control equipment

 The nominal current of the SPD is limited to 100 mA, allowing the device to be used for the vast majority of applications
in information technology systems. In some applications where the signal line is also used for power supply the current
may exceed 100 mA.
 All signals are transmitted with signal frequencies up to 25 MHz.
 In bus systems the SPD can be used for applications based on RS 485 / RS 422 interfaces (not RS 232).

For more detailed information, please refer to page 179.

174 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS SPDs for Information Technology Systems

Cate- Type of Impulse Impulse Minimum quan- Test


gory test voltage current tity of impulses for

C1 0.5 kV or 0.25 kA or 300


1 kV, 1.2/50 μs 0.5 kA, 8/20 μs

Surge arrester
C2 steep 2 kV, 4 kV, 1 kA, 2 kA 10
rate of or 10 kV, or 5 kA,
rise 1.2/50 μs 8/20 μs

C3 v 1 kV, 10 A, 25 A 300
1 kV/μs or 100 A,
10/1000 μs

D1 high v 1 kV 0.5 kA, 1 kA 2


energy or 2.5 kA, *)
10/350 μs

*) Lightning current arrester / Combined lightning current and surge arrester


Voltage and current impulses (preferred values) for determining the voltage limiting
characteristics (based on Table 3 of IEC 61643-21 / EN 61643-21)

General
The surge protection components of SPDs have no radioactive isotopes Immunity of terminal devices to be protected
and usually consist of at least one voltage-limiting or voltage-switching Within the scope of the test for electromagnetic compatibility (EMC), elec-
device, and sometimes of overcurrent-limiting components as well. SPDs trical and electronic equipment (devices) must have a predefined immuni-
consisting of several stages, must be designed without blind spot, i.e. it has ty against conducted pulse interferences (surges).
to be ensured that the different protective stages are fully coordinated Requirements for the immunity and test set-up are specified in EN 61000-
with each other. Otherwise, the protective stages will respond only partial- 4-5.
ly and lead to faults within the surge protective device. Different electromagnetic environmental conditions make different de-
mands on the immunity of the devices. The immunity of a device is linked
to the test level applied. For classifying the different immunities of termi-
Selection of SPDs
nal devices, the test levels are subdivided into four different stages. Test
When selecting SPDs, the following aspects must be especially taken into level 1 includes the minimum requirements for the immunity of the termi-
consideration: nal device. Generally, the test level can be taken from the documentation
– Protective effect [Yellow/Line SPD class (discharge capacity and protec- on the device or requested from its manufacturer.
tion level)]
– System parameters (system voltage, nominal current and transmission Test levels Corresponds to charging voltage
parameters) according to EN 61000-4-5 of the test generator
– Installation environment (design, connection conditions and certifica- 1 0.5 kV
tions) 2 1 kV
3 2 kV
The selection guide according to interface/signal on pages 156 to 174 shall 4 4 kV
facilitate the choice of the right SPD.

Protective effect of SPDs


Relevant product standard for the SPDs: Yellow/Line SPDs for use in IT systems can limit conducted interferences to
IEC 61643-21 / EN 61643-21 safe values to ensure that the immunity of the terminal device is not
Low voltage surge protective devices – Part 21: Surge protective devices exceeded. For protecting a terminal device tested for test level 2, a surge
connected to telecommunications and signalling networks – Performance arrester with a let-through value below the EMC test values of the termi-
requirements and testing methods. nal device has to be chosen:
Impulse voltage < 1 kV in combination with a pulse current of some
Discharge capacity amperes (depending on the coupling network).
According to IEC 61643-21 / EN 61643-21, SPDs must be tested with at
least one impulse voltage or impulse current as mentioned in the
following table, with the indicated number of impulses. Further tests can
be performed – even with different pulse amplitudes or quantities. The
maximum protection level during this or these tests is indicated
as voltage protection level UP measured at the output of the device.
Category C represents especially disturbing pulses with a steep rate of rise
and less energy, compared to the disturbing pulses of category D, which is
supposed to simulate high energy loads due to induced partial lightning
currents. The category is also indicated in the technical data of the SPDs –
both in the description of the discharge capacity (In, Iimp) and protection
level (UP).

www.dehn.de 175
Yellow/Line SPD Classes – Symbols INFORMATION TECHNOLOGY SYSTEMS

All SPD types of the Yellow/Line family for IT systems are assigned a Yellow/Line SPD class and marked correspondingly with a symbol in the technical
data sheet and on their rating plates. The symbol for the Yellow/Line SPD class graphically connects 3 important characteristics of the SPD and can be
one single symbol or a combination of individual symbols:

Characteristics Single symbol Definition

Discharge capacity of an SPD Impulse D1 (10/350 μs), lightning impulse current v 2.5 kA/line or v 5 kA/total
(according to categories from A • exceeds the discharge capacity of B – D
IEC 61643-21 / EN 61643-21)
Impulse C2 (8/20 μs), increased impulse load v 2.5 kA/line or v 5 kA/total
B • exceeds the discharge capacity of C – D

Impulse C1 (8/20 μs), impulse load v 0.25 kA/line or v 0.5 kA/total


C • exceeds the discharge capacity of D

D Load < C

Protective effect of an SPD Required test level of the terminal device: 1 or higher
(limitation below the test levels
according to EN 61000-4-5) Required test level of the terminal device: 2 or higher

Required test level of the terminal device: 3 or higher

Required test level of the terminal device: 4

Energy coordination SPD with decoupling impedance, suitable


(with a further Yellow/Line SPD)
k for coordination with an SPD marked

SPD is suitable for coordination with an SPD


with decoupling impedance k

Examples for energy coordination of SPDs according to Yellow/Line SPD classes:


Use of a combined lightning current and surge arrester

immunity severity
lightning current acc. to EN 61000-4-5

terminal
device

Cascaded use of SPDs


immunity severity
lightning current surge acc. to EN 61000-4-5

G O
terminal
device
1

Energy coordination of Yellow/Line


is independent from the conductor length GO
discharge capacity

G O

specific protection of
SPD suitable for coordination decoupling for coordination terminal equipment
with another SPD ( ) with a further SPD ( ) EN 61000-4-5

176 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS LifeCheck® SPD Test

SPD
diagnostics with early
warning function!

• Higher protection and availability of installa-


tions and systems due to integrated LifeCheck
monitoring system
– Integrated three-stage monitoring of all circuit
components
– Quick diagnostics of surge protective devices
Testing an SPD module via RFID technology (LifeCheck) – Easy testing of SPD modules without downtime via
contactless RFID technology
– Even detects previously damaged SPDs
Regular testing of SPDs installed
During operation, an SPD can be overloaded by discharge processes
exceeding the equipment specification. In order to ensure high system
availability, it is therefore essential to test SPDs on a regular basis.
DIN EN 62305-3, supplement 3 (see table excerpt) specifies the maximum
intervals between tests of external and internal lightning protection sys-
tems. Functional principal of the LifeCheck diagnostics systems
Protection Visual Complete Complete inspection Transponder (SPD) Reader (test device)
level inspection inspection of critical systems
I and II 1 year 2 years 1 year energy
SPD
III and IV 2 years 4 years 1 year
identification IC

reader IC micro-
controller
Easy testing with LifeCheck
indication
Maintenance of BLITZDUCTOR XT with integrated LifeCheck is particular- of operating
data
state
ly easy. LifeCheck uses modern RFID (Radio Frequency Identification) tech-
nology for monitoring the protective circuit and for communication.
power communication
Irrespective of downtimes of the system, LifeCheck allows for quick and
easy testing of SPDs by means of the hand-held DRC LC M3+ reader or a Principle of communication of an SPD a test device
stationary DRC MCM XT condition monitoring unit.
The diagnostics system consists of two functional units:
Signal before arrester failure 1. RFID reading and signalling device (reader)
The 3-stage LifeCheck monitoring circuit with early warning function Combined with a visual and electrical display, an electronic system
detects the extreme electrical or thermal load of all protection elements transmits energy without contact to the RFID transponder in the SPD
of an SPD below their destruction limit. This can be read out within sec- via antenna. If the operating state can be read out, an “OK“ message
onds and without contact by means a RFID reader. If the reader displays is displayed.
“OK“, no extreme load was detected. If the contrary is the case, the mod- 2. Monitoring unit within the SPD:
ule has to be replaced as soon as possible in order not to threaten the Diagnostics of the 3-stage LifeCheck monitoring circuit is combined
availability of the protected circuit. with communication of the RFID transponder:
• Diagnostics of electrical overload (impulse current)
Lightning strikes or overvoltage exceeding the specified discharge
capacity of the SPD will damage or even destroy the protection ele-
1 1´ ments. This electrical overload is detected by the LifeCheck monitor-
ing device. When reading out the transponder, the ”Replace SPD!”
2 2´
message appears.
• Diagnostics of thermal overload (overheating)
protected

If LifeCheck monitors a protective Active and passive protection elements which are operated in the
3 3‘
circuit of an SPD, this is shown critical temperature range will be pre-damaged or even destroyed
4 4‘ graphically in the basic circuit dia- depending on the type and duration. This overload is detected by the
gram. For BXT, the complete protec- LifeCheck monitoring device. When reading out the transponder, the
tive circuit is monitored. ”Replace SPD!” message appears.

www.dehn.de 177
INFORMATION TECHNOLOGY SYSTEMS

178 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XTU
PLUGGABLE SPDs FOR DIN RAIL MOUNTING Universal lightning current /
surge arrester
• With actiVsense technology
– Automatically detects the operating voltage of
the wanted signal from 0 to 180 V
– Optimally adjusts the voltage protection level to
the operating voltage currently applied
– Low voltage protection level, also suited for the
protection of terminal equipment
• Eases your processes
– Reduction of the variety of types
– Only one type of SPD for different signal lines
– Easy planning and storage
– Can be easily retrofitted

Example of use of BLITZDUCTOR XTU.

BLITZDUCTOR XTU combined lightning current and surge arresters for the Completely mounted BLITZDUCTOR XTU.
protection of information and automation systems stand out due to their Two-part design with base part and SPD
new, revolutionary technology: The nominal voltage is not specified thus module. Particularly space-saving, for DIN
the arrester can be used for any voltage in the range from 0 to 180 V d.c. rail mounting.
Its innovative technology allows the arrester to automatically detect the
signal voltage of the wanted signal and to adjust its protection perform-
ance to this voltage. Moreover, it continuously adjusts its voltage protec-
tion level to the operating voltage currently applied and is thus ideally
suited for all applications where changing voltages occur.

In case of interference, BLITZDUCTOR XTU arresters always have an


adjusted, minimal residual voltage for every signal voltage thus providing
maximum protection for the devices and systems connected to them.

BLITZDUCTOR XTU arresters also considerably reduce planning efforts


and minimise storage requirements. Even if it is not known at the plan-
ning stage which voltages are used for signal transmission, BLITZDUCTOR
XTU arresters now allow to specify a concrete protective device even at
the planning stage thus facilitating procurement and storage at the exe-
cution stage of the project.
BLITZDUCTOR XTU arresters are also ideally suited to be retrofitted into
existing systems or to replace existing arresters as it is frequently not
entirely clear which types of nominal voltage are to be used. This does not
matter if BLITZDUCTOR XTU arresters are used.

clic
k

The function-optimised design of the arrester allows both to safely plug


the arrester module into the base part and to remove it without problems.
The module is secured in the base part by snapping it in (audible click).
When pressing the grey buttons, the module can be removed with little
effort. This is ensured by the laminated contacts in the base part and the
release spring of the module. A mechanical reverse voltage protection
ensures that the module is installed in the correct position.

www.dehn.de 179
BLITZDUCTOR® XTU INFORMATION TECHNOLOGY SYSTEMS
Universal lightning current / PLUGGABLE SPDs FOR DIN RAIL MOUNTING
surge arrester
• Combined lightning current and surge arrester
– Capable of carrying lightning currents up to 10 kA
(10/350 μs) LifeCheck
RFID Symbol
– Low voltage protection level, also suited for the
protection of terminal equipment
– For use in conformity with the lightning protec-
tion zones concept at the boundaries from 0A – 2
and higher
• SPD consists of a protection module and base
part
– Easy replacement of protection modules
– Make-before-break switch contact in the base
part allows removal and insertion without inter-
ruption
• With integrated LifeCheck monitoring function
– SPDs can be tested without downtime Testing of an SPD module via RFID technology (LifeCheck)

– Even detects previously damaged arresters

BLITZDUCTOR XTU arresters are pluggable, multipole and universal DIN


rail mounted lightning current and surge arresters for the protection of
measuring and control circuits, bus systems and telecommunication sys-
2'4
tems in which high levels of availability are essential. For effective pro- ' 1'3
'
tection of terminal equipment against lightning effects and surges, BLITZ-
DUCTOR XTU arresters combine the permanently high impulse current 24
discharge capacity of a lightning current arrester with the low voltage
protection level of a surge arrester which is optimally adjusted to the 13
operating voltage currently applied.

LifeCheck allows easy and fast testing of SPDs without removing the
module from the system circuit. Integrated into the SPD modules,
LifeCheck permanently monitors the proper condition of the SPD and acts
like an early warning system, detecting imminent electrical or thermal Up to four lines can be connected on two levels. For DIN rail mounting
overload of the protection components. The LifeCheck status can be read purposes, lines of a pair belonging to each other are connected on top of
out within a matter of seconds via contactless RFID technology by means one another.
of the portable DEHNrecord LC reader and shows the date of the last test
of the SPD module.
Stationary installed, a condition monitoring system allows condition-
based maintenance of 10 BXT arresters (for more detailed information, LifeCheck module
please refer to page 359). BXTU ML2 ... S ...
2 2’
The module locking mechanism ensures safe operation, thus the arrester 4 4’
provides protection against vibration effects and shock loads up to a 30-
fold acceleration of gravity. The function-optimised design of the arrester 1 2 3 4 4´ 3´ 2´ 1´

ensures both fast and easy replacement of the arrester module which 1 1’
3
houses all relevant protection elements. 3’
Base part
BXT BAS 9
A wide range of accessories makes the BLITZDUCTOR XTU arrester partic-
ularly user-friendly. Elements for labelling, earthing of unused lines or If the line shield cannot be directly earthed on both sides for technical rea-
easy testing of lines complete the product range. sons, one-sided indirect shield earthing might be advisable. This can be
performed by using arrester modules of type BXTU ML2 ... S. The terminal
3, 3’ is connected to a gas discharge tube which is capable of carrying
lightning currents and prevents compensating currents. Transient impulse
currents on the shield are discharged via indirect shield earthing.

180 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XTU
920 349 BXTU ML4 BD 0-180

PLUGGABLE SPDs FOR DIN RAIL MOUNTING BXTU ML4 BD 0-180

BXTU ML4 BD 0-180


NEW
920 349
1 1‘
i U>UN

2 2‘
i
9 protected
3 3‘
i U>UN

4 4‘
i

Dimension drawing BXTU ML4 BD 0-180 Basic circuit diagram BXTU ML4 BD 0-180 • Universal voltage type with
actiVsense technology
Space-saving combined SPD module with actiVsense and LifeCheck technology for protecting • For installation in compliance with
2 pairs with the same operating voltage or with a different operating voltage of balanced inter- the lightning protection zones con-
faces which are galvanically isolated. Automatically detects the operating voltage of the wanted cept at the boundaries from 0A – 2
signal and optimally adjusts the voltage protection level to it. and higher
• With integrated LifeCheck monitoring
function

BXTU ML4 BD 0-180


SPD class M
SPD monitoring system LifeCheck
Operating voltage UN 0 - 180 V
Frequency of the operating voltage fUN ) 400 Hz
Max. continuous operating d.c. voltage UC 180 V
Max. continuous operating a.c. voltage UC 127 V
Permissible superimposed signal voltage USignal ) +/- 5 V
Cut-off frequency line-line (Usignal, balanced 100 ohms) fG 25 MHz
Nominal current at 80° C IL 100 mA
D1 Total lightning impulse current (10/350 μs) Iimp 10 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA
Voltage protection level line-line for In C2 Up see diagram on page 183, line C2
Voltage protection level line-line at 1 kV/μs C3 Up see diagram on page 183, line C3
Voltage protection level line-line for Iimp D1 Up ) UN + 53 V
Voltage protection level line-PG for C2/C3/D1 ) 550 V
Series impedance per line R ) 10 ohms; typically 7.5 ohms
Capacitance line-line C ) 200 pF
Capacitance line-PG C ) 16 pF
Operating temperature range -40°C...+80°C
Degree of protection (SPD plugged-in) IP 20
Pluggable into BXT BAS base part
Earthing via BXT BAS base part
Enclosure material polyamide PA 6.6
Colour yellow
Test standards EN 61643-21
Approvals, Certifications GOST

Ordering information
Type BXTU ML4 BD 0-180
Part No. 920 349
Packing unit 1 pc(s).

Accessory Part for BLITZDUCTOR® XTU Accessory Part for BLITZDUCTOR® XTU Accessory Part for BLITZDUCTOR® XTU
LifeCheck® Module LifeCheck® Module LifeCheck® Module

DRC LC M3+ DRC MCM XT BXT BAS


910 653 DRC LC 910 695 DRC 920 300 BXT BAS
M3+ MCM XT

Portable device with LifeCheck sensor for DIN rail mountable device with integrated Base part for use as very space-saving,
flexible use. For fast and easy testing of DRC LC M3+
LifeCheck sensor for condition monitoring of DRC MCM XT Condition
four-pole, universal feed-through terminal for BXT BAS BXT-
Ableiterprüfgerät LifeCheck 910 653 Monitoring System LifeCheck 910 695 Basisteil 920 300

LifeCheck-equipped arresters. max. 10 BXT devices with LifeCheck function. insertion of SPD modules without signal inter-
PU Part PU Part ruption.
Type pc(s). No. Type pc(s). No. PU Part
DRC LC M3+ 1 910 653 DRC MCM XT 1 910 695 Type pc(s). No.
BXT BAS 1 920 300

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 183/360/362.

www.dehn.de 181
BLITZDUCTOR® XTU INFORMATION TECHNOLOGY SYSTEMS
920 249 BXTU ML2 BD S 0-180

BXTU ML2 BD S 0-180 PLUGGABLE SPDs FOR DIN RAIL MOUNTING

NEW 1 1‘
BXTU ML2 BD S 0-180
920 249

i U>UN

2 2‘
i
9 protected

3 3‘

4 4‘

• Universal voltage type with Basic circuit diagram BXTU ML2 BD S 0-180 Dimension drawing BXTU ML2 BD S 0-180
actiVsense technology
• For installation in conformity with the Space-saving combined SPD module with actiVsense and LifeCheck technology for protecting
lightning protection zones concept at 1 pair. Direct or indirect shield earthing. Automatically detects the operating voltage of the want-
the boundaries from 0A – 2 and higher ed signal and optimally adjusts the voltage protection level to it.
• With integrated LifeCheck monitoring
function

BXTU ML2 BD S 0-180


SPD class M
SPD monitoring system LifeCheck
Operating voltage UN 0 - 180 V
Frequency of the operating voltage fUN ) 400 Hz
Max. continuous operating d.c. voltage UC 180 V
Max. continuous operating a.c. voltage UC 127 V
Permissible superimposed signal voltage USignal ) +/- 5 V
Cut-off frequency line-line (Usignal, balanced 100 ohms) fG 25 MHz
Nominal current at 80° C IL 100 mA
D1 Total lightning impulse current (10/350 μs) Iimp 9 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA
Voltage protection level line-line for In C2 Up see diagram page on 183, line C2
Voltage protection level line-line at 1 kV/μs C3 Up see diagram page on 183, line C3
Voltage protection level line-line for Iimp D1 Up ) UN + 53 V
Voltage protection level line-PG for C2/C3/D1 ) 550 V
Series impedance per line R ) 10 ohm(s); typically 7.5 ohm(s)
Capacitance line-line C ) 200 pF
Capacitance line-PG C ) 25 pF
Operating temperature range -40°C...+80°C
Degree of protection (SPD plugged-in) IP 20
Pluggable into BXT BAS base part
Earthing via BXT BAS base part
Enclosure material polyamide PA 6.6
Colour yellow
Test standards EN 61643-21
Approvals, Certifications GOST

Ordering information
Type BXTU ML2 BD S 0-180
Part No. 920 249
Packing unit 1 pc(s).

Accessory Part for BLITZDUCTOR® XTU Accessory Part for BLITZDUCTOR® XTU Accessory Part for BLITZDUCTOR® XTU
LifeCheck® Module LifeCheck® Module LifeCheck® Module

BXT BAS DRC MCM XT DRC LC M3+


920 300 BXT BAS 910 695 DRC 910 653 DRC LC
MCM XT M3+

Base part for use as very space-saving, DIN rail mountable device with integrated Portable device with LifeCheck sensor for
BXT BAS BXT-
four-pole, universal feed-through terminal for DRC MCM XT Condition
LifeCheck sensor for condition monitoring of DRC LC M3+
flexible use. For fast and easy testing of
Basisteil 920 300 Monitoring System LifeCheck 910 695 Ableiterprüfgerät LifeCheck 910 653

insertion of SPD modules without signal inter- max. 10 BXT devices with LifeCheck function. LifeCheck-equipped arresters.
ruption. PU Part PU Part
PU Part Type pc(s). No. Type pc(s). No.
Type pc(s). No. DRC MCM XT 1 910 695 DRC LC M3+ 1 910 653
BXT BAS 1 920 300
For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 183/360/362.

182 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XTU
PLUGGABLE SPDs FOR DIN RAIL MOUNTING Diagrams

250 V
U
Up
Operating voltage UN
C2
200 V
C3
UN
USignal

UN 150 V

100 V

t [time]
Up line-line for In (8/20 μs) C2
Operating voltage UN and superimposed signal voltage 50 V
Up line-line for 1 kV/μs C3
USignal
UN
0V 20 V 40 V 60 V 80 V 100 V 120 V 140 V 160 V 180 V
Operating voltage UN

Voltage protection level Up as a function of the operating voltage UN

BLITZDUCTOR® XT Base Part


920 300 BXT BAS

BXT BAS

BXT BAS
920 300
2 2´
4 4´
BXT BAS 1234 4´ 3´ 2´1´
protected
1 1´
3 3´

BXT ML4...

2 2´ protected
4 4´
BXT BAS 1 2 3 4 4´ 3´ 2´ 1´

1 1´
3 3´

Dimension drawing BXT BAS Basic circuit diagram with and without plug-in • Four-pole version for universal use
module with all types of SPD modules
The BLITZDUCTOR XT base part is a very space-saving, four-pole, universal feed-through terminal • Allows to plug in and remove the
for the insertion of SPD modules without signal interruption. The snap-in mechanism at the sup- modules without signal interruption
porting foot of the base part allows the device to be safely earthed via the DIN rail. As no compo-
• Universal design without protection
nents of the protective circuit are situated in the base part, maintenance operation is only required
elements
for the protection modules.

BXT BAS
Operating temperature range -40°C...+80°C
Degree of protection IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection type input / output screw / screw
Cross-sectional area, solid 0.08 - 4 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Tightening torque (terminals) 0.4 Nm
Earthing via 35 mm DIN rail acc. to EN 60715
Enclosure material polyamide PA 6.6
Colour yellow
Ex certifications *) ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
Approvals, Certifications CSA, VdS, UL, GOST

Ordering information
Type BXT BAS
Part No. 920 300
Packing unit 1 pc(s).

*) In combination with certified module

www.dehn.de 183
BLITZDUCTOR® XT INFORMATION TECHNOLOGY SYSTEMS
Lightning current / surge arrester PLUGGABLE SPDs FOR DIN RAIL MOUNTING

• Combined lightning current and surge arrester


– Maximum discharge capacity for two-, three- or
four-pole interfaces
– Lightning current carrying capacity up to 10 kA
(10/350 μs)
– Low voltage protection level, also suited for the
protection of terminal equipment
• SPD consists of a protection module and base
part
– Easy replacement of protection modules with
little effort
– Base part incorporates make-before-break switch
contact for insertion and removal without inter- Example of use of BLITZDUCTOR XT with an earthing module (grey). The
ruption lines can be measured by means of the measuring module (grey strings)
– All protection components integrated in the pro- without disconnecting the clamps.
tection module
• Functional and appealing design
– DIN rail mounting with integrated earthing
– Minimum space requirements, 2 pairs over proper condition of the SPD and acts like an early warning system, detect-
a width of 2/3 modules ing imminent electrical or thermal overload of the protection components.
– Vibration- and shock-proof for safe operation The status of the SPD can be read out within a matter of seconds via con-
tactless RFID technology by means of the portable DEHNrecord LC read-
er. The LifeCheck feature also saves the date of the last test of the SPD
BLITZDUCTOR XT combined arresters are pluggable, multipole, universal module and indicates it. Stationary installed, the condition monitoring
DIN rail mounted lightning current and surge arresters for the protection system permanently monitors the condition of up to 10 BXT devices (for
of measuring and control circuits, bus systems and telecommunication more detailed information, please refer to page 359).
systems. They are particularly suited for installations and systems in which The module locking system ensures safe operation; thus the SPD provides
high levels of availability are essential. For effective protection of termi- protection against vibration effects and shock up to a 30-fold acceleration
nal equipment against the effects of lightning and overvoltages, BLITZ- of gravity. The function-optimised design of the device ensures both quick
DUCTOR XT arresters combine the permanently high impulse current dis- and easy replacement of SPD modules which house all relevant protection
charge capacity of a lightning current arrester with the low protection elements.
level of a surge arrester. A wide range of accessories makes BLITZDUCTOR XT arresters especially
LifeCheck allows quick and easy SPD testing without removing the mod- user-friendly. Elements for easy labelling, earthing of unused lines or easy
ule. Integrated into the SPD modules, LifeCheck permanently monitors the testing of lines complete the product range.

Completely installed BLITZDUCTOR XT. Universal base part accommodates all


Two-part design with universal base part types of SPD modules thereby minimising
and application-specific SPD module. storage requirements and easing prewiring
Especially space-saving design, for DIN and maintenance operations. The modules
rail mounting. can be easily removed from the base part
without signal interruption due to make-
before-break switch contacts.

BXT ML4 B ...:


Dimension drawing of BLITZDUCTOR XT LifeCheck-equipped SPD modules for 4 sin-
base part with plugged-in SPD module. gle lines or 2 pairs for high partial lightning
Width: 2/3 modules (12 mm), for DIN rail currents.
mounting in distribution boards. BXT ML2 B:
LifeCheck-equipped SPD modules for 2 sin-
gle lines or 1 pair for high partial lightning
currents. Type BXT ML2 ... S additionally
provides contacts for direct or indirect
shield earthing.

184 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XT
PLUGGABLE SPDs FOR DIN RAIL MOUNTING Lightning current / surge arrester

General Technical Data for BLITZDUCTOR XT LifeCheck Modules


Degree of protection (plugged-in) IP 20
Pluggable into BLITZDUCTOR XT base part
Earthing by BLITZDUCTOR XT base part
Enclosure material polyamide PA 6.6
Colour yellow

clic
k
Maximum nominal current at ambient temperature

The function-optimised design of the device allows both to safely plug the 2.0
1.9
SPD module into the base part and to remove it without problems. The 1.8
module is secured in the base part by snapping it in (audible click). When 1.7
pressing the grey buttons, the module can be removed with little effort. 1.6
1.5
This is ensured by the laminated spring contacts and the module release

Nominal current IL in A
1.4
spring. A mechanical reverse voltage protection ensures that the module 1.3
1.2
is installed in the correct position. 1.1
1.0
0.9
0.8
0.7
0.6
2'4 0.5
' 1'3
' 0.4
0.3
24 0.2
0.1
0.0
13 – 40 – 20 0 20 40 60 80

Ambient temperature in °C
Colour-coded characteristic curves:
BXT ML4 / ML2 ...

Up to 4 lines can be connected on 2 levels. For DIN rail mounting purpos- BE 5 12 24 36 48 60 180
BD 5 12 24 48 60 180
es, lines of a pair belonging to each other are connected on top of one BC 5 24
another. BE HF 5
BD HF 5 24

LifeCheck module
BXTU ML2 ... S ...
2 2’
4 4’ !
1 2 3 4 4´ 3´ 2´ 1´
1 1’ protected
3
3’
Base part The protected lines always
BXT BAS 9 have to be assigned to termi- ok
If the line shield cannot be earthed on both sides for technical reasons, nals 1´ to 4´ (protected) of the
one-sided indirect shield earthing might be advisable. This can be per- base part. In order not to
formed by using SPD modules of type BXT ML2 ... S. The terminal 3, 3´ is reduce the protective effect,
connected to a gas discharge tube which is capable of carrying lightning protected and unprotected
currents and prevents compensating currents. Transient impulse currents lines have to be installed sep-
on the shield are discharged via indirect shield earthing. arately.

Earthing Module
BXT M4 E
2 2’
4
4’
The terminals integrated into the base
1 2 3 4 4´ 3´ 2´ 1´
1 part can be used with many two-pole
1’
3 modules for shield earthing. Especially for
3’
Base Part
BXT BAS 9 bus systems, the EMC spring terminal
should be used for large-area connection
In case of a stranded cable, unused lines should be laid and earthed. If the of line shields.
unused lines are connected to base parts, earthing modules of type BXT
M4 E should be used. These reserve space for retrofitting the SPD mod-
ules and the lines can be integrated efficiently into the equipotential
bonding. For further types of ”BLITZDUCTOR XT for intrinsically safe circuits" please refer to pages 311-316.

www.dehn.de 185
BLITZDUCTOR® XT Base Part INFORMATION TECHNOLOGY SYSTEMS
920 300 BXT BAS

BXT BAS PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BXT BAS
2 2´ 920 300

4 4´
BXT BAS 1234 4´ 3´ 2´1´
protected
1 1´
3 3´

BXT ML4...

2 2´ protected
4 4´
BXT BAS 1 2 3 4 4´ 3´ 2´ 1´

1 1´
3 3´

• Four-pole version for universal use Basic circuit diagram with and without plug-in Dimension drawing BXT BAS
with all types of SPD modules module

• Allows to plug in and remove the The BLITZDUCTOR XT base part is a very space-saving, four-pole, universal feed-through terminal
modules without signal interruption for the insertion of SPD modules without signal interruption. The snap-in mechanism at the sup-
• Universal design without protection porting foot of the base part allows the device to be safely earthed via the DIN rail. As no compo-
elements nents of the protective circuit are situated in the base part, maintenance operation is only required
for the protection modules.

BXT BAS
Operating temperature range -40°C...+80°C
Degree of protection IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection type input / output screw / screw
Cross-sectional area, solid 0.08 - 4 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Tightening torque (terminals) 0.4 Nm
Earthing via 35 mm DIN rail acc. to EN 60715
Enclosure material polyamide PA 6.6
Colour yellow
Ex certifications *) ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
Approvals, Certifications CSA, VdS, UL, GOST

Ordering information
Type BXT BAS
Part No. 920 300
Packing unit 1 pc(s).

*) in combination with certified module

Clear identification of the Leading/retarded make-before-break


“protected“ side for switch contacts for uninterrupted
faultless installation removal and insertion without downtime

Module release spring The earthing foot ensures cost-


for removing the protection effective installation. No additional
module without problems earth connection is required since the
device is safely earthed via the DIN rail

Lightning current carrying Reverse polarity protection prevents


laminated contacts incorrect insertion of the protection
module

High-quality, four-pole screw terminals


for the following cross-sections:
Designation space stranded: 2.5 mm2
for marking the circuits solid: 4 mm2

186 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XT LifeCheck® Modules
920 310 BXT ML4
B 180

PLUGGABLE SPDs FOR DIN RAIL MOUNTING BXT ML4 B 180

BXT ML4 B 180


920 310
1 1´

2 2´

protected

3 3´

4 4´

Dimension drawing BXT ML4 B If LifeCheck detects thermal and electrical overload, • LifeCheck SPD monitoring function
the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader. • Four-pole lightning equipotential
bonding
• For installation in conformity with the
Space-saving four-pole lightning current arrester module with LifeCheck monitoring function for lightning protection zones concept at
almost all types of applications. For use in connection with downstream surge arresters Q the boundaries from 0A – 1 and higher
or combined lightning current and surge arresters with a lower or equal voltage level.

BXT ML4 B 180


SPD class H
SPD monitoring system LifeCheck
Nominal voltage UN 180 V
Max. continuous operating d.c. voltage UC 180 V
Max. continuous operating a.c. voltage UC 127 V
Nominal current at 45°C IL 1.2 A
D1 Total lightning impulse current (10/350 μs) Iimp 10 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA
Voltage protection level line-line for Iimp D1 Up ) 600 V
Voltage protection level line-PG for Iimp D1 Up ) 550 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 650 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 550 V
Series impedance per line 0.4 ohm(s)
Capacitance line-line C ) 16 pF
Capacitance line-PG C ) 16 pF
Operating temperature range -40°C...+80°C
Test standards IEC 61643-21, UL 497B
SIL classification SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
Ex certifications ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
Approvals, Certifications CSA, VdS, GOST

Ordering information
Type BXT ML4 B 180
Part No. 920 310
Packing unit 1 pc(s).

Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT
LifeCheck® Module LifeCheck® Module LifeCheck® Module

DRC LC M3+ DRC MCM XT BXT BAS


910 653 DRC LC 910 695 DRC 920 300 BXT BAS
M3+ MCM XT

Portable device with LifeCheck sensor for DIN rail mountable device with integrated Base part for use as very space-saving,
flexible use. For fast and easy testing of DRC LC M3+
LifeCheck sensor for condition monitoring of DRC MCM XT Condition
four-pole, universal feed-through terminal for BXT BAS BXT-
Ableiterprüfgerät LifeCheck 910 653 Monitoring System LifeCheck 910 695 Basisteil 920 300

LifeCheck-equipped arresters. max. 10 BXT devices with LifeCheck function. insertion of SPD modules without signal inter-
PU Part PU Part ruption.
Type pc(s). No. Type pc(s). No. PU Part
DRC LC M3+ 1 910 653 DRC MCM XT 1 910 695 Type pc(s). No.
BXT BAS 1 920 300

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

www.dehn.de 187
BLITZDUCTOR® XT LifeCheck® Modules INFORMATION TECHNOLOGY SYSTEMS
920 320 BXT ML4
BE 5

BXT ML4 BE 5 – BE 180 PLUGGABLE SPDs FOR DIN RAIL MOUNTING


920 322 BXT ML4
BE 12
920 324 BXT ML4
BE 24
920 336 BXT ML4
BE 36
920 325 BXT ML4
BE 48
920 326 BXT ML4
BE 60
920 327 BXT ML4
BE 180

BXT ML4 BE 5
920 320
1 1´ BXT ML4 BE 12
920 322
BXT ML4 BE 24
920 324
BXT ML4 BE 36
920 336
BXT ML4 BE 48
920 325
BXT ML4 BE 60
2 2´ 920 326
BXT ML4 BE 180
920 327

protected

3 3‘

4 4‘

• LifeCheck SPD monitoring function If LifeCheck detects thermal and electrical overload, Dimension drawing BXT ML4 BE
the SPD has to be replaced. This status is indicated
• Optimal protection of 4 single lines contactlessly by the DEHNrecord LC reader.
• For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A – 2 and higher Space-saving combined lightning current and surge arrester module with LifeCheck monitoring func-
tion for protecting 4 single lines with common reference potential as well as unbalanced interfaces.

BXT ML4 ... BE 5 BE 12 BE 24 BE 36 BE 48 BE 60 BE 180


SPD class M M M M M M L
SPD monitoring system LifeCheck LifeCheck LifeCheck LifeCheck LifeCheck LifeCheck LifeCheck
Nominal voltage UN 5V 12 V 24 V 36 V 48 V 60 V 180 V
Max. continuous operating d.c. voltage UC 6.0 V 15 V 33 V 45 V 54 V 70 V 180 V
Max. continuous operating a.c. voltage UC 4.2 V 10.6 V 23.3 V 31 V 38.1 V 49.5 V 127 V
Nominal current at 45°C IL 1.0 A 0.75 A 0.75 A 1.8 A 0.75 A 1.0 A 1.0 A
D1 Total lightning impulse current (10/350 μs) Iimp 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA
Voltage protection level line-line for Iimp D1 Up ) 29 V ) 50 V ) 102 V — ) 160 V ) 220 V ) 520 V
Voltage protection level line-PG for Iimp D1 Up ) 27 V ) 37 V ) 66 V ) 85 V ) 95 V ) 125 V ) 300 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 18 V ) 38 V ) 90 V ) 112 V ) 140 V ) 180 V ) 500 V
Voltage protection level line-PG at 1 kV/μs C3 Up )9V ) 19 V ) 45 V ) 56 V ) 70 V ) 90 V ) 250 V
Series impedance per line 1.0 ohm(s) 1.8 ohm(s) 1.8 ohm(s) 0.43 ohm(s) 1.8 ohm(s) 1.0 ohm(s) 1.0 ohm(s)
Cut-off frequency line-PG fG 1.0 MHz 2.7 MHz 6.8 MHz 3.8 MHz 8.7 MHz 9.0 MHz 25.0 MHz
Capacitance line-line C ) 2.7 nF ) 1.0 nF ) 0.5 nF ) 0.8 nF ) 0.35 nF ) 250 pF ) 120 pF
Capacitance line-PG C ) 5.4 nF ) 2.0 nF ) 1.0 nF ) 1.6 nF ) 0.7 nF ) 500 pF ) 240 pF
Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C
Test standards IEC 61643-21, IEC 61643-21, IEC 61643-21, IEC 61643-21 IEC 61643-21, IEC 61643-21, IEC 61643-21,
UL 497B UL 497B UL 497B –– UL 497B UL 497B UL 497B
SIL classification SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
Ex certifications ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
Approvals, Certifications CSA, VdS, CSA, VdS, CSA, VdS, VdS, CSA, VdS, CSA, VdS, CSA, VdS,
UL, GOST UL, GOST UL, GOST GOST UL, GOST UL, GOST UL, GOST

Ordering information
Type BXT ML4 BE 5 BXT ML4 BE 12 BXT ML4 BE 24 BXT ML4 BE 36 BXT ML4 BE 48 BXT ML4 BE 60 BXT ML4 BE 180
Part No. 920 320 920 322 920 324 920 336 920 325 920 326 920 327
Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT
LifeCheck® Module LifeCheck® Module LifeCheck® Module

BXT BAS DRC MCM XT DRC LC M3+


920 300 BXT BAS 910 695 DRC 910 653 DRC LC
MCM XT M3+

Base part for use as very space-saving, DIN rail mountable device with integrated Portable device with LifeCheck sensor for
BXT BAS BXT-
four-pole, universal feed-through terminal for DRC MCM XT Condition
LifeCheck sensor for condition monitoring of DRC LC M3+
flexible use. For fast and easy testing of Life-
Basisteil 920 300 Monitoring System LifeCheck 910 695 Ableiterprüfgerät LifeCheck 910 653

insertion of SPD modules without signal inter- max. 10 BXT devices with LifeCheck function. Check-equipped arresters.
ruption. PU Part PU Part
PU Part Type pc(s). No. Type pc(s). No.
Type pc(s). No. DRC MCM XT 1 910 695 DRC LC M3+ 1 910 653
BXT BAS 1 920 300

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

188 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XT LifeCheck® Modules
920 340 BXT ML4
BD 5

PLUGGABLE SPDs FOR DIN RAIL MOUNTING BXT ML4 BD 5 – BD 180


920 342 BXT ML4
BD 12
920 344 BXT ML4
BD 24
920 345 BXT ML4
BD 48
920 346 BXT ML4
BD 60
920 347 BXT ML4
BD 180

BXT ML4 BD 5
920 340
BXT ML4 BD 12
920 342 1 1´
BXT ML4 BD 24
920 344
BXT ML4 BD 48
920 345
BXT ML4 BD 60
920 346
BXT ML4 BD 180
920 347 2 2´

protected

3 3´

4 4´

Dimension drawing BXT ML4 BD If LifeCheck detects thermal and electrical overload, • LifeCheck SPD monitoring function
the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader. • Optimal protection of 2 single pairs
• For installation in conformity with the
lightning protection zones concept at
Space-saving combined lightning current and surge arrester module with LifeCheck monitoring the boundaries from 0A – 2 and higher
function for protecting 2 pairs of balanced interfaces which are galvanically isolated.

BXT ML4 ... BD 5 BD 12 BD 24 BD 48 BD 60 BD 180


SPD class M M M M M L
SPD monitoring system LifeCheck LifeCheck LifeCheck LifeCheck LifeCheck LifeCheck
Nominal voltage UN 5V 12 V 24 V 48 V 60 V 180 V
Max. continuous operating d.c. voltage UC 6.0 V 15 V 33 V 54 V 70 V 180 V
Max. continuous operating a.c. voltage UC 4.2 V 10.6 V 23.3 V 38.1 V 49.5 V 127 V
Nominal current at 45°C IL 1.0 A 1.0 A 1.0 A 1.0 A 1.0 A 0.75 A
D1 Total lightning impulse current (10/350 μs) Iimp 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA
Voltage protection level line-line for Iimp D1 Up ) 25 V ) 26 V ) 52 V ) 80 V ) 110 V ) 270 V
Voltage protection level line-PG for Iimp D1 Up ) 550 V ) 550 V ) 550 V ) 550 V ) 550 V ) 550 V
Voltage protection level line-line at 1 kV/μs C3 Up )9V ) 19 V ) 45 V ) 70 V ) 90 V ) 250 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 550 V ) 550 V ) 550 V ) 550 V ) 550 V ) 550 V
Series impedance per line 1.0 ohm(s) 1.0 ohm(s) 1.0 ohm(s) 1.0 ohm(s) 1.0 ohm(s) 1.8 ohm(s)
Cut-off frequency line-line fG 1.0 MHz 2.8 MHz 7.8 MHz 8.7 MHz 11.0 MHz 25.0 MHz
Capacitance line-line C ) 5.4 nF ) 2.0 nF ) 1.0 nF ) 0.7 nF ) 500 pF ) 240 pF
Capacitance line-PG C ) 16 pF ) 16 pF ) 16 pF ) 16 pF ) 16 pF ) 16 pF
Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C
Test standards IEC 61643-21, IEC 61643-21, IEC 61643-21, IEC 61643-21, IEC 61643-21, IEC 61643-21,
UL 497B UL 497B UL 497B UL 497B UL 497B UL 497B
SIL classification SIL2 / SIL3
for more details see: www.dehn.de/en/sil
Ex certifications ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
Approvals, Certifications CSA, VdS, CSA, VdS, CSA, VdS, CSA, VdS, CSA, VdS, CSA, VdS,
UL, GOST UL, GOST UL, GOST UL, GOST UL, GOST UL, GOST

Ordering information
Type BXT ML4 BD 5 BXT ML4 BD 12 BXT ML4 BD 24 BXT ML4 BD 48 BXT ML4 BD 60 BXT ML4 BD 180
Part No. 920 340 920 342 920 344 920 345 920 346 920 347
Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT
LifeCheck® Module LifeCheck® Module LifeCheck® Module

Marking system BA1-BA15


920 398
BA15 BXT
BS BA1

Earthing module 920 308 BXT M4 E Test / Disconnection Module 920 309 BXT M4 T

2 x 165 adhesive labels for labelling DRC MCM For direct earthing of lines connected to the Module for testing lines, to be plugged into
XT monitoring devices with their bus addresses. BS BA1 BA15 BXT
BLITZDUCTOR XT base part.
BXT M4 E
Erdungsmodul
BXT-
920 308
the BLITZDUCTOR XT base part. BXT M4 T
/Trennmodul
BXT-Prüf-
920 309

Bezeichnungssystem für BXT 920 398

PU Part PU Part PU Part


Type pc(s). No. Type pc(s). No. Type pc(s). No.
BS BA1 BA15 BXT 1 920 398 BXT M4 E 1 920 308 BXT M4 T 1 920 309

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

www.dehn.de 189
BLITZDUCTOR® XT LifeCheck® Modules INFORMATION TECHNOLOGY SYSTEMS
920 350 BXT ML4
BC 5

BXT ML4 BC 5 / 24 PLUGGABLE SPDs FOR DIN RAIL MOUNTING


920 354 BXT ML4
BC 24

BXT ML4 BC 5
920 350
1 1´ BXT ML4 BC 24
920 354

2 2´

protected

3 3´

4 4´

• LifeCheck SPD monitoring function If LifeCheck detects thermal and electrical overload, Dimension drawing BXT ML4 BC
the SPD has to be replaced. This status is indicated
• Optimal protection of max. 4 lines contactlessly by the DEHNrecord LC reader.
• For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A – 2 and higher Space-saving combined lightning current and surge arrester module with LifeCheck monitoring
function for protecting max. 4 earth-potential-free single lines with common reference potential.

BXT ML4 BC 5 BXT ML4 BC 24


SPD class M M
SPD monitoring system LifeCheck LifeCheck
Nominal voltage UN 5V 24 V
Max. continuous operating d.c. voltage UC 6.0 V 33 V
Max. continuous operating a.c. voltage UC 4.2 V 23.3 V
Nominal current at 45°C IL 1.0 A 0.75 A
D1 Total lightning impulse current (10/350 μs) Iimp 10 kA 10 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA 10 kA
Voltage protection level line-line for Iimp D1 Up ) 25 V ) 55 V
Voltage protection level line-PG for Iimp D1 Up ) 550 V ) 550 V
Voltage protection level line-line at 1 kV/μs C3 Up )9V ) 45 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 550 V ) 550 V
Series impedance per line 1.0 ohm(s) 1.8 ohm(s)
Cut-off frequency line-line fG 1.0 MHz 5.7 MHz
Capacitance line-line C ) 5.4 nF ) 1.0 nF
Capacitance line-PG C ) 16 pF ) 16 pF
Operating temperature range -40°C...+80°C -40°C...+80°C
Test standards IEC 61643-21, UL 497B IEC 61643-21, UL 497B
SIL classification SIL2 / SIL3 SIL2 / SIL3
for more details see: www.dehn.de/en/sil/ for more details see: www.dehn.de/en/sil/
Ex certifications ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4 ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc IECEx KEM 09.0053X: Ex nA II T4 Gc
Approvals, Certifications CSA, VdS, GOST CSA, VdS, GOST

Ordering information
Type BXT ML4 BC 5 BXT ML4 BC 24
Part No. 920 350 920 354
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT
LifeCheck® Module LifeCheck® Module LifeCheck® Module

BXT BAS DRC MCM XT DRC LC M3+


920 300 BXT BAS 910 695 DRC 910 653 DRC LC
MCM XT M3+

Base part for use as very space-saving, DIN rail mountable device with integrated Portable device with LifeCheck sensor for
BXT BAS BXT-
four-pole, universal feed-through terminal for DRC MCM XT Condition
LifeCheck sensor for condition monitoring of DRC LC M3+
flexible use. For fast and easy testing of Life-
Basisteil 920 300 Monitoring System LifeCheck 910 695 Ableiterprüfgerät LifeCheck 910 653

insertion of SPD modules without signal inter- max. 10 BXT devices with LifeCheck function. Check-equipped arresters.
ruption. PU Part PU Part
PU Part Type pc(s). No. Type pc(s). No.
Type pc(s). No. DRC MCM XT 1 910 695 DRC LC M3+ 1 910 653
BXT BAS 1 920 300

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

190 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XT LifeCheck® Modules
920 362 BXT ML4
BE C 12

PLUGGABLE SPDs FOR DIN RAIL MOUNTING BXT ML4 BE C 12 / 24


920 364 BXT ML4
BE C 24

BXT ML4 BE C 12
920 362
BXT ML4 BE C 24
920 364 1 1´

2 2´

protected

3 3´

4 4´

Dimension drawing BXT ML4 BE C If LifeCheck detects thermal and electrical overload, • LifeCheck SPD monitoring function
the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader. • Additional decoupling to the terminal
equipment
• For installation in conformity with the
Space-saving combined lightning current and surge arrester module with LifeCheck monitoring lightning protection zones concept at
function for protecting 2 pairs of balanced interfaces with protective diode circuit at the input, cur- the boundaries from 0A – 2 and higher
rent loops (TTY) and optocoupler inputs.

BXT ML4 BE C 12 BXT ML4 BE C 24


SPD class M M
SPD monitoring system LifeCheck LifeCheck
Nominal voltage UN 12 V 24 V
Max. continuous operating d.c. voltage UC 15 V 33 V
Max. continuous operating a.c. voltage UC 10.6 V 23.3 V
Nominal current at 80°C IL 0.1 A 0.1 A
D1 Total lightning impulse current (10/350 μs) Iimp 10 kA 10 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA 10 kA
Voltage protection level line-line for Iimp D1 Up ) 30 V ) 52 V
Voltage protection level line-PG for Iimp D1 Up ) 35 V ) 66 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 19 V ) 45 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 19 V ) 45 V
Series impedance per line 13.8 ohm(s) 28.8 ohm(s)
Cut-off frequency line-PG fG 1.57 MHz 1.7 MHz
Capacitance line-line C ) 3.2 nF ) 1.5 nF
Capacitance line-PG C ) 3.2 nF ) 1.5 nF
Operating temperature range -40°C ... +80°C -40°C...+80°C
Test standards IEC 61643-21 IEC 61643-21, UL 497B
SIL classification SIL2 / SIL3 SIL2 / SIL3
for more details see: www.dehn.de/en/sil/ for more details see: www.dehn.de/en/sil/
Ex certifications ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4 ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc IECEx KEM 09.0053X: Ex nA II T4 Gc
Approvals, Certifications GOST CSA, VdS, GOST

Ordering information
Type BXT ML4 BE C 12 BXT ML4 BE C 24
Part No. 920 362 NEW 920 364
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT
LifeCheck® Module LifeCheck® Module LifeCheck® Module

Marking system BA1-BA15


920 398
BA15 BXT
BS BA1

Earthing module 920 308 BXT M4 E Test / Disconnection Module 920 309 BXT M4 T

2 x 165 adhesive labels for labelling DRC MCM For direct earthing of lines connected to the Module for testing lines, to be plugged into
XT monitoring devices with their bus addresses. BS BA1 BA15 BXT
BLITZDUCTOR XT base part.
BXT M4 E
Erdungsmodul
BXT-
920 308
the BLITZDUCTOR XT base part. BXT M4 T
/Trennmodul
BXT-Prüf-
920 309

Bezeichnungssystem für BXT 920 398

PU Part PU Part PU Part


Type pc(s). No. Type pc(s). No. Type pc(s). No.
BS BA1 BA15 BXT 1 920 398 BXT M4 E 1 920 308 BXT M4 T 1 920 309

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

www.dehn.de 191
BLITZDUCTOR® XT LifeCheck® Modules INFORMATION TECHNOLOGY SYSTEMS
920 370 BXT ML4
BE HF 5

BXT ML4 BE HF 5 PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BXT ML4 BE HF 5
920 370
1 1´

2 2´

protected

3 3´

4 4´

• LifeCheck SPD monitoring function If LifeCheck detects thermal and electrical overload, Dimension drawing BXT ML4 BE HF
the SPD has to be replaced. This status is indicated
• Optimal protection of 4 single lines contactlessly by the DEHNrecord LC reader.
• For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A – 2 and higher Space-saving combined lightning current and surge arrester module with LifeCheck monitoring
function for protecting 4 single lines with common reference potential as well as high-frequency
transmissions without electrical isolation.

BXT ML4 BE HF 5
SPD class M
SPD monitoring system LifeCheck
Nominal voltage UN 5V
Max. continuous operating d.c. voltage UC 6.0 V
Max. continuous operating a.c. voltage UC 4.2 V
Nominal current at 45°C IL 1.0 A
D1 Total lightning impulse current (10/350 μs) Iimp 10 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA
Voltage protection level line-line for Iimp D1 Up ) 26 V
Voltage protection level line-PG for Iimp D1 Up ) 40 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 11 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 11 V
Series impedance per line 1.0 ohm(s)
Cut-off frequency line-PG fG 100.0 MHz
Capacitance line-line C ) 20 pF
Capacitance line-PG C ) 25 pF
Operating temperature range -40°C...+80°C
Test standards IEC 61643-21, UL 497B
SIL classification SIL2
for more details see: www.dehn.de/en/sil/
Ex certifications ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
Approvals, Certifications CSA, VdS, UL, GOST

Ordering information
Type BXT ML4 BE HF 5
Part No. 920 370
Packing unit 1 pc(s).

Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT
LifeCheck® Module LifeCheck® Module LifeCheck® Module

BXT BAS DRC MCM XT DRC LC M3+


920 300 BXT BAS 910 695 DRC 910 653 DRC LC
MCM XT M3+

Base part for use as very space-saving, DIN rail mountable device with integrated Portable device with LifeCheck sensor for
BXT BAS BXT-
four-pole, universal feed-through terminal for DRC MCM XT Condition
LifeCheck sensor for condition monitoring of DRC LC M3+
flexible use. For fast and easy testing of Life-
Basisteil 920 300 Monitoring System LifeCheck 910 695 Ableiterprüfgerät LifeCheck 910 653

insertion of SPD modules without signal inter- max. 10 BXT devices with LifeCheck function. Check-equipped arresters.
ruption. PU Part PU Part
PU Part Type pc(s). No. Type pc(s). No.
Type pc(s). No. DRC MCM XT 1 910 695 DRC LC M3+ 1 910 653
BXT BAS 1 920 300

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

192 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XT LifeCheck® Modules
920 371 BXT ML4
BD HF 5

PLUGGABLE SPDs FOR DIN RAIL MOUNTING BXT ML4 BD HF 5 / 24


920 375 BXT ML4
BD HF 24

BXT ML4 BD HF 5
920 371
BXT ML4 BD HF 24
920 375
1 1´

2 2´

protected

3 3´

4 4´

Dimension drawing BXT ML4 BD HF If LifeCheck detects thermal and electrical overload, • LifeCheck SPD monitoring function
the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader. • Minimum signal disturbance
• For installation in conformity with the
lightning protection zones concept at
Space-saving combined lightning current and surge arrester module with LifeCheck monitoring the boundaries from 0A – 2 and higher
function for protecting 2 pairs in high-frequency bus systems or video transmission systems.

BXT ML4 BD HF 5 BXT ML4 BD HF 24


SPD class M M
SPD monitoring system LifeCheck LifeCheck
Nominal voltage UN 5V 24 V
Max. continuous operating d.c. voltage UC 6.0 V 33 V
Max. continuous operating a.c. voltage UC 4.2 V 23.3 V
Nominal current at 45°C IL 1.0 A 1.0 A
D1 Total lightning impulse current (10/350 μs) Iimp 10 kA 10 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA 10 kA
Voltage protection level line-line for Iimp D1 Up ) 25 V ) 65 V
Voltage protection level line-PG for Iimp D1 Up ) 550 V ) 550 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 11 V ) 47 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 550 V ) 550 V
Series impedance per line 1.0 ohm(s) 1.0 ohm(s)
Cut-off frequency line-line fG 100.0 MHz 100.0 MHz
Capacitance line-line C ) 25 pF ) 25 pF
Capacitance line-PG C ) 16 pF ) 16 pF
Operating temperature range -40°C...+80°C -40°C...+80°C
Test standards IEC 61643-21, UL 497B IEC 61643-21, UL 497B
SIL classification SIL2 SIL2
for more details see: www.dehn.de/en/sil/ for more details see: www.dehn.de/en/sil/
Ex certifications ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4 c ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc IECEx KEM 09.0053X: Ex nA II T4 Gc
Approvals, Certifications CSA, VdS, UL, GOST CSA, VdS, UL, GOST

Ordering information
Type BXT ML4 BD HF 5 BXT ML4 BD HF 24
Part No. 920 371 920 375
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT
LifeCheck® Module LifeCheck® Module LifeCheck® Module

Marking system BA1-BA15


920 398
BA15 BXT
BS BA1

Earthing module 920 308 BXT M4 E Test / Disconnection Module 920 309 BXT M4 T

2 x 165 adhesive labels for labelling DRC MCM For direct earthing of lines connected to the Module for testing lines, to be plugged into
XT monitoring devices with their bus addresses. BS BA1 BA15 BXT
BLITZDUCTOR XT base part.
BXT M4 E
Erdungsmodul
BXT-
920 308
the BLITZDUCTOR XT base part. BXT M4 T
/Trennmodul
BXT-Prüf-
920 309

Bezeichnungssystem für BXT 920 398

PU Part PU Part PU Part


Type pc(s). No. Type pc(s). No. Type pc(s). No.
BS BA1 BA15 BXT 1 920 398 BXT M4 E 1 920 308 BXT M4 T 1 920 309

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

www.dehn.de 193
BLITZDUCTOR® XT LifeCheck® Modules INFORMATION TECHNOLOGY SYSTEMS
920 389 BXT ML4 MY 250

BXT ML4 MY 250 PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BXT ML4 MY 250


920 389
1 1´

2 2´

protected

3 3´

4 4´

• LifeCheck SPD monitoring function If LifeCheck detects thermal and electrical overload, Dimension drawing BXT ML4 MY
the SPD has to be replaced. This status is indicated
• Distinctive “Y” circuit contactlessly by the DEHNrecord LC reader.
• For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B – 2 and higher Space-saving surge arrester module with LifeCheck monitoring function for protecting 4 lines of
stranded signal interfaces up to 250 V a.c.

BXT ML4 MY 250


SPD class V
SPD monitoring system LifeCheck
Nominal voltage UN 250 V
Max. continuous operating d.c. voltage UC line - PG 320 V
Max. continuous operating a.c. voltage UC line - PG 250 V
Nominal current at 45°C IL 3.0 A
C2 Total nominal discharge current (8/20 μs) In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 2.5 kA
Voltage protection level line-line for In C2 Up ) 1700 V
Voltage protection level line-PG for In C2 Up ) 1300 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 1100 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 1200 V
Cut-off frequency line-line fG 20 MHz
Capacitance line-line C ) 300 pF
Capacitance line-PG C ) 16 pF
Operating temperature range -40°C...+80°C
Test standards IEC 61643-21
SIL classification SIL2
for more details see: www.dehn.de/en/sil/
Approvals, Certifications GOST

Ordering information
Type BXT ML4 MY 250
Part No. 920 389
Packing unit 1 pc(s).

Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT
LifeCheck® Module LifeCheck® Module LifeCheck® Module

BXT BAS DRC MCM XT DRC LC M3+


920 300 BXT BAS 910 695 DRC 910 653 DRC LC
MCM XT M3+

Base part for use as very space-saving, DIN rail mountable device with integrated Portable device with LifeCheck sensor for
BXT BAS BXT-
four-pole, universal feed-through terminal for DRC MCM XT Condition
LifeCheck sensor for condition monitoring of DRC LC M3+
flexible use. For fast and easy testing of Life-
Basisteil 920 300 Monitoring System LifeCheck 910 695 Ableiterprüfgerät LifeCheck 910 653

insertion of SPD modules without signal inter- max. 10 BXT devices with LifeCheck function. Check-equipped arresters.
ruption. PU Part PU Part
PU Part Type pc(s). No. Type pc(s). No.
Type pc(s). No. DRC MCM XT 1 910 695 DRC LC M3+ 1 910 653
BXT BAS 1 920 300

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

194 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XT LifeCheck® Modules
920 211 BXT ML2 B 180

PLUGGABLE SPDs FOR DIN RAIL MOUNTING BXT ML2 B 180

BXT ML2 B 180


NEW
920 211

Dimension drawing BXT ML2 B If LifeCheck detects thermal and electrical overload, • LifeCheck SPD monitoring function
the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader. • Two-pole lightning equipotential
bonding with 4 terminals for shield
and/or functional earthing
Space-saving two-pole lightning current arrester module with LifeCheck monitoring function and • For installation in conformity with the
shield earthing for almost all applications. For use in connection with downstream surge arresters lightning protection zones concept at
Q or combined lightning current and surge arresters with a lower or equal voltage level. the boundaries from 0A – 1 and higher

BXT ML2 B 180


SPD class H
SPD monitoring system LifeCheck
Nominal voltage UN 180 V
Max. continuous operating d.c. voltage UC 180 V
Max. continuous operating a.c. voltage UC 127 V
Nominal current at 45°C IL 1.2 A
D1 Total lightning impulse current (10/350 μs) Iimp 10 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA
Voltage protection level line-line for Iimp D1 Up ) 600 V
Voltage protection level line-PG for Iimp D1 Up ) 550 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 650 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 550 V
Series impedance per line 0.4 ohm(s)
Capacitance line-line C ) 16 pF
Capacitance line-PG C ) 16 pF
Operating temperature range -40°C...+80°C
Test standards IEC 61643-21
SIL classification SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
Approvals, Certifications CSA, GOST

Ordering information
Type BXT ML2 B 180
Part No. 920 211
Packing unit 1 pc(s).

Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT
LifeCheck® Module LifeCheck® Module LifeCheck® Module

Marking system BA1-BA15


920 398
BA15 BXT
BS BA1

Earthing module 920 308 BXT M4 E Test / Disconnection Module 920 309 BXT M4 T

2 x 165 adhesive labels for labelling DRC MCM For direct earthing of lines connected to the Module for testing lines, to be plugged into
XT monitoring devices with their bus addresses. BS BA1 BA15 BXT
BLITZDUCTOR XT base part.
BXT M4 E
Erdungsmodul
BXT-
920 308
the BLITZDUCTOR XT base part. BXT M4 T
/Trennmodul
BXT-Prüf-
920 309

Bezeichnungssystem für BXT 920 398

PU Part PU Part PU Part


Type pc(s). No. Type pc(s). No. Type pc(s). No.
BS BA1 BA15 BXT 1 920 398 BXT M4 E 1 920 308 BXT M4 T 1 920 309

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

www.dehn.de 195
BLITZDUCTOR® XT LifeCheck® Modules INFORMATION TECHNOLOGY SYSTEMS
920 247 BXT ML2
BD 180

BXT ML2 BD 180 PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BXT ML2 BD 180


920 247
1

protected

• LifeCheck SPD monitoring function If LifeCheck detects thermal and electrical overload, Dimension drawing BXT ML2 BD
the SPD has to be replaced. This status is indicated
• Optimal protection of 1 pair contactlessly by the DEHNrecord LC reader.
• For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A – 2 and higher Space-saving combined lightning current and surge arrester module with LifeCheck monitoring
function for protecting 1 pair of balanced interfaces which are galvanically isolated.

BXT ML2 BD 180


SPD class L
SPD monitoring system LifeCheck
Nominal voltage UN 180 V
Max. continuous operating d.c. voltage UC 180 V
Max. continuous operating a.c. voltage UC 127 V
Nominal current at 45°C IL 0.75 A
D1 Total lightning impulse current (10/350 μs) Iimp 5 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA
Voltage protection level line-line for Iimp D1 Up ) 270 V
Voltage protection level line-PG for Iimp D1 Up ) 550 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 250 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 550 V
Series impedance per line 1.8 ohm(s)
Cut-off frequency line-line fG 25.0 MHz
Capacitance line-line C ) 240 pF
Capacitance line-PG C ) 16 pF
Operating temperature range -40°C...+80°C
Test standards IEC 61643-21
SIL classification SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
Approvals, Certifications CSA, GOST

Ordering information
Type BXT ML2 BD 180
Part No. 920 247
Packing unit 1 pc(s).

Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT
LifeCheck® Module LifeCheck® Module LifeCheck® Module

BXT BAS DRC MCM XT DRC LC M3+


920 300 BXT BAS 910 695 DRC 910 653 DRC LC
MCM XT M3+

Base part for use as very space-saving, DIN rail mountable device with integrated Portable device with LifeCheck sensor for
BXT BAS BXT-
four-pole, universal feed-through terminal for DRC MCM XT Condition
LifeCheck sensor for condition monitoring of DRC LC M3+
flexible use. For fast and easy testing of Life-
Basisteil 920 300 Monitoring System LifeCheck 910 695 Ableiterprüfgerät LifeCheck 910 653

insertion of SPD modules without signal inter- max. 10 BXT devices with LifeCheck function. Check-equipped arresters.
ruption. PU Part PU Part
PU Part Type pc(s). No. Type pc(s). No.
Type pc(s). No. DRC MCM XT 1 910 695 DRC LC M3+ 1 910 653
BXT BAS 1 920 300

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

196 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XT LifeCheck® Modules
920 240 BXT ML2
BD S 5

PLUGGABLE SPDs FOR DIN RAIL MOUNTING BXT ML2 BD S 5 – BD S 48


920 242 BXT ML2
BD S 12
920 244 BXT ML2
BD S 24
920 245 BXT ML2
BD S 48

BXT ML2 BD S 5
920 240
BXT ML2 BD S 12
920 242
1 1´
BXT ML2 BD S 24
920 244
BXT ML2 BD S 48
920 245

2 2´

protected

3 3´

4 4´

Dimension drawing BXT ML2 BD If LifeCheck detects thermal and electrical overload, • LifeCheck SPD monitoring function
the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader. • Optimal protection of 1 pair and
shield
• For installation in conformity with the
Space-saving combined lightning current and surge arrester module with LifeCheck monitoring lightning protection zones concept at
function for protecting 1 pair of balanced interfaces which are galvanically isolated, available with the boundaries from 0A – 2 and higher
direct or indirect shield earthing.

BXT ML2 BD S 5 BXT ML2 BD S 12 BXT ML2 BD S 24 BXT ML2 BD S 48


SPD class M M M M
SPD monitoring system LifeCheck LifeCheck LifeCheck LifeCheck
Nominal voltage UN 5V 12 V 24 V 48 V
Max. continuous operating d.c. voltage UC 6.0 V 15 V 33 V 54 V
Max. continuous operating a.c. voltage UC 4.2 V 10.6 V 23.3 V 38.1 V
Nominal current at 45°C IL 1.0 A 1.0 A 1.0 A 1.0 A
D1 Total lightning impulse current (10/350 μs) Iimp 9 kA 9 kA 9 kA 9 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA 2.5 kA 2.5 kA 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA 20 kA 20 kA 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA 10 kA 10 kA 10 kA
Voltage protection level line-line for Iimp D1 Up ) 25 V ) 26 V ) 52 V ) 80 V
Voltage protection level line-PG for Iimp D1 Up ) 550 V ) 550 V ) 550 V ) 550 V
Voltage protection level line-line at 1 kV/μs C3 Up )9V ) 19 V ) 45 V ) 70 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 550 V ) 550 V ) 550 V ) 550 V
Series impedance per line 1.0 ohm(s) 1.0 ohm(s) 1.0 ohm(s) 1.0 ohm(s)
Cut-off frequency line-line fG 1.0 MHz 2.8 MHz 7.8 MHz 8.7 MHz
Capacitance line-line C ) 5.4 nF ) 2.0 nF ) 1.0 nF ) 0.7 nF
Capacitance line-PG C ) 25 pF ) 25 pF ) 25 pF ) 25 pF
Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C
Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21
SIL classification SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
Approvals, Certifications CSA, GOST CSA, GOST CSA, GOST CSA, GOST

Ordering information
Type BXT ML2 BD S 5 BXT ML2 BD S 12 BXT ML2 BD S 24 BXT ML2 BD S 48
Part No. 920 240 920 242 920 244 920 245
Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT
LifeCheck® Module LifeCheck® Module LifeCheck® Module

Marking system BA1-BA15


920 398
BA15 BXT
BS BA1

Earthing module 920 308 BXT M4 E Test / Disconnection Module 920 309 BXT M4 T

2 x 165 adhesive labels for labelling DRC MCM For direct earthing of lines connected to the Module for testing lines, to be plugged into
XT monitoring devices with their bus addresses. BS BA1 BA15 BXT
BLITZDUCTOR XT base part.
BXT M4 E
Erdungsmodul
BXT-
920 308
the BLITZDUCTOR XT base part. BXT M4 T
/Trennmodul
BXT-Prüf-
920 309

Bezeichnungssystem für BXT 920 398

PU Part PU Part PU Part


Type pc(s). No. Type pc(s). No. Type pc(s). No.
BS BA1 BA15 BXT 1 920 398 BXT M4 E 1 920 308 BXT M4 T 1 920 309

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

www.dehn.de 197
BLITZDUCTOR® XT LifeCheck® Modules INFORMATION TECHNOLOGY SYSTEMS
920 243 BXT ML2 BD DL S 15

BXT ML2 BD DL S 15 PLUGGABLE SPDs FOR DIN RAIL MOUNTING

NEW BXT ML2 BD DL S 15


920 243
1 1´

2 2´

protected

3 3´

4 4´

• Suitable for Dupline buses If LifeCheck detects thermal and electrical overload, Dimension drawing BXT ML2 BD
the SPD has to be replaced. This status is indicated
• LifeCheck SPD monitoring function contactlessly by the DEHNrecord LC reader.
• Effective protection for 1 pair and
shield
• For installation in conformity with the Space-saving LifeCheck-equipped combined SPD module for protecting 1 pair of balanced and gal-
lightning protection zones concept at vanically isolated interfaces, which specifically fulfils the requirements of Dupline buses, direct or
the boundaries from 0A – 2 and higher indirect shield earthing.

BXT ML2 BD DL S 15
SPD class M
SPD monitoring system LifeCheck
Nominal voltage UN 15 V
Max. continuous operating d.c. voltage UC 17 V
Max. continuous operating a.c. voltage UC 12 V
Nominal current at 70° C IL 0.4 A
D1 Total lightning impulse current (10/350 μs) Iimp 9 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA
Voltage protection level line-line for Iimp D1 Up ) 30 V
Voltage protection level line-PG for Iimp D1 Up ) 550 V
Voltage protection level line-line for In C2 Up ) 35 V
Voltage protection level line-PG for In C2 Up ) 600 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 24 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 550 V
Series impedance per line 2.2 ohm(s)
Cut-off frequency line-line fG 2.7 MHz
Capacitance line-line C ) 1.9 nF
Capacitance line-PG C ) 25 pF
Operating temperature range -40°C...+80°C
Test standards IEC 61643-21
SIL classification SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
Approvals, Certifications GOST

Ordering information
Type BXT ML2 BD DL S 15
Part No. 920 243
Packing unit 1 pc(s).

Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT
LifeCheck® Module LifeCheck® Module LifeCheck® Module

BXT BAS DRC MCM XT DRC LC M3+


920 300 BXT BAS 910 695 DRC 910 653 DRC LC
MCM XT M3+

Base part for use as very space-saving, DIN rail mountable device with integrated Portable device with LifeCheck sensor for
BXT BAS BXT-
four-pole, universal feed-through terminal for DRC MCM XT Condition
LifeCheck sensor for condition monitoring of DRC LC M3+
flexible use. For fast and easy testing of Life-
Basisteil 920 300 Monitoring System LifeCheck 910 695 Ableiterprüfgerät LifeCheck 910 653

insertion of SPD modules without signal inter- max. 10 BXT devices with LifeCheck function. Check-equipped arresters.
ruption. PU Part PU Part
PU Part Type pc(s). No. Type pc(s). No.
Type pc(s). No. DRC MCM XT 1 910 695 DRC LC M3+ 1 910 653
BXT BAS 1 920 300

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

198 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XT LifeCheck® Modules
920 220 BXT ML2
BE S 5

PLUGGABLE SPDs FOR DIN RAIL MOUNTING BXT ML2 BE S 5 – BE S 48


920 222 BXT ML2
BE S 12
920 224 BXT ML2
BE S 24
920 225 BXT ML2
BE S 48

BXT ML2 BE S 5
920 220
BXT ML2 BE S 12
920 222 1 1´
BXT ML2 BE S 24
920 224
BXT ML2 BE S 48
920 225

2 2´

protected

3 3´

4 4´

Dimension drawing BXT ML2 BE If LifeCheck detects thermal and electrical overload, • LifeCheck SPD monitoring function
the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader. • Optimal protection of 2 single lines
and shield
• For installation in conformity with the
Space-saving combined lightning current and surge arrester module with LifeCheck monitoring lightning protection zones concept at
function for protecting 2 single lines with common reference potential as well as unbalanced inter- the boundaries from 0A – 2 and higher
faces, available with direct or indirect shield earthing.

BXT ML2 BE S 5 BXT ML2 BE S 12 BXT ML2 BE S 24 BXT ML2 BE S 48


SPD class M M M M
SPD monitoring system LifeCheck LifeCheck LifeCheck LifeCheck
Nominal voltage UN 5V 12 V 24 V 48 V
Max. continuous operating d.c. voltage UC 6.0 V 15 V 33 V 54 V
Max. continuous operating a.c. voltage UC 4.2 V 10.6 V 23.3 V 38.1 V
Nominal current for 45°C IL 1.0 A 0.75 A 0.75 A 0.75 A
D1 Total lightning impulse current (10/350 μs) Iimp 9 kA 9 kA 9 kA 9 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA 2.5 kA 2.5 kA 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA 20 kA 20 kA 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA 10 kA 10 kA 10 kA
Voltage protection level line-line for Iimp D1 Up ) 29 V ) 50 V ) 102 V ) 160 V
Voltage protection level line-PG for Iimp D1 Up ) 27 V ) 37 V ) 66 V ) 95 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 18 V ) 38 V ) 90 V ) 140 V
Voltage protection level line-PG at 1 kV/μs C3 Up )9V ) 19 V ) 45 V ) 70 V
Series impedance per line 1.0 ohm(s) 1.8 ohm(s) 1.8 ohm(s) 1.8 ohm(s)
Cut-off frequency line-PG fG 1.0 MHz 2.7 MHz 6.8 MHz 8.7 MHz
Capacitance line-line C ) 2.7 nF ) 1.0 nF ) 0.5 nF ) 0.35 nF
Capacitance line-PG C ) 5.4 nF ) 2.0 nF ) 1.0 nF ) 0.7 nF
Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C
Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21
SIL classification SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
Approvals, Certifications CSA, GOST CSA, GOST CSA, GOST CSA, UL, GOST

Ordering information
Type BXT ML2 BE S 5 BXT ML2 BE S 12 BXT ML2 BE S 24 BXT ML2 BE S 48
Part No. 920 220 920 222 920 224 920 225
Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT
LifeCheck® Module LifeCheck® Module LifeCheck® Module

Marking system BA1-BA15


920 398
BA15 BXT
BS BA1

Earthing module 920 308 BXT M4 E Test / Disconnection Module 920 309 BXT M4 T

2 x 165 adhesive labels for labelling DRC MCM For direct earthing of lines connected to the Module for testing lines, to be plugged into
XT monitoring devices with their bus addresses. BS BA1 BA15 BXT
BLITZDUCTOR XT base part.
BXT M4 E
Erdungsmodul
BXT-
920 308
the BLITZDUCTOR XT base part. BXT M4 T
/Trennmodul
BXT-Prüf-
920 309

Bezeichnungssystem für BXT 920 398

PU Part PU Part PU Part


Type pc(s). No. Type pc(s). No. Type pc(s). No.
BS BA1 BA15 BXT 1 920 398 BXT M4 E 1 920 308 BXT M4 T 1 920 309

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

www.dehn.de 199
BLITZDUCTOR® XT LifeCheck® Modules INFORMATION TECHNOLOGY SYSTEMS
920 270 BXT ML2
BE HFS 5

BXT ML2 BE HFS 5 PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BXT ML2 BE HFS 5


920 270
1 1´

2 2´

protected

3 3´

4 4´

• LifeCheck SPD monitoring function If LifeCheck detects thermal and electrical overload, Dimension drawing BXT ML2 BE HFS
the SPD has to be replaced. This status is indicated
• Optimal protection of 1 pair and contactlessly by the DEHNrecord LC reader.
shield
• For installation in conformity with the
lightning protection zones concept at Space-saving combined lightning current and surge arrester module with LifeCheck monitoring
the boundaries from 0A – 2 and higher function for protecting 1 pair in high-frequency transmissions without electrical isolation; available
with direct or indirect shield earthing.

BXT ML2 BE HFS 5


SPD class M
SPD monitoring system LifeCheck
Nominal voltage UN 5V
Max. continuous operating d.c. voltage UC 6.0 V
Max. continuous operating a.c. voltage UC 4.2 V
Nominal current at 45°C IL 1.0 A
D1 Total lightning impulse current (10/350 μs) Iimp 9 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA
Voltage protection level line-line for Iimp D1 Up ) 26 V
Voltage protection level line-PG for Iimp D1 Up ) 40 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 11 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 11 V
Series impedance per line 1.0 ohm(s)
Cut-off frequency line-PG fG 100 MHz
Capacitance line-line C ) 20 pF
Capacitance line-PG C ) 30 pF
Operating temperature range -40°C...+80°C
Test standards IEC 61643-21
SIL classification SIL2
for more details see: www.dehn.de/en/sil/
Approvals, Certifications CSA, UL, GOST

Ordering information
Type BXT ML2 BE HFS 5
Part No. 920 270
Packing unit 1 pc(s).

Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT
LifeCheck® Module LifeCheck® Module LifeCheck® Module

BXT BAS DRC MCM XT DRC LC M3+


920 300 BXT BAS 910 695 DRC 910 653 DRC LC
MCM XT M3+

Base part for use as very space-saving, DIN rail mountable device with integrated Portable device with LifeCheck sensor for
BXT BAS BXT-
four-pole, universal feed-through terminal for DRC MCM XT Condition
LifeCheck sensor for condition monitoring of DRC LC M3+
flexible use. For fast and easy testing of Life-
Basisteil 920 300 Monitoring System LifeCheck 910 695 Ableiterprüfgerät LifeCheck 910 653

insertion of SPD modules without signal inter- max. 10 BXT devices with LifeCheck function. Check-equipped arresters.
ruption. PU Part PU Part
PU Part Type pc(s). No. Type pc(s). No.
Type pc(s). No. DRC MCM XT 1 910 695 DRC LC M3+ 1 910 653
BXT BAS 1 920 300

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

200 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XT LifeCheck® Modules
920 271 BXT ML2
BD HFS 5

PLUGGABLE SPDs FOR DIN RAIL MOUNTING BXT ML2 BD HFS 5

BXT ML2 BD HFS 5


920 271
1 1´

2 2´

protected

3 3´

4 4´

Dimension drawing BXT ML2 BD HFS If LifeCheck detects thermal and electrical overload, • LifeCheck SPD monitoring function
the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader. • Minimum signal interference
• For installation in conformity with the
lightning protection zones concept at
Space-saving combined lightning current and surge arrester module with LifeCheck monitoring the boundaries from 0A – 2 and higher
function for protecting 1 pair in high-frequency bus systems or video transmission systems, avail-
able with direct or indirect shield earthing.

BXT ML2 BD HFS 5


SPD class M
SPD monitoring system LifeCheck
Nominal voltage UN 5V
Max. continuous operating d.c. voltage UC 6.0 V
Max. continuous operating a.c. voltage UC 4.2 V
Nominal current at 45°C IL 1.0 A
D1 Total lightning impulse current (10/350 μs) Iimp 9 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA
Voltage protection level line-line for Iimp D1 Up ) 25 V
Voltage protection level line-PG for Iimp D1 Up ) 550 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 11 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 550 V
Series impedance per line 1.0 ohm(s)
Cut-off frequency line-line fG 100 MHz
Capacitance line-line C ) 25 pF
Capacitance line-PG C ) 25 pF
Operating temperature range -40°C...+80°C
Test standards IEC 61643-21
SIL classification SIL2
for more details see: www.dehn.de/en/sil/
Approvals, Certifications CSA, UL, GOST

Ordering information
Type BXT ML2 BD HFS 5
Part No. 920 271
Packing unit 1 pc(s).

Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT Accessory Part for BLITZDUCTOR® XT
LifeCheck® Module LifeCheck® Module LifeCheck® Module

Marking system BA1-BA15


920 398
BA15 BXT
BS BA1

Earthing module 920 308 BXT M4 E Test / Disconnection Module 920 309 BXT M4 T

2 x 165 adhesive labels for labelling DRC MCM For direct earthing of lines connected to the Module for testing lines, to be plugged into
XT monitoring devices with their bus addresses. BS BA1 BA15 BXT
BLITZDUCTOR XT base part.
BXT M4 E
Erdungsmodul
BXT-
920 308
the BLITZDUCTOR XT base part. BXT M4 T
/Trennmodul
BXT-Prüf-
920 309

Bezeichnungssystem für BXT 920 398

PU Part PU Part PU Part


Type pc(s). No. Type pc(s). No. Type pc(s). No.
BS BA1 BA15 BXT 1 920 398 BXT M4 E 1 920 308 BXT M4 T 1 920 309

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

www.dehn.de 201
Accessories for BLITZDUCTOR® XT INFORMATION TECHNOLOGY SYSTEMS
920 308 BXT M4 E

Earthing module PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BXT M4 E
920 308
1 1´

2 2´

protected

3 3´

4 4´

• For plugging onto BLITZDUCTOR XT Basic circuit diagram BXT M4 E Dimension drawing BXT M4 E
base parts
• Easy handling The plugged-in earthing module short-circuits all lines connected to the BLITZDUCTOR XT base part
• Quick replacement when retrofitting to PG. It directly earths initially used cable cores, which are already connected to the base part.
an SPD module

BXT M4 E
D1 Total lightning impulse current (10/350 μs) Iimp 10 kA
Operating temperature range -40°C...+80°C
Degree of protection (plugged-in) IP 20
For plugging into base part
Enclosure material polyamide PA 6.6
Colour grey

Ordering information
Type BXT M4 E
Part No. 920 308
Packing unit 1 pc(s).

920 395 SAK BXT


LR

EMC spring terminals

SAK BXT LR
920 395

• Lightning current carrying capability Dimension drawing SAK BXT LR


• Flat conductor with low impedance
Two spring terminals for permanent low-impedance shield contact with the protected and unpro-
• Flexible spring terminal
tected side of a BXT device. With integrated terminal coding for direct or indirect shield earthing,
cable ties and insulating strips included.

SAK BXT LR
D1 Lightning impulse current (10/350 μs) 5 kA
For plugging into clamp connection BXT BAS
Clamping range 3 - 10 mm
Colour bare
Accessories cable tie, insulating strips

Ordering information
Type SAK BXT LR
Part No. 920 395
Packing unit 1 pc(s).

202 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Accessories for BLITZDUCTOR® XT
920 309 BXT M4 T

PLUGGABLE SPDs FOR DIN RAIL MOUNTING Test / Disconnection Module

BXT M4 T
920 309

1 1´

2 2´

3 3´

4 4´

Dimension drawing BXT M4 T Basic circuit diagram BXT M4 T • For plugging into the BLITZDUCTOR XT
base parts
The plugged-in test/disconnection module interrupts the cable run of the lines connected to the BLITZ- • Easy maintenance and troubleshooting
DUCTOR XT base part and leads them to a test socket at the front side of the module. This allows to
• Measuring lines included
carry out measurements in the installation without removing the lines from the base part.

BXT M4 T
Max. continuous operating d.c. voltage UC 180 V
Max. continuous operating a.c. voltage UC 127 V
Nominal current at 80° C IL 1.0 A
Volume resistance 0.1 ohm
Operating temperature range -40°C ... +80°C
Degree of protection (plugged-in) IP 20
For plugging into base part
Test sockets gold-plated, 1 mm
Enclosure material polyamide PA 6.6
Colour grey
Accessories 2 measuring lines (1 m), protective bag

Ordering information
Type BXT M4 T
Part No. 920 309
Packing unit 1 pc(s).

www.dehn.de 203
Accessories for BLITZDUCTOR® XT INFORMATION TECHNOLOGY SYSTEMS
920 398 BS BA1 BA15 BXT

Marking system BA1-BA15 PLUGGABLE SPDs FOR DIN RAIL MOUNTING

NEW BS BA1 BA15 BXT


920 398

• For DRC MCM XT condition monitor-


ing system
• Abrasion-proof 2 x 165 adhesive labels for labelling DRC MCM XT monitoring devices with their bus addresses (BA1
to BA15) and with consecutive numbers of the assigned BXT base parts or modules (1.1-1.10 to
• Pre-printed
15.1-15.10)
• Transparent

BS BA1 BA15 BXT


Dimension W x H 13 x 7 mm

Ordering information
Type BS BA1 BA15 BXT
Part No. 920 398
Packing unit 1 pc(s).

Marking system 1-50 920 399 BS 1 50 BXT

BS 1 50 BXT
920 399

• Abrasion-proof
• Pre-printed Plate with 2 plate numbers from 1 to 50 for attaching to BXT base parts or modules.

BS 1 50 BXT
Dimension W x H 11 x 4 mm

Ordering information
Type BS 1 50 BXT
Part No. 920 399
Packing unit 1 pc(s).

204 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XT
PLUGGABLE SPDs FOR DIN RAIL MOUNTING ATEX Certificate

www.dehn.de 205
BLITZDUCTOR® XT INFORMATION TECHNOLOGY SYSTEMS
IECEx Certificate PLUGGABLE SPDs FOR DIN RAIL MOUNTING

206 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XT
PLUGGABLE SPDs FOR DIN RAIL MOUNTING Information on SIL

The term safety integration level (SIL) is defined in the international the risk. The aim of functional safety is to minimise the risk of failure of
IEC 61508 and IEC61511 standards and is used in the field of functional the individual sub-systems so that the risk for the entire system or instal-
safety. It is intended for assessing the reliability and safety of electrical, lation is reduced to an acceptable level. The values in the table below can
electronic or programmable electronic systems. "Functional safety" be used for calculating the functional safety of systems with the surge
describes the safety level of a system or installation, which depends on protective devices used.
the correct operation of sub-systems and external installations to reduce

λSD λSU λDD λDU Total SFF *3 SIL AC *4


Surge Protection Device Failure rates according to IEC 61508 in FIT Safe Failure Fraction SIL

*1 *2 *1 *2 *1 *2 *1 *2

BXT ML2(4) B 180 0 21 0 1 3 2 24 86.8% 92.7% SIL2 SIL3

BXT ML4(2) BD *, BXT ML2 BD S * 0 21 0 4 6 2 27 78.2% 92.8% SIL2 SIL3

BXT ML4 BD HF *, BXT ML2 BD HFS * 0 29 0 4 14 10 43 67.7% 76.8% SIL2 SIL2

BXT ML2 BD DL S 15 0 21 0 4 6 2 27 78.2% 92.8% SIL2 SIL3

BXT ML4 BE *, BXT ML2 BE S * 0 21 0 7 9 2 30 71.4% 93.0% SIL2 SIL3

BXT ML4 BE HF *, BXT ML2 BE HFS * 0 33 0 8 18 10 51 64.9% 80.4% SIL2 SIL2

BXT ML4 BE C * 0 23 0 9 12 3 35 65.4% 91.3% SIL2 SIL3

BXT ML4 BC EX 24 0 39 0 8 11 3 50 78.8% 93.7% SIL2 SIL3

BXT ML4 BD EX 24 0 57 0 6 10 4 67 85.3% 94.1% SIL2 SIL3

BXT ML2 BD HF EX 6 0 28 0 1 16 15 44 64.0% 67.2% SIL2 SIL2

BXT ML4 BC * 0 21 0 7 9 2 30 71.4% 93.0% SIL2 SIL3

BXT ML4 MY 250 0 20 0 0.5 10 9.5 30 66.6% 67.9% SIL2 SIL2

* All voltages available


*1 Analysis 1 represents a worst-case analysis
*2 Analysis 2 represents an analysis with the assumption that line short circuits and short circuits to GND are detectable or do not have an effect.
*3 The complete sensor or final element subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only.
*4 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not
imply all related IEC 61508 requirements are fulfilled. See also previous footnote.

www.dehn.de 207
INFORMATION TECHNOLOGY SYSTEMS
PLUGGABLE SPDs FOR DIN RAIL MOUNTING

208 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNconnect RK
COMPACT SPDs FOR DIN RAIL MOUNTING Terminal block with integrated
surge protection

• Minimum installation width of only 6 mm


• Quick installation with jumper bar
(accessory part)
• Spring-loaded connection system

6 mm two-pole terminal block with integrated surge protection and cage


clamp terminal. Earthing via DIN rail or clamp.

DEHNconnect RK is a 6 mm terminal block with integrated surge protec- to be safely earthed via the DIN rail. For reduced wiring, jumper bars can
tion and has five spring-loaded cage clamp terminals allowing two lines be plugged into the protected side of the SPD to transmit signals. As the
to be protected and equipotential bonding to the terminal equipment to enclosure of the SPDs is open on one side to minimise the width, a cov-
be established. The snap-in fixing at the supporting foot allows the device ering plate should be used at the end of every SPD block.

DEHNconnect RK is available in two per- A wide range of accessories such as


formance classes: jumper bars, marking plates or covering
DCO RK M: plates make DCO RK a system easy to
Surge arrester with energy-coordinated operate, which has been specifically
protection stages designed for use in industrial environ-
DCO RK E (D): ments.
Surge arrester with diodes only, for
improving the electromagnetic compati-
bility (EMC) of terminal equipment
DCO RK DCO RK Accessories

In order to minimise the width, the enclo-


sure is open to one side. For protection
OUT 3
against electrical shock, the SPD can be 3
IP 20
closed with a covering plate (accessories).
If several devices are arranged next to
each other, one covering plate could be
sufficient.

KB 10 DCO RK
DCO RK with covering plate

ok marking plates

Use of jumper bars

Operating state controls of switch contacts in industrial environments are


often fed by a common power source. If several DCO RK units are used,
wiring can be reduced by bridging the feeding signal on the protected side
(accessories).

www.dehn.de 209
DEHNconnect RK INFORMATION TECHNOLOGY SYSTEMS
919 920 DCO RK
ME 12

DCO RK ME COMPACT SPDs FOR DIN RAIL MOUNTING


919 921 DCO RK
ME 24
919 922 DCO RK
ME 48
919 923 DCO RK
ME 110

DCO RK ME 12
DEHNconnect RK 12 V 919 920
DCO RK ME 24
DEHNconnect RK 24 V 919 921
DCO RK ME 48

1 3 DEHNconnect RK 48 V
DCO RK ME 110
DEHNconnect RK 110 V
919 922

919 923

2 4

IN OUT

• Standard protection with modular ter- Energy-coordinated gas discharge tubes and Dimension drawing DCO RK ME
minal blocks diodes to earth

• Low series impedance


• For installation in conformity with the 2-stage SPD for protecting 2 single lines with common reference potential as well as unbalanced
lightning protection zones concept at interfaces.
the boundaries from 0B – 2 and higher

DCO RK ME 12 DCO RK ME 24 DCO RK ME 48 DCO RK ME 110


SPD class Q Q Q R
Nominal voltage UN 12 V 24 V 48 V 110 V
Max. continuous operating d.c. voltage Uc 14 V 33 V 55 V 170 V
Max. continuous operating a.c. voltage Uc 9.5 V 23 V 38.5 V 120 V
Nominal current IL 0.5 A 0.5 A 0.5 A 0.5 A
C2 Total nominal discharge current (8/20 μs) In 10 kA 10 kA 10 kA 10 kA
C2 Nominal discharge current (8/20 μs) per line In 5 kA 5 kA 5 kA 5 kA
Voltage protection level line-line for In C2 Up ) 55 V ) 110 V ) 175 V ) 500 V
Voltage protection level line-PG for In C2 Up ) 40 V ) 65 V ) 100 V ) 270 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 36 V ) 90 V ) 160 V ) 460 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 19 V ) 45 V ) 80 V ) 230 V
Series impedance per line 1.8 ohms 1.8 ohms 1.8 ohms 1.8 ohms
Cut-off frequency line-PG fG 2.5 MHz 6 MHz 10 MHz 16 MHz
Capacitance line-line C ) 1.2 nF ) 0.5 nF ) 0.3 nF ) 0.2 nF
Capacitance line-PG C ) 2.4 nF ) 1 nF ) 0.6 nF ) 0.4 nF
Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C
Degree of protection IP 00, with cover IP 20 IP 00, with cover IP 20 IP 00, with cover IP 20 IP 00, with cover IP 20
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60175
Connection input/output spring / spring spring / spring spring / spring spring / spring
Cross-sectional area, solid 0.08 - 2.5 mm2 0.08 - 2.5 mm2 0.08 - 2.5 mm2 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2 0.08 - 2.5 mm2 0.08 - 2.5 mm2 0.08 - 2.5 mm2
Earthing via DIN rail / terminal DIN rail / terminal DIN rail / terminal DIN rail / terminal
Enclosure material polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6
Colour yellow yellow yellow yellow
Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21
Approvals, Certifications GOST GOST GOST GOST

Ordering information
Type DCO RK ME 12 DCO RK ME 24 DCO RK ME 48 DCO RK ME 110
Part No. 919 920 919 921 919 922 919 923
Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNconnect RK Accessory Part for DEHNconnect RK


919 977 BS 1 50
DCO RK

919 979
RK GE
AD DCO Covering plate Quick marking system, horizontal imprint
AD DCO RK GE Covering
For DCO RK BS 1 50 DCO RK Quick
Plate with 2 plate numbers from 1 to 50 for DCO RK, horizontal imprint
Plate for DCO, yellow 919 979 Marking System for DCO RK 919 977

PU Part PU Part
Type Enclosure material Colour pc(s). No. Type Material pc(s). No.
AD DCO RK GE polyamide PA 6.6 yellow 1 919 979 BS 1 50 DCO RK plastic 1 919 977

210 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNconnect RK
919 940 DCO RK
MD 12

COMPACT SPDs FOR DIN RAIL MOUNTING DCO RK MD 12 / MD 24


919 941 DCO RK
MD 24

DCO RK MD 12
DEHNconnect RK 12 V 919 940
DCO RK MD 24
DEHNconnect RK 24 V 919 941

1 3

2 4

IN OUT

Dimension drawing DCO RK MD 12 / MD 24 Protective circuit, no leakage currents to earth, • Standard protection with modular ter-
energy-coordinated minal blocks
• Low series impedance
2-stage SPD for protecting a floating pair as well as balanced interfaces. • For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B – 2 and higher

DCO RK MD 12 DCO RK MD 24
SPD class Q Q
Nominal voltage UN 12 V 24 V
Max. continuous operating d.c. voltage Uc 14 V 33 V
Max. continuous operating a.c. voltage Uc 9.5 V 23 V
Nominal current IL 0.5 A 0.5 A
C2 Total nominal discharge current (8/20 μs) In 10 kA 10 kA
C2 Nominal discharge current (8/20 μs) per line In 5 kA 5 kA
Voltage protection level line-line for In C2 Up ) 25 V ) 50 V
Voltage protection level line-PG for In C2 Up ) 750 V ) 750 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 19 V ) 45 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 650 V ) 650 V
Series impedance per line 1.8 ohms 1.8 ohms
Cut-off frequency line-line fG 2.5 MHz 6 MHz
Capacitance line-line C ) 2.4 nF ) 1 nF
Capacitance line-PG C ) 5 pF ) 5 pF
Operating temperature range -40°C...+80°C -40°C...+80°C
Degree of protection IP 00, with cover IP 20 IP 00, with cover IP 20
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Connection input/output spring / spring spring / spring
Cross-sectional area, solid 0.08 - 2.5 mm2 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2 0.08 - 2.5 mm2
Earthing via DIN rail / terminal DIN rail / terminal
Enclosure material polyamide PA 6.6 polyamide PA 6.6
Colour yellow yellow
Test standards IEC 61643-21 IEC 61643-21
Approvals, Certifications GOST GOST

Ordering information
Type DCO RK MD 12 DCO RK MD 24
Part No. 919 940 919 941
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNconnect RK Accessory Part for DEHNconnect RK


Quick marking system, vertical imprint 919 976
DCO RK
BS 1 50 S

NEW Covering plate 919 979


RK GE
AD DCO

Plate with 2 plate numbers from 1 to 50 for DCO RK, vertical imprint For DCO RK AD DCO RK GE Covering
Plate for DCO, yellow 919 979

PU Part BS 1 50 S DCO RK
919 976 PU Part
Type Material pc(s). No. Type Enclosure material Colour pc(s). No.
BS 1 50 S DCO RK plastic 1 919 976 AD DCO RK GE polyamide PA 6.6 yellow 1 919 979

www.dehn.de 211
DEHNconnect RK INFORMATION TECHNOLOGY SYSTEMS
919 942 DCO RK
MD 48

DCO RK MD 48 COMPACT SPDs FOR DIN RAIL MOUNTING

DCO RK MD 48
DEHNconnect RK 48 V 919 942

1 3

2 4

IN OUT

• Standard protection with modular ter- Protective circuit, no leakage currents to earth, Dimension DCO RK MD 48
minal blocks energy-coordinated

• Extremely low series impedance


• For installation in conformity with the 2-stage SPD for protecting a floating pair as well as balanced interfaces up to 1.7 A.
lightning protection zones concept at
the boundaries from 0B – 2 and higher

DCO RK MD 48
SPD class Q
Nominal voltage UN 48 V
Max. continuous operating d.c. voltage Uc 55 V
Max. continuous operating a.c. voltage Uc 38.5 V
Nominal current IL 1.7 A
C2 Total nominal discharge current (8/20 μs) In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 5 kA
Voltage protection level line-line for In C2 Up ) 100 V
Voltage protection level line-PG for In C2 Up ) 750 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 70 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 650 V
Series impedance per line 0.4 ohms
Cut-off frequency line-line fG 10 MHz
Capacitance line-line C ) 0.6 nF
Capacitance line-PG C ) 10 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 00, with cover IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output spring / spring
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Earthing via DIN rail / terminal
Enclosure material polyamide PA 6.6
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type DCO RK MD 48
Part No. 919 942
Packing unit 1 pc(s).

Accessory Part for DEHNconnect RK Accessory Part for DEHNconnect RK


919 977 BS 1 50
DCO RK

919 979
RK GE
AD DCO Covering plate Quick marking system, horizontal imprint
AD DCO RK GE Covering
For DCO RK BS 1 50 DCO RK Quick
Plate with 2 plate numbers from 1 to 50 for DCO RK, horizontal imprint
Plate for DCO, yellow 919 979 Marking System for DCO RK 919 977

PU Part PU Part
Type Enclosure material Colour pc(s). No. Type Material pc(s). No.
AD DCO RK GE polyamide PA 6.6 yellow 1 919 979 BS 1 50 DCO RK plastic 1 919 977

212 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNconnect RK
919 943 DCO RK
MD 110

COMPACT SPDs FOR DIN RAIL MOUNTING DCO RK MD 110

DCO RK MD 110
DEHNconnect RK 110 V 919 943

1 3

2 4

IN OUT

Dimension drawing DCO RK MD 110 Protection circuit, free of leakage currents to • Standard protection with modular ter-
earth, energy-coordinated minal blocks
• Low series impedance
2-stage SPD for protecting a floating pair, telecommunications. • For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B – 2 and higher

DCO RK MD 110
SPD class R
Nominal voltage UN 110 V
Max. continuous operating d.c. voltage Uc 170 V
Max. continuous operating a.c. voltage Uc 120 V
Nominal current IL 0.5 A
C2 Total nominal discharge current (8/20 μs) In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 5 kA
Voltage protection level line-line for In C2 Up ) 260 V
Voltage protection level line-PG for In C2 Up ) 750 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 230 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 650 V
Series impedance per line 1.8 ohms
Cut-off frequency line-line fG 16 MHz
Capacitance line-line C ) 0.4 nF
Capacitance line-PG C ) 5 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 00, with cover IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output spring / spring
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Earthing via DIN rail / terminal
Enclosure material polyamide PA 6.6
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type DCO RK MD 110
Part No. 919 943
Packing unit 1 pc(s).

Accessory Part for DEHNconnect RK Accessory Part for DEHNconnect RK


Quick marking system, vertical imprint 919 976
DCO RK
BS 1 50 S

NEW Covering plate 919 979


RK GE
AD DCO

Plate with 2 plate numbers from 1 to 50 for DCO RK, vertical imprint For DCO RK AD DCO RK GE Covering
Plate for DCO, yellow 919 979

PU Part BS 1 50 S DCO RK
919 976 PU Part
Type Material pc(s). No. Type Enclosure material Colour pc(s). No.
BS 1 50 S DCO RK plastic 1 919 976 AD DCO RK GE polyamide PA 6.6 yellow 1 919 979

www.dehn.de 213
DEHNconnect RK INFORMATION TECHNOLOGY SYSTEMS
919 970 DCO RK
MD HF 5

DCO RK MD HF COMPACT SPDs FOR DIN RAIL MOUNTING

DCO RK MD HF 5
DEHNconnect RK MD HF, 5 V 919 970

1 3

2 4

IN OUT

• Low self-capacitance The capacitance of the protective circuit can be Dimension drawing DCO RK MD HF
minimised by combining several diodes to one
• Very good transmission performance matrix.
• For installation in conformity with the
lightning protection zones concept at 2-stage SPD for protecting balanced or unbalanced interfaces with extra-low voltages. Can also be
the boundaries from 0B – 2 and higher used for high transmission rates. For shielded bus lines, SAK shield connection systems should be used.

DCO RK MD HF 5
SPD class Q
Nominal voltage UN 5V
Max. continuous operating d.c. voltage Uc 6.0 V
Max. continuous operating a.c. voltage Uc 4.2 V
Nominal current IL 0.1 A
C2 Total nominal discharge current (8/20 μs) In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 5 kA
Voltage protection level line-line for In C2 Up ) 27 V
Voltage protection level line-PG for In C2 Up ) 50 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 14 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 14 V
Series impedance per line 1.0 ohm
Cut-off frequency line-line fG 250 MHz
Cut-off frequency line-PG fG 180 MHz
Capacitance line-line C ) 19 pF
Capacitance line-PG C ) 16 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 00 with cover IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output spring / spring
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Earthing via DIN rail / terminal
Enclosure material thermoplastic PA 6.6
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type DCO RK MD HF 5
Part No. 919 970
Packing unit 1 pc(s).

Accessory Part for DEHNconnect RK Accessory Part for DEHNconnect RK


919 977 BS 1 50
DCO RK

919 979
RK GE
AD DCO Covering plate Quick marking system, horizontal imprint
AD DCO RK GE Covering
For DCO RK BS 1 50 DCO RK Quick
Plate with 2 plate numbers from 1 to 50 for DCO RK, horizontal imprint
Plate for DCO, yellow 919 979 Marking System for DCO RK 919 977

PU Part PU Part
Type Enclosure material Colour pc(s). No. Type Material pc(s). No.
AD DCO RK GE polyamide PA 6.6 yellow 1 919 979 BS 1 50 DCO RK plastic 1 919 977

214 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNconnect RK
919 987 DCO RK E
12

COMPACT SPDs FOR DIN RAIL MOUNTING DCO RK E


919 988 DCO RK E
24
919 989 DCO RK E
48
919 990 DCO RK E
60

DCO RK E 12
DEHNconnect RK 12 V 919 987
DCO RK E 24
DEHNconnect RK 24 V 919 988
DCO RK E 48
DEHNconnect RK 48 V
DCO RK E 60
DEHNconnect RK 60 V
919 989

919 990
1 3

2 4

IN OUT

Dimension drawing DCO RK E Powerful diodes limit surges to earth. • Protection with modular terminal
blocks
• High nominal current
Fine limiting surge protective device for 2 single lines with common reference potential as well as • For installation in conformity with the
unbalanced interfaces. lightning protection zones concept at
the boundaries from 1 – 2 and higher

DCO RK E 12 DCO RK E 24 DCO RK E 48 DCO RK E 60


SPD class W W [ [
Nominal voltage UN 12 V 24 V 48 V 60 V
Max. continuous operating d.c. voltage Uc 13 V 28 V 58 V 70 V
Max. continuous operating a.c. voltage Uc 9V 19.5 V 41 V 49.5 V
Nominal current IL 10 A 10 A 10 A 10 A
C1 Total nominal discharge current (8/20 μs) In 0.8 kA 0.6 kA 0.3 kA 0.24 kA
C1 Nominal discharge current (8/20 μs) per line In 0.4 kA 0.3 kA 0,15 kA 0.12 kA
Voltage protection level line-line for In C1 Up ) 50 V ) 96 V ) 180 V ) 220 V
Voltage protection level line-PG for In C1 Up ) 25 V ) 48 V ) 90 V ) 110 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 36 V ) 76 V ) 156 V ) 190 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 18 V ) 38 V ) 78 V ) 95 V
Cut-off frequency line-PG fG 2.5 MHz 5.5 MHz 11 MHz 14 MHz
Capacitance line-line C ) 1.2 nF ) 0.6 nF ) 0.3 nF ) 0.25 nF
Capacitance line-PG C ) 2.5 nF ) 1.2 nF ) 0.6 nF ) 0.5 nF
Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C
Degree of protection IP 00, with cover IP 20 IP 00, with cover IP 20 IP 00, with cover IP 20 IP 00, with cover IP 20
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Connection input/output spring / spring spring / spring spring / spring spring / spring
Cross-sectional area, solid 0.08 - 2.5 mm2 0.08 - 2.5 mm2 0.08 - 2.5 mm2 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2 0.08 - 2.5 mm2 0.08 - 2.5 mm2 0.08 - 2.5 mm2
Earthing via DIN rail / terminal DIN rail / terminal DIN rail / terminal DIN rail / terminal
Enclosure material polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6
Colour yellow yellow yellow yellow
Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21
Approvals, Certifications GOST GOST GOST GOST

Ordering information
Type DCO RK E 12 DCO RK E 24 DCO RK E 48 DCO RK E 60
Part No. 919 987 919 988 919 989 919 990
Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNconnect RK Accessory Part for DEHNconnect RK


Quick marking system, vertical imprint 919 976
DCO RK
BS 1 50 S

NEW Covering plate 919 979


RK GE
AD DCO

Plate with 2 plate numbers from 1 to 50 for DCO RK, vertical imprint For DCO RK AD DCO RK GE Covering
Plate for DCO, yellow 919 979

PU Part BS 1 50 S DCO RK
919 976 PU Part
Type Material pc(s). No. Type Enclosure material Colour pc(s). No.
BS 1 50 S DCO RK plastic 1 919 976 AD DCO RK GE polyamide PA 6.6 yellow 1 919 979

www.dehn.de 215
DEHNconnect RK INFORMATION TECHNOLOGY SYSTEMS
919 986 DCO RK D
5 24

DCO RK D COMPACT SPDs FOR DIN RAIL MOUNTING

DCO RK D 5 24
DEHNconnect RK 5/24 V 919 986

1 3

IN OUT

2 4

• EMC protection with modular termi- Powerful diodes limit surges between the signal Dimension drawing DCO RK D
nal blocks lines.

• High nominal current


• For installation in conformity with the Surge protective device for SIEMENS-SPS S7-300 output digital modules (laboratory tested). The
lightning protection zones concept at terminal allows for increased EMC protection. No connection to PG.
the boundaries from 1 – 2 and higher

DCO RK D 5 24
SPD class [
Nominal voltage UN +24 V / -5 V
Max. continuous operating d.c. voltage Uc +30 V / -6 V
Nominal current IL 10 A
C1 Total nominal discharge current (8/20 μs) In 0.3 kA
C1 Nominal discharge current (8/20 μs) per line In 0.3 kA
Voltage protection level line-line for In C1 Up ) 70 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 45 V
Cut-off frequency line-line fG 3.5 MHz
Capacitance line-line C ) 2 nF
Operating temperature range -40°C...+80°C
Degree of protection IP 00, with cover IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output spring / spring
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Enclosure material polyamide PA 6.6
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type DCO RK D 5 24
Part No. 919 986
Packing unit 1 pc(s).

Accessory Part for DEHNconnect RK


919 979
RK GE
AD DCO Covering plate
AD DCO RK GE Covering
For DCO RK
Plate for DCO, yellow 919 979

PU Part
Type Enclosure material Colour pc(s). No.
AD DCO RK GE polyamide PA 6.6 yellow 1 919 979

216 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Accessories for DEHNconnect RK
COMPACT SPDs FOR DIN RAIL MOUNTING

Covering plate
919 979 AD DCO
RK GE

AD DCO RK GE
AD DCO RK GE Covering

Enclosure material polyamide PA 6.6


Plate for DCO, yellow 919 979

Colour yellow

Ordering information
Type AD DCO RK GE
Part No. 919 979
Packing unit 1 pc(s).
• Easy to open

Jumper bar
919 880 KB 10
DCO RK

Multipole unit for DCO RK

KB 10 DCO RK Jumper
Bar for DEHNconnect RK 919 880

KB 10 DCO RK
Poles 10

Ordering information • Reduced wiring


Type KB 10 DCO RK
• Use at protected outputs of DCO RK
Part No. 919 880 only
Packing unit 1 pc(s).

Quick marking system, horizontal imprint


919 977 BS 1 50
DCO RK

Plate with 2 plate numbers from 1 to 50 for DCO RK, horizontal imprint

BS 1 50 DCO RK Quick
Marking System for DCO RK 919 977

BS 1 50 DCO RK
Material plastic

Ordering information
Type BS 1 50 DCO RK
Part No. 919 977
Packing unit 1 pc(s). • Pre-printed marking for DCO RK

Quick marking system, vertical imprint


919 976 BS 1 50 S DCO RK

Plate with 2 plate numbers from 1 to 50 for DCO RK, vertical imprint NEW

BS 1 50 S DCO RK
919 976
BS 1 50 S DCO RK
Material plastic

Ordering information
Type BS 1 50 S DCO RK
Part No. 919 976
Packing unit 1 pc(s). • Pre-printed marking for DCO RK

www.dehn.de 217
BLITZDUCTOR® VT INFORMATION TECHNOLOGY SYSTEMS
Lightning current / Surge arrester COMPACT SPDs FOR DIN RAIL MOUNTING

• Cost-effective protection of multi-core signal


lines
• Interface-specific types, e.g. TTY, RS 485
• Types for d.c. power supply systems

Compact protection with screw terminals for multi-core lines for DIN rail
mounting.

BLITZDUCTOR VT is a family of compact DIN rail mounted SPDs and con- nal lines or special applications. The equipment is earthed via a screw ter-
sists of different types of enclosures. Most of the SPDs protect 4-wire sig- minal.

The enclosure concept of BLITZDUCTOR VT


is variable. Depending on the application,
SPDs are distinguished between
– width: 1.5 modules,
4 protected signal lines
– width: 1.5 modules,
2 protected lines for d.c. power supply
BVT enclosure family
systems
– width: 3 modules,
6 protected lines for RS 485/422

Connection
Connection to the ground has to be performed
with a terminal instead of the snap-on DIN rail.
Direct equipotential bonding can be established
to the terminal device with the second terminal
compartment of this double terminal.

218 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® VT
918 400 BVT TTY
24

COMPACT SPDs FOR DIN RAIL MOUNTING BVT TTY

BVT TTY 24 BLITZ-


DUCTOR VT TTY 918 400
1 1

2 2

3 3

IN OUT

4 4

Dimension drawing BVT TTY The resistors at the circuit output protect the • Simultaneous protection of two TTY
optocoupler and protective diodes in the terminal loops
equipment against overloads.
• Additional decoupling to the terminal
Owing to the additional decoupling resistors at the output, only diodes in the terminal equipment, device
which can withstand loads only to a certain extent, are integrated into the energy coordination of • For installation in conformity with the
the protective stages. This is especially important for optocoupler interfaces. lightning protection zones concept at
the boundaries from 0B – 2 and higher

BVT TTY 24
SPD class Q
Nominal d.c. voltage UN 24 V
Max. continuous operating d.c. voltage UC 26.8 V
Max. continuous operating a.c. voltage UC 18.9 V
Nominal current IL 0.1 A
C2 Total nominal discharge current (8/20 μs) In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA
Voltage protection line-line for In C2 Up ) 65 V
Voltage protection level line-PG for In C2 Up ) 700 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 36 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 600 V
Series impedance per line 17.2 ohms per pair
Cut-off frequency line-line fG 8 MHz
Capacitance line-line C ) 1 nF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output screw / screw
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Tightening torque (terminals) 0.5 Nm
Earthing via screw terminal
Enclosure material thermoplastic, UL 94 V-0
Colour yellow
Test standards IEC 61643-21, UL 497B
Approvals, Certifications CSA, GOST

Ordering information
Type BVT TTY 24
Part No. 918 400
Packing unit 1 pc(s).

www.dehn.de 219
BLITZDUCTOR® VT INFORMATION TECHNOLOGY SYSTEMS
918 407 BVT MTTY
24

BVT MTTY COMPACT SPDs FOR DIN RAIL MOUNTING

BVT MTTY 24

4 4 918 407

3 3

2 2

IN OUT

1 1

• Cost-effective compact protection Protection circuit with simple decoupling, no leak- Dimension drawing BVT MTTY
age currents to earth, energy-coordinated.
• For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B – 2 and higher Surge arrester for two floating pairs. Unbalanced use of the decoupling impedance.

BVT MTTY 24
SPD class Q
Nominal d.c. voltage UN 24 V
Max. continuous operating d.c. voltage UC 26.8 V
Max. continuous operating a.c. voltage UC 18.9 V
Nominal current IL 0.1 A
C2 Total nominal discharge current (8/20 μs) In 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA
Voltage protection line-line for In C2 Up ) 65 V
Voltage protection level line-PG for In C2 Up ) 700 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 36 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 600 V
Series impedance per line 2.2 ohms per pair
Cut-off frequency line-line fG 10 MHz
Capacitance line-line C ) 1 nF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output screw / screw
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Tightening torque (terminals) 0.5 Nm
Earthing via screw terminal
Enclosure material thermoplastic, UL 94 V-0
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type BVT MTTY 24
Part No. 918 407
Packing unit 1 pc(s).

220 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® VT
918 401 BVT
RS485 5

COMPACT SPDs FOR DIN RAIL MOUNTING BVT RS485


8 8
BVT RS485 5 BLITZ-
DUCTOR VT RS485 918 401

7 7

4 4
3 3
IN OUT
6 6

5 5

1 1
2 2

Dimension drawing BVT RS485 Circuiting diodes to a common reference point • Terminals for 4 bus lines and SG
allows for a low protection level between the
signal lines. • Direct or indirect shield earthing
• For installation in conformity with the
Surge arrester for a wide range of applications, e.g. for balanced 4-wire RS 485/422 interfaces or lightning protection zones concept at
temperature sensors. Allows for either direct or indirect shield earthing and connection of a signal the boundaries from 0B – 2 and higher
ground (SG).

BVT RS485 5
SPD class Q
Nominal d.c. voltage UN 5V
Max. continuous operating d.c. voltage UC 6V
Max. continuous operating a.c. voltage UC 4.2 V
Nominal current IL 0.5 A
C2 Total nominal discharge current (8/20 μs) In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA
Voltage protection line-line for In C2 Up ) 20 V
Voltage protection level line-PG for In C2 Up ) 700 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 8.5 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 600 V
Series impedance per line 1.8 ohms
Cut-off frequency line-line fG 1.7 MHz
Capacitance line-line C ) 5 nF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output screw / screw
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Tightening torque (terminals) 0.5 Nm
Earthing via screw terminal
Enclosure material thermoplastic, UL 94 V-0
Colour yellow
Test standards IEC 61643-21, UL 497B
Approvals, Certifications CSA, GOST

Ordering information
Type BVT RS485 5
Part No. 918 401
Packing unit 1 pc(s).

www.dehn.de 221
BLITZDUCTOR® VT INFORMATION TECHNOLOGY SYSTEMS
918 402 BVT AD
24

BVT AD COMPACT SPDs FOR DIN RAIL MOUNTING

BVT AD 24 BLITZ-
DUCTOR VT 24 V 918 402

0V 0V

+24 V +24 V

IN OUT

• EMC protection for PLC 24 V power As a unipolar diode is used, negative operating Dimension drawing BVT AD
supply voltages are not permissible.

• Especially low protection level


• For installation in conformity with the Quickly responding surge protective device, for e.g. Siemens SPS S7-300 with d.c. power supply.
lightning protection zones concept at Especially for use in electromagnetically harsh environments where common varistor-based surge
the boundaries from 1 – 2 and higher arresters do not limit sufficiently.

BVT AD 24
SPD class W
Nominal d.c. voltage UN 24 V
Max. continuous operating d.c. voltage UC 35 V
Nominal current IL 10 A
C2 Total nominal discharge current (8/20 μs) In 2 kA
C2 Nominal discharge current (8/20 μs) per line In 1 kA
Voltage protection line-line for In C2 Up ) 70 V
Voltage protection level line-PG for In C2 Up ) 700 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 50 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 700 V
Capacitance line-line C ) 7 nF
Capacitance line-PG C ) 10 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output screw / screw
Cross-sectional area, solid 0.5 - 4.0 mm2
Cross-sectional area, flexible 0.5 - 4.0 mm2
Tightening torque (terminals) 0.8 Nm
Earthing via screw terminal
Enclosure material thermoplastic, UL 94 V-0
Colour yellow
Test standards IEC 61643-21, UL 497B
Approvals, Certifications CSA, GOST, UL

Ordering information
Type BVT AD 24
Part No. 918 402
Packing unit 1 pc(s).

222 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® VT
918 408 BVT ALD 36

COMPACT SPDs FOR DIN RAIL MOUNTING BVT ALD

BVT ALD 36
NEW
918 408

1 1

protected

2 2

Dimension drawing BVT ALD Basic circuit diagram BVT ALD • For d.c. supplies up to nominal cur-
rents of 4 A
Energy-coordinated combined lightning current and surge arrester for protection of unearthed d.c. • Low voltage protection level
supplies for DIN rail mounting
• For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A - 2 and higher

BVT ALD 36
SPD class M
Nominal d.c. voltage UN 36 V
Max. continuous operating d.c. voltage UC 45 V
Nominal current at 80°C IL 4A
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA
D1 Total lightning impulse current (10/350 μs) Iimp 5 kA
C2 Total nominal discharge current (8/20 μs) In 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA
Voltage protection line-line for In C2 Up ) 80 V
Voltage protection level line-PG for In C2 Up ) 1000 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 60 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 650 V
Series impedance per line 22 μH
Capacitance line-line C ) 1.5 pF
Capacitance line-PG C ) 100 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output screw / screw
Cross-sectional area, solid 0.5 - 6.0 mm2
Cross-sectional area, flexible 0.5 - 4.0 mm2
Tightening torque (terminals) 0.8 Nm
Earthing via screw terminal
Enclosure material thermoplastic, UL 94 V-0
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type BVT ALD 36
Part No. 918 408
Packing unit 1 pc(s).

www.dehn.de 223
BLITZDUCTOR® VT KKS INFORMATION TECHNOLOGY SYSTEMS
Combined lightning current and COMPACT SPDs FOR DIN RAIL MOUNTING
surge arrester for cathodic corrosion protection systems
• Maximum efficiency due to high discharge
capacity
• Easy maintenance due to remote signalling
contact
• Resistant to permanent interference voltages
up to 65 V a.c.

SPD for protecting active cathodic corrosion protection systems.


Integrated floating remote signalling contact (break contact) for function
monitoring.
The protective circuit and voltage measuring circuit are protected against be considered and further measures have to be taken.
surge impulses caused by atmospheric discharges (lightning) or switching The devices can be overloaded by overcurrents caused by mains faults
operations (in power supply lines). (short circuits or earth faults). Therefore, they should be installed into a
The devices are designed for operation at permanent interference volt- separate metallic enclosure or a prewired terminal unit (ITAK) should be
ages up to 65 V a.c. between pipelines and earth. If this value is exceed- used. The integrated remote signalling contact indicates thermal overload
ed, the relevant regulations for protection against electrical shock have to of the discharge paths.

In cathodic corrosion protection systems,


SPDs for protective circuits and voltage
measuring circuits are often used at the
same time. For easy identification, the
SPDs have different colours, i.e. yellow for
voltage measuring circuits and red for
protective circuits.
DEHN has long-
standing experience
BVT KKS surge arrester family in using SPDs for
pipeline networks
and would be
Experience has shown that the installa-
pleased to assist
tion of SPDs into a separate metal enclo-
you to find the
sure is reasonable as the enclosure pro-
appropriate protec-
vides additional protection from over-
tion for your appli-
loads caused by short circuits. With ITAK,
cations.
DEHN provides adequate prewired units
for cathodic corrosion protection systems.
The ITAK serial number serves as refer-
ence number for ordering.

ITAK, Serial No. 4305

Application example

224 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® VT KKS
918 420 BVT KKS
ALD 75

COMPACT SPDs FOR DIN RAIL MOUNTING BVT KKS ALD

BVT KKS ALD 75 BLITZ- K− Kp−


DUCTOR VT 918 420

K+ Kp+

FM

Dimension drawing BVT KKS ALD Thermal fuses monitor the varistors. Capacitive • For protective circuits
control for a low impulse sparkover voltage.
• High nominal current
• For installation in conformity with the
Energy-coordinated combined lightning current and surge arrester for protecting the inverter in the lightning protection zones concept at
protective circuit (red colour). Plug-in remote signalling contact (break contact) for indicating over- the boundaries from 0A – 2 and higher
loads. Installation into the steel plate enclosure recommended.

BVT KKS ALD 75


SPD class M
Nominal voltage UN 70 V
Max. continuous operating d.c. voltage Uc 75 V
Nominal current IL 12 A
D1 Total lightning impulse current (10/350 μs) Iimp 7 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 3.5 kA
C2 Total nominal discharge current (8/20 μs) In 40 kA
C2 Nominal discharge current (8/20 μs) per line In 20 kA
Voltage protection level line-line for Iimp D1 Up ) 400 V
Voltage protection level line-PG for Iimp D1 Up ) 400 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 350 V
Voltage protection level line-PG at 1 kV/μs PG Up ) 350 V
A2 Total a.c. current carrying capacity 20 A
Series impedance per line 5 μH
Cut-off frequency line-line fG 1 MHz
Capacitance line-line C ) 2 nF
Capacitance line-PG C ) 2 nF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output screw / screw
Cross-sectional area, solid 0.5 - 6 mm2
Cross-sectional area, flexible 0.5 - 4 mm2
Tightening torque (terminal) 0.8 Nm
Earthing via screw terminal
Enclosure material thermoplastic, UL 94 V-0
Colour red
Test standards IEC 61643-21
Approvals, Certifications GOST
Type of remote signalling contacts break contact
Switching capacity d.c. 250 V/0.1 A, 125 V/0.2 A, 75 V/0.5 A
Switching capacity a.c. 250 V/0.5 A
Cross-sectional area for remote signalling terminals max 1.5 mm2

Ordering information
Type BVT KKS ALD 75
Part No. 918 420
Packing unit 1 pc(s).

www.dehn.de 225
BLITZDUCTOR® VT KKS INFORMATION TECHNOLOGY SYSTEMS
918 421 BVT KKS
APD 36

BVT KKS APD COMPACT SPDs FOR DIN RAIL MOUNTING

M− Mp− BVT KKS APD 36


918 421

M+ Mp+

FM

• For voltage measuring circuits Thermal fuses monitor the discharge circuits. Dimension drawing BVT KKS APD
Capacitive control for a low impulse sparkover
• Plug-in remote signalling contact voltage.
• For installation in conformity with the
lightning protection zones concept at Energy-coordinated combined lightning current and surge arrester for protecting voltage measur-
the boundaries from 0A – 2 and higher ing circuits (yellow colour). Plug-in remote signalling contact (break contact) for indicating over-
loads. Installation into a steel plate enclosure recommended.

BVT KKS APD 36


SPD class M
Nominal voltage UN 36 V
Max. continuous operating d.c. voltage Uc 36.8 V
Nominal current IL 0.05 A
D1 Total lightning impulse current (10/350 μs) Iimp 7 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 3.5 kA
C2 Total nominal discharge current (8/20 μs) In 40 kA
C2 Nominal discharge current (8/20 μs) per line In 20 kA
Voltage protection level line-line for Iimp D1 Up ) 65 V
Voltage protection level line-PG for Iimp D1 Up ) 800 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 48 V
Voltage protection level line-PG at 1 kV/μs PG Up ) 600 V
A2 Total a.c. current carrying capacity 20 A
Series impedance per line 70 ohms
Cut-off frequency line-line fG 4.5 dB at 1 MHz (100 ohms)
Capacitance line-line C ) 1 nF
Capacitance line-PG C ) 10 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output screw / screw
Cross-sectional area, solid 0.5 mm - 6 mm2
Cross-sectional area, flexible 0.5 mm - 4 mm2
Tightening torque (terminal) 0.8 Nm
Earthing via screw terminal
Enclosure material thermplastic, UL 94 V-0
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications GOST
Type of remote signalling contacts break contact
Switching capacity d.c. 250 V/0.1 A, 125 V/0.2 A, 75 V/0.5 A
Switching capacity a.c. 250 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2

Ordering information
Type BVT KKS APD 36
Part No. 918 421
Packing unit 1 pc(s).

226 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® VT KKS
918 404 BVT KKS
ALD SN

COMPACT SPDs FOR DIN RAIL MOUNTING BVT KKS ALD SN

BVT KKS ALD SN BLITZ- M Mp


DUCTOR VT 918 404

D Dp

FM

Dimension drawing BVT KKS ALD SN Thermal fuses monitor the varistors. Capacitive • For protective circuits
control for a low impulse sparkover voltage.
• Device acc. to SNAM specification
• For installation in conformity with the
Energy-coordinated combined lightning current and surge arrester for protecting the inverter in the lightning protection zones concept at
protective circuit (red colour). Plug-in remote signalling contact (break contact) for indicating over- the boundaries from 0A – 2 and higher
loads. Installation into steel plate enclosure recommended. Device according to SNAM specification.

BVT KKS ALD SN


SPD class M
Nominal voltage UN 70 V
Max. continuous operating d.c. voltage Uc 75 V
Nominal current IL 12 A
D1 Total lightning impulse current (10/350 μs) Iimp 7 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 3.5 kA
C2 Total nominal discharge current (8/20 μs) In 40 kA
C2 Nominal discharge current (8/20 μs) per line In 20 kA
Voltage protection level line-line for Iimp D1 Up ) 400 V
Voltage protection level line-PG for Iimp D1 Up ) 400 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 350 V
Voltage protection level line-PG at 1 kV/μs PG Up ) 350 V
A2 Total a.c. current carrying capacity 20 A
Series impedance per line 5 μH
Cut-off frequency line-line fG 1 MHz
Capacitance line-line C ) 2 nF
Capacitance line-PG C ) 2 nF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output screw / screw
Cross-sectional area, solid 0.5 - 6 mm2
Cross-sectional area, flexible 0.5 - 4 mm2
Tightening torque (terminal) 0.8 Nm
Earthing via screw terminal
Enclosure material thermoplastic, UL 94 V-0
Colour red
Test standards IEC 61643-21
Approvals, Certifications SNAM specification, GOST
Type of remote signalling contacts break contact
Switching capacity d.c. 250 V/0.1 A, 125 V/0.2 A, 75 V/0.5 A
Switching capacity a.c. 250 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2

Ordering information
Type BVT KKS ALD SN
Part No. 918 404
Packing unit 1 pc(s).

www.dehn.de 227
BLITZDUCTOR® VT KKS INFORMATION TECHNOLOGY SYSTEMS
918 405 BVT KKS
APD SN

BVT KKS APD SN COMPACT SPDs FOR DIN RAIL MOUNTING

E Ep BVT KKS APD SN BLITZ-


DUCTOR VT 918 405

M Mp

FM

• For voltage measuring circuits Thermal fuses monitor the discharge circuits. Dimension drawing BVT KKS APD SN
Capacitive control for a low impulse sparkover
• Device acc. to SNAM specification voltage.
• For installation in conformity with the
lightning protection zones concept at Energy-coordinated combined lightning current and surge arrester for protecting the voltage meas-
the boundaries from 0A – 2 and higher uring circuit (yellow colour). Plug-in remote signalling contact (break contact) for indicating over-
loads. Installation into steel plate enclosure recommended. Device according to SNAM specification.

BVT KKS APD SN


SPD class M
Nominal voltage UN 36 V
Max. continuous operating d.c. voltage Uc 36.8 V
Nominal current IL 0.1 A
D1 Total lightning impulse current (10/350 μs) Iimp 7 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 3.5 kA
C2 Total nominal discharge current (8/20 μs) In 40 kA
C2 Nominal discharge current (8/20 μs) per line In 20 kA
Voltage protection level line-line for Iimp D1 Up ) 65 V
Voltage protection level line-PG for Iimp D1 Up ) 900 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 48 V
Voltage protection level line-PG at 1 kV/μs PG Up ) 600 V
A2 Total a.c. current carrying capacity 20 A
Series impedance per line 10 ohms
Cut-off frequency line-line fG 6 MHz
Capacitance line-line C ) 1 nF
Capacitance line-PG C ) 10 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output screw / screw
Cross-sectional area, solid 0.5 - 6 mm2
Cross-sectional area, flexible 0.5 - 4 mm2
Tightening torque (terminal) 0.8 Nm
Earthing via screw terminal
Enclosure material thermoplastic, UL 94 V-0
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications SNAM specification, GOST
Type of remote signalling contacts break contact
Switching capacity d.c. 250 V/0.1 A, 125 V/0.2 A, 75 V/0.5 A
Switching capacity a.c. 250 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2

Ordering information
Type BVT KKS APD SN
Part No. 918 405
Packing unit 1 pc(s).

228 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNrapid® LSA
SPDs FOR LSA TECHNOLOGY Lightning current / surge arrester

• Variable protection for 1 – 10 pairs for LSA sys-

0
tems, type series 2/10

9
8
7
6
5
• LSA disconnection block function integrated in

4
3
2
1
the lightning current arrester provides protec-
tion for testing, disconnecting and patching
• Modular system of lightning current and surge
arresters, allows also for combination to one
combined SPD

DRL plug-in SPD block (10 pairs):


Lightning current arrester for 10 pairs.
DRL plug (1 pair):
Surge protective plug for 1 pair, energy-coordinated with
DRL plug-in SPD blocks.

Lightning current arrester, surge arrester or combined lightning current of pairs with plugged-in protection or the additional attachment of single-
and surge arrester, pluggable into type 2 LSA disconnection blocks. The pair surge arresters for optimal protection of terminal equipment. The
10-pair plug-in SPD block with lightning current carrying capacity incor- surge arresters snap into the earthing frame and can be removed as a
porates gas discharge tubes (optional visual fault indication) and discon- block, whenever required.
nection block contacts. This allows for testing, disconnecting or patching

The DEHNrapid LSA lightning current arrester for LSA disconnection blocks
DRL XX XXX ... surge arrester effectively protects sensitive hardware from surges and allows for simul-
O taneous testing, disconnecting and patching of connected lines. The mod-
ular SPD system for LSA disconnection blocks can be extended to a com-
bined lightning current and surge arrester and features fail-safe overload
= combined lightning

EF 10 DRL
protection with visual fault indication of the discharge elements.
surge arrester
O

+
current and

DRL 10 B 180

lightning
current
arrester
G
TL 2 10DA LSA
91.4
82.9
72.2
52.5

MB 2 10DA LSA

DRL system design DRL assembly with the relevant heights

www.dehn.de 229
DEHNrapid® LSA INFORMATION TECHNOLOGY SYSTEMS
Lightning current / surge arrester SPDs FOR LSA TECHNOLOGY

With the appropriate earthing frame, the fine limiting DEHNrapid LSA sin-
gle-pair surge arresters can be plugged directly into the DRL plug-in SPD
0
9
8

block or optionally into LSA disconnection blocks. The decoupling imped-


7
6
5

ances integrated in the protective plugs allow energy coordination with


4
3
2

the DRL plug-in SPD block irrespective of the cable length. The single-pair
1

plug also allows partial insertion of disconnection blocks including the


possibility to plug protective plugs with different circuits or nominal volt-
ages into one block.
DRL protective plugs with earthing frame

ab ab
a’ b a’ b
’ ’

a a'
a a'
DRL 10 B 180... TL 2 10DA LSA

DRL combined lightning current and surge arrester Disconnection block function

The integrated unit of plug-in SPD block, earthing frame and protective The plug-in SPD block has disconnection contacts that are compatible
plug (combined lightning current and surge arrester) can be completely with the disconnection block. A measuring or disconnection adapter can
removed and plugged in. The combined lightning current and surge be plugged into the DRL in the same way as a disconnection block to
arrester corresponds to SPD Class G O. ensure protection during maintenance operation.

A fail-safe function short-circuits the lines to earth to protect the gas dis- DRL 10 B 180 FSD
charge tube from a possible burn-off due to overcurrents. In the event of fail-safe
an overcurrent, the disconnecting solder between the spring and the SPD fail-safe
light pink
melts, the lines are short-circuited and the temperature-sensitive colour
dark purple
on the spring changes from light pink to dark purple, signalling the user
to replace the SPD.

new

ok replace
Replace the faulty gas discharge tube

230 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNrapid® LSA
907 400 DRL 10 B
180

SPDs FOR LSA TECHNOLOGY DRL 10 B

DRL 10 B 180
907 400 IN
a b
1 2 3 4 5 6 7 8 9 10

0
9
8
7
6
5
4
3
2
1
a’ b’
OUT • Lightning current arrester for use as
plug-in SPD block with integrated LSA
Dimension drawing DRL 10 B SPD block with 3-pole gas discharge tubes. disconnection block function
Integrated isolating contacts for plugging
additional elements.
• Extendible to a combined lightning
current and surge arrester
DRL plug-in SPD block (10 pairs) with lightning current carrying capacity, for nearly all kinds of appli- • For installation in conformity with the
cations. Extendible with DRL protective plug to a combined lightning current and surge arrester. The lightning protection zones concept at
integrated disconnection block contacts allow for testing, measuring and patching in case of plugged- the boundaries from 0A – 1 and higher
in protection.

DRL 10 B 180
SPD class G
Nominal voltage UN 180 V
Max. continuous operating d.c. voltage UC 180 V
Max. continuous operating a.c. voltage UC 127 V
Nominal current IL 0.4 A
D1 Total lightning impulse current (10/350 μs) Iimp 5 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 5 kA
Voltage protection level line-line for Iimp D1 Up ) 500 V
Voltage protection level line-PG for Iimp D1 Up ) 500 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 500 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 450 V
Series impedance per line ) 0.005 ohms
Capacitance line-line C ) 5 pF
Capacitance line-PG C ) 5 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 10
Pluggable into LSA disconnection block 2/10
Earthing via mounting frame
Enclosure material polyamide PA 6.6
Colour grey
Test standards IEC 61643-21
Approvals, Certifications VdS, GOST

Ordering information
Type DRL 10 B 180
Part No. 907 400
Packing unit 10 pc(s).

Accessory Part for DEHNrapid® LSA Accessory Part for DEHNrapid® LSA
Label holder 907 497 SR DRL

Gas discharge tube


Universal label holder made of stainless steel, for clear marking of High-capacity spare gas discharge tubes for DRL 10 or BM 10 DRL. Three- 907 218
B3
907 219
B3 FSD
GDT 230

GDT 230

LSA connections. Can be snapped onto DEHNrapid LSA plug-in SR DRL


907 497
pole unit with common arc chamber for a constant voltage protection level
SPD blocks, earthing frames with protective plug or mounting for line-line and line-ground.
frames with LSA SPD blocks, 2/10 series. Type GDT 230 B3 GDT 230 B3 FSD
GDT 230 B3
907 218
GDT 230 B3 FSD
907 219

PU Part Integrated into Part No. 907 400 907 401


Type pc(s). No. Visual fault indicator — 3
SR DRL 1 907 497 Fail-safe spring — 3
PU Part
Type pc(s). No.
GDT 230 B3 1 907 218
GDT 230 B3 FSD 1 907 219

www.dehn.de 231
DEHNrapid® LSA INFORMATION TECHNOLOGY SYSTEMS
907 401 DRL 10 B
180 FSD

DRL 10 B FSD SPDs FOR LSA TECHNOLOGY

IN DRL 10 B 180 FSD


907 401
a b
1 2 3 4 5 6 7 8 9 10
0
9
8
7
6
5
4
3
2
1

• Lightning current arrester for use as


plug-in SPD block with integrated LSA
a’ b’
disconnection block function OUT

• Visual fault indicator of the gas


discharge tubes SPD block with 3-pole gas discharge tubes with Dimension drawing DRL 10 B FSD
fail-safe function. Integrated isolating contacts
• Extendible with DRL protective plugs for plugging additional elements.
to a combined lightning current and
surge arrester DRL plug-in SPD block (10 pairs) with lightning current carrying capacity, for nearly all types of appli-
• For installation in conformity with the cations. Extendible with DRL protective plug to a combined lightning current and surge arrester. The
lightning protection zones concept at integrated disconnection block contacts allow for testing, measuring and patching in case of plugged-
the boundaries from 0A – 1 and higher in protection.The gas discharge tubes have a fail-safe function with visual indicator for potential faults.

DRL 10 B 180 FSD


SPD class G
Fault indication visually by colour change
Nominal voltage UN 180 V
Max. continuous operating d.c. voltage UC 180 V
Max. continuous operating a.c. voltage UC 127 V
Nominal current IL 0.4 A
D1 Total lightning impulse current (10/350 μs) Iimp 5 kA
D1 Lightning impulse current (10/350 μs) per line Iimp 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 5 kA
Voltage protection level line-line for Iimp D1 Up ) 500 V
Voltage protection level line-PG for Iimp D1 Up ) 500 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 500 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 450 V
Series impedance per line ) 0.005 ohms
Capacitance line-line C ) 5 pF
Capacitance line-PG C ) 5 pF
Fail-safe performance gas discharge tube with spring contacts
Operating temperature range -40°C...+80°C
Degree of protection IP 10
Pluggable into LSA disconnection block 2/10
Earthing via mounting frame
Enclosure material polyamide PA 6.6
Colour grey
Test standards IEC 61643-21
Approvals, Certifications VdS, GOST

Ordering information
Type DRL 10 B 180 FSD
Part No. 907 401
Packing unit 10 pc(s).

Gas discharge tube 907 497 SR DRL

Label holder
907 218
B3
907 219
B3 FSD
GDT 230

GDT 230 High-capacity spare gas discharge tubes for DRL 10 or BM 10 DRL. Three- Universal label holder made of stainless steel, for clear marking of
pole unit with common arc chamber for a constant voltage protection level SR DRL
907 497
LSA connections. Can be snapped onto DEHNrapid LSA plug-in
for line-line and line-ground. SPD blocks, earthing frames with protective plug or mounting
GDT 230 B3
907 218
GDT 230 B3 FSD
907 219
Type GDT 230 B3 GDT 230 B3 FSD frames with LSA SPD blocks, 2/10 series.
Integrated into Part No. 907 400 907 401 PU Part
Visual fault indicator — 3 Type pc(s). No.
Fail-safe spring — 3 SR DRL 1 907 497
PU Part
Type pc(s). No.
GDT 230 B3 1 907 218
GDT 230 B3 FSD 1 907 219

232 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNrapid® LSA
907 420 DRL RE 5
907 421 DRL RE

SPDs FOR LSA TECHNOLOGY DRL RE


12
907 422 DRL RE
24
907 423 DRL RE
48
907 424 DRL RE
60
907 425 DRL RE
180

DRL RE 5
907 420
DRL RE 12
907 421
DRL RE 24
907 422
DRL RE 48
907 423
a a
DRL RE 60

22 9.4
907 424

0
DRL RE 180
907 425

9
8
7
6
5
33.4

IN OUT

4
8.5

3
2
1
b b

Dimension drawing DRL RE Protective circuit energy-coordinated with DRL 10 B • Low voltage protection level for the
for protecting terminal equipment, fine limitation protection of terminal equipment
between line and PG
• Energy-coordinated with DRL plug-in
Protective plug (1 pair), energy-coordinated with DRL plug-in SPD block, for use as single-stage SPD block
protection for terminal equipment with decoupling impedances. Ideally suited for signal circuits • For installation in conformity with the
with common potential. Earthing via EF 10 DRL. For disconnection blocks or DRL plug-in SPD blocks lightning protection zones concept at
only. the boundaries from 1 – 2 and higher

DRL RE 5 DRL RE 12 DRL RE 24 DRL RE 48 DRL RE 60 DRL RE 180


SPD class O O O O O O
Nominal voltage UN 5V 12 V 24 V 48 V 60 V 180 V
Max. continuous operating d.c. voltage UC 6V 14 V 28 V 54 V 70 V 180 V
Max. continuous operating a.c. voltage UC 4.2 V 9.5 V 19.5 V 38 V 49.5 V 127 V
Nominal current IL 0.4 A 0.4 A 0.4 A 0.4 A 0.4 A 0.1 A
D1 Total lightning impulse current (10/350 μs)
in combination with DRL 10 B... Iimp 5 kA 5 kA 5 kA 5 kA 5 kA 5 kA
D1 Lightning impulse current (10/350 μs) per line
in combination with DRL 10 B... Iimp 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA
C2 Total nominal discharge current (8/20 μs)
in combination with DRL 10 B... In 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA
C2 Nominal discharge current (8/20 μs) per line
in combination with DRL 10 B... In 5 kA 5 kA 5 kA 5 kA 5 kA 5 kA
Voltage protection level line-PG for Iimp D1
in combination with DRL 10 B... Up ) 40 V ) 45 V ) 65 V ) 95 V ) 115 V ) 280 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 17.0 V ) 36 V ) 72 V ) 135 V ) 185 V ) 500 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 9.5 V ) 19 V ) 38 V ) 70 V ) 95 V ) 270 V
Series impedance per line 4.7 ohms 4.7 ohms 4.7 ohms 6.8 ohms 6.8 ohms 4.7 ohms
Cut-off frequency line-PG fG 0.95 MHz 2.7 MHz 4.5 MHz 7.35 MHz 10.5 MHz 42 MHz
Capacitance line-line C ) 3 nF ) 1 nF ) 0.55 pF ) 350 pF ) 250 pF ) 50 pF
Capacitance line-PG C ) 6 nF ) 2 nF ) 1.1 nF ) 700 pF ) 500 pF ) 80 pF
Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C
Degree of protection IP 20 plugged in IP 20 plugged in IP 20 plugged in IP 20 plugged in IP 20 plugged in IP 20 plugged in
Pluggable into LSA disconnection block 2/10 or DRL 10 B ... plug-in SPD block
Earthing via earthing frame earthing frame earthing frame earthing frame earthing frame earthing frame
Enclosure material polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6
Colour yellow yellow yellow yellow yellow yellow
Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21
Approvals, Certifications VdS, GOST VdS, GOST VdS, GOST VdS, GOST VdS, GOST VdS, GOST

Ordering information
Type DRL RE 5 DRL RE 12 DRL RE 24 DRL RE 48 DRL RE 60 DRL RE 180
Part No. 907 420 907 421 907 422 907 423 907 424 907 425
Packing unit 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s).

Label holder 907 497 SR DRL

Earthing frame 907 498 EF 10 DRL

Universal label holder made of stainless steel, for clear marking of LSA Earthing frame with snap-on mechanism, required for earthing and
connections. Can be snapped onto DEHNrapid LSA plug-in SPD blocks, SR DRL
907 497
mounting max. 10 DRL protective plugs. Pluggable onto a 10-pair dis- EF 10 DRL
907 498

earthing frames with protective plug or mounting frames with LSA SPD connection block or DRL plug-in SPD block.
blocks, 2/10 series. PU Part
PU Part Type pc(s). No.
Type pc(s). No. EF 10 DRL 1 907 498
SR DRL 1 907 497

www.dehn.de 233
DEHNrapid® LSA INFORMATION TECHNOLOGY SYSTEMS
907 440 DRL RD 5
907 441 DRL RD

DRL RD SPDs FOR LSA TECHNOLOGY


12
907 442 DRL RD
24
907 443 DRL RD
48
907 444 DRL RD
60
907 445 DRL RD
110

DRL RD 5
907 440
DRL RD 12
907 441
DRL RD 24
907 442
a a´ DRL RD 48
907 443
DRL RD 60

22 9.4
907 444
0

DRL RD 110
907 445
9
8
7
6
5

33.4
IN OUT
4

8.5
3
2
1

b b´

• Low voltage protection level line/line


for the protection of terminal equip- Line-line protective circuit, energy-coordinated Dimension drawing DRL RD
ment with DRL 10 B for protecting terminal equipment.
• Energy-coordinated with DRL plug-in
SPD block Protective plug (1 pair), energy-coordinated with DRL plug-in SPD block for use as single-stage pro-
• For installation in conformity with the tection for terminal equipment. Low voltage protection levels line-line for electrically isolated inter-
lightning protection zones concept at faces. For mounting with EF 10 DRL. Installation recommended only in combination with DRL plug-
the boundaries from 1 – 2 and higher in SPD block.

DRL RD 5 DRL RD 12 DRL RD 24 DRL RD 48 DRL RD 60 DRL RD 110


SPD class O O O O O O
Nominal voltage UN 5V 12 V 24 V 48 V 60 V 110 V
Max. continuous operating d.c. voltage UC 6V 14 V 28 V 54 V 70 V 180 V
Max. continuous operating a.c. voltage UC 4.2 V 9.5 V 19.5 V 38 V 49.5 V 127 V
Nominal current IL 0.4 A 0.4 A 0.4 A 0.4 A 0.4 A 0.4 A
D1 Total lightning impulse current (10/350 μs)
in combination with DRL 10 B... Iimp 5 kA 5 kA 5 kA 5 kA 5 kA 5 kA
D1 Lightning impulse current (10/350 μs) per line
in combination with DRL 10 B... Iimp 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA
C2 Total nominal discharge current (8/20 μs)
in combination with DRL 10 B... In 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA
C2 Nominal discharge current (8/20 μs) per line
in combination with DRL 10 B... In 5 kA 5 kA 5 kA 5 kA 5 kA 5 kA
Voltage protection level line-PG for Iimp D1
in combination with DRL 10 B... Up ) 500 V ) 500 V ) 500 V ) 500 V ) 500 V ) 500 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 8.5 V ) 18 V ) 36 V ) 70 V ) 95 V ) 250 V
Series impedance per line 2.2 ohms 2.2 ohms 2.2 ohms 4.7 ohms 4.7 ohms 4.7 ohms
Cut-off frequency line-line fG 1 MHz 2.7 MHz 5.4 MHz 7.8 MHz 11 MHz 20 MHz
Capacitance line-line C ) 5.5 nF ) 2.0 nF ) 1.1 nF ) 700 pF ) 500 pF ) 200 pF
Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C
Degree of protection IP 20 plugged in IP 20 plugged in IP 20 plugged in IP 20 plugged in IP 20 plugged in IP 20 plugged in
Pluggable into LSA disconnection block 2/10 or DRL 10 B... plug-in SPD block
Enclosure material polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6
Colour yellow yellow yellow yellow yellow yellow
Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21
Approvals, Certifications VdS, GOST VdS, GOST VdS, GOST VdS, GOST VdS, GOST GOST

Ordering information
Type DRL RD 5 DRL RD 12 DRL RD 24 DRL RD 48 DRL RD 60 DRL RD 110
Part No. 907 440 907 441 907 442 907 443 907 444 907 445
Packing unit 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s).

907 498 EF 10 DRL


Earthing frame 907 497 SR DRL Label holder
Earthing frame with snap-on mechanism, required for earthing and Universal label holder made of stainless steel, for clear marking of LSA
EF 10 DRL
907 498
mounting of max. 10 DRL protective plugs. Pluggable onto a 10-pair SR DRL
connections. Can be snapped onto DEHNrapid LSA plug-in SPD blocks,
disconnection block or DRL plug-in SPD block. 907 497
earthing frames with protective plug or mounting frames with LSA SPD
PU Part blocks, 2/10 series.
Type pc(s). No. PU Part
EF 10 DRL 1 907 498 Type pc(s). No.
SR DRL 1 907 497

234 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNrapid® LSA
907 430 DRL PD
180

SPDs FOR LSA TECHNOLOGY DRL PD

DRL PD 180
907 430

a a´
22 9.4

0
9
8
7
6
5
33.4

IN OUT

4
8.5

3
2
1
b b´

Dimension drawing DRL PD Protective circuit, energy-coordinated with DRL 10 B • For maximum transmission rates –
for protecting terminal equipment, fine limitation combined with overcurrent protection
between the lines and additional overcurrent
protection. • Energy-coordinated with DRL plug-in
SPD block
Protective plug (1 pair), energy-coordinated with DRL plug-in SPD block for use as single-stage pro- • For installation in conformity with the
tection for terminal equipment. Low voltage protection level line-line and integrated overcurrent pro- lightning protection zones concept at
tection for ADSL, ISDN Uk0 or a/b lines. For mounting with EF 10 DRL. Installation recommended only the boundaries from 1 – 2 and higher
in combination with DRL plug-in SPD block.

DRL PD 180
SPD class O
Nominal voltage UN 180 V
Max. continuous operating d.c. voltage UC 180 V
Max. continuous operating a.c. voltage UC 127 V
Nominal current IL 0.1 A
D1 Total lightning impulse current (10/350 μs)
in combination with DRL 10 B... Iimp 5 kA
D1 Lightning impulse current (10/350 μs) per line
in combination with DRL 10 B... Iimp 2.5 kA
C2 Total nominal discharge current (8/20 μs)
in combination with DRL 10 B... In 10 kA
C2 Nominal discharge current (8/20 μs) per line
in combination with DRL 10 B... In 5 kA
Voltage protection level line-PG for Iimp D1
in combination with DRL 10 B... Up ) 500 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 270 V
Series impedance per line 10 ohms
Cut-off frequency line-line fG 61 MHz
Capacitance line-line C ) 80 pF
Integrated overcurrent protection 3
Operating temperature range 0°C...+70°C
Degree of protection IP 20 plugged in
Pluggable into LSA disconnection block 2/10 or DRL 10 B... plug-in SPD block
Enclosure material polyamide PA 6.6
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type DRL PD 180
Part No. 907 430
Packing unit 10 pc(s).

Label holder 907 497 SR DRL Earthing frame 907 498 EF 10 DRL

Universal label holder made of stainless steel, for clear marking of Earthing frame with snap-on mechanism, required for earthing and
LSA connections. Can be snapped onto DEHNrapid LSA plug-in SR DRL
mounting of max. 10 DRL protective plugs. Pluggable onto a 10-pair EF 10 DRL
907 498

SPD blocks, earthing frames with protective plug or mounting 907 497
disconnection block or DRL plug-in SPD block.
frames with LSA SPD blocks, 2/10 series. PU Part
PU Part Type pc(s). No.
Type pc(s). No. EF 10 DRL 1 907 498
SR DRL 1 907 497

www.dehn.de 235
DEHNrapid® LSA INFORMATION TECHNOLOGY SYSTEMS
907 465 DRL HD 5
907 470 DRL HD

DRL HD SPDs FOR LSA TECHNOLOGY


24

DRL HD 5
907 465
DRL HD 24
907 470

a a´
22 9.4
0
9
8
7
6
5

33.4
IN OUT
4

8.5
3
2
1

b b´

• For maximum transmission rates Protective circuit, energy-coordinated with DRL 10 B, Dimension drawing DRL HD
with low capacitance for protection of terminal
• Energy-coordinated with DRL plug-in equipment line-line.
SPD block
• For installation in conformity with the Protective plug (1 pair), energy-coordinated with DRL plug-in SPD block, for use as single-stage
lightning protection zones concept at protection for terminal equipment for high-frequency transmissions such as G.703 or ISDN U2m, S2m
the boundaries from 1 – 2 and higher and S0. To be mounted with EF 10 DRL. Installation recommended only in combination with DRL
plug-in SPD block.

DRL HD 5 DRL HD 24
SPD class O O
Nominal voltage UN 5V 24 V
Max. continuous operating d.c. voltage UC 6.5 V 28 V
Max. continuous operating a.c. voltage UC 4.6 V 19.5 V
Nominal current IL 0.4 A 0.4 A
D1 Total lightning impulse current (10/350 μs)
in combination with DRL 10 B... Iimp 5 kA 5 kA
D1 Lightning impulse current (10/350 μs) per line
in combination with DRL 10 B... Iimp 2.5 kA 2.5 kA
C2 Total nominal discharge current (8/20 μs)
in combination with DRL 10 B... In 10 kA 10 kA
C2 Nominal discharge current (8/20 μs) per line
in combination with DRL 10 B... In 5 kA 5 kA
Voltage protection level line-PG for Iimp D1
in combination with DRL 10 B... Up ) 500 V ) 500 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 25 V ) 46 V
Series impedance per line 2.2 ohms 4.7 ohms
Cut-off frequency line-line fG 90 MHz 94 MHz
Capacitance line-line C ) 22 pF ) 22 pF
Operating temperature range -40°C...+80°C -40°C...+80°C
Degree of protection IP 20 plugged in IP 20 plugged in
Pluggable into LSA disconnection block 2/10 or DRL 10 B... plug-in SPD block
Enclosure material polyamide PA 6.6 polyamide PA 6.6
Colour yellow yellow
Test standards IEC 61643-21 IEC 61643-21
Approvals, Certifications GOST VdS, GOST

Ordering information
Type DRL HD 5 DRL HD 24
Part No. 907 465 907 470
Packing unit 10 pc(s). 10 pc(s).

907 498 EF 10 DRL


Earthing frame 907 497 SR DRL Label holder
Earthing frame with snap-on mechanism, required for earthing and Universal label holder made of stainless steel, for clear marking of LSA
EF 10 DRL
907 498
mounting of max. 10 DRL protective plugs. Pluggable onto a 10-pair SR DRL
connections. Can be snapped onto DEHNrapid LSA plug-in SPD blocks,
disconnection block or DRL plug-in SPD block. 907 497
earthing frames with protective plug or mounting frames with LSA SPD
PU Part blocks, 2/10 series.
Type pc(s). No. PU Part
EF 10 DRL 1 907 498 Type pc(s). No.
SR DRL 1 907 497

236 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Accessories for DEHNrapid® LSA
907 498 EF 10 DRL

SPDs FOR LSA TECHNOLOGY Earthing frame

EF 10 DRL
907 498

0
9
8
7
6
5
4
3
2
1
Dimension drawing EF 10 DRL

Earthing frame with snap-on mechanism, required for earthing and mounting of max. 10 DRL pro-
tective plugs. Pluggable onto a 10-pair disconnection block or DRL plug-in SPD block.

EF 10 DRL
Pluggable into LSA disconnection blocks or DRL plug-in block
Earthing via mounting frame or DRL plug-in block
Enclosure material polyamide PA 6.6
Colour yellow

Ordering information
Type EF 10 DRL
Part No. 907 498
Packing unit 1 pc(s).

www.dehn.de 237
DEHNrapid® LSA Plug-in SPD Block INFORMATION TECHNOLOGY SYSTEMS
907 499 BM 10
DRL

(without SPDs) SPDs FOR LSA TECHNOLOGY

IN BM 10 DRL
a b 907 499

1 2 3 4 5 6 7 8 9 10
0
9
8
7
6
5
4
3
2
1

a’ b’
OUT

• Integrated disconnection contacts SPD block for 3-pole gas discharge tubes. Dimension drawing BM 10 DRL
Integrated disconnection contacts for plugging
• For LSA disconnection blocks of type additional elements.
2/10
• Individual insertion of SPDs Plug-in SPD block (without SPDs) for 1 to max. 10 gas discharge tubes of type GDT 230 B3 ... .
Can also be used for inserting DRL protective plugs with earthing frame.

BM 10 DRL
Pluggable into LSA disconnection blocks
Earthing via mounting frame
Enclosure material polyamide PA 6.6
Colour grey

Ordering information
Type BM 10 DRL
Part No. 907 499
Packing unit 10 pc(s).

Accessory Part for DEHNrapid® LSA Plug-in SPD Block Accessory Part for DEHNrapid® LSA Plug-in SPD Block
(without SPDs) (without SPDs)
Gas discharge tube Label holder
907 218
B3
GDT 230 High-capacity spare gas discharge tubes for DRL 10 or BM 10 DRL. Three- 907 497 SR DRL
Universal label holder made of stainless steel, for clear marking of
pole unit with common arc chamber for a constant voltage protection level LSA connections. Can be snapped onto DEHNrapid LSA plug-in
907 219 GDT 230
B3 FSD

GDT 230 B3
for line-line and line-ground. SR DRL
SPD blocks, earthing frames with protective plug or mounting
frames with LSA SPD blocks, 2/10 series.
907 218 907 497
GDT 230 B3 FSD
907 219
Type GDT 230 B3 GDT 230 B3 FSD
Integrated into Part No. 907 400 907 401 PU Part
Visual fault indicator — 3 Type pc(s). No.
Fail-safe spring — 3 SR DRL 1 907 497
PU Part
Type pc(s). No.
GDT 230 B3 1 907 218
GDT 230 B3 FSD 1 907 219

238 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DPL 10 G3
SPDs FOR LSA TECHNOLOGY Surge arrester

• Suitable for terminal and disconnection blocks

0
of LSA systems, type series 2/10

9
8
7
6
5
• For 10 pairs with individually tested gas dis-

4
3
2
1
charge tubes
• Individually replaceable protection elements
(gas discharge tubes)

Pluggable SPDs for use in LSA systems, type series 2/10.


Unit for use as protection block for 10 pairs with individually replaceable
protection elements.

Pluggable surge arresters for use as protection blocks in IT installations The surge arresters for 10 pairs can be easily installed and removed for
and devices, which have to be connected via terminal or disconnection testing purposes. The contact to earth via the mounting frame is automat-
blocks with LSA IDC terminal. Installation onto terminal blocks, however, ically established when plugging in the SPD. After being overloaded, the
is the preferred method, as their contact forces provide better fixation – protection elements can be individually replaced.
even in case of slight vibrations.

The protection blocks consist of simi-


lar basic SPD blocks, which are sup- DPL 10 G3 ...
plied and tested with different pro-
tection elements according to
requirements. AL 2 10DA LSA or
DPL 10 G3:
TL 2 10DA LSA
10 standard gas discharge tubes
DPL 10 G3 FSD:
10 gas discharge tubes with fail-safe
function and visual indicator
MB 2 10DA LSA

DPL 10 G3 family Installation of DPL

www.dehn.de 239
DPL 10 G3 INFORMATION TECHNOLOGY SYSTEMS
907 214 DPL 10
G3 110

DPL 10 G3 SPDs FOR LSA TECHNOLOGY


907 216 DPL 10
G3 110 FSD

IN DPL 10 G3 110
Technology, 10 TC
LSA-Plus
907 214
DPL 10 G3 110 FSD
1 2 3 4 5 6 7 8 9 10 907 216
0
9
8
7
6
5
4
3
2
1

OUT

• Powerful SPD block Block with 3-pole gas discharge tubes. As soon as Dimension drawing DPL 10 G3
the fail-safe function is activated, the relevant
• Types with/without fail-safe function lines are short-circuited to earth.
or visual indicator
• For installation in conformity with the Protective plug for 10 pairs with tripod gas discharge tubes for nearly all types of applications. SPDs
lightning protection zones concept at of type FSD have a fail-safe function and provide additional visual indication after the fail-safe fea-
the boundaries from 0B – 1 and higher ture has been activated. This helps to recognise immediately if an SPD has to be replaced.

DPL 10 G3 110 DPL 10 G3 110 FSD


SPD class B B
Fault indicator — visually by colour change
Nominal voltage UN 110 V 110 V
Max. continuous operating d.c. voltage Uc 180 V 180 V
Max. continuous operating a.c. voltage Uc 127 V 127 V
Nominal current IL 0.4 A 0.4 A
C2 Total nominal discharge current (8/20 μs) In 10 kA 10 kA
C2 Nominal discharge current (8/20 μs) per line In 5 kA 5 kA
Voltage protection level line-line for In C2 UP ) 600 V ) 600 V
Voltage protection level line-PG for In C2 Up ) 600 V ) 600 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 600 V ) 600 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 600 V ) 600 V
Capacitance line-line C ) 5 pF ) 5 pF
Capacitance line-PG C ) 5 pF ) 5 pF
Fail-safe performance — gas discharge tube with spring contacts
Operating temperature range -40°C...+80°C -40°C...+80°C
Pluggable into LSA disconnection and terminal blocks (type 2) LSA disconnection and terminal blocks (type 2)
Earthing via mounting frame mounting frame
Enclosure material polyamide polyamide
Colour grey grey
Test standards IEC 61643-21 IEC 61643-21

Ordering information
Type DPL 10 G3 110 DPL 10 G3 110 FSD
Part No. 907 214 907 216
Packing unit 10 pc(s). 10 pc(s).

Accessory Part for DPL 10 G3


907 208
G3
907 217
G3 FSD
GDT 230

GDT 230 Gas discharge tube


High-capacity spare gas discharge tube for DPL 10 G3. Three-pole type
GDT 230 G3
907 208
GDT 230 G3 FSD
with common arc chamber for a constant protection level for both
907 217
line/line and line/earth.
Type GDT 230 G3 GDT 230 G3 FSD
Integrated into Part No. 907 214 907 216
Visual fault indicator — 3
Fail-safe spring — 3
PU Part
Type pc(s). No.
GDT 230 G3 1 907 208
GDT 230 G3 FSD 1 907 217

240 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHN Enclosure for Equipotential Bonding
SPDs FOR LSA TECHNOLOGY Enclosure system for SPDs protecting IT equipment

• Premounted enclosure system for wiring and

0
protection components

9
8
7
6
5
• Tested lightning impulse current carrying

4
3
2
1
capacity
• Optimised for equipotential bonding (surge
arrester and shield connection)
• Metal enclosure, lockable against unauthorised
access

DEHN enclosures for equipotential bonding (DPG) are lockable metal


enclosures and intended for installation of wiring and protection compo-
nents. Available in four different sizes, the enclosures which are capable
of carrying lightning currents provide terminals to integrate surge
arresters and shields into the equipotential bonding.

Enclosure with lightning current carrying capacity, IP 40, for different Despite of a high packing density, a structured cabling management is
designs of distribution boards and for the insertion of surge arresters. The ensured – crossings between cabling and wiring are avoided and the
cover can be removed from the wall plate without tools and is equipped cabling of e.g. the LSA blocks becomes concise due to the 30 mm grid. For
with a lock with cylinder quarter turn and a key. The C-shaped design of this kind of cabling, an optional shield connection system is available
the wall plate facilitates installation work by sidewise or front access. LSA (constant force spring). The sophisticated earthing system permanently
mounting frames or DIN rails can be attached to the wall plate by means connects all conductive components of the enclosure system by mechan-
of cable entry plates and cable rails. ical contacting or earth conductors by means of an earthing block.

DEHN enclosures for equipotential bonding (DPG) are available in 4 dif- The shields of incoming conduc-
ferent sizes, allowing for the insertion of 3/6/12/22 LSA blocks. Even if tors can be contacted with con-
20/50/100/200 pairs are used, enough space is provided for the earth con- stant force springs of type SA KRF
ductor block for supporting shielded sheath wires. in a space-saving way and with
lightning current capacity. All
equipotential bonding conductors
are led together in the central
earthing block.

Shield connection with SA KRF

DEHN enclosures for equipotential bonding (DPG) in 4 different sizes

www.dehn.de 241
DEHN Enclosure for Equipotential Bonding INFORMATION TECHNOLOGY SYSTEMS
906 100 DPG LSA
30 P

DPG LSA SPDs FOR LSA TECHNOLOGY


906 101 DPG LSA
60 P
906 102 DPG LSA
120 P
906 103 DPG LSA
220 P

• Earthing system with lightning current


carrying capacity for SPDs and shield
DPG LSA 30 P
906 100
DPG LSA 60 P
906 101
DPG LSA 120 P
906 102

connection DPG LSA 220 P


906 103
0
9

• Integrated mounting frame for LSA


8
7
6

blocks with a grid dimension of 30 mm


5
4
3

• Reserved space for uninterfered


2
1

cabling and surge arresters

DPG LSA is a completely premounted enclosure system with LSA mounting frame and allows opti-
mised use of SPDs and shield connection systems (constant force spring).

DPG LSA 30 P DPG LSA 60 P DPG LSA 120 P DPG LSA 220 P
Carrying capacity of connection components
D1 Total lightning impulse current (10/350 μs) Iimp 15 kA 30 kA 50 kA 50 kA
LSA mounting frame for 1 x 3 blocks 2/10 1 x 6 blocks 2/10 2 x 6 blocks 2/10 2 x 11 blocks 2/10
Grid dimension of mounting frame 30 mm 30 mm 30 mm 30 mm
Wirings 1 pc(s). 2 pc(s). 2 pc(s). 3 pc(s).
Cable entries top / bottom top / bottom top / bottom top / bottom
Cable rail top / bottom top / bottom top / bottom top / bottom
Lock yes yes yes yes
For mounting on wall wall wall wall
Degree of protection IP 40 IP 40 IP 40 IP 40
Earthing via earthing block earthing block earthing block earthing block
Dimension W x H x D 240 x 260 x 130 mm 240 x 350 x 130 mm 330 x 350 x 130 mm 330 x 500 x 130 mm
Enclosure material steel plate steel plate steel plate steel plate
Colour RAL 9002 RAL 9002 RAL 9002 RAL 9002

Ordering information
Type DPG LSA 30 P DPG LSA 60 P DPG LSA 120 P DPG LSA 220 P
Part No. 906 100 906 101 906 102 906 103
Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHN Enclosure for Equipotential Bonding Accessory Part for DEHN Enclosure for Equipotential Bonding
919 030
9M SW
SKB 19

Self-bonding rubber tape


919 031
10 V2A
919 032
15 V2A
919 033
SA KRF

SA KRF

SA KRF
Constant force spring
22 V2A

Reel with 9 m self-bonding rubber tape for wrapping around constant 919 034
29 V2A
919 035
37 V2A
SA KRF

SA KRF
Constant force springs allow solderless shield connections for equipo-
SKB 19 9M SW
Selfbonding Rubber Tape 919 030
force springs for permanent corrosion protection. SA KRF 10 V2A
Force Spring for shield connection
SA KRF 15 V2A
Contact
919 031
Contact
tential bonding or lightning equipotential bonding. They can be instal-
PU Part
Force Spring for shield connection
SA KRF 22 V2A
Force Spring for shield connection
SA KRF 29 V2A
919 032
Contact
919 033
Contact
led subsequently without interrupting the conductor shield or requiring
tools for installation. Approved for nuclear installations according to
Force Spring for shield connection 919 034
SA KRF 37 V2A Contact
Type pc(s). No. Force Spring for shield connection 919 035

SKB 19 9M SW 1 919 030 TÜV Certificate No. T12-04-ETL003 (TÜV = German Technical
Inspectorate).
PU Part
Type Clamping range Material pc(s). No.
SA KRF 10 V2A 4 - 10 mm StSt 20 919 031
SA KRF 15 V2A 9 - 15 mm StSt 20 919 032
SA KRF 22 V2A 14 - 22 mm StSt 20 919 033
SA KRF 29 V2A 18.5 - 29 mm StSt 10 919 034
SA KRF 37 V2A 23.5 - 37 mm StSt 10 919 035

242 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Accessories for LSA Technology
SPDs FOR LSA TECHNOLOGY

• Proven quality

0
9
8
• 45° angled blades in the contact for a lower

7
6
5
cross-sectional variation in the conductor

4
3
2
1
– Enhanced stability of the conductor
– Enhanced corrosion resistance
• Further accessories available on request

The IDC method is used for installing many lines quickly and economical- After using wires with a diameter of 0.65 mm, rewiring to smaller diam-
ly. This method is commonly used in telecommunications (e.g. Deutsche eters is no longer possible.
Telekom AG).
The blocks are suitable for connecting plastic-insulated wires with copper
conductor material:
Conductor diameter: 0.4-0.8 mm
Outer diameter: 0.7-1.5 mm

Monuting frame for 10 LSA blocks, type series 2/10. Total width: 104.5 mm Mounting frame
MB2 10 LSA
907 995 MB2 10
LSA

Ordering information
Type MB2 10 LSA
MB2 10 LSA
Frame 10 DA LSA-PLUS
Mounting
907 995
Part No. 907 995
Packing unit 1 pc(s).

Insertion tools with sensor for LSA technology for connecting the wires and simultaneously cutting Insertion tools
residual lengths. With extractor hook and unlatching blade.
907 994 AW2 LSA

AW2 LSA

Ordering information
AW2 LSA Insertion
Tool LSA-PLUS 907 994

Type AW2 LSA


Part No. 907 994
Packing unit 1 pc(s).

www.dehn.de 243
Accessories for LSA Technology INFORMATION TECHNOLOGY SYSTEMS
SPDs FOR LSA TECHNOLOGY

Terminal block Type series 2 for LSA technology for connecting 10 pairs, each to a non-open termination on the 907 997 AL2 10DA
LSA

cable and routing side. Allows to plug in DPL 10 G3 arresters. Parallel protective circuit only.
0
9
8
7
6
5
4
3

AL2 10DA LSA Terminal


Block 10TC LSA-PLUS 907 997
2
1

AL2 10DA LSA


Enclosure material PBT
Test standards DIN 47608-1, -2
IPC terminal for solid conductor diameters 0.40 - 0.80 mm
Outer diameter via insulation of IPC terminal 0.70 - 1.50 mm
Contacting frequency ) 0.65 conductor diameter > 50 x
Contacting frequency 0.8 conductor diameter ) 50 x
Contact material special brass
Contact surface silver
Flame protection UL 94 V-0
Insulation resistance 5 x 10.000 mohms
Volume resistance of IPC terminal < 10 mohms
Electric strength 2 kV / 50 Hz

Ordering information
Type AL2 10DA LSA
Part No. 907 997
Packing unit 1 pc(s).

Disconnection block Type series 2 for LSA technology for connecting 10 pairs, each on the cable and routing side. By
plugging in DRL, the protection is serially provided between the disconnection contacts. Allows also 907 996
LSA
TL2 10DA

for plugging in DPL 10 G3 arresters.

TL2 10DA LSA TL2 10DA LSA


Disconnection Modules 10 TC LSA-PLUS 907 996

Enclosure material PBT


Test standards DIN 47608-1, -2
Standards, Certifications corresponds to DTAG TS 0272/96
IPC terminal for solid conductor diameters 0.40 - 0.80 mm
Outer diameter via insulation of IPC terminal 0.70 - 1.50 mm
Contacting frequency ) 0.65 conductor diameter > 50 x
Contacting frequency 0.8 conductor diameter ) 50 x
Contact material special brass
Contact surface silver
Flame protection UL 94 V-0
Insulation resistance 5 x 10.000 mohms
Volume resistance of IPC terminal < 10 mohms
Electric strength 2 kV / 50 Hz

Ordering information
Type TL2 10DA LSA
Part No. 907 996
Packing unit 1 pc(s).

Earth conductor block Type series 2 for LSA technology for connecting 38 earth wires or shields.
907 993 EL2 38EA
LSA

EL2 38EA LSA

Ordering information
EL2 38EA LSA Earth

Type EL2 38EA LSA Conductor Block, 38-pole LSA-PLUS 907 993

Part No. 907 993


Packing unit 1 pc(s).

244 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Accessories for LSA Technology
SPDs FOR LSA TECHNOLOGY

Routing module with LSA spring-loaded terminal

0
9
907 991 TL2 10DA

for disconnection blocks


CC

8
7
6
5
4
3
2
1
TL2 10DA CC
907 991

Dimension drawing • Optional connection to LSA or spring-


loaded terminals
• Routing of different wire diameters
DIN rail mounted routing module for disconnection blocks with LSA disconnection block of type • DRL adapted to DIN rail systems
series 2/10 as well as spring-loaded terminals for variable wire connection. DPL and DEHNrapid
LSA surge arresters can be plugged into the routing module.

TL2 10DA CC
Carrying capacity of connection components
D1 Total lightning impulse current (10/350 μs) Iimp 5 kA
Operating temperature range -40°C...+80°C
Degree of protection IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input / output spring or LSA / spring or LSA
Cross-sectional area of spring terminal, solid 0.08 mm2 - 2.5 mm2
Cross-sectional area of spring terminal, flexible 0.08 mm2 - 2.5 mm2
Earthing via DIN rail / flat connector 6.3 mm
Enclosure material PA / PBT
IPC terminal for solid conductor diameters 0.40 - 0.80 mm
Outer diameter via insulation of IPC terminal 0.70 - 1.60 mm
Volume resistance of IPC terminal < 10 mohms

Ordering information
Type TL2 10DA CC
Part No. 907 991
Packing unit 1 pc(s).

www.dehn.de 245
INFORMATION TECHNOLOGY SYSTEMS
SPDs FOR LSA TECHNOLOGY
0
9
8
7
6
5
4
3
2
1

246 www.dehn.de
1 2 3 4 5 6 7 8 9 0

INFORMATION TECHNOLOGY SYSTEMS NET Protector


SPDs FOR 482.6 MM (19 INCH) DATA CABINETS Surge arrester

• Protects switches, HUBs and telecommunica-


tion systems
• Allows for class D according to EN 50173
(Gigabit Ethernet)
• Patch panels allow for flexible equipment
• Retrofit versions with plug-in inputs and out-
puts

The 482.6 mm (19 inch) enclosure can be supplied with surge protective
boards for protecting network components (class D) or telecommunica-
tion systems.

The 482.6 mm (19 inch) enclosure can be equipped with up to 3 surge The NET Protector surge arresters require the space of only one vertical
protection boards to protect active network components such as HUBs, module and are generally installed in terminal boards. They are inserted
switches (class D) or telecommunication systems. Typical applications: as a patch panel with surge protection or as a retrofit version for patch-
Ethernet, Token Ring, E1 and telephones. ing between the patch panel and the device to be protected.

b
9

7
4
a
7
33

c 8

c
1

Assembly drawing

NET PRO is modular in design. The empty enclosure can be optionally


equipped with 1, 2 or 3 surge protective panels.

GHMT Certificate
The fully shielded 482.6 mm (19 inch) enclosure and its 4TP
circuit board allow class D networks to be established. This
has been confirmed by the independent GHMT test institute.

www.dehn.de 247
1 2 3 4 5 6 7 8 9 0

NET Protector INFORMATION TECHNOLOGY SYSTEMS


Surge arrester SPDs FOR 482.6 MM (19 INCH) DATA CABINETS

protected protected The protective boards do not only provide a


patch cable patch cable different protective circuit, but also a different
connection. While the protected output is
NET PRO ... LSA active component NET PRO active component
always an RJ45 unit, the input can be an IDC
terminal or RJ45 unit. The IDC terminal is
often used for the first equipment in a new
EBB min. EBB min.
2.5 mm2
installation, which does not include any patch
2.5 mm2 panel. The RJ45 unit is a retrofit version for
existing systems and it is patched easily be-
tween the patch panel and the active compo-
NET PRO ... LSA patch panel nent.
patch cable
active component
19" distribution board NET PRO

protected active component


EBB min.
patch cable
2.5 mm2 19" distribution board
min. protected cable
EBB
2.5 mm2

LSA type as patch panel (left) / retrofit version (right)

248 www.dehn.de
1 2 3 4 5 6 7 8 9 0

INFORMATION TECHNOLOGY SYSTEMS NET Protector


929 035 NET PRO
4TP

SPDs FOR 482.6 MM (19 INCH) DATA CABINETS NET PRO 4TP
929 036 NET PRO
LSA 4TP
929 037 NET PRO
4TP 30

NET PRO 4TP NET-


Protector 4TP 929 035 1 1
NET PRO LSA 4TP NET-
Protector/LSA-PLUS/4TP 929 036
NET PRO 4TP 30 NET-
Protector 4TP 30 929 037

2 2
3 3

6 6
4 4

5 5
7 7

8 8

Dimension drawing NET PRO 4TP Surge protection for all pairs due to low • GHMT certificate for class D channel
capacitance diode matrix for each pair. link
• Low protection level for all lines
Surge protective board fitted with 8-way shielded ports for universal cablings (class D). For univer- • For installation in conformity with the
sal use as all 4 pairs (4 TP) are protected. To be installed into EG NET PRO 19“ and mounted into lightning protection zones concept at
distribution cabinets as a patch panel or retrofit version. the boundaries from 1 – 2 and higher

NET PRO 4TP NET PRO LSA 4TP NET PRO 4TP 30
SPD class W W [
Nominal voltage UN 5V 5V 24 V
Max. continuous operating d.c. voltage Uc 6V 6V 30 V
Max. continuous operating a.c. voltage Uc 4.2 V 4.2 V 21.1 V
Nominal current IL 100 mA 100 mA 100 mA
C2 Nominal discharge current (8/20 μs) per port In 2.4 kA 2.4 kA 0.8 kA
C2 Nominal discharge current (8/20 μs) per line In 0.3 kA 0.3 kA 0.1 kA
Voltage protection level line-line for In C2 Up ) 35 V ) 35 V ) 60 V
Voltage protection level line-PG for In C2 Up ) 35 V ) 35 V ) 60 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 13 V ) 13 V ) 40 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 13 V ) 13 V ) 40 V
Cut-off frequency line-line at 100 ohms fG 165 MHz 170 MHz 300 MHz
Insertion loss at 100 MHz < 0.4 dB < 0.3 dB < 0.4 dB
Capacitance line-line C ) 35 pF ) 35 pF ) 16 pF
Capacitance line-PG C ) 50 pF ) 50 pF ) 20 pF
Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C
Degree of protection IP 00 IP 00 IP 00
For installation into enclosure enclosure enclosure
Connection input/output RJ45 shielded / RJ45 shielded LSA / RJ45 shielded RJ45 shielded / RJ45 shielded
Pinning 1/2, 3/6, 4/5, 7/8 1/2, 3/6, 4/5, 7/8 1/2, 3/6, 4/5, 7/8
Earthing via enclosure enclosure enclosure
Dimension W x L 135 x 77 mm 135 x 107 mm 135 x 77 mm
Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21
Approvals, Certifications Class D, GOST GOST GOST

Ordering information
Type NET PRO 4TP NET PRO LSA 4TP NET PRO 4TP 30
Part No. 929 035 929 036 929 037
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for NET Protector


482.6 mm (19 Inch) Enclosure 929 034
PRO 19”
EG NET

Fully shielded empty enclosure for max. 3 NET Protector protective


boards. EG NET PRO 19”
929 034

Type EG NET PRO 19”


Capacity 1 vertical module
Enclosure material stainless steel front / galvanised sheet metal
PU Part
Type pc(s). No.
EG NET PRO 19” 1 929 034

www.dehn.de 249
1 2 3 4 5 6 7 8 9 0

NET Protector INFORMATION TECHNOLOGY SYSTEMS


929 071 NET PRO
TC 2

NET PRO TC SPDs FOR 482.6 MM (19 INCH) DATA CABINETS


929 072 NET PRO
TC 2 LSA

NET PRO TC 2 NET-


Protector TC 2, 110 V 929 071
NET PRO TC 2 LSA NET-

4 4 Protector TC 2 LSA,+B433 110 V 929 072

5 5

3 3

6 6

• Patch panel or retrofit version PTC thermistors decouple the protective stages and Dimension drawing NET PRO TC
thus provide additional protection against “power
• Protection against power crossing crossings“ for terminal equipment.
integrated
• For installation in conformity with the Protective board fitted with 8-way unshielded ports for protection against surges and a.c. interfer-
lightning protection zones concept at ences, for protecting telecommunication systems with analogue or system transmission technology.
the boundaries from 0B – 2 and higher For installation into EG NET PRO 19“ as retrofit or patch panel version (LSA).

NET PRO TC 2 NET PRO TC 2 LSA


SPD class R R
Nominal voltage UN 130 V 130 V
Max. continuous operating d.c. voltage Uc 170 V 170 V
Max. continuous operating a.c. voltage Uc 120 V 120 V
Nominal current IL 150 mA 150 mA
C2 Nominal discharge current (8/20 μs) per port In 10 kA 20 kA
C2 Nominal discharge current (8/20 μs) per line In 2.5 kA 5 kA
Voltage protection level line-line for In C2 Up ) 250 V ) 275 V
Voltage protection level line-PG for In C2 Up ) 600 V ) 600 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 230 V ) 230 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 600 V ) 600 V
Series impedance per line 10 ohms 10 ohms
Cut-off frequency line-line fG 10 MHz 10 MHz
Capacitance line-line C ) 300 pF 300 pF
Capacitance line-PG C ) 15 pF 15 pF
Operating temperature range -40°C...+80°C -40°C...+80°C
Degree of protection IP 00 IP 00
For installation into enclosure enclosure
Connection input/output RJ45 / RJ45 LSA / RJ45
Pinning 4/5, 3/6 4/5, 3/6
Earthing via enclosure enclosure
Dimension W x L 135 x 77 mm 135 x 107 mm
Test standards IEC 61643-21 IEC 61643-21
Approvals, Certifications GOST GOST

Ordering information
Type NET PRO TC 2 NET PRO TC 2 LSA
Part No. 929 071 929 072
Packing unit 1 pc(s). 1 pc(s).

Accessory Part for NET Protector


929 034
PRO 19”
EG NET

482.6 mm (19 Inch) Enclosure


Fully shielded empty enclosure for max. 3 NET Protector protective
EG NET PRO 19”
929 034
boards.
Type EG NET PRO 19”
Capacity 1 vertical module
Enclosure material stainless steel front / galvanised sheet metal
PU Part
Type pc(s). No.
EG NET PRO 19” 1 929 034

250 www.dehn.de
1 2 3 4 5 6 7 8 9 0

INFORMATION TECHNOLOGY SYSTEMS NET Protector


929 075 NET PRO
E1 LSA G703

SPDs FOR 482.6 MM (19 INCH) DATA CABINETS NET PRO E1 LSA

NET PRO E1 LSA G703


929 075

1 1

2 2

4 4

5 5

Dimension drawing NET PRO E1 LSA Energy-coordinated 2-pair protective circuit for E1 • Patch panel version
interfaces
• Corresponds to G.703 specification
• For installation in conformity with the
Surge protective board, patch panel version, fitted with 8-way unshielded ports for E1 interfaces. lightning protection zones concept at
Installation into EG NET PRO 19“ and mounting in distribution boards upstream of the telecom- the boundaries from 0B – 2 and higher
munication system. For 2 MBit/s transmissions according to G.703.

NET PRO E1 LSA G703


SPD class T
Nominal voltage UN 5V
Max. continuous operating d.c. voltage Uc 6V
Max. continuous operating a.c. voltage Uc 4.2 V
Nominal current IL 200 mA
C2 Nominal discharge current (8/20 μs) per port In 20 kA
C2 Nominal discharge current (8/20 μs) per line In 5 kA
Voltage protection level line-line for In C2 Up ) 40 V
Voltage protection level line-PG for In C2 Up ) 500 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 15 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 450 V
Series impedance per line 1 ohm
Cut-off frequency line-line at 100 ohms fG 210 MHz
Capacitance line-line C ) 20 pF
Capacitance line-PG C ) 25 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 00
For installation into enclosure
Connection input/output LSA / RJ45 socket
Pinning 1/2, 4/5
Earthing via enclosure
Dimension W x L 135 x 108 mm
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type NET PRO E1 LSA G703
Part No. 929 075
Packing unit 1 pc(s).

Accessory Part for NET Protector


482.6 mm (19 Inch) Enclosure 929 034
PRO 19”
EG NET

Fully shielded empty enclosure for max. 3 NET Protector protective


boards. EG NET PRO 19”
929 034

Type EG NET PRO 19”


Capacity 1 vertical module
Enclosure material stainless steel front / galvanised sheet metal
PU Part
Type pc(s). No.
EG NET PRO 19” 1 929 034

www.dehn.de 251
1 2 3 4 5 6 7 8 9 0

NET Protector INFORMATION TECHNOLOGY SYSTEMS


929 230 NET PRO 10X TC1 RST

NET PRO 10X TC1 RST SPDs FOR 482.6 MM (19 INCH) DATA CABINETS
available from May 2010

NEW NET PRO 10X TC1 RST


929 230

a 4

b 5
RJ45

• Particularly compact design Basic circuit diagram per pair Dimension drawing NET PRO 10X TC1 RST
• Power crossing protection integrated
• Installation in conformity with the Protective board with 10 ports for protecting telecommunications systems with analogue or sys-
lightning protection zones concept at tem transmission against overvoltage and a.c. interference.
the boundaries from 0B – 2 and higher Input equipped with cage spring terminals which can be removed from the PCB as a block. This
allows to test the lines. For installation into EG NET PRO 10X 19" or EG NET PRO 10X. Enclosure
for 3 vertical modules.

NET PRO 10X TC1 RST


SPD class R
Nominal voltage UN 180 V
Max. continuous operating d.c. voltage Uc 180 V
Max. continuous operating a.c. voltage Uc 120 V
Nominal current at 20°C / 50°C / 70°C IL 120 mA / 100 mA / 60 mA
C2 Nominal discharge current (8/20 μs) per port In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 5 kA
Voltage protection level line-line for In C2 Up ) 300 V
Voltage protection level line-PG for In C2 Up ) 600 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 250 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 500 V
Series impedance per line 3 ohms to 12 ohms
Cut-off frequency at 100 ohms fG 40 MHz
Capacitance line-line C ) 70 pF
Capacitance line-PG C ) 30 pF
Operating temperature range -40°C...+70°C
Degree of protection IP 00
For installation into enclosure
Connection type input/output plug-in spring terminal / RJ45
Pinning 4/5
Earthing via enclosure
Dimension W x L 90 x 76 mm
Test standards IEC 61643-21

Ordering information
Type NET PRO 10X TC1 RST
Part No. 929 230
Packing unit 1 pc(s).

Accessory Part for NET Protector Accessory Part for NET Protector
929 234
PRO 10X 19”
EG NET

Unshielded 482.6 mm (19 Inch) Enclosure 929 235


PRO 10X 3HE
EG NET

Enclosure 482,6 mm (19 inches), 3 vertical modules


Unshielded 19 inch enclosure with a capacity of 5 NET PRO 10X verti- Unshielded 19 inch enclosure for vertical installation. 3 vertical modu-
EG NET PRO 10X 19”
929 234
cal modules, two earth connections and cable anchoring rail. EG NET PRO 10X 3HE
929 235
les for the insertion of a NET PRO 10X, with earth connection.
Accessories: two nuts, two flat washers and two toothed lock washers Accessories: nut, flat washer, toothed lock washer for installing the
for installing the earth connection. NEW earth connection.
Type EG NET PRO 10X 19” Type EG NET PRO 10X 3HE
NEW Capacity 1 vertical module Capacity 1 vertical module
Enclosure material StSt (V2A) Enclosure material StSt (V2A)
PU Part PU Part
Type pc(s). No. Type pc(s). No.
EG NET PRO 10X 19” 1 929 234 EG NET PRO 10X 3HE 1 929 235

252 www.dehn.de
1 2 3 4 5 6 7 8 9 0

INFORMATION TECHNOLOGY SYSTEMS DEHNpatch


SPDs FOR RJ CONNECTION Surge arrester

• Patch cable with built-in surge protection


• Cat. 6 according to ISO/IEC 11801
• For universal use up to 48 V
• Easy to retrofit

DEHNpatch is the first Cat. 6 certified patch cable with built-in surge pro-
tection that can be used universally according to EN 50173 for voltages
up to 48 V d.c.

Designed as a patch cable, DEHNpatch is easy to install. The unit is equal- Category 6 and can be universally used for all data services up to nomi-
ly suited for use in new installations or retrofitting into existing installa- nal voltages of 48 V. It is equally applicable to existing services in offices
tions at any time with little effort. and industrial environments such as Gigabit Ethernet, ATM or ISDN as
DEHNpatch is simply plugged in between the patch panel and the active well as future systems such as Voice over IP and Power over Ethernet.
component (a switch for example) instead of the conventional patch Thanks to its fully shielded design, DEHNpatch can be used in shielded
cable. The snap-in mechanism of the supporting foot allows the device to and unshielded networks. Its width is similar to that of an RJ45 socket
be safely earthed via the DIN rail. For single applications, a section of DIN thus allowing up to 24 devices to be installed in one series and integrat-
rail and a fixing device are included as a standard while for multiple appli- ed into a 19” rack.
cations in 19“ distribution boards an optional DEHNpatch mounting set DEHNpatch is supplied with a standard patch cable length of 3 m and 5 m
is available as an accessory. DEHNpatch fulfils the requirements of (other lengths available on request).

GHMT Certificate DPA M CAT6 RJ45S 48 GHMT Certificate DPA M CAT6 RJ45H 48

www.dehn.de 253
1 2 3 4 5 6 7 8 9 0

DEHNpatch INFORMATION TECHNOLOGY SYSTEMS


929 100 DPA M
CAT6 RJ45S 48

DPA M CAT6 SPDs FOR RJ CONNECTION


929 110 DPA M
CAT6 RJ45H 48

DPA M CAT6 RJ45S 48 Patch


cable with surge protection 929 100
DPA M CAT6 RJ45H 48 Patch
cable with surge protection 929 110

1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8

• Ideally suited for retrofitting, protec- Protection of all pairs due to heavy-duty gas dis- Dimension drawing DPA M CAT6 RJ45S 48
tion of all lines charge tubes and an adapted filter matrix per pair.

• Cat. 6 according to ISO/IEC 118001


• For installation in conformity with the Universal SPD ideal for use as a patch cable in Ethernet and similar applications in universally struc-
lightning protection zones concept at tured cabling systems. Certified according to Category 6 and class E. Fully shielded.
the boundaries from 0B – 2 and higher

DPA M CAT6 RJ45S 48 DPA M CAT6 RJ45H 48


SPD class T T
Nominal voltage UN 48 V 48 V
Max. continuous operating d.c. voltage Uc 48 V 48 V
Max. continuous operating a.c. voltage Uc 34 V 34 V
Nominal current IL 1A 1A
C2 Nominal discharge current (8/20 μs) line-line In 150 A 150 A
C2 Total nominal discharge current (8/20 μs) line-PG In 10 kA 10 kA
C2 Nominal discharge current (8/20 μs) line-PG In 2.5 kA 2.5 kA
Voltage protection level line-line for In C2 UP ) 190 V ) 190 V
Voltage protection level line-PG for In C2 UP ) 600 V ) 600 V
Voltage protection level line-line at 1 kV/μs C3 UP ) 145 V ) 145 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 500 V ) 500 V
Insertion loss at 250 MHz ) 2 dB ) 3 dB
Capacitance line-line C ) 165 pF ) 250 pF
Capacitance line-PG C ) 255 pF ) 400 pF
Operating temperature range -20°C ...+60°C -20°C ...+60°C
Degree of protection IP 20 IP 20
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Connection input/output RJ45 connecting lead / RJ45 connecting lead RJ45 connecting lead / RJ45 connecting lead
Pinning 1/2, 3/6, 4/5, 7/8 1/2, 3/6, 4/5, 7/8
Connecting lead Cat. 6, L1 = approx. 0.5 m, L2 = approx. 3 m Cat. 6, L1 = approx. 1 m, L2 = approx. 5 m
Connector Stewart 39 series Hirose TM 21P
Earthing via 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material zinc die casting zinc die casting
Colour bare bare
Test standards IEC 61643-21 IEC 61643-21
Approvals, Certifications Cat. 6 acc. to ISO/IEC 11801, GOST Cat. 6 acc. to ISO/IEC 11801, GOST
Accessories fixing material fixing material

Ordering information
Type DPA M CAT6 RJ45S 48 DPA M CAT6 RJ45H 48
Part No. 929 100 929 110
Packing unit 1 pc(s). 1 pc(s).

Mounting set for DEHNpatch 929 199 MS DPA

The set comprises a DIN rail for up to 24 DEHNpatch devices and different MS DPA
Set for DEHNpatch
Mounting
929 199

distance bolts with sliding nuts for installation into data distributors. The
DIN rail can be mounted in a space-saving way at the panel of the distri-
butor or even in front of the mounting stations according to a 19” grid.
PU Part
Type pc(s). No.
MS DPA 1 929 199

254 www.dehn.de
1 2 3 4 5 6 7 8 9 0

INFORMATION TECHNOLOGY SYSTEMS DEHNpatch


929 121 DPA M
CLE RJ45B 48

SPDs FOR RJ CONNECTION DEHNpatch Class E

DPA M CLE RJ45B 48


929 121

1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
(1 mod.)

Dimension drawing DPA CLE Protection of all pairs due to heavy-duty gas • Ideally suited for retrofitting, protec-
discharge tubes and an adapted filtering matrix tion of all lines
per pair.
• Cat. 6 in channel (class E)
Universal SPD ideal for use in Industrial Ethernet and similar applications in structured cabling systems • For installation in conformity with the
according to class E up to 250 MHz. Fully shielded adapter with sockets for DIN rail mounting. lightning protection zones concept at
the boundaries from 0B – 2 and higher

DPA M CLE RJ45B 48


SPD class T
Nominal voltage UN 48 V
Max. continuous operating d.c. voltage Uc 48 V
Max. continuous operating a.c. voltage Uc 34 V
Nominal current IL 1A
C2 Nominal discharge current (8/20 μs) line-line In 150 A
C2 Total nominal discharge current (8/20 μs) line-PG In 10 kA
Voltage protection level line-line at 1 kV/μs C3 UP ) 180 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 500 V
Capacitance line-line C ) 30 pF
Capacitance line-PG C ) 25 pF
Operating temperature range -40°C ...+80°C
Degree of protection IP 10
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output RJ45 socket / RJ45 socket
Pinning 1/2, 3/6, 4/5, 7/8
Earthing via 35 mm DIN rail acc. to EN 60715
Enclosure material zinc die casting
Colour bare
Test standards IEC 61643-21
Approvals, Certifications GOST
Accessories fixing material

Ordering information
Type DPA M CLE RJ45B 48
Part No. 929 121
Packing unit 1 pc(s).

Mounting set for DEHNpatch 929 199 MS DPA

The set comprises a DIN rail for up to 24 DEHNpatch devices and different MS DPA
Set for DEHNpatch
Mounting
929 199

distance bolts with sliding nuts for installation into data distributors. The
DIN rail can be mounted in a space-saving way at the panel of the distri-
butor or even in front of the mounting stations according to a 19” grid.
PU Part
Type pc(s). No.
MS DPA 1 929 199

www.dehn.de 255
1 2 3 4 5 6 7 8 9 0

BLITZDUCTOR® VT INFORMATION TECHNOLOGY SYSTEMS


Surge arrester SPDs FOR RJ CONNECTION

• Ideally suited for DIN rail mounted modems or


gateways
• Ease of installation due to RJ sockets
• Adaptable to the environment of the installa-
tion with additional screw terminals

DIN rail mounted surge arrester for telecommunications terminal devices


and telephone systems with RJ connector.

DIN rail mounted surge arrester for telecommunications terminal devices tions upstream of residential gateways (TK/EiB interface) or for protecting
and telephone systems with RJ connector. They are often used in installa- industrial DIN rail mounted modems.

RJ sockets and screw terminals at the The DIN rail mounted SPD was developed
input and output of BVT TC 1 surge for installation-friendly protection of the
arresters allow for universal use, e.g. for S0 input of residential gateways. The inte-
installation upstream of NTBAs with grated distribution function at the pro-
screw wiring or screw/plug-in connection tected output allows wiring of two pro-
upstream of modems and telecommuni- tected outgoing ISDN bus circuits.
cation systems.

BLITZDUCTOR VT TC1 BLITZDUCTOR VT ISDN

256 www.dehn.de
1 2 3 4 5 6 7 8 9 0

INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® VT


918 410 BVT ISDN

SPDs FOR RJ CONNECTION BVT ISDN

BVT ISDN BLITZ- 3 3


DUCTOR VT 918 410

6 6
IN OUT
4 4

5 5
a2
a1
b1
b2

Dimension drawing BVT ISDN Energy-coordinated ISDN 4-wire protective circuit • RJ45 sockets
with additional protection for the remote power
supply. • Additional screw terminals for the
ISDN lines
For ISDN S0 buses with RJ45 connections. The additional screw terminal connection at the protect- • For installation in conformity with the
ed output allows for double wiring of the S0 bus (distribution function). lightning protection zones concept at
the boundaries from 0B – 2 and higher

BVT ISDN
SPD class Q
Nominal voltage UN 5V
Nominal voltage pa-pa UN 40 V
Max. continuous operating d.c. voltage UC 7.5 V
Max. continuous operating d.c. voltage pa-pa UC 60 V
Nominal current IL 200 mA
C2 Total nominal discharge current (8/20 μs) In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 2.5 kA
Voltage protection level line-line for In C2 Up ) 30 V
Voltage protection level line-PG for In C2 Up ) 600 V
Voltage protection level pa-pa for In C2 Up ) 130 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 17 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 600 V
Voltage protection level pa-pa at 1 kV/μs C3 Up ) 100 V
Series impedance per line 1.0 ohm
Cut-off frequency line-line fG 1.7 MHz
Capacitance line-line C ) 3.3 nF
Capacitance line-PG C ) 15 pF
Capacitance pa-pa C ) 600 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 10
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output RJ45 / RJ45 or terminals
Pinning 3/6, 4/5
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Earthing via terminal
Enclosure material thermoplastic, UL 94 V-0
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type BVT ISDN
Part No. 918 410
Packing unit 1 pc(s).

www.dehn.de 257
1 2 3 4 5 6 7 8 9 0

BLITZDUCTOR® VT INFORMATION TECHNOLOGY SYSTEMS


918 411 BVT TC 1

BVT TC SPDs FOR RJ CONNECTION

BVT TC 1 BLITZ-
DUCTOR VT 918 411

4 4

IN OUT

5 5

a1 a1
b1 b1

• RJ sockets, compatible with RJ12 pins Energy-coordinated protective circuit, no leakage Dimension drawing BVT TC
currents to earth.
• Additional screw terminals for a/b
lines
• For installation in conformity with the For a/b lines, ISDN Uk0 or ADSL with RJ45 connections and additional screw terminal connections.
lightning protection zones concept at Pinning of the RJ45 sockets is compatible with RJ11/12. The parallel screw terminals are more
the boundaries from 0B – 2 and higher robust than the RJ45 sockets and increase In to 10 kA.

BVT TC 1
SPD class R
Nominal voltage UN 130 V
Max. continuous operating d.c. voltage UC 170 V
Nominal current IL 200 mA
C2 Total nominal discharge current (8/20 μs) In 5 kA
C2 Nominal discharge current (8/20 μs) per line In 2.5 kA
Voltage protection level line-line for In C2 Up ) 275 V
Voltage protection level line-PG for In C2 Up ) 600 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 240 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 600 V
Series impedance per line 4.7 ohms
Cut-off frequency line-line fG 17 MHz
Capacitance line-line C ) 300 pF
Capacitance line-PG C ) 15 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 10
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output RJ45 or terminals / RJ45 or terminals
Pinning 4/5
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Earthing via screw terminal
Enclosure material thermoplastic, UL 94 V-0
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type BVT TC 1
Part No. 918 411
Packing unit 1 pc(s).

258 www.dehn.de
1 2 3 4 5 6 7 8 9 0

INFORMATION TECHNOLOGY SYSTEMS DSM TM


SPDs FOR RJ CONNECTION Surge arrester

• Surge arrester for ISDN or Ethernet applica-


tions
• Minimum space required for flush mounting
• Ideal for Touch Manager wave (Residential
Gateway)

Surge arrester for flush mounting used in LAN interfaces.

DSM TM is a surge arrester which is installed close to terminal devices Because of the universal reservation of the pluggable RJ45 output, it can
and designed for Touch Manager wave (Siemens). The SPD is ideally suit- be used for protecting both ISDN S0 and Ethernet 10 BT (class C cabling)
ed for installation into flush-mounted or small-sized distribution boards applications. As screw terminals are available at the input, they can be
and connected to the local equipotential bonding of the terminal device. connected to both rigid and flexible conductors or shields.

A self-adhesive fixing strip and a 4-pole


plug-in distribution terminal are included
in delivery.

Scope of delivery of DSM TM

www.dehn.de 259
1 2 3 4 5 6 7 8 9 0

DSM TM INFORMATION TECHNOLOGY SYSTEMS


924 274 DSM TM

DSM TM SPDs FOR RJ CONNECTION

DSM TM SPD for


Data Sockets 924 274

1
2
a1 3
b1 4
5
a2 6
b2 7
8
SHL

• Indirect shield earthing Low-capacitance design with high discharge Dimension drawing DSM TM
capacity and low protection level between the
• Installation accessories included signal lines.
• For installation in conformity with the
lightning protection zones concept at For IT installations, class C, or services such as Ethernet 10 BT or ISDN S0 interfaces. Transition from
the boundaries from 0B – 2 and higher screw terminal to RJ45 plug. No leakage pickups are generated due to indirect shielding.

DSM TM
SPD class Q
Nominal voltage UN 5V
Max. continuous operating d.c. voltage UC 6V
Max. continuous operating a.c. voltage UC 4.2 V
Nominal current IL 200 mA
C1 Nominal discharge current (8/20 μs) line-line In 500 A
C2 Nominal discharge current (8/20 μs) line-PG In 5 kA
C2 Total nominal discharge current (8/20 μs) line-PG In 10 kA
Voltage protection level line-line for In C1 Up ) 28 V
Voltage protection level line-PG for In C2 UP ) 600 V
Voltage protection level shield-PG for In C2 UP ) 600 V
Voltage protection level line-line at 1 kV/μs C3 UP ) 11 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 380 V
Voltage protection level shield-PG at 1 kV/μs C3 UP ) 600 V
Cut-off frequency fG 55 MHz
Capacitance line-line C ) 75 pF
Capacitance line-PG C ) 20 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Connection input/output screw terminal / RJ45 connecting lead
Pinning Ethernet 1/2, 3/6 or ISDN 4/5, 3/6
Cross-sectional area, solid 0 - 1.0 mm2
Cross-sectional area, flexible 0 - 1.0 mm2
Tightening torque (terminal) 0.3 Nm
Earthing via lead 1.0 mm2
Enclosure material polyamide PA 6.6
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications GOST
Accessories adhesive pad, socket terminal

Ordering information
Type DSM TM
Part No. 924 274
Packing unit 1 pc(s).

260 www.dehn.de
1 2 3 4 5 6 7 8 9 0

INFORMATION TECHNOLOGY SYSTEMS DEHNlink


SPDs FOR RJ CONNECTION Surge arrester

• Surface-mounted surge protective device for


telecommunication systems
• Quick installation due to plug-in terminals
• Different interface-specific types

Surge arrester for telecommunications terminal devices and telephone


systems with RJ plug-in connector for surface mounting.

Surge arrester for surface mounting with a modern design. It protects Compared to conventional devices
especially modems and telephone systems with RJ plug-in connectors. The ( ... ECO), the different SPD units with ...I
plug-in connectors allow for easy installation. type designation have an additional LED
indication of the supply voltage. This
helps to immediately recognise system
failures. Furthermore, they provide a wide
range of accessories such as connecting
cables or fixing material.

Devices with and without oper-


ating state indication

DLI ISDN I can protect two terminal devices at the same time due to the
integrated distribution function. The operating state indicator is only illu-
minated if the NTBA is also connected to the power supply and not in
case of emergency operation (remote supply of telecommunication net-
work operators).

Wiring of DLI ISDN I

LED on OK
State

NT NT The operating state indicator informs on the proper condition of the


device. In the event of a fault, the connections and cables have to be
checked. If no installation fault can be detected, the SPD has been over-
LED off
loaded and has to be replaced.
State ISDN SO Interface Service

Faulty

Operating state indication DLI ISDN I

www.dehn.de 261
1 2 3 4 5 6 7 8 9 0

DEHNlink INFORMATION TECHNOLOGY SYSTEMS


929 024 DLI ISDN I

DLI ISDN I SPDs FOR RJ CONNECTION

3 3 DLI ISDN I DEHNlink


ISDN/I 929 024

6 6

protected
4 4

5 5
3
6
4
5

• 2 protected outputs Energy-coordinated ISDN 4-wire protective circuit Dimension drawing DLI ISDN I
with additional protection and indication of the
• Surge protection and LED indication remote power supply.
for the remote supply included
• For installation in conformity with the
lightning protection zones concept at SPD with two protected ISDN S0 outputs (distribution function) and operating state indication (LED)
the boundaries from 0B – 2 and higher of the remote supply voltage. No indication during emergency operation (supply from telephone
system only). Connecting cable and mounting material included.

DLI ISDN I
SPD class Q
Nominal voltage UN 5V
Nominal voltage pa-pa UN 40 V
Max. continuous operating d.c. voltage Uc 7.5 V
Max. continuous operating a.c. voltage Uc 5.2 V
Max. continuous d.c. voltage pa-pa UC 45 V
Nominal current IL 200 mA
C2 Total nominal discharge current (8/20 μs) In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 2.5 kA
Voltage protection level line-line for In C2 Up ) 30 V
Voltage protection level line-PG for In C2 Up ) 600 V
Voltage protection level pa-pa for In C2 Up ) 180 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 17 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 600 V
Voltage protection level pa-pa at In C2 Up ) 100 V
Series impedance per line 1 ohm
Cut-off frequency line-line 2 MHz
Capacitance line-line C ) 3 nF
Capacitance line-PG C ) 15 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Connection input/output RJ45 / 2 x RJ45
Pinning 3/6, 4/5
Earthing via flat connector 6.3 mm
Enclosure material polyamide PA 6.6
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications GOST
Accessories connecting cable, mounting material

Ordering information
Type DLI ISDN I
Part No. 929 024
Packing unit 1 pc(s).

262 www.dehn.de
1 2 3 4 5 6 7 8 9 0

INFORMATION TECHNOLOGY SYSTEMS DEHNlink


929 028 DLI TC 2 I

SPDs FOR RJ CONNECTION DLI TC I

DLI TC 2 I
TC 2
DEHNlink
929 028
3 3

6 6
protected

4 4

5 5

Dimension drawing DLI TC I 2-stage protective circuit with overcurrent protec- • LED indicates supply voltage
tion and system voltage indication of DLI TC 2 I.
• Protection against power crossing
integrated
• For installation in conformity with the
Protective device for analogue or system telephones with operating state indication (LED). Protects lightning protection zones concept at
even against alternating current interference. Compatible with pins of RJ11/12 plugs. Connecting the boundaries from 0B – 2 and higher
cable and mounting material included.

DLI TC 2 I
SPD class R
Nominal voltage UN 110 V
Max. continuous operating d.c. voltage Uc 170 V
Max. continuous operating a.c. voltage Uc 120 V
Nominal current IL 150 mA
C2 Total nominal discharge current (8/20 μs) In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 2.5 kA
Voltage protection level line-line for In C2 Up ) 250 V
Voltage protection level line-PG for In C2 Up ) 600 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 230 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 600 V
Series impedance per line 10 ohms
Cut-off frequency line-line 10 MHz
Capacitance line-line C ) 0.3 nF
Capacitance line-PG C ) 15 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Connection input/output RJ45 / RJ 45 (compatible with RJ12)
Pinning 3/6, 4/5 (3/4, 2/5 for RJ12)
Earthing via flat connector 6.3 mm
Enclosure material polyamide PA 6.6
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications GOST
Accessories connecting cable, mounting material

Ordering information
Type DLI TC 2 I
Part No. 929 028
Packing unit 1 pc(s).

www.dehn.de 263
1 2 3 4 5 6 7 8 9 0

DEHNlink INFORMATION TECHNOLOGY SYSTEMS


929 081 DLI TC
ECO RJ12

DLI TC SPDs FOR RJ CONNECTION

DLI TC ECO RJ12 DEHNlink-


Denmark 929 081

3 3

protected

4 4

• Economical protection for 1 pair Using a high-capacity varistor makes decoupling Dimension drawing DLI TC
to the gas discharge tube unnecessary.
• Modern design
• For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B – 2 and higher Protective device for analogue or system telephones, RJ12 unit.

DLI TC ECO RJ12


SPD class R
Nominal voltage UN 130 V
Max. continuous operating d.c. voltage Uc 170 V
Max. continuous operating a.c. voltage Uc 120 V
Nominal current IL 200 mA
C2 Total nominal discharge current (8/20 μs) In 5 kA
C2 Nominal discharge current (8/20 μs) per line In 2.5 kA
Voltage protection level line-line for In C2 Up ) 480 V
Voltage protection level line-PG for In C2 Up ) 600 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 280 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 600 V
Cut-off frequency line-line 10 MHz
Capacitance line-line C ) 0.7 nF
Capacitance line-PG C ) 15 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Connection input/output RJ12 / RJ12
Pinning 3/4
Earthing via flat connector 6.3 mm
Enclosure material polyamide PA 6.6
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications GOST
Accessories mounting material

Ordering information
Type DLI TC ECO RJ12
Part No. 929 081
Packing unit 1 pc(s).

264 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNlink TC BT
SPDs FOR BT JACK CONNECTION Surge arrester

• Surface-mountable protective device for tele-


communication systems
• Quick installation due to plug-in terminals
• Device acc. to British Telecom requirements

Surge arrester for telecommunications terminal equipment and telephone


systems with BT plug-in connection for surface mounting.

Surge arrester for telecommunications terminal equipment and telephone between a terminal point of a public telephone installation and any
systems with BT plug-in connection for surface mounting. The device telecommunications terminal equipment. Fulfils BS6651:1992, Appendix C,
meets the requirements of Oftel NS/G/23/L/100005 for connections Category C-High and CCITT K17.

www.dehn.de 265
DEHNlink TC BT INFORMATION TECHNOLOGY SYSTEMS
929 026 DLI TC BT

DLI TC BT SPDs FOR BT JACK CONNECTION

DLI TC BT DEHNlink
BT 929 026
1 1

6 6
2 2

protected
5 5
3 3

4 4

• Device acc. to British Telecom require- Energy-coordinated protective circuit for all pairs, Dimension drawing DLI TC BT
ments free of leakage currents to earth.

• Protection for all lines


• For installation in conformity with the Protective device for analogue or system telephones in accordance with British Telecom require-
lightning protection zones concept at ments. Pluggable terminals for easy installation.
the boundaries from 0B – 2 and higher

DLI TC BT
SPD class R
Nominal voltage UN 130 V
Max. continuous operating d.c. voltage UC 145 V
Nominal current IL 125 mA
C2 Total nominal discharge current (8/20 μs) In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 5 kA
Voltage protection level line-line for In C2 Up ) 210 V
Voltage protection line-PG for In C2 Up ) 550 V
Voltage protection level line-line at 1 kV/μs C3 UP ) 185 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 450 V
Series impedance per line 4.7 ohms
Bandwidth fG 13 MHz
Capacitance line-line C ) 400 pF
Capacitance line-PG C ) 10 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Connection input/output BT jack / BT jack
Pinning 1/6, 2/5, 3/4
Earthing by flat connector 6.3 mm
Enclosure thermoplastic
Colour black
Test standards IEC 61643-21
Accessories connecting cable, mounting material

Ordering information
Type DLI TC BT
Part No. 929 026
Packing unit 1 pc(s).

266 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS UGKF
SPDs FOR COAXIAL CONNECTION Surge arrester

• Plug-in surge protective adapter for easy retro-


fitting
• Integrated indirect shield earthing avoids leak-
age pickups

Surge arrester for use as cable adapter to protect coaxial systems such as
video and camera systems from potential damage.

UGKF BNC surge arresters are shielded devices for plugging into coaxial being influenced by leakage pickups, the cable shield is earthed indirect-
terminal devices or connections. Frequent fields of application are the pro- ly via a gas discharge tube. The SPD inputs are used as sockets and the
tection of outdoor or central video surveillance systems. In order to avoid protected outputs as plugs.

UGKF BNC types DGA BNC VC ...

Devices for protecting video surveillance systems with higher supply volt- DGA BNC VC ... surge arresters of the DEHNgate familiy can be easily
age or with a two-sided socket connection are also available on request. installed on supporting rails.

www.dehn.de 267
UGKF INFORMATION TECHNOLOGY SYSTEMS
929 010 UGKF
BNC

UGKF BNC SPDs FOR COAXIAL CONNECTION

UGKF BNC SPD for


Comupter Systems 929 010

protected

• Easily adaptable Low-capacitance, 2-stage protective circuit with Dimension drawing UGKF BNC
indirect shield earthing to avoid leakage pickups.
• Avoids leakage pickups
• For installation in conformity with the
lightning protection zones concept at UGKF BNC surge arresters are suitable for protecting video cameras and Arcnet with BNC connec-
the boundaries from 0B – 2 and higher tion. Special versions for video cameras with higher nominal voltage available on request.

UGKF BNC
SPD class T
Nominal voltage UN 5V
Max. continuous operating d.c. voltage UC 8V
C2 Nominal discharge current (8/20 µs) per line In 2.5 kA
C2 Nominal discharge current (8/20 µs) shield-PG In 10 kA
Voltage protection level line-shield for In C2 UP ) 25 V
Voltage protection level line-shield at 1 kV/µs C3 UP ) 15 V
Voltage protection level shield-PG at 1 kV/µs C3 Up ) 600 V
Series impedance per line 10 ohms
Cut-off frequency fG 300 MHz
Return loss * 20 dB up to 40 MHz
Connection input/output BNC socket / BNC connector
Earthing via outgoing earth conductor 0.75 mm2
Shield earthing via indirectly by an integrated spark gap
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type UGKF BNC
Part No. 929 010
Packing unit 1 pc(s).

268 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNgate
SPDs FOR COAXIAL CONNECTION Lightning current and surge arrester

• Application-specific SPD designs


• SPD for use in satellite and cable TV systems
with measuring output
• Combined lightning current and surge arrester
with a high discharge capacity and low protec-
tion level
• Contact materials with extremely high
endurance

Lightning current and surge arrester for use as cable adapter to protect
coaxial systems such as CCTV, mobile radio stations and antenna systems
from potential damage.

DEHNgate is a family of lightning current and surge arresters with a cable tions and antenna systems from potential damage. Depending on the
adapter design for protecting coaxial systems such as mobile radio sta- application, different mechanical and electrical types are available.

The coaxial DGA arrester family comes in DGA FF TV can be mounted onto a DIN rail
different designs for different applica- in a space-saving way to protect satellite
tions. Different types of plugs and arrester systems with several outputs. For single
technologies allow for optimised solu- applications such as cable TV, the device
tions. Further types are available on can be simply snapped into a wall-mount-
request. ed adapter. 2 F cable connectors are also
included.
DGA arrester family

The Lambda/4 surge arresters of type Delivery of DGA FF TV


DGA L4 feature an internal coaxial con-
nection of the inner conductor as a band-
pass. Only frequencies within this band If high partial lightning currents can be
are transmitted. For low-frequency coupled into antenna lines or if very high
impulses, such as lightning currents, they transmission performances are required,
cause a short circuit. This makes them the use of Lambda/4 surge arresters is
mechanically very robust and mainte- advisable. If additional remote supply is
nance-free. Due to their low protection needed for the antenna, a combination of
level and high discharge capacity, they a gas discharge tube and Lambda/4 tech-
Principle of Lambda/4 can be used as combined lightning cur- nology (DGA LG) should be used. The
rent and surge arresters. surge arresters are made of top-quality
material and provide excellent endurance.

Spark-gap-based surge arresters have an internal gas-filled surge arrester and can be
defined as a low pass. This also allows for d.c. transmission (antenna supply). Peak volt-
ages exceeding the threshold value of the gas discharge tube are discharged. These surge
arresters provide extensive contact surfaces from the inner conductor to the gas dis- Application of Lambda/4
charge tube. This minimises burn-off of the material during the discharge process and arresters
ensures a constant transmission performance.

Principle of a spark-gap-based SPD

www.dehn.de 269
DEHNgate INFORMATION TECHNOLOGY SYSTEMS
Lightning current and surge arresters SPDs FOR COAXIAL CONNECTION

1 signal test
HF test signal
te

SPD FF TV
DEHNga

24 V
I N 703
U C 2A
No. 909
DG A

5-2400 MHz
TP
-20 dB
ok
5-3000 MHz protected
meter
DEHNgate
DGA FF TV
SPD
No. 909 703
IN 2A
TP = test point
2
UC 24 V

A
KLASSE

CLASS

HF test signal
check
system
te

SPD FF TV
DEHNga

24 V
I N 703
U C 2A
No. 909
DG A

5-2400 MHz
TP
-20 dB
meter
5-3000 MHz protected

DEHNgate
DGA FF TV
SPD
No. 909 703
IN 2A

input UC 24 V

A
protected output
KLASSE

CLASS

The DGA FF TV arrester is the first of its kind


to have an integrated measuring output for
antenna signals allowing the system to be
easily tested.
3
te

SPD FF TV
DEHNga

24 V
I N 703
U C 2A
No. 909
DGA

TP
5-2400 MHz -20 dB

5-3000 MHz protected

DEHNgate
DGA FF TV
SPD
No. 909 703
IN 2A
UC 24 V

A
KLASSE

CLASS

signal test for DGA FF TV

Earthing of the surge arresters is different


according to the various designs. For details,
please see the relevant technical data.

EB
cable length
max. 0.5 m
AWG 6/16 mm2

EB

Earthing of DGA AG N and DGA L ...

270 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNgate
909 710 DGA BNC
VCD

SPDs FOR COAXIAL CONNECTION DGA BNC VC


909 711 DGA BNC
VCID

DGA BNC VCD


909 710
DGA BNC VCID protected
909 711

DGA BNC VCD


Part No. 909 710

(1 mod.)
protected

DGA BNC VCID


Part No. 909 711

Dimension drawing DGA BNC VC ... 2-stage protective circuit with low capacitance. • Easily adaptable due to BNC sockets
DGA BNC VCD with direct shield earthing and
DGA BNC VCID with indirect shield earthing. • Available with direct or indirect shield
earthing, according to type
• For installation in conformity with the
Space-saving surge arrester with BNC socket for mounting on supporting rails for protecting video lightning protection zones concept at
and camera systems. Available with direct (VCD) or indirect shield connection (VCID), according to the boundaries from 0B – 2 and higher
type, to avoid leakage pickups.

DGA BNC VCD DGA BNC VCID


SPD class T T
Nominal voltage UN 5V 5V
Max. continuous operating d.c. voltage UC 6.4 V 6.4 V
Nominal current IL 0.1 A 0.1 A
C2 Nominal discharge current (8/20 µs) shield-PG In 10 kA 10 kA
C2 Nominal discharge current (8/20 µs) In 5 kA 5 kA
C2 Nominal discharge current (8/20 µs) line-shield In 5 kA 5 kA
Voltage protection level line-shield for In C2 Up ) 35 V ) 35 V
Voltage protection level shield-PG for In C2 Up — ) 650 V
Voltage protection level line-shield at 1 kV/µs C3 Up ) 13 V ) 13 V
Voltage protection level shield-PG at 1 kV/µs C3 Up — ) 600 V
Frequency range 0 - 300 MHz 0 - 300 MHz
Insertion loss at 160 MHz ) 0.4 dB at 160 MHz ) 0.4 dB
Return loss at 130 MHz * 20 dB at 130 MHz * 20 dB
Capacitance line-shield C ) 25 pF ) 25 pF
Operating temperature range -40°C...+80°C -40°C...+80°C
Degree of protection IP 10 IP 10
For mounting on 35 mm DIN rail according to EN 60715 35 mm DIN rail according to EN 60715
Connection input/output BNC socket / BNC socket BNC socket / BNC socket
Earthing via 35 mm DIN rail according to EN 60715 35 mm DIN rail according to EN 60715
Enclosure material zinc die casting zinc die casting
Colour bare bare
Test standards IEC 61643-21 IEC 61643-21
Approvals, Certifications GOST GOST

Ordering information
Type DGA BNC VCD DGA BNC VCID
Part No. 909 710 909 711
Packing unit 1 pc(s). 1 pc(s).

www.dehn.de 271
DEHNgate INFORMATION TECHNOLOGY SYSTEMS
909 703 DGA FF
TV

DGA TV SPDs FOR COAXIAL CONNECTION


909 704 DGA GF
TV
909 705 DGA GFF
TV

DGA GFF TV DGA FF TV DGA GF TV


DGA GFF TV DGA FF TV
909 703
DGA GF TV
DEHNgate

909 704
DGA GFF TV
909 705

TP

protected

• Frequency range for analogue and digital DGA GF TV DGA FF TV

TV, also suitable for reverse LAN channels


• SPDs of type FF and GFF with integrated Schematic diagram of the protective circuit of Dimension drawing DGA GFF TV – Combination
measuring output DGA GFF TV consisting of lightning current of DGA GF TV and DGA FF TV
arrester of type DGA GF TV and terminal
• 3 types for adapted use for installation in equipment protection DGA FF TV.
conformity with the lightning protection
zones concept at the boundaries from DGA ... TV are SPDs with F connector for remote supply for 75 ohm satellite and cable TV systems.
0A – 2 (combined lightning current The SPDs fulfil the high shielding requirements of class A according to EN 50083-2. They allow for
and surge arresters of type GFF), space-saving installation into all common TV and satellite applications and are available as light-
0A – 1 (lightning current arresters of ning current arresters, surge arresters as well as combined lightning current and surge arresters
type GF) with integrated measuring output for testing installations.
1 – 2 (surge arresters of type FF)

DGA FF TV DGA GF TV DGA GFF TV


SPD class _ H H_
Max. continuous operating d.c. voltage UC 24 V 60 V 24 V
Nominal current IL 2A 2A 2A
D1 Lightning impulse current (10/350 µs) Iimp 0.2 kA 2.5 kA 2.5 kA
C2 Nominal discharge current (8/20 µs) In 1.5 kA 10 kA 10 kA
Voltage protection level for Iimp D1 UP ) 230 V ) 700 V ) 230 V
Voltage protection level for In C2 UP ) 300 V ) 700 V ) 300 V
Voltage protection level at 1 kV/µs C3 UP ) 60 V ) 600 V ) 60 V
Frequency range d.c., 5-3000 MHz d.c. - 2400 MHz d.c., 5-2400 MHz
Insertion loss — 0.5 dB —
Insertion loss 5 - 862 MHz 1.2 dB — 1.7 dB
Insertion loss 862 - 2400 MHz 1.4 dB — 1.9 dB
Insertion loss 2400 - 3000 MHz 2 dB — —
Return loss * 14 dB * 18 dB (-1.5 dB/octave) dB —
Return loss (5 - 8 MHz) — — * 10 dB
Return loss (8 - 47 MHz) — — * 14 dB
Return loss (47 - 2400 MHz) * 18 dB (-1.5 dB/octave) — * 18 dB (-1.5 dB/octave)
Return loss test socket (5 - 47 MHz) * 18 dB — * 18 dB
Test socket connection loss 20 dB — 20 dB
Shield attenuation 5 - 300 MHz * 85 dB * 85 dB * 85 dB
Shield attenuation 300 - 470 MHz * 80 dB * 80 dB * 80 dB
Shield attenuation 470 - 1000 MHz * 75 dB * 75 dB * 75 dB
Shield attenuation 1000 - 2400 MHz * 55 dB * 55 dB * 55 dB
Impedance Z 75 ohms 75 ohms 75 ohms
Operating temperature range -40°C...+80°C -20°C...+55°C -20°C...+55°C
Degree of protection IP 30 IP 30 IP 30
For mounting on 35 mm DIN rail acc. to EN 60715 earthing bracket 35 mm DIN rail acc. to EN 60715
or wall mounting or wall mounting
Connection input/output F socket / F socket F socket / F connector F socket / F socket
Earthing via DIN rail or screw connection earthing bracket with screw connection DIN rail or screw connection
Enclosure material metal metal metal
Colour bare bare bare
Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21
Approvals, Certifications GOST GOST GOST
Accessories 2 x F connector earthing bracket and 2 x F connector 2 x F connector

Ordering information
Type DGA FF TV DGA GF TV DGA GFF TV
Part No. 909 703 909 704 909 705
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

272 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNgate
929 040 DGA F 1.6
5.6

SPDs FOR COAXIAL CONNECTION DGA F

DGA F 1.6 5.6 DEHNgate


929 040

Dimension drawing DGA F Low-capacitance diode matrix for optimised • For easy retrofitting
transmission performance.
• For high transmission rates
• For installation in conformity with the
lightning protection zones concept at
Quickly responding surge arrester for G.703 interfaces. Earthing via enclosure. 1.6/5.6 connector. the boundaries from 1 – 2 and higher

DGA F 1.6 5.6


SPD class W
Nominal voltage UN 5V
Max. continuous operating d.c. voltage UC 6V
Nominal current IL 0.25 A
C2 Nominal discharge current (8/20 µs) In 0.3 kA
Voltage protection level for In C2 UP ) 30 V
Voltage protection level at 1 kV/µs C3 UP ) 12 V
Frequency range d.c. -80 MHz
Insertion loss ) 0.2 dB
Impedance Z 75 ohms
Capacitance line-shield C 50 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Connection input/output 1.6/5.6 connector / 1.6/5.6 socket
Earthing via externally via shield earthing
Enclosure material metal
Colour bare
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type DGA F 1.6 5.6
Part No. 929 040
Packing unit 1 pc(s).

www.dehn.de 273
DEHNgate INFORMATION TECHNOLOGY SYSTEMS
929 042 DGA G
BNC

DGA G SPDs FOR COAXIAL CONNECTION


929 044 DGA G N

DGA G BNC DEHNgate


929 042
DGA G N DEHNgate
929 044

• Minimal dimensions Built-in coaxial gas discharge tube. Dimension drawing Dimension drawing
DGA G BNC DGA G N
• Extremely wide transmission range
• For installation in conformity with the
lightning protection zones concept at Surge arrester for remote power supply with integrated gas discharge tube. Especially adapted to
the boundaries from 0B – 1 and higher wireless LAN and wireless local loop applications in BNC, N or 1.6/5.6 connectors for bushing
installation.

DGA G BNC DGA G N


SPD class B B
Max. continuous operating d.c. voltage UC 135 V 135 V
Nominal current IL 3.5 A 6A
Max. transmission capacity 25 W 25 W
D1 Lightning impulse current (10/350 µs) Iimp 1 kA 1 kA
C2 Nominal discharge current (8/20 µs) In 5 kA 5 kA
Voltage protection level for In C2 UP ) 500 V ) 500 V
Frequency range d.c. - 4 GHz d.c. - 5.8 GHz
Insertion loss < 0.2 dB < 0.2 dB
Return loss * 20 dB * 20 dB
Impedance Z 50 ohms 50 ohms
Operating temperature range -40°C...+85°C -40°C...+85°C
Degree of protection IP 20 IP 65
Connection input/output BNC socket / BNC connector N socket / N connector
Earthing via bushing Ø12.9 mm bushing Ø16.2 mm
Enclosure material brass, refined surface with trimetal plating brass, refined surface with trimetal plating
Colour gold gold
Test standards IEC 61643-21 IEC 61643-21
Approvals, Certifications GOST GOST

Ordering information
Type DGA G BNC DGA G N
Part No. 929 042 929 044
Packing unit 1 pc(s). 1 pc(s).

274 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNgate
929 043 DGA AG
BNC

SPDs FOR COAXIAL CONNECTION DGA AG


929 045 DGA AG
N
929 057 DGA AG
U

DGA AG BNC DEHNgate


929 043
DGA AG N DEHNgate
929 045
DGA AG U
929 057

DGA AG BNC DGA AG N DGA AG U

Dimension drawings DGA AG Replaceable gas discharge tube • Large surface for connecting gas dis-
charge tubes
• Longevity due to minimum contact
Surge arrester suitable for remote supply with replaceable gas discharge tube. Excellent RF service burn-off at the inner conductor
life due to minimum contact burn-off and large-area contact surface of the gas discharge tube in • For installation in conformity with the
a special cage. lightning protection zones concept at
the boundaries from 0A – 1 and higher

DGA AG BNC DGA AG N DGA AG U


SPD class A A A
Max. continuous operating d.c. voltage UC 180 V 180 V 180 V
Nominal current IL 3.5 A 6A 10 A
Max. transmission capacity 150 W 150 W 150 W
D1 Lightning impulse current (10/350 µs) Iimp 5 kA 5 kA 5 kA
C2 Nominal discharge current (8/20 µs) In 20 kA 20 kA 20 kA
Voltage protection level for In C2 UP ) 750 V ) 750 V ) 750 V
Frequency range d.c. - 1 GHz d.c. - 2.5 GHz d.c. - 300 MHz
Insertion loss < 0.1 dB < 0.2 dB < 0.1 dB
Return loss * 20 dB * 20 dB * 20.8 dB
Impedance Z 50 ohms 50 ohms 50 ohms
Operating temperature range -40°C...+85°C -40°C...+85°C -40°C...+85°C
Degree of protection IP 20 IP 65 IP 20
Connection input/output BNC socket / BNC connector N socket / N connector UHF socket / UHF connector
Earthing via bushing Ø16.1 mm bushing Ø16.1 mm or earthing screw bushing Ø19.3 mm
Enclosure material brass, refined surface with trimetal plating brass, refined surface with trimetal plating brass, refined surface with trimetal plating
Colour bare bare bare
Replaceable gas discharge tube yes yes yes
Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21
Approvals, Certifications GOST GOST GOST

Ordering information
Type DGA AG BNC DGA AG N DGA AG U
Part No. 929 043 929 045 929 057
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNgate


Gas discharge tube 929 498
230
929 499
470
GDT DGA

GDT DGA

Spare gas discharge tube for DEHNgate with lightning current carrying
capability. High quality with especially low capacitance. GDT DGA 230
929 498
GDT DGA 470
929 499

Type GDT DGA 230


Lightning impulse current
carrying capability (10/350 µs) 5 kA
Design H 8 x 6 mm
PU Part
Type pc(s). No.
GDT DGA 230 1 929 498

www.dehn.de 275
DEHNgate INFORMATION TECHNOLOGY SYSTEMS
929 046 DGA LG 7
16

DGA LG SPDs FOR COAXIAL CONNECTION


929 446 DGA LG 7
16 X

DGA LG 7 16 DEHNgate
929 046
DGA LG 7 16 X
929 446

NEW

/4

• For multi-frequency applications with Quarterwave arrester combined with gas dis- Dimension drawing Dimension drawing
d.c. power supply charge tube DGA LG 7 16 DGA LG 7 16 X
• Optionally available with self-extin-
guishing gas discharge capsule up to Quarterwave arrester combined with a spark gap suitable for remote supply for multi-frequency
a nominal current of 2.5 A applications (multi-carrier systems) due to minimum passive intermodulation. Broadband device
• Maximum transmission and PIM per- for all 4+3G services.
formance
• For installation in conformity with the DGA LG 7 16 X with self-extinguishing gas discharge capsule with automatic reset function for a
lightning protection zones concept at high degree of safety and negligible system downtimes.
the boundaries from 0A – 1 and higher

DGA LG 7 16 DGA LG 7 16 X
SPD class A A
Max. continuous operating d.c. voltage UC 65 V 65 V
Nominal current IL 13 A 2.5 A
Max. transmission capacity 500 W 500 W
D1 Lightning impulse current (10/350 µs) Iimp 5 kA 5 kA
C2 Nominal discharge current (8/20 µs) In 20 kA 20 kA
Voltage protection level for In C2 UP ) 1000 V ) 1000 V
Frequency range d.c., 806 MHz - 2.2 GHz d.c., 806 MHz - 2.2 GHz
Insertion loss ) 0.15 dB ) 0.15 dB
Insertion loss 2176 MHz typically 0.1 dB typically 0.1 dB
Return loss * 20 dB * 20 dB
Return loss 2176 MHz typically 20.0 dB typically 20.0 dB
Impedance Z 50 ohms 50 ohms
Intermodulation typically -150 dBc @ 2*43 dBm typically -150 dBc @ 2*43 dBm
Operating temperature range -40°C...+85°C -20°C...+85°C
Degree of protection IP 65 IP 65
Connection input/output 7/16 socket / 7/16 connector 7/16 socket / 7/16 connector
Earthing via earthing screw earthing screw
Enclosure material brass, refined surface with trimetal plating brass, surface-coated with trimetal plating
Colour bare bare
Replaceable gas discharge tube yes Part No. 929496
Test standards IEC 61643-21 IEC 61643-21
Approvals, Certifications GOST GOST

Ordering information
Type DGA LG 7 16 DGA LG 7 16 X
Part No. 929 046 NEW 929 446
Packing unit 1 pc(s). 1 pc(s).

Zubehör für DEHNgate Gas discharge tube with screw cap


Spare gas discharge tube capable of carrying lightning currents with screw cap for
Gas discharge tube DEHNgate LG 7 16 X. Self-extinguishing gas capsule with automatic reset function in
929 497
90
GDT DGA Spare gas discharge tube for DEHNgate with lightning case of d.c. feeding currents up to 2.5 A or higher HF performances.
current carrying capability. High quality with especially
low capacitance. Also suited for retrofitting DEHNgate LG 7 16 with conventional gas capsule technolo-
GDT DGA 90
929 497
gy (replacement of the complete capsule unit!).
Type GDT DGA 90
Type GDT DGA 90 X
Lightning impulse current 929 496 GDT DGA

carrying capability (10/350 µs) 5 kA


90 X
Lightning impulse current carrying capability (10/350 µs) 5 kA
Design H 8 x 6 mm NEW
GDT DGA 90 X
929 496 Integrated into Part No. 929 446
Integrated into (Part No.) 929 046 Can be retrofitted into Part No. 929 046
PU Part PU Part
Type pc(s). No. Type pc(s). No.
GDT DGA 90 1 929 497 GDT DGA 90 X 1 929 496

276 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNgate
929 047 DGA L4 7
16 S

SPDs FOR COAXIAL CONNECTION DGA L4


929 048 DGA L4 7
16 B

DGA L4 7 16 S
929 047
DGA L4 7 16 B DEHNgate
929 048

/4

Dimension drawing Dimension drawing Maintenance-free quarterwave SPD without • Maintenance-free combined lightning
DGA L4 7 16 S DGA L4 7 16 B discrete components. current and surge arrester (high dis-
charge capacity and low voltage pro-
tection level)
Combined lightning current and surge arrester with maintenance-free quarterwave technology • Maximum transmission and PIM per-
with adapted frequency band. The SPDs can also discharge high partial lightning currents. No formance
remote supply possible as the SPD represents an electrical short circuit for low-frequency signals. • For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A – 2 and higher

DGA L4 7 16 S DGA L4 7 16 B
SPD class M M
Max. continuous operating d.c. voltage UC 0V 0V
Nominal current IL 0V 0V
Max. transmission capacity 3000 W 1700 W
D1 Lightning impulse current (10/350 µs) Iimp 25 kA 40 kA
C2 Nominal discharge current (8/20 µs) In 50 kA 80 kA
Voltage protection level for In C2 UP ) 130 V ) 180 V
Frequency range 380 MHz - 512 MHz 880 MHz - 2.2 GHz
Insertion loss < 0.1 dB < 0.15 dB
Return loss * 20 dB * 20 dB
Impedance Z 50 ohms 50 ohms
Intermodulation — typically -150 dBc @ 2*43 dBm
Operating temperature range -40°C...+85°C -40°C...+85°C
Degree of protection IP 65 IP 65
Connection input/output 7/16 socket / 7/16 connector 7/16 socket / 7/16 connector
Earthing via earthing screw earthing screw
Enclosure material brass, refined surface with trimetal plating brass, refined surface with trimetal plating
Colour bare bare
Test standards IEC 61643-21 IEC 61643-21
Approvals, Certifications GOST GOST

Ordering information
Type DGA L4 7 16 S DGA L4 7 16 B
Part No. 929 047 929 048
Packing unit 1 pc(s). 1 pc(s).

www.dehn.de 277
DEHNgate INFORMATION TECHNOLOGY SYSTEMS
929 059 DGA L4 N
EB

DGA L4 N EB SPDs FOR COAXIAL CONNECTION

DGA L4 N EB
929 059

/4

• Maintenance-free combined lightning Maintenance-free quarterwave SPD without Dimension drawing DGA L4 N EB
current and surge arrester, optimised discrete components.
bandwidth and dimensions
• Maximum transmission performance Especially broadband combined lightning current and surge arrester with maintenance-free quar-
for WiMax and Wi-Fi applications terwave technology, adapted frequency band for Broadband Wireless Access applications and small
• For installation in conformity with the dimensions of the enclosure. No remote supply possible as the SPD represents an electrical short
lightning protection zones concept at circuit for low-frequency signals.
the boundaries from 0A – 2 and higher

DGA L4 N EB
SPD class M
Nominal voltage UN 0V
Max. continuous operating d.c. voltage UC 0V
Nominal current IL 0V
Max. transmission capacity 300 W
D1 Lightning impulse current (10/350 µs) Iimp 25 kA
C2 Nominal discharge current (8/20 µs) In 50 kA
Voltage protection level for Iimp D1 UP ) 18 V
Voltage protection level for In C2 UP ) 30 V
Frequency range 2.0 GHz - 6.0 GHz
Insertion loss ) 0.2 dB
Return loss * 20 dB
Impedance Z 50 ohms
Operating temperature range -40°C...+85°C
Degree of protection IP 65
Connection input/output N socket / N socket
Earthing via bushing Ø19.3 mm
Enclosure material aluminium
Colour bare
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type DGA L4 N EB
Part No. 929 059
Packing unit 1 pc(s).

278 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Accessories for DEHNgate
SPDs FOR COAXIAL CONNECTION
Gas discharge tube 929 497
90
929 498
230
929 499
GDT DGA

GDT DGA

GDT DGA
Angled fixing plate 106 310

470

Spare gas discharge tube for DEHNgate with lightning current carrying Made of stainless steel, suitable for installation of DEHNgate,
capability. High quality with especially low capacitance. GDT DGA 90
Gasentladungsableiter für DEHNgate
GDT DGA 230
929 497
Part No. 929 045 – 929 048. 106 310

Gasentladungsableiter für DEHNgate 929 498

Type GDT DGA 90 GDT DGA 230 GDT DGA 470


GDT DGA 470
Gasentladungsableiter für DEHNgate 929 499
PU Part
pc(s). No.
Lightning impulse current
carrying capability (10/350 µs) 5 kA 5 kA 5 kA 20 106 310
Design H 8 x 6 mm H 8 x 6 mm H 8 x 6 mm
Integrated into Part No. 929 046 929 043, 929 045 —
PU Part
Type pc(s). No.
GDT DGA 90 1 929 497
Angled fixing plate for HF arresters 106 329

GDT DGA 230 1 929 498


Made of stainless steel, with 3 mounting holes for 3 different sizes of
DEHNgate, e. g. 1x 929 042 + 1x 929 057 + 1x (929 043, 929 044,
GDT DGA 470 1 929 499 106 329

929 045 or 929 058).


PU Part
pc(s). No.
1 106 329
Gas discharge tube with screw cap 929 496
90 X
GDT DGA

Spare gas discharge tube capable of carrying lightning currents with


screw cap for DEHNgate LG 7 16 X. Self-extinguishing gas capsule with GDT DGA 90 X
Gasentladungsableiter für DEHNgate mit Schraubverschluss 929 496

automatic reset function in case of d.c. feeding currents up to 2.5 A or


higher HF performances. Equipotential bonding bars for industrial 472 209
M10 V2A
PAS I 6AP

installations
Also suited for retrofitting DEHNgate LG 7 16 with conventional gas Made of stainless steel, suitable for direct screwing of 3 DEHNgate PAS I 6AP M10 V2A
Potentialausgleichsschiene 472 209

capsule technology (replacement of the complete capsule unit!). devices, Part No. 929 045 – 929 049.
Type GDT DGA 90 X PU Part
Lightning impulse current carrying capability (10/350 µs) 5 kA Type pc(s). No.
Integrated into Part No. 929 046 NEW PAS I 6AP M10 V2A 1 472 209
Can be retrofitted into Part No. 929 046
PU Part
Type pc(s). No.
GDT DGA 90 X 1 929 496
Earth conductor, open / closed cable lugs 416 411

Cable lug, 1x open M8/M10 and 1x closed M8, suitable for combina-
tion with Part No. 106 310, 106 329 and 472 209. 416 411

PU Part
Cable lug with earth conductor 929 096 EL 16 B17

pc(s). No.
Cable lug with highly flexible black copper earth conductor for earthing 1 416 411
of DEHNgate, Part No. 929 043, 929 044 or 929 045. EL 16 B17
929 096

PU Part
Type pc(s). No.
EL 16 B17 1 929 096

Earthing block 4xF 929 095 EB 4 F

Four-pole earthing block with F sockets, for equipotential bonding of


satellite cable shields or DGA GF TV lightning current arresters. EB 4 F
929 095

Type EB 4 F
Max. continuous operating d.c. voltage 65 V
D1 Lightning impulse current (10/350 µs) 10 kA
Frequency range d.c. - 2400 MHz
PU Part
Type pc(s). No.
EB 4 F 1 929 095

www.dehn.de 279
INFORMATION TECHNOLOGY SYSTEMS
SPDs FOR COAXIAL CONNECTION

280 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS FS / USD
SPDs FOR D-SUB CONNECTION Surge arrester

• Surge protective adapter for easy retrofitting


• 9-pole, 15-pole or 25-pole shielded types avail-
able
• Adapter with single-stage (FS) and 2-stage
(USD) protective circuit

Surge protective adapter, D-Sub plug-in connection, socket-pin type.

Surge protective adapter available in a shielded enclosure with D-Sub use in switchgear cabinets, the powerful USD surge arrester can be
plug-in connection, socket-pin type. The UNC screws of the protection for snapped onto DIN rails. Special types with other pinnings or circuits are
terminal equipment (FS) can be exchanged in any way. The thread is thus also available.
situated either on the pin or socket side, depending on the application. For

The surge arresters are available USD devices can be


in three different designs cover- snapped onto a DIN rail
ing the most frequent applica- which is supposed to dis-
tions. Due to their small size, they charge surges. Three plug-
can be easily integrated into the in types are available.
cabling.

9-pole, 15-pole and 25-pole 9-pole, 15-pole and 25-pole USD surge arrester
FS surge arrester

www.dehn.de 281
FS / USD INFORMATION TECHNOLOGY SYSTEMS
924 017 FS 9E PB
6

FS 9E PB SPDs FOR D-SUB CONNECTION

6 6 FS 9E PB 6
Surge Protection Adapter FS 6 V
Fine
924 017

3 3

8 8

5 5

1 1

• Adapted to Profibus-DP Diode protective circuit with very low capacity. Dimension drawing FS 9E PB
Pins 5 and 6 without protection for the
• Transmission up to 12 MBit/s programming interface.
• For installation in conformity with the
lightning protection zones concept at 9-pole D-Sub, for Profibus-DP applications.
the boundaries from 1 – 2 and higher

FS 9E PB 6
SPD class [
Nominal voltage UN 6V
Max. continuous operating d.c. voltage Uc 7V
C2 Nominal discharge current (8/20 μs) line-line In 0.2 kA
C2 Nominal discharge current (8/20 μs) line-SG In 0.2 kA
C2 Nominal discharge current (8/20 μs) SG-PG In 0.4 kA
Voltage protection level line-line for In C2 UP ) 25 V
Voltage protection level line-SG for In C2 Up ) 25 V
Voltage protection level SG-PG for In C2 Up ) 25 V
Voltage protection level line-line at 1 kV/μs C3 UC ) 18 V
Voltage protection level line-SG at 1 kV/μs C3 Up ) 18 V
Voltage protection level SG-PG at 1 kV/μs C3 Up ) 18 V
Cut-off frequency fG 90 MHz
Capacitance line-line C 25 pF
Capacitance line-SG C 35 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 40
For mounting on D-Sub (2 threaded screws 4/40 UNC)
Connection input/output D-Sub 9 plug / D-Sub 9 socket
Pinning Line: 3/8, SG: 5, PG: 1, 6: unprotected
Earthing via outgoing earth conductor 0.75 mm2, 0.3 m long (PG)
Enclosure material plastic, metallised
Colour silver
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type FS 9E PB 6
Part No. 924 017
Packing unit 1 pc(s).

282 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS FS / USD
924 019 FS 9E HS
12

SPDs FOR D-SUB CONNECTION FS 9E HS

FS 9E HS 12
Surge Protection Adapter FS 12 V
Fine
924 019
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9

Dimension drawing FS 9E HS 8-pole fine protection to common SG. • All pins protected
• Low voltage protection level
• For installation in conformity with the
9-pole D-Sub. V-24 version with handshake function. lightning protection zones concept at
the boundaries from 1 – 2 and higher

FS 9E HS 12
SPD class [
Nominal voltage UN 12 V
Max. continuous operating d.c. voltage Uc 15 V
C2 Nominal discharge current (8/20 μs) line-SG In 0.1 kA
C2 Nominal discharge current (8/20 μs) SG-PG In 0.1 kA
Voltage protection level line-SG for In C2 Up ) 24 V
Voltage protection level SG-PG for In C2 Up ) 200 V
Voltage protection level line-SG at 1 kV/μs C3 Up ) 21 V
Voltage protection level SG-PG at 1 kV/μs C3 Up ) 90 V
Cut-off frequency fG 10 MHz
Capacitance line-SG C 700 pF
Capacitance SG-PG C 350 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 40
For mounting on D-Sub (2 threaded screws 4/40 UNC)
Connection input/output D-Sub 9 plug / D-Sub 9 socket
Pinning line: 1/2/3/4/6/7/8/9, SG: 5
Earthing via outgoing earth conductor 0.75 mm2, 0.3 m long (PG)
Enclosure material plastic, metallised
Colour silver
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type FS 9E HS 12
Part No. 924 019
Packing unit 1 pc(s).

www.dehn.de 283
FS / USD INFORMATION TECHNOLOGY SYSTEMS
924 016 FS 15E 5

FS 15E SPDs FOR D-SUB CONNECTION

2 2 FS 15E 5
Surge Protection Adapter FS 5 V
Fine
924 016

9 9
4 4

11 11

8 8

1 1

• For 4-wire interfaces Fine protection for 2 pairs to common SG. Dimension drawing FS 15E
• Low voltage protection level
• For installation in conformity with the
lightning protection zones concept at 15-pole D-Sub. RS-422, V.11 version.
the boundaries from 1 – 2 and higher

FS 15E 5
SPD class [
Nominal voltage UN 5V
Max. continuous operating d.c. voltage Uc 8V
C2 Nominal discharge current (8/20 μs) line-SG In 0.2 kA
C2 Nominal discharge current (8/20 μs) SG-PG In 0.6 kA
Voltage protection level line-line for In C2 UP ) 16 V
Voltage protection level line-SG for In C2 Up ) 16 V
Voltage protection level SG-PG for In C2 Up ) 16 V
Voltage protection level line-line at 1 kV/μs C3 UC ) 11 V
Voltage protection level line-SG at 1 kV/μs C3 Up ) 11 V
Voltage protection level SG-PG at 1 kV/μs C3 Up ) 11 V
Cut-off frequency fG 4 MHz
Capacitance line-line C 1500 pF
Capacitance line-SG C 1600 pF
Capacitance line-PG C 1200 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 40
For mounting on D-Sub (2 threaded screws 4/40 UNC)
Connection input/output D-Sub 15 plug / D-Sub 15 socket
Pinning line: 2/9, 4/11, SG: 8, PG: 1
Earthing via outgoing earth conductor 0.75 mm2, 0.3 m long (PG)
Enclosure material plastic, metallised
Colour silver
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type FS 15E 5
Part No. 924 016
Packing unit 1 pc(s).

284 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS FS / USD
924 018 FS 25E HS
12

SPDs FOR D-SUB CONNECTION FS 25E HS

FS 25E HS 12 Fine
Surge Protection Adapter FS 12 V 924 018
2 2
3 3
4 4
5 5
6 6
8 8
20 20

7 7

1 1

Dimension drawing FS 25E HS 8-pole fine protection to common SG. • All lines interconnected
• Low voltage protection level
• For installation in conformity with the
25-pole D-Sub. V.24 version with handshake function. lightning protection zones concept at
the boundaries from 1 – 2 and higher

FS 25E HS 12
SPD class [
Nominal voltage UN 12 V
Max. continuous operating d.c. voltage Uc 15 V
C2 Nominal discharge current (8/20 μs) line-SG In 0.1 kA
C2 Nominal discharge current (8/20 μs) SG-PG In 0.1 kA
Voltage protection level line-SG for In C2 Up ) 24 V
Voltage protection level SG-PG for In C2 Up ) 200 V
Voltage protection level line-SG at 1 kV/μs C3 Up ) 21 V
Voltage protection level SG-PG at 1 kV/μs C3 Up ) 90 V
Cut-off frequency fG 10 MHz
Capacitance line-SG C 700 pF
Capacitance SG-PG C 350 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 40
For mounting on D-Sub (2 threaded screws 4/40 UNC)
Connection input/output D-Sub 25 plug / D-Sub 25 socket
Pinning line: 2/3/4/5/6/8/20, SG: 7, other lines are unprotected
Earthing via outgoing earth conductor 0.75 mm2, 0.3 m long (PG)
Enclosure material plastic, metallised
Colour silver
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type FS 25E HS 12
Part No. 924 018
Packing unit 1 pc(s).

www.dehn.de 285
FS / USD INFORMATION TECHNOLOGY SYSTEMS
924 061 USD 9
V24 S B

USD 9 V24 SPDs FOR D-SUB CONNECTION

USD 9 V24 S B Cable


Adapter 924 061

2 2

3 3 protected

5 5

• Plug-in surge arrester with 2-stage Combination of gas discharge tubes, decoupling Dimension drawing USD 9 V24
protective circuit resistors and diodes to PG.

• For installation in conformity with the


lightning protection zones concept at 9-pole D-Sub. V.24 version.
the boundaries from 0B – 2 and higher

USD 9 V24 S B
SPD class T
Nominal voltage UN 12 V
Max. continuous operating d.c. voltage Uc 12.5 V
C2 Nominal discharge current (8/20 μs) line-PG In 2.5 kA
C2 Nominal discharge current (8/20 μs) SG-PG In 7.5 kA
Voltage protection level line-SG for In C2 Up ) 20 V
Voltage protection level SG-PG for In C2 Up ) 250 V
Voltage protection level line-SG at 1 kV/μs C3 Up ) 18 V
Voltage protection level SG-PG at 1 kV/μs C3 Up ) 180 V
Series impedance per line 15 ohms
Operating temperature range -40°C...+80°C
For mounting on D-Sub or 35 mm DIN rail acc. to EN 60715
Connection input/output D-Sub 9 plug / D-Sub 9 socket
Pinning Line: 2/3, SG: 5
Earthing via earthing screw or DIN rail
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type USD 9 V24 S B
Part No. 924 061
Packing unit 1 pc(s).

286 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS FS / USD
924 051 USD 15
V11 S B

SPDs FOR D-SUB CONNECTION USD 15 V11

USD 15 V11 S B Cable


Adapter 924 051 11 11

4 4

9 9
protected
2 2

8 8

1 1

Dimension drawing USD 15 V11 The resistors at the output of the circuit protect • Plug-in surge arrester with 2-stage
optocoupler and protective diodes in the terminal protective circuit
equipment against overloads.
• Integrated decoupling of the protec-
15-pole D-Sub. RS 422, V.11 version. tive circuit to the terminal equipment
• For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B – 2 and higher

USD 15 V11 S B
SPD class T
Nominal voltage UN 8V
Max. continuous operating d.c. voltage Uc 8.5 V
C2 Nominal discharge current (8/20 μs) line-PG In 2.5 kA
C2 Nominal discharge current (8/20 μs) SG-PG In 7.5 kA
Voltage protection level line-line/line-SG C2 Up ) 15 V
Voltage protection level SG-PG for In C2 Up ) 20 V
Voltage protection level line-line/line-SG at 1 kV/μs C3 Up ) 11 V
Voltage protection level SG-PG at 1 kV/μs C3 Up ) 15 V
Series impedance per line 37 ohms
Operating temperature range -40°C...+80°C
For mounting on D-Sub or 35 mm DIN rail acc. to EN 60715
Connection input/output D-Sub 15 plug / D-Sub 15 socket
Pinning Line: 2/9/4/11, SG: 8, PG: 1
Earthing via earthing screw or DIN rail
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type USD 15 V11 S B
Part No. 924 051
Packing unit 1 pc(s).

www.dehn.de 287
FS / USD INFORMATION TECHNOLOGY SYSTEMS
924 046 USD 25
V24 HS S B

USD 25 V24 SPDs FOR D-SUB CONNECTION

USD 25 V24 HS S B Cable


2 2 Adapter 924 046

3 3
4 4
5 5
6 6
8 8
20 20

protected

7 7

1 1

• Plug-in surge arrester with 2-stage Combination of gas discharge tubes, decoupling Dimension drawing USD 25 V24
protective circuit resistors and diodes to signal ground (SG).

• For installation in conformity with the


lightning protection zones concept at 25-pole D-Sub. V.24 version, HS type with handshake function.
the boundaries from 0B – 2 and higher

USD 25 V24 HS S B
SPD class T
Nominal voltage UN 12 V
Max. continuous operating d.c. voltage Uc 12.5 V
C2 Nominal discharge current (8/20 μs) line-PG In 2.5 kA
C2 Nominal discharge current (8/20 μs) SG-PG In 7.5 kA
Voltage protection level line-SG for In C2 Up ) 20 V
Voltage protection level SG-PG/line-PG for In C2 Up ) 250 V
Voltage protection level line-SG at 1 kV/μs C3 Up ) 18 V
Voltage protection level SG-PG at 1 kV/μs C3 Up ) 180 V
Series impedance per line 15 ohms
Operating temperature range -40°C...+80°C
Connection input/output D-Sub 25 plug / D-Sub 25 socket
Pinning Line: 2/3/4/5/6/8/20, SG: 7, PG: 1
Earthing via earthing screw or DIN rail
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type USD 25 V24 HS S B
Part No. 924 046
Packing unit 1 pc(s).

288 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DSM
SPDs FOR TERMINAL CONNECTION Surge arrester

• SPD for telecommunications equipment


• For space-saving flush mounting
• Easy installation due to plug-in terminals

Surge arrester for protection of telecommunications equipment for instal-


lation into flush-type boxes or small-sized distribution boards. Plug-in ter-
minals at the input.
In a typical installation, DSM surge arresters are integrated into the dis- systems or devices. Of course, the SPDs can also be integrated into small-
tribution socket downstream of the socket outlet of the terminal equip- sized distribution boards. The use of the removable plug-in terminals
ment or into the cable duct. This makes them independent from the switch makes the installation of DSM easier. As each plug-in terminal is designed
or box programme and protect, invisibly for the user, telecommunications for four lines, through-wiring of an S0 bus, for example, is possible.

DSM is compact enough to allow for


the types to be installed easily even 3 4
1 2 5-
into small-sized distribution boards 6m l = 500 mm
m
situated in damp rooms. min. 1.0 mm2
0.
5-
1
m
m
K

A
k
IS D 270
V

5
M S

,5
4

n
E

D DN
H

is
UC
Y

9
W
K

.
D

o
B

N
R

P
d

S
S
cte
te
ro
p

S 0 PD
->

4
S

3
2

2
1
N

b
a2
D

1
IS

b
a1

DSM installed into a surface- Apart from plug-in terminals, delivery also
mounted distribution board includes a prewired earth conductor. Delivery (example)

Installation – Step 1 Installation – Step 2 Installation – Step 3

Prewired cables Connecting DSM ... SK to the Final installation


The plug-in connectors are prewired. telecommunications box The telecommunications box is inserted
Through-wiring of the ISDN bus is possible. The lines fixed at DSM are connected to into the mounting panel together with
the telecommunications box and DSM the DSM surge arrester. Now, only an
is placed at the rear panel of the box. adequate cover has to be mounted.
Then, the prewired connectors can be
plugged in.

www.dehn.de 289
DSM INFORMATION TECHNOLOGY SYSTEMS
924 270 DSM ISDN
SK

DSM ISDN SPDs FOR TERMINAL CONNECTION

DSM ISDN SK SPD for


1 RD telecomm. terminal equipment 924 270

2 BK

protected
3 WH

4 YE

• Optional through-wiring of the ISDN Energy-coordinated ISDN 4-wire protective circuit Dimension drawing DSM ISDN
bus via plug-in terminals with additional protection of the remote supply.

• Integrated protection for the remote


supply
• For installation in conformity with the For ISDN S0 interfaces. Through-wiring of the ISDN bus possible by means of four-pole terminal.
lightning protection zones concept at
the boundaries from 0B – 2 and higher

DSM ISDN SK
SPD class Q
Nominal voltage UN 5V
Nominal voltage pa-pa UN 40 V
Max. continuous operating d.c. voltage UC 7.5 V
Max. continuous operating d.c. voltage pa-pa UC 45 V
Nominal current IL 200 mA
C2 Total nominal discharge current (8/20 μs) In 20 kA
C2 Nominal discharge current (8/20 μs) per line In 5 kA
Voltage protection level line-line for In C2 UP ) 30 V
Voltage protection level line-PG for In C2 UP ) 600 V
Voltage protection level pa-pa for In C2 UP ) 180 V
Voltage protection level line-line at 1 kV/μs C3 UP ) 17 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 600 V
Voltage protection level pa-pa at 1 kV/μs C3 UP ) 100 V
Series impedance per line 4.7 ohms
Cut-off frequency fG 4 MHz
Capacitance line-line C ) 1.5 nF
Capacitance line-PG C ) 15 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Connection input/output quad pillar terminals / stranded conductors 0.25 mm2
Pinning 2 pairs
Termination diameter, solid 0.5 - 1.0 mm
Earthing via flat connector 2.8 mm
Enclosure material polyamide PA 6.6
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications GOST
Accessories flat connector, earth conductor 500 mm

Ordering information
Type DSM ISDN SK
Part No. 924 270
Packing unit 1 pc(s).

290 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DSM
924 272 DSM TC 2
SK

SPDs FOR TERMINAL CONNECTION DSM TC

DSM TC 2 SK SPD for


telecomm. terminal equipment 924 272
1 RD

2 BK

protected
3 WH

4 YE

Dimension drawing DSM TC Energy-coordinated protective circuit, free of leak- • Excellent transmission performance
age currents to earth.
• Also suitable for installation into dis-
tribution boards
• For installation in conformity with the
For (system) telephones, Uk0, ADSL, for use with 2 pairs. lightning protection zones concept at
the boundaries from 0B – 2 and higher

DSM TC 2 SK
SPD class R
Nominal voltage UN 110 V
Max. continuous operating d.c. voltage UC 170 V
Nominal current IL 200 mA
C2 Total nominal discharge current (8/20 μs) In 20 kA
C2 Nominal discharge current (8/20 μs) per line In 5 kA
Voltage protection level line-line for In C2 UP ) 275 V
Voltage protection level line-PG for In C2 UP ) 600 V
Voltage protection level line-line at 1 kV/μs C3 UP ) 220 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 600 V
Series impedance per line 4.7 ohms
Cut-off frequency fG 17 MHz
Capacitance line-line C ) 300 pF
Capacitance line-PG C ) 10 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Connection input/output quad pillar terminals / stranded conductors 0.25 mm2
Pinning 2 pairs
Termination diameter, solid 0.5 - 1.0 mm
Earthing via flat connector 2.8 mm
Enclosure material polyamide PA 6.6
Colour yellow
Test standards IEC 61643-21
Approvals, Certifications GOST
Accessories flat connector, earth conductor 500 mm

Ordering information
Type DSM TC 2 SK
Part No. 924 272
Packing unit 1 pc(s).

www.dehn.de 291
BUStector INFORMATION TECHNOLOGY SYSTEMS
Surge arrester SPDs FOR TERMINAL CONNECTION

• Extremely space-saving due to EIB / KNX bus


terminal design
• System-tested with EIBA certification
• Also suitable for KNX buses

Surge arrester for EIB / KNX buses with connecting leads.

The discharge capacity, protective effect and mechanical design of minal pins of a terminal device and can be wired with the existing con-
BUStector surge arresters is adapted to the installation environment of necting cables. It protects especially line and area couplers as well as
EIB / KNX buses. Like a bus terminal it can be plugged onto the bus ter- gateways and sensors installed at outer walls of buildings.

292 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BUStector
925 001 BT 24

SPDs FOR TERMINAL CONNECTION BT

BT 24 BUStector
925 001

Dimension drawing BT Heavy-duty gas discharge tube, adapted to the • Suitable for EIB / KNX systems
withstand capability of the equipment of KNX
systems. • Minimum space requirements
• For installation in conformity with the
SPD with the design of a bus terminal. Approved by EIBA. lightning protection zones concept at
the boundaries from 0B – 1 and higher

BT 24
SPD class B
Nominal voltage Un 24 V
Max. continuous operating d.c. voltage UC 45 V
Nominal current IL 6A
C2 Nominal discharge current per line In 5 kA
Voltage protection level for In C2 ) 1200 V
Voltage protection level line-PG for In C2 ) 650 V
Voltage protection level line-line at 1 kV/μs C3 ) 750 V
Voltage protection level line-PG at 1 kV/μs C3 ) 500 V
Cut-off frequency line-line 70 MHz
Capacitance line-line ) 10 pF
Capacitance line-PG ) 10 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Connection input/output spring contacts Ø1 mm / connecting leads Ø0.8 mm
Earthing via lead 0.75 mm2, length 200 mm
Enclosure material thermoplastic
Colour blue
Test standards IEC 61643-21
Approvals, Certifications EIBA Certification No. Z 32/1399/95

Ordering information
Type BT 24
Part No. 925 001
Packing unit 1 pc(s).

www.dehn.de 293
AS IBAS INFORMATION TECHNOLOGY SYSTEMS
Surge arrester SPDs FOR TERMINAL CONNECTION

• Protects the data line of AS interfaces


• No bus address required
• Easy installation for use as coupling module

Surge arrester for devices with AS interface connection.

Surge arrester for devices with AS interface connection according to the


requirements of AS interface buses. The surge arresters are adapted to the
installation environment of the bus systems and require no bus address.

Due to the low self-impedance, the grey-coloured coupling module with


integrated surge protection can be inserted even into well-extended bus
segments. In addition, it provides a distribution function for data trans-
mission.

294 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS AS IBAS
925 013 AS IBAS
YE

SPDs FOR TERMINAL CONNECTION AS IBAS

AS IBAS YE
1
925 013

2
3

Dimension drawing of coupling module The especially low-capacitance protective circuit • Also protects ESD and switching peak
hardly stresses the AS interface voltages
(1/6 bus equivalent).
• Replaces coupling module with distri-
bution function
The coupling module protects the yellow data line of the AS interface. In addition, it provides a dis- • For installation in conformity with the
tribution function. Earthing via DIN rail or plug-in contact. lightning protection zones concept at
the boundaries from 0B – 2 and higher

AS IBAS YE
SPD class T
Max. continuous operating d.c. voltage Uc 36 V
Nominal current IL 0.3 A
C2 Nominal discharge current (8/20 μs) line-line In 0.15 kA
C2 Nominal discharge current (8/20 μs) line-PG In 5 kA
Voltage protection level line-line for In C2 UP ) 60 V
Voltage protection level line-PG for In C2 UP ) 1100 V
Voltage protection level line-line at 1 kV/μs C3 UP * 50 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 900 V
Capacitance line-line C < 13 pF
Operating temperature range -40°C...+80°C
Degree of protection for coupling module construction with AS interface module IP 67
For mounting on DIN rail or plane surface
Connection input/output yellow AS interface line
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type AS IBAS YE
Part No. 925 013
Packing unit 1 pc(s).

www.dehn.de 295
INFORMATION TECHNOLOGY SYSTEMS
SPDs FOR TERMINAL CONNECTION

296 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNpipe
SCREWABLE SPDs Surge arrester

• Maximum protection due to installation into


the cable run
• Surges are discharged via the enclosure of the
field device
• For nearly all types of two-conductor field
devices with suitable cable gland

Surge arrester for outdoor use to be screwed onto two-conductor field


devices. Stainless steel, IP 67.

DEHNpipe is made of corrosion-resistant stainless steel and is screwed tects the inside of the field device against dangerous overvoltage with the
onto the field device instead of a conventional cable gland. The perma- interfering impulses being discharged via the metal enclosure only and
nently installed lines are then connected to the terminals of the field not via the inside of the field device. Earthing accessories are also avail-
device. Thus the protective components are directly situated in the cable able for plastic field enclosures.
run. This provides an energy-coordinated surge protection. The SPD pro-

DEHNpipe is designed for two-conductor The universal surge


measuring sensors with 4-20 mA inter- arrester is even suitable
faces. The surge arresters provide energy- for applications allowing
coordinated surge protection for space- only for a single assign-
limited field devices in outdoor areas and ment of the terminals of
reduce installation work. field devices, or providing
only one terminal for
DPI types Advantages for installation cable glands.

installation
1 2 3 4

BK cable (black)
tauten transmitter
the cable RD cable (red)
max. 10 Nm
+
receiver −

GNYE
removal GNYE cable
4 3 2 1 (green/yellow)

Installation of DPI MD 24 M 2S Installation of DPI ME 24 N A2G

Due to the two-part design of the SPD, the field cable can be connected The type for installation into pipes provides …-14 NPT male threads and per-
as usual, just like being connected to a measuring sensor. manently installed lines. The device is installed as shown in the above figure.
Thanks to the cable gland a degree of protection of IP 67 is achieved.
DEHNpipe supports common earthing concepts for cable shield treatment
of field cables. Depending on the cable gland used, the cable shield is
earthed directly or indirectly or is not earthed at all. Indirect earthing inte-
grates the shield into the protective concept – without leakage pickups.

www.dehn.de 297
DEHNpipe INFORMATION TECHNOLOGY SYSTEMS
929 941 DPI MD
24 M 2S

DPI MD SCREWABLE SPDs

DPI MD 24 M 2S DEHNpipe
929 941

RD

SHL protected

BK

• Easy installation due to 2-part design Energy-coordinated protective circuit, no leakage Dimension drawing DPI MD
currents to earth, with gas discharge tube for
• Suitable for 3 shielding concepts indirect shield earthing.
• For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B – 2 and higher For 4-20 mA interfaces with thread M20 x 1.5 (female/male). Direct, indirect or no shield earthing.
Cable gland available as accessory part.

DPI MD 24 M 2S
SPD class Q
Nominal voltage UN 24 V
Max. continuous operating d.c. voltage UC 34.8 V
Max. continuous operating a.c. voltage UC 24.5 V
Nominal current IL 0.5 A
D1 Lightning impulse current (10/350 μs) per line Iimp 1 kA
C2 Total nominal discharge current (8/20 μs) In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA
C2 Nominal discharge current (8/20 μs) shield-PG In 20 kA
Voltage protection level line-line for In C2 UP ) 65 V
Voltage protection level line-PG for In C2 UP ) 650 V
Voltage protection level shield-PG for In C2 UP ) 650 V
Voltage protection level line-line at 1 kV/μs C3 UP ) 50 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 500 V
Voltage protection level shield-PG at 1 kV/μs C3 UP ) 600 V
Series impedance per line 2.2 ohms
Cut-off frequency line-line fG 14 MHz
Capacitance line-line C ) 400 pF
Capacitance line-PG C ) 20 pF
Capacitance shield-PG C ) 15 pF
Operating temperature range -40°C ...+80°C
Degree of protection IP 67
For mounting on the field/device side M20 x 1.5 female thread / M20 x 1.5 male thread
Connection input/output screw/connecting leads 1.5 mm2, length of 200 mm
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 1.5 mm2
Earthing via enclosure or earthing ring (accessories)
Enclosure material V2A
Colour bare
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type DPI MD 24 M 2S
Part No. 929 941
Packing unit 1 pc(s).

298 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNpipe
929 921 DPI ME
24 N A2G

SCREWABLE SPDs DPI ME

DPI ME 24 N A2G DEHNpipe


929 921

RD BU

BK BK

protected

GNYE GNYE

Dimension drawing DPI ME Gas discharge tube and diodes, • Robust design
energy-coordinated to earth.
• Encapsulated protective circuit
• Single-ended type available on
request
For unbalanced interfaces with thread …-14 NPT (male/male). Earth conductor led through the • For installation in conformity with the
surge arrester. lightning protection zones concept at
the boundaries from 0B – 2 and higher

DPI ME 24 N A2G
SPD class Q
Nominal voltage UN 24 V
Max. continuous operating d.c. voltage UC 34.8 V
Max. continuous operating a.c. voltage UC 24.5 V
Nominal current IL 0.5 A
D1 Lightning impulse current (10/350 μs) per line Iimp 1 kA
C2 Total nominal discharge current (8/20 μs) In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA
Voltage protection level line-line for In C2 UP ) 120 V
Voltage protection level line-PG for In C2 UP ) 65 V
Voltage protection level line-line at 1 kV/μs C3 UP ) 98 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 49 V
Series impedance per line 4.7 ohms
Capacitance line-line C ) 250 pF
Capacitance line-PG C ) 450 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 67
For mounting on the field/device side …-14 NPT male thread / …-14 NPT male thread
Connection input/output connecting leads AWG 16, length of 500 mm
Earthing via enclosure and connecting lead
Enclosure material V2A
Colour bare
Test standards IEC 61643-21
Approvals, Certifications GOST

Ordering information
Type DPI ME 24 N A2G
Part No. 929 921
Packing unit 1 pc(s).

www.dehn.de 299
Accessories for DEHNpipe INFORMATION TECHNOLOGY SYSTEMS
SCREWABLE SPDs

EMC cable gland


929 982 KV S M20
MS 9.5

Brass gland with shield connection.

KV S M20 MS 9.5 KV S M20 MS 9.5


Cable Gland
EMC
929 982

Sealing range Rd 6.5 - 9.5 mm


Shield diameter 3.2 - 6.5 mm
For mounting on M20 x 1.5
Degree of protection IP 68
Material nickel-plated brass

Ordering information
• For direct shield earthing Type KV S M20 MS 9.5
• Tested with DEHNpipe Part No. 929 982
Packing unit 1 pc(s).

929 984 KV M20


MS 10.5

Cable gland
Brass gland without shield connection.
KV M20 MS 10.5 EMC
Cable Gland 929 984

KV M20 MS 10.5
Sealing range Rd 7.0 - 10.5 mm
For mounting on M20 x 1.5
Degree of protection IP 68
Material nickel-plated brass

Ordering information
Type KV M20 MS 10.5
• No direct shield connection Part No. 929 984
• Tested with DEHNpipe Packing unit 1 pc(s).

929 996 ER DPI


M20

MS earthing ring
Earthing ring made of nickel-plated brass, for external earthing of DPI.
ER DPI M20 Set of
Earthing Rings for DEHNpipe 929 996

ER DPI M20
For mounting on DPI M20 x 1.5
Material nickel-plated brass

Ordering information
Type ER DPI M20
Part No. 929 996
Packing unit 1 pc(s).
• Recommended for mounting
DEHNpipe in an insulating enclosure

300 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNpipe MD Ex (i)
SPDs FOR POTENTIALLY EXPLOSIVE AREAS Surge arrester

• Maximum protection due to installation into


the cable run
• For all field devices with suitable cable gland
• Two-part design for easy installation
• Tested according to ATEX and FISCO require-
ments

Surge arrester for outdoor use to be screwed onto two-conductor field


devices. Stainless steel, installation up to IP 67.

DEHNpipe is made of corrosion-resistant stainless steel and is screwed tects the inside of the field device against dangerous surges with the
onto the field device instead of the conventional cable gland. The perma- interfering impulses being discharged via the metal enclosure only and
nently installed lines are then connected to the terminals of the field not via the inside of the field device. DEHNpipe MD Ex (i) can be either
device. Thus, the protective components are directly situated in the cable used in Ex zone 1 or 2.
run. This provides an energy-coordinated surge protection. The SPD pro-

DEHNpipe is designed for intrinsically safe The universal surge


two-conductor measuring sensors with arrester covers even appli-
4-20 mA or Profibus PA interfaces. The cations allowing only sin-
surge arresters provide energy-coordinat- gle assignment of the ter-
ed surge protection for space-limited field minals of field devices or
devices in outdoor areas and reduce providing only one termi-
DPI MD EX installation work. nal for cable glands.

Advantages for installation

Due to the two-part design of the protective device, the field cable can be
mounting
connected as usual, like being connected to a measuring sensor.
1 2 3 4 Thanks to the cable gland a degree of protection of IP 67 is achieved.
DEHNpipe supports common earthing concepts for cable shield treatment
of field cables. Depending on the cable gland used, the cable shield is
earthed directly or is not earthed at all.
max. 10 Nm

removal
4 3 2 1

Installation of DPI MD EX

www.dehn.de 301
DEHNpipe MD Ex (i) INFORMATION TECHNOLOGY SYSTEMS
Surge arrester SPDs FOR POTENTIALLY EXPLOSIVE AREAS

EC-Type Examination Certificate DPI MD EX

302 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNpipe MD Ex (i)
929 960 DPI MD
EX 24 M 2

SPDs FOR POTENTIALLY EXPLOSIVE AREAS DPI MD EX

DPI MD EX 24 M 2 DEHNpipe
929 960

RD

protected

BK

Dimension drawing DPI MD EX Low-capacitance, energy-coordinated protective cir- • Easy installation due to two-part
cuit with an insulation resistance > 500 V to earth. design
• Self-capacitance and self-inductance
negligibly small
Surge arrester for protecting intrinsically safe measuring circuits and bus systems, meets FISCO • For installation in conformity with the
requirements. Cable gland must be ordered separately. lightning protection zones concept at
the boundaries from 0B – 2 and higher

DPI MD EX 24 M 2
SPD class T
Nominal voltage UN 24 V
Max. continuous operating d.c. voltage Uc 34.8 V
Max. continuous operating a.c. voltage UC 24.5 V
Max. input voltage acc. to EN 50020 Ui 30 V
Max. input current acc. to EN 50020 Ii 0.5 A
Nominal current IL 0.5 A
D1 Lightning impulse current (10/350 μs) per line Iimp 1 kA
C2 Total nominal discharge current (8/20 μs) In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 5 kA
Voltage protection level line-line for In C2 UP ) 55 V
Voltage protection level line-PG for In C2 UP ) 1100 V
Voltage protection level line-line at 1 kV/μs C3 UP ) 49 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 1000 V
Series impedance per line 1.8 ohms
Cut-off frequency line-line fG 7 MHz
Capacitance line-line C ) 850 pF
Capacitance line-PG C ) 15 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 67
For mounting on field/device side M20 x 1.5 female thread / M20 x 1.5 male thread
Connection input/output screw / connecting leads 1.5 mm2, length of 200 mm
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 1.5 mm2
Earthing via enclosure
Enclosure material V2A
Colour bare
Test standards IEC 61643-21
Ex certifications ATEX: KEMA 09ATEX0122 X: II 2 (1) G Ex ia IIC T4 ... T6
Approvals, Certifications GOST

Ordering information
Type DPI MD EX 24 M 2
Part No. 929 960
Packing unit 1 pc(s).

www.dehn.de 303
Accessories for DEHNpipe MD Ex (i) INFORMATION TECHNOLOGY SYSTEMS
SPDs FOR POTENTIALLY EXPLOSIVE AREAS

EMC cable gland 929 982


MS 9.5
KV S M20

Brass gland with shield connection.


KV S M20 MS 9.5 EMC
Cable Gland 929 982

KV S M20 MS 9.5
Sealing range Rd 6.5 - 9.5 mm
Shield diameter 3.2 - 6.5 mm
For mounting on M20 x 1.5
Degree of protection IP 68
Material nickel-plated brass

Ordering information
• For direct shield earthing Type KV S M20 MS 9.5
• Tested with DEHNpipe Part No. 929 982
Packing unit 1 pc(s).

Cable gland
929 984 KV M20
MS 10.5

Brass gland without shield connection.

KV M20 MS 10.5 KV M20 MS 10.5


Cable Gland
EMC
929 984

Sealing range Rd 7.0 - 10.5 mm


For mounting on M20 x 1.5
Degree of protection IP 68
Material nickel-plated brass

Ordering information
Type KV M20 MS 10.5
• No direct shield connection Part No. 929 984
• Tested with DEHNpipe Packing unit 1 pc(s).

304 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNpipe CD Ex (i)
SPDs FOR POTENTIALLY EXPLOSIVE AREAS Surge arrester

• Economical SPD for field devices with spare


cable gland
• Easy to retrofit and extremely space-saving
• Tested according to ATEX and FISCO require-
ments

Surge arrester for outdoor use to be screwed onto two-conductor field


devices. Stainless steel, installation up to a degree of protection of IP 67.

DEHNpipe C is made of corrosion-resistant stainless steel and is screwed A degree of protection of IP 67 can be achieved due to the design of the
directly onto the field device. Like a field cable, the permanently installed surge arrester.
lines are connected to the terminals of the field device. Thus, the protective Intrinsically safe surge arresters are typically used in 4-20 mA measuring
components are situated in parallel to the cable run. The connection with circuits or bus systems up to 30 V. According to the type used, DEHNpipe C
the metal or plastic enclosures can be carried out easily as the earth wire is designed for measuring sensors with M20 x 1.5 or …-14 NPT cable gland
of the protective device can be connected to the earth terminal of a field connections. DEHNpipe CD Ex (i) can be either installed in Ex zones 1 or 2.
device.

EC-Type Examination Certificate DPI CD Ex(i)

www.dehn.de 305
DEHNpipe CD Ex (i) INFORMATION TECHNOLOGY SYSTEMS
929 961 DPI CD
EXI 24 M

DPI CD EXI SPDs FOR POTENTIALLY EXPLOSIVE AREAS


929 963 DPI CD
EXI 24 N

DPI CD EXI 24 M DEHNpipe


929 961
DPI CD EXI 24 N DEHNpipe
929 963

RD

BK
GNYE

• Easy installation on field devices with Low-capacitance protective circuit with an Dimension drawing DPI CD EXI 24 M
spare cable gland insulation strength > 500 V to earth.

• Self-capacitance and self-inductance


negligibly small
• For installation in conformity with the Surge arrester for protecting intrinsically safe measuring circuits and bus systems, meets FISCO
lightning protection zones concept at requirements.
the boundaries from 0B – 2 and higher

DPI CD EXI 24 M DPI CD EXI 24 N


SPD class T T
Nominal voltage UN 24 V 24 V
Max. continuous operating d.c. voltage UC 32 V 32 V
Max. continuous operating a.c. voltage UC 22.6 V 22.6 V
Max. input voltage acc. to EN 50020 Ui 30 V 30 V
Max. input current acc. to EN 50020 Ii 0.55 A 0.55 A
Nominal current IL 0.55 A 0.55 A
D1 lightning impulse current (10/350 μs) line-PG Iimp 1 kA 1 kA
C2 Total nominal discharge current (8/20 μs) In 10 kA 10 kA
C2 Nominal discharge current (8/20 μs) line-line In 150 A 150 A
C2 Nominal discharge current (8/20 μs) line-PG In 10 kA 10 kA
Voltage protection level line-line for In C2 UP ) 58 V ) 58 V
Voltage protection level line-PG for In C2 UP ) 1700 V ) 1700 V
Voltage protection level line-line at 1 kV/μs C3 UP ) 50 V ) 50 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 1200 V ) 1200 V
Cut-off frequency line-line fG 67 MHz 67 MHz
Capacitance line-line C ) 25 pF ) 25 pF
Capacitance line-PG C ) 15 pF ) 15 pF
Operating temperature range -40°C...+80°C -40°C...+80°C
Degree of protection design in IP 67 design in IP 67
For mounting on field/device side M20 x 1.5 male thread …-14 NPT male thread
Connection input/output connecting leads 1.3 mm2, length of 250 mm connecting leads 1.3 mm2, length of 250 mm
Earthing via connecting lead connecting lead
Enclosure material V4A V4A
Colour bare bare
Test standards IEC 61643-21 IEC 61643-21
Ex certifications ATEX: KEMA 04ATEX1189 X: II 2 (1) G Ex ia IIC T5 ... T6 ATEX: KEMA 04ATEX1189 X: II 2 (1) G Ex ia IIC T5 ... T6
Approvals, Certifications GOST GOST

Ordering information
Type DPI CD EXI 24 M DPI CD EXI 24 N
Part No. 929 961 929 963
Packing unit 1 pc(s). 1 pc(s).

306 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNpipe CD Ex (d)
SPDs FOR POTENTIALLY EXPLOSIVE AREAS Surge arrester

• Economical SPD for field devices with spare


cable gland or field bus distributors in haz-
ardous areas
• Easy to retrofit and extremely space-saving
• ATEX certification

Surge arrester for outdoor use to be screwed onto two-conductor field


devices. Stainless steel. Installation up to a degree of protection of IP 67.

The flameproof DEHNpipe C surge arrester is made of corrosion-resistant A degree of protection of IP 67 can be achieved due to the design of the
stainless steel and is directly screwed onto the field device. Like a field surge arrester. These flameproof SPDs are typically used in 4-20 mA meas-
cable, the permanently installed lines are connected to the terminals of uring circuits or bus systems up to 30 V. According to the type used,
the field device. Thus, the protection components are situated in parallel DEHNpipe C is designed for measuring sensors with M20 x 1.5 or …-14
to the cable run. The device can be easily installed into metal or plastic NPT cable gland connection. DEHNpipe CD Ex (d) can be either installed
field enclosures as the earth wire of the protective device can be connect- in Ex zone 1 or 2.
ed to the earth terminal of a field device.

EC-Type Examination Certificate DPI CD Ex (d)

www.dehn.de 307
DEHNpipe CD Ex (d) INFORMATION TECHNOLOGY SYSTEMS
929 962 DPI CD
EXD 24 M

DPI CD EXD SPDs FOR POTENTIALLY EXPLOSIVE AREAS


929 964 DPI CD
EXD 24 N

DPI CD EXD 24 M DEHNpipe


929 962
DPI CD EXD 24 N DEHNpipe
929 964

RD

BK
GNYE

• Easy installation on the spare cable Low-capacitance protective circuit with an Dimension drawing DPI CD EXD 24 M
gland of field devices insulation resistance > 500 V to earth.

• Type Ex(d) for universal use


• For installation in conformity with the
lightning protection zones concept at Flameproof surge arrester for use in potentially explosive atmospheres for protecting measuring
the boundaries from 0B – 2 and higher circuits and bus systems.

DPI CD EXD 24 M DPI CD EXD 24 N


SPD class T T
Nominal voltage UN 24 V 24 V
Max. continuous operating d.c. voltage Uc 32 V 32 V
Max. continuous operating a.c. voltage Uc 22.6 V 22.6 V
Nominal current IL 0.55 A 0.55 A
D1 Lightning impulse current (10/350 μs) line-PG Iimp 1 kA 1 kA
C2 Total nominal discharge current (8/20 μs) In 10 kA 10 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA 10 kA
Voltage protection level line-line for In C2 UP ) 58 V ) 58 V
Voltage protection level line-PG for In C2 UP ) 1700 V ) 1700 V
Voltage protection level line-line at 1 kV/μs C3 UP ) 50 V ) 50 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 1200 V ) 1200 V
Cut-off frequency line-line fG 67 MHz 67 MHz
Capacitance line-line C ) 25 pF ) 25 pF
Capacitance line-PG C ) 15 pF ) 15 pF
Operating temperature range -40°C...+80°C -40°C...+80°C
Degree of protection design in IP 67 design in IP 67
For mounting on field/device side M20 x 1.5 male thread …-14 npt male thread
Connection input/output connecting leads 1.3 mm2, length of 250 mm connecting leads 1.3 mm2, length of 250 mm
Earthing via connecting lead connecting lead
Enclosure material V4A V4A
Colour bare bare
Test standards IEC 61643-21 IEC 61643-21
Ex certifications ATEX: KEMA 04ATEX2190 X: II 2 G Ex d IIC T5 or T6 ATEX: KEMA 04ATEX2190 X: II 2 G Ex d IIC T5 or T6
Approvals, Certifications GOST GOST

Ordering information
Type DPI CD EXD 24 M DPI CD EXD 24 N
Part No. 929 962 929 964
Packing unit 1 pc(s). 1 pc(s).

308 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNpipe CD Ex (d)
929 971 DPI CD HF EXD 5 M

SPDs FOR POTENTIALLY EXPLOSIVE AREAS DPI CD HF EXD

DPI CD HF EXD 5 M
NEW
929 971

RD
SW27

M20 x 1.5

75
BU
GNYE
approx. BK
300 55 BN

Dimension drawing DPI CD HF EXD 5 M Low-capacitance, energy-coordinated protective • Easy installation on the spare cable
circuit. gland of field devices
• Ex (d) version for a variety of applica-
tions
Flameproof surge arrester for use in potentially explosive atmospheres for protecting measuring • For installation in conformity with the
circuits and bus systems. lightning protection zones concept at
the boundaries from 0B – 2 and higher

DPI CD HF EXD 5 M
SPD class T
Nominal voltage UN 5V
Max. continuous operating d.c. voltage Uc 6V
Max. continuous operating a.c. voltage Uc 4.2 V
Nominal current at 80° C IL 0.1 A
C2 Total nominal discharge current (8/20 μs) In 20 kA
C2 Nominal discharge current (8/20 μs) per line In 10 kA
Voltage protection level line-line for In C2 UP ) 55 V
Voltage protection level line-PG for In C2 UP ) 1000 V
Voltage protection level line-line at 1 kV/μs C3 UP ) 12 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 700 V
Series impedance per line 4.7 ohms
Cut-off frequency line-line fG 100 MHz
Capacitance line-line C ) 40 pF
Capacitance line-PG C ) 30 pF
Operating temperature range -40°C...+80°C
Degree of protection design in IP 67
For mounting on field/device side M20 x 1.5 male thread
Connection input/output connecting cables 1.3 mm2, length of 300 mm
Earthing via connecting cable
Enclosure material V4A
Colour bare
Test standards IEC 61643-21
Ex certifications ATEX: KEMA 04ATEX2190 X: II 2 G Ex d IIC T5 or T6
Approvals, Certifications GOST

Ordering information
Type DPI CD HF EXD 5 M
Part No. 929 971
Packing unit 1 pc(s).

www.dehn.de 309
DEHNpipe CD Ex (d) INFORMATION TECHNOLOGY SYSTEMS
929 969 DPI CD EXD 230 24 M
929 970 DPI CD EXD 230 24 N

DPI CD EXD 230 24 SPDs FOR POTENTIALLY EXPLOSIVE AREAS


Available by mid 2010

NEW BK DPI CD EXD 230 24 M


929 969
DPI CD EXD 230 24 N
929 970

230 V

SW27

M20 x 1.5
BL

GN/YE 63

RD

24 V
approx.
250 83
BR

• Dual surge protection for 230 V Basic circuit diagram DPI CD EXD 230 24 M Dimension drawing DPI CD EXD 230 24 M
power supplies and 0/4-20 mA inter-
faces • Ex (d) version can be used for all Flameproof surge arrester for use in poten-
• Easy installation on field devices with types of applications tially explosive areas for protecting 230 V ter-
a spare cable gland • For installation in conformity with the minal equipment and 0/4-20 mA interfaces
• Increased safety due to distinctive Y lightning protection zones concept at
circuit for 230 V power supplies the boundaries from 0B – 2 and higher ATEX certification (EEX d IIC T5 or T6) pending

Protection for the data side DPI CD EXD 230 24 M DPI CD EXD 230 24 N
SPD class V V
Nominal voltage UN 24 V 24 V
Max. continuous operating d.c. voltage Uc 32 V 32 V
Max. continuous operating a.c. voltage Uc 22.6 V 22.6 V
Nominal current at 80° C IL 0.55 A 0.55 A
D1 Lightning impulse current (10/350 μs) line-PG Iimp 1 kA 1 kA
C2 Total nominal discharge current (8/20 μs) In 10 kA 10 kA
Voltage protection level line-line for In C2 UP ) 58 V ) 58 V
Voltage protection level line-PG for In C2 UP ) 2000 V * ) 2000 V *
Voltage protection level line-line at 1 kV/μs C3 UP ) 50 V ) 50 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 1700 V * ) 1700 V *
Capacitance line-line C ) 25 pF ) 25 pF
Capacitance line-PG C ) 15 pF * ) 15 pF *
Operating temperature range -40°C...+80°C -40°C...+80°C
Degree of protection design in IP 67 design in IP 67
For mounting on field/device side M20 x 1.5 male thread …-14 NPT male thread
Connection input/output connecting leads 1.3 mm2, length of 250 mm connecting leads 1.3 mm2, length of 250 mm
Earthing via connecting lead connecting lead
Enclosure material V4A V4A
Colour bare bare
Test standards IEC 61643-21 IEC 61643-21
Approvals, Certifications GOST GOST
Protection for the power side DPI CD EXD 230 24 M DPI CD EXD 230 24 N
SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Nominal a.c. voltage UN 230 V 230 V
Maximum continuous operating a.c. voltage Uc 255 V 255 V
Nominal discharge current (8/20 μs) In 3 kA 3 kA
Total discharge current (8/20) L/N-PE Itotal 5 kA 5 kA
Voltage protection level L-N Up ) 1.4 kV ) 1.4 kV
Voltage protection level L/N-PE Up ) 1.5 kV ) 1.5 kV
Max. discharge current L/N-PE Imax 3 kA 3 kA
Max. supply-side overcurrent protection 16 A gL/gG or B 16 A 16 A gL/gG or B 16 A
Short-circuit current withstand capability in case
of supply-side overcurrent protection with 16 A gL/gG 6 kArms 6 kArms
TOV L-N UT 335 V/5 sec 335 V/5 sec
TOV L/N-PE (1) UT 400 V/5 sec 400 V/5 sec
TOV L/N-PE (2) UT 1200 V+U0 /200 ms 1200 V+U0 /200 ms
Indication of the disconnection device upstream fuse element upstream fuse element

Ordering information
Type DPI CD EXD 230 24 M DPI CD EXD 230 24 N
Part No. 929 969 929 970
Packing unit 1 pc(s). 1 pc(s).

*) preliminary data
310 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XT Ex (i)
SPDs FOR POTENTIALLY EXPLOSIVE AREAS Surge arrester

• Effective protection with minimum space


requirements
• For use with 2-pole, 3-pole or 4-pole intrinsical-
ly safe interfaces
• Function-optimised design for safe handling
and easy installation
• Quick testing of LifeCheck-equipped SPD mod-
ules
• ATEX approval, FISCO

Pluggable, multipole, universal surge arrester for use in intrinsically safe


systems with integrated LifeCheck monitoring device.

BLITZDUCTOR XT EX is a pluggable, four-pole, universal DIN rail mounted proper condition of the SPD. Like an early warning system, LifeCheck reli-
surge arrester designed for the most stringent requirements on the avail- ably detects potential electrical and thermal overloads of the protection
ability of intrinsically safe measuring and control circuits and bus systems. components. The LifeCheck status can be read out within a matter of sec-
With regard to intrinsic safety, the SPD is considered earth-free and its onds by means of DEHNrecord LC via contactless RFID technology and
self-inductance and self-capacitance are negligibly small. The high also shows the date of the last test of the SPD module. A stationary con-
impulse current discharge capacity (min. 10x) and the low voltage protec- dition monitoring system allows status-oriented maintenance of 10 BXT.
tion level are supported by the low-impedance design of the device. To ensure safe operation, the SPD provides protection against vibration
LifeCheck allows for quick and easy testing of SPDs. However, the SPD effects and shock up to a 30-fold acceleration of gravity. The function-
modules may only be read out by means of the hand-held DRC LC reader optimised design of the devices allows both quick and easy replacement
in non-explosive atmospheres. of SPD modules which house all relevant protection elements. The SPD
Integrated into the SPD modules, LifeCheck permanently monitors the module and the base part must be ordered separately.

Completely installed BLITZDUCTOR XT EX. Universal base part accommodates all


Two-part design with universal base part types of SPD modules. The SPD modules
and application-specific SPD module. can be easily removed from the base part
Particularly space-saving, for DIN rail without signal interruption thereby min-
mounting. imising storage requirements as well as
prewiring and maintenance operations.

BLITZDUCTOR XT EX Base part

Dimension drawing of a BLITZDUCTOR XT BXT ML4 BD EX 24:


EX base part with plugged-in SPD module. Universal LifeCheck-equipped SPD module
Width: 2/3 mods. (12 mm), for use in dis- for 2 intrinsically safe circuits such as 4-20
tribution boards with DIN rails. mA, HART, PROFIBUS-PA, FF, NAMUR.
BXT ML4 BC EX 24:
For protection of e.g. 3-wire or 4-wire tem-
perature measuring systems.
BXT ML2 BD HF EX 6:
Protection of a pair for fast data transmis-
sion and a feeding currents up to 4.8 A.
Dimension drawing 3 basic types

www.dehn.de 311
BLITZDUCTOR® XT Ex (i) INFORMATION TECHNOLOGY SYSTEMS
Surge arrester SPDs FOR POTENTIALLY EXPLOSIVE AREAS

EC-Type Examination Certificate BXT EX

312 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XT Ex (i) Base Part
920 301 BXT BAS
EX

SPDs FOR POTENTIALLY EXPLOSIVE AREAS BXT BAS EX

BXT BAS EX
2 2´
920 301
4 4´
BXT BAS 1234 4´ 3´ 2´1´
protected
1 1´
3 3´

BXT ML4...

2 2´ protected
4 4´
BXT BAS 1 2 3 4 4´ 3´ 2´ 1´

1 1´
3 3´

Dimension drawing BXT BAS EX Basic circuit diagram with and without • Four-pole and universal device for all
plugged-in module types of intrinsically safe SPD mod-
ules
BLITZDUCTOR XT base part for use as very space-saving, four-pole, universal feed-through termi-
nal for intrinsically safe circuits for the insertion of SPD modules without signal interruption. The • Insertion and removal without signal
snap-in mechanism at the supporting foot of the base part allows the device to be safely earthed interruption
via the DIN rail. As no components of the protective circuit are situated in the base part, mainte- • Universal design without protection
nance operation is only required for the protection modules. components

BXT BAS EX
Operating temperature range -50°C...+80°C
Degree of protection IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output screw / screw
Cross-sectional area, solid 0.08 - 4 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Tightening torque (terminals) 0.4 Nm
Earthing via 35 mm DIN rail acc. to EN 60715
Enclosure material polyamide PA 6.6
Colour blue
Ex certifications ATEX: KEMA 06ATEX0274 X: II 2 (1) G Ex ia IIC T4 ... T6
Approvals, Certifications CSA, GOST

Ordering information
Type BXT BAS EX
Part No. 920 301
Packing unit 1 pc(s).

Clear identification of the Leading/retarded make-before-break


“protected“ side for switch contacts for uninterrupted
faultless installation removal and insertion without downtime

Module release spring The earthing foot ensures cost-


for removing the protection effective installation. No additional
module without problems earth connection is required since the
device is safely earthed via the DIN rail

Lightning current carrying Reverse polarity protection prevents


laminated contacts incorrect insertion of the protection
module

High-quality, four-pole screw terminals


for the following cross-sections:
Designation space stranded: 2.5 mm2
for marking the circuits solid: 4 mm2

www.dehn.de 313
BLITZDUCTOR® XT Ex (i) LifeCheck® Modules INFORMATION TECHNOLOGY SYSTEMS
920 381 BXT ML4
BD EX 24

BXT ML4 BD EX 24 SPDs FOR POTENTIALLY EXPLOSIVE AREAS

BXT ML4 BD EX 24
920 381
1 1´

2 2´

protected

3 3´

4 4´

• For universal use, with LifeCheck SPD


monitoring function The RFID chip of the LifeCheck SPD monitoring Dimension drawing BXT ML4 BD EX
device can be read out without contact via
• Self-capacitance and self-inductance DEHNrecord LC. Insulation resistance > 500 V
negligibly small line-earth.
• For installation in conformity with the
lightning protection zones concept at Space-saving LifeCheck-equipped surge arrester module for protecting 2 pairs in intrinsically safe
the boundaries from 0B – 2 and higher measuring circuits and bus systems, meets FISCO requirements.

BXT ML4 BD EX 24
SPD class T
SPD monitoring LifeCheck
Nominal voltage UN 24 V
Max. continuous operating d.c. voltage Uc 33 V
Max. continuous operating a.c. voltage Uc 23 V
Max. input voltage acc. to EN 60079-11 Ui 30 V
Max. input current acc. to EN 60079-11 Ii 0.5 A
D1 Total lightning impulse current (10/350 µs) Iimp 4 kA
D1 Lightning impulse current (10/350 µs) per line Iimp 1 kA
C2 Total nominal discharge current (8/20 µs) In 20 kA
C2 Nominal discharge current (8/20 µs) per line In 5 kA
Voltage protection level line-line for Iimp D1 Up ≤ 50 V
Voltage protection level line-PG for Iimp D1 Up ≤ 1300 V
Voltage protection level line-line for In C2 Up ≤ 52 V
Voltage protection level line-PG for In C2 Up ≤ 1400 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 45 V
Voltage protection level line-PG at 1 kV/µs C3 Up ≤ 1100 V
Series impedance per line 1.0 ohm
Cut-off frequency line-line fG 7.7 MHz
Capacitance line-line C ≤ 0.8 nF
Capacitance line-PG C ≤ 16 pF
Operating temperature range -40°C...+80°C
Degree of protection (plugged-in) IP 20
For plugging into base part
Earthing via base part
Enclosure material polyamide PA 6.6
Colour blue
Test standards IEC 61643-21, UL 497B
SIL classification SIL2 / SIL3 for more details see: www.dehn.de/en/sil/
Ex certifications ATEX: KEMA 06ATEX0274 X: II 2 (1) G Ex ia IIC T4 ... T6
Approvals, Certifications CSA, GOST

Ordering information
Type BXT ML4 BD EX 24
Part No. 920 381
Packing unit 1 pc(s).

920 301
EX
BXT BAS
BXT BAS EX 910 695
MCM XT
DRC

DRC MCM XT
910 653
M3
DRC LC

DRC LC M3+
Base part for use as a feed-through terminal in DIN rail mounted device with integrated Portable device with LifeCheck sensor for
BXT BAS EX
920 301
intrinsically safe circuits for the insertion of DRC MCM XT
LifeCheck sensor for status-oriented monitor- DRC LC M3
flexible use. For fast and easy testing of
SPD modules without signal interruption.
910 695 Ableiterprüfgerät LifeCheck 910 653

ing of max. 10 BXT devices with LifeCheck LifeCheck-equipped arresters.


PU Part function. PU Part
Type pc(s). No. PU Part Type pc(s). No.
BXT BAS EX 1 920 301 Type pc(s). No. DRC LC M3+ 1 910 653
DRC MCM XT 1 910 695

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 313/317/318/319/360/362.

314 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® XT Ex (i) LifeCheck® Modules
920 384 BXT ML4
BC EX 24

SPDs FOR POTENTIALLY EXPLOSIVE AREAS BXT ML4 BC EX 24

BXT ML4 BC EX 24
920 384
1 1´

2 2´

protected

3 3´

4 4´

• For multi-wire measuring systems,


Dimension drawing BXT ML4 BC EX The RFID chip of the LifeCheck SPD monitoring with LifeCheck SPD monitoring device
device can be read out without contact via
DEHNrecord LC. Insulation resistance > 500 V
• Self-capacitance and self-inductance
line-earth. negligibly small
• For installation in conformity with the
Space-saving LifeCheck-equipped surge arrester module for protecting up to 4 earth-potential-free lightning protection zones concept at
single lines with common reference potential in intrinsically safe circuits, meets FISCO requirements. the boundaries from 0B – 2 and higher

BXT ML4 BC EX 24
SPD class T
SPD monitoring LifeCheck
Nominal voltage UN 24 V
Max. continuous operating d.c. voltage Uc 33 V
Max. continuous operating a.c. voltage Uc 23.3 V
Max. input voltage acc. to EN 60079-11 Ui 30 V
Max. input current acc. to EN 60079-11 Ii 0.5 A
D1 Total lightning impulse current (10/350 µs) Iimp 4 kA
D1 Lightning impulse current (10/350 µs) per line Iimp 1 kA
C2 Total nominal discharge current (8/20 µs) In 20 kA
C2 Nominal discharge current (8/20 µs) per line In 5 kA
Voltage protection level line-line for Iimp D1 Up ≤ 53 V
Voltage protection level line-PG for Iimp D1 Up ≤ 1300 V
Voltage protection level line-line for In C2 Up ≤ 55 V
Voltage protection level line-PG for In C2 Up ≤ 1400 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 45 V
Voltage protection level line-PG at 1 kV/µs C3 Up ≤ 1100 V
Series impedance per line 1 ohm
Cut-off frequency line-line fG 6.4 MHz
Capacitance line-line C ≤ 0.8 nF
Capacitance line-PG C ≤ 16 pF
Operating temperature range -40°C...+80°C
Degree of protection (plugged-in) IP 20
For plugging into base part
Earthing via base part
Enclosure material polyamide PA 6.6
Colour blue
Test standards IEC 61643-21, UL 497B
SIL classification SIL2 / SIL3 for more details see: www.dehn.de/en/sil/
Ex certifications ATEX: KEMA 06ATEX0274 X: II 2 (1) G Ex ia IIC T4 ... T6
Approvals, Certifications CSA, GOST

Ordering information
Type BXT ML4 BC EX 24
Part No. 920 384
Packing unit 1 pc(s).

Test / Disconnection Module 920 309 BXT M4 T


Earthing module 920 308 BXT M4 E
Partition 910 697
MCM EX
TW DRC

Module for testing lines, to be plugged into For direct earthing of lines connected to the BXT M4 E
Erdungsmodul
BXT-
920 308
For DRC MCM XT
the BLITZDUCTOR XT base part. BLITZDUCTOR XT base part. PU Part TW DRC MCM EX Ex i-
Trennwand f. DRC MCM 910 697

PU Part BXT M4 T
/Trennmodul
BXT-Prüf-
920 309
PU Part Type pc(s). No.
Type pc(s). No. Type pc(s). No. TW DRC MCM EX 1 910 697
BXT M4 T 1 920 309 BXT M4 E 1 920 308

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 313/317/318/319/360/362.

www.dehn.de 315
BLITZDUCTOR® XT Ex (i) LifeCheck® Modules INFORMATION TECHNOLOGY SYSTEMS
920 538 BXT ML2 BD HF EX 6

BXT ML2 BD HF EX 6 SPDs FOR POTENTIALLY EXPLOSIVE AREAS

NEW 1 1´
BXT ML2 BD HF EX 6
920 538

2 2´

protected

3 3´

4 4´

• Universal use, with LifeCheck SPD


monitoring device The RFID chip of the LifeCheck SPD monitoring Dimension drawing BXT ML2 BD HF EX 6
device can be read out without contact via
• Self-capacitance and self-inductance DEHNrecord LC. Insulation strength
negligibly small > 500 V line-earth.
• For installation in conformity with the
lightning protection zones concept at Space-saving LifeCheck-equipped surge arrester module for protecting 1 pair in intrinsically safe
the boundaries from 0B – 2 and higher measuring circuits and RS485 bus systems.

BXT ML2 BD HF EX 6
SPD class T
SPD monitoring LifeCheck
Nominal voltage UN 6V
Max. continuous operating d.c. voltage Uc 6V
Max. continuous operating a.c. voltage Uc 4.2 V
Max. input voltage acc. to EN 60079-11 Ui 4.2 V
Max. input current acc. to EN 60079-11 Ii 4.8 A
Max. input current acc. to EN 60079-11
(without protection module only up to 60°C) Ii 4.8 A
D1 Lightning impulse current (10/350 µs) per line Iimp 1 kA
C2 Total nominal discharge current (8/20 µs) In 10 kA
C2 Nominal discharge current (8/20 µs) per line In 5 kA
Voltage protection level line-line for Iimp D1 Up ≤ 35 V
Voltage protection level line-PG for Iimp D1 Up ≤ 1600 V
Voltage protection level line-line for In C2 Up ≤ 35 V
Voltage protection level line-PG for In C2 Up ≤ 1800 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 20 V
Voltage protection level line-PG at 1 kV/µs C3 Up ≤ 1400 V
Cut-off frequency line-line fG 100 MHz
Capacitance line-line C ≤ 25 nF
Capacitance line-PG C ≤ 20 pF
Operating temperature range -40°C...+80°C
Degree of protection (plugged-in) IP 20
For plugging into base part
Earthing via base part
Enclosure material polyamide PA 6.6
Colour blue
Test standards IEC 61643-21
SIL classification SIL2 for more details see: www.dehn.de/en/sil/
Ex certifications ATEX: KEMA 06ATEX0274 X: II 2 G Ex ib IIC T4 ... T6

Ordering information
Type BXT ML2 BD HF EX 6
Part No. 920 538
Packing unit 1 pc(s).

920 301
EX
BXT BAS
BXT BAS EX 910 695
MCM XT
DRC

DRC MCM XT
910 653
M3
DRC LC

DRC LC M3+
Base part for use as a feed-through terminal in DIN rail mounted device with integrated Portable device with LifeCheck sensor for
BXT BAS EX
920 301
intrinsically safe circuits for the insertion of DRC MCM XT
LifeCheck sensor for status-oriented monitor- DRC LC M3
flexible use. For fast and easy testing of
SPD modules without signal interruption.
910 695 Ableiterprüfgerät LifeCheck 910 653

ing of max. 10 BXT devices with LifeCheck LifeCheck-equipped arresters.


PU Part function. PU Part
Type pc(s). No. PU Part Type pc(s). No.
BXT BAS EX 1 920 301 Type pc(s). No. DRC LC M3+ 1 910 653
DRC MCM XT 1 910 695

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 313/317/318/319/360/362.

316 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Accessories for BLITZDUCTOR® XT Ex (i)
920 308 BXT M4 E

SPDs FOR POTENTIALLY EXPLOSIVE AREAS Earthing module

BXT M4 E
920 308
1 1´

2 2´

protected

3 3´

4 4´

Dimension drawing BXT M4 E Basic circuit diagram BXT M4 E • For plugging onto BLITZDUCTOR XT
base parts
The plugged-in earthing module short-circuits all lines connected to the BLITZDUCTOR XT base part • Easy handling
to PG. It directly earths initially used cable cores, which are already connected to the base part.
• Quick replacement when retrofitting
an SPD module

BXT M4 E
D1 Total lightning impulse current (10/350 μs) Iimp 10 kA
Operating temperature range -40°C...+80°C
Degree of protection (plugged-in) IP 20
For plugging into base part
Enclosure material polyamide PA 6.6
Colour grey

Ordering information
Type BXT M4 E
Part No. 920 308
Packing unit 1 pc(s).

920 398 BS BA1 BA15 BXT


Marking system BA1-BA15
NEW

BS BA1 BA15 BXT


920 398

• For DRC MCM XT condition monitor-


ing systems
2 x 165 adhesive labels for labelling DRC MCM XT monitoring devices with their bus address • Abrasion-proof
(BA1 to BA15) and BXT base parts or modules with consecutive numbers (1.1-1.10 to 15.1-15.10)
• Pre-printed
• Transparent

BS BA1 BA15 BXT


Dimension W x H 13 x 7 mm

Ordering information
Type BS BA1 BA15 BXT
Part No. 920 398
Packing unit 1 pc(s).

www.dehn.de 317
Accessories for BLITZDUCTOR® XT Ex (i) INFORMATION TECHNOLOGY SYSTEMS
920 309 BXT M4 T

Test / Disconnection Module SPDs FOR POTENTIALLY EXPLOSIVE AREAS

BXT M4 T
920 309

1 1´

2 2´

3 3´

4 4´

• For plugging into the BLITZDUCTOR XT Basic circuit diagram BXT M4 T Dimension drawing BXT M4 T
base part
• Easy maintenance and troubleshooting The plugged-in test/disconnection module interrupts the cable run of the lines connected to the
BLITZDUCTOR XT base part and leads them to a test socket at the front side of the module. This
• Measuring lines included
allows to carry out measurements in the installation without removing the lines from the base part.

BXT M4 T
Max. continuous operating d.c. voltage UC 180 V
Max. continuous operating a.c. voltage UC 127 V
Nominal current at 80° C IL 1.0 A
Volume resistance 0.1 ohm
Operating temperature range -40°C ... +80°C
Degree of protection (plugged-in) IP 20
For plugging into base part
Test sockets gold-plated, 1 mm
Enclosure material polyamide PA 6.6
Colour grey
Accessories 2 measuring lines (1 m), protective bag

Ordering information
Type BXT M4 T
Part No. 920 309
Packing unit 1 pc(s).

Marking system 1-50 920 399 BS 1 50 BXT

BS 1 50 BXT
920 399

• Abrasion-proof
• Pre-printed Plate with 2 plate numbers from 1 to 50 for attaching to BXT base parts or modules.

BS 1 50 BXT
Dimension W x H 11 x 4 mm

Ordering information
Type BS 1 50 BXT
Part No. 920 399
Packing unit 1 pc(s).

318 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Accessories for BLITZDUCTOR® XT Ex (i)
910 697 TW DRC MCM EX

SPDs FOR POTENTIALLY EXPLOSIVE AREAS Partition

TW DRC MCM EX
NEW
910 697

137 2.5

76
90

Dimensional drawing of the partition • Allows non-intrinsically circuits to be


placed directly next to Ex i circuits
For DRC MCM XT (space gain)
Certain installation instructions have to be observed when using Blitzductor XT Ex (i) surge protective • Increase of the thread measure to
devices in intrinsically safe circuits. * 50 mm in accordance with
In accordance with EN 60079-11;2007 a minimum distance (thread measure) of * 50 mm has to be EN 60079-11
maintained between intrinsically and non-intrinsically safe circuits (connecting parts, e.g. terminals)!
• Suitable for mounting rails with
When using the Ex i partition of type TW DRC MCM EX, this distance is also maintained if the surge
a height of 7.5 mm and 15 mm
protective devices are arranged directly next to one other.
• Easy installation by simply snapping
the partition onto a mounting rail

TW DRC MCM EX
Material polyamide PA 6.6
Colour blue
For mounting on 35 mm DIN rail according to EN 60715

Ordering information
Type TW DRC MCM EX
Part No. 910 697
Packing unit 1 pc(s).

www.dehn.de 319
ITAK Ex (i) INFORMATION TECHNOLOGY SYSTEMS
Surge arrester SPDs FOR POTENTIALLY EXPLOSIVE AREAS

• Prewired unit
• Built-in SPD, tested according to ATEX and FISCO
requirements
• Further customised versions available on request

Example: ITAK for use in intrinsically safe circuits.

ITAK stands for the German designation “Informationstechnik- tomer specifications. Our standard product range includes e.g. ITAK EXI
Anschaltkasten“ [English: switchbox for information technology systems]. BXT 24, a combination of ALGA 5 X enclosure and BXT BD EX 24 for pro-
Generally, ITAKs are a combination of enclosure, SPDs and terminals or tecting two intrinsically safe measuring circuits in outdoor systems.
shield terminals. These switchboxes can be produced according to cus-

320 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS ITAK Ex (i)
989 408 ITAK EXI
BXT 24

SPDs FOR POTENTIALLY EXPLOSIVE AREAS ITAK EXI BXT

ITAK EXI BXT 24


989 408
1 1´

2 2´

3 3´

4 4´

Dimension drawing ITAK EXI BXT The RFID chip of the LifeCheck SPD monitoring • Prewired unit for 2 Ex(i) circuits
system can be read out without contact via
DEHNrecord LC. Insulation resistance • Self-capacitance and self-inductance
> 500 V line-earth. negligibly small
• For installation in conformity with the
BXT ML4 BD EX 24 and BXT BAS EX – Completely mounted, meets FISCO requirements. lightning protection zones concept at
the boundaries from 0B - 2 and higher

ITAK EXI BXT 24


SPD class T
SPD monitoring system LifeCheck
Nominal voltage UN 24 V
Max. continuous operating d.c. voltage Uc 33 V
Max. input voltage acc. to EN 50020 Ui 30 V
Max. input current acc. EN 50020 Ii 0.5 A
Total nominal discharge current (8/20 μs) In 20 kA
Nominal discharge current (8/20 μs) per line In 5 kA
Voltage protection level line-line for In C2 Up ) 52 V
Voltage protection level line-PG for In C2 Up ) 1400 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 45 V
Voltage protection level line-PG at 1 kV/μs C3 UP ) 1100 V
Series impedance per line 1.0 ohm
Cut-off frequency line-line fG 7.7 MHz
Capacitance line-line C 0.8 nF
Operating temperature range -40°C...+80°C
Degree of protection IP 65
For mounting on wall in Ex zones 1, 2
Connection input/output cable gland M20 x 1.5
Cross-sectional area, solid 0.08 - 4 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Cross-sectional area of equipotential bonding 4 mm2
Tightening torque (terminal) 0.4 Nm
Earthing via screw terminal at enclosure panel
Enclosure material grey aluminium
Test standards for installed BXT IEC 61643-21, UL 497B
Approvals, Certifications for installed BXT ATEX, CSA

Ordering information
Type ITAK EXI BXT 24
Part No. 989 408
Packing unit 1 pc(s).

Accessory Part for ITAK Ex (i)


Mounting set 906 059
5X
MS ALGA

For ALGA 5 X enclosures for fixing at masts and pipes.


Enclosure PU Part MS ALGA 5 X
Set for Enclosures
Mounting
906 059

Type material pc(s). No.


MS ALGA 5 X StSt 1 906 059

www.dehn.de 321
DEHNconnect RK Ex (i) INFORMATION TECHNOLOGY SYSTEMS
Terminal block with integrated SPDs FOR POTENTIALLY EXPLOSIVE AREAS
surge protection

• Extremely space-saving (only 6 mm in width)


• Spring pressure connection system
• Tested by KEMA according to ATEX and FISCO
requirements

6 mm two-pole terminal block with integrated surge protection and cage


clamp terminal. Earthing via DIN rail or terminal.

DEHNconnect RK MD EX is a 6 mm terminal block with integrated surge mechanism at the supporting foot of the base part allows the arrester to
protection for intrinsically safe circuits. 2 lines can be protected with the be safely earthed via the DIN rail. As the enclosure of the arrester is open
5 cage clamp spring measuring connections and additional equipotential to one side to minimise the width, it is advisable to use a cover plate at
bonding to the terminal equipment can be established. The snap-in fixing the end of each terminal block.

application

Zones 1, 2

DEHNconnect RK EX 24

DCO RK MD EX with cover cable length max. 1m


Zone 0
min. 4 mm 2 min. 4 mm2

EB

Application in an Ex(i) circuit

322 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNconnect RK Ex (i)
919 960 DCO RK
MD EX 24

SPDs FOR POTENTIALLY EXPLOSIVE AREAS DCO RK MD EX

DCO RK MD EX 24
DEHNconnect RK 24 V EX 919 960

1 3

2 4

IN OUT

Dimension drawing DCO RK MD EX Low-capacitance, energy-coordinated protective • For universal use


circuit with an insulation resistance > 500 V to
earth. • Self-capacitance and self-inductance
negligibly small
Surge arrester for protecting intrinsically safe measuring circuits and bus systems, meets FISCO • For installation in conformity with the
requirements. lightning protection zones concept at
the boundaries from 0B – 2 and higher

DCO RK MD EX 24
SPD class T
Nominal voltage UN 24 V
Max. continuous operating d.c. voltage Uc 33 V
Max. continuous operating a.c. voltage Uc 23 V
Max. input voltage acc. to EN 50020 Ui 30 V
Max. input current acc. to EN 50020 Ii 0.5 A
Nominal current IL 0.5 A
C2 Total nominal discharge current (8/20 μs) In 10 kA
C2 Nominal discharge current (8/20 μs) per line In 5 kA
Voltage protection level line-line for In C2 Up ) 50 V
Voltage protection level line-PG for In C2 Up ) 1500 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 45 V
Voltage protection level line-PG at 1 kV/μs C3 Up ) 1400 V
Series impedance per line 1.8 ohms
Cut-off frequency line-line fG 6 MHz
Capacitance line-line C ) 1 nF
Capacitance line-PG C ) 6 pF
Operating temperature range -40°C...+80°C
Degree of protection IP 00, with cover IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output spring / spring
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Earthing via DIN rail / terminal
Enclosure material polyamide PA 6.6
Colour blue
Test standards IEC 61643-21
Ex certifications ATEX: KEMA 09ATEX0124 X: II 2 (1) G Ex ia IIC T4 ... T6
Approvals, Certifications GOST

Ordering information
Type DCO RK MD EX 24
Part No. 919 960
Packing unit 1 pc(s).

Accessory Part for DEHNconnect RK Ex (i) Accessory Part for DEHNconnect RK Ex (i)
Quick marking system, horizontal imprint 919 977
DCO RK
BS 1 50

Covering plate 919 978


RK BL
AD DCO

Plate with 2 plate numbers from 1 to 50 for DCO RK, horizontal imprint For DCO RK
PU Part BS 1 50 DCO RK
Marking System for DCO RK
Quick
919 977 PU Part AD DCO RK BL
Plate for DCO, blue
Covering
919 978

Type Material pc(s). No. Type Enclosure material Colour pc(s). No.
BS 1 50 DCO RK plastic 1 919 977 AD DCO RK BL polyamide PA 6.6 blue 1 919 978

www.dehn.de 323
DEHNconnect RK Ex (i) INFORMATION TECHNOLOGY SYSTEMS
Terminal block with integrated SPDs FOR POTENTIALLY EXPLOSIVE AREAS
surge protection

EC-Type Examination Certificate for DCO RK MD EX

324 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Shield Connection on Anchor Bars
ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

• Tested with lightning impulse currents up to


10 kA (10/350 μs)
• Corrosion-resistant stainless steel material
• Permanent shield connection due to spring ele-
ment

Shield connection system for anchor bars which is capable of carrying


lightning currents. The yield of the cable materials used is compensated
by a slipping spring element.

Shield connection system, tested with lightning currents, for specific use
on anchor bars. As, in the course of time, the conductor materials are sub-
ject to a yield, this yield is compensated by a slipping spring element. The
shield connection of the rail types can also be installed using adequate
insulating elements after isolating it from local potential.

This very robust shield connection


system is particularly suited for
cables with medium-sized diame-
ters. It has been tested with light-
ning currents and was approved
for nuclear installations.

Application on anchor bars

www.dehn.de 325
Shield Connection on Anchor Bars INFORMATION TECHNOLOGY SYSTEMS
308 403 SAK 10 AS V4A
308 404 SAK 14 AS V4A

Shield terminals ACCESSORIES FOR TERMINAL BLOCK SYSTEMS


308 405 SAK 18 AS V4A
308 406 SAK 21 AS V4A
308 407 SAK 26 AS V4A
308 408 SAK 33 AS V4A

SAK 10 AS V4A Shielding Terminal,


stainless steel, Rd 5-10 308 403
SAK 14 AS V4A Shielding Terminal,
stainless steel, Rd 8-14 308 404
SAK 18 AS V4A Shielding Terminal,
stainless steel, Rd 13-18 308 405
SAK 21 AS V4A Shielding Terminal,
stainless steel, Rd 17-21 308 406
SAK 26 AS V4A Shielding Terminal,
stainless steel, Rd 19-26 308 407
SAK 33 AS V4A Shielding Terminal,
stainless steel, Rd 25-33 308 408

• System for anchor bars which is capa- Dimension drawing SAK


ble of carrying lightning currents
• Shield support with large surface Shield terminals for earthing cable shields on anchor bars. Suitable for lightning equipotential
bonding purposes. Allows for subsequent use without interrupting the cable shield – no tools
• Compensates the yield of cable
required for installation. Approved for use in nuclear facilities with TÜV test certificate ETL 10/PB
materials
301/97 (TÜV = German Technical Inspectorate).

SAK 10 AS V4A SAK 14 AS V4A SAK 18 AS V4A SAK 21 AS V4A SAK 26 AS V4A SAK 33 AS V4A
Lightning impulse current capacity (10/350 μs) 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA
Clamping range Rd 5 - 10 mm 8 - 14 mm 13 - 18 mm 17 - 21 mm 19 - 26 mm 25 - 33 mm
Material StSt StSt StSt StSt StSt StSt
Spring pressure 21 - 27 N 30 - 76 N 34 - 73 N 30 - 63 N 90 - 124 N 76 - 137 N
For mounting on anchor bar anchor bar anchor bar anchor bar anchor bar anchor bar
Dimension W x L x H 16 x 40 x 48 mm 19.5 x 40 x 50 mm 24 x 40 x 56 mm 29 x 40 x 59 mm 36.5 x 40 x 74 mm 45 x 40 x 82 mm
Approvals, Certifications ETL 10/PB 301/97 ETL 10/PB 301/97 ETL 10/PB 301/97 ETL 10/PB 301/97 ETL 10/PB 301/97 ETL 10/PB 301/97

Ordering information
Type SAK 10 AS V4A SAK 14 AS V4A SAK 18 AS V4A SAK 21 AS V4A SAK 26 AS V4A SAK 33 AS V4A
Part No. 308 403 308 404 308 405 308 406 308 407 308 408
Packing unit 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s).

308 421 AS SAK


1000 V2A

Anchor bar

AS SAK 1000 V2A Anchor


Bar, stainless steel, 1 m long 308 421

• Can be cut to length according to Dimension drawing AS SAK 1000 V2A


requirements
Mounting rail for earthing and fixing the shield terminals.

AS SAK 1000 V2A


Material StSt
Dimension W x L x H 29 x 1000 x 15 mm
Approvals, Certifications ETL 10/PB 301/97

Ordering information
Type AS SAK 1000 V2A
Part No. 308 421
Packing unit 10 pc(s).

326 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Shield Connection on Anchor Bars
308 425 ST AS
SAK K

ACCESSORIES FOR TERMINAL BLOCK SYSTEMS Insulated busbar support

ST AS SAK K Bar
Support, plastic 308 425

Dimension drawing ST AS SAK K • Non-conductive connection of mount-


ing plate and anchor bar
Busbar support for insulated fixing of the AS SAK 1000 V2A anchor bar, with M4 threaded socket. • Equipotential bonding via AK 16 AS
SAK MS terminal

ST AS SAK K
Material plastic
Approvals, Certifications ETL 10/PB 301/97

Ordering information
Type ST AS SAK K
Part No. 308 425
Packing unit 10 pc(s).

308 411 AK 16 AS
SAK MS

Terminal
AK 16 AS SAK MS Protective
Conductor Terminal, -16 mm3 308 411

Dimension drawing AK 16 AS SAK MS • Space-saving


• 2 fixing screws for conductor included
For connecting equipotential bonding conductors to AS SAK 1000 V2A anchor bars.

AK 16 AS SAK MS
Cross-sectional area, solid 16 mm2
For mounting on anchor bar
Approvals, Certifications ETL 10/PB 301/97

Ordering information
Type AK 16 AS SAK MS
Part No. 308 411
Packing unit 5 pc(s).

www.dehn.de 327
Shield Connection on DIN Rails INFORMATION TECHNOLOGY SYSTEMS
ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

• Tested with lightning impulse currents up to


5 kA (10/350 μs)
• Corrosion-resistant stainless steel material
• Permanent shield connection with spring ele-
ment

Shield connection system with lightning current carrying capability, partic-


ularly suited for smaller cables, for DIN rails with slipping spring element
for compensating the yield of the cable materials.

Shield connection system, tested with lightning currents, for versatile materials are subject to a yield, this is compensated by a slipping spring
applications in DIN rail installations. Suitable especially for smaller cable element. The shield connection of the rail types can also be installed using
diameters such as bus cables. As, in the course of time, the conductor adequate insulating elements after isolating it from local potential.

328 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Shield Connection on DIN Rails
919 010 SAK 6.5
SN MS

ACCESSORIES FOR TERMINAL BLOCK SYSTEMS Shield terminals


919 011 SAK 11
SN MS

SAK 6.5 SN MS Shielding


Terminal round wire 1,5-6,5 919 010
SAK 11 SN MS Shielding
Terminal 5-B42211 919 011

Dimension drawing SAK • Lightning current carrying system for


busbars
Shield terminals for earthing cable shields on busbars (18x3). Suitable for lightning equipotential • Shield support with large surface
bonding purposes. Allows for subsequent use without interruption of the cable shield – no tools
• Compensates the yield of cable mate-
required for installation.
rials

SAK 6.5 SN MS SAK 11 SN MS


Lightning impulse current capacity (10/350 μs) 5 kA 5 kA
Clamping range Rd 1.5 - 6.5 mm 5 - 11 mm
Material nickel-plated brass nickel-plated brass
Spring pressure 8 - 13 N 22 - 31 N
For mounting on SN 18x3 CU 1000 SN 18x3 CU 1000
Dimension W x L x H 10 x 25 x 40 mm 17 x 25 x 47 mm

Ordering information
Type SAK 6.5 SN MS SAK 11 SN MS
Part No. 919 010 919 011
Packing unit 10 pc(s). 10 pc(s).

919 016 SN 18X3


CU 1000

Busbar

SN 18X3 CU 1000 Busbar,


tinned 919 016

Dimension drawing SN 18X3 CU 1000 • Can be cut to length according to


requirements
Mounting rail for shield terminals. Can be mounted onto the busbar supports. • Can be mounted onto busbar supports

SN 18X3 CU 1000
Material tin-plated copper
For mounting on bar holder
Dimension W x L x H 18 x 1000 x 3 mm

Ordering information
Type SN 18X3 CU 1000
Part No. 919 016
Packing unit 1 pc(s).

www.dehn.de 329
Shield Connection on DIN Rails INFORMATION TECHNOLOGY SYSTEMS
919 012 SH1 18X3
ST

Rail support ACCESSORIES FOR TERMINAL BLOCK SYSTEMS


919 013 SH2 18X3
ST

SH1 18X3 ST Bar


Holder, steel 919 012
SH2 18X3 ST Bar
Holder ISO 919 013

• Extremely space-saving Dimension drawing SH1 18X3 ST Dimension drawing SH2 18X3 ST
• With one or two shield terminals
Rail support for earthed construction, suitable for DIN rail mounting. Low-impedance connection
• For 35 mm DIN rails acc. to EN 60715
of the shield terminals to the DIN rail via the busbar.

SH1 18X3 ST SH2 18X3 ST


Version 1 shield terminal 2 shield terminals
Material tin-plated steel tin-plated steel
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Ordering information
Type SH1 18X3 ST SH2 18X3 ST
Part No. 919 012 919 013
Packing unit 1 pc(s). 1 pc(s).

919 014 SH 18X3


K

Insulated rail support

SH 18X3 K Bar
Holder, plastic 919 014

• No conductive connection from bus- Dimension drawing SH 18X3 K


bar to DIN rail
• Equipotential bonding via AK 35 SN
18X3 GG terminal Rail support for insulated installation, for DIN rail mounting or screw connection.

SH 18X3 K
Material plastic
Colour black
For mounting on DIN rail or mounting plate

Ordering information
Type SH 18X3 K
Part No. 919 014
Packing unit 10 pc(s).

330 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Shield Connection on DIN Rails
919 015 AK 35 SN
18X3 GG

ACCESSORIES FOR TERMINAL BLOCK SYSTEMS Terminal

AK 35 SN 18X3 GG Terminal
for Busbar 919 015

Dimension drawing AK 35 SN 18X3 GG • Wide cross-sectional area


• For insulated shield construction with
Particularly suited for insulated busbar constructions, e.g. for indirect shield earthing. SH 18X3 K

AK 35 SN 18X3 GG
Cross-sectional area, solid 35 mm2
For mounting on busbar

Ordering information
Type AK 35 SN 18X3 GG
Part No. 919 015
Packing unit 1 pc(s).

www.dehn.de 331
Shield Connection for Cables INFORMATION TECHNOLOGY SYSTEMS
ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

• Tested with lightning impulse currents up to


10 kA (10/350 μs)
• Extremely space-saving
• Permanent shield connection with spring ele-
ment

Extremely space-saving shield connection system for use as constant


force spring. A spring element compensates the yield of the cable materi-
als used.

The shields of incoming IT and power supply lines can be contacted by conductor materials are subject to a yield, this can be compensated by a
means of constant force springs of type SA KRF in a space-saving way and spring element. For permanent corrosion protection of the clamping point,
with lightning current carrying capability. As, in the course of time, the it is wrapped with a self-bonding SKB rubber tape.

Test certificate for constant force spring of type SA KRF ...

332 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Shield Connection for Cables
919 031 SA KRF
10 V2A

ACCESSORIES FOR TERMINAL BLOCK SYSTEMS Constant force spring


919 032 SA KRF
15 V2A
919 033 SA KRF
22 V2A
919 034 SA KRF
29 V2A
919 035 SA KRF
37 V2A
919 036 SA KRF
50 V2A
919 037 SA KRF
70 V2A
919 038 SA KRF
94 V2A

SA KRF 10 V2A Contact


Force Spring for shield connection 919 031
SA KRF 15 V2A Contact
Force Spring for shield connection 919 032
SA KRF 22 V2A Contact
Force Spring for shield connection 919 033
SA KRF 29 V2A Contact
Force Spring for shield connection 919 034
SA KRF 37 V2A Contact
Force Spring for shield connection 919 035
SA KRF 50 V2A Contact
Force Spring for shield connection 919 036
SA KRF 70 V2A Contact
Force Spring for shield connection 919 037
SA KRF 94 V2A Contact
Force Spring for shield connection 919 038

• For solderless connection of a con-


ductor to the shield
Constant force springs allow solderless shield connections for equipotential bonding or lightning • For use with all plastic and lead-
equipotential bonding. They can be installed subsequently without interrupting the conductor sheathed cables
shield or requiring tools for installation. Approved for nuclear installations according to TÜV • Also suitable for steel-reinforced
Certificate No. T12-04-ETL003 (TÜV = German Technical Inspectorate). lead-sheathed cables

SA KRF ... 10 V2A 15 V2A 22 V2A 29 V2A 37 V2A 50 V2A 70 V2A 94 V2A
Lightning impulse current
10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA
capacity (10/350 μs)
Clamping range Rd 4 - 10 mm 9 - 15 mm 14 - 22 mm 18.5 - 29 mm 23.5 - 37 mm 31 - 50 mm 44 - 70 mm 58 - 94 mm
Material StSt StSt StSt StSt StSt StSt StSt StSt
Colour bare bare bare bare bare bare bare bare
For mounting on cable shield cable shield cable shield cable shield cable shield cable shield cable shield cable shield
Approvals, Certifications T12-04-ETL 003 T12-04-ETL003 T12-04-ETL003 T12-04-ETL003 T12-04-ETL003 T12-04-ETL003 T12-04-ETL003 T12-04-ETL003

Ordering information
Type SA KRF 10 V2A SA KRF 15 V2A SA KRF 22 V2A SA KRF 29 V2A SA KRF 37 V2A SA KRF 50 V2A SA KRF 70 V2A SA KRF 94 V2A
Part No. 919 031 919 032 919 033 919 034 919 035 919 036 919 037 919 038
Packing unit 20 pc(s). 20 pc(s). 20 pc(s). 10 pc(s). 10 pc(s). 25 pc(s). 20 pc(s). 10 pc(s).

919 030 SKB 19


9M SW

Self-bonding rubber tape

SKB 19 9M SW
Selfbonding Rubber Tape 919 030

Roll with 9 m self-bonding rubber tape for • Self-bonding


wrapping around constant force springs for • Flexible
permanent corrosion protection.

SKB 19 9M SW
Colour black
Dimension W x L x H tape: 9 m x 19 mm

Ordering information
Type SKB 19 9M SW
Part No. 919 030
Packing unit 1 pc(s).

www.dehn.de 333
Enclosure / Protective Conductor Terminal INFORMATION TECHNOLOGY SYSTEMS
906 055 ALGA 5

Aluminium enclosure ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

ALGA 5
Aluminium Enclosure IP65 906 055

• DIN rail integrated Dimension drawing of aluminium enclosure


• Different types available on request
For installing DIN rail mounted devices. With
2 brass glands PG 11.

ALGA 5
Degree of protection IP 65
For mounting on wall
Dimension W x H x D 100 x 200 x 81 mm
Installation space 6 mods.
Enclosure material aluminium

Ordering information
Type ALGA 5
Part No. 906 055
Packing unit 1 pc(s).

906 058 ALGA 5 X

Aluminium enclosure for Ex(i) surge arresters

ALGA 5 X
Aluminium Enclosure IP65 for BCT 906 058

• DIN rail integrated Dimension drawing of aluminium enclosure for


Ex(i) surge arresters
• All cables entering from below
With 4 plastic glands M20 x 1.5, sealable,
pressure compensating membrane.

ALGA 5 X
Degree of protection IP 65
For mounting on wall
Dimension W x H x D 160 x 100 x 85 mm
Installation space 6 mods., DIN 43880
Enclosure material aluminium

Ordering information
Type ALGA 5 X
Part No. 906 058
Packing unit 1 pc(s).

334 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Enclosure / Protective Conductor Terminal
906 059 MS ALGA
5X

ACCESSORIES FOR TERMINAL BLOCK SYSTEMS Mounting set

MS ALGA 5 X Mounting
Set for Enclosures 906 059

For ALGA 5 X enclosures for fixing at masts • Stainless steel


and pipes. • For rough environmental conditions

MS ALGA 5 X
For mounting on mast, pipe for diameters 25 - 140 mm
Enclosure material StSt

Ordering information
Type MS ALGA 5 X
Part No. 906 059
Packing unit 1 pc(s).

910 099 SLK 16

Protective conductor terminal

SLK 16 PE
Terminal 910 099

Dimension drawing of protective conductor terminal • With lightning current carrying capa-
bility
For installing DIN rail mounted devices. For
earthing DIN rails, width: 12 mm.

SLK 16
Cross-sectional area, flexible 6 - 16 mm2
Cross-sectional area, solid 6 - 25 mm2
For mounting on DIN rail acc. to EN 60715
Enclosure material green-yellow polyamide 6.6

Ordering information
Type SLK 16
Part No. 910 099
Packing unit 1 pc(s).

www.dehn.de 335
336 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNprotector
COMBINED ADAPTERS Surge arrester

• Surge protective adapter with a modern design


for quick retrofitting
• Easy integration of the power supply and data
side of a terminal device into equipotential
bonding

Combined surge protective adapter for plugging into earthed socket out-
lets, with visual operating state and fault indication.

The SPDs of the Protector family for plugging into earthed socket outlets retrofitting of SPDs easier. The surge protection of the power supply side
protect consumers with additional data interfaces. Surges will be dischar- provides a visual operating state and fault indicator to facilitate mainten-
ged via the PE pin of the socket outlet. The plug-in installation makes ance.

socket outlet ISDN S0 socket outlet with ISDN


TAE/F earth contact RJ 45 earth contact fax / telephone
telephone
systems
or
router
PROTECTOR

PROTECTOR

TAE/F
NTBA
or
splitter

Application of DPRO 230 NT Application of DPRO 230 ISDN

socket outlet with socket outlet with


LAN earth contact earth contact TV
PC
TV
PROTECTOR
PROTECTOR

Application of DPRO 230 LAN100 Application of DPRO 230 TV

Note
For further types of surge protective adapters for protecting the mains
supply of electronic devices please also refer to pages 138 – 140.

www.dehn.de 337
DEHNprotector INFORMATION TECHNOLOGY SYSTEMS
909 300 DPRO 230
TV

DPRO 230 TV COMBINED ADAPTERS

Protection for the data side DPRO 230 TV / DPRO 230 SE TV DPRO 230 TV

909 300

SPD class B
Max. continuous operating d.c. voltage UC 60 V
C2 Nominal discharge current (8/20 μs) line-shield (PE) In 5 kA
Voltage protection level line-shield (PE) at 1 kV/μs C3 Up ) 600 V
Insertion loss 0-2400 MHz ) 1.5 dB
Operating temperature range -25°C...+40°C
Degree of protection IP 20
Connection input / output F socket / F socket
Earthing via protective conductor connection
Enclosure material thermoplastic, UL 94 V-2
• Protection for TV or radio applicati-
ons with a modern design Colour pure white
Test standards IEC 61643-21
• Adapter for F sockets to IEC terminals
included Protection for the power side DPRO 230 TV / DPRO 230 SE TV
• For installation in conformity with the SPD according to EN 61643-11 Type 3
lightning protection zones concept at SPD according to IEC 61643-1 Class III
the boundaries from 2 – 3 and higher Nominal a.c. voltage UN 230 V
Max. continuous operating a.c. voltage Uc 255 V
Combined surge protection for power and
Nominal load current IL 16 A
antenna sides of TV, radio or video systems.
Nominal discharge current (8/20 μs) L-N In 3 kA
With visual operating state and fault indica-
tion. Nominal discharge current (8/20 μs) L/N-PE In 5 kA [(L+N)-PE]
Combined impulse (1.2/50 μs - 8/20 μs) L-N Uoc 6 kV
Combined impulse (1.2/50 μs - 8/20 μs) L/N-PE Uoc 10 kV [(L+N)-PE]
Voltage protection level L-N Up ) 1.25 kV
Voltage protection level L/N-PE Up ) 1.5 kV
L/N Response time L-N tA ) 25 ns
Response time L/N-PE tA ) 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
red
L'/N' Short-circuit withstand capability
PE green PE for max. mains-side overcurrent protection 6 kArms a.c.
Temporary overvoltage (TOV) L-N UT 335 V/5 sec
N'/L'
Temporary overvoltage (TOV) L/N-PE (1) UT 400 V/5 sec
Temporary overvoltage (TOV) L/N-PE (2) UT 1200 V+U0 /200 ms
N/L
Fault indication red light
Operating state indication green light
For mounting on plug-in system with centre earthing contact system
earth contact according to CEE 7,
DIN 49440/DIN 49441 standard sheet V
Test standards IEC 61643-11

Protection for the data side: A gas discharge tube Ordering information
discharges potential surges to PE. Type DPRO 230 TV DPRO 230 SE TV
Part No. 909 300 909 305
Packing unit 1 pc(s). 1 pc(s).

Dimension drawing DPRO TV

338 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNprotector
909 310 DPRO 230
NT

COMBINED ADAPTERS DPRO 230 NT

DPRO 230 NT
909 310
Protection for the data side DPRO 230 NT / DPRO 230 SE NT
SPD class R
Max. continuous operating d.c. voltage UC 180 V
C2 Nominal discharge current (8/20 μs) per line C2 In 2.5 kA
Voltage protection level line-line for In C2 Up ) 300 V
Voltage protection level line-PE for In C2 Up ) 500 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 300 V
Voltage protection level line-PE at 1 kV/μs C3 Up ) 500 V
Cut-off frequency line-line fG 50 MHz
Operating temperature range -25°C...+40°C
Degree of protection IP 20
• Protection for a telecommunication
Connection input / output RJ12 socket / RJ12 socket terminal device with a modern design
Pinning 3/4
• Includes accessories, suitable for RJ
Earthing via protective conductor connection
11/12 and TAE connections
Enclosure material thermoplastic, UL 94 V-2
• For installation in conformity with the
Colour pure white
lightning protection zones concept at
Test standards IEC 61643-21
the boundaries from 2 – 3 and higher
Protection for the power side DPRO 230 NT / DPRO 230 SE NT
Combined surge protection for power and
SPD according to EN 61643-11 Type 3
data sides of a digital network termination
SPD according to IEC 61643-1 Class III
(NT). Also suitable for telephones and fax
Nominal a.c. voltage UN 230 V machines. With visual operating state and
Max. continuous operating a.c. voltage Uc 255 V fault indication.
Nominal load current IL 16 A
Nominal discharge current (8/20 μs) L-N In 3 kA
Nominal discharge current (8/20 μs) L/N-PE In 5 kA [(L+N)-PE]
Combined impulse (1.2/50 μs - 8/20 μs) L-N Uoc 6 kV L/N

Combined impulse (1.2/50 μs - 8/20 μs) L/N-PE Uoc 10 kV [(L+N)-PE]


Voltage protection level L-N Up ) 1.25 kV red
L'/N'
Voltage protection level L/N-PE Up ) 1.5 kV
PE green PE
Response time L-N tA ) 25 ns
Response time L/N-PE tA ) 100 ns N'/L'
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
Short-circuit withstand capability N/L
for max. mains-side overcurrent protection 6 kArms a.c.
3 3’
Temporary overvoltage (TOV) L-N UT 335 V/5 sec
Temporary overvoltage (TOV) L/N-PE (1) UT 400 V/5 sec
4 4’
Temporary overvoltage (TOV) L/N-PE (2) UT 1200 V+U0 /200 ms
2 2’
Fault indication red light
5 5’
Operating state indication green light
For mounting on plug-in system with centre earthing contact system
earth contact according to CEE 7, Protection for the data side: Also suitable for
digital interfaces due to low-capacitance circuit
DIN 49440/DIN 49441 standard sheet V design
Test standards IEC 61643-11

Ordering information
Type DPRO 230 NT DPRO 230 SE NT
Part No. 909 310 909 315
Packing unit 1 pc(s). 1 pc(s).

Dimension drawing DPRO NT

www.dehn.de 339
DEHNprotector INFORMATION TECHNOLOGY SYSTEMS
909 320 DPRO 230
ISDN

DPRO 230 ISDN COMBINED ADAPTERS

Protection for the data side DPRO 230 ISDN / DPRO 230 SE ISDN DPRO 230 ISDN
909 320

SPD class Q
Max. continuous operating d.c. voltage UC 48 V
C2 Nominal discharge current (8/20 μs) line-line In 120 A
C2 Nominal discharge current (8/20 μs) line-PE In 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 10 kA
Voltage protection level line-line for In C2 Up ) 100 V
Voltage protection level line-PE for In C2 Up ) 500 V
Voltage protection level line-line at 1 kV/μs C3 Up ) 80 V
Voltage protection level line-PE at 1 kV/μs C3 Up ) 500 V
Cut-off frequency line-line fG 50 MHz
• Protection of ISDN or Ethernet appli-
cations with a modern design Operating temperature range -25°C...+40°C
Degree of protection IP 20
• Shielded patch cable (1.5 m) included
Connection input / output RJ45 shielded socket / RJ45 shielded socket
• For installation in conformity with the
Pinning 1(5)/2(4), 3/6
lightning protection zones concept at
Earthing via protective conductor connection
the boundaries from 2 – 3 and hig-
Enclosure material thermoplastic, UL 94 V-2
her
Colour pure white
Combined surge protection for the power Test standards IEC 61643-21
and ISDN S0 side of ISDN systems and devi- Protection for the power side DPRO 230 ISDN / DPRO 230 SE ISDN
ces. Shielded port allows for protection of
Ethernet 10 BT. With visual operating state SPD according to EN 61643-11 Type 3
and fault indication. SPD according to IEC 61643-1 Class III
Nominal a.c. voltage UN 230 V
Max. continuous operating a.c. voltage Uc 255 V
Nominal load current IL 16 A
Nominal discharge current (8/20 μs) L-N In 3 kA
L/N Nominal discharge current (8/20 μs) L/N-PE In 5 kA [(L+N)-PE]
Combined impulse (1.2/50 μs - 8/20 μs) L-N Uoc 6 kV
Combined impulse (1.2/50 μs - 8/20 μs) L/N-PE Uoc 10 kV [(L+N)-PE]
red
L'/N' Voltage protection level L-N Up ) 1.25 kV
green Voltage protection level L/N-PE Up ) 1.5 kV
PE PE
Response time L-N tA ) 25 ns
N'/L' Response time L/N-PE tA ) 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
N/L Short-circuit withstand capability
for max. mains-side overcurrent protection 6 kArms a.c.
1 1’
Temporary overvoltage (TOV) L-N UT 335 V/5 sec
2 2’ Temporary overvoltage (TOV) L/N-PE (1) UT 400 V/5 sec
5 5’ Temporary overvoltage (TOV) L/N-PE (2) UT 1200 V+U0 /200 ms
4 4’
Fault indication red light
3 3’
Operating state indication green light
6 6’ For mounting on plug-in system with centre earthing contact system
earth contact according to CEE 7,
DIN 49440/DIN 49441 standard sheet V
Protection of the data side: Low-capacitance
4-wire protective circuit for ISDN and Test standards IEC 61643-11
Ethernet pin assignment.
Ordering information
Type DPRO 230 ISDN DPRO 230 SE ISDN
Part No. 909 320 909 325
Packing unit 1 pc(s). 1 pc(s).

Dimension drawing DPRO ISDN

340 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNprotector
909 321 DPRO 230 LAN100

COMBINED ADAPTERS DPRO 230 LAN100

DPRO 230 LAN100


Protection for the data side DPRO 230 LAN100 / DPRO 230 SE LAN100 NEW
909 321

SPD class Q
Max. continuous operating d.c. voltage UC 58 V
C2 Nominal discharge current (8/20 μs) line-line In 30 A
C2 Nominal discharge current (8/20 μs) line-PE In 2.5 kA
C2 Total nominal discharge current (8/20 μs) In 10 kA
Voltage protection level line-line for In C2 Up ) 100 V
Voltage protection level line-PE for In C2 Up ) 500 V
Voltage protection level line-line at 1 kV/μs C3 Up 90 V
Voltage protection level line-PE at 1 kV/μs C3 Up ) 500 V
Operating temperature range -20°C...+40°C
• Protection of Ethernet applications
Degree of protection IP 20 (1000 BASE-T) with an elegant design
Connection input / output RJ45 shielded socket / RJ45 shielded socket
• Shielded Cat 5e patch cable (1.5 m)
Pinning 1/2, 3/6, 4/5, 7/8
included
Earthing via protective conductor connection
• For installation in conformity with the
Enclosure material thermoplastic, UL 94 V-2
lightning protection zones concept at
Colour pure white
the boundaries from 2 – 3 and higher
Test standards IEC 61643-21
Protection for the power side DPRO 230 LAN100 / DPRO 230 SE LAN100 Combined surge protection for the power
SPD according to EN 61643-11 Type 3
side and data input for the protection of LAN
components.
SPD according to IEC 61643-1 Class III
Meets the requirements for Channel Class D
Nominal a.c. voltage UN 230 V
in accordance with EN 50173 and is thus
Max. continuous operating a.c. voltage Uc 255 V suitable for 1000Base-T (Gigabit Ethernet).
Nominal load current IL 16 A
Nominal discharge current (8/20 μs) L-N In 3 kA
Nominal discharge current (8/20 μs) L/N-PE In 5 kA [(L+N)-PE]
Combined impulse (1.2/50 μs - 8/20 μs) L-N Uoc 6 kV L/N
Combined impulse (1.2/50 μs - 8/20 μs) L/N-PE Uoc 10 kV [(L+N)-PE]
Voltage protection level L-N Up ) 1.25 kV red
L'/N'
Voltage protection level L/N-PE Up ) 1.5 kV
PE green PE
Response time L-N tA ) 25 ns
N'/L'
Response time L/N-PE tA ) 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
N/L
Short-circuit withstand capability
1 1'
for max. mains-side overcurrent protection 6 kArms a.c.
Temporary overvoltage (TOV) L-N UT 335 V/5 sec 2 2'
3 3'
Temporary overvoltage (TOV) L/N-PE (1) UT 400 V/5 sec
Temporary overvoltage (TOV) L/N-PE (2) UT 1200 V+U0 /200 ms 6 6'
Fault indication red light 4 4'

Operating state indication green light 5 5'


For mounting on plug-in system with centre earthing contact system 7 7'

earth contact according to CEE 7, 8 8'


DIN 49440/DIN 49441 standard sheet V
Test standards IEC 61643-11
Data side: Low-capacitance protective circuit of
Ordering information all pairs for Ethernet pin assignment
Type DPRO 230 LAN100 DPRO 230 SE LAN100
Part No. 909 321 909 326
Packing unit 1 pc(s). 1 pc(s).

Dimension drawing DPRO LAN100

www.dehn.de 341
342 www.dehn.de
LIGHTNING EQUIPOTENTIAL BONDING Isolating Spark Gap
ISOLATING SPARK GAPS For lightning equipotential bonding

• For indirect connection/earthing of functionally


isolated installation components when being
affected by lightning
• For lightning equipotential bonding application
according to IEC 62305
• With corrosion-resistant stainless steel connec-
tions
• For mounting inside of buildings, outdoors, in
damp rooms as well as for underground instal-
lation
• Extremely heavy-duty devices

For lightning equipotential bonding according to IEC 62305 as well as for TFS: High-capacity isolating spark gap
use in IT installations according to IEC 60364-5-54. KFSU: Isolating spark gap

TFS / KFSU

923 023 TFS


923 021 KFSU

TFS Isolating
Spark Gap 923 023
KFSU Ex-
Isolating Spark Gap 923 021

Dimension drawing TFS / KFSU Basic circuit diagram TFS / KFSU

TFS / KFSU: Isolating spark gaps with plastic coating and 2 connections (Rd 10 mm) made of stain-
less steel

TFS KFSU
Lightning impulse current (10/350 μs) Iimp 100 kA —
Class of lightning current carrying capability acc. to EN 50164-3 H —
Nominal discharge current (8/20 μs) In 100 kA 100 kA
Rated power-frequency withstand voltage (50 Hz) UW/AC 300 V 300 V
100% Lightning impulse sparkover voltage Urimp ) 4 kV ) 4 kV
Power frequency sparkover voltage (50 Hz) Uaw ) 2.5 kV ) 2.5 kV
Operating temperature range TU -20°C...+80°C -20°C...+80°C
Degree of protection IP 65 IP 65
Length 160 mm 160 mm
Diameter of enclosure 43 mm 43 mm
Enclosure material steel-plastic coating steel-plastic coating
Connection Rd 10 mm Rd 10 mm
Material (connection) stainless steel stainless steel

Ordering information
Type TFS KFSU
Part No. 923 023 923 021
Packing unit 1 pc(s). 1 pc(s).

www.dehn.de 343
EXFS 100 / EXFS 100 KU LIGHTNING EQUIPOTENTIAL BONDING
For explosion-hazard areas ISOLATING SPARK GAPS

• For indirect connection/earthing of functionally


isolated installation components when being
affected by lightning
• Device for lightning equipotential bonding
according to IEC 62305 in explosion-hazard
areas
• For bridging insulating pieces, insulating
flanges etc. in cathodically corrosion-protected
pipe sections
• For safe installation in explosion protected zone
1 (gas) or 21 (dust)
• Especially low sparkover voltage
• Especially high a.c. current withstand capability

ATEX-certified isolating spark gap for lightning equipotential bonding


according to IEC 62305 with low sparkover voltage

EXFS 100: Isolating spark gap for use in explosion-hazard areas with plastic coating and M10 connecting thread nut
EXFS 100 KU: Isolating spark gap for use in explosion-hazard areas with 2 m connecting cable for underground installation

The Ex isolating spark gaps of the EXFS 100 / EXFS 100 KU product fam-
ily are used when conductive installation components situated in explo-
sion-hazard areas cannot be connected directly with each other.
The spark gaps with low sparkover voltage are especially efficient for iso-
lated installation components with little insulation resistance.
No special regulations have to be observed for safe application in zone 1
with gases or zone 21 with dusts.
With a maximum lightning impulse current of 100 kA (10/350 μs), EXFS
100 and EXFS 100 KU meet class H according to EN 50164-3 ”Lightning
Protection Components (LPC) – Part 3: Requirements for isolating spark
gaps”.
The ATEX-certified spark gaps EXFS 100 and EXFS 100 KU provide
approved safety according to harmonised European standards.
For connecting EXFS 100 spark gaps, prewired connecting cables with dif-
ferent lengths are available as accessories.
Flat and angled connection brackets (IF) make it easier to connect the
spark gaps to pipe flanges.
EXFS 100 KU types are enclosed by a damp-proof plastic coating and can
therefore be ideally used for underground installation at insulating cou-
plings.

Type examination certificate

344 www.dehn.de
LIGHTNING EQUIPOTENTIAL BONDING EXFS 100 / EXFS 100 KU
923 100 EXFS 100

ISOLATING SPARK GAPS EXFS 100

EXFS 100
923 100

Dimension drawing EXFS 100 Installation of EXFS 100

EXFS 100: Ex isolating spark gap with plastic coating and M10 connecting thread nuts

EXFS 100
Lightning impulse current (10/350 μs) Iimp 100 kA
Class of lightning current carrying capability acc. to EN 50164-3 H
Nominal discharge current (8/20 μs) In 100 kA
Rated power-frequency withstand voltage (50 Hz) UW/AC 250 V
100% Lightning impulse sparkover voltage Urimp ) 1.25 kV
Power-frequency sparkover voltage (50 Hz) Uaw ) 0.5 kV
Rated discharge current (50 Hz) Imax 500 A / 0.5 sec. (TU: ) 45°C)
(Ex) marking acc. to EN 60079 (gases) II 2G Ex d IIC T6
(Ex) marking according to EN 61241 (dusts) II 2D Ex tD A21 IP67 T 80°C
Operating temperature range TU -20°C...+60°C
Degree of protection IP 67
Approvals, Certifications BVS 06 ATEX E 099, IECEx KEM 09.0051...
Length of enclosure 100 mm
Diameter of enclosure 45,5 mm
Enclosure material plastic coating
Connection of enclosure thread nut M10, 2x M10x25 mm, 2x spring washer

Ordering information
Type EXFS 100
Part No. 923 100
Packing unit 1 pc(s).

Accessory Part for EXFS 100 / EXFS 100 KU Accessory Part for EXFS 100 / EXFS 100 KU
EXFS 100: Connecting cable, Cu 25 mm2 923 025
L100 KS
923 035
L200 KS
923 045
AL EXFS

AL EXFS

AL EXFS
Pair of angled connection brackets – IF 1 – 923 011

L300 KS

Connecting cable for EXFS 100; 2 cable lugs Ø10.5 mm, hexa- Pair of angled connection brackets for EXFS ...; diameter corre-
gon screw and nut (M10), StSt and spring washer AL EXFS L100 KS
923 025
AL EXFS L200 KS
sponds to bolt diameter of the bolted flange joint (d1 up to max. Connection Bracket Type IF -SET- 923 011

923 035

Cable lug Cross Cable PU Part


AL EXFS L300 KS
923 045 60 mm, please indicate the diameter required when placing
Type material section length pc(s). No. your order)
AL EXFS L100 KS Cu/gal Sn 25 mm2 100 mm 1 923 025 PU Part
AL EXFS L200 KS Cu/gal Sn 25 mm2 200 mm 1 923 035 Type Material pc(s). No.
AL EXFS L300 KS Cu/gal Sn 25 mm2 300 mm 1 923 045 IF1 St/tZn 1 923 011

Pair of flat connection brackets – IF 3 – 923 016

Pair of flat connection brackets for EXFS ...; diameter corre-


sponds to bolt diameter of the bolted flange joint (d1 up to max. Connection Bracket Type IF -SET- 923 016

60 mm, please indicated the diameter required when placing


your order)
PU Part
Type Material pc(s). No.
IF3 St/tZn 1 923 016

www.dehn.de 345
EXFS 100 / EXFS 100 KU LIGHTNING EQUIPOTENTIAL BONDING
923 101 EXFS 100
KU

EXFS 100 KU ISOLATING SPARK GAPS

EXFS 100 KU
923 101

isolating spark gap/


Funkenstrecke

insulating piece/ insulation / Isolierung


Isolierstück

Installation of EXFS 100 KU Dimension drawing EXFS 100 KU

EXFS 100 KU: Ex isolating spark gap with connecting cable for aboveground and underground
installation

EXFS 100 KU
Lightning impulse current (10/350 μs) Iimp 100 kA
Class of lightning current carrying capability acc. to EN 50164-3 H
Nominal discharge current (8/20 μs) In 100 kA
Rated power-frequency withstand voltage (50 Hz) UW/AC 250 V
100% Lightning impulse sparkover voltage Urimp ) 1.25 kV
Power-frequency sparkover voltage (50 Hz) Uaw ) 0.5 kV
Rated discharge current (50 Hz) Imax 500 A / 0.5 sec. (TU: ) 45°C)
(Ex) marking acc. to EN 60079 (gases) II 2G Ex d IIC T6
(Ex) marking according to EN 61241 (dusts) II 2D Ex tD A21 IP67 T 80°C
Operating temperature range TU -20°C...+60°C
Degree of protection IP 67
Approvals, Certifications BVS 06 ATEX E 099, IECEx KEM 09.0051...
Length of enclosure 123 mm
Diameter of enclosure 34 mm
Enclosure material plastic coating; water-proof coating
Connection of enclosure NYY-J-1x25 mm2, approx. 2 m long

Ordering information
Type EXFS 100 KU
Part No. 923 101
Packing unit 1 pc(s).

346 www.dehn.de
LIGHTNING EQUIPOTENTIAL BONDING EXFS L / EXFS KU
ISOLATING SPARK GAPS For use in explosion-hazard areas

• For indirect connection/earthing of functionally


isolated installation components when being
affected by lightning
• Device for lightning equipotential bonding acc.
to IEC 62305 in explosion-hazard areas (Zone 2)
• According to ”ATEX Directive” 94/9/EC
• Corrosion-resistant zinc diecasting enclosure
with plastic cover and flexible conductor con-
nection
• For bridging insulating pieces, insulating
flanges etc. in cathodically corrosion protected
pipe sections
• Extremely heavy-duty device

ATEX-certified isolating spark gap for lightning equipotential bonding


according to IEC 62305, approved device with flexible conductor connec-
tion

EXFS L ...: Isolating spark gap for use in explosion-hazard areas with flexible connecting cable
EXFS KU: Isolating spark gap for use in explosion-hazard areas with 1.5 m connecting cable for underground installation

Ex isolating spark gaps of the EXFS L / EXFS KU product family are used
when the direct interconnection of electrically conductive installation
components in Ex areas is not applicable. As, for example, in case of
cathodically corrosion protected pipeline sections.
ATEX-certified EXFS L and EXFS KU spark gaps provide approved and test-
ed safety in accordance with harmonised European standards.
The arc-resistant tungsten-copper electrodes ensure a long service life of
the Ex spark gaps.
The approved type EXFS L with flexible conductor connection quickly
adapts to any application environment. The prewired spark gaps provide
connecting cables with different lengths with cable lugs, screws and M10
nut. The flat or angled connection brackets (IF), which are available as
accessories, allow for easy connection of the spark gap to pipeline
flanges.
The EXFS KU type is enclosed in a damp-proof PVC enclosure and is ideal
for underground installation at insulating couplings.

www.dehn.de 347
EXFS L / EXFS KU LIGHTNING EQUIPOTENTIAL BONDING
923 060 EXFS
L100

EXFS L ISOLATING SPARK GAPS


923 061 EXFS
L200
923 062 EXFS
L300

EXFS L100 Ex-


Isolating Spark Gap 923 060
EXFS L200 Ex-
Isolating Spark Gap 923 061
EXFS L300 Ex-
Isolating Spark Gap 923 062

lmax = 300 mm
(avoid loops
where possible)

Installation of EXFS Dimension drawing EXFS

EXFS L ...: Ex isolating spark gap for aboveground installation

EXFS L100 EXFS L200 EXFS L300


Lightning impulse current (10/350 μs) Iimp 50 kA 50 kA 50 kA
Class of lightning current carrying capability acc. to EN 50164-3 N N N
Nominal discharge current (8/20 μs) In 100 kA 100 kA 100 kA
Rated power-frequency withstand voltage (50 Hz) UW/AC 300 V 300 V 300 V
100% Lightning impulse sparkover voltage Urimp ) 2.5 kV ) 2.5 kV ) 2.5 kV
Power frequency sparkover voltage (50 Hz) Uaw ) 1.2 kV ) 1.2 kV ) 1.2 kV
Type of protection acc. to EN 50014, EN 50021 II 3 G EEx nC II T4 II 3 G EEx nC II T4 II 3 G EEx nC II T4
Operating temperature range TU -20°C...+80°C -20°C...+80°C -20°C...+80°C
Degree of protection IP 54 IP 54 IP 54
Approvals, Certifications ZELM 03 ATEX 3192X ZELM 03 ATEX 3192X ZELM 03 ATEX 3192X
Length of enclosure 90 mm 90 mm 90 mm
Diameter of enclosure 63 mm 63 mm 63 mm
Enclosure material zinc diecasting, plastic zinc diecasting, plastic zinc diecasting, plastic
Connecting cable H01N2-D 25 mm2 with cable lug and screw/nut (M10)
Cable length 100 mm 200 mm 300 mm
Suitable for flange size 20-130 mm 120-230 mm 220-320 mm

Ordering information
Type EXFS L100 EXFS L200 EXFS L300
Part No. 923 060 923 061 923 062
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for EXFS L / EXFS KU Accessory Part for EXFS L / EXFS KU
923 011
Pair of angled connection brackets – IF 1 – 923 016

Pair of flat connection brackets – IF 3 –


Connection Bracket Type IF -SET- 923 011
Pair of angled connection brackets for EXFS ...; diameter corre- Pair of flat connection brackets for EXFS ...; diameter corre-
sponds to bolt diameter of the bolted flange joint (d1 up to max. Connection Bracket Type IF -SET- 923 016 sponds to bolt diameter of the bolted flange joint (d1 up to max.
60 mm, please indicate the diameter required when placing 60 mm, please indicated the diameter required when placing
your order) your order)
PU Part PU Part
Type Material pc(s). No. Type Material pc(s). No.
IF1 St/tZn 1 923 011 IF3 St/tZn 1 923 016

348 www.dehn.de
LIGHTNING EQUIPOTENTIAL BONDING EXFS L / EXFS KU
923 019 EXFS KU

ISOLATING SPARK GAPS EXFS KU

EXFS KU Ex-
Isolating Spark Gap 923 019

Dimension drawing EXFS KU

EXFS KU: Ex isolating spark gap with connecting cables for aboveground
and underground installation

EXFS KU
Lightning impulse current (10/350 μs) Iimp 50 kA
Class of lightning current carrying capability acc. to EN 50164-3 N
Nominal discharge current (8/20 μs) In 100 kA
Rated power-frequency withstand voltage (50 Hz) UW/AC 300 V
100% Lightning impulse sparkover voltage Urimp ) 2.5 kV
Power frequency sparkover voltage (50 Hz) Uaw ) 1.2 kV
Type of protection acc. to EN 50014, EN 50021 II 3 G EEx nC II T4
Operating temperature range TU -20°C...+80°C
Degree of protection IP 67
Approvals, Certifications ZELM 03 ATEX 3192X
Length of enclosure 90 mm
Diameter of enclosure 63 mm
Enclosure material zinc diecasting, plastic
Connecting cable NYY-J-1x25 mm2
Cable length 2 x approx. 1500 mm

Ordering information
Type EXFS KU
Part No. 923 019
Packing unit 1 pc(s).

www.dehn.de 349
Pipe Clamp for Explosion Hazard Areas LIGHTNING EQUIPOTENTIAL BONDING
For fixing at pipes in explosion hazard areas

• For use in explosion hazard areas Ex zones 1


and 2 (gases, vapours, fogs) as well as Ex zones
21 and 22 (dusts)
• Tested for explosion group IIB
• Time-saving installation – deactivation of the
system/areas for welding or drilling work not
necessary

Pipe clamp for explosion hazard areas from Ø26.9 mm


(¬”) to Ø88.9 mm (3”); Ø88.9 mm (3”) to 300 mm and
from Ø300 to 500 mm.
Pipe clamp for electrical contacting of pipes in explosion hazard areas, for
Separate clamping body for endless tightening strap (Part implementing of lightning equipotential bonding according to EN 62305-3
No. 540 901) from Ø26.9 mm (¬”) to 500 mm. (VDE 0185-305-3)

So far, the method of choice for implementing equipotential bonding and The Ex pipe clamp can be connected by
lightning equipotential bonding terminals in explosion hazard areas has – round conductor, Cu, St/tZn, Al, StSt with Ø8/10 mm or flexible / strand-
been welding or threaded bushings. Using pipe clamps was only permit- ed copper conductors, cross section 16-35 mm2, with E-Cu crimped
ted if there was proof of ignition spark immunity in case of lightning cur- cable lug (DIN 46235)
rent loading. DEHN + SÖHNE has now provided evidence of ignition spark
– flat copper conductor with minimum dimension 20x2.5 mm and a
absence for a pipe clamp at lightning current loading. By realising the test
Ø10.5 mm bore hole
according to EN 50164-1 (VDE 0185-201): Requirements for connection
components (clamps and connectors) in a potentially explosive atmos-
phere, absence of ignition sparks was proved for the test sample with a
lightning current carrying capability up to 50 kA (10/350 μs). The design
of this novel pipe clamp for explosion risk areas not only provides a safe
electrical contact by means of two contact clips, but also the mechanical
fixing by an electrically insulated clamping body.

DECLARATION OF MANUFACTURER

Product: Pipe clamp for explosive zones


Product description: Part No. 540 821
Part No. 540 801
Part No. 540 803
Part No. 540 805
Part No. 540 810

Manufacturer: DEHN + SÖHNE GmbH + Co.KG.


Hans-Dehn-Str. 1
92318 Neumarkt i.d.OPf., Germany

Application:

The pipe clamp for explosive zones is used for connecting pipes of different materials and
diameters to the lightning equipotential bonding structure in explosive atmospheres.

Lightning currents are discharged without formation of sparks as specified in the technical
data sheet.

We herewith confirm that the pipe clamp for explosive zones is suitable for the use in explo-
sive zones 1 and 2 (gas, vapour, mist) and explosive zones 21 and 22 (combustible dust) in
connection with the installation instructions, P

not legally admissi-


ble and not necessary with respect to explosion protection.

Attached to a StSt pipe

Neumarkt i.d.OPf., 12 Okt. 2009


Dr.-Ing. Ralph Brocke
Director R&D

c:\dokume~1\drb\lokale~1\temp\xpgrpwise\herstellererklärung bandrohrschelle ex-bereiche upd ate ausführung klein und groß engl. .doc
Page 1

350 www.dehn.de
LIGHTNING EQUIPOTENTIAL BONDING Pipe Clamp for Explosion Hazard Areas
540 821 EX BRS
27

Ex Pipe Clamp for Ø6 mm to 26.9 mm

EX BRS 27
540 821

Type EX BRS 27 clamping range from Ø6 mm


to 26.9 mm (¬”)

EX BRS 27
Lightning impulse current (10/350 μs) for Cu Iimp 10 kA-> Ø6-12 mm I 20 kA-> Ø12-26.9 mm (¬’’) I 25 kA-> Ø26.9 mm (¬’’)
Lightning impulse current (10/350 μs) for St/tZn Iimp 25 kA-> Ø17.2-26.9 mm (¬’’)
Lightning impulse current (10/350 μs) for StSt Iimp 10 kA-> Ø6-12 mm I 12 kA-> Ø12-26.9 mm (¬’’) I 25 kA-> Ø26.9 mm (¬’’)
Clamping range Ø6 - 26.9 mm (¬’’)
Dimension tensioning strap (l1 x w x d) 190x10x0.25 mm
Clamping body material polyamide
Grip head/strap material StSt
Contact angle material Ms/gal Sn

Ordering information
Type EX BRS 27
Part No. 540 821
Packing unit 1 pc(s).

540 801
540 803

Ex Pipe Clamp for Ø26.9 mm to 500 mm


540 805

540 801

540 803

540 805

Type EX BRS 90, Part No. 540 801, clamping


range from Ø26.9 mm (¬”) to 88.9 mm (3”)
Type EX BRS 300, Part No. 540 803, clamping
range from Ø88.9 mm (3”) to 300 mm and
Type EX BRS 500, Part No. 540 805, clamping
range from Ø300 to 500 mm

EX BRS 90 EX BRS 300 EX BRS 500


Lightning impulse current (10/350 μs) for Cu Iimp 50 kA 50 kA 50 kA
Lightning impulse current (10/350 μs) for St/tZn Iimp 50 kA 50 kA 50 kA
Lightning impulse current (10/350 μs) for StSt Iimp 25 kA 50 kA 50 kA
Class of lightning current carrying capability acc. to DIN EN 50164-1 N N N
Clamping range Ø26.9 (¬”) - 88.9 mm (3”) Ø88.9 (3”) - 300 mm Ø300 - 500 mm
Dimension tensioning strap (l1 x w x d) 410x25x0.3 mm 1100x25x0.3 mm 1850x25x0.3 mm
Clamping body material polyamide polyamide polyamide
Grip head/strap material StSt StSt StSt
Contact angle material Cu/gal Sn Cu/gal Sn Cu/gal Sn

Ordering information
NEW
Type EX BRS 90 EX BRS 300 EX BRS 500
Part No. 540 801 540 803 540 805
Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

www.dehn.de 351
Pipe Clamp for Explosion Hazard Areas LIGHTNING PROTECTION
540 810

Separate clamping body for endless tightening strap TECHNOLOGY SYSTEMS

540 810

Separate clamping body with endless strap (Part


No. 540 901)
Clamping ranges from Ø26.9 mm (¬”) to 500 mm

Lightning impulse current (10/350 μs) for Cu Iimp 50 kA


Lightning impulse current (10/350 μs) for St/tZn Iimp 50 kA
Lightning impulse current (10/350 μs) for StSt Iimp 25 kA
Class of lightning current carrying capability acc. to DIN EN 50164-1 N
Clamping range Ø26.9 mm (¬”) - 500 mm
Clamping body material polyamide
Grip head/strap material StSt
Contact angle material Cu/gal Sn

Ordering information
Part No. 540 810
Packing unit 1 pc(s).

Accessory Part for Pipe Clamp for Explosion Hazard Areas


540 901

Tensioning strap
Endless tensioning strap (100 m long)
540 901
Strap dimension PU Part
Material (l x w x d) pc(s). No.
StSt (V2A) ... x 25 x 0.3 mm 1 540 901

352 www.dehn.de
LIGHTNING EQUIPOTENTIAL BONDING SDS
ISOLATING SPARK GAPS Voltage Limiting Device

• Electrical isolation of insulated track sections


and earthed parts of installations
• Safe equipotential bonding in case of a short
circuit or earth fault at the overhead contact
line due to high-current-resistant welding of
the electrodes
• Discharge of surges without formation of short
circuits due to lightning-resistant SDS ... volt-
age limiting device
• Short-circuit withstand capability 25 kArms /
100 ms; 36 kArms / 75 ms

SDS ...: Cylindrical SDS spark gap unit for insertion into rail adapter Siemens No. 8WL6503-xx

DIN EN 50122-1 describes the use of voltage limiting devices for d.c. and
a.c. railways for so-called ”open earthing of railways” for live compo- mostly unnecessary
nents of overhead contact lines and current collectors.
In order to prevent the occurrence of hazardous surges between the insu-
lated tracks or track sections of electrical railways and earthed parts of
the installation, voltage limiting devices (SDS ...) are used.

Their function is to connect parts of the installation in overhead contact


lines and current collectors permanently to the return circuit, as soon as
the threshold voltage is exceeded.
SDS spark gap unit for use with rail adapter, Siemens No. 8WL6503-xx
In case of atmospheric overvoltages, the lightning-resistant SDS ... voltage
limiting device is capable of returning to its initial state after discharging
the impulse current. Only if the specified lightning current loads are
exceeded, a permanent short circuit is initiated by heavy-current-resistant
welding of the electrodes and the fuse link has to be replaced.

The SDS voltage limiting device consists of a spark gap unit and the
respective connecting kit for direct connection to the rail or overhead con-
tact line tower.

The spark gap unit type SDS 1, Part No. 923 110, developed by DEHN +
SÖHNE, has also been approved by the German Federal Railway Authority
(EBA).

www.dehn.de 353
SDS LIGHTNING EQUIPOTENTIAL BONDING
923 110 SDS 1

SDS ... ISOLATING SPARK GAPS

SDS 1
Sicherungseinsatz SDS 1 923 110

Basic circuit diagram SDS ... Dimension drawing SDS ...

SDS 1 SDS 2 SDS 3 SDS 4 SDS 5


Power frequency sparkover voltage Uaw ) 940 V –– –– –– ––
d.c. sparkover voltage Uag 600 V +/- 20 % 350 V +/- 20 % 550 V 230 V +/- 20 % 120 V +/- 20 %
Impulse sparkover voltage ) 1400 V (1 kV/μs) ) 900 V (1 kV/μs) ) 1000 V (1 kV/μs) ) 650 V (1 kV/μs) ) 600 V (1 kV/μs)
Self-extinguishing capability 300 A / 65 V –– –– –– ––
Lightning current discharge capacity
(10/350 μs) 0.1x / 0.5x / 1x 5 kA 2 kA 2.5 kA 2.5 kA 2 kA
Lightning current withstand capability (10/350 μs) 25 kA 25 kA 25 kA 25 kA 25 kA
Impulse current discharge capacity
(8/20 μs) 0.1x / 0.5x / 1x –– –– –– 20 kA 20 kA
Safe short circuit due to welding of the
electrodes for alternating currents @ 100 ms * 1.5 kA / 1000 V / 100 ms –– –– –– ––
Safe short circuit due to welding of the
electrodes for alternating currents @ 30 ms * 2.5 kA / 1000 V / 30 ms –– –– –– ––
Safe short circuit due to welding of the
electrodes for direct currents * 750 A / 250 ms * 600 A / 250 ms –– * 600 A / 250 ms * 600 A / 250 ms
Short circuit withstand capability 25 kArms / 100 ms; 25 kArms / 100 ms; 25 kArms / 100 ms; 25 kArms / 100 ms; 25 kArms / 100 ms;
36 kArms / 75 ms 36 kArms / 75 ms –– 36 kArms / 75 ms 36 kArms / 75 ms
Long-term current 1 kArms for t ) 120 s 1 kArms for t ) 120 s –– 1 kArms for t ) 120 s 1 kArms for t ) 120 s
Leakage current Ilc < 1 μA for 100 V d.c. < 1 μA for 100 V d.c. –– < 1 μA for 100 V d.c. < 1 μA for 100 V d.c.
Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C
For mounting on allows for installation into voltage breakdown protector/SIEMENS rail adapter No. 8WL6503-xx
Tightening torque of the fuse link
in the busbar adapter 15 Nm 15 Nm 15 Nm 15 Nm 15 Nm
Approvals, Certifications EBA –– –– –– ––
DB Drawing No. 4 Ebs 15.13.20 Sheet 2 –– –– –– ––

Ordering information
Type SDS 1 SDS 2 SDS 3 SDS 4 SDS 5
Part No. 923 110 923 117 923 116 923 118 923 119
Packing unit 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s).

354 www.dehn.de
LIGHTNING EQUIPOTENTIAL BONDING Equipotential Bonding

Equipotential Bonding Bars

563 200 PAS 11AK

Equipotential busbar K12, 563 010

Equipotential Bonding Bars R15,


with snap-on terminals with Terminal Block System
PAS 11AK
Busbar
Earthing
563 200 For equipotential bonding according to DIN VDE 0100 Part 563 010 For main equipotential bonding according to DIN VDE 0100 Part
410/540 and the lightning equipotential bonding according to 410/540 and lightning equipotential bonding according to EN
EN 62305-3 (VDE 0185-305-3) 62305-3 (DIN VDE 0185-305-3)
Type K12 with 12 contact studs: Type A:
10 terminals for Rd 2.5 – 95 mm2 or Rd 10 mm conductors 7 terminal blocks 2.5 – 25 mm2
and 1 terminal for Fl -30x4 mm conductors 2 terminal blocks 16 – 95 mm2 or Rd 8 – 10 mm
Contact Cross PU Part 1 terminal block Fl -30x4 mm
Type bar section pc(s). No. Clamping Cross PU Part
PAS 11AK Cu/gal Sn 30 mm2 1 563 200 Type bar section pc(s). No.
PAS 10RK Ms/gal Sn 100 mm2 1 563 010
563 201
UV
PAS 11AK
Type K12 with 12 contact studs, UV-stabilised:
10 terminals for Rd 2.5 – 95 mm2 or Rd 10 mm conductors
563 020
Type B:
PAS 11AK UV
563 201 and 1 terminal for Fl –30x4 mm 5 terminal blocks 2.5 – 25 mm2
Contact Cross PU Part 563 020 3 terminal blocks 16 – 95 mm2 or Rd 8 – 10 mm
Type bar section pc(s). No. 1 terminal block Fl –30x4 mm
PAS 11AK UV Cu/gal Sn 30 mm2 1 563 201 Clamping Cross PU Part
Type bar section pc(s). No.
563 222
PAS
AK FL40

Accessories – PAS 9RK Ms/gal Sn 100 mm2 1 563 020


Snap-on Terminal for Fl 40 Conductors
AK FL40 PAS
for Fl 40
Terminal
563 222 PU Part
563 030
Type C:
Type pc(s). No. 13 terminal blocks 2.5 – 25 mm2
AK FL40 PAS 50 563 222 563 030 1 terminal block 16 – 95 mm2 or Rd 8 – 10 mm
Clamping Cross PU Part
Type bar section pc(s). No.
563 050 PAS 9AK

Equipotential Bonding Bar MS PAS 14RK Ms/gal Sn 100 mm2 1 563 030
For equipotential bonding
PAS 9AK Earthing
Busbar 563 050
Connections for:
7 Rd conductors Rd 2.5 – 16 mm2
563 105
OH
PAS 6RK

Equipotential Bonding Busbar,


1 Rd conductor 7 – 10 mm with miniature terminal block system
1 Fl conductor –30x3.5 mm or Rd conductor 8 – 10 mm PAS 6RK OH
Busbar
Earthing
563 105 Miniature unit: For surface mounting without cover
Contact Cross PU Part Clamping Cross PU Part
Type bar section pc(s). No. Type bar Connection section pc(s). No.
PAS 9AK Ms 50 mm2 1 563 050 PAS 6RK OH Ms/gal Sn 6 x 2.5-25 mm2 100 mm2 10 563 105

Accessories / Construction Kit Terminal Block


563 019 RK FL40
PAS

Flat conductor 40 mm
PU Part
RK FL40 PAS Modular
Terminal, flat strip -40 mm for EB 563 019

Type Material Connection Modules pc(s). No.


RK FL40 PAS St/gal Zn -40x5 mm 5 25 563 019

563 011
PAS
RK 16

Terminal Block 563 016


PAS
563 017
PAS
KS 198

KS 398 Clamping Bar


563 018 KS 798
PAS

2.5 to 25 mm2 PU Part


RK 16 PAS
Terminal, -16 mm3 for EB
Modular
563 011
PU Part KS 198 PAS
Bar, brass, 198 mm long
KS 398 PAS
Terminal
563 016
Terminal
Type Material Length Modules pc(s). No.
bar, brass, 398 mm long 563 017

Type Material Connection Modules pc(s). No. KS 798 PAS


bar, brass, 798 mm long
Terminal
563 018 KS 198 PAS Ms/gal Sn 198 mm 15 10 563 016
RK 16 PAS St/gal Zn 2.5-25 mm2 1 200 563 011 KS 398 PAS Ms/gal Sn 398 mm 30 10 563 017
KS 798 PAS Ms/gal Sn 798 mm 60 10 563 018
563 013

Terminal Block
Up to 95 mm2 or Rd 8-10 mm
563 014
RK
SB PAS

Bar Frame
563 013
PU Part Fixing PU Part
Type Material Connection Modules pc(s). No. SB PAS RK
der, plastic, grey
Bar hol-
563 014
Type Material holes pc(s). No.
RK 95 PAS St/gal Zn 16-95 mm2 2 100 563 013 SB PAS RK Plastic 6x4 mm 50 563 014

563 012
PAS
RK FL30

Terminal Block 563 015


RK
AH PAS

Cover
Flat conductor 30 mm to snap on / to be labelled
PU Part
RK FL30 PAS Modular

PU Part
AH PAS RK Plastic
Terminal, flat strip -30 mm for EB 563 012 cover, grey 563 015

Type Material Connection Modules pc(s). No. Type Material Modules pc(s). No.
RK FL30 PAS St/gal Zn -30x4 mm 4 25 563 012 AH PAS RK Plastic 15 10 563 015

Note: For our complete product range for earthing and equipotential bonding please refer to our current Lightning Protection catalogue, which
can be requested from Export Department.

www.dehn.de 355
Equipotential Bonding LIGHTNING EQUIPOTENTIAL BONDING

Equipotential Bonding Bars Earthing Busbars


for industial use

472 207
M10 CU
472 209
M10 V2A
PAS I 6AP

PAS I 6AP Equipotential Bonding Busbar for industrial use 472 023
10 ST
472 109
10 V2A
ES 2X2AP

ES 2X2AP Earthing Busbars


For main equipotential bonding according to DIN VDE 0100 Part To be screwed or welded to steel structures
PAS I 6AP M10 CU
Busbar
PAS I 6AP M10 V2A
Earthing
472 207
Earthing
410/540 and lightning equipotential bonding according to EN ES 2X2AP 10 Stk.
472 023
ES 2X2AP 10 V2A Borehole distance 50 mm
Busbar 472 209 472 109

62305-3 (DIN VDE 0185-305-3)


2x2 connections
Also for use in hazardous zones (screws protected against self-
Dimension Cross PU Part
loosening) Type Material (l x w x d) section pc(s). No.
6 connections with insulators ES 2X2AP 10 ST St/tZn 196x60x4 mm 240 mm2 1 472 023
Dimension Cross PU Part ES 2X2AP 10 V2A StSt 196x60x5 mm 300 mm2 1 472 109
Type Material (l x w x d) section pc(s). No.
PAS I 6AP M10 CU Cu 295x40x5 mm 200 mm2 1 472 207 472 022
10 ST
472 119
ES 2X3AP

ES 2X3AP 2x3 connections


PAS I 6AP M10 V2A StSt 295x40x6 mm 240 mm2 1 472 209 10 V2A

Dimension Cross PU Part


ES 2X3AP 10 Stk.
472 022
Type Material (l x w x d) section pc(s). No.
472 227
M10 CU
472 229
M10 V2A
PAS I 8AP

PAS I 8AP 8 connections with insulators ES 2X3AP 10 V2A


472 119
ES 2X3AP 10 ST St/tZn 242x60x4 mm 240 mm2 1 472 022
Dimension Cross PU Part ES 2X3AP 10 V2A StSt 242x60x5 mm 300 mm2 1 472 119
PAS I 8AP M10 CU
Busbar
Earthing
472 227
Type Material (l x w x d) section pc(s). No.
PAS I 8AP M10 V2A Earthing
Busbar 472 229
PAS I 8AP M10 CU Cu 365x40x5 mm 200 mm2 1 472 227 472 024
ST
472 129
ES 2X4AP

ES 2X4AP 2x4 connections


PAS I 8AP M10 V2A StSt 365x40x6 mm 240 mm2 1 472 229 10 V2A

Dimension Cross PU Part


ES 2X4AP Stk.
472 024
Type Material (l x w x d) section pc(s). No.
472 217
10AP M10 CU
472 219
10AP M10 V2A
PAS I

PAS I 10 connections with insulators ES 2X4AP 10 V2A


472 129
ES 2X4AP ST St/tZn 293x60x4 mm 240 mm2 1 472 024
Dimension Cross PU Part ES 2X4AP 10 V2A StSt 293x60x5 mm 300 mm2 1 472 129
PAS I 10AP M10 CU
Busbar
Earthing
472 217
Type Material (l x w x d) section pc(s). No.
PAS I 10AP M10 V2A Earthing
Busbar 472 219
PAS I 10AP M10 CU Cu 435x40x5 mm 200 mm2 1 472 217 472 021
10 ST
472 139
ES 2X6AP

ES 2X6AP 2x6 connections


PAS I 10AP M10 V2A StSt 435x40x6 mm 240 mm2 1 472 219 10 V2A

Dimension Cross PU Part


ES 2X6AP 10 Stk.
472 021
Type Material (l x w x d) section pc(s). No.
472 237
12AP M10 CU
472 239
12AP M10 V2A
PAS I

PAS I 12 connections with insulators ES 2X6AP 10 V2A


472 139
ES 2X6AP 10 ST St/tZn 393x60x4 mm 240 mm2 1 472 021
Dimension Cross PU Part ES 2X6AP 10 V2A StSt 393x60x5 mm 300 mm2 1 472 139
PAS I 12AP M10 CU
472 237
Type Material (l x w x d) section pc(s). No.
PAS I 12AP M10 V2A
472 239
PAS I 12AP M10 CU Cu 505x40x5 mm 200 mm 2 1 472 237
PAS I 12AP M10 V2A StSt 505x40x6 mm 240 mm2 1 472 239

472 279
6AP V2A
472 269
8AP V2A
472 289
AD PAS

AD PAS

AD PAS
Accessories – Cover for EBB (Industry)
10AP V2A

Covers for EBB with insulators


472 299 AD PAS
12AP V2A

Material EBB Dimension PU Part


AD PAS 6AP V2A Cover
NIRO, for 6-pole EB 472 279
AD PAS 8AP V2A Cover
NIRO, for 8-pole EB 472 269

Type screw/nut type (l x w x d) pc(s). No.


AD PAS 10AP V2A Cover
NIRO, for 10-pole EB 472 289
AD PAS 12AP V2A Cover
NIRO, for 12-pole EB 472 299

AD PAS 6AP V2A StSt 6 connections 301x60x0.8 mm 1 472 279


AD PAS 8AP V2A StSt 8 connections 371x60x0.8 mm 1 472 269
AD PAS 10AP V2A StSt 10 connections 441x60x0.8 mm 1 472 289
AD PAS 12AP V2A StSt 12 connections 511x60x0.8 mm 1 472 299

472 201
PAS
BS M10

Accessories – Fixing Set for EBB (Industry)


Screw Screw Plastic PU Part
BS M10 PAS
for EB
Fixing Set
472 201
Type material type dowel pc(s). No.
BS M10 PAS St/tZn 45 mm c M10x20 mm Ø12x60 mm 1 472 201

472 210
M10
IS PAS

Accessories – Insulator for EBB (Industry)


Material Terminal PU Part
IS PAS M10
für PAS Industrie
Isolator
472 210
Type Isolator thread pc(s). No.
IS PAS M10 UP (thermoset) M10 1 472 210

Note: For our complete product range for earthing and equipotential bonding please refer to our current Lightning Protection catalogue, which
can be requested from Export Department.

356 www.dehn.de
LIGHTNING EQUIPOTENTIAL BONDING Equipotential Bonding

Connecting Clamps Components


for ring equipotential bonding

308 025
ST
VK A UNI

Connecting Clamp, for reinforcements 277 230


277 237
277 239 Strip Holder, with thrust pad
For connecting reinforced concrete mats or reinforcements to For wall mounting
VK A UNI Stk.
Connection Clamp St/tZn 308 025 round and flat conductors 277 230
Thrust pad with M8 screw for strip conductor up to 11 mm and
277 237

For T, cross and parallel connections 277 239


round conductor 6-10 mm.
Clamping range PU Part 11 mm distance from the wall
Type Material Rd / Rd Rd / Fl Fl / Fl pc(s). No.
Material Material PU Part
VK A UNI ST St/tZn (+) 6-10 / (+) 6-10 / (II) 30 / 50 308 025 Type CH screw pc(s). No.
6-10 mm 30 mm 30 mm FBH 6 ST St/tZn StSt 25 277 230
FBH 6 CU Cu StSt 25 277 237
308 026
V2 ST
VK A UNI
For T, cross and parallel connections FBH 6 V2A StSt StSt 25 277 239
Clamping range PU Part
VK A UNI V2 Stk.
Connection Clamp St/tZn 308 026
Type Material Rd / Fl Fl / Fl pc(s). No. 277 240
15 mm distance from the wall
VK A UNI V2 ST St/tZn (+) 6-10 / (+ / II) 30 / 25 308 026
Material Material PU Part
30 mm 30 mm Type CH screw pc(s). No.
Tape
Conductors with Pressure Plate 277 240

FBH 11 ST St/tZn StSt 25 277 240


308 030
F40 STBL
VK A R22
For T and cross connections
Clamping range PU Part
VK A R22 F40 STBL
Connection Clamp St/bare 308 030
Type Material Rd / Fl pc(s). No.
VK A R22 F40 STBL St/bare (+) 6-22 / 40 mm 25 308 030 563 169
V2A
AK RPA

Terminal Clamp
For universal connection to the ring equipotential bonding for
308 041
R16 R25 ST
308 040
R16 R25 STBL
MMVK

MMVK MAXI MV Clamp for T, cross and parallel connections AK RPA V2A
563 169 St/tZn, copper or stainless steel (StSt)
Part No. 308 040 with UL certification CH Cross-sectional PU Part
MMVK R16 R25 Stk.
terminal, St/bare
MAXI MV
308 041
Clamping range PU Part Type Material Rd / Fl area pc(s). No.
MMVK R16 R25 STBL
terminal, St/tZn
MAXI MV
308 040
Type Material Rd/Rd pc(s). No. AK RPA V2A StSt 8-10 / 3-11x30 mm 2.5-95 mm2 50 563 169
MMVK R16 R25 ST St/tZn (+/II) 8-16 / 15-25 mm 20 308 041
MMVK R16 R25 STBL St/bare (+/II) 8-16 / 15-25 mm 20 308 040

Components
for foundation earthing electrodes

308 120
R10 F30 ST
308 129
R10 F30 V2A
VK EH

VK EH Connecting Clamp, for Foundation Earth 290 001


VG
AH FE RF

Spacer
Electrodes Reinforced angled type
VK EH R10 F30 Stk.
Connection Clamp St/tZn
VK EH R10 F30 V2A
Connection Clamp StSt (V2A)
308 120

308 129
For connecting round and flat conductors in the concrete foun- AH FE RF V G
Holder St/tZn, reinf. version 300 mm
Distance
290 001
Support Support PU Part
dation Type Material Fl Rd pc(s). No.
For T, cross and parallel connections, no threading of the con- AH FE RF V G St/tZn 40 mm 8-10 mm 25 290 001
ductors required
Clamping range mm PU Part
290 002 AH FE RF

Spacer
Type Material Rd / Fl Fl / Fl pc(s). No. Straight type
VK EH R10 F30 ST St/tZn (+) 10 / 30 (+/II) 30 / 30 25 308 120
Support Support PU Part
AH FE RF Distance
Holder St/tZn, DIN 48833 A, 280 mm 290 002

VK EH R10 F30 V2A StSt (+) 10 / 30 (+/II) 30 / 30 25 308 129 Type Material Fl Rd pc(s). No.
AH FE RF St/tZn 40 mm 8-10 mm 50 290 002
308 150

Expansion Strap for Foundation Earth Electrodes


For leading the foundation earth electrode in extended founda-
308 150 tions (several sections) through the expansion or isolating
joints. Thus no need to lead the earth electrode out of the base
plate.
Strap Dimension Block PU Part
material (l x w x d) material pc(s). No.
StSt (V2A) approx. 700x30x(4x1) mm styrene 1 308 150

Note: For our complete product range for earthing and equipotential bonding please refer to our current Lightning Protection catalogue, which
can be requested from Export Department.

www.dehn.de 357
358 www.dehn.de
MEASURING AND TEST DEVICES Condition Monitoring System LifeCheck®

• Maximum protection and availability of sys-


tems by means of permanent condition moni-
toring of LifeCheck-equipped SPDs
• The early detection system already detects
arrester overload and warns of imminent fail-
ure of the arrester
– Visual indication of faulty or previously dam-
aged SPDs
– Compact dimensions and minimum wiring
– Monitoring of up to 10 SPDs (40 signal lines)
– Remote signalling contact
– Remote signalling also via RS 485 interface
and PC software

Example of use of the DEHNrecord condition monitoring system.

Condition Monitoring: The ”Status Display and Service Console” PC software


The DRC MCM XT condition monitoring system is a compact DIN rail is an optional user software for the DRC MCM XT condition monitoring
mounted device for monitoring the condition of up to 10 pre-programmed system which indicates the status of the SPDs and addresses LifeCheck-
BXT arresters with integrated LifeCheck monitoring circuit. equipped BLITZDUCTOR modules.
The software can be installed on a standard PC using an RS485/USB inter-
ntegrated into the SPD modules, LifeCheck permanently monitors the face converter of type ”USB-NANO 485” which is available as accessory.
proper condition of the SPD and acts like an early warning system, detect-
ing imminent electrical or thermal overload of the protection components. The software can be downloaded free of charge from
The LifeCheck status can be read out within a matter of seconds via con- www.dehn.de/download/ or is available as CD for a nominal fee.
tactless RFID technology by means of the portable DEHNrecord LC device
and also shows the date of the last test of the SPD module. Stationary
installed, the condition monitoring system supports condition-based
maintenance of 10 BXT.

The unit acts like an early warning system, generating a fault message
even in case of imminent arrester overload, indicates it by means of the
integrated three-colour LED and transmits it to one of the two integrated
remote signalling contacts. Failure of the monitoring unit, e.g. due to a
voltage breakdown, is also indicated via the remote signalling contact.
The Show function integrated into the DRC MCM system allows to detect
previously damaged SPDs in the monitoring group.

If several condition monitoring systems are used in one switchgear cabi-


net, these systems are connected via the integrated RS 485 interfaces to
synchronise the monitoring cycles. Up to 15 DRC MCM systems can be
connected to the RS 485 bus. Thus, up to 150 BLITZDUCTORs or 300 pairs
can be monitored simultaneously with minimum wiring effort.

Graphical status indication of DRC MCM XT monitoring devices


and of all programmed protection modules assigned to them.

The Service functions allow to switch to the ”Service Console”


function complex. The protection modules can be easily addressed,
tested and reset due to the user-friendly user interface.

www.dehn.de 359
Condition Monitoring System LifeCheck® MEASURING AND TEST DEVICES
910 695 DRC
MCM XT

DRC MCM XT

DRC MCM XT
910 695

• Monitoring the condition of Life- The DRC MCM XT Status Display software allows The Service Console offers various service func-
Check-equipped SPDs PC-aided remote indication of the status of all tions, e.g. SPDs can be parameterised or reset
SPDs monitored. by means of the address data.
• Permanent monitoring of up to
10 SPDs (40 signal lines)
DIN rail mounted device with integrated LifeCheck sensor for monitoring the condition of max. 10
• Minimum wiring effort LifeCheck-equipped ”BLITZDUCTOR XT” devices. Visual three-coloured SPD operating state indica-
• Optional remote signalling via RS 485 tion combined with remote signalling function (break or make contact). The free ”Status Display
or remote signalling contacts and Service Console” software can be optionally used via an RS 485 interface converter.

DRC MCM XT
For testing up to 10 BLITZDUCTOR XT ML devices
up to 10 BLITZDUCTOR XT ML EX devices; for use in non-hazardous atmospheres only! Observe thread measure!
Operating elements multiway button, DIP switch
Indicator element 3-coloured LED (green, orange, red)
Input d.c. voltage range UIN 18...48 V
Max. nominal current input IIN 100 mA
RFID transmission frequency 125 kHz
Message: Replacing of SPD recommended LED, remote signalling contact (break and make contact)
Test cycle continuous
Operating temperature range for monitoring 10 BXT devices -20°C...+60°C
Operating temperature range for monitoring 8 BXT devices -40°C...+80°C
Degree of protection IP 20
For mounting on 35 mm DIN rail acc. to EN 60715
Connection type screw
Cross-sectional area, solid 0.08 - 4 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Tightening torque (terminal) 0.4 Nm
Enclosure material polyamide PA 6.6
Colour grey
Test standards EN 61010-1, 61000-6-2/4
Type of remote signalling contact make (no) and break contact (nc)
Switching capacity d.c. 350 V/0.12 A
Switching capacity a.c. 250 V/0.07 A
Delivery includes base part, monitoring module, quick guide and marking system

Ordering information
Type DRC MCM XT
Part No. 910 695
Packing unit 1 pc(s).

Accessory Part for Condition Monitoring System LifeCheck® Accessory Part for Condition Monitoring System LifeCheck®
910 486
NANO 485
USB

USB interface converter of type USB NANO 485 920 398


BA15 BXT
BS BA1

Marking system BA1-BA15


USB NANO 485 converts signals between USB and RS-485. The interface conver- 2 x 165 adhesive labels for labelling DRC MCM XT monito-
USB NANO 485
910 486
ter is specifically designed for 2-wire RS-485 buses. LEDs indicate operation (yel- BS BA1 BA15 BXT
920 398
ring devices with their bus address (BA1 to BA15) and BXT
low), Rx (green) and Tx (red). base parts or modules with consecutive numbers (1.1-1.10
to 15.1-15.10)
USB NANO 485 is ideally suited for use with notebooks due to its small size.
Stationary use is also possible. PU Part
Type pc(s). No.
PU Part BS BA1 BA15 BXT 1 920 398
Type pc(s). No.
USB NANO 485 1 910 486

360 www.dehn.de
MEASURING AND TEST DEVICES LifeCheck® SPD Test Device

• A higher degree of protection and availability is


achieved by preventive maintenance.
– The LifeCheck monitoring device detects
thermal or electrical overload of all compo-
nents.
– To avoid imminent failure and thus system
downtime, the SPD module should be
replaced as soon as possible.
• This type of SPD testing has the following ben-
efits:
– Very easy and within a matter of seconds
– Module does not have to be removed during
system operation
– Detection of thermal or electrical overload of
all components
DIN EN 62305-3, supplement 3 (see table excerpt) specifies maintenance Transponder (SPD) Reader (test device)
tests and intervals of a lightning protection systems. However, these spec-
ifications are only normative minimum requirements. energy
SPD
identification IC

Protection Visual Complete Complete inspection reader IC micro-


level inspection inspection of critical systems controller

I and II 1 year 2 years 1 year indication


of operating
data
III and IV 2 years 4 years 1 year state

power communication
It makes no sense to inspect SPDs for information technology systems
visually since the status of the devices is generally not visible. For this pur- Principle of operation of the LifeCheck diagnostic system
pose, another method has to be selected as is the case for complete
inspections. In the past, measurement equipment was used to test SPDs.
These measurements were very time consuming, required expertise and
the measurements did not provide sufficient information. This type of monitoring reliably detects thermal and electrical overload of
all components, generally before the SPD fails and the availability of the
system to be protected is limited. In addition, no expertise is required for
testing. The reader also facilitates documentation of the test results,
which is mandatory in compliance with the EN 62305-3 standard.
Preventive maintenance: The test data (date, time, results) of all SPDs are saved and can be trans-
When using this maintenance strategy, SPDs are tested and measured at mitted to a PC for printing or storage via USB interface. Thus a higher
regular intervals. The SPDs are assessed according to certain criteria and, degree of protection and availability is achieved by means of preventive
if required, replaced. maintenance with LifeCheck as it already detects overload of components
before the protection of the system circuit fails.
In the past, this was very time consuming, expensive and required down-
time of the system.
For some years, SPDs with LifeCheck feature have been available which
allow to determine the status of the SPD via RFID technology. A monitor-
ing circuit with a transponder in the SPD permanently monitors the pro-
tective circuit for impermissible overload due to thermal overheating or
electrical impulse currents.

Information is read out via a hand-held tester. This tester incorporates the
reader, an RFID reader unit.
It contactlessly transmits electromagnetic energy to the transponder in
the SPD, reads out the status and displays it. Information is simple: "SPD
OK" or "Replace SPD!". This test is carried out easily within a matter of
seconds and without removing the SPD. The test can be carried out at any
time without interruption as it does not interrupt signal transmission.

www.dehn.de 361
LifeCheck® SPD Test Device MEASURING AND TEST DEVICES
910 653 DRC LC M3+

DRC LC M3+

NEW DRC LC M3+


910 653

• Fast testing of LifeCheck-equipped The database function allows easy documentation NEW Snap-on LifeCheck sensor
SPDs of the test results on the PC

• Hand-held device, easy transport and


Portable device with LifeCheck sensor for flexible use. For fast and easy testing of LifeCheck-
operation
equipped arresters. Visual and acoustic indication. With additional USB connection and database
• With database function for documen- software for PC-aided management of test objects and documentation of the test results. DRC LC
tation M3+ features a new snap-on LifeCheck sensor, allowing to test the SPD without holding the sen-
• Easy and fast parameterisation of sor. The handheld device allows parameterisation of SPDs for condition monitoring.
SPDs for condition monitoring with
LifeCheck

DRC LC M3+
For testing BLITZDUCTOR XT ML
BLITZDUCTOR XT ML EX; for use in non-hazardous atmospheres only!
Voltage supply (included in delivery) Li-ion battery
RFID transmission frequency 125 kHz
Measured value indication beep and LCD
Testing period typically 3 to 10 sec.
Operating temperature range -10°C...+65°C
Battery test automatic switch-off in case of flat battery
Cable length to LifeCheck sensor approx. 1000 mm
Dimensions of LifeCheck sensor 90 x 51 x 12 mm
Dimensions of handheld device 166 x 95 x 30 mm
Delivery includes handheld device, LifeCheck sensor BXT, charging device, USB cable,
test module for reference, software CD, storage case
Dimensions of storage case 340 x 275 x 83 mm

Ordering information
Type DRC LC M3+
Part No. 910 653
Packing unit 1 pc(s).

Accessory Part for LifeCheck® SPD Test Device


910 652
BXT
910 654
BCT
LCS DRC

LCS DRC LifeCheck Sensor for DRC BXT / BCT


LifeCheck sensor and test module for use as spare part / extension for
LCS DRC BXT
Sensor für DRC BXT
LCS DRC BCT
LifeCheck-
910 652
LifeCheck-
portable LifeCheck test devices.
Sensor für DRC BCT 910 654

PU Part
Type Testing of pc(s). No.
LCS DRC BXT BLITZDUCTOR XT ML 1 910 652
LCS DRC BCT BLITZDUCTOR CT MLC 1 910 654

362 www.dehn.de
MEASURING AND TEST DEVICES SPD Test Device

• For routine tests of surge protective devices


• Compact dimensions
• Suitable for mains and battery operation
• Low-battery indicator
• Test cables included in delivery
• Test adapter included as accessory part,
protected against accidental contact

For testing the sparkover voltage of surge arresters. The sample to be test-
ed is connected via the included test cables or special test adapters.

The PM 20 SPD test device with integrated sparkover detection allows to


test Yellow/Line or Red/Line surge arresters with integrated varistor, Zener
diode or gas discharge tube. Both the response performance between the
connections of the SPDs as well as the continuity can be tested. The
results can be compared to reference values. In case of deviations, the SPD
or SPD module has to be replaced. Test adapters with a corresponding
support make testing of the SPD modules easier.

Scope of the delivery of PM20 SPD test device

www.dehn.de 363
SPD Test Device MEASURING AND TEST DEVICES
910 511 PM 20

PM 20

PM 20
910 511

• Combined testing of protective cir- Combined device for testing the sparkover voltage of surge arresters (with gas discharge
cuits with gas discharge tubes, varis- tubes/varistors/zener diodes). Storage bag and measuring accessories included.
tors and zener diodes
• Easy handling and flexible use
• For use with PA BXT and PA DRL test
adapters

PM 20
Nominal d.c. voltage UN 8-12 V d.c.
Test parameter: Test voltage max. 1250 V d.c.
Test parameter: Test current (reference voltage) 1 mA d.c., constant
Measured value indication alphanumeric, 8-digit LCD display
Test output sockets safety pole terminals (4 mm), positive pole: red colour, negative pole: black colour
Testing period ≤ 1.5 sec.
Number of individual tests during battery operation typically 2000
Accessories included in delivery 2 test cables, each 1 m long, 2 safety tapping test clips, 1 plug-in power supply unit (230 V a.c.), 1 storage bag
Dimension of storage bag 300x 110 x 110 mm

Ordering information
Type PM 20
Part No. 910 511
Packing unit 1 pc(s).

Accessory Part for SPD Test Device Accessory Part for SPD Test Device
910 507 PA DRL

PA DRL test adapter 910 508 PA BXT

PA BXT test adapter


For connecting to PM 10 / PM 20 and for plugging in and testing SPD For connecting to PM 10 / PM 20 and for plugging in and testing SPD
PA DRL
910 507
modules PA BXT
910 508
modules
PU Part PU Part
Type Plug-in SPD modules pc(s). No. Type Plug-in SPD modules pc(s). No.
PA DRL DEHNrapid LSA and DPL 1 910 507 PA BXT BLITZDUCTOR XT and BLITZDUCTOR CT 1 910 508

364 www.dehn.de
MEASURING AND TEST DEVICES DEHNisola
SPD monitoring device

• SPD monitoring device for potential-free meas-


uring of leakage currents of surge arresters
• Measuring and evaluation device with a com-
pact DIN rail mounted enclosure (1.5 modules)
• 3 hard-wired winding-type transformers
• Self-test and reset function
• Battery supply
• 2 limit values for the leakage currents to be
monitored
• LED indication on site and remote signalling
contact

Continuous function test of installed lightning current and surge arresters DEHNisola: Measuring and evaluation device with 3 hard-
by DEHNisola monitoring device. wired winding-type transformers and fixing
material

910 600 DISO 3

DISO 3
DEHNisola 910 600

Dimension drawing DISO 3 DISO 3: Measuring and evaluation unit with 3 winding-type transformers

DISO 3
Indication of limit value 1 IL 0.5 mArms (indication only on site, will be reset when the value falls below the limit value)
Indication of limit value 2 IL 5 mArms (indication on site and remote signalling, will be reset only by pushing the reset button at the device)
Measuring cycle every hour or acyclically after every discharge process of the protective device to be monitored
Self-test generation of fault currents in each sensor for testing the measuring unit, ‘’reset’’ > 2 sec.
Battery supply battery life: approx. 10 years, LowBatt indication and remote signalling
Remote signalling contact: Max. a.c. switching voltage 125 V
Remote signalling contact: Max. d.c. switching voltage 110 V
Remote signalling contact: Max. switching capacity 30 W
Remote signalling contact: Max. switching current 1A
Remote signalling contact: Cross-sectional area 0.5 to 4 mm2
Operating temperature range -25°C...+60°C
For mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material of measuring and evaluation device thermoplastic, red, UL 94 V-0
Degree of protection of measuring and evaluation device IP 20
Dimension of measuring and evaluation device 1.5 mods., DIN 43880
Dimension of sensors inner Ø11 mm, outer Ø33 mm
Length of the sensor lines 300 mm each
Weight 0.23 kg

Ordering information
Type DISO 3
Part No. 910 600
Packing unit 1 pc(s).

www.dehn.de 365
Impulse Meter MEASURING AND TEST DEVICES
Registration of discharges

• Potential-free registration of discharge cur-


rents of surge protective devices
• Easy installation by enclosing the earth conduc-
tor of the arrester with an open toroidal core
• Counter in a DIN rail mounted enclosure
(2 modules)
• Twisted sensor cable, 1 m long

P2 Impulse Meter: Counter, sensor cable and toroidal core


with fixing material
Counter with integrated battery supply (9 V) and battery
charge control. Indication by 2-digit LCD display with setting
and resetting buttons.

L1

Imp
uls
zäh
ler
P2

910 502 P2

P2 Impulse
Meter P2 910 502

Dimension drawing P2

P2
Response wave for impulse currents (rise time ≥ 8 µs) > 1 kA
Sequence of impulses >1s
LCD display electronic counter 0...99
Power supply 9 V battery, IEC 6LR61 included in delivery, replaceable, battery life > 1 year
Battery charge control button and LED situated at device
Setting device button at device for setting the counter (e.g. after replacing a battery)
Resetting device button at device for resetting the counter to 0
Operating temperature range -10°C...+50°C
For mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material (counter) thermoplastic, red, UL 94 V-0
Enclosure material (sensor) PA 6, grey colour
Degree of protection IP 20
Dimension (counter) 2 mods., DIN 43880
Dimension (sensor) inner Ø 15 mm, outer Ø 36 mm
Length of the connecting cable (between sensor and counter) max. 1 m, twisted
Weight (counter, sensor and connecting cable) 0.2 kg
Accessories included in delivery 9 V battery, IEC 6LR61; cable tie (fixing of sensors)

Ordering information
Type P2
Part No. 910 502
Packing unit 1 pc(s).

366 www.dehn.de
More Information and Documentation
Publications DEHN CD Seminars

DS103 DEHN protects Wind Turbines. DS707 DEHNtour We also give seminars about
DEHN + SÖHNE – Company – Lightning Protection
DS104 DEHN protects Cell Sites. Presentation
DS107 Surge Protection: Safety for Sewage – Surge Protection
DS708 3D Animated films
Plants. – DEHN protects photovoltaic systems – Safety Equipment
DS109 DEHN protects Photovoltaic Systems. – DEHNguard T H...LI
as well as protection for special applications
with Pro-Active-Thermo-Control
DS113 DEHN tests and analyses. like cell sites, photovoltaics, wind turbines, etc.
– New Red/Line-DEHNventil modular
DS122 DEHN protects the Oil and Gas – DEHN protects Cell Sites For more information regarding topics, dates,
Industry. – Protection of Ex (i) circuits locations, etc., please contact the responsible
– Maintenance strategy with representative of DEHN + SÖHNE in your
DS137 DEHN protects Antenna Feeders. BLITZDUCTOR XT country. They shall be pleased to give you the
DS143 BLITZDUCTOR® XT with LifeCheck®. requested information.

DS144 DEHN protects Biogas Plants. Reprints


DS145E LSA with Lightning Current Carrying 61E Surge Protection – Practice-Oriented and Note
Capacity. Standard-Conform; from etz, 10/2006 Like our catalogues and publications, our
DS164E BLITZDUCTOR XTU 63E Lightning and Surge Protection for installation and mounting instructions
Telecommunications and Signalling can also be downloaded from our website
DS150 Easy choice surge protection. Networks; from etz, 02/2007 www.dehn.de.
DS509 DEHN protects.
DS614E DEHN stops Surges. Contact
DS641E Coordinated Surge Protection. The printed publications can be ordered free of
DS649E Surge Protection – Easy choice. charge from our Export Department
Fax +49 9181 906-444
DS702E Lightning Protection Guide export@dehn.de

Further main catalogues


DS396E Safety Equipment
DS427E Lightning Protection

www.dehn.de 367
Literature
DIN VDE Standards, VDE-Verlag, Berlin DIN EN 62305-1 DIN VDE 0800-1:1989-05
DIN VDE 0100-100:2009-06 VDE 0185-305-1:2006-10 Telecommunications;
Low-voltage electrical istallations - Part 1: Protection against lightning – Part 1: General concepts; requirements and tests for
Fundamental principles, assessment of general General principles (IEC 62305-1:2006); the safety of facilities and apparatus
characteristics, definitions (IEC 60364-1:2005, German version EN 62305-1:2006
modified); DIN VDE 0800-2:1985-07
German implementation HD 60364-1:2008 DIN EN 62305-2 Telecommunications;
VDE 0185-305-2:2006-10 Earthing and equipotential bonding
DIN VDE 0100-410:2007-06 Protection against lightning – Part 2:
Risk management (IEC 62305-2:2006); DIN VDE 0800-10:1991-03
Low-voltage electrical installations – Part 4-41:
Protection for safety – Protection against German version EN 62305-2:2006 Telecommunications;
electric shock Transitional requirements on erection and
(IEC 60364-4-41:2005, modified); DIN EN 62305-3 operation of installations
German implementation HD 60364-4-41:2007 VDE 0185-305-3:2006-10
Protection against lightning – Part 3: DIN EN 50114
DIN VDE 0100-540:2007-06 Physical damage to structures and live hazard DIN VDE 0805-514:2009-04
Low-voltage electrical installations – Part 5-54: (IEC 62305-3:2006, modified); Audio, video and information technology
Selection and erection of electrical equipment German version EN 62305-3:2006 equipment - Routine electrical safety testing
– Earthing arrangements, protective conduc- in production;
tors and protective bonding conductors DIN EN 62305-4 German version EN 50514:2008
(IEC 60364-5-54:2002, modified); VDE 0185-305-4:2006-10
German implementation HD 60364- 5-54:2007 Protection against lightning – Part 4: Electrical DIN EN 41003
and electronic systems within structures DIN VDE 0804-100:2009-04
DIN VDE 0100-443:2007-06 (IEC 62305-4:2006); Particular safety requirements for equipment to
German version EN 62305-4:2006 be connected to telecommunication networks;
Low-voltage electrical installations – Part 4-44:
German version EN 41003:2008
Protection for safety – Protection against
DIN EN 50164-1
voltage disturbances and electromagnetic
DIN VDE 0185-201:2009-03 DIN VDE 0845-1:1987-10
disturbances – Clause 443: Protection against
overvoltages of atmospheric origin or due to Lightning protection components (LPC) – Protection of telecommunication systems
switching Part 1: Requirements for connection compo- against lightning, electrostatic discharges and
(IEC 60364-4-44:2001 + A1:2003, modified); nents overvoltages from electric power installations;
German implementation HD 60364-4-443:2006 German version EN 50164-1:2008 provisions against overvoltages

DIN IEC 60060-1 E DIN VDE 0845-2:1993-10


DIN VDE 0100-534:2009-02
DIN VDE 0432-1:1994-06 Protection of information technology and
Low-voltage electrical installations - Part 5-53:
High voltage test techniques – Part 1: General telecommunication against lightning, electro-
Selection and erection of electrical equipment -
specifications and test requirements static discharges and overvoltages from electric
Isolation, switching and control - Clause 534:
(IEC 60060-1:1989 + corrigendum March power installations; requirements and tests of
Devices for protection against overvoltages
1990); German version HD 588.1 S1:1991 overvoltage protection devices
(IEC 60364-5-53:2001/A1:2002 (Clause 534),
modified);
DIN VDE 0618-1:1989-08 DIN EN 60728-11
German implementation HD 60364-5-534:2008
Equipment for equipotential bonding; equipo- VDE 0855-1:2005-10
DIN EN 60664-1 tential bonding busher for main equipotential Cable networks for television signals, sound
bonding signals and interactive services –
DIN VDE 0110-1:2008-01
Part 11: Safety (IEC 60728-11:2005);
Insulation coordination for equipment within
DIN EN 60099-1 German version EN 60728-11:2005
low-voltage systems – Part 1: Principles,
DIN VDE 0675-1:2000-08 remain valid alongside this standard until
requirements and tests
Surge arresters – Part 1: Non-linear resistor 2008-04-01.
(IEC 60664-1:2007) German version
EN 60664-1:2007 type gapped surge arresters for a.c. systems
(IEC 60099-1:1991) DIN 18014:2007-09
DIN VDE 0141:2000-01 German version EN 60099-1:1994 + A1:1999 Foundation earth electrode – General planning
criteria
Earthing system for special power installations
DIN EN 61643-11
with nominal voltages above 1 kV
VDE 0675-6-11:2007-08 IEC 60664-1:2007-04
DIN EN 50178 Low-voltage surge protective devices – Insulation coordination for equipment within
Part 11: Surge protective devices connected to low-voltage systems; part 1: principles,
DIN VDE 0160:1998-04
low-voltage power systems; Requirements and requirements and tests
Electronic equipment for use in power installa-
tests
tions
(IEC 61643-1:1998 + corrigendum 1998, modi- IEC 61643-1:2005-03
German version EN 50178:1997
fied); German version EN 61643-11:2002 + Low-voltage surge protective devices – Part 1:
A11:2007 Surge protective devices connected to low-
voltage power distribution systems –
Requirements and tests

368 www.dehn.de
IEC 61643-21:2000-09 Books
Low voltage surge protective devices – – Hasse P., Wiesinger J., Zischank W.: – Raab V.:
Part 21: Surge protective devices connected to "Handbuch für Blitzschutz und Erdung" "Überspannungsschutz in Verbraucher-
telecommunications and signalling networks – [Lightning Protection and Earthing Guide] anlagen – Auswahl, Errichtung, Prüfung"
Performance requirements and testing methods Pflaum Verlag GmbH & Co.KG, Munich, [Surge protection for consumer’s installati-
5th edition of 2006, ISBN 3-7905-0931-0 ons – Selection, Installation and Testing],
IEC 62305-1:2006-01 Huss-Medien GmbH Verlag Technik, Berlin
– Hasse P., Landers U., Wiesinger J.,
Protection against lightning – Part 1: 2nd updated and amended edition of 2003
Zahlmann P.:
General principles ISBN 3-341-01347-4
"EMV-Blitzschutz von elektrischen und
elektronischen Systemen in baulichen – Raab P., Zahlmann P.:
IEC 62305-3:2006-01
Anlagen – Risiko-Management, Planen und "Loseblattsammlung VDE-Kompass"
Protection against lightning – Part 2: Ausführen nach den neuen Normen der [VDE Guide – Loose leaf collection]
Risk Reihe VDE 0185-305” InfoPLUS-Paket 6 (12th supplemental set)
management 2. vollständig überarbeitete und erweiterte "Neue Blitzschutz-Normen in der Praxis",
Auflage 2007, [EMC-based lightning pro- [New lightning protection standards in
IEC 62305-3:2006-01 tection for electrical and electronic systems practice], VDE Verlag, Berlin Offenbach
Protection against lightning – Part 3: installed into structures – Risk manage-
Physical damage to structures and life hazard ment, design and performance according
to new standard series DIN VDE 0185-305,
IEC 62305-4:2006-01 2nd completely revised and amended
Protection against lightning – Part 4: Electrical edition of 2007], series volume No. 185,
and electronic systems within structures Berlin-Offenbach: VDE Verlag GmbH,
ISBN 9-783800-730018

VG Standards, Beuth-Verlag GmbH


VG 95 372:2009-04
Electromagnetic Compatibility (EMC) including
Electromagnetic Pulse (EMP) and Lightning
Protection – Survey

VG 95 371-10:2003-08
Electromagnetic compatibility (EMC) including Legal Notes
electromagnetic pulse (EMP) and lightning pro-
tection – Fundamentals – Part 10: Threat levels Since we do not carry out the design of systems different conditions of use which are beyond our
for NEMP and lightning or system components, the suggested applica- control. We recommend to check whether the
tion of our products should be regarded as prod- respective DEHN product is suitable for the
VG 96 907-1:2006-10 uct information and for advisory purposes only. intended application.
Nuclear Electromagnetic Pulse (NEMP) and Our oral and written advice on application is Application, use and processing of our products
lightning protection – Design guidelines and based on experience and given to the best of our take place beyond our control. Therefore, the
protective devices – Part 1: Fundamentals knowledge. However, it must be also considered product is completely subject to the user’s res-
as not binding. This particularly applies to the ponsibility.

Further Standards
DVGW GW 309: Elektrische Überbrückung bei
Rohrtrennungen [Electrical bridging of separate Trademarks
pipe sections]. ZfGW-Verlag GmbH, Frankfurt.
– actiVsense® and our brand
Arbeitsgemeinschaft DVGW/VDE für Korrosions-
– BLITZDUCTOR®
fragen (AfK): AfK-Empfehlung Nr. 5/02.86,
Kathodischer Korrosionsschutz in Verbindung – DEHNbloc®
mit explosionsgefährdeten Bereichen [German
– DEHNguard®
Corrosion Protection Committee (AfK): AfK rec-
ommendation No. 5/02.86, Cathodic corrosion – DEHNport®
protection in connection with potentially explo-
– DEHNrapid®
sive areas] ZfGW-Verlag GmbH, Frankfurt are registered trademarks of
– DEHNventil® DEHN + SÖHNE GMBH + CO. KG.
KTA 2206/2000-06: Auslegung von Kernkraft- in Germany
– LifeCheck®
werken gegen Blitzeinwirkung [Protection for
nuclear power plants against lightning effects] – ...MIT SICHERHEIT DEHN.

www.dehn.de 369
General Terms of Sale
1. General, Scope 6. Retention of Title, Assignment, Release of Securities 10. Return of Goods without Legal Liability
1.1 All deliveries and services in business dealings with 6.1 Delivered goods remain our property until the payment 10.1 If no legal claim to return exists, delivered goods will
entrepreneurs take place exclusively under our general of all open business claims up to the point of invoicing. be accepted only with previous agreement from us.
terms of sale (hereinafter “terms of sale”). We oppose The claims of the customer including value-added tax Returns without previous agreement will be send back
deviating regulations, especially conflicting terms of pur- from the resale of reserved goods, i.e., from a work per- – postage-due – to the sender without inspection. The
chase of the customer, unless we expressly agreed to the formance using our goods, should already be transferred customer bears the shipping costs for the return delivery
validity in writing. Our terms of sale apply even if we to us in the amount of the open invoice. In the case that in No. 10.1.
complete unconditional delivery to the customer while the reserved goods from the customer are sold together 10.2 The goods must still be in their original packaging.
knowing that the terms of sale of the customer are in with other goods that do not belong to us, whether it be Special orders or deliveries, which date back more than
conflict with our own. without or after processing, or are delivered within the three months or the net value of which is less than
1.2 Our terms of sale only apply to entrepreneurs within the framework of a working contract, the assignment of the € 75.00, cannot be returned. A processing fee of 15 % of
meaning of section 310, paragraph 1 of the German Civil resulting claim of the reserve buyer is calculated in the the net value of the goods will be charged to cover the
Code (BGB), to current business relationships and to all amount of the value of the reserved goods. cost of the return. If the goods can no longer be resold at
future transactions with the customer. 6.2 Should the value of the granted securities exceed the the list price at the time of the return, an additional
claims by more than 10 %, we are obliged to retransfer deduction (old goods deduction) will be made in addition
2. Offer and Order, Reservation of Right of Modifi- or release the securities upon request. We shall select the to the processing fee. If we make an exception and agree
cation and Copyright securities to be released. to accept the return of parts that are unpackaged or that
2.1 Insofar as not expressly indicated by us as binding, doc- 6.3 Our goods may only be transferred within the framework are no longer in their original packaging, an expense
uments such as diagrams, drawings, and measurements of proper business activity. The customer is not allowed remuneration of at least 15 % will be charged for
are only roughly binding. to pawn or transfer the ownership of goods that are still reworking and repackaging in addition to the processing
2.2 Should our order confirmation contain reasonable expan- in our possession. fee and, if applicable, the old goods deduction.
sions, limitations, or other modifications with respect to 6.4 At our request, the customer is obliged to inform us of 10.3 Returned goods will only be credited to a new invoice.
the order, then the customer’s agreement is implied, if it the purchaser and the arranged price and to show the Credits cannot be used to clear invoices due at the time
does not immediately, at the latest however within 3 assignment to its debtor. of the return.
business days from receipt of the order confirmation,
oppose it. 7. Delivery Period and Appointment 11. Product Information, No Advisory Obligation
2.3 Any order placed in our web shop shall be regarded as an 7.1 The start of the delivery period presupposes the involve- Our deliveries are intended only for speciality stores or
offer to conclude a sales contract. A sales contract only ment of the customer for the clarification of all technical skilled users. Our user information and instructions are
comes into existence if the customer receives a written questions. limited to the details of each written product information
order confirmation or the goods are delivered / services 7.2 Delivery periods as well as delivery schedules will be (e.g., installation instructions, catalogues, data sheets).
are rendered. appropriately extended if they cannot be adhered to as a Further advisory obligations do not exist. Application,
2.4 Our goods are only delivered in the packaging units indi- result of military mobilisation, war, uprising, strike or use, and processing of the products lie solely in the cus-
cated in the catalogues. If a different number of items is lockout, delayed delivery of raw and auxiliary materials, tomer’s realm of responsibility.
ordered, the amount and price of the next larger packag- late delivery by our suppliers, or similar circumstances
ing unit is considered agreed upon. beyond our control. A lasting obstruction under these cir- 12. Use and Protection of Customer Data
2.5 We reserve the right to make technical modifications to cumstances gives us the right to withdraw from the con- We use customer data, which concern the business deal-
our services, insofar as such modifications promote tech- tract without liability for damages. ings with the customer, in terms of the Federal Data
nical progress or are unavoidable based on other circum- Protection Act.
stances and are reasonable for the customer. 8. Liability for Material and Title Defects
2.6 We reserve ownership and copyright rights to diagrams, 8.1 Insofar as there exists a defect of the contract subject 13. Applicable Law, Jurisdiction
drawings, calculations, and other documents; these may that was beyond our control, we can choose to fix the 13.1 German law applies to the mutual contractual obliga-
not be made available to third parties without our defect or provide a defect-free contract subject (replace- tions, their materialisation, interpretation, and imple-
express written consent. ment). mentation as well as all resulting contractual and busi-
8.2 Should the replacement (No. 8.1) not function properly, ness relationships. The application of the UN Agreement
3. Prices, Value-Added Tax, Packaging Costs or should it be unreasonable to the customer, or should on Contracts on the International Purchase of Goods and
3.1 Our prices are subject to change without notice. we seriously and conclusively refuse it or unreasonably the thereafter enacted laws of the Federal Republic of
3.2 Prices include, insofar as nothing else is arranged, cus- delay it, or if other circumstances exist that, upon weigh- Germany is excluded.
tomary packaging from our plant without value-added ing mutual interests, justify immediate resignation or 13.2 Place of performance and jurisdiction for delivery, pay-
tax. On the day of invoicing, the legally identified VAT compensation, then the customer is entitled to choose to ment, and for all obligations, including those from ex-
amount is to be reimbursed to us. lower the contract price or to withdraw from the contract change and cheque payments, is exclusively Nuremberg.
3.3 The cost of non-customary packaging, e.g., collective or and/or demand compensation (No. 8.3). The customer is We reserve the right to file a complaint against the cus-
seaworthy packaging, is invoiced separately. The custo- not entitled to withdraw from the contract if only tomer at its official location.
mer bears the cost of the disposal or return of packaging. insignificant contract inconformities exist, especially
insignificant defects. 14. VAT Identification Number
4. Passing of Risk, Optional Insurance 8.3 Should the customer exclusively choose compensation VAT ID No. DE 133251475
The risk of accidental loss, destruction, or deterioration after proper replacement (No. 8.2), the contract subject
passes to the customer upon dispatch to the customer remains with the customer, if it considers this reasonable.
from our plant, even if carriage-paid delivery is agreed Compensation is limited to the difference between the DEHN + SÖHNE GmbH + Co. KG.
upon. At the request and expense of the customer, we purchase price (without value-added tax) and the value Nürnberg – Neumarkt
will insure the delivery against breakage, damage to of the defective subject of the contract that remains with
goods in transit and fire damage. the customer. Update July 2009
8.4 Material and title defect claims, including claims for com-
5. Payment Due Dates, Discounts, Right of Refusal, pensation due to material and title defects, with the
Default, Small Order Quantity Surcharge exception of claims under the Product Liability Act, lapse
5.1 Unless otherwise agreed, invoices are payable net 10 12 months after delivery of the goods.
days. Purchaser shall pay the costs of payment. Discount 8.5 Numbers 8.1 through 8.4 do not impair the customer’s
amounts are deductible only if they have been agreed on rights if we maliciously concealed a defect or if we
with us and all accounts payable due have been paid. offered a quality guarantee.
5.2 If purchaser is in default with his payments, interest on
the outstanding amount shall be payable at the rate of 9. Liability for Other Reasons
8 % above the base interest rate. We reserve the right to 9.1 Our liability is excluded for slightly negligent infringe-
prove and allege higher default damages. We reserve the ment of immaterial contractual obligations. Our liability
right to cause default by demanding early payment. If we is limited to the contractual, foreseeable damage for
are required to advance performance and, if after the negligent infringement of other obligations.
execution of the contract, it becomes apparent that our 9.2 The above regulation does not apply to claims under the
claim, in particular for payment, may be jeopardised by Product Liability Act. Insofar as the limitation on liability
purchaser’s inability to perform we may refuse perform- pursuant to No. 9.1 for claims from the producer’s liabil-
ance. ity pursuant to § 823 of the German Civil Code does not
5.3 The customer cannot charge counter-claims against our interfere, our liability is limited to the replacement of the
due payment claims or exercise a right of retention, insurance. Insofar as this does not occur or does not
unless the customer is entitled to a claim recognised by occur in full, we are liable up to the insured amount.
declaratory judgement that is not contested by us and if, 9.3 Insofar as our liability is excluded or limited, this also
while exercising the right of retention, the counter-claim applies for the personal liability of all of our employees,
from the customer is based on the same contractual rela- representatives, and vicarious agents.
tionship. 9.4 Our liability is unrestricted if the customer loses his/her
5.4 Orders, with the exception of cash sales, for which the life or suffers a bodily or health injury due to an action or
net amount (invoiced amount without shipping costs and failure attributable to us.
value-added tax) is less than € 75.00, a small order sur-
charge of € 25.00 will be charged.

370 www.dehn.de
Key to Symbols used in Basic Circuit Diagrams

Symbol Description Standard Symbol Description Standard


Creepage discharge spark gap, Gas discharge tube EN 60617
energy-controlled, encapsulated (single) Part 7
(DEHNventil® TNC/TNS/TT/2P/2P TT) tA ≤ 100 ns 07-22-04

Creepage discharge spark gap, Gas discharge tube EN 60617


non-exhausting, encapsulated (balanced) Part 7
(DEHNbloc®, DEHNbloc® NH) tA ≤ 100 ns 07-22-05

Resistor, EN 60617
Creepage discharge spark gap Decoupling element, Part 4
general 04-01-01

EN 60617 EN 60617
Varistor Part 4 Capacitor Part 4
tA ≤ 25 ns 04-01-04 04-02-01

EN 60617
Thermal disconnector Part 7 Inductor
07-09-03

EN 60617
Thermo Dynamic Control Parts 7 + 11 Resistor,
07-09-03 temperature-controlled
111-07-02

EN 60617 EN 60617
Spark gap, general Part 7 Socket and plug connector Part 3
07-22-01 03-03-05

EN 60617 EN 60617
Fuse Part 7 Break contact Part 7
07-21-01 07-02-03

EN 60617
Temperature fuse Changeover contact Part 7
07-02-04

EN 60617 EN 60617
Filter, general Part 10 Close contact Part 7
10-16-03 07-02-01

EN 60617 EN 60617
LED, general Part 8 Enclosure with Parts 2 + 3
08-10-01 terminals 02-01-07
03-02-02

EN 60617 EN 60617
Suppressor diode, bipolar Part 5 Acoustic signal Part 8
tA ≤ 1 ns 05-03-07 08-10-05

EN 60617
Z diode, unipolar Part 5
tA ≤ 1 ns 05-03-06

www.dehn.de 371
Part No. Index
Part No. Type Page Part No. Type Page Part No. Type Page Part No. Type Page

106 310 – 279 563 010 PAS 10RK 355 906 058 ALGA 5 X 334 910 502 P2 366
106 329 – 279 563 011 RK 16 PAS 355 906 059 MS ALGA 5 X 335 910 507 PA DRL 364
563 012 RK FL30 PAS 355 906 100 DPG LSA 30 P 242 910 508 PA BXT 364
277 230 FBH 6 ST 357 563 013 RK 95 PAS 355 906 101 DPG LSA 60 P 242 910 511 PM 20 364
277 237 FBH 6 CU 357 563 014 SB PAS RK 355 906 102 DPG LSA 120 P 242 910 600 DISO 3 365
277 239 FBH 6 V2A 357 563 015 AH PAS RK 355 906 103 DPG LSA 220 P 242 910 631 DSI E 3 57
277 240 FBH 11 ST 357 563 016 KS 198 PAS 355 910 641 LWL ST DSI 57
907 208 GDT 230 G3 240
563 017 KS 398 PAS 355 910 642 LWL DSI 18M 57
290 001 AH FE RF V G 357 907 214 DPL 10 G3 110 240
563 018 KS 798 PAS 355 910 652 LCS DRC BXT 362
290 002 AH FE RF 357 907 216 DPL 10 G3 110 FSD 240
563 019 RK FL40 PAS 355 910 653 DRC LC M3+ 362
907 217 GDT 230 G3 FSD 240
308 001 KV FE UNI 357 563 020 PAS 9RK 355 910 654 LCS DRC BCT 362
907 218 GDT 230 B3 238
308 025 VK A UNI ST 357 563 030 PAS 14RK 355 910 695 DRC MCM XT 360
907 219 GDT 230 B3 FSD 238
308 026 VK A UNI V2 ST 357 563 050 PAS 9AK 355 910 697 TW DRC MCM EX 319
907 400 DRL 10 B 180 231
308 030 VK A R22 F40 STBL 357 563 105 PAS 6RK OH 355
907 401 DRL 10 B 180 FSD 232 912 253 SPS PRO 127
308 040 MMVK R16 R25 STBL 357 563 169 AK RPA V2A 357
907 420 DRL RE 5 233 912 254 NF 10 125
308 041 MMVK R16 R25 ST 357 563 200 PAS 11AK 355
907 421 DRL RE 12 233 912 260 SFL PRO 142
308 120 VK EH R10 F30 ST 357 563 201 PAS 11AK UV 355
907 422 DRL RE 24 233 912 261 SFL PRO SE 142
308 129 VK EH R10 F30 V2A 357 563 222 AK FL40 PAS 355
907 423 DRL RE 48 233
308 150 – 357 918 400 BVT TTY 24 219
900 050 DGPM 1 255 S 65 907 424 DRL RE 60 233
308 403 SAK 10 AS V4A 326 918 401 BVT RS485 5 221
308 404 SAK 14 AS V4A 326 900 120 DB 3 255 H 59 907 425 DRL RE 180 233
918 402 BVT AD 24 222
900 132 DGP BN 255 66 907 430 DRL PD 180 235
308 405 SAK 18 AS V4A 326 918 404 BVT KKS ALD SN 227
900 159 DB 1 440 61 907 440 DRL RD 5 234
308 406 SAK 21 AS V4A 326 918 405 BVT KKS APD SN 228
900 216 T C H 255 102 907 441 DRL RD 12 234
308 407 SAK 26 AS V4A 326 918 407 BVT MTTY 24 220
900 220 DBM 1 255 S 55 907 442 DRL RD 24 234
308 408 SAK 33 AS V4A 326 918 408 BVT ALD 36 223
900 222 DB 1 255 H 59 907 443 DRL RD 48 234
308 411 AK 16 AS SAK MS 327 918 410 BVT ISDN 257
900 255 DBM NH00 255 50 907 444 DRL RD 60 234
308 421 AS SAK 1000 V2A 326 918 411 BVT TC 1 258
900 261 V NH00 280 116 907 445 DRL RD 110 234
308 425 ST AS SAK K 327 918 420 BVT KKS ALD 75 225
900 262 VA NH00 280 117 907 465 DRL HD 5 236
918 421 BVT KKS APD 36 226
416 411 – 279 900 263 V NH00 280 FM 116 907 470 DRL HD 24 236
900 264 VA NH00 280 FM 117 907 497 SR DRL 238 919 010 SAK 6.5 SN MS 329
472 021 ES 2X6AP 10 ST 356 900 269 DGP B NH00 N 255 67 907 498 EF 10 DRL 237 919 011 SAK 11 SN MS 329
472 022 ES 2X3AP 10 ST 356 900 270 V NH1 280 116 907 499 BM 10 DRL 238 919 012 SH1 18X3 ST 330
472 023 ES 2X2AP 10 ST 356 900 271 VA NH1 280 117 907 991 TL2 10DA CC 245 919 013 SH2 18X3 ST 330
472 024 ES 2X4AP ST 356 900 273 DB NH00 255 H 60 907 993 EL2 38EA LSA 244 919 014 SH 18X3 K 330
472 109 ES 2X2AP 10 V2A 356 900 330 DLM PV 1000 43 907 994 AW2 LSA 243 919 015 AK 35 SN 18X3 GG 331
472 119 ES 2X3AP 10 V2A 356 900 390 DV ZP TNC 255 40 907 995 MB2 10 LSA 243 919 016 SN 18X3 CU 1000 329
472 129 ES 2X4AP 10 V2A 356 900 391 DV ZP TT 255 41 907 996 TL2 10DA LSA 244 919 030 SKB 19 9M SW 333
472 139 ES 2X6AP 10 V2A 356 900 411 EB DG 1000 1 3 151 907 997 AL2 10DA LSA 244 919 031 SA KRF 10 V2A 333
472 201 BS M10 PAS 356 900 417 EB 1 4 9 151 919 032 SA KRF 15 V2A 333
472 207 PAS I 6AP M10 CU 356 909 230 DPRO 230 139
900 471 VC 280 2 144 919 033 SA KRF 22 V2A 333
472 209 PAS I 6AP M10 V2A 356 909 235 DPRO 230 SE 139
900 589 STAK 2X16 145 919 034 SA KRF 29 V2A 333
472 210 IS PAS M10 356 909 240 DPRO 230 F 140
900 595 MVS 3 6 150 919 035 SA KRF 37 V2A 333
472 217 PAS I 10AP M10 CU 356 909 245 DPRO 230 SE F 140
900 610 MVS 1 4 149 919 036 SA KRF 50 V2A 333
472 219 PAS I 10AP M10 V2A 356 909 300 DPRO 230 TV 338
900 611 MVS 1 8 150 919 037 SA KRF 70 V2A 333
472 227 PAS I 8AP M10 CU 356 909 305 DPRO 230 SE TV 338
900 612 MVS 1 57 150 919 038 SA KRF 94 V2A 333
472 229 PAS I 8AP M10 V2A 356 909 310 DPRO 230 NT 339
900 614 MVS 4 56 151 919 880 KB 10 DCO RK 217
472 237 PAS I 12AP M10 CU 356 909 315 DPRO 230 SE NT 339
900 615 MVS 1 3 149 919 920 DCO RK ME 12 210
472 239 PAS I 12AP M10 V2A 356 909 320 DPRO 230 ISDN 340
900 617 MVS 1 2 149 919 921 DCO RK ME 24 210
472 269 AD PAS 8AP V2A 356 909 325 DPRO 230 SE ISDN 340
900 813 MVS 3 6 8 150 919 922 DCO RK ME 48 210
472 279 AD PAS 6AP V2A 356 909 321 DPRO 230 LAN100 341
900 814 MVS 4 8 11 151 919 923 DCO RK ME 110 210
472 289 AD PAS 10AP V2A 356 909 326 DPRO 230 SE LAN100 341
900 815 MVS 1 6 149 919 940 DCO RK MD 12 211
472 299 AD PAS 12AP V2A 356 909 703 DGA FF TV 272
900 848 MVS 1 7 150 919 941 DCO RK MD 24 211
909 704 DGA GF TV 272
540 801 EX BRS 90 351 919 942 DCO RK MD 48 212
902 315 IGA 10 V2 IP54 146 909 705 DGA GFF TV 272
540 803 EX BRS 300 351 919 943 DCO RK MD 110 213
902 471 IGA 12 IP54 147 909 710 DGA BNC VCD 271
540 805 EX BRS 500 351 919 960 DCO RK MD EX 24 323
902 472 IGA 24 IP54 147 909 711 DGA BNC VCID 271
540 810 – 352 919 970 DCO RK MD HF 5 214
902 485 IGA 6 IP54 148
540 821 EX BRS 27 351 910 099 SLK 16 335 919 976 BS 1 50 S DCO RK 217
540 901 – 352 906 055 ALGA 5 334 910 486 USB NANO 485 360 919 977 BS 1 50 DCO RK 217

372 www.dehn.de
Part No. Index
Part No. Type Page Part No. Type Page Part No. Type Page Part No. Type Page

919 978 AD DCO RK BL 323 923 021 KFSU 343 929 047 DGA L4 7 16 S 277 951 205 DV M TN 255 FM 35
919 979 AD DCO RK GE 217 923 023 TFS 343 929 048 DGA L4 7 16 B 277 951 300 DV M TNC 255 32
919 986 DCO RK D 5 24 216 923 025 AL EXFS L100 KS 345 929 057 DGA AG U 275 951 305 DV M TNC 255 FM 32
919 987 DCO RK E 12 215 923 035 AL EXFS L200 KS 345 929 059 DGA L4 N EB 278 951 310 DV M TT 255 34
919 988 DCO RK E 24 215 923 045 AL EXFS L300 KS 345 929 071 NET PRO TC 2 250 951 315 DV M TT 255 FM 34
919 989 DCO RK E 48 215 923 060 EXFS L100 348 929 072 NET PRO TC 2 LSA 250 951 400 DV M TNS 255 33
919 990 DCO RK E 60 215 923 061 EXFS L200 348 929 075 NET PRO E1 LSA G703 251 951 405 DV M TNS 255 FM 33
923 062 EXFS L300 348 929 081 DLI TC ECO RJ12 264
920 211 BXT ML2 B 180 195 952 010 DG MOD 275 95
923 100 EXFS 100 345 929 095 EB 4 F 279
920 220 BXT ML2 BE S 5 199 952 011 DG MOD 75 95
923 101 EXFS 100 KU 346 929 096 EL 16 B17 279
920 222 BXT ML2 BE S 12 199 952 012 DG MOD 150 95
923 110 SDS 1 354 929 100 DPA M CAT6 RJ45S 48 254
920 224 BXT ML2 BE S 24 199 952 013 DG MOD 320 95
923 116 SDS 3 354 929 110 DPA M CAT6 RJ45H 48 254
920 225 BXT ML2 BE S 48 199 952 014 DG MOD 385 95
923 117 SDS 2 354 929 121 DPA M CLE RJ45B 48 255
920 240 BXT ML2 BD S 5 197 952 015 DG MOD 440 95
923 118 SDS 4 354 929 199 MS DPA 254
920 242 BXT ML2 BD S 12 197 952 016 DG MOD 600 95
923 119 SDS 5 354 929 230 NET PRO 10X TC1 RST 252
920 243 BXT ML2 BD DL S 15 198 952 017 DG MOD 750 95
929 234 EG NET PRO 10X 19” 252
920 244 BXT ML2 BD S 24 197 924 016 FS 15E 5 284 952 018 DG MOD 48 95
929 235 EG NET PRO 10X 3HE 252
920 245 BXT ML2 BD S 48 197 924 017 FS 9E PB 6 282 952 020 DG MOD CI 275 98
929 446 DGA LG 7 16 X 276
920 247 BXT ML2 BD 180 196 924 018 FS 25E HS 12 285 952 025 DG MOD 75 VA 97
929 496 GDT DGA 90 X 279
920 249 BXTU ML2 BD S 0-180 182 924 019 FS 9E HS 12 283 952 027 DG MOD 275 VA 97
929 497 GDT DGA 90 279
920 270 BXT ML2 BE HFS 5 200 924 046 USD 25 V24 HS S B 288 929 498 GDT DGA 230 279 952 029 DG MOD 385 VA 97
920 271 BXT ML2 BD HFS 5 201 924 051 USD 15 V11 S B 287 952 030 DGP C S 93
929 499 GDT DGA 470 279
920 300 BXT BAS 183 924 061 USD 9 V24 S B 286 952 035 DGP C S FM 93
929 921 DPI ME 24 N A2G 299
920 301 BXT BAS EX 313 924 270 DSM ISDN SK 290 952 050 DG MOD NPE 96
929 941 DPI MD 24 M 2S 298
920 308 BXT M4 E 202 924 272 DSM TC 2 SK 291 952 051 DG MOD PV SCI 500 97
929 960 DPI MD EX 24 M 2 303
920 309 BXT M4 T 203 924 274 DSM TM 260 952 053 DG MOD PV SCI 300 97
929 961 DPI CD EXI 24 M 306
920 310 BXT ML4 B 180 187 924 328 AR1 STW 129 952 054 DG MOD PV SCI 600 97
929 962 DPI CD EXD 24 M 308
920 320 BXT ML4 BE 5 188 924 329 ZAP STW 129 952 060 DGP C MOD 96
929 963 DPI CD EXI 24 N 306
920 322 BXT ML4 BE 12 188 924 335 NSM PRO TW 137 952 070 DG S 275 89
929 964 DPI CD EXD 24 N 308
920 324 BXT ML4 BE 24 188 924 336 AR1 TW 137 952 071 DG S 75 89
929 969 DPI CD EXD 230 24 M 310
920 325 BXT ML4 BE 48 188 924 337 NSM PRO SI 137 952 072 DG S 150 89
929 970 DPI CD EXD 230 24 N 310
920 326 BXT ML4 BE 60 188 924 338 AR1 SI 137 952 073 DG S 320 89
929 971 DPI CD HF EXD 5 M 309
920 327 BXT ML4 BE 180 188 924 339 NSM PRO AZ 137 952 074 DG S 385 89
929 982 KV S M20 MS 9.5 300
920 336 BXT ML4 BE 36 188 924 340 AR1 AZ 137 952 075 DG S 440 89
929 984 KV M20 MS 10.5 300
920 340 BXT ML4 BD 5 189 924 342 NSM PRO EW 137 929 996 ER DPI M20 300 952 076 DG S 600 89
920 342 BXT ML4 BD 12 189 924 343 AR1 EW 137 952 077 DG S WE 600 91
920 344 BXT ML4 BD 24 189 924 350 STC 230 131 950 102 DG 1000 111 952 078 DG S 48 89
920 345 BXT ML4 BD 48 189 924 370 DSA 230 LA 129 950 112 DG 1000 FM 111 952 079 DG S CI 275 75
920 346 BXT ML4 BD 60 189 924 389 DFL A 255 134 950 120 DG T H 275 LI 103 952 080 DG S 75 VA 113
920 347 BXT ML4 BD 180 189 924 395 DFL D 255 135 950 121 DG T H 385 LI 103 952 082 DG S 275 VA 113
920 349 BXTU ML4 BD 0-180 181 924 396 DFL M 255 133 950 130 T H 275 LI 103 952 084 DG S 385 VA 113
920 350 BXT ML4 BC 5 190 950 131 T H 385 LI 103 952 085 DG S 75 VA FM 114
925 001 BT 24 293
920 354 BXT ML4 BC 24 190 950 150 DG TT H230 400 LI 102 952 087 DG S 275 VA FM 114
925 013 AS IBAS YE 295
920 362 BXT ML4 BE C 12 191 950 151 DG TT H230 400 LI385 102 952 089 DG S 385 VA FM 114
920 364 BXT ML4 BE C 24 191 950 160 DG TNC H230 400 LI 100 952 090 DG S 275 FM 90
929 010 UGKF BNC 268
920 370 BXT ML4 BE HF 5 192 950 170 DG TNS H230 400 LI 101 952 091 DG S 75 FM 90
929 024 DLI ISDN I 262
920 371 BXT ML4 BD HF 5 193 950 500 DG PV 500 SCP 108 952 092 DG S 150 FM 90
929 026 DLI TC BT 266
920 375 BXT ML4 BD HF 24 193 950 501 DG PV 700 SCP 108 952 093 DG S 320 FM 90
929 028 DLI TC 2 I 263
920 381 BXT ML4 BD EX 24 314 950 502 DG PV 1200 SCP 108 952 094 DG S 385 FM 90
929 034 EG NET PRO 19” 249
920 384 BXT ML4 BC EX 24 315 950 505 DG PV 500 SCP FM 109 952 095 DG S 440 FM 90
929 035 NET PRO 4TP 249
920 389 BXT ML4 MY 250 194 950 506 DG PV 700 SCP FM 109 952 096 DG S 600 FM 90
929 036 NET PRO LSA 4TP 249
920 395 SAK BXT LR 202 950 507 DG PV 1200 SCP FM 109 952 097 DG S WE 600 FM 91
929 037 NET PRO 4TP 30 249
920 398 BS BA1 BA15 BXT 204 952 098 DG S 48 FM 90
929 040 DGA F 1.6 5.6 273 951 001 DV MOD 255 38
920 399 BS 1 50 BXT 204 952 099 DG S CI 275 FM 75
929 042 DGA G BNC 274 951 050 DV MOD NPE 50 38
920 538 BXT ML2 BD HF EX 6 316 952 110 DG M TT 2P 275 85
929 043 DGA AG BNC 275 951 100 DV MOD NPE 100 38 952 111 DG M TT 2P 385 85
929 044 DGA G N 274
923 011 IF1 345 951 110 DV M TT 2P 255 36 952 115 DG M TT 2P 275 FM 86
929 045 DGA AG N 275
923 016 IF3 345 951 115 DV M TT 2P 255 FM 36 952 116 DG M TT 2P 385 FM 86
929 046 DGA LG 7 16 276
923 019 EXFS KU 349 951 200 DV M TN 255 35 952 130 DG M TT 2P 320 85

www.dehn.de 373
Part No. Index
Part No. Type Page Part No. Type Page Part No. Type Page Part No. Type Page

952 135 DG M TT 2P 320 FM 86 952 315 DG M TT 275 FM 82 952 517 DG M YPV SCI 1200 FM 106 961 001 DB M MOD 150 48
952 171 DG M TT 2P CI 275 74 952 316 DG M TT 385 FM 82 952 699 DK 25 145 961 002 DB M MOD 255 48
952 173 DG M TN CI 275 73 952 318 DG M TNC 150 FM 78 961 003 DB M MOD 320 48
953 010 DR MOD 255 124
952 176 DG M TT 2P CI 275 FM 74 952 319 DG M TNC 385 FM 78 961 010 DGP M MOD 255 64
953 011 DR MOD 30 124
952 178 DG M TN CI 275 FM 73 952 320 DG M TT 320 81 961 101 DGP M 255 64
953 012 DR MOD 60 124
952 200 DG M TN 275 83 952 322 DG M TT CI 275 72 961 105 DGP M 255 FM 64
953 013 DR MOD 75 124
952 201 DG M TN 150 83 952 325 DG M TT 320 FM 82 961 110 DB M 1 150 46
953 014 DR MOD 150 124
952 205 DG M TN 275 FM 84 952 327 DG M TT CI 275 FM 72 961 115 DB M 1 150 FM 47
953 020 DR MOD 4P 255 124
952 206 DG M TN 150 FM 84 952 400 DG M TNS 275 79 961 120 DB M 1 255 46
953 200 DR M 2P 255 120
952 300 DG M TNC 275 77 952 401 DG M TNS CI 275 71 961 125 DB M 1 255 FM 47
953 201 DR M 2P 30 120
952 302 DG M WE 600 87 952 403 DG M TNS 150 79 961 130 DB M 1 320 46
953 202 DR M 2P 60 120
952 303 DG M TNC 440 77 952 404 DG M TNS 385 79 961 135 DB M 1 320 FM 47
953 203 DR M 2P 75 120
952 304 DG M TNC CI 275 70 952 405 DG M TNS 275 FM 80 961 140 DBM 1 440 52
953 204 DR M 2P 150 120
952 305 DG M TNC 275 FM 78 952 406 DG M TNS CI 275 FM 71 961 145 DBM 1 440 FM 52
953 205 DR M 2P 255 FM 121
952 307 DG M WE 600 FM 87 952 408 DG M TNS 150 FM 80 961 160 DGPM 440 68
953 206 DR M 2P 30 FM 121
952 308 DG M TNC 440 FM 78 952 409 DG M TNS 385 FM 80 961 165 DGPM 440 FM 68
953 207 DR M 2P 60 FM 121
952 309 DG M TNC CI 275 FM 70 952 510 DG M YPV SCI 1000 105 961 175 DBM 1 760 FM 53
953 208 DR M 2P 75 FM 121
952 310 DG M TT 275 81 952 511 DG M YPV SCI 600 105
953 209 DR M 2P 150 FM 121 989 408 ITAK EXI BXT 24 321
952 311 DG M TT 385 81 952 512 DG M YPV SCI 1200 105
953 400 DR M 4P 255 123
952 313 DG M TNC 150 77 952 515 DG M YPV SCI 1000 FM 106
952 314 DG M TNC 385 77 952 516 DG M YPV SCI 600 FM 106 953 405 DR M 4P 255 FM 123

374 www.dehn.de
Type / Product Index
Type Product Part No. Page Type Product Part No. Page

– Angled fixing plate for DEHNgate 106 310 279 BXT ML2 BD DL S 15 BXT Protection Module LifeCheck BD DL, 17 V 920 243 198
– Angled fixing plate for DEHNgate 106 329 279 BXT ML2 BD HF EX 6 BXT Protection Module LifeCheck BD HF EX, 6 V 920 538 316
– Expansion strap f. foundation earthing electrodes 308 150 357 BXT ML2 BD HFS 5 BXT Protection Module LifeCheck BD, 6 V 920 271 201
– Earth conductor, open/closed cable lugs 416 411 279 BXT ML2 BD S 5 BXT Protection Module LifeCheck BD, 6 V 920 240 197
– Separate clamping element 540 810 352 BXT ML2 BD S 12 BXT Protection Module LifeCheck BD, 15 V 920 242 197
– Tensioning strap 540 901 352 BXT ML2 BD S 24 BXT Protection Module LifeCheck BD, 33 V 920 244 197
BXT ML2 BD S 48 BXT Protection Module LifeCheck BD, 54 V 920 245 197
AD DCO RK BL Covering Plate for DCO, blue 919 978 323 BXT ML2 BE HFS 5 BXT Protection Module LifeCheck BE, 6 V 920 270 200
AD DCO RK GE Covering Plate for DCO, yellow 919 979 217 BXT ML2 BE S 5 BXT Protection Module LifeCheck BE, 6 V 920 220 199
AD PAS 6AP V2A Cover NIRO, for 6-pole EB 472 279 356 BXT ML2 BE S 12 BXT Protection Module LifeCheck BE, 15 V 920 222 199
AD PAS 8AP V2A Cover NIRO, for 8-pole EB 472 269 356 BXT ML2 BE S 24 BXT Protection Module LifeCheck BE, 33 V 920 224 199
AD PAS 10AP V2A Cover NIRO, for 10-pole EB 472 289 356 BXT ML2 BE S 48 BXT Protection Module LifeCheck BE, 54 V 920 225 199
AD PAS 12AP V2A Cover NIRO, for 12-pole EB 472 299 356 BXT ML4 B 180 BXT Protection Module LifeCheck B, 180 V 920 310 187
AH FE RF Distance Holder St/tZn, DIN 48833 A, 280 mm 290 002 357 BXT ML4 BC 5 BXT Protection Module LifeCheck BC, 6 V 920 350 190
AH FE RF V G Distance Holder St/tZn, reinf. version 300 mm 290 001 357 BXT ML4 BC 24 BXT Protection Module LifeCheck BC, 33 V 920 354 190
AH PAS RK Plastic cover, grey 563 015 355 BXT ML4 BC EX 24 BXT Protection Module LifeCheck BC EX, 24 V 920 384 315
AK 16 AS SAK MS Protective Conductor Terminal, -16 mm√ 308 411 327 BXT ML4 BD 5 BXT Protection Module LifeCheck BD, 6 V 920 340 189
AK 35 SN 18X3 GG Terminal for Busbar 919 015 331 BXT ML4 BD 12 BXT Protection Module LifeCheck BD, 15 V 920 342 189
AK FL40 PAS Terminal for Fl 40 563 222 355 BXT ML4 BD 24 BXT Protection Module LifeCheck BD, 33 V 920 344 189
AK RPA V2A Terminal St/tZn 563 169 357 BXT ML4 BD 48 BXT Protection Module LifeCheck BD, 54 V 920 345 189
AL EXFS L100 KS Connecting cable for EXFS 100, length: 100 mm 923 025 345 BXT ML4 BD 60 BXT Protection Module LifeCheck BD, 70 V 920 346 189
AL EXFS L200 KS Connecting cable for EXFS 100, length: 200 mm 923 035 345 BXT ML4 BD 180 BXT Protection Module LifeCheck BD, 180 V 920 347 189
AL EXFS L300 KS Connecting cable for EXFS 100, length: 300 mm 923 045 345 BXT ML4 BD EX 24 BXT Protection Module LifeCheck BD EX, 24 V 920 381 314
AL2 10DA LSA Terminal Block 10TC LSA-PLUS 907 997 244 BXT ML4 BD HF 5 BXT Protection Module LifeCheck BD HF, 6 V 920 371 193
ALGA 5 Aluminium Enclosure IP65 906 055 334 BXT ML4 BD HF 24 BXT Protection Module LifeCheck BD HF, 24 V 920 375 193
ALGA 5 X Aluminium Enclosure IP65 for BCT 906 058 334 BXT ML4 BE 5 BXT Protection Module LifeCheck BE, 6 V 920 320 188
AR1 AZ Protector Cover, single piece, anthracite 924 340 137 BXT ML4 BE 12 BXT Protection Module LifeCheck BE, 15 V 920 322 188
AR1 EW Protector Cover, single piece, studio white 924 343 137 BXT ML4 BE 24 BXT Protection Module LifeCheck BE, 33 V 920 324 188
AR1 SI Protector Cover, single piece, silver 924 338 137 BXT ML4 BE 36 BXT Protection Module LifeCheck BE, 45 V 920 336 188
AR1 STW Covering Frame for DEHNsafe, studio white 924 328 129 BXT ML4 BE 48 BXT Protection Module LifeCheck BE, 54 V 920 325 188
AR1 TW Protector Cover, single-piece, titan white 924 336 137 BXT ML4 BE 60 BXT Protection Module LifeCheck BE, 70 V 920 326 188
AS IBAS YE Coupling Module 925 013 295 BXT ML4 BE 180 BXT Protection Module LifeCheck BE, 180 V 920 327 188
AS SAK 1000 V2A Anchor Bar, stainless steel, 1 m long 308 421 326 BXT ML4 BE C 12 BXT Protection Module LifeCheck BE C, 12 V 920 362 191
AW2 LSA Insertion Tool LSA-PLUS 907 994 243 BXT ML4 BE C 24 BXT Protection Module LifeCheck BE C, 33 V 920 364 191
BXT ML4 BE HF 5 BXT Protection Module LifeCheck BE HF, 6 V 920 370 192
BM 10 DRL Plug-in SPD Block (without SPDs) 907 499 238
BXT ML4 MY 250 BXT Protection Module LifeCheck MY, 320 V 920 389 194
BS 1 50 BXT Labelling System, printed with numbers 1-50 920 399 204
BXTU ML4 BD 0-180 BXT Protection Module LifeCheck BD, 0-180 V 920 349 181
BS 1 50 DCO RK Quick Marking System for DCO RK 919 977 217
BXTU ML2 BD S 0-180 BXT Protection Module LifeCheck BD S, 0-180 V 920 249 182
BS 1 50 S DCO RK Quick Marking System for DCO RK 919 976 217
BS BA1 BA15 BXT Marking System for BXT 920 398 204 DB 1 255 H DEHNbloc 1 255 H 900 222 59
BS M10 PAS Fixing Set for EB 472 201 356 DB 1 440 DEHNbloc 1 440 900 159 61
BT 24 BUStector 925 001 293 DB 3 255 H DEHNbloc 3 255 H 900 120 59
BVT AD 24 BLITZDUCTOR VT 918 402 222 DB M 1 150 DEHNbloc Maxi modular 1 150 961 110 46
BVT ALD 36 BLITZDUCTOR VT 918 408 223 DB M 1 150 FM DEHNbloc Maxi modular 1 150 FM 961 115 47
BVT ISDN BLITZDUCTOR VT 918 410 257 DB M 1 255 DEHNbloc Maxi modular 1 255 961 120 46
BVT KKS ALD 75 BLITZDUCTOR VT 918 420 225 DB M 1 255 FM DEHNbloc Maxi modular 1 255 FM 961 125 47
BVT KKS ALD SN BLITZDUCTOR VT 918 404 227 DB M 1 320 DEHNbloc Maxi modular 1 320 961 130 46
BVT KKS APD 36 BLITZDUCTOR VT 918 421 226 DB M 1 320 FM DEHNbloc Maxi modular 1 320 FM 961 135 47
BVT KKS APD SN BLITZDUCTOR VT 918 405 228 DB M MOD 150 Protection module for DB M, 150 V 961 001 48
BVT MTTY 24 BLITZDUCTOR VT 918 407 220 DB M MOD 255 Protection module for DB M, 255 V 961 002 48
BVT RS485 5 BLITZDUCTOR VT 918 401 221 DB M MOD 320 Protection module for DB M, 320 V 961 003 48
BVT TC 1 BLITZDUCTOR VT 918 411 258 DB NH00 255 H DEHNbloc NH00 255 H 900 273 60
BVT TTY 24 BLITZDUCTOR VT 918 400 219 DBM 1 255 S DEHNbloc Maxi S 900 220 55
BXT BAS BXT Base Part 920 300 183 DBM 1 440 DEHNbloc Maxi 1 440 961 140 52
BXT BAS EX BXT Base Part Ex(i) 920 301 313 DBM 1 440 FM DEHNbloc Maxi 1 440 FM 961 145 52
BXT M4 E BXT Earthing Module 920 308 202 DBM 1 760 FM DEHNbloc Maxi 1 760 FM 961 175 53
BXT M4 T BXT Testing / Disconnecting Module 920 309 203 DBM NH00 255 DEHNbloc Maxi NH00 900 255 50
BXT ML2 B 180 BXT Protection Module LifeCheck B, 180 V 920 211 195 DCO RK D 5 24 DEHNconnect RK D, +24/-5 V 919 986 216
BXT ML2 BD 180 BXT Protection Module LifeCheck BD, 180 V 920 247 196 DCO RK E 12 DEHNconnect RK E, 12 V 919 987 215

www.dehn.de 375
Type / Product Index
Type Product Part No. Page Type Product Part No. Page

DCO RK E 24 DEHNconnect RK E, 24 V 919 988 215 DG M WE 600 FM DEHNguard modular M WE FM, 3-pole 952 307 87
DCO RK E 48 DEHNconnect RK E, 48 V 919 989 215 DG M YPV SCI 600 DEHNguard M YPV SCI 600 952 511 105
DCO RK E 60 DEHNconnect RK E, 60 V 919 990 215 DG M YPV SCI 600 FM DEHNguard M YPV SCI 600 FM 952 516 106
DCO RK MD 12 DEHNconnect RK MD, 12 V 919 940 211 DG M YPV SCI 1000 DEHNguard M YPV SCI 1000 952 510 105
DCO RK MD 24 DEHNconnect RK MD, 24 V 919 941 211 DG M YPV SCI 1000 FM DEHNguard M YPV SCI 1000 FM 952 515 106
DCO RK MD 48 DEHNconnect RK MD, 48 V 919 942 212 DG M YPV SCI 1200 DEHNguard M YPV SCI 1200 952 512 105
DCO RK MD 110 DEHNconnect RK MD, 110 V 919 943 213 DG M YPV SCI 1200 FM DEHNguard M YPV SCI 1200 FM 952 517 106
DCO RK MD EX 24 DEHNconnect RK MD EX, 24 V 919 960 323 DG MOD 48 Protection Module for DG M and DG S, 48 V 952 018 95
DCO RK MD HF 5 DEHNconnect RK MD HF, 5 V 919 970 214 DG MOD 75 Protection Module for DG M and DG S, 75 V 952 011 95
DCO RK ME 12 DEHNconnect RK ME, 12 V 919 920 210 DG MOD 75 VA Protection Module for DG S VA, 75 V 952 025 97
DCO RK ME 24 DEHNconnect RK ME, 24 V 919 921 210 DG MOD 150 Protection Module for DG M and DG S, 150 V 952 012 95
DCO RK ME 48 DEHNconnect RK ME, 48 V 919 922 210 DG MOD 275 Protection Module for DG M and DG S, 275 V 952 010 95
DCO RK ME 110 DEHNconnect RK ME, 110 V 919 923 210 DG MOD 275 VA Protection Module for DG S VA, 275 V 952 027 97
DFL A 255 DEHNflex A 924 389 134 DG MOD 320 Protection Module for DG M and DG S, 320 V 952 013 95
DFL D 255 DEHNflex D 924 395 135 DG MOD 385 Protection Module for DG M and DG S, 385 V 952 014 95
DFL M 255 DEHNflex M 924 396 133 DG MOD 385 VA Protection Module for DG S VA, 385 V 952 029 97
DG 1000 DEHNguard 1000 950 102 111 DG MOD 440 Protection Module for DG M and DG S, 440 V 952 015 95
DG 1000 FM DEHNguard 1000 FM 950 112 111 DG MOD 600 Protection Module for DG M and DG S, 600 V 952 016 95
DG M TN 150 DEHNguard modular TN, 2-pole 952 201 83 DG MOD 750 Protection Module for DG M and DG S, 750 V 952 017 95
DG M TN 150 FM DEHNguard modular TN FM, 2-pole 952 206 84 DG MOD CI 275 Protection Module for DG M CI, 275 V 952 020 98
DG M TN 275 DEHNguard modular TN, 2-pole 952 200 83 DG MOD NPE N-PE Spark-gap-based prot. module, 255 V 952 050 96
DG M TN 275 FM DEHNguard modular TN FM, 2-pole 952 205 84 DG MOD PV SCI 300 Protection Module for DG M YPV SCI, 300 V 952 053 97
DG M TN CI 275 DEHNguard modular TN CI, 2-pole 952 173 73 DG MOD PV SCI 500 Protection Module for DG M YPV SCI, 500 V 952 051 97
DG M TN CI 275 FM DEHNguard modular TN CI FM, 2-pole 952 178 73 DG MOD PV SCI 600 Protection Module for DG M YPV SCI, 600 V 952 054 97
DG M TNC 150 DEHNguard modular TNC, 3-pole 952 313 77 DG PV 500 SCP DEHNguard PV 500 SCP 950 500 108
DG M TNC 150 FM DEHNguard modular TNC FM, 3-pole 952 318 78 DG PV 500 SCP FM DEHNguard PV 500 SCP FM 950 505 109
DG M TNC 275 DEHNguard modular TNC, 3-pole 952 300 77 DG PV 700 SCP DEHNguard PV 700 SCP 950 501 108
DG M TNC 275 FM DEHNguard modular TNC FM, 3-pole 952 305 78 DG PV 700 SCP FM DEHNguard PV 700 SCP FM 950 506 109
DG M TNC 385 DEHNguard modular TNC, 3-pole 952 314 77 DG PV 1200 SCP DEHNguard PV 1200 SCP 950 502 108
DG M TNC 385 FM DEHNguard modular TNC FM, 3-pole 952 319 78 DG PV 1200 SCP FM DEHNguard PV 1200 SCP FM 950 507 109
DG M TNC 440 DEHNguard modular TNC, 3-pole 952 303 77 DG S 48 DEHNguard S, 48 V 952 078 89
DG M TNC 440 FM DEHNguard modular TNC FM, 3-pole 952 308 78 DG S 48 FM DEHNguard S FM, 48 V 952 098 90
DG M TNC CI 275 DEHNguard modular TNC CI, 3-pole 952 304 70 DG S 75 DEHNguard S, 75 V 952 071 89
DG M TNC CI 275 FM DEHNguard modular TNC CI FM, 3-pole 952 309 70 DG S 75 FM DEHNguard S FM, 75 V 952 091 90
DG M TNS 150 DEHNguard modular TNS, 4-pole 952 403 79 DG S 75 VA DEHNguard S VA, 75 V 952 080 113
DG M TNS 150 FM DEHNguard modular TNS FM, 4-pole 952 408 80 DG S 75 VA FM DEHNguard S VA FM, 75 V 952 085 114
DG M TNS 275 DEHNguard modular TNS, 4-pole 952 400 79 DG S 150 DEHNguard S, 150 V 952 072 89
DG M TNS 275 FM DEHNguard modular TNS FM, 4-pole 952 405 80 DG S 150 FM DEHNguard S FM, 150 V 952 092 90
DG M TNS 385 DEHNguard modular TNS, 4-pole 952 404 79 DG S 275 DEHNguard S, 275 V 952 070 89
DG M TNS 385 FM DEHNguard modular TNS FM, 4-pole 952 409 80 DG S 275 FM DEHNguard S FM, 275 V 952 090 90
DG M TNS CI 275 DEHNguard modular TNS CI, 4-pole 952 401 71 DG S 275 VA DEHNguard S VA, 275 V 952 082 113
DG M TNS CI 275 FM DEHNguard modular TNS CI FM, 4-pole 952 406 71 DG S 275 VA FM DEHNguard S VA FM, 275 V 952 087 114
DG M TT 2P 275 DEHNguard modular TT, 2-pole 952 110 85 DG S CI 275 DEHNguard S CI, 275 V 952 079 75
DG M TT 2P 275 FM DEHNguard modular TT FM, 2-pole 952 115 86 DG S CI 275 FM DEHNguard S CI FM, 275 V 952 099 75
DG M TT 2P 320 DEHNguard modular TT, 2-pole 952 130 85 DG S 320 DEHNguard S, 320 V 952 073 89
DG M TT 2P 320 FM DEHNguard modular TT FM, 2-pole 952 135 86 DG S 320 FM DEHNguard S FM, 320 V 952 093 90
DG M TT 2P 385 DEHNguard modular TT, 2-pole 952 111 85 DG S 385 DEHNguard S, 385 V 952 074 89
DG M TT 2P 385 FM DEHNguard modular TT FM, 2-pole 952 116 86 DG S 385 FM DEHNguard S FM, 385 V 952 094 90
DG M TT 2P CI 275 DEHNguard modular TT CI, 2-pole 952 171 74 DG S 385 VA DEHNguard S VA, 385 V 952 084 113
DG M TT 2P CI 275 FM DEHNguard modular TT CI FM, 2-pole 952 176 74 DG S 385 VA FM DEHNguard S VA FM, 385 V 952 089 114
DG M TT 275 DEHNguard modular TT, 4-pole 952 310 81 DG S 440 DEHNguard S, 440 V 952 075 89
DG M TT 275 FM DEHNguard modular TT FM, 4-pole 952 315 82 DG S 440 FM DEHNguard S FM, 440 V 952 095 90
DG M TT 320 DEHNguard modular TT, 4-pole 952 320 81 DG S 600 DEHNguard S, 600 V 952 076 89
DG M TT 320 FM DEHNguard modular TT FM, 4-pole 952 325 82 DG S 600 FM DEHNguard S FM, 600 V 952 096 90
DG M TT 385 DEHNguard modular TT, 4-pole 952 311 81 DG S WE 600 DEHNguard S WE, 600 V 952 077 91
DG M TT 385 FM DEHNguard modular TT FM, 4-pole 952 316 82 DG S WE 600 FM DEHNguard S WE FM, 600 V 952 097 91
DG M TT CI 275 DEHNguard modular TT CI, 4-pole 952 322 72 DG T H 275 LI DEHNguard T H LI, single-pole, 275 V 950 120 103
DG M TT CI 275 FM DEHNguard modular TT CI FM, 4-pole 952 327 72 DG T H 385 LI DEHNguard T H LI, single-pole, 385 V 950 121 103
DG M WE 600 DEHNguard modular M WE, 3-pole 952 302 87 DG TNC H230 400 LI DEHNguard TNC H LI, 3-pole 950 160 100

376 www.dehn.de
Type / Product Index
Type Product Part No. Page Type Product Part No. Page

DG TNS H230 400 LI DEHNguard TNS H LI, 4-pole 950 170 101 DPRO 230 SE F DEHNpro integrated mains filter 909 245 140
DG TT H230 400 LI DEHNguard TT H LI, 4-pole 950 150 102 DPRO 230 ISDN Protection adapter for ISDN/Ethernet applications 909 320 340
DG TT H230 400 LI385 DEHNguard TT H LI, 4-pole, 385 V 950 151 102 DPRO 230 SE ISDN Protection adapter for ISDN/Ethernet applications 909 325 340
DGA AG BNC DEHNgate 929 043 275 DPRO 230 LAN100 Protection adapter for LAN applications 909 321 341
DGA AG N DEHNgate 929 045 275 DPRO 230 SE LAN100 Protection adapter for LAN applications 909 326 341
DGA AG U DEHNgate 929 057 275 DPRO 230 NT Prot. adapter for NTBA/DSL splitter applications 909 310 339
DGA BNC VCD DEHNgate 909 710 271 DPRO 230 SE NT Prot. adapter for NTBA/DSL splitter applications 909 315 339
DGA BNC VCID DEHNgate 909 711 271 DPRO 230 TV Protection adapter for TV/radio applications 909 300 338
DGA F 1.6 5.6 DEHNgate 929 040 273 DPRO 230 SE TV Protection adapter for TV/radio applications 909 305 338
DGA FF TV DEHNgate 909 703 272 DR M 2P 30 DEHNrail modular, 2-pole, 24 V 953 201 120
DGA G BNC DEHNgate 929 042 274 DR M 2P 30 FM DEHNrail modular FM, 2-pole, 24 V 953 206 121
DGA G N DEHNgate 929 044 274 DR M 2P 60 DEHNrail modular, 2-pole, 48 V 953 202 120
DGA GF TV DEHNgate 909 704 272 DR M 2P 60 FM DEHNrail modular FM, 2-pole, 48 V 953 207 121
DGA GFF TV DEHNgate 909 705 272 DR M 2P 75 DEHNrail modular, 2-pole, 60 V 953 203 120
DGA L4 7 16 B DEHNgate 929 048 277 DR M 2P 75 FM DEHNrail modular FM, 2-pole, 60 V 953 208 121
DGA L4 7 16 S DEHNgate 929 047 277 DR M 2P 150 DEHNrail modular, 2-pole, 120 V 953 204 120
DGA L4 N EB DEHNgate 929 059 278 DR M 2P 150 FM DEHNrail modular FM, 2-pole, 120 V 953 209 121
DGA LG 7 16 DEHNgate 929 046 276 DR M 2P 255 DEHNrail modular, 2-pole, 230 V 953 200 120
DGA LG 7 16 X DEHNgate 929 446 276 DR M 2P 255 FM DEHNrail modular FM, 2-pole, 230 V 953 205 121
DGP B NH00 N 255 DEHNgap B/NH00/n 900 269 67 DR M 4P 255 DEHNrail modular, 4-pole 953 400 123
DGP BN 255 DEHNgap B/n 900 132 66 DR M 4P 255 FM DEHNrail modular FM, 4-pole 953 405 123
DGP C MOD N-PE Spark-gap-based prot. module f. DGP C S 952 060 96 DR MOD 30 Protection module for DR M 2P, 2-pole, 30 V 953 011 124
DGP C S DEHNgap C S 952 030 93 DR MOD 60 Protection module for DR M 2P, 2-pole, 60 V 953 012 124
DGP C S FM DEHNgap C S FM 952 035 93 DR MOD 75 Protection module for DR M 2P, 2-pole, 75 V 953 013 124
DGP M 255 DEHNgap M 255 961 101 64 DR MOD 150 Protection module for DR M 2P, 2-pole, 150 V 953 014 124
DGP M 255 FM DEHNgap M 255 FM 961 105 64 DR MOD 255 Protection module for DR M 2P, 2-pole, 255 V 953 010 124
DGP M MOD 255 N-PE Spark-gap-based prot. module for DGP M 961 010 64 DR MOD 4P 255 Protection module for DR M 4P, 4-pole, 255 V 953 020 124
DGPM 1 255 S DEHNgap Maxi 1 255 S 900 050 65 DRC LC M3+ LifeCheck SPD test device 910 653 362
DGPM 440 DEHNgap Maxi 440 961 160 68 DRC MCM XT Condition Monitoring System LifeCheck 910 695 360
DGPM 440 FM DEHNgap Maxi 440 FM 961 165 68 DRL 10 B 180 DRL plug-in SPD block (10 pairs), 180 V 907 400 231
DISO 3 DEHNisola, SPD monitoring device 910 600 365 DRL 10 B 180 FSD DRL plug-in SPD block (10 pairs), fault indication 907 401 232
DK 25 Feed-through Terminal, 25 mm2 952 699 145 DRL HD 5 DEHNrapid LSA HD, 6 V 907 465 236
DLI ISDN I DEHNlink ISDN/I 929 024 262 DRL HD 24 DEHNrapid LSA HD, 28 V 907 470 236
DLI TC 2 I DEHNlink TC 2 929 028 263 DRL PD 180 DEHNrapid LSA PD, 180 V 907 430 235
DLI TC BT DEHNlink BT 929 026 266 DRL RD 5 DEHNrapid LSA RD, 6 V 907 440 234
DLI TC ECO RJ12 DEHNlink-Denmark 929 081 264 DRL RD 12 DEHNrapid LSA RD, 14 V 907 441 234
DLM PV 1000 DEHNlimit 900 330 43 DRL RD 24 DEHNrapid LSA RD, 28 V 907 442 234
DPA M CAT6 RJ45H 48 Patch cable with surge protection 929 110 254 DRL RD 48 DEHNrapid LSA RD, 54 V 907 443 234
DPA M CAT6 RJ45S 48 Patch cable with surge protection 929 100 254 DRL RD 60 DEHNrapid LSA RD, 70 V 907 444 234
DPA M CLE RJ45B 48 Patch cable with surge protection 929 121 255 DRL RD 110 DEHNrapid LSA RD, 110 V 907 445 234
DPG LSA 30 P DEHN enclosure for equipotential bonding, 15 kA 906 100 242 DRL RE 5 DEHNrapid LSA RE, 6 V 907 420 233
DPG LSA 60 P DEHN enclosure for equipotential bonding, 30 kA 906 101 242 DRL RE 12 DEHNrapid LSA RE, 14 V 907 421 233
DPG LSA 120 P DEHN enclosure for equipotential bonding, 50 kA 906 102 242 DRL RE 24 DEHNrapid LSA RE, 28 V 907 422 233
DPG LSA 220 P DEHN enclosure for equipotential bonding, 50 kA 906 103 242 DRL RE 48 DEHNrapid LSA RE, 54 V 907 423 233
DPI CD EXD 230 24 M DEHNpipe 929 969 310 DRL RE 60 DEHNrapid LSA RE, 70 V 907 424 233
DPI CD EXD 230 24 N DEHNpipe 929 970 310 DRL RE 180 DEHNrapid LSA RE, 180 V 907 425 233
DPI CD EXD 24 M DEHNpipe 929 962 308 DSA 230 LA DEHNsafe 924 370 129
DPI CD EXD 24 N DEHNpipe 929 964 308 DSI E 3 Optical-Fibre-Based Receiver Module 910 631 57
DPI CD EXI 24 M DEHNpipe 929 961 306 DSM ISDN SK SPD for telecomm. terminal equipment 924 270 290
DPI CD EXI 24 N DEHNpipe 929 963 306 DSM TC 2 SK SPD for telecomm. terminal equipment 924 272 291
DPI CD HF EXD 5 M DEHNpipe 929 971 309 DSM TM SPD for Data Sockets 924 274 260
DPI MD 24 M 2S DEHNpipe 929 941 298 DV M TN 255 DEHNventil modular TN, 2-pole 951 200 35
DPI MD EX 24 M 2 DEHNpipe 929 960 303 DV M TN 255 FM DEHNventil modular TN FM, 2-pole 951 205 35
DPI ME 24 N A2G DEHNpipe 929 921 299 DV M TNC 255 DEHNventil modular TNC, 3-pole 951 300 32
DPL 10 G3 110 LSA-Plus Technology, 10 DA 907 214 240 DV M TNC 255 FM DEHNventil modular TNC FM, 3-pole 951 305 32
DPL 10 G3 110 FSD LSA-Plus Technology, 10 DA 907 216 240 DV M TNS 255 DEHNventil modular TNS, 4-pole 951 400 33
DPRO 230 DEHNpro 909 230 139 DV M TNS 255 FM DEHNventil modular TNS FM, 4-pole 951 405 33
DPRO 230 SE DEHNpro 909 235 139 DV M TT 255 DEHNventil modular TT, 4-pole 951 310 34
DPRO 230 F DEHNpro integrated mains filter 909 240 140 DV M TT 255 FM DEHNventil modular TT FM, 4-pole 951 315 34

www.dehn.de 377
Type / Product Index
Type Product Part No. Page Type Product Part No. Page

DV M TT 2P 255 DEHNventil modular TT 2P, 2-pole 951 110 36 GDT DGA 90 Gas Discharge Tube for DEHNgate 929 497 279
DV M TT 2P 255 FM DEHNventil modular TT 2P FM, 2-pole 951 115 36 GDT DGA 90 X Gas Discharge Tube for DEHNgate
DV MOD 255 Spark-gap-based protection module 951 001 38 with screw cap 929 496 279
DV MOD NPE 50 N PE Spark-gap-based protection module, 50 kA 951 050 38 GDT DGA 230 Gas Discharge Tube for DEHNgate 929 498 279
DV MOD NPE 100 N PE Spark-gap-based protection module, 190 kA 951 100 38 GDT DGA 470 Gas Discharge Tube for DEHNgate 929 499 279
DV ZP TNC 255 DEHNventil ZP TNC 255 900 390 40
IF1 Connection Bracket Type IF -SET- 923 011 345
DV ZP TT 255 DEHNventil ZP TT 255 900 391 41
IF3 Connection Bracket Type IF -SET- 923 016 345
EB 1 4 9 Earthing clip, 4-pole, single-phase 900 417 151 IGA 6 IP54 Insulating Enclosure 6 mods. 902 485 148
EB 4 F Earthing blocks 4xF 929 095 279 IGA 10 V2 IP54 Insulating Enclosure 10 mods. 902 315 146
EB DG 1000 1 3 DB Earthing clip, 3-pole, single-phase 900 411 151 IGA 12 IP54 Insulating Enclosure 12 mods. 902 471 147
EF 10 DRL Earthing frame 907 498 237 IGA 24 IP54 Insulating Enclosure 24 mods. 902 472 147
EG NET PRO 10X 19” Enclosure for NET Protector 929 234 252 IS PAS M10 Isolator for PAS Industry 472 210 356
EG NET PRO 10X 3HE Enclosure for NET Protector 929 235 252 ITAK EXI BXT 24 IT Connection Box 989 408 321
EG NET PRO 19” Enclosure for NET Protector 929 034 249
KB 10 DCO RK Jumper Bar for DEHNconnect RK 919 880 217
EL 16 B17 Cable Lug with Earth Conductor 929 096 279
KFSU Ex-Isolating Spark Gap 923 021 343
EL2 38EA LSA Earth Conductor Block, 38-pole LSA-PLUS 907 993 244
KS 198 PAS Terminal Bar, brass, length 198 mm 563 016 355
ER DPI M20 Set of Earthing Rings for DEHNpipe 929 996 300
KS 398 PAS Terminal bar, brass, length 398 mm 563 017 355
ES 2X2AP 10 ST Earthing busbars St/tZn, 2x2 connections 472 023 356
KS 798 PAS Terminal bar, brass, length 798 mm 563 018 355
ES 2X2AP 10 V2A Earthing busbars St/St, 2x2 connections 472 109 356
KV FE UNI Wedge Connector St/tZn, with grid position 308 001 357
ES 2X3AP 10 ST Earthing busbars St/tZn, 2x3 connections 472 022 356
KV M20 MS 10.5 EMC Cable Gland 929 984 300
ES 2X3AP 10 V2A Earthing busbars St/St, 2x3 connections 472 119 356
KV S M20 MS 9.5 EMC Cable Gland 929 982 300
ES 2X4AP 10 V2A Earthing busbars St/tZn, 2x4 connections 472 129 356
ES 2X4AP ST Earthing busbars St/tZn, 2x4 connections 472 024 356 LCS DRC BCT LifeCheck-Sensor für DRC BCT 910 654 362
ES 2X6AP 10 ST Earthing busbars St/tZn, 2x6 connections 472 021 356 LCS DRC BXT LifeCheck-Sensor für DRC BXT 910 652 362
ES 2X6AP 10 V2A Earthing busbars St/tZn, 2x6 connections 472 139 356 LWL DSI 18M Optical fibre, length 18 m 910 642 57
EX BRS 27 Pipe clamp for use in hazardous areas 540 821 351 LWL ST DSI Plug for Optical Fibre 910 641 57
EX BRS 90 Pipe clamp for use in hazardous areas 540 801 351
EX BRS 300 Pipe clamp for use in hazardous areas 540 803 351 MB2 10 LSA Mounting Frame 10 DA LSA-PLUS 907 995 243
EX BRS 500 Pipe clamp for use in hazardous areas 540 805 351 MMVK R16 R25 STBL MAXI MV clamp, St/tZn 308 040 357
EXFS 100 Ex Isolating Spark Gap, 100 kA 923 100 345 MMVK R16 R25 ST MAXI MV clamp, St/bare 308 041 357
EXFS 100 KU Ex Isolating Spark Gap, 100 kA 923 101 346 MS ALGA 5 X Mounting Set for Enclosures 906 059 335
EXFS KU Ex Isolating Spark Gap, 50 kA 923 019 349 MS DPA Mounting Set for DEHNpatch 929 199 254
EXFS L100 Ex Isolating Spark Gap, 50 kA 923 060 348 MVS 1 2 Busbar single-phase, 2-pole 900 617 149
EXFS L200 Ex Isolating Spark Gap, 50 kA 923 061 348 MVS 1 3 Busbar single-phase, 3-pole 900 615 149
EXFS L300 Ex Isolating Spark Gap, 50 kA 923 062 348 MVS 1 4 Busbar single-phase, 4-pole 900 610 149
MVS 1 6 Busbar single-phase, 6-pole 900 815 149
FBH 6 CU Tape conductors with pressure plate 12 mm, Cu 277 237 357 MVS 1 7 Busbar single-phase, 7-pole 900 848 150
FBH 6 ST Tape conductors with pressure plate 12 mm, St/tZn 277 230 357 MVS 1 8 Busbar single-phase, 8-pole 900 611 150
FBH 6 V2A Tape conductors with pressure plate 12 mm, St/St 277 239 357 MVS 1 57 Busbar single-phase, 57-pole 900 612 150
FBH 11 ST Tape conductors with pressure plate 11 mm, St/tZn 277 240 357 MVS 3 6 Busbar 3-phase, 6-pole 900 595 150
FS 9E HS 12 Fine Surge Protection Adapter FS 12 V 924 019 283 MVS 3 6 8 Busbar 3-phase, 8-pole 900 813 150
FS 9E PB 6 Fine Surge Protection Adapter FS 6 V 924 017 282 MVS 4 8 11 Busbar 4-phase, 11-pole 900 814 151
FS 15E 5 Fine Surge Protection Adapter FS 5 V 924 016 284 MVS 4 56 Busbar 4-phase, 56-pole 900 614 151
FS 25E HS 12 Fine Surge Protection Adapter FS 12 V 924 018 285
NET PRO 10X TC1 RST NET Protector 10X TC1 RST 929 230 252
GDT 230 B3 Gas Discharge Tube for DRL 10 907 218 238 NET PRO 4TP NET Protector 4TP 929 035 249
GDT 230 B3 FSD Gas Discharge Tube for DRL 10 907 219 238 NET PRO 4TP 30 NET Protector 4TP 30 929 037 249
GDT 230 G3 Gas Discharge Tube for DPL 10 G3 907 208 240 NET PRO E1 LSA G703 NET Protector E1 LSA G703 929 075 251
GDT 230 G3 FSD Gas Discharge Tube for DPL 10 G3 907 217 240 NET PRO LSA 4TP NET Protector/LSA-PLUS/4TP 929 036 249

378 www.dehn.de
Type / Product Index
Type Product Part No. Page Type Product Part No. Page

NET PRO TC 2 NET Protector TC 2, 110 V 929 071 250 SAK BXT LR EMC spring terminals 920 395 202
NET PRO TC 2 LSA NET Protector TC 2 LSA,+B433 110 V 929 072 250 SB PAS RK Bar Holder, plastic, grey 563 014 355
NF 10 Mains Filter 10 A 912 254 125 SDS 1 Voltage limiting device, SDS 1 923 110 354
NSM PRO AZ NSM Protector DELTA profile, anthracite 924 339 137 SDS 2 Voltage limiting device, SDS 2 923 117 354
NSM PRO EW NSM Protector DELTA profile, studio white 924 342 137 SDS 3 Voltage limiting device, SDS 3 923 116 354
NSM PRO SI NSM Protector DELTA profile, silver 924 337 137 SDS 4 Voltage limiting device, SDS 4 923 118 354
NSM PRO TW NSM Protector DELTA profile, titanium white 924 335 137 SDS 5 Voltage limiting device, SDS 5 923 119 354
SFL PRO SFL Protector 912 260 142
P2 Impulse Meter P2 910 502 366 SFL PRO SE SFL Protector 912 261 142
PA BXT Test adapter for BXT 910 508 364 SH 18X3 K Bar Holder, plastic 919 014 330
PA DRL Test adapter for BCT 910 507 364 SH1 18X3 ST Bar Holder, steel 919 012 330
PAS 9AK Earthing Busbar 563 050 355 SH2 18X3 ST Bar Holder ISO 919 013 330
PAS 11AK Earthing Busbar 563 200 355 SKB 19 9M SW Selfbonding Rubber Tape 919 030 333
PAS 11AK UV Earthing Busbar 563 201 355 SLK 16 PE Terminal 910 099 335
PAS 6RK OH Earthing Busbar 563 105 355 SN 18X3 CU 1000 Busbar, tinned 919 016 329
PAS 9RK Earthing Busbar 563 020 355 SPS PRO SPS Protector 912 253 127
PAS 10RK Earthing Busbar 563 010 355 SR DRL Label Holder 907 497 238
PAS 14RK Earthing Busbar 563 030 355 ST AS SAK K Bar Support, plastic 308 425 327
PAS I 10AP M10 CU Earthing Busbar 472 217 356 STAK 2X16 Pin-shape terminal 900 589 145
PAS I 10AP M10 V2A Earthing Busbar 472 219 356 STC 230 STC Surge Protection Module 924 350 131
PAS I 12AP M10 CU Earthing Busbar 472 237 356
PAS I 12AP M10 V2A Earthing Busbar 472 239 356 T C H 255 N-PE Spark-gap-based-Protection Module 900 216 102
PAS I 6AP M10 CU Earthing Busbar 472 207 356 T H 275 LI Protection Module with Pro-Aktive Thermo Control 950 130 103
PAS I 6AP M10 V2A Earthing Busbar 472 209 356 T H 385 LI Protection Module with Pro-Aktive Thermo Control 950 131 103
PAS I 8AP M10 CU Earthing Busbar 472 227 356 TFS Isolating Spark Gap 923 023 343
PAS I 8AP M10 V2A Earthing Busbar 472 229 356 TL2 10DA CC Routing module with LSA tension spring 907 991 245
PM 20 SPD Test Device 910 511 364 TL2 10DA LSA Disconnection Modules 10 TC LSA-PLUS 907 996 244
TW DRC MCM EX Partition 910 697 319
RK 16 PAS Modular Terminal, -16 mm2 for EB 563 011 355
RK 95 PAS Modular Terminal, 16-95 mm2 for EB 563 013 355 UGKF BNC SPD for Comupter Systems 929 010 268
RK FL30 PAS Modular Terminal, flat strip -30 mm for EB 563 012 355 USB NANO 485 USB interface converter of type USB NANO 485 910 486 360
RK FL40 PAS Modular Terminal, flat strip -40 mm for EB 563 019 355 USD 9 V24 S B Cable Adapter 924 061 286
USD 15 V11 S B Cable Adapter 924 051 287
SA KRF 10 V2A Contact Force Spring f. shield connection 4-10 mm 919 031 333 USD 25 V24 HS S B Cable Adapter 924 046 288
SA KRF 15 V2A Contact Force Spring f. shield connection 9-15 mm 919 032 333
SA KRF 22 V2A Contact Force Spring f. shield connection 14-22 mm 919 033 333 V NH00 280 VNH Surge Arrester, Size 00 900 261 116
SA KRF 29 V2A Contact Force Spring f. shield connection 18,5-29mm 919 034 333 V NH00 280 FM VNH FM Surge Arrester, Size 00 900 263 116
SA KRF 37 V2A Contact Force Spring f. shield connection 23,5-37mm 919 035 333 V NH1 280 VNH Surge Arrester, Size 1 900 270 116
SA KRF 50 V2A Contact Force Spring f. shield connection 31-50 mm 919 036 333 VA NH00 280 VANH Surge Arrester, Size 00 900 262 117
SA KRF 70 V2A Contact Force Spring f. shield connection 44-70 mm 919 037 333 VA NH00 280 FM VANH FM Surge Arrester, Size 00 900 264 117
SA KRF 94 V2A Contact Force Spring f. shield connection 58-94 mm 919 038 333 VA NH1 280 VANH 280, Size 1 900 271 117
SAK 10 AS V4A Shielding Terminal, stainless steel, Rd 5-10 mm 308 403 326 VC 280 2 Mains Surge Protection Module, 2-pole 900 471 144
SAK 14 AS V4A Shielding Terminal, stainless steel, Rd 8-14 mm 308 404 326 VK A R22 F40 STBL Connection Clamp St/bare 308 030 357
SAK 18 AS V4A Shielding Terminal, stainless steel, Rd 13-18 mm 308 405 326 VK A UNI ST Connection Clamp St/tZn 308 025 357
SAK 21 AS V4A Shielding Terminal, stainless steel, Rd 17-21 mm 308 406 326 VK A UNI V2 ST Connection Clamp St/tZn 308 026 357
SAK 26 AS V4A Shielding Terminal, stainless steel, Rd 19-26 mm 308 407 326 VK EH R10 F30 ST Connection Clamp St/tZn 308 120 357
SAK 33 AS V4A Shielding Terminal, stainless steel, Rd 25-33 mm 308 408 326 VK EH R10 F30 V2A Connection Clamp StSt (V2A) 308 129 357
SAK 6.5 SN MS Shielding Terminal, stainless steel, Rd 1,5-6,5 mm 919 010 329
ZAP STW Central Covering Plate for DEHNsafe 924 329 129
SAK 11 SN MS Shielding Terminal, stainless steel, Rd 5-11 mm 919 011 329

www.dehn.de 379
Key Words
Accessories / Construction Kit 355 DEHNgate 269 Impulse meter 366 Protective adapter for LAN 341
Accessories for BLITZDUCTOR® XT 202 DEHNguard® ... H LI 99 Information technology systems 153 Protective adapter for
Accessories for BLITZDUCTOR® XT DEHNguard® modular 76 Insertion tools 243 NTBA/DSL splitter applications 339
Ex (i) 317 DEHNguard® modular CI, Insulating enclosure 146 Protective adapter for
Accessories for DEHNconnect 217 with integrated backup fuse 69 Insulated rail support 330 TV/radio applications 338
Accessories for DEHNgate 279 DEHNguard® S 88 Insulated busbar support 327 Protective conductor terminal 335
Accessories for DEHNpipe 300 DEHNguard® S ... VA 112 Isolating spark gaps 343
Accessories for DEHNpipe MD Ex (i) 304 DEHNguard® PV ... SCP 107 ITAK Ex (i) 320 Rail support 330
Accessories for LSA Technology 243 DEHNguard® M YPV SCI 104 Registration of discharges 366
Accessories for terminal block DEHNguard® 1000 FM 110 Key to symbols used in
systems 325 DEHNisola 365 basic circuit diagrams 371 Screwable SPDs 297
Accessories Red/Line 145 DEHNlimit 42 SDS 353
Aluminium enclosure 334 DEHNlink 261 LifeCheck® SPD test 177 Self-bonding rubber tape 333
Aluminium enclosure for Ex(i)- DEHNlink TC BT 265 LifeCheck® SPD test device 361 SFL Protector 141
surge arresters 334 DEHNpatch 253 Lightning current arresters – Type 1 45 Shield connection on anchor bars 325
Anchor bar 326 DEHNpipe 297 Lightning equipotential bonding 343 Shield connection on DIN rails 328
AS IBAS 294 DEHNpipe CD Ex (d) 307 Literature 368 Shield connection on cables 332
DEHNpipe CD Ex (i) 305 Shield terminals 326/329
BLITZDUCTOR® VT 218/256 DEHNpipe MD Ex (i) 301 Mains filter 125 SPDs for D-Sub connection 281
BLITZDUCTOR® VT KKS 224 DEHN enclosure for equipotential bon- Marking system 204 SPDs for BT Jack connection 265
BLITZDUCTOR® XT 184 ding 241 Measuring and test devices 359 SPDs for coaxial connection 267
BLITZDUCTOR® XT Ex (i) 311 DEHNprotector 138/337 Modular surge arrester with SPDs for LSA technology 229
BLITZDUCTOR® XTU 179 DEHNrail modular 119 integrated backup fuse 69 SPDs for RJ connection 253
Busbar 329 DEHNrail modular, multipole 122 More information and SPDs for use in potentially
Busbars / Modular wiring system 149 DEHNrapid® LSA 229 documentation 367 explosive areas 301
BUStector 292 DEHNrapid® LSA plug-in SPD block Mounting frame 243 SPDs for 482.6 mm (19 inch)
(without SPDs) 238 Mounting set 335 data cabinets 247
Combined adapters 337 DEHNsafe 128 Multipole combined lightning current SPD monitoring device 365
Combined lightning current and surge DEHNsignal 56 and surge arrester for primary SPD test device 363
arrester for cathodic corrosion DEHNventil® modular 31 power systems 39 SPS Protector 126
protection systems 224 DEHNventil® ZP 39 Multipole modular combined lightning STC Module 130
Combined SPDs – Type 1 31 current and surge arrester 31 Surge arresters – Type 2 69
Disconnection block 244
Compact protection for terminal Multipole, modular surge arrester 76 Surge arresters – Type 3 119
Discontinued products RL/YL 29/154
equipment 143 Multipole surge arrester with Surge arresters for earthed socket
DPL 10 G3 239
Compact SPDs for DIN rail ‘Pro-Active Thermo Control’ 99 outlets 130
DSM 289
Mounting 209 Surge arresters for use in cable ducts128
DSM TM 259
Components for foundation N-PE Lightning current arresters 63 Surge protective adapter 138
earthing electrodes 357 N-PE spark-gap-based protection
Earthing busbars 356 Surge protective multiple socket
Components for ring equipotential module 38/96 outlet with filter 141
bonding 357 Earth conductor block 244
N-PE surge arrester 92 Surge protective socket outlet 136
Condition monitoring system Earthing module 202
NET Protector 247
LifeCheck® 359 Easy choice Red/Line 18
NH Surge arresters 115 Terminal 327/331
Connecting clamps 357 Easy choice according to
NSM Protector 136 Terminal block 244
Constant force spring 333 Interface / Signal 156
EMC spring terminals 202 Terminal block with integrated
Coordinated lightning current arrester 49 Part No. Index 372 surge protection 209
Coordinated lightning current Enclosure / Protective conductor
Photovoltaic systems 42/104 Test / Disconnection module 203
arrester for busbars 54 terminal 334
Pipe clamp for explosion hazard TFS / KFSU 343
Cross-reference Red/Line 29 Enclosure system for SPDs
areas 350 Type / Product index 375
protecting IT equipment 241
Cross-reference Yellow/Line 154 Pluggable SPDs for DIN rail
Equipotential bonding 355
mounting 179
Equipotential bonding bars 355/356 UGKF 267
DEHNbloc® 58 Power supply systems 15
EXFS 100 / EXFS 100 KU 344
DEHNbloc® M 45 Power supply systems worldwide 28
EXFS L / EXFS KU 347 V NH / VA NH 115
DEHNbloc® Maxi 49 Protection module for DEHNbloc® M 48
Varistor-based protection module 95
DEHNbloc® Maxi S 54 Protection module for DEHNguard® M,
Flexible protection of terminal VC 280 2 143
DEHNbloc® Maxi 440/760 51 ... S and DEHNgap C/ S 94
equipment 132
DEHNconnect RK 209 Protection module for DEHNrail
FS / USD 281 Wiring accessories 145
DEHNconnect RK Ex (i) 322 modular 124
DEHNflex 132 Protection module for DEHNventil®
Gas discharge tube 279 modular 37 Yellow/Line SPD classes – Symbols 176
DEHNgap 63
General terms of sale 370 Protective adapter for
DEHNgap C S 92
ISDN / Ethernet applications 340

380 www.dehn.de
Lightning Protection
Surge Protection
Safety Equipment

DEHN + SÖHNE
GmbH + Co.KG.
Hans-Dehn-Str. 1
Postfach 1640
92306 Neumarkt
Germany

Tel. +49 9181 906-0


© Copyright 2010 DEHN + SÖHNE

Fax +49 9181 906-444


www.dehn.de
export@dehn.de
DS570/E/0410