Acoustic Calculation of Ventilation Systems

Octave Band Center Fr


63 125 250
1 Sound Power Fan 110 105 101
2 Safety Factors 7 7 7
10 Room and terminal effect -5 -5 -5
11 Allowance for end reflection -12 -8 -4
12 Ductwork attenuation -17 -17 -9
13 Elbow attentuation 0 0 -7
14 Power level split, branch to terminals -6 -6 -6
15 Power level split, main duct to branch duct -10 -10 -10
0 0 0
0 0 0
0 0 0
0 0 0
20 Resulting Sound Power Fan 67 66 67
21 Sound Pressure Criterion 59 48 40
22 Silencer Requirements 8 18 27

Acoustic Calculation of Ventilation System

120

100 1S
2S
10
80
11
12
60 13
Sound Power (dB)

14
40 15
Row
Row
20
Row
Row
0
63 125 250 500 1,000 2,000 4,000 8,000 20
21
-20 22

-40
Row
0
63 125 250 500 1,000 2,000 4,000 8,000 20
21
-20 22

-40

Frequency (Hz)
Octave Band Center Frequency (Hz)
500 1,000 2,000 4,000 8,000
101 90 95 90 85
7 7 7 7 7
-5 -5 -5 -5 -5
-1 0 0 0 0
-5 -5 -5 -5 -5
-15 -25 -25 -29 -15
-6 -6 -6 -6 -6
-10 -10 -10 -10 -10
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
66 46 51 42 51
34 30 27 25 23
32 16 24 17 28

entilation System

1 Sound Power Fan


2 Safety Factors
10 Room and terminal effect
11 Allowance for end reflection
12 Ductwork attenuation
13 Elbow attentuation
14 Power level split, branch to terminals
15 Power level split, main duct to branch duct
Row 13
Row 14
Row 15
Row 16
4,000 8,000 20 Resulting Sound Power Fan
21 Sound Pressure Criterion
22 Silencer Requirements
Row 16
4,000 8,000 20 Resulting Sound Power Fan
21 Sound Pressure Criterion
22 Silencer Requirements