PLUMBING FIXTURES
FUNDAMENTALS OF PLUMBING
DANILO V. RAVINA 1
KEYWORDS:
• PLUMBING FIXTURE
• FIXTURE UNIT
• DRAINAGE FIXTURE UNIT (DFU)
• WATER SUPPLY FIXTURE (WSFU)
• ROUGHING-IN
DANILO V. RAVINA 2
What are Plumbing Fixtures?
207.8
FIXTURE UNIT is an arbitrary quantity in terms of
which the load-producing effects or water
requirements on the plumbing system of different
kinds of plumbing fixtures are expressed in some
arbitrarily chosen scale. One fixture unit is
equivalent to a rate of flow at 28.3 liters per
minute (1 cubic feet per minute) or (7.5 gpm).
*Drainage Fixture Unit (DFU) and Water Supply Fixture Unit (WSFU) – is a numerical weighing factor to
account for the sewage flow or water demand of various plumbing fixtures, using the lavatory (for private
use) as 1 DFU or 1 WSFU. It is just an index number meant to put all fixtures on a common basis.
DANILO V. RAVINA 6
What is a Water Closet & What are its
Classifications?
• Water Closet is a plumbing fixture used
to receive human excrement & to
discharge it through a waste pipe, using
water as a conveying medium.
This type of bowl develops its The trap way located at the rear
flushing action through the eliminated the bulge at the front.
water entering the diagonal The design of the bowl plus its
holes around the rim which large water area & quietness in
creates a swirling action which operation, makes it desirable
forms a vortex in the center. than the siphon washdown.
From HCG
DANILO V. RAVINA, NAMPAP -
10
CEBU
Close Coupled Water Closet:
From HCG
• A water closet wherein the flush tank
is separate but is attached to the
toilet bowl. It is a two-piece model.
From Mariwasa ToTo
• Flushometer Valve is a
valve designed to supply a
fixed quantity of water for
flushing purposes. It is
activated by direct water
pressure without the use
of a flush tank. It requires
a flow pressure of 69 to
138 kPa (10 to 20 psi)
Section 401
Water closet bowls for
public use shall be the
elongated bowl types
equipped with
open-front seats.
Shower Pan
dimension shall be
maintained from a point
above the shower drain
Min. Area = 0.6 m² outlet to a height of 1.78
meters with no protrusions
762 mm other than the fixture valve
or valves, shower head and
safety grab bars or rails.
DANILO V. RAVINA 26
What is a Kitchen Sink?
A Kitchen Sink is
a plumbing fixture
consisting of a
basin with a water
supply, connected
with a drain & used
for dishwashing.
WASHLET
A Scrub Sink is a
plumbing fixture
usually located in the
O.R. in a hospital to
enable personnel to
scrub their hands
prior to a surgical
procedure. The Hot
& Cold water supply
is activated by a A Drinking Fountain is a
knee – action mixing plumbing fixture consisting
valve or by wrist or of a shallow basin, together
pedal control or by with a water jet, designed
automatic sensors. to provide potable water for
human consumption.
DANILO V. RAVINA 37
WATER CLOSET
Clearances are
minimum distances 375 mm
750 mm 762 mm
of fixtures for
human safety and
comfort.
1524 mm
457 mm
457 mm
219.9
ROUGHING-IN - the
installation of all pipings
and fitting parts of the
plumbing system, which
can be completed prior to
the installation of fixtures 600 mm 600 mm
381 mm
and accessories. These 300 mm
Section 401
Water closet bowls for public use 750 mm 762 mm
shall be the elongated bowl types 375 mm
1524 mm
457 mm
457 mm
219.9
ROUGHING-IN - the installation of 600 mm 600 mm
381 mm
all pipings and fitting parts of the 300 mm
plumbing system, which can be
completed prior to the installation
of fixtures and accessories. These
include sanitary and storm
drainage, tap, hot and chilled 457 mm
water supplies, gas pipings, vent
pipings and the necessary fixture
supports.
CLEARANCE DIMENSIONS
DANILO V. RAVINA 39
300 mm
750 MM
375 MM
457 MM
206 mm
150 mm
300 mm
206 mm
ROUGHING-IN FOR WATER CLOSET
DANILO V. RAVINA 40
WATER CLOSET ROUGHING-IN
DANILO V. RAVINA 41
DANILO V. RAVINA 42
ANATOMY OF A WATERCLOSET
DANILO V. RAVINA 43
DANILO V. RAVINA 44
FLOOR DRAINS SHOWER RECEPTORS
409.1 409.2
Floor drains shall be considered Shower receptors are plumbing fixtures.
plumbing fixtures.
409.3
Each shower receptor shall be an approved type and be
constructed to have a finish dam, curb or threshold which is
at least 25.4 mm lower than the outside floor at the sides
and back of such receptor. In no case shall any dam or
threshold be less than 51 mm nor more than 228 mm in
depth when measured from the top of the dam or threshold
to the drain. The finished floor of the receptor shall slope
uniformly from the sides towards the drain not less than 2%
or 20mm/m or more than 4% or 40mm/m. Thresholds shall
be of sufficient width to accommodate a minimum 559mm
wide door.
DANILO V. RAVINA 45
SHOWER / BATH TUB
DANILO V. RAVINA 46
PLUMBING ACCESSORIES
DANILO V. RAVINA 47
TOILET FOR THE DISABLED
DANILO V. RAVINA 48
SHOWER FOR THE DISABLED
DANILO V. RAVINA 49
TOILET / POWDER ROOM PLAN
207.8
FIXTURE UNIT is an arbitrary quantity in terms of
which the load-producing effects or water
requirements on the plumbing system of different
kinds of plumbing fixtures are expressed in some
arbitrarily chosen scale. One fixture unit is
equivalent to a rate of flow at 28.3 liters per
minute (1 cubic feet per minute) or (7.5 gpm).
(Single)
NOTE: For more details,
refer to Table 7-2 of the
NPC. Page 80
(Private installation )
DANILO V. RAVINA 53
*MAXIMUM FIXTURE UNIT LOADING AND MAXIMUM LENGTH OF
EXCRETA DRAINAGE AND VENT PIPING
*THESE
FIGURES ARE
FOUND IN
TABLE 7-5 OF
THE NPC ON
PAGE 88.
NOTES:
1. Excluding trap arm
2. Except sinks, urinals and dishwashers.
3. Except 6 fixture unit traps or water closets.
4. Only four (4) water closet or 6 fixture unit traps are allowed on any vertical pipe or stack, and not
to exceed three (3) water closets or six (6) fixture unit traps on any horizontal branch or drain.
5. Based on 2% or 20.9 mm/m slope. For one (1) percent or 10.4mm/m slope, multiply horizontal
fixture units by a factor of 0.80.
DANILO V. RAVINA 54
WATER SUPPLY FIXTURE UNITS (WSFU)
EQUIVALENT *WATER SUPPLY FIXTURE UNITS (WSFU)
Number of Water Supply Fixture Units
(WSFU)
Type of Fixture Private Use Public Use
Bar Sink 1 2
1 - - 60 54.0 3.41
2 - - 70 58.0 3.66
3 - - 80 61.2 3.86
4 - - 90 64.3 4.06
5 15.0 0.95 100 67.5 4.26
6 17.4 1.10 120 73.0 4.61
7 19.8 1.25 140 77.0 4.86
8 22.2 1.40 160 81.0 5.11
9 24.6 1.55 180 85.5 5.39
10 27.0 1.70 200 90.0 5.68
12 28.6 1.80 250 101.0 6.37
DANILO V. RAVINA 58