RELAY DATA:
Manufacturer: SIEMENS
Type: 7SA510
Nominal Current: 1A
Relay burden: 0.05 VA
Remark:
DEMO-Department//DEMO-User 6/7/2020
Revision
1
National Grid
DEMO-Department
CT 1 (CT1):
Name / transf. ratio Burden:
Relay burden: Prelay 7SA510 = 0.05 VA
Sum of add. relay burdens: Padd = 0 VA
The cable burden is calculated by the single length, the cross section, the specific resistivity and an
effective factor for the wire length. This factor kwire is 2 if the return wire is to be considered.
Secondary wiring burden:
Length: l wire = 100 m
Cross section: Awire = 4 mm2
Spec. resistivity: ρ = 0.0225 Ω mm2/m (Cu at 75 OC)
Sec. wire current: Isn,wire =1A
Eff. wire length in p.u.: kwire =2
k wire Cu l wire
Pwire I sn2 ,wire = 1.1249 VA
a wire
The total effective burden is given by the sum of all the connected burdens:
Ptotal = Prelay + Padd +
Total burden: = 1.1749 VA
Pwire
CHECK OF CT REQUIREMENTS:
The CT behaviour acc. to IEC-P will be described by the operating accuracy limiting factor ALFo. It
depends on the nominal accuracy limiting factor ALFn, the nominal burden Pn, the internal CT burden
Pct and the total effective connected burden P total.
CT 1 (CT1):
Pn Pct
ALFo ALFn = 72.171
Ptotal Pct
where
ALFn : nominal accuracy limiting factor = 20
Pn: nominal burden = 15 VA
Pct: internal CT burden = 4.125 VA
Ptotal: total effective connected burden = 1.1749 VA
For ct dimensioning, the short-circuit current and system time constant at set zone 1 limit of 80 % has
to be taken into consideration. With a max. sym. short-circuit current of 21 kA and a nominal system
voltage of 132 kV, the equivalent source impedance can be calculated:
DEMO-Department//DEMO-User 6/7/2020
Revision
2
National Grid
DEMO-Department
1.1 U n
ZQ = 3.992 Ω
3 I kQ
Taking into account the system time-constant of 10 ms the resistive and reactive part of the source
impedance can be calculated:
ZQ
RQ = 1.024 Ω
1 (2 f T p ) 2
X Q Z Q2 RQ2 = 3.859 Ω
With the ohmic and reactive per line length values R' an X' the set zone 1 limit Klim, and the line
length, the short-circuit current at zone 1 limit Ik,lim and the corresponding time-constant Tlim can be
calculated:
RL K lim l L RL' = 12 Ω
X L K lim l L X L' = 32 Ω
Rk RQ RL = 13.024 Ω
Xk XQ X L = 35.859 Ω
Z k Rk2 X k2 = 38.15 Ω
1.1 U n
I k ,lim = 2.197 kA
3 Zk
Xk
Tlim = 7.304 ms
2 f Rk
where
Klim: set zone 1 limit = 80 %
l L: line length = 100 km
R'L: resistance per unit length = 0.15 Ω/km
X'L: reactance per unit length = 0.4 Ω/km
CT-DIMENSIONING CHECK:
For the protection relay 7SA510 the requirements for close-up faults and faults at zone 1 limit have to
be fulfilled.
Check of Requirement 1:
Ik
Tp = 10 ms
I pn
ALFo ≥ 2
ALFo = 72.171
DEMO-Department//DEMO-User 6/7/2020
Revision
3
National Grid
DEMO-Department
o
Ik
Meets requirement 1
I pn
2 = 35
Check of Requirement 2:
I k ,lim
I pn
ALFo ≥ 10
ALFo = 72.171
I k ,lim
Meets requirement 2
I pn
10 = 18.312
DEMO-Department//DEMO-User 6/7/2020
Revision