You are on page 1of 3

LTVR and Energy saving calculation(Before Bifergation of existing 250KVA TC)

LTVR ENERGY LOSS

Nod Load at Cummulative


Km Load2 Km
e No Node Load in HP

1 40 40 × 0.0125 = 0.50 1600 × 0.0125 = 20.00


2 45 85 × 0.022 = 1.87 7225 × 0.022 = 158.95
3 45 130 × 0.013 = 1.69 16900 × 0.013 = 219.70
4 40 170 × 0.014 = 2.38 28900 × 0.014 = 404.60
5 45 215 × 0.023 = 4.95 46225 × 0.023 = 1063.18
6 15 230 × 0.014 = 3.22 52900 × 0.014 = 740.60
7 20 250 × 0.015 = 3.75 62500 × 0.015 = 937.50
8 20 270 × 0.026 = 7.02 72900 × 0.026 = 1895.40
9 10 280 × 0.024 = 6.72 78400 × 0.024 = 1881.60
Total 32.10 Total 7321.53

32.095 × 0.59 7321.525 × 0.0074 × 8760


Squirrel 1 1

Total LTVR = 18.93605 Total energy loss = 94922 Unit/annum

32.095 × 0.28 7321.525 × 0.0034 × 8760


Rabbit 1 1

Total LTVR = 8.9866 Total energy loss = 43613 Unit/annum

LTVR and Energy saving calculation(After Bifergation on Existing 250KVA TC)


LTVR ENERGY LOSS

Nod Load at Cummulative


Km Load2 Km
e No Node Load in HP

1 40 40 × 0.0125 = 0.50 1600 × 0.0125 = 20.00


2 45 85 × 0.022 = 1.87 7225 × 0.022 = 158.95
3 45 130 × 0.013 = 1.69 16900 × 0.013 = 219.70
4 40 170 × 0.014 = 2.38 28900 × 0.014 = 404.60
5 45 215 × 0.023 = 4.95 46225 × 0.023 = 1063.18
6 0 215 × 0 = 0.00 46225 × 0 = 0.00
7 0 215 × 0 = 0.00 46225 × 0 = 0.00
8 0 215 × 0 = 0.00 46225 × 0 = 0.00
Total 11.39 Total 1866.43

11.39 × 0.59 1866.425 × 0.0074 × 8760


Squirrel 1 1

Total LTVR = 6.71715 Total energy loss = 24198 Unit/annum

11.385 × 0.28 1866.425 × 0.0034 × 8760


Rabbit 1 1

Total LTVR = 3.1878 Total energy loss = 11118 Unit/annum


LTVR and Energy saving calculation(After Bifergation on Proposed New 100KVA TC)
LTVR ENERGY LOSS

Nod Load at Cummulative


Km Load2 Km
e No Node Load in HP

1 15 15 × 0.014 = 0.21 225 × 0.014 = 3.15


2 20 35 × 0.015 = 0.53 1225 × 0.015 = 18.38
3 20 55 × 0.026 = 1.43 3025 × 0.026 = 78.65
4 10 65 × 0.024 = 1.56 4225 × 0.024 = 101.40
5 0 65 × 0 = 0.00 4225 × 0 = 0.00
6 0 65 × 0 = 0.00 4225 × 0 = 0.00
7 0 65 × 0 = 0.00 4225 × 0 = 0.00
8 0 65 × 0 = 0.00 4225 × 0 = 0.00
9 0 65 × 0 = 0.00 4225 × 0 = 0.00
Total 3.73 Total 201.58

3.725 × 0.59 201.575 × 0.0074 × 8760


Squirrel 1 1

Total LTVR = 2.19775 Total energy loss = 2613.4 Unit/annum

3.725 × 0.28 201.575 × 0.0034 × 8760


Rabbit 1 1

Total LTVR = 1.043 Total energy loss = 1200.7 Unit/annum

Annual Energy Loss before bifurgation


1 43613.00
on existing 250KVA

Annual Energy Loss after bifurgation


2 11118.00
on existing 250KVA

Annual Energy Loss after bifurgation


3 1201.00
on proposed 100KVA

4 Annual Energy Savings in units 31294.00

Annual Energy Savings in Cost


5 156470.00
(Rs.5.00 /unit)
6 Estimate Cost (in Rs.) 694970.96

7 Pay Back Period 4.44

9 Return on Investment
22.000

You might also like