ABU DHABI CIVIL DEFENSE GENERAL NOTES FOR SHOP DRAWING

1. ALL THE SHOP/EXECUTIVE DRAWINGS ARCHITECTURAL LAYOUT


SHALL BE AS PER ADCD APPROVED FIRE LIFE SAFETY INITIAL
ARCHITECTURAL DRAWINGS.
2. ANY ARCHITECTURAL CHANGES LIKE ADDITION, DELETION,
MODIFICATION DURING CONSTRUCTION OR IN FUTURE SHALL BE
SUBMITTED TO ADCD FOR BOTH ARCHITECTURAL AND
SHOP APPROVALS.
3. FIRE ALARM, FIRE FIGHTING, EMERGENCY/EXIT LIGHT SYSTEM
AND VOICE EVACUATION SYSTEM SHALL BE INSTALLED AS PER
APPROVED SHOP DRAWING.
STAIR CASE.3 STAIR CASE.2 STAIR CASE.1 4. ALL THE MATERIALS, SYSTEMS, ASSEMBLIES, EQUIPMENT,
PRODUCTS AND ACCESSORIES, REFERRED TO IN THIS DRAWING
WITH RESPECT TO LIFE SAFETY, FIRE SAFETY AND EMERGENCY
SERVICES AND ALL OTHER SYSTEMS SHALL BE LISTED,
APPROVED AND REGISTERED BY THE CIVIL DEFENCE MATERIAL
APPROVAL DEPARTMENT.
5. ALL PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED
AS PER (UAE FIRE AND LIFE SAFETY CODE AND NFPA 10)
6. EMERGENCY LIGHT AND EXIT SIGN SHALL BE PROVIDED
ACCORDING TO (UAE FIRE AND LIFE SAFETY CODE AND NFPA 101)
7. ALL PORTIONS OF THESE BUILDINGS AND COMMON AND
UN-SWITCHED REFERENCE SUPPLY SERVICES AREAS SHALL BE FULLY COVER BY SMOKE
FROM LOCAL DB's FOR SENSING DETECTIONS AND FULLY COVERED BY VOICE ANNOUNCEMENT
POWER FAILURE(TYP.) ROOF FLOOR SYSTEM ACCORDING TO (NFPA 72).
2x1Cx1.5sq.mm PVC WIRES 8. ALL PORTIONS OF THESE BUILDING SHALL BE FULLY
SYMBOL DESCRIPTION
PROTECTED BY AUTOMATIC SPRINKLERS SYSTEM ACCORDING 9.3W LED SURFACE MOUNTED EMERGENCY LIGHT
TO (NFPA 13.) NON-MAINTAINED TYPE-IP65 (B.O.H AREAS)
MAKE/ MODEL: EATON/ IP65+
9. ALL STANDPIPE SYSTEM SHALL BE PROVIDED IN THESE
1 LIGHTING DB 11.6W LED RECESS MOUNTED EMERGENCY LIGHT
FDB-BLD2A-L2-L1
BUILDING ACCORDING TO (NFPA 14). NON-MAINTAINED TYPE-IP20 (F.O.H AREAS)
1 10. ANY AREA PROVIDED WITH FALSE CEILING IF THE VOID MAKE/ MODEL: EATON/ RXS2S 15KZ
DLS-SUB-CIRCUIT DEPTH MORE THAN 800MM SHALL BE PROTECTED WITH BOTH 3.2W LED SURFACE MOUNTED EMERGENCY LIGHT
MONITORING MODULE DLS NON-MAINTAINED TYPE-IP65 (B.O.H AREAS)
CEILING VOID SMOKE DETECTORS AND CEILING VOID UPRIGHT
MAKE/ MODEL: EATON/ SAFELITE
SPRINKLERS AS PER UAE FLS CODE 3.2W LED RECESS MOUNTED EMERGENCY LIGHT
11. ALL SPECIAL SYSTEM LIKE CLEAN AGENT, FOAM, NON-MAINTAINED TYPE-IP65 (F.O.H AREAS)
WATER SPRAY, WATER MIST, WET CHEMICAL KITCHEN HOOD MAKE/ MODEL: EATON/ SAFELITE
SYSTEMS SHALL BE INSTALLED IN THIS BUILDING IN ACCORDANCE 8W LED SURFACE MOUNTED EMERGENCY LIGHT
1 LOCATION:ELEC.ROOM NON-MAINTAINED TYPE-IP65 (STAIRCASES)
2ND FLOOR (2A-SF-07) TO THE RELEVANT NFPA CODE. MAKE/ MODEL: EATON/ NEXI500
230VAC
B8/ESMDB-BLD2A-L2-02 12. ALL FIRE DOOR AND WINDOWS SHALL BE ACCORDING 2.6W LED ABOVE DOOR/ WALL MOUNTED EXIT LIGHT
1 TO (NFPA 80). MAINTAINED TYPE-IP40(F.O.H AREAS)
13. ALL TYPES OF SMOKE CONTROL SYSTEMS (INCLUDE PRESSURE MAKE/ MODEL: EATON/ GUIDE LED 11024
SECOND FLOOR
NETWORK CABLE BELDEN 5341FE

DIFFERENCE BETWEEN ADJACENT ZONES) SHALL BE INSTALLED IN 2.6W LED RECESS MOUNTED EXIT LIGHT
2Cx4sq.mm FP200 DC CABLE MAINTAINED TYPE-IP40(F.O.H AREAS)
THIS BUILDING IN ACCORDANCE WITH UAE FLS CODE AND OTHER MAKE/ MODEL: EATON/ GUIDE LED 11024
INTERNATIONAL CODES AND STANDARDS. 1.2 W LED ABOVE DOOR/ WALL MOUNTED EXIT LIGHT
UN-SWITCHED REFERENCE SUPPLY
14. ALL INTERIORS FINISHING MATERIAL SHALL BE PROVIDED AS MAINTAINED TYPE-IP65(B.O.H AREAS)
FROM LOCAL DB's FOR SENSING POWER (UAE FIRE AND LIFE SAFETY CODE AND NFPA 101). MAKE/ MODEL: EATON/ SAFELITE
FAILURE(TYP.) 2x1Cx1.5sq.mm PVC WIRES
15. FIRE PUMP AND FIRE WATER TANK SHALL BE LISTED AND CENTRAL BATTERY MAIN PANEL
TESTED AND INSTALLED ACCORDING TO CIVIL DEFENSE
REQUIREMENT AND INTERNATIONAL STANDARDS. AND ALL PUMP CENTRAL BATTERY SUB PANEL
CAPACITY THAT LESS THAN 350 GPM SHALL BE ONLY REGISTER
2Cx2.5mm.sq. FP200 CABLE
1 LIGHTING DB WITH ABUDHABI QUALITY AND CONFORMITY COUNCIL WITHOUT
FDB-BLD2A-L1-L1 ANY REGISTRATION AND APPROVAL FROM ANY REGISTER ABBREVIATIONS
1
LABORATORY.
DLS-SUB-CIRCUIT T/A TO ABOVE T/B TO BELOW
MONITORING MODULE DLS 16. EMERGENCY POWER SYSTEM SHALL BE INSTALLED IN THIS
BUILDING IN ACCORDANCE TO THE RELEVANT NFPA CODE. F/A FROM ABOVE F/B FROM BELOW
17. ALL PENETRATIONS THROUGH FIRE RESISTANCE RATED
WALLS SHALL BE PROTECTED BY APPROVED FIRE STOP SYSTEM
AND MATERIALS, INSTALLED AND TESTED IN ACCORDANCE WITH REFERENCE NO:
1
LOCATION:ELEC.ROOM ASTM E 814 OR UL 1479. IFC 256282-BLD2A-SCH-ELE-0060-2
1ST FLOOR (2A-FF-03)
230VAC 18. ALL MEANS OF AGGRESS COMPONENTS DETAILS AND
R8/ESMDB-BLD2A-L0-1A AE 1156-4TCD-PROSW-ELE-SPE-0001
DIMENSIONS SHALL BE PROVIDED AND CONSTRUCTED ACCORDING SPECIFICATION
31.SECTION 26 52 00
1 TO (UAE FIRE AND LIFE SAFETY CODE AND NFPA 101 AND 5000).
2Cx4sq.mm FP200 DC CABLE 19.CONSULTANT AND CONTRACTOR SHALL COMPLY WITH
FIRST FLOOR UAE FIRE AND LIFE SAFETY CODE CHAPTER 12 IN TERMS OF
REQUIREMENTS OF BUILDING UNDER CONSTRUCTION.
UN-SWITCHED REFERENCE SUPPLY 20. EMERGENCY ACTION PLAN SHALL BE IMPLEMENTING IN
FROM LOCAL DB's FOR SENSING POWER
FAILURE(TYP.) THESE BUILDINGS ACCORDING TO UAE FIRE AND LIFE SAFETY CODE.
21.ALL DECORATION DESIGN AND MATERIALS AND ALL SERVICE
SYSTEMS IN THIS BUILDING SHALL NOT OBSTRUCT ALL
FIRE SAFETY SYSTEM ESPECIALLY SPRINKLER SYSTEM
NETWORK CABLE BELDEN 5341FE

1 22.AIR CONDITION EQUIPMENT'S IS NOT ALLOWED INSIDE


LIGHTING DB
FDB-B2-L0-L4
A PROTECTED STAIRCASE.
23.CONSULTANT AND CONTRACTORS MUST COMPLY WITH THE
REVISION
UN-SWITCHED REFERENCE SUPPLY
FROM LOCAL DB's FOR SENSING POWER GENERAL NOTES AND APPLICABLE CODES AND STANDARDS
FAILURE(TYP.) EVEN IF THE CODE REQUIREMENT WAS MISSED DURING
PLAN REVIEW.

1
LIGHTING DB
FDB-B2-L0-L3

UN-SWITCHED REFERENCE SUPPLY


FROM LOCAL DB's FOR SENSING POWER
FAILURE(TYP.)

1
LIGHTING DB
FDB-B2-L0-L1
2x1Cx1.5sq.mm PVC WIRES

2Cx4sq.mm FP200 DC CABLE

1
DLS-SUB-CIRCUIT
DLS
MONITORING MODULE

INTERFACE WITH BMS OVER IP


FIRE ALARM SYSTEM INTERFACE
THROUGH DRY CONTACT

ZB-S/10C
1 CBMP-BLD02
PANEL
PC WITH GRAPHIC
1
LOCATION: BUILDING.01
SEC. CONTROL ROOM (01.GF.09)

1 2Cx2.5mm.sq. FP200 STRANDED TYPE WHITE COLOR CABLE

LOCATION:- ELEC.ROOM
GROUND FLOOR 2A.GF.39

STAIR CASE.3 STAIR CASE.2 STAIR CASE.1 GROUND FLOOR

BUILDING-02

FZ - LLC

STEEL BUILDING CONTRACTING Co. L.L.C. P.O.BOX: 27444, DUBAI, UAE.

P.O.Box: 46625
Tel: 02-4067888, Fax: 02-5512955
Abu Dhabi, U.A.E
E-mail : gisco@giscoauh.ae,

SCHLUMBERGER ACE BASE EXPANSION


ABU DHABI

BUILDING 02A
SCHEMATIC DIAGRAM
CENTRAL BATTERY SYSTEM

AJ-420-0-EN-SEE-02-GIS-0001