(14) Perform daily and 6-month inspections for the G9SE. Otherwise, the system may fail to work properly,
resulting in serious injury. Turn OFF the signal to Safety input and make sure G9SE operates without fault by
●Preset Switches (only applies to Type G9SE-221-T
Change the value of the preset switches only when G9SE is disconnected from power supply. 4 Ratings and Specifications
checking the state of the LED indicator in inspection.
(15) Conformity to requirements of performance level is determined as an entire system. It is recommended to consult
Name Function Value ●Ratings
a certification body regarding assessment of conformity to the required safety level. OFF-delayed Presets OFF-delay For Type G9SE-221-T05 Item G9SE-201 G9SE-401 G9SE-221-T□
0(default setting value)/0.1/0.2/0.3/0.4/0.5/0.6/0.7/0.8/1.0/1.5/2.0/2.5/3.0/4.0/5.0(s)(*2)
Type G9SE-201 Type G9SE-401 (16) OMRON shall not be responsible for conformity with any safety standards regarding to customer's entire
system.
time preset time (duplicate)
For Type G9SE-221-T30 Power
Rated supply voltage 24 VDC
□ switch (*1) Operating voltage range -15% to 10% of rated supply voltage
Type G9SE-221-T (17) Dispose of the Units according to local ordinances as they apply. 0(default setting value)/1/2/4/5/6/7/8/9/10/12/14/16/20/25/30(s)(*2) input
Rated power consumption (See Note1) 3 W max. 4 W max. 4 W max.
Safety Relay Unit Precautions for Correct Use (*1) Set both of the two Off-delay Time Preset Switches, one each on the front and back, to the same value.
Safety output Contact output
When setting the different value, it is detected as a fault.
(1) Handle with care (*2) See following illustration for setting position of Off-delay Time Preset Switch. Make sure that the direction of cutting Outputs OFF-delayed Safety output 250 VAC 5 A 30 VDC 5 A (resistive load)
English USER'S MANUAL Do not drop G9SE to the ground or expose to excessive vibration or mechanical shocks. G9SE may be damaged
and may not function properly.
edge of preset switch is correctly pointed to the off-delay time value which must be set. Auxiliary output PNP transistor output Load current :100 mA DC max.
(2) Adhesion of solvent such as alcohol, thinner, trichloroethane or gasoline on the product should be 0.30.40.5 0.30.40.5
Thank you for purchasing G9SE Safety Relay Unit.
avoided. Such solvents make the marking on G9SE illegible and cause deterioration of parts. 0.2 0.6 0.2 0.6 ●Specifications and performance
Please read and understand this manual before using the products. 0.1 0.7 0.1 0.7
(3) Conditions of storage 0 0.8 G9SE-201 G9SE-401 G9SE-221-T□
Keep this manual ready to use whenever needed. 0 0.8
Only qualified person trained in professional electrical technique should handle G9SE. Do not store in such conditions stated below. 5.0 1.0 5.0 1.0 Operating time (OFF to ON state) (See Note2) 100 ms Max. (See Note3)
4.0 1.5 4.0 1.5 Response time (ON to OFF state) 15 ms Max.
Please consult your OMRON representative if you have any questions or comments. 1) In direct sunlight 3.0 2.5 2.0 3.0 2.5 2.0
cutting edge cutting edge
2) At ambient temperatures out of the range of -10 to 55 ℃ Accuracy of OFF-delay time ー ー Within plus or minus 10 % of
OFF-DELAY OFF-DELAY the set value
3) At relative humidity out of the range of 25% to 85% or under such temperature change that causes condensation.
4022078-4 E
4) At atmospheric pressure out of the range 86 to 106 kPa.
ex.1) 0 second off-delay ex.2) 1.5 second off-delay Input current 5 mA Min.
3
before commissioning the system in which G9SE is incorporated.
(5) Do not apply DC voltages exceeding the rated voltages, or AC voltages to G9SE.
71
(6) Use SELV/PELV DC porwer supply satisfying requirements below to prevent electric shock.
- DC power supply with double or reinforced insulation, for example, according to IEC/EN60950 or EN50178 or a transformer
according to IEC/EN61558. OMRON Corporation (Manufacturer)
Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 JAPAN
124
- DC supply satisfies the requirement for class 2 circuits stated in UL 508.
133 ±0.3
(7) The lifetime of G9SE depends on the conditions of switching of its outputs. Be sure to conduct its test operation Regional Headquarters OMRON ELECTRONICS LLC
under actual operating conditions in advance and use it within appropriate switching cycles. Apply protection Safety Outputs
(Instantaneous) Safety Outputs (OFF-delay) OMRON EUROPE B.V. 2895 Greenspoint Parkway, Suite 200
circuitry against back electromotive force in case connecting inductive loads to safety outputs.
(8) Do not operate the G9SE with flammable or explosive gas. An arc with operation and the heat of relay will cause (Representative and Importer in EU) Hoffman Estates, IL 60169 U.S.A.
a fire or an explosion.
●LED Indicators Wegalaan 67-69, 2132 JD Hoofddorp Tel: (1) 847-843-7900
(9) Do not drop G9SE to the ground or dismantle, repair, modify G9SE, otherwise an electric shock may occur or Marking Color Name Function The Netherlands Fax: (1) 847-843-7787
73.5
the G9SE may malfunction. It may lead to loss of its safety functions. Power supply Lights up while power is supplied.
PWR Green
(10) Use protective device (Fuse etc.) for short-circuit protection and ground fault protection, otherwise a fire may occur Indicator Blinks corresponding to the occurring error
or the G9SE may malfunction. Safety Input Lights up while high signal is input to T12 OMRON (CHINA) CO., LTD.
IN1 Orange OMRON ASIA PACIFIC PTE. LTD.
3
5.6
(11) Auxiliary monitoring outputs are NOT safety outputs. Do not use auxiliary outputs as any safety output. #1 indicator Blinks when error relating to Safety input #1 occurs.
Safety Input
No. 438A Alexandra Road # 05-05/08 Room 2211, Bank of China Tower,
Such incorrect use causes loss of safety function of G9SE and its relevant system. IN2 Orange
Lights up while high signal is input to T22
(12) After installation of G9SE, qualified personnel shall confirm the installation, and shall conduct test #2 indicator Blinks when error relating to Safety input #2 occurs. (Lobby 2), Alexandra Technopark, 200 Yin Cheng Zhong Road,
operations and maintenance. OUT Safety Output Lights up while Safety outputs (13-14, 23-24, 33-34, 43-44) are in ON-state. Singapore 119967 PuDong New Area, Shanghai, 200120, China
The qualified personnel shall be qualified and authorized to secure the safety on each phases of design, Orange Mounting holes Tel: (65) 6835-3011/Fax: (65) 6835-2711 Tel: (86) 21-5037-2222/Fax: (86)
OUT1 indicator Blinks when an error relating to Safety output occurs. Type G9SE-201 Type G9SE-401 9.9
installation, running, maintenance and disposal of system. OFF-delayed
(13) A person in charge, who is familiar to the machine in which G9SE is to be installed, shall conduct and verify Safety Output Lights up while off-delayed Safety outputs (37-38, 47-48) are in ON-state. Type G9SE-221-T □ Contact: www.ia.omron.com
OUT2 Orange [mm]
the installation. indicator Blinks when an error relating to Safety off-delayed solid-state output occurs.
Note: Specifications subject to change without notice.
●Wiring of inputs and outputs 5 Examples of application 7 Fault Detection
Signal Terminal Type G9SE-201 Type G9SE-221-T□ When G9SE detects a fault, LED indicators blink to show the information of the fault.
Description of operation Wiring
Name Name <2-channel emergency stop switch input / Manual reset> <Guard lock safety door switch (Mechanical Lock)・ Safety limit switch inputs
Power A1, The input terminals for power supply. Connect the power supply plus to the A1 Note1 : This example is corresponding to category 4 / Manual reset> Note1 : This example is corresponding to category 4 When PWR indicator blinks, check and take needed measures referring to the following table.
supply A2 Connect the power source to the A1 and A2 terminal. And then apply supply voltage to G9SE.
terminals. Connect the power supply minus to the A2 Feedback loop LED indicator
input Device Lock Device Expected causes of Checking points and
terminal. S1 S2
+24V S1 :Emergency stop switch release S1 :Safety limit switch PWR IN1 IN2 OUT OUT2 the faults measures to take
Safety T11, To set Safety outputs in ON state, HIGH 1-channel signal KM1 OUT1
KM1 S2 :Reset switch S2 :Guard lock safety 1) Failures involving the wiring of 1) Check the wiring to T11 and T12.
input 1 state signals must be input to both of
T12 Safety input 1 and Safety input 2. Safety input KM1,KM2 :Contactor door switch Safety input 1
KM2 (Mechanical Lock) Blink 2) Failures of the parts of the circuits 2) Replace with a new product.
Otherwise Safety outputs cannot be in KM2 M :3-phase motor
of Safety input 1.
ON state. T11 T12 T21 T22 S3 :Reset switch 1) Failures involving the wiring of
S2 1) Check the wiring to T21 and T22.
2-channel
Safety sensor S4 S4 :Lock release switch Safety input 2
2) Failures of the parts of the circuits 2) Replace with a new product.
Safety input
KM1,KM2:Contactor Blink
of Safety input 2.
M :3-phase motor Safety inputs: ON-state 1) Failures involving the wiring of 1) Check the wiring to T31, T32, and T33
Safety T21, OSSD1 OSSD2 A1 T11 T12 T31 T32 T33 13 23 Feedback/Reset input.
input 2 T22 T11 T12 T21 T22 Light Light 2) Failures of the parts of the circuits 2) Replace with a new product.
up up of Feedback/Reset input.
Safety inputs: OFF-state
Safety Light Light
Input1 Reset/ off off
Power Safety Blink
T11 T12 T21 T22 24V Feedback 1) Failures of the parts or relays of the 1) Replace with a new product.
supply Output Feedback loop
To set Safety outputs in ON state, ON Auto reset Input (Instant
circuits of Safety Output.
Reset/ T31, Feedback loop circuit Blink Blink
Feedback T32, state signal must be input to T33. Safety aneous) Guard
Otherwise Safety outputs cannot be in +24V KM
Input2 Auxiliary S3 1) Mismatch of the two Off-delay 1) Check both of the two Off-delay Time
input S1 KM1 Time Preset Switches. Preset Switches.
T33 ON state. (See Note1) output
T31 T32 T33 OPEN Blink
KM2
To set Safety outputs in ON state, the Manual Reset Feedback loop
signal input to T32 must change from reset
Switch A2 T21 T22 X1 14 24 1) Supply voltage outside the 1) Check the supply voltage to G9SE.
KM +24V rated value.
OFF state to ON state, and then to OFF The all indicators Blink
Stop signal
state. Otherwise Safety outputs cannot PLC etc. KM1 KM2 1) By excessive electro-magnetic 1) Check the disturbance level around
be in ON state. T31 T32 T33 disturbance. G9SE and its related system.
The all indicators Light off 2) Failures of the parts of internal 2) Replace with a new product.
Safety 13-14, Turns ON/OFF according to the state of Keep these outputs Open when NOT used. circuits
output 23-24, safety inputs, Feedback/Reset inputs.
33-34, During off-delay state, safety outputs When indicators other than PWR indicator blink while PWR indicator lights up, check and take needed
43-44, are not able to turn ON. measures referring to the following table. After removing the fault, turn both safety inputs to OFF state.
A1 T11 T12 T31 T32 T33 13 23 37 47 LED indicator
Off- 37-38, Off-delayed safety outputs. Keep these outputs Open when NOT used. Expected causes of Checking points and
(See Note2)
Timing chart PWR IN1 IN2 OUT OUT2 the faults measures to take
delayed 47-48 OUT1
Safety Off-delay time is set by off-delay Safety inputs: ON-state 1) Mismatch between Safety input 1 1) Check the wiring from safety input devices
preset switch. KM1 Emergency stop switch S1 Safety and Safety input 2. to G9SE. Or check the inputs sequence of
output Safety Output
When the delay time is set to zero, (OFF timing) safety input devices.
Input1 Reset/ (Instant Blink Blink
these outputs can be used as Reset switch S2 Power
KM2 24V Feedback aneous) Light
instantaneous outputs. supply up
KM1,KM2 NC contact Input Light
circuit Safety Blink
Auxiliary X1 Outputs a signal of the same logic as Keep these outputs Open when NOT used. off
Safety Output
output Safety outputs M KM1,KM2 NO contact Input2 Auxiliary (OFF- Light
output delay) Blink
off
(1) Construct the safety system taking into account that in the Auto reset mode Safety outputs turn ON
automatically when Safety inputs 1 and 2 turn ON. Type G9SE-401
A2 T21 T22 X1 14 24 38 48
8 Wiring
(2) When the inputs of G9SE-221-T□ are restored during off-delay time, G9SE-221-T□ will operate <2-channel safety sensor / Auto reset> Use the following to wire to G9SE.
as below. Depending on the reset mode.
Note1 : This example is corresponding to category 4 - Solid wire: AWG24 to AWG16 (0.25 to 1.5 mm2)
- Auto reset mode: Outputs turn off after off-delay time, then immediately turns on. KM1 KM2
Safety PLC etc. - Stranded wire: AWG24 to AWG16 (0.25 to 1.5 mm2)
- Manual reset mode: Outputs turn off after off-delay time, then turn on when reset input is given. Motor controller
Emitter sensor Receiver Feedback loop Strip the cover of wire no longer than 8 to 10 mm
●Connecting Safety Sensors and G9SE (Operation command) When using stranded wire, insulated ferrule should be used. Use below insulated ferrule.
Device When using ferrule, G9SE is suitable for Factory Wiring Only. When using G9SE as a "UL Listed" product
In many case, Safety Sensor outputs include the off-shot pulse for its self test.
Safety sensor Timing chart for Field Wiring, do not use ferrule but insert the strand or solid wire (CU only) directly into the holes on
The following condition of test pulse is applicable as safety inputs for G9SE.
- Off-shot pulse width of the sensor, during the ON-state : 640 µs KM1 KM1∼KM4 :Contactor Guard closed → opened the terminal block.
- Insulated ferrule: AWG24 to AWG16 (0.25 to 1.5 mm2)
M1,M2 :3-phase motor Safety limit switch S1 - Crimp height(H): 2.0 mm max. Width(W): 2.7 mm max. Conductor length: 8 to 10 mm
KM2 When using the twin type ferrule, use equal-sized wires and preferred insulated ferrule.
Motor controller 14 Guard lock safety The twin type ferrule should not be above the adjoining release hole.
door switch S2
640 µs Max. KM3 ■Recommended insulated ferrule: manufactured by Phoenix contact
OSSD1