Electrical Thumb Rules You MUST Follow (4)

×
Get Notifications
By jiguparmar    November, 15th 2013   Save to PDF ♛
Electrical Thumb Rules You MUST Follow – part 4 (on photo: Distribution substation bus on a clear
night in February by Eli Nelson, via Flickr)

Continued from: Electrical Thumb Rules You MUST Follow (Part 3)

Eight rules to follow:


1.  Substation Capacity and Short Circuit Current Capacity (As per GERC)
2.  Substation Capacity and Short Circuit Current Capacity (As per Central Electricity
Authority)
3.  Minimum Ground Clearance and Fault Clearing Time
4.  Busbar Ampere Rating
5.  Busbar Spacing
6.  Sound Level of Diesel Generator (ANSI 89.2 and NEMA 51.20)
7.  IR Value of Transformer
8.  Standard Size of MCB, MCCB, ELCB, RCCB, SFU and Fuse

1. Substation Capacity and Short Circuit Current Capacity

As per GERC
Voltage Sub Station Capacity Short Circuit Current
400 KV Up to 1000 MVA 40 KA  (1 to 3 Sec)
220 KV Up to 320 MVA 40 KA  (1 to 3 Sec)
132 KV Up to 150 MVA 32 KA  (1 to 3 Sec)
66 KV Up to 80 MVA 25 KA  (1 to 3 Sec)
33 KV 1.5 MVA to 5 MVA 35 KA (Urban) (1 to 3 Sec)
11 KV 150 KVA to 1.5 MVA 25 KA (Rural) (1 to 3 Sec)
415 V 6  KVA to 150 KVA 10 KA  (1 to 3 Sec)
220 V Up to 6 KVA 6 KA  (1 to 3 Sec)

Go back to Rules ↑

2. Substation Capacity and Short Circuit Current Capacity

As per Central Electricity Authority
Voltage Sub Station Capacity Short Circuit Current
765 KV 4500 MVA 31.5 KA for 1 Sec
400 KV 1500 MVA 31.5 KA for 1 Sec
220 KV 500 MVA 40 KA for 1 Sec
110/132 KV 150 MVA 40 KA or 50 KA for 1 Sec
66 KV 75 MVA 40 KA or 50 KA for 1 Sec

Go back to Rules ↑

3. Minimum Ground Clearance and Fault Clearing Time

Voltage Min. Ground Clearance Fault Clear Time


400 KV 8.8 Meter 100 mille second
220 KV 8.0 Meter 120 mille second
132 KV 6.1 Meter 160 mille second
66 KV 5.1 Meter 300 mille second
33 KV 3.7 Meter –
11 KV 2.7 Meter –

Go back to Rules ↑

4. Busbar Ampere Rating

For Phase Busbar Aluminium 130 Amp / Sq.cm or 800Amp / Sq.inch.
For Phase Busbar Copper 160 Amp / Sq.cm or 1000Amp / Sq.inch
For Neutral Busbar Same as Phase Busbar up to 200 Amp than Size
of Neutral Busbar is at least half of Phase Busbar.

Go back to Rules ↑

5. Busbar Spacing

Between Phase and Earth 26mm (Min)
Between Phase and Phase 32mm (Min)
Busbar Support between Two Insulator 250mm.

Go back to Rules ↑

6. Sound Level of Diesel Generator (ANSI 89.2 and NEMA 51.20)

KVA Max. Sound Level
<9 KVA 40 DB
10 KVA to 50 KVA 45 DB
51 KVA to 150 KVA 50 DB
151 KVA to 300 KVA 55 DB
301 KVA to 500 KVA 60 DB

Go back to Rules ↑

7. IR Value of Transformer

IR Value of Transformer
Voltage 30°C 40°C 50°C
>66KV 600MΩ 300MΩ 150MΩ
22KV to 33KV 500MΩ 250MΩ 125MΩ
6.6KV to 11KV 400MΩ 200MΩ 100MΩ
<6.6KV 200MΩ 100MΩ 50MΩ
415V 100MΩ 50MΩ 20MΩ

Go back to Rules ↑
8. Standard Size of MCB, MCCB, ELCB, RCCB, SFU and Fuse

MCB, MCCB, ELCB, RCCB, SFU, Fuse – Standard Ratings
MCB Up to 63 Amp (80Amp and 100 Amp a    per Request)
MCCB Up to 1600 Amp (2000 Amp as per Request)
ACB Above 1000 Amp
MCB Rating 6A,10A,16A,20A,32A,40A,50A,63A
MCCB Rating 0.5A,1A,2A,4A,6A,10A,16A,20A,32A,40A,50A,63A,80A,100A
(Domestic Max 6A)
RCCB/ELCB 6A,10A,16A,20A,32A,40A,50A,63A,80A,100A
Sen. of ELCB 30ma (Domestic),100ma (Industrial),300ma
DPIC (Double 5A,15A,30 A for 250V
Pole Iron Clad)
main switch
TPIC (Triple Pole 30A, 60A, 100A, 200 A For 500 V
Iron Clad) main
switch
DPMCB 5A, 10A, 16A, 32A and 63 A for 250V
TPMCCB 100A,200A, 300Aand 500 A For 660 V
TPN main switch 30A, 60A, 100A, 200A, 300 A For 500 V
TPNMCB 16A, 32A,63A For 500 V, beyond this TPNMCCB: 100A,
200A, 300A, 500 A For 660 V
TPN Fuse Unit 16A,32A,63A,100A,200A
(Rewirable)
Change over 32A,63A,100A,200A,300A,400A,630A,800A
switch (Off
Load)
SFU (Switch 32A,63A,100A,125A,160A,200A,250A,315A,400A,630A
Fuse Unit)
HRC Fuse TPN 125A,160A,200A,250A,400A.630A
(Bakelite)
HRC Fuse DPN 16A,32A,63A
(Bakelite)
MCB/MCCB/ELCB Termination Wire / Cable
Up to 20A MCB Max. 25 Sq.mm
20A to 63A MCB Max. 35 Sq.mm
MCCB Max. 25 Sq.mm
6A to 45A ELCB 16 Sq.mm
24A to 63A 35 Sq.mm
ELCB
80A to 100A 50 Sq.mm
ELCB

Related EEP's content with sponsored links

Premium Membership
Get access to premium HV/MV/LV technical articles, electrical engineering guides,
research studies and much more! It helps you to shape up your technical skills in
your everyday life as an electrical engineer.

MORE INFORMATION

Jignesh Parmar

Jignesh Parmar has completed M.Tech (Power System
Control), B.E (Electrical). He is member of Institution of
Engineers (MIE), India. He has more than 20 years experience
in transmission & distribution­energy theft detection and
maintenance electrical projects.

13 Comments

Praveen Kumar Yadav


AUG 25, 2018

What is Maximum sound level for
1000 KVA and 1250 KVA DG Set’s

Reply

NITIN
APR 19, 2018

I want to install a bus bar. For total 6 rooms having 6 electric water
gyser of 25 litres (2000 watt) and lighting.
Which bus bar suits me.
63 amp
100 amp

Reply
Hari Haran GKM
NOV 21, 2017

MCB/MCCB/ELCB Termination Wire / Cable
MCCB Max. 25 Sq.mm is it correct??

Reply

Ghazanfar Ali Khan


NOV 11, 2017

How the maximum voltage is specified for 132­KV and 220­KV for
Lightning arresters ?
How Tertiary winding a transformer mitigate third harmonics? This
question is pending since Feb.2015 to answer.

Reply

Uday Desai
OCT 23, 2015

Excellent information, which will usefull in daily working.

Reply

Joseph Auo
JUL 08, 2015

Dear Sir,

the minimum Ground clearances to Ground for the voltages 11kV to
132kV seem to be too small. They should be 5.6 for 11kV and 22kV
and 6.5 for 33kV and 6.7 for 66kV and 132kV. The condition should
be @ he maximum operating temperature of 75 Deg. C.

Reply
Y M Yacoob
JUN 19, 2015

Sorry Jignesh, I just found all the past copies, Thanks

Reply

Y M Yacoob
JUN 19, 2015

Hello Jignesh, thank you for the very interesting info. Where can I find
parts 1 ; 2 & 3 ?

Reply

Anuja
FEB 20, 2015

Its too useful n knowledgeable thanku

Reply

Bavya
DEC 04, 2014

You are a motivation for many of unsuccessful electrical engineers

Reply

Manoj Badave
JUN 02, 2014

Hello dear,
you have a grand collection of information, very useful one for the
freshers as well as for practicing engineers

Reply

Hoss
MAR 22, 2014

Hi mr. Parmar.Please send to me your experiences via my email
hosseinke@yahoo.com.Best regards.

Reply

Merksab
DEC 01, 2013

Excelleng

Reply

Leave a Comment

Tell us what you're thinking... we care about your opinion! Please keep in mind
that comments are moderated and rel="nofollow" is in use. So, please do not use a
spammy keyword or a domain as your name, or it will be deleted. Let's have a
professional and meaningful conversation instead. Thanks for dropping by!

YO UR  REAL  NAME  *

EMAIL  ADDRESS  *
Pr ov e  that  y ou  ar e  not  R2D2.  Solv e  s ome  math:

Ten  ∕  One  =  

SUBMIT COMMENT

© 2021 EEP ­ Electrical Engineering Portal. All Rights Reserved | Privacy Policy | Terms and Conditions

You might also like