VICINITY MAP

HOLABIRD ACADEMY
M
ELEMENTARY / MIDDLE SCHOOL M

CITY OF BALTIMORE, MD
L ABBREVIATIONS 1500 IMLA STREET, BALTIMORE, MD 21224 L
Above finished floor AFF Footing FTG Project PROJ
Acoustic ACST Foundation FDN Property PROP
Acoustic Panel Ceiling APC Furnish(ed), furniture FURN Public Address PA
Addendum ADD Furring FURR Quality control QC
Alternate ALT Gage (gauge) GA Quality QUAL
Aluminum AL Galvanize(d) GALV Quantity QTY
Angle L Galvanized Iron GALVI Quarry Tile QT
Approximate APPROX Glazed Wall Tile GWT Radius RAD
Architecture, architectural ARCH Grab Bar GB Rain Leader RL
Asbestos ASB Grade GR Received RCVD
Asphalt ASPH Gravel GVL Receptacle RCPT
Assistant ASST Gypsum Wallboard GWB Receptionist RECPT
Association ASSN Gypsum GYP Recess(ed) REC
Automatic AUTO Handicapped HC Refer, reference REF
Average AVG Hardware HDW Refrigerate, refrigerator REFR
K Base plate BP Heating ventilating and HVAC Reinforce REINF K
Basement BSMT air conditioning Reinforced concrete RC
Beam BM Height HGT Remove RMV
Bearing BRG High Point HPT Repair RPR
Bedroom BR High Performance HP Required REQD
Benchmark BM High Performance Coating HPC Revise, revision REV
Board BD Hollow Metal HM Right hand RH
Boiler BLR Horizontal HORIZ Road RD
Bottom BOT Include(d), inclusive INCL Roof Drain RD
Brick BRK Incorporated INC Roof RF
Building line BL Information INFO Roofing RFG
Building BLDG Inside diameter ID Room RM
Built-up-roof BUR Install(ed), installation INSTL Rubber tile floor RTF
Cabinet CAB Insulation INSUL Rubber RBR
Carpet CPT Interior INT Schedule SCHED
Catalog CAT Janitor JAN Schematic SCHEM
J Ceiling height
Ceiling
CH
CLG
Joint
Joist
JT
J, JST
Section
Service
SECT
SVCE J
Center CTR Junction box JB "Sheet, sheeting" SHT
Centerline CL Knock down KD Shower SH
Ceramic Tile CT Laboratory LAB Siding SDG
Ceramic CER Lavatory LAV Similar SIM
Chalkboard CB Left Hand LH Slope SL
Clear CLR Left L Sound-transmission class STC
Closet CLO Length LG South S
Coated CTD Level LVL Speaker SPKR
Cold rolled CR Light LT Specification SPEC
Column COL Machine MACH Sprinkler SPR
Company CO Maintenance MAINT Square SQ
Composition COMP Manager MGR Stainless steel SS
Concrete Masonry Unit CMU Manual MNL Standard STD
Concrete CONC Manufacturing MFG Standpipe SP
Construction joint CJ Markerboard MB Steel STL
H H

www.grimmandparker.com
Construction CONSTR Masonry opening MO Storage STOR
"Continue, Continuous" CONT Masonry MSNRY Structural Glazed Facing Tile SGFT
Corridor CORR Master bedroom MBR Structural, structure STRUCT

11720 Beltsville Drive

Calverton, MD 20705
Countersink CSK Material MATL Substitute SUBST
Cubic CU Maximum MAX Surface SURF

Tel: 301.595.1000
Curve(d) CRV Mechanical MECH Suspend(ed) SUSP
Dampproofing DP Membrane MEMB Switch SW
Degree DEG Men M Symmetrical SYM
Department(al) DEPT Metal MET, MTL System SYS

Suite 600
Detail DET Mezzanine MEZZ Tackboard TB

BID SET
Diagonal DIAG Minimum MIN Tackstrip TS
Diameter DIA Mirror MIR Telephone TEL
Dimension DIM Miscellaneous MISC Television TV
Dishwasher DW Mounted MTD Temporary TEMP

Architectural
Dispenser DISP Mounting MTG Terrazzo TER
Door DR Necessary NEC Thick THK
Double DBL Noise-reduction coefficient NRC Through THRU
G Double-hung DH Nominal NOM Toilet T G
Down DN Non Combustible NC, NONCOM Tongue and groove T&G

03/13/2017
Downspout DS North N Top and bottom T&B
Drain
Drawing
Each
East
Electric Water Cooler
DR
DWG
EA
E
EWC
Not in Contract
Not to scale
Not available
Number
Office
NIC
NTS
NA
NO
OFF
Top chord
Top of Masonry Parapet
Top of Bearing
Top of Steel
Topping
TC
TMP
TOFB
T.O.S.
TOPG
& Structural
"Electric, electrical" ELEC On center OC Total TOT
Elevation EL Opening OPNG Transformer XFMR
Elevator ELEV Opposite OPP Transom TR

PSC 30.240.15/17
Engineer ENGR Outside diameter OD Transparent TRANS
Entrance ENTR Overall OA Tread TRD

F
Equal
Equipment
Exhaust
Existing
EQ
EQUIP
EXH
EXIST
Overhead
Page
Painted
Pair
OVHD
P
PTD
PR
Threshold
Typical
Underground
Underwriters Laboratories
THRESH
TYP
UG
UL
BALTIMORE CITY PUBLIC SCHOOLS F
Expansion joint EXP JT Panel PNL Unfinished UNF
Exposed EXP Partition PTN Unit Ventilator UV
Exterior EXT Percent PCT Unless Otherwise Noted UON
Fabricate FAB Perforate(d) PERF Urinal UR BALTIMORE CITY SCHOOLS
Face of Stud
Fan Coil Unit
Fiberglass-reinforced plastics
F. OF S.
FCU
FRP
Permanent
Perpendicular
Piece
PERM
PERP
PC
US Gypsum Company
Vertical
Vestibule
USG
VERT
VEST, V 200 E NORTH AVENUE GP# 21553
Finish FIN Plastic Laminate PLAM Vinyl Reducing Strip VRS
Finished Floor
Fire Extinguisher
FF
FE
Plastic Laminate
Plate
PLAS.LAM
PL
Vinyl Composite Tile
Vinyl asbestos tile
VCT
VAT BALTIMORE, MD 21202
Fire Extinguisher & Cabinet FEC Plumbing PLMB Wardrobe WARD
Fire Retardant Treated FRT Plywood PLYWD Water closet WC
Fireproof FPRF Point PT Waterproof WP

DESIGN TEAM
Fixture FXTR Polyvinyl chloride PVC Weight WT
Flange FLG Precast PRCST Welded WLD
Flashing FL Prefabricated PREFAB Welded Wire Mesh WWM
E Floor FL Preliminary PRELIM With W/ E
Floor drain FD Preparation, prepare PREP Without W/O
Flooring FLG Program PRGM Women W
Fluorescent FLUOR Projection Screen PS Wood WD
Wrought Iron WI

SYMBOLS OF MATERIALS
EARTH STEEL - LARGE SCALE
ARCHITECT: STRUCTURAL ENGINEER: ACOUSTICAL ENGINEER:
GRIMM + PARKER ARCHITECTS, INC. COLUMBIA ENGINEERING INC. CONVERGENT TECHNOLOGIES DESIGN GROUP

CITY OF BALTIMORE, MARYLAND


GRAVEL ALL METALS - SMALL SCALE

CONCRETE CAST STONE


11720 BELTSVILLE DRIVE, SUITE 600 6210 OLD DOBBIN LANE, SUITE 150 6501 YORK ROAD
D CONCRETE MASONRY UNITS GLASS - LARGE SCALE
CALVERTON, MD 20705 COLUMBIA, MD 21045 BALTIMORE, MD 21212 D

HOLABIRD ACADEMY PK-8


SOLID CONCRETE MASONRY UNITS BATT INSULATION
(301) 595-1000 (410) 992-9970 (410) 532-2395
BRICK RIGID INSULATION

WOOD-FINISHED CERAMIC TILE LANDSCAPE ARCHITECT: MECHANICAL LIGHTING/ENERGY MODELING: TECHNOLOGY (AV/IT):
WOOD ROUGH
CARPET SP ARCHITECTS, INC. CMTA EDUCATIONAL SYSTEMS PLANNING
3613 MILFORD MILL ROAD 10411 MEETING STREET 49 OLD SOLOMONS ISLAND ROAD, SUITE 301

TITLE SHEET
PLYWOOD
GYPSUM BOARD
C ACOUSTIC TILE WINDSOR MILL, MD 21244 PROSPECT, KY 40059 ANNAPOLIS, MD 21401 C
(410) 565-0432 (502) 326-3085 (410) 573-9148
DRAWING KEY
0
DETAIL NUMBER
GRID LINES
CIVIL ENGINEER/ LANDSCAPE: ELECTRICAL/ FIRE PROTECTION/ PLUMBING: FOODSERVICE CONSULTANT: DATE DESCRIPTION

#
SIM
SECTIONS
MK CONSULTING ENGINEERS, LLC SETTY + ASSOCIATES INTERNATIONAL, PLLC HOPKINS FOODSERVICE SPECIALISTS
#
SHEET NUMBER 301 CENTRAL AVENUE 3040 WILLIAMS DRIVE, SUITE 600 7906 MACARTHUR BLVD
DETAIL NUMBER
B 1
SIM
DETAILS IN PLAN/SECTION
DETAIL NUMBER GLYNDON, MD 21071 FAIRFAX, VA 22031 CABIN JOHN, MD 20818 B
SHEET NUMBER
A101
SHEET NUMBER
#
(301) 641-6074 (703) 691-2115 (301) 320-9200
# #-#.# # INTERIOR ELEVATION

# BUILDING AREA
ROOM NAME
B101a
ROOM NUMBER #

DEPT.
REVISION: TYPE =
A.S.I/P.R./C.C.D./ADD.

CASEWORK
A3
MECH BASEMENT
FIRST FLOOR
1015 SF
61994 SF
TS-1H
B101a DOOR NO. ON PLAN WALL TYPE
# (FURNISHING PLANS ONLY)
SECOND FLOOR 31323 SF 03/13/2017
H.M. FRAME NO. ALUM. FRAME/WINDOW BID SET
##
ON PLAN TYPE
Grand total 94332 SF
A © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

LIST OF DRAWINGS LIST OF DRAWINGS LIST OF DRAWINGS


0
TS-1H TITLE SHEET
TS-2H LIST OF DRAWINGS
A-7.3 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN - AREA C P-4.2 PLUMBING ENLARGED KITCHEN PLAN
M CIVIL A-7.4 PARTIAL SECOND FLR REFLECTED CEILING PLAN - AREA A P-5.1 PLUMBING DOMESTIC WATER RISER DIAGRAM M
C-1.00H EXISTING CONDITIONS/DEMOLITION PLAN A-7.5 PARTIAL SECOND FLR REFLECTED CEILING PLAN - AREA B P-5.2 PLUMBING SANITARY RISER DIAGRAM
C-2.00H PROPOSED SITE PLAN A-7.6 PARTIAL SECOND FLR REFLECTED CEILING PLAN - AREA C P-5.3H PLUMBING SANITARY RISER DIAGRAM
C-3.00H SITE DETAILS A-7.7 CEILING DETAILS P-5.4 PLUMBING NATURAL GAS RISER DIAGRAM
C-3.01H SITE DETAILS A-8.1 ALTERNATES - ENTRY CANOPY P-5.5H PLUMBING STORM RISER DIAGRAM
C-4.00H PAVING, STRIPING & SIGNAGE PLAN A-8.2 ALTERNATES - ENTRY CANOPY DETAILS P-6.1 PLUMBING SCHEDULES
C-5.01H UTILITY PLAN A-9.1 PARTIAL FIRST FLOOR FURNISHING PLAN - AREA A P-7.1 PLUMBING DETAILS
C-5.02H UTILITY PROFILES A-9.2 PARTIAL FIRST FLOOR FURNISHING PLAN - AREA B P-7.2 PLUMBING DETAILS
C-5.03H UTILITY PROFILES A-9.3 PARTIAL FIRST FLOOR FURNISHING PLAN - AREA C PD-1.1H PLUMBING PARTIAL PLAN - DEMOLITION
C-5.04H UTILITY PROFILES A-9.4 PARTIAL SECOND FLOOR FURNISHING PLAN - AREA B PD-1.2H PLUMBING OVERALL PLAN - DEMOLITION
C-5.05H UTILITY PROFILES A-9.5 PARTIAL SECOND FLOOR FURNISHING PLAN - AREA C
L L
C-6.00H EROSION AND SEDIMENT CONTROL PLAN - PHASE 1 A-9.6 MILLWORK DETAILS FIRE PROTECTION
C-6.01H EROSION AND SEDIMENT CONTROL PLAN - PHASE 2 A-9.7 MILLWORK DETAILS FP-0.1H FIRE PROTECTION GENERAL NOTES, SYMBOLS &
C-6.02H EROSION & SEDIMENT CONTROL DETAILS A-9.8H MILLWORK DETAILS - WONDER WALL ABBREVATIONS
C-6.03H EROSION & SEDIMENT CONTROL NOTES FP-1.1H FIRE PROTECTION PARTIAL FIRST FLOOR PLAN – AREA A
C-6.04H EROSION & SEDIMENT CONTROL STABILIZATION NOTES KITCHEN FP-1.2 FIRE PROTECTION PARTIAL FIRST FLOOR PLAN – AREA C
C-6.05H EROSION & SEDIMENT CONTROL STABILIZATION NOTES K-1.1 FOOD SERVICE EQUIPMENT PLAN FP-1.3 FIRE PROTECTION PARTIAL SECOND FLOOR PLAN – AREA C
C-6.06H EROSION AND SEDIMENT CONTROL DRAINAGE AREA MAPS K-1.2 FOOD SERVICE ELECTRICAL SPOT CONNECTION PLAN FP-5.1H FIRE PROTECTION RISER DIAGRAM
- PHASE 1 K-1.3 FOOD SERVICE PLUMBING SPOT CONNECTION PLAN FP-6.1H FIRE PROTECTION SCHEDULES
C-6.07H EROSION AND SEDIMENT CONTROL DRAINAGE AREA MAPS K-1.4 FOOD SERVICE VENTILATION SPOT CONNECTION PLAN FP-7.1 FIRE PROTECTION DETAILS
- PHASE 2
K C-7.00H NATURAL RESOURCES MAP STRUCTURAL ELECTRICAL LIGHTING K
C-7.01H IMPERVIOUS AREA MAP S-0.0H GENERAL NOTES EL-0.1 LIGHTING DETAILS & LEGEND
C-7.02H QUANTITY MANAGEMENT DRAINAGE AREA MAPS S-0.1H INSPECTION TABLES EL-1.0H LIGHTING - SITE - HOLABIRD
C-7.03H STORMWATER MANAGEMENT PLAN S-1.1H FOUNDATION AND SLAB ON GRADE PLAN - AREA A EL-1.1 LIGHTING - FIRST FLOOR AREA A
C-7.04H STORMWATER MANAGEMENT FACILITY 1 S-1.2H FOUNDATION AND SLAB ON GRADE PLAN - AREA B EL-1.2 LIGHTING - FIRST FLOOR AREA B
C-7.05H STORMWATER MANAGEMENT FACILITY 2 S-1.3H FOUNDATION AND SLAB ON GRADE PLAN - AREA C EL-1.3 LIGHTING - FIRST FLOOR AREA C
C-7.06H STORMWATER MANAGEMENT FACILITY 3 S-1.4H PENTHOUSE FLOOR AND LOW ROOF FRAMING PLAN - AREA EL-1.4 LIGHTING - SECOND FLOOR AREA B
C-7.07H STORMWATER MANAGEMENT FACILITY 4 A EL-1.5 LIGHTING - SECOND FLOOR AREA C
C-7.08H STORMWATER MANAGEMENT DETAILS S-1.5H 2ND FLOOR AND LOW ROOF FRAMING PLAN - AREA B EL-1.6 LIGHTING - MECHANICAL ROOMS
C-7.09H STORMWATER MANAGEMENT NOTES S-1.6H 2ND FLOOR AND PENTHOUSE FLOOR FRAMING PLAN - EL-2.0 LIGHTING FIXTURE SCHEDULE
J C-8.00H PHASE 1 SITE PLAN AREA C ELECTRICAL LIGHTING DEMO J
C-8.01H PHASE 2 SITE PLAN S-1.7H ROOF FRAMING PLAN - AREA A ED-1.1 PARTIAL DEMOLITION PLANS
C-9.00H TITLE SHEET S-1.8H ROOF FRAMING PLAN - AREA B
C-9.01H CARDIFF AVENUE ROAD PLAN S-1.9H ROOF FRAMING PLAN - AREA C ELECTRICAL
C-9.02H DANVILLE AVENUE ROAD PLAN S-3.1H TYPICAL DETAILS E-0.1H ELECTRICAL GENERAL NOTES, SYMBOLS & ABBREVATIONS
C-9.03H STREET LIGHT PLAN S-3.2H TYPICAL DETAILS E-0.2H ELECTRICAL SITE PLAN- POWER
C-9.04H WATER METER PLAN S-3.3H TYPICAL DETAILS E-2.1H PARTIAL FIRST FLOOR POWER PLAN – AREA A
S-3.4H TYPICAL DETAILS E-2.2 PARTIAL FIRST FLOOR POWER PLAN – AREA B
LANDSCAPE S-3.5H TYPICAL DETAILS E-2.3 PARTIAL FIRST FLOOR POWER PLAN – AREA C
F-1.00H FOREST CONSERVATION PLAN S-4.1H SECTIONS E-2.4 PARTIAL SECOND FLOOR POWER PLAN – AREA B
H S-4.2H SECTIONS H

www.grimmandparker.com
L-0.01H ABBREVIATIONS, GENERAL NOTES, SYMBOLS, MATERIALS, E-2.5 PARTIAL SECOND FLOOR POWER PLAN – AREA C
AND VICINITY PLAN S-5.1H SECTIONS E-2.6 ROOF POWER PLAN

11720 Beltsville Drive

Calverton, MD 20705
L-1.01H LANDSCAPE PLAN S-5.2H SECTIONS E-3.1H PARTIAL FIRST FLOOR FIRE ALARM PLAN – AREA A

Tel: 301.595.1000
L-1.02H PLANTING PLAN S-5.3H SECTIONS E-3.2 PARTIAL FIRST FLOOR FIRE ALARM PLAN – AREA B
L-2.00H ENLARGED LANDSCAPE PLANS S-5.4H SECTIONS E-3.3 PARTIAL FIRST FLOOR FIRE ALARM PLAN – AREA C
L-2.01H ENLARGED PLANTING PLANS E-3.4 PARTIAL SECOND FLOOR FIRE ALARM PLAN – AREA B

Suite 600
L-2.02H ENLARGED GATE PLANS MECHANICAL E-3.5 PARTIAL SECOND FLOOR FIRE ALARM PLAN – AREA C
L-2.03H ENLARGED STAIR PLANS, AND STAIR DETAILS M-0.1H MECHANICAL LEGEND E-4.1H ELECTRICAL ENLARGED PLANS
L-2.04H ENLARGED STAIR PLANS, AND STAIR DETAILS M-1.1 AIR DISTRIBUTION - FIRST FLOOR AREA A E-4.2 KITCHEN EQUIPMENT ENLARGED PLANS
L-2.05H STAIR DETAILS M-1.2 AIR DISTRIBUTION - FIRST FLOOR AREA B E-5.1H ELECTRICAL POWER RISER DIAGRAM
L-3.00H RETAINING WALL ELEVATIONS M-1.3 AIR DISTRIBUTION - FIRST FLOOR AREA C
G L-3.01H RETAINING WALL ELEVATIONS AND ENCLOSURE TYPES
E-5.2 FIRE ALARM RISER DIAGRAM G
M-1.4 AIR DISTRIBUTION - SECOND FLOOR AREA B E-5.3H FIRE ALARM ANNUNICATOR PANEL
L-3.02H GATE ELEVATIONS M-1.5 AIR DISTRIBUTION - SECOND FLOOR AREA C E-6.1H ELECTRICAL SCHEDULES
L-3.03H ENCLOSURE SECTIONS M-2.1 HYDRONIC DESIGN - FIRST FLOOR AREA A E-6.2H ELECTRICAL SCHEDULES
L-4.00H DETAILS M-2.2 HYDRONIC DESIGN - FIRST FLOOR AREA B E-6.3H ELECTRICAL SCHEDULES
L-4.01H PLANTING DETAILS M-2.3 HYDRONIC DESIGN - FIRST FLOOR - AREA C E-6.4H ELECTRICAL SCHEDULES
M-2.4 HYDRONIC DESIGN - SECOND FLOOR AREA B E-6.5H ELECTRICAL SCHEDULES
ARCHITECTURAL M-2.5 HYDRONIC DESIGN - SECOND FLOOR AREA C E-7.1 ELECTRICAL DETAILS
A-0.1H PHASING PLAN M-3.0 MECHANICAL ROOF PLAN E-8.1H ROOF LIGHTNING PROTECTION SYSTEM PLAN
A-0.2H CODE STUDY - GROUND AND FIRST FLOOR M-4.0 ENLARGED PLANS E-8.2H LIGHTINING PROTECTION DETAILS
A-0.3H CODE STUDY - SECOND FLOOR M-4.1 ENLARGED PLANS ED-0.3H ELECTRICAL PARTIAL PLAN - DEMOLITION
F A-0.4H SELECTIVE DEMOLITION PLAN M-4.2 ENLARGED PLANS
F
ED-0.4H ELECTRICAL OVERALL PLAN - DEMOLITION
A-0.5 OVERALL PLAN - FIRST FLOOR M-4.3 ENLARGED PLANS
A-0.6 OVERALL PLAN - SECOND FLOOR M-4.4 ENLARGED PLANS TECHNOLOGY
A-0.8 ACOUSTICAL ATTENUATION DIAGRAMS M-4.5 ENLARGED PLANS T-0.0 TECHNOLOGY SYMBOLS & NOTES GP# 21553
A-1.1 PARTIAL FIRST FLOOR PLAN - AREA A M-4.6 ENLARGED PLANS T-0.1 OVERALL PLAN - FIRST FLOOR
A-1.2 PARTIAL FIRST FLOOR PLAN - AREA B M-4.7 ENLARGED PLANS T-0.2 OVERALL PLAN - SECOND FLOOR
A-1.3 PARTIAL FIRST FLOOR PLAN - AREA C M-4.8 ENLARGED PLANS T-1.0H HOLABIRD SITE PLAN
A-1.4 PARTIAL SECOND FLOOR PLAN - AREA A M-4.9 ENLARGED PLANS T-1.1 PARTIAL FIRST FLOOR PLAN - AREA A
A-1.5 PARTIAL SECOND FLOOR PLAN - AREA B M-5.0 SECTIONS & ISOMETRICS T-1.2 PARTIAL FIRST FLOOR PLAN - AREA B
A-1.6 PARTIAL SECOND FLOOR PLAN - AREA C M-5.1 SECTIONS & ISOMETRICS T-1.3 PARTIAL FIRST FLOOR PLAN - AREA C
E A-1.7 ROOF PLAN M-5.2 SECTIONS & ISOMETRICS T-1.4 PARTIAL SECOND FLOOR PLAN - AREA A
E
A-1.8 ROOF PLAN - PHOTOVOLTAIC ARRAY M-5.3 SECTIONS & ISOMETRICS T-1.5 PARTIAL SECOND FLOOR PLAN - AREA B
A-1.9 ROOF DETAILS M-5.4 SECTIONS & ISOMETRICS T-1.6 PARTIAL SECOND FLOOR PLAN - AREA C
A-1.10 ROOF DETAILS M-5.5 SECTIONS & ISOMETRICS T-5.0 MAIN TELECOM ROOM DETAILS
A-1.11 ENTRY CANOPY DETAILS M-5.6 SECTIONS & ISOMETRICS T-5.1 TELECOM ROOM DETAILS
A-2.1H ELEVATIONS M-6.0 SCHEMATICS T-5.2 PATHWAY DETAILS
A-2.2H ELEVATIONS M-6.1 SCHEMATICS T-5.3 INTERCOM & CLOCK SYSTEM DETAILS
A-2.3H ELEVATIONS M-7.0 MECHANICAL DETAILS T-5.4 GYMNASIUM SOUND SYSTEM DETAILS

CITY OF BALTIMORE, MARYLAND


A-2.4H ELEVATIONS M-7.1 MECHANICAL DETAILS T-5.5 CAFETERIA AV SYSTEM DETAILS
A-3.1 FINISH SCHEDULE M-7.2 MECHANICAL DETAILS T-5.6 MUSIC ROOM SOUND SYSTEMS
D A-3.2 DOOR SCHEDULE M-7.3 MECHANICAL DETAILS D

HOLABIRD ACADEMY PK-8


A-3.3 HEAD, SILL AND JAMB DETAILS M-8.0 CONTROL SCHEMATICS SECURITY
A-3.6 FRAMING ELEVATIONS - CURTAINWALL M-8.1 CONTROL SCHEMATICS TY-0.0 SECURITY NOTES & SYMBOLS
A-3.7 FRAME ELEVATIONS - HM, STOREFRONT AND LOUVERS M-8.2 CONTROL SCHEMATICS TY-1.1 PARTIAL FIRST FLOOR SECURITY PLAN - AREA A
A-3.8 STOREFRONT DETAILS M-8.3 CONTROL SCHEMATICS TY-1.2 PARTIAL FIRST FLOOR SECURITY PLAN - AREA B

LIST OF DRAWINGS
A-3.20 WALL TYPES AND WALL TERMINATION DETAILS M-9.1 HVAC CONTROLS - FIRST FLOOR AREA A TY-1.3 PARTIAL FIRST FLOOR SECURITY PLAN - AREA C
A-4.1 BUILDING SECTIONS M-9.2 HVAC CONTORLS - FIRST FLOOR AREA B TY-1.4 PARTIAL SECOND FLOOR SECURITY PLAN - AREA A
A-4.2 BUILDING SECTIONS M-9.3 HVAC CONTORLS - FIRST FLOOR AREA C TY-1.5 PARTIAL SECOND FLOOR SECURITY PLAN - AREA B
A-4.2a BUILDING SECTIONS M-9.4 HVAC CONTORLS - SECOND FLOOR AREA B TY-1.6 PARTIAL SECOND FLOOR SECURITY PLAN - AREA C
A-4.3 WALL SECTIONS M-9.5 HVAC CONTORLS - SECOND FLOOR AREA C TY-5.0 ACCESS CONTROL & INTRUSION DETECTION SYSTEMS
C A-4.4 WALL SECTIONS - GYM & COMMUNITY AREA M-10.0 MECHANICAL SCHEDULES TY-5.1 CCTV SYSTEM C
A-4.5 WALL SECTIONS - ENTRY VESTIBULE M-10.1 MECHANICAL SCHEDULES
A-4.6 WALL SECTIONS -CORRIDOR AND VESTIBULE M-11.0 MECHANICAL CALCULATIONS PHOTOVOLTAICS
A-4.7 WALL SECTIONS - MEDIA AND CENTRAL MECH. ROOM M-12.0 MEMA / EMERGENCY EQUIPMENT W-0.1 PHOTOVOLTAICS - DETAILS & LEGEND
A-4.8 WALL SECTIONS - CLASSROOM WING MD-1.1 PARTIAL DEMOLITION PLANS W-0.2 PHOTOVOLTAICS - SCHEDULES
A-4.9 WALL SECTIONS - CLASSROOM WING MECHANICAL SITE UTILITIES W-1.1A PHOTOVOLTAICS - ROOF AREA A DATE DESCRIPTION
A-5.1 ENLARGED STAIR PLANS AND SECTIONS UM-1.0 MECHANICAL UTILITIES W-1.1B PHOTOVOLTAICS - ROOF AREA B & C
A-5.2 ENLARGED STAIR PLANS AND SECTIONS H C
A-5.3 ENLARGED STAIR PLANS AND SECTIONS W-2.0 PHOTOVOLTAICS - FLOOR PLANS
A-5.4 STAIR DETAILS AND ELEVATOR PLANS AND SECTION PLUMBING
A-5.5 ENLARGED TOILET PLANS P-0.1H PLUMBING GENERAL NOTES, SYMBOLS & ABBREVATIONS
B B
A-5.6 ENLARGED PLAN DETAILS P-1.1H PLUMBING PARTIAL FIRST FLOOR PLAN – AREA A
A-5.10 TYPICAL DETAILS P-1.2H PLUMBING PARTIAL FIRST FLOOR PLAN – AREA B
A-6.1 INTERIOR ELEVATIONS P-1.3H PLUMBING PARTIAL FIRST FLOOR PLAN – AREA C
A-6.2 INTERIOR ELEVATIONS P-1.4 PLUMBING PARTIAL SECOND FLOOR PLAN - AREA A
A-6.3 INTERIOR ELEVATIONS P-1.5 PLUMBING PARTIAL SECOND FLOOR PLAN – AREA B
A-6.4
A-6.5
INTERIOR ELEVATIONS
INTERIOR ELEVATIONS
P-1.6 PLUMBING PARTIAL SECOND FLOOR PLAN – AREA C
P-1.7H PLUMBING PARTIAL ROOF PLAN - AREA A TS-2H
A-7.1 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN - AREA A P-1.8 PLUMBING PARTIAL ROOF PLAN – AREA B 03/13/2017
A-7.2 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN - AREA B P-1.9 PLUMBING PARTIAL ROOF PLAN – AREA C BID SET
P-4.1 PLUMBING ENLARGED PLANS
A © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

TRANSFORMER TO BE DEMOLISHED IN PHASE 2 TRANSFORMER TO BE DEMOLISHED IN PHASE 2 TRANSFORMER TO BE DEMOLISHED IN PHASE 2

M M

L PHASE 1A L

REF.

REF.
UP UP
UP UP
DEMOLITION
A7
A-0.4H

UP

UP

K K

FE FE

UP UP

FE

FE
PHASE 1
PHASE 2 NEW CONSTRUCTION
J WD WD J
DEMOLITION
EXISTING MODULAR
REF.

REF.
TO BE DEMOLISHED

REF.

REF.
REF. REF.

UP UP

H H

www.grimmandparker.com
PHASE 1A

11720 Beltsville Drive

Calverton, MD 20705
DEMOLITION

Tel: 301.595.1000
REF. REF.

Suite 600
REF.

REF.
FDC FDC

G PHASE 2 PHASE 1 PHASE 2 PHASE 1 PHASE 2 PHASE 1 G


REFER TO CIVIL DRAWINGS FOR
EXTENT OF SITE PHASING WORK
REFER TO CIVIL DRAWINGS FOR REFER TO CIVIL DRAWINGS FOR
EXTENT OF SITE PHASING WORK EXTENT OF SITE PHASING WORK

PHASE 2 - DEMOLITION PHASE 1B - NEW CONSTRUCTION PHASE 1A - DEMOLITON


F18 1" = 30'-0" F11 1" = 30'-0" F5 1" = 30'-0"

F F
TRANSFORMER TO BE DEMOLISHED IN PHASE 2

8' - 4 1/4"
GP# 21553

E E

PHASE 1

REF.
UP UP
DEMOLITION

CITY OF BALTIMORE, MARYLAND


D D

HOLABIRD ACADEMY PK-8


40' - 6"

UP
FE
DEMOLITION KEY PLAN

PHASING PLAN
FE
PHASE 2 PHASE 1 PORTION OF EXISTING
SCHOOL TO BE REMOVED
DEMOLITION
WD NEW CONSTRUCTION
C C

REF.

REF.
REF.

UP
DATE DESCRIPTION

PHASE 1
DEMOLITION EXISTING NEW
B REF. SCHOOL
TO REMAIN
SCHOOL
B

REF.
FDC

EXISTING
MODULAR
PHASE 2 PHASE 1
REFER TO CIVIL DRAWINGS FOR
EXTENT OF SITE PHASING WORK PHASE 2 PHASE 1 TO BE REMOVED
SEE CIVIL DWGS. A-0.1H
OVERALL PHASING PLAN 03/13/2017
A9 1" = 40'-0"
BID SET
A N © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

CODE REVIEW
FIRE ZONE 1 - FIRST FLOOR OCCUPANCY SUMMARY FIRE ZONE 1 - FIRST FLOOR OCCUPANCY SUMMARY FIRE ZONE 1 - FIRST FLOOR OCCUPANCY SUMMARY FIRE ZONE 2 - FIRST FLOOR OCCUPANCY SUMMARY
AREA AREA PER GROSS OR OCCUPANCY EGRESS AREA AREA PER GROSS OR OCCUPANCY EGRESS AREA AREA PER GROSS OR OCCUPANCY EGRESS AREA AREA PER GROSS OR OCCUPANCY EGRESS PROJECT NAME AND LOCATION
(SF) OCCUPANT (SF) NET LOAD WIDTH REQ'D (SF) OCCUPANT (SF) NET LOAD WIDTH REQ'D (SF) OCCUPANT (SF) NET LOAD WIDTH REQ'D (SF) OCCUPANT (SF) NET LOAD WIDTH REQ'D NAME HOLABIRD ACADEMY ELEMENTARY MIDDLE SCHOOL #229
AREA NAME AREA NAME AREA NAME AREA NAME
STREET ADDRESS 1500 IMLA STREET
ACCESSORY STORAGE / MECHANICAL EQUIPMENT ASSEMBLY (CONCENTRATED) 51 10.3
STORAGE 148 SF 300 SF GROSS 0 0.1 COMMUNITY CENTER 1175 SF 7 SF NET 168 33.6 EDUCATIONAL (VOCATIONAL) ACCESSORY STORAGE / MECHANICAL EQUIPMENT COUNTY --
OUTDOOR STORAGE 88 SF 300 SF GROSS 0 0.1 GYM 5929 SF 7 SF NET 847 169.4 MUSIC 845 SF 50 SF NET 17 3.4 ELEC 79 SF 300 SF GROSS 0 0.1 CITY, STATE BALTIMORE, MARYLAND
MECH 110 SF 300 SF GROSS 0 0.1 DINING 2525 SF 7 SF NET 361 72.1 MUSIC 987 SF 50 SF NET 20 3.9 TELECOM/ UTILITY 183 SF 300 SF GROSS 1 0.1
STORAGE 95 SF 300 SF GROSS 0 0.1 1376 275.1 PLATFORM 849 SF 50 SF NET 17 3.4 MECH 65 SF 300 SF GROSS 0 0.0 PROJECT DESCRIPTION: NEW ELEMENTARY SCHOOL, THREE-STORY
ELEC 94 SF 300 SF GROSS 0 0.1 ASSEMBLY (UN-CONCENTRATED) 54 10.7 STORAGE 248 SF 300 SF GROSS 1 0.2
M STORAGE 116 SF 300 SF GROSS 0 0.1 CONFERENCE 318 SF 15 SF NET 21 4.2 KITCHEN STORAGE 79 SF 300 SF GROSS 0 0.1 APPLICABLE CODES M
LAUNDRY 85 SF 300 SF GROSS 0 0.1 CONFERENCE 257 SF 15 SF NET 17 3.4 KITCHEN 1759 SF 100 SF GROSS 18 3.5 STORAGE 71 SF 300 SF GROSS 0 0.0 Building Code: INTERNATIONAL BUILDING CODE 2015
FURN. STORAGE 202 SF 300 SF GROSS 1 0.1 CONFERENCE 404 SF 15 SF NET 27 5.4 18 3.5 STORAGE 240 SF 300 SF GROSS 1 0.2 Fire Code: NFPA 101 LIFE SAFETY CODE 2015
PANTRY 96 SF 300 SF GROSS 0 0.1 WAITING 273 SF 15 SF NET 18 3.6 LIBRARY (READING) MECH 64 SF 300 SF GROSS 0 0.0 Accessibility: AMERICANS WITH DISABILITY ACT ACCESSIBILITY GUIDELINES (ADAAG) AND
STORAGE 335 SF 300 SF GROSS 1 0.2 83 16.7 MEDIA CENTER 2031 SF 50 SF NET 41 8.1 KILN 98 SF 300 SF GROSS 0 0.1 MARYLAND ACCESSIBILITY CODE (COMAR.05.02.02 REV. 20002)
STORAGE 148 SF 300 SF GROSS 0 0.1 BUSINESS AREAS 41 8.1 STORAGE 142 SF 300 SF GROSS 0 0.1 BUILDING USE AND CONSTRUCTION CLASSIFICATIONS
FIRE PUMP SVC. 106 SF 300 SF GROSS 0 0.1 WORKROOM 186 SF 100 SF GROSS 2 0.4 LOCKER ROOMS MECH 64 SF 300 SF GROSS 0 0.0 IBC Code Fire Code
PANTRY 112 SF 300 SF GROSS 0 0.1 GUIDANCE OFFICES 1055 SF 100 SF GROSS 11 2.1 LOCKER ROOM 251 SF 50 SF GROSS 5 1.0 MECH 73 SF 300 SF GROSS 0 0.0 Use Group: E EDUCATIONAL 305.1 6.1.3
PLATFORM STORAGE 108 SF 300 SF GROSS 0 0.1 HEALTH 905 SF 100 SF GROSS 9 1.8 LOCKER ROOM 251 SF 50 SF GROSS 5 1.0 5 0.9
Building Area:
ELEC 287 SF 300 SF GROSS 1 0.2 WORKROOM 155 SF 100 SF GROSS 2 0.3 LOCKER ROOM 57 SF 50 SF GROSS 1 0.2 BUSINESS AREAS
MECH BASEMENT 1015 SF
ELEC 77 SF 300 SF GROSS 0 0.1 ADMIN OFFICES 1247 SF 100 SF GROSS 12 2.5 LOCKERS 93 SF 50 SF GROSS 2 0.4 RESOURCE 254 SF 100 SF GROSS 3 0.5
FIRST FLOOR 61994 SF
OUTDOOR STORAGE 86 SF 300 SF GROSS 0 0.1 COMMUNITY OFFICES 746 SF 100 SF GROSS 7 1.5 LOCKER ROOM 140 SF 50 SF GROSS 3 0.6 PLANNING 247 SF 100 SF GROSS 2 0.5
SECOND FLOOR 31323 SF
CAN WASH 46 SF 300 SF GROSS 0 0.0 FAMILY RESOURCE 278 SF 100 SF GROSS 3 0.6 16 3.2 FACULTY LOUNGE 404 SF 100 SF GROSS 4 0.8
Grand total 94332 SF
STORAGE 28 SF 300 SF GROSS 0 0.0 OFFICE 113 SF 100 SF GROSS 1 0.2 TOILET OFFICE 207 SF 100 SF GROSS 2 0.4
L HEAD END 221 SF 300 SF GROSS 1 0.1 STORAGE 91 SF 100 SF GROSS 1 0.2 PERSONAL CARE 98 SF 0 SF OFFICE 132 SF 100 SF GROSS 1 0.3 Proposed Type of Construction: IBC TYPE IIB L
CENTRAL STORAGE 169 SF 300 SF GROSS 1 0.1 OFFICE 79 SF 100 SF GROSS 1 0.2 0 0.0 PLANNING 254 SF 100 SF GROSS 3 0.5 Allowable Building Height: 55'+20' (IBC TABLE 504.3, TABLE 504.4)=75' (MAX ALLOWABLE PER IBC 504.4), 3 Stories
WATER SVC. 124 SF 300 SF GROSS 0 0.1 OFFICE 80 SF 100 SF GROSS 1 0.2 Grand total 1648 329.7 RESOURCE 240 SF 100 SF GROSS 2 0.5 Actual Building Height: 48' MAXIMUM
RECIEVING 194 SF 300 SF GROSS 1 0.1 OFFICE 101 SF 100 SF GROSS 1 0.2 OFFICE/ STOR 268 SF 100 SF GROSS 3 0.5
10 2.0 SECURITY OFFICE 92 SF 100 SF GROSS 1 0.2 20 4.0
OCCUPANCY LOADS AND EGRESS REQUIREMENTS
EDUCATIONAL (CLASSROOM)

FIRE ZONE 2 CLASSROOM 872 SF 20 SF NET 44 8.7

210

210
CLASSROOM 872 SF 20 SF NET 44 8.7 Area in Sq. Ft. per Occupant Egress Width Egress Width Number Exits Number Exits
CLASSROOM 939 SF 20 SF NET 47 9.4 Location Calculated Sq. Ft. Person Load Required Provided Required Provided

32"

42"

32"

42"
CLASSROOM 889 SF 20 SF NET 44 8.9 GYMNASIUM 5929 7 849 172" 272" 3 3

49
CLASSROOM 870 SF 20 SF NET 44 8.7 MEDIA CENTER 2031 50 41 32" 72" 2 2

210

47
CLASSROOM 870 SF 20 SF NET 44 8.7 DINING 2523 7* 361 72" 136" 2 2
10' - 0"

10' - 0"
CLASSROOM 884 SF 20 SF NET 44 8.8

32"

42"
KILN CLASSROOM 847 20 43 32" 33" 1 1
K CLASSROOM
CLASSROOM
98 SF CLASSROOM 968 SF 20 SF NET 48 9.7 K
TECH LAB 878 50 18 32" 33" 1 1

49
872 SF CLASSROOM 999 SF 20 SF NET 50 10.0
872 SF 0 OFFICE/ STOR CLASSROOM
6' - 2" CLASSROOM 943 SF 20 SF NET 47 9.4 MUSIC 912 50 46 32" 33" 1 1
44 268 SF
44 943 SF CLASSROOM 943 SF 20 SF NET 47 9.4

390
TECH LAB 3
CLASSROOM ART LAB 47 CLASSROOM 971 SF 20 SF NET 49 9.7 FIRE PROTECTION SYSTEM REQUIREMENTS
878 SF CLASSROOM CLASSROOM
DN 941 SF CLASSROOM 968 SF 20 SF NET 48 9.7 System IBC Code Fire Code
939 SF 999 SF

68"

78"
18 943 SF
MECH STORAGE 19 COLLABORATIVE 834 SF 20 SF NET 42 8.3 Automatic Sprinklers YES 903.2.3 9.7
29' - 6"

47 50 47 LEARNING

338
73 SF 142 SF Fire Alarm System YES 907.2.3 9.6, 14.3.4
COLLABORATIVE 870 SF 20 SF NET 43 8.7
0 0 LEARNING Smoke Detection System NO -- 9.6.2.9
UP 685 136.9 Partial Smoke Detection YES -- 9.6.5.2 (1)
UP 66" MECH MECH 32" Location DOORS WITH HOLD -- --
FIRE ZONE 2

FIRE ZONE 2
330 270 64 SF 3 330 EDUCATIONAL (VOCATIONAL)
54" 64 SF OPEN DEVICES
66" ART LAB 941 SF 50 SF NET 19 3.8
0 0 TECH LAB 878 SF 50 SF NET 18 3.5 INTERIOR FINISH REQUIREMENTS
MAX TRAVEL DISTANCE 134' -4"

10' - 0"

10' - 0"
J 12' - 9 1/2" COLLABORATIVE LEARNING 36 7.3 Per IBC Table 803.11 & NFPA 14.3.3.2, 14.3.3.3 J
870 SF COLLABORATIVE LEARNING 1 HR FIRE RATING Grand total 746 149.1
1 HR FIRE 834 SF
1 HR FIRE RATING 43 5' - 4" RATING AT TRAVEL DISTANCE TO EXITS
42
FIRE ZONE 2

FEC
RESOURCE TELECOM/ UTILITY ELEVATOR IBC Code Fire Code
PLANNING STORAGE RESOURCE
THIS AREA TO BE UTILIZED BY 254 SF ELEC PLANNING 183 SF 6' - 8" Maximum Length of Travel in Fully Sprinklered Building 250' (Table 1017.2) 200' (14.2.6.3)
254 SF 240 SF 240 SF
OCCUPANTS IN SURROUNDING 79 SF 247 SF
3 1 3 1 OCCUPANCY 1,546 Maximum Length Common Path of Travel in Fully Sprinklered Building 75' (Table 1006.2.1) 100' (14.2.5.3.1)
CLASSROOMS AND DOES NOT FEC 0 2 FEC
2 USE GROUP E Spaces with One Means of Egress, Maximum Travel Distance to an Exit
CONTRIBUTE TO OCCUPANCY STORAGE 75' (Table 1006.2.1) 75' (14.2.5.5 (2))
CONSTRUCTION TYPE II-B Access Door

450
79 SF NUMBER OF STORIES 3
MECH
0 MINIMUM CORRIDOR WIDTH REQUIREMENTS
65 SF

68"

90"
OFFICE BASEMENT FLOOR 1,023 SF
0 132 SF FIRST FLOOR 27,628 SF Width IBC Code Fire Code
SECOND FLOOR 26,373 SF
338
UP CLASSROOM 6 FT., EXIT CORRIDOR Table 1020.2 14-2.3.2
1 CLASSROOM CLASSROOM TOTAL BUILDING AREA 54,024 SF
UP CLASSROOM 968 SF 44 IN., CLR. STAIR WIDTH 1011.2 7.2.2.2.1.2, 7.3.4
968 SF 971 SF
H H

www.grimmandparker.com
CLASSROOM CLASSROOM OFFICE 884 SF 48 ALLOWABLE AREA PER STORY 43,500 SF (TABLE 506.2)
STORAGE 2 HR FIRE RATING 48 49
870 SF 889 SF 207 SF % INCREASE FOR ACCESS: 38.86% 5,635 SF (506.3) PANIC HARDWARE
FACULTY LOUNGE 44

11720 Beltsville Drive


CLASSROOM 248 SF

Calverton, MD 20705
44 404 SF TOTAL ALLOWABLE AREA PER STORY 49,135 SF Per IBC Code 1010.1.10 & NFPA 7.2.1.7, 14.2.2.2.2
44 2
870 SF 1

Tel: 301.595.1000
4 TOTAL ALLOWABLE BUILDING AREA 98,263 SF ALL DOORS SERVING MORE THAN 50 & AT SMOKE BARRIER DOORS
44

48
STORAGE

48
48
450

71 SF EMERGENCY LIGHTING REQUIREMENTS

32"

42"

32"

42"
32"

42"
0
55"

90"

Per IBC Code 1008 & NFPA 7.9, 14.2.9


32"

Suite 600
165 17 ALL MEANS OF EGRESS

210
WORKROOM

210
210
MAX TRAVEL DISTANCE 123'-2"
272

2 HR FIREWALL
186 SF
2
33"

MUSIC
MAX TRAVEL DISTANCE 125'-8" FIRE ZONE 1 FIRE RATING REQUIREMENTS- STRUCTURAL ELEMENTS/ EGRESS COMPONENTS
101' - 4 1/256" 2 HR RATED CURTAINWALL SYSTEM UL ASSEMBLY THIS AREA TO BE UTILIZED BY OCCUPANCY 1,722 Rating Required IBC Code Fire Code
2 HR RATED CURTAINWALL SYSTEM 845 SF
2 HR FIREWALL DESIGN NO. U930 OCCUPANTS IN SURROUNDING USE GROUP E
2 HR FIRE WALL Exterior Bearing Walls 0 TABLE 601, TABLE 602 TABLE A.8.2.1.2
BUILDING FIRE SEPARATION LINE 17 2 HR RATING CLASSROOMS AND DOES NOT CONSTRUCTION TYPE II-B
10' - 10' - 0" NUMBER OF STORIES 2 Exterior Non-Bearing Walls 0 TABLE 602 TABLE A.8.2.1.2
G 0"
21
32"
165
BUILDING FIRE SEPARATION LINE CONCRETE BEARING WALL CONTRIBUTE TO OCCUPANCY
Fire Walls 2 TABLE 706.4 TABLE A.8.2.1.2 G
FIRST FLOOR 34,366 SF Interior Bearing Walls 0 TABLE 601 TABLE A.8.2.1.2
33"
STORAGE SECOND FLOOR 4,655 SF
148 SF TOTAL BUILDING AREA 39,021 SF PLUMBING CALCULATIONS Floor/ Ceiling Assemblies
Roof/ Ceiling Assemblies
0
0
TABLE 601
TABLE 601
TABLE A.8.2.1.2
TABLE A.8.2.1.2
0 ALLOWABLE AREA PER STORY 43,500 SF (TABLE 506.2)
PLANNED CAPACITY Columns 0 TABLE 601 TABLE A.8.2.1.2
% INCREASE FOR ACCESS: 45.00% 6,525 SF (506.3)
ALTERNATING TREAD STAIR, TOTAL ALLOWABLE AREA PER STORY 50,025 SF GENERAL SPACES Beams 0 TABLE 601 TABLE A.8.2.1.2
1 HR FIRE RATING UL ASSEMBLY
SECONDARY MEANS OF EGRESS DESIGN NO. U469 Egress Corridors 0 TABLE 1020.1 7.1.3.1, 14.3.6
MUSIC FROM SECOND FLOOR TOTAL ALLOWABLE BUILDING AREA 100,050 SF STUDENTS 604
1 HR RATED 1 HR RATING Shafts (Stairs) 1 1023.2 7.1.3.2.1
987 SF MECHANICAL ROOM CEILING ASSEMBLY CEILING ASSEMBLY STAFF 87 Shafts Other than Stairs 1 713.4 8.6.5
MAX TRAVEL DISTANCE 150' -4"

MEDIA CENTER 20 CONSTRUCTION


Corridor Doors 0 716.5.3, Table 1020.1 14.3.6
32" 2031 SF 32"
330 20 LOCKERS FIRE PUMP SVC. 32" MINIMUM FIXTURE COUNT REQUIREMENTS BY STATE RATED PLANNED CAPACITY Smoke Barrier 1 709.3 8.5
165 22 41 WATER SVC. 1 165
33" 66" 93 SF 106 SF Smoke Partitions 0 710.3 8.4, 14.3.7, 14.3.6 (2)(a)
124 SF 33" 2 HR FIRE RATING
F OUTDOOR STORAGE 32" 2
0 0 2 HR RATED SPACES TOTALS
Smoke Barrier Doors 20 MIN. 710.5.2, 716.5.3 8.5 F
5' - 0"

165

88 SF 165 0
FEC 33" ELEC CEILING ASSEMBLY SPACE TYPE STUDENTS STAFF REQUIRED PROVIDED Mixed Use Separation 1 or Auto Fire Extinguishing System 508, TABLE 508.4 --
CONFERENCE
0 318 SF PLATFORM STORAGE ELEC 287 SF
32"

33"

UL ASSEMBLY USE GROUP E B EGRESS WIDTH


1HR RATING 108 SF 77 SF 1
OUTDOOR STORAGE
21 NOT INCLUDED PER IBC 410.5.1
0
5' - 0" DESIGN NO. U438
USOCCUPANCY 604 87 691
Width IBC Code Fire Code
GP# 21553
0

IN OVERALL 0 2 HR RATING
86 SF 32" CENTRAL STORAGE CEILING ASSEMBLY
33 165 BLDG COUNT PLATFORM FE MALE/ FEMALE RATIO MALE FEMALE MALE FEMALE MALE FEMALE MALE FEMALE UNISEX Egress width at stairs .3"/OCC. (1005.3.1) .3"/OCC. (TABLE 7.3.3.1)
0 169 SF CONSTRUCTION
33" 849 SF
HEAD END FURN. STORAGE RECIEVING 32" 302 302 44 44 346 346 346 346
221 SF 11' - 11 1/4" 17 1 194 SF 6 330
202 SF FIXTURE REQUIREMENTS
UP 66"
STORAGE 1 1 LOCKER ROOM 1 Egress width at doors and corridors .15"/OCC. (1005.3.2, Exception 1) .2"/OCC.(TABLE 7.3.3.1)
WATER CLOSETS (1 PER/#) 50 50 25 25
95 SF 57 SF OFFICE Fire Code
37" URINALS 50% OF WC COUNT 50% OF WC 50% OF WC
0 330 181 1 101 SF
MECH OFFICE NUMBER OF REMOTE EXITS REQUIRED
66" 80 SF 1 LAVATORIES 100 100 40 40
GUIDANCE OFFICES 110 SF
E 1055 SF 0 REMOTENESS OF 1
STORAGECAN WASH
28 SF 46 SF DRINKING FOUNTAINS 100 100
By Room IBC Code Fire Code E
FE

EXITS > 1/3 ROOM


11 ELEC 0 0 CALCULATIONS Rooms Less Than 50 Occupants 1 Exit (Table 1006.2.1) --
DIAGONAL
94 SF Rooms with 50 - 500 Occupants 2 Exits (1006.2.1) --

CODE STUDY - GROUND AND FIRST FLOOR


FIRE ZONE 1

FIRE ZONE 1
DINING WATER CLOSETS 4 7 1 2 5 9 8 13 28 Rooms with 501 - 1000 Occupants 3 Exits (1006.2.1.1) --
0 Rooms with More than 1000 Occupants 4 Exits (1006.2.1.1) --
2525 SF URINALS 4 - 1 - 5 - 6 -
STORAGE 361 KITCHEN
40' - 0"

LAVATORIES 4 4 2 2 6 6 9 9 28 By Story IBC Code Fire Code


LAUNDRY PERSONAL CARE
/8"

116 SF 1759 SF
95

225

85 SF 98 SF DRINKING FOUNTAINS 7 1 8 36
'-

0 1 - 500 Occupants 2 Exits (Table 1006.3.1) 2 Exits, 14.2.4


70

18
0 32" 501 - 1000 Occupants 3 Exits (Table 1006.3.1) 3 Exits, 7.4.1.2
32"

45"

0 165 More than 1000 Occupants 4 Exits (Table 1006.3.1) 4 Exits, 7.4.1.2
NOTES:

CITY OF BALTIMORE, MARYLAND


33"
8' - 8 1/2"
1. THE TABLE ABOVE TABULATES MINIMUM FIXTURE REQUIREMENTS FOR THE PROPOSED SCHOOL BASED ON PLANNED MAXIMUM SCHOOL
21

REMOTENESS OF EXITS
STORAGE CAPACITY.
MAX TRAVEL DISTANCE 107' -1" OFFICE STORAGE STORAGE 2. PLUMBING FIXTURE CALCULATIONS ARE PER IPC 2012, 403.1 Life Safety A.7.5.1.3.3 - 1/3 the Length of Maximum Room Diagonal (Credit for Sprinklered Building)
PANTRY 335 SF
D ADMIN OFFICES 37" 112 SF 79 SF 91 SF 148 SF
1
3.
4.
THE CALCULATIONS ASSUME THAT DURING SCHOOL DAY THAT THE SCHOOL IS OCCUPIED ONLY BY STUDENTS AND STAFF.
CALCULATIONS ASSUME THAT STUDENTS AND STAFF WILL BE EVENLY DISTRIBUTED ON ALL FLOORS.
IBC 1007.1.1 Exception 2 - 1/3 the Length of Maximum Room Diagonal (Credit for Sprinklered Building) D
32" 330 181

HOLABIRD ACADEMY PK-8


1247 SF HEALTH 0 1 1 0 5. PROVIDED DRINKING FOUNTAIN CALCULATION IS BASED ON NUMBER OF WATER FOUNTAIN IN CORRIDORS PLUS THE NUMBER OF BUBBLERS FOR
9 165 66"
905 SF 33" DRINKING WATER PROVIDED AT THE SINKS IN CLASSROOMS MAXIMUM DEAD END DISTANCES
12
FEC

WORKROOM 43"
10' - 0 5/8"
308

9 85" IBC Code Fire Code


155 SF 219 330
308

450 424
2 90" 66" 50 FT. (1020.4) Exception 2 50 FT. (14.2.5.2)
62"

66"

NOTES:
FIRE ZONE 2 - BASEMENT OCCUPANCY SUMMARY
62"

66"

OFFICE 1. Mixed use separation walls shall have 45 minute rated opening protectives.
330

WAITING SECURITY OFFICE 113 SF 2. All fire separation walls shall comply with Section 708.4 of the 2015 IBC Code. They shall extend from the top of the fire resistance rated
AREA AREA PER GROSS OR OCCUPANCY EGRESS
330

273 SF 92 SF floor/ ceiling assembly below to the underside of the floor or roof slab or deck above and shall be securely attached thereto.
1
1 AREA NAME (SF) OCCUPANT (SF) NET LOAD WIDTH REQ'D 3. All fire walls shall comply with Section 706 of the 2015 IBC Code.
CONFERENCE 18 GYM 4. Elevator shaft to be (2) hour rated - UL# U906.
257 SF 5929 SF 5. Exterior walls indicated to provide (1) hour rating (UL# U906) - At stairs and fire walls where exterior walls form an angle less than 180
ACCESSORY STORAGE / MECHANICAL EQUIPMENT
3' - 6 3/4"

32"
17 47 165 847 degrees, the exterior wall shall be rated at stairs per L.S. 7.2.2.5.2, and at fire walls per IBC 1023.7.
MECHANICAL BASEMENT 393 SF 300 SF GROSS 1 0.3
33" UP LOCKER ROOM 6. Stair enclosures are (1) hour rated, unless noted otherwise.
C 251 SF
3/4
"
Grand total
1
1
0.3
0.3
7. Refer to 1/8" plans & coord. w/ MEP drawings for chases thru floor shown thus enclosure wall around these floor opn'gs. shall be (1) hour
rated & shall extend from floor tight to deck above - pack w/ safing insulation rating shall be as follows:
C
5 '-2
45" 114 CMU - U.L. #U906
LOCKER ROOM Gyp. Bd. - Gypsum Assoc. assembly WP1110
330 221
8. Refer to sheet A-3.20 for wall termination details at rated walls.
66" 140 SF
9. Refer to the Door Schedule for doors with closers required.
3 1 HR RATING 10. All rated walls and partitions shall be permanently identified with signs or stenciling as follows:
45" MECHANICAL BASEMENT a. Identification markings shall be located in accessible concealed floor, floor-ceiling and attic spaces.
330 221 LOCKER ROOM
393 SF b. Identification markings shall be located within 15'-0" of the end of each wall and at intervals not exceeding 30'-0" measured
66" 251 SF DATE DESCRIPTION
horizontally along the wall or partiion.
5 FE 1 c. Lettering shall not be less than 3" in height with a minimum 3/8" stroke in contrasting color incorporating the following wording:
45" 44"
219 330 "FIRE AND/OR SMOKE BARRIER - PROTECT ALL OPENINGS".
330 221 11. No penetration of rated ceiling assemblies is allowed.
66" 66"
FEC FEC
FEC

B
COMMUNITY OFFICES
746 SF 165
32"

33"
5
4' - 0"
SYMBOL KEY B
7
PANTRY COMMUNITY CENTER ALLOWABLE # OCC.
96 SF 1175 SF REQ'D WIDTH
160

5' - 0" 0 168


FAMILY RESOURCE CONFERENCE 32"
42

404 SF 90 165
32"

33"

278 SF
33"
32"

33"

3 27
165

ACTUAL WIDTH

A-0.2H
165

FDC
ACTUAL # OCC.
MAX TRAVEL DISTANCE 111'-0"
2 HOUR CEILING ASSEMBLY
CODE STUDY PLAN - FIRST FLOOR MECHANICAL BASEMENT CODE STUDY PLAN 2 HOUR RATING
1 HOUR RATING
03/13/2017
A18 1/16" = 1'-0" A8 1/16" = 1'-0"
SMOKE PARTITION
NFPA 101 SECTION 14.3.6 EXCEPTION #2 1 HOUR CEILING ASSEMBLY
BID SET
A N © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

CODE REVIEW
FIRE ZONE 2 - SECOND FLOOR OCCUPANCY SUMMARY FIRE ZONE 2 - SECOND FLOOR OCCUPANCY SUMMARY FIRE ZONE 1 - SECOND FLOOR OCCUPANCY SUMMARY
PROJECT NAME AND LOCATION
AREA AREA PER GROSS OR OCCUPANCY EGRESS AREA AREA PER GROSS OR OCCUPANCY EGRESS AREA AREA PER GROSS OR OCCUPANCY EGRESS
NAME HOLABIRD ACADEMY ELEMENTARY MIDDLE SCHOOL #229
AREA NAME (SF) OCCUPANT (SF) NET LOAD WIDTH REQ'D AREA NAME (SF) OCCUPANT (SF) NET LOAD WIDTH REQ'D AREA NAME (SF) OCCUPANT (SF) NET LOAD WIDTH REQ'D
STREET ADDRESS 1500 IMLA STREET
COUNTY --
ACCESSORY STORAGE / MECHANICAL EQUIPMENT CLASSROOM 857 SF 20 SF NET 43 8.6 ACCESSORY STORAGE / MECHANICAL EQUIPMENT
CITY, STATE BALTIMORE, MARYLAND
MECH 77 SF 300 SF GROSS 0 0.1 CLASSROOM 885 SF 20 SF NET 44 8.9 MECHANICAL ROOM 3721 SF 300 SF GROSS 12 2.5
SCIENCE PREP 160 SF 300 SF GROSS 1 0.1 CLASSROOM 902 SF 20 SF NET 45 9.0 MECHANICAL ROOM 1227 SF 300 SF GROSS 4 0.8
MECH/ UTILITY 365 SF 300 SF GROSS 1 0.2 CLASSROOM 902 SF 20 SF NET 45 9.0 16 3.3 PROJECT DESCRIPTION: NEW ELEMENTARY SCHOOL, THREE-STORY
MECH 384 SF 300 SF GROSS 1 0.3 COLLABORATIVE 955 SF 20 SF NET 48 9.5 EDUCATIONAL (CLASSROOM)
M MECH 129 SF 300 SF GROSS 0 0.1 LEARNING OUTDOOR LEARNING LAB 969 SF 20 SF NET 48 9.7 APPLICABLE CODES M
MECH 124 SF 300 SF GROSS 0 0.1 CLASSROOM 868 SF 20 SF NET 43 8.7 48 9.7 Building Code: INTERNATIONAL BUILDING CODE 2015
STORAGE 230 SF 300 SF GROSS 1 0.2 CLASSROOM 867 SF 20 SF NET 43 8.7 Grand total 65 13.0 Fire Code: NFPA 101 LIFE SAFETY CODE 2015
STORAGE 230 SF 300 SF GROSS 1 0.2 CLASSROOM 902 SF 20 SF NET 45 9.0 Accessibility: AMERICANS WITH DISABILITY ACT ACCESSIBILITY GUIDELINES (ADAAG) AND
MECH 78 SF 300 SF GROSS 0 0.1 CLASSROOM 784 SF 20 SF NET 39 7.8 MARYLAND ACCESSIBILITY CODE (COMAR.05.02.02 REV. 20002)
CLASSROOM 879 SF 20 SF NET 44 8.8 BUILDING USE AND CONSTRUCTION CLASSIFICATIONS
6 1.2
CLASSROOM 893 SF 20 SF NET 45 8.9 IBC Code Fire Code
BUSINESS AREAS
RESOURCE 250 SF 100 SF GROSS 3 0.5 CLASSROOM 917 SF 20 SF NET 46 9.2 Use Group: E EDUCATIONAL 305.1 6.1.3
PLANNING 243 SF 100 SF GROSS 2 0.5 CLASSROOM 913 SF 20 SF NET 46 9.1
Building Area:
PLANNING 233 SF 100 SF GROSS 2 0.5 COLLABORATIVE 893 SF 20 SF NET 45 8.9
LEARNING MECH BASEMENT 1015 SF
RESOURCE 256 SF 100 SF GROSS 3 0.5
756 151.2 FIRST FLOOR 61994 SF
10 2.0
EDUCATIONAL (VOCATIONAL) SECOND FLOOR 31323 SF
EDUCATIONAL (CLASSROOM)
SCIENCE LAB 946 SF 50 SF NET 19 3.8 Grand total 94332 SF
L CLASSROOM
CLASSROOM
934 SF
887 SF
20 SF
20 SF
NET
NET
47
44
9.3
8.9 19 3.8 Proposed Type of Construction: IBC TYPE IIB L
CLASSROOM 882 SF 20 SF NET 44 8.8 Grand total 791 158.1 Allowable Building Height: 55'+20' (IBC TABLE 504.3, TABLE 504.4)=75' (MAX ALLOWABLE PER IBC 504.4), 3 Stories
Actual Building Height: 48' MAXIMUM

STAIR 2 OCCUPANCY LOADS AND EGRESS REQUIREMENTS


EGRESS WIDTH 72"
ALLOWABLE OCCUPANTS 240
REQUIRED WIDTH 70" Area in Sq. Ft. per Occupant Egress Width Egress Width Number Exits Number Exits
ACTUAL OCCUPANTS 231 Required Required
FIRE ZONE 2 Location Calculated
GYMNASIUM
Sq. Ft.
5929
Person
7
Load
849 172"
Provided
272" 3
Provided
3
MEDIA CENTER 2031 50 41 32" 72" 2 2
DINING 2523 7* 361 72" 136" 2 2
CLASSROOM 847 20 43 32" 33" 1 1
K K
TECH LAB 878 50 18 32" 33" 1 1
MUSIC 912 50 46 32" 33" 1 1
10' - 0"

10' - 0"
FIRE PROTECTION SYSTEM REQUIREMENTS
STORAGE STORAGE
230 SF 230 SF CLASSROOM System IBC Code Fire Code
CLASSROOM CLASSROOM 868 SF
1 HR FIRE RATING CLASSROOM 1 HR FIRE RATING Automatic Sprinklers YES 903.2.3 9.7
12' - 9 1/2" 913 SF 917 SF 1 1
867 SF 43 Fire Alarm System YES 907.2.3 9.6, 14.3.4
46 46 Smoke Detection System NO -- 9.6.2.9
CLASSROOM 43
CLASSROOM 879 SF MECH Partial Smoke Detection YES -- 9.6.5.2 (1)
MECH 893 SF 124 SF

29' - 6"
44 Location DOORS WITH HOLD -- --
DN 78 SF CLASSROOM CLASSROOM DN STAIR 3
45 0 OPEN DEVICES
PLANNING EGRESS WIDTH 72"
0 784 SF 902 SF
233 SF PLANNING ALLOWABLE OCCUPANTS 240 INTERIOR FINISH REQUIREMENTS
J 46" 2
39 243 SF 45
FEC
230
46"
330
REQUIRED WIDTH
ACTUAL OCCUPANTS
69"
230
Per IBC Table 803.11 & NFPA 14.3.3.2, 14.3.3.3 J
330 230
FIRE ZONE 2

FIRE ZONE 2
2
66" 66"
TRAVEL DISTANCE TO EXITS
1 HR FIRE RATING
AT ELEVATOR AND IBC Code Fire Code
COLLABORATIVE LEARNING MAX TRAVEL DISTANCE 177'-3" MAX TRAVEL DISTANCE 169'-6" COLLABORATIVE LEARNING 12' - 9 1/2"
ELEV. CONTROL ROOM Maximum Length of Travel in Fully Sprinklered Building 250' (Table 1017.2) 200' (14.2.6.3)
893 SF 955 SF
Maximum Length Common Path of Travel in Fully Sprinklered Building 75' (Table 1006.2.1) 100' (14.2.5.3.1)

20' - 0"
45 48
Spaces with One Means of Egress, Maximum Travel Distance to an Exit 75' (Table 1006.2.1) 75' (14.2.5.5 (2))
RESOURCE
250 SF
RESOURCE
256 SF
FIRE ZONE 2 Access Door

MINIMUM CORRIDOR WIDTH REQUIREMENTS

229
3 OCCUPANCY 1,546
FEC 3
USE GROUP E Width IBC Code Fire Code
MECH/ UTILITY

46"

FEC 90"
MECH CONSTRUCTION TYPE II-B 6 FT., EXIT CORRIDOR Table 1020.2 14-2.3.2
365 SF NUMBER OF STORIES 3
77 SF 44 IN., CLR. STAIR WIDTH 1011.2 7.2.2.2.1.2, 7.3.4
1
450
H H

www.grimmandparker.com
MECH MECH
0 BASEMENT FLOOR 1,023 SF
384 SF 129 SF FIRST FLOOR 27,628 SF
SCIENCE PREP PANIC HARDWARE

11720 Beltsville Drive


SECOND FLOOR 26,373 SF

Calverton, MD 20705
1 0
160 SF Per IBC Code 1010.1.10 & NFPA 7.2.1.7, 14.2.2.2.2
CLASSROOM CLASSROOM CLASSROOM TOTAL BUILDING AREA 54,024 SF
CLASSROOM

Tel: 301.595.1000
934 SF CLASSROOM CLASSROOM CLASSROOM ALL DOORS SERVING MORE THAN 50 & AT SMOKE BARRIER DOORS
887 SF 1 902 SF
882 SF SCIENCE LAB 857 SF 885 SF 902 SF ALLOWABLE AREA PER STORY 43,500 SF (TABLE 506.2)
47 44 2 HR FIRE RATING 45 % INCREASE FOR ACCESS: 38.86% 5,635 SF (506.3)
44 946 SF 43 44 45 EMERGENCY LIGHTING REQUIREMENTS
TOTAL ALLOWABLE AREA PER STORY 49,135 SF
19 Per IBC Code 1008 & NFPA 7.9, 14.2.9

Suite 600
DN DN TOTAL ALLOWABLE BUILDING AREA 98,263 SF ALL MEANS OF EGRESS

FIRE RATING REQUIREMENTS- STRUCTURAL ELEMENTS/ EGRESS COMPONENTS


Rating Required IBC Code Fire Code
270

Exterior Bearing Walls 0 TABLE 601, TABLE 602 TABLE A.8.2.1.2


THIS AREA TO BE UTILIZED BY
MAX TRAVEL DISTANCE =119'-6" TO STAIR 3
FIRE ZONE 1
32"

54"

THIS AREA TO BE UTILIZED BY MAX TRAVEL DISTANCE 121' TO STAIR 2 169'-6" TO STAIR 1 OCCUPANTS IN SURROUNDING Exterior Non-Bearing Walls 0 TABLE 602 TABLE A.8.2.1.2
G OCCUPANTS IN SURROUNDING 177'-3" TO STAIR 1 OPEN TO
BELOW 2 HR RATED CURTAINWALL SYSTEM CLASSROOMS AND DOES NOT Fire Walls 2 TABLE 706.4 TABLE A.8.2.1.2 G
CLASSROOMS AND DOES NOT
12

2 HR RATED CURTAINWALL SYSTEM CONTRIBUTE TO OCCUPANCY OCCUPANCY 1,722 Interior Bearing Walls 0 TABLE 601 TABLE A.8.2.1.2
CONTRIBUTE TO OCCUPANCY 2HR RATED CEILING ASSEMBLY UL ASSEMBLY USE GROUP E
OUTDOOR LEARNING LAB 2 HR FIREWALL Floor/ Ceiling Assemblies 0 TABLE 601 TABLE A.8.2.1.2
DESIGN NO. U930 CONSTRUCTION TYPE II-B
969 SF UL ASSEMBLY NUMBER OF STORIES 2
2 HR FIREWALL 2 HR RATING Roof/ Ceiling Assemblies 0 TABLE 601 TABLE A.8.2.1.2
48 DESIGN NO. U438 CONCRETE BEARING WALL
2 HR RATING Columns 0 TABLE 601 TABLE A.8.2.1.2
FIRST FLOOR 34,366 SF
CEILING ASSEMBLY SECOND FLOOR 4,655 SF Beams 0 TABLE 601 TABLE A.8.2.1.2
VEGETATIVE ROOF CONSTRUCTION TOTAL BUILDING AREA 39,021 SF Egress Corridors 0 TABLE 1020.1 7.1.3.1, 14.3.6
STAIR 1
EGRESS WITH 99" Shafts (Stairs) 1 1023.2 7.1.3.2.1
ALLOWABLE AREA PER STORY 43,500 SF (TABLE 506.2)
ALLOWABLE OCCUPANTS 330 % INCREASE FOR ACCESS: 45.00% 6,525 SF (506.3) Shafts Other than Stairs 1 713.4 8.6.5
MECHANICAL ROOM REQUIRED WIDTH 79" ALTERNATING TREAD STAIR, TOTAL ALLOWABLE AREA PER STORY 50,025 SF Corridor Doors 0 716.5.3, Table 1020.1 14.3.6
42" HIGH METAL RAILING 3721 SF ACTUAL OCCUPANTS 261 SECONDARY MEANS OF EGRESS Smoke Barrier 1 709.3 8.5
FROM SECOND FLOOR TOTAL ALLOWABLE BUILDING AREA 100,050 SF
12 MECHANICAL ROOM Smoke Partitions 0 710.3 8.4, 14.3.7, 14.3.6 (2)(a)
F (NFPA 14.2.2.9) Smoke Barrier Doors 20 MIN. 710.5.2, 716.5.3 8.5 F
Mixed Use Separation 1 or Auto Fire Extinguishing System 508, TABLE 508.4 --

EGRESS WIDTH
0

Width IBC Code Fire Code


GP# 21553
32"

33"

Egress width at stairs .3"/OCC. (1005.3.1) .3"/OCC. (TABLE 7.3.3.1)


165

STAIR 5
EGRESS WITH 23"
MINIMUM TREAD WIDTH 7" Egress width at doors and corridors .15"/OCC. (1005.3.2, Exception 1) .2"/OCC.(TABLE 7.3.3.1)

Fire Code

NUMBER OF REMOTE EXITS REQUIRED


E By Room IBC Code Fire Code E
Rooms Less Than 50 Occupants 1 Exit (Table 1006.2.1) --
Rooms with 50 - 500 Occupants 2 Exits (1006.2.1) --
Rooms with 501 - 1000 Occupants 3 Exits (1006.2.1.1) --
Rooms with More than 1000 Occupants 4 Exits (1006.2.1.1) --

By Story IBC Code Fire Code


OPEN TO
FIRE ZONE 1

FIRE ZONE 1
BELOW 1 - 500 Occupants 2 Exits (Table 1006.3.1) 2 Exits, 14.2.4
501 - 1000 Occupants 3 Exits (Table 1006.3.1) 3 Exits, 7.4.1.2
More than 1000 Occupants 4 Exits (Table 1006.3.1) 4 Exits, 7.4.1.2
ROOF

CITY OF BALTIMORE, MARYLAND


CODE STUDY - SECOND FLOOR
REMOTENESS OF EXITS
Life Safety A.7.5.1.3.3 - 1/3 the Length of Maximum Room Diagonal (Credit for Sprinklered Building)
D IBC 1007.1.1 Exception 2 - 1/3 the Length of Maximum Room Diagonal (Credit for Sprinklered Building) D

HOLABIRD ACADEMY PK-8


MAXIMUM DEAD END DISTANCES
IBC Code Fire Code

NOTES: 50 FT. (1020.4) Exception 2 50 FT. (14.2.5.2)

1. Mixed use separation walls shall have 45 minute rated opening protectives.
2. All fire separation walls shall comply with Section 708.4 of the 2015 IBC Code. They shall extend from the top of the fire resistance rated
floor/ ceiling assembly below to the underside of the floor or roof slab or deck above and shall be securely attached thereto.
3. All fire walls shall comply with Section 706 of the 2015 IBC Code.
4. Elevator shaft to be (2) hour rated - UL# U906.
5. Exterior walls indicated to provide (1) hour rating (UL# U906) - At stairs and fire walls where exterior walls form an angle less than 180
degrees, the exterior wall shall be rated at stairs per L.S. 7.2.2.5.2, and at fire walls per IBC 1023.7.
6. Stair enclosures are (1) hour rated, unless noted otherwise.
C OPEN TO
7. Refer to 1/8" plans & coord. w/ MEP drawings for chases thru floor shown thus enclosure wall around these floor opn'gs. shall be (1) hour
rated & shall extend from floor tight to deck above - pack w/ safing insulation rating shall be as follows:
C
BELOW CMU - U.L. #U906
Gyp. Bd. - Gypsum Assoc. assembly WP1110
8. Refer to sheet A-3.20 for wall termination details at rated walls.
9. Refer to the Door Schedule for doors with closers required.
MECHANICAL ROOM
10. All rated walls and partitions shall be permanently identified with signs or stenciling as follows:
1227 SF a. Identification markings shall be located in accessible concealed floor, floor-ceiling and attic spaces.
4 b. Identification markings shall be located within 15'-0" of the end of each wall and at intervals not exceeding 30'-0" measured
horizontally along the wall or partiion. DATE DESCRIPTION
CANOPY c. Lettering shall not be less than 3" in height with a minimum 3/8" stroke in contrasting color incorporating the following wording:
BELOW "FIRE AND/OR SMOKE BARRIER - PROTECT ALL OPENINGS".
11. No penetration of rated ceiling assemblies is allowed.
STAIR 6
EGRESS WITH 44"

B
ALLOWABLE OCCUPANTS
REQUIRED WIDTH
147
44" DN
SYMBOL KEY B
ACTUAL OCCUPANTS 4
ALLOWABLE # OCC.
REQ'D WIDTH

32"
90 165
CODE STUDY PLAN - SECOND FLOOR 33"

3 1/16" = 1'-0" ACTUAL WIDTH


ROOF
ACTUAL # OCC.

2 HOUR CEILING ASSEMBLY


A-0.3H
2 HOUR RATING
1 HOUR RATING
03/13/2017
SMOKE PARTITION BID SET
NFPA 101 SECTION 14.3.6 EXCEPTION #2 1 HOUR CEILING ASSEMBLY
A N © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

GENERAL DEMOLITION NOTES


1. ALL WORK SHOWN IS EXISTING TO REMAIN UNLESS NOTED OR INDICATED AS DASHED LINES TO BE
REMOVED. THE EXTENT OF DEMOLITION WORK SHALL INCLUDE ALL INCIDENTAL DEMOLITION WORK
NECESSARY TO PROPERLY PROVIDE ALL NEW WORK SHOWN AND SPECIFIED, TO INCLUDE MECHANICAL,
ELECTRICAL, & PLUMBING ITEMS.
2. DEMOLITION WORK SHOWN IS BASED ON EXISTING DRAWINGS AND INSPECTIONS. THE CONTRACTOR
SHALL VISUALLY INSPECT ALL EXISTING CONDITIONS, AND IS RESPONSIBLE FOR PERFORMING THE
INDICATED DEMOLITION WORK EVEN IF ACTUAL CONDITIONS DIFFER FROM THESE SHOWN ON THE
DRAWINGS.
3. DEMOLITION CONTRACTOR SHALL COORDINATE WITH NEW WORK SECTIONS FOR ADDITIONAL
INFORMATION RELATED TO EXTENT OF DEMOLITION.
4. REFER TO ALL OTHER DRAWINGS IN THIS SET FOR INCIDENTAL DEMOLITION WORK NOT NOTED ON THE
M EXISTING ROOF
5.
DEMOLITION PLANS.
THE OWNER HAS FIRST RIGHT OF REFUSAL OF ALL SALVAGE ITEMS. THE CONTRACTOR SHALL PROPERLY
M
TO BE DEMOLISHED
DISPOSE OF ALL CONSTRUCTION DEBRIS. DO NOT STOCKPILE DEBRIS ON SITE.
6. ITEMS TO BE DEMOLISHED SHALL BE REMOVED COMPLETELY INCLUDING ALL ANCHORS, HANGERS,
FASTENERS, PIPES, CONDUCTS, DUCTS, ETC. UNLESS OTHERWISE INDICATED TO BE ABANDONED IN PLACE.
A7 2 7. CONC. SLAB PATCHES MUST BE FLUSH WITH REMAINING SURFACES TO PERMIT APPLICATION OF FINISHES.
A-0.4H PROVIDE WELDED WIRE MESH IN PATCH AREAS LARGER THAT (4) FOUR SQUARE FEET.
8. CONC. SLABS TO REMAIN SHALL BE PATCHED, SCRAPED, LEVELED, AD CLEANED TO PROVIDE SURFACE
SUITABLE FOR NEW FINISHES. WHERE RENOVATED AREAS ARE RECEIVING NEW UNDERGROUND
6 MECHANICAL, PLUMBING, ELECTRICAL, OR ADDITIONAL FOUNDATION WORK, SEE MECHANICAL, PLUMBING,
ELECTRIC, AND STRUCTURAL DRAWINGS, AS WELL AS ARCHITECTURAL DRAWINGS TO DETERMINE EXTENT
OF REQUIRED CUT AND PATCH OF EXISTING SLAB. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL
CONC. SLAB DEMOLITION AND REPLACEMENT NECESSARY TO INSTALL THE NEW WORK. BACKFILL ALL
BELOW GRADE DEMOLITION WORK WITH SUITABLE FILL MEETING STRUCTURAL REQUIREMENTS FOR NEW
WORK.
9. PARTITIONS SHOWN TO BE REMOVED SHALL BE CONFIRMED BY THE CONTRACTOR AS TO TYPE OF
PARTITION AND EXACT LOCATION. COMPLETELY REMOVE PARTITIONS FROM FLOOR TO STRUCTURE
L ABOVE INCLUDING BASE, ALL FASTENERS, GROUTS, SEAL ANTS, ETC., UNLESS NOTED OTHERWISE. L
MASONRY PARTITIONS WHICH EXTEND THROUGH THE SLAB SHALL BE REMOVED TO 8" BELOW FINISH
FLOOR. FILL SLAB OPENING WITH CONCRETE FILL TO RECEIVE FINISH FLOOR. WHERE WALLS SCHEDULED
TO BE REMOVED SIT ON SLABS, GRIND SLAB TO RECEIVE FINISH FLOOR.
10. REMOVE, PATCH AND REPAIR PORTIONS OF WALL PARTITIONS WHICH CONFLICT WITH NEW WORK TO BE
INSTALLED, EVEN IF NOT SPECIFICALLY NOTED TO BE DEMOLISHED ON PLANS.
11. WALLS TO BE REMOVED FROM INTERSECTING WALLS SHALL INCLUDE TOOTHED IN REPLACEMENT OF
DAMAGED MASONRY ON WALL TO REMAIN AND REMOVAL OF TIES PROJECTING FROM WALLS. SEE
DETAILS FOR ADDITIONAL CONDITIONS.
12. WALLS TO BE PARTIALLY REMOVED SHALL BE TERMINATED WITH FINISHED MASONRY ENDS BY TOOTHING
IN NEW MASONRY UNITS, TO MATCH ADJACENT MASONRY. SEE DETAILS FOR OTHER CONDITIONS. NO
WALLS SHALL BE TERMINATED WITH EXPOSED OPEN CELLS OR DAMAGED MASONRY UNITS.
13. WHERE NEW OPENINGS ARE SHOWN IN EXISTING WALLS, CAREFULLY REMOVE MASONRY TO NEAREST
SELECTIVE DEMOLITION PLAN - ROOF PLAN JOINT LINE WITHOUT DISTURBING ADJACENT WORK SO THAT NEW WORK CAN BE PATCHED IN TO MATCH.
K18 1/16" = 1'-0" 14.
ALL NEW MASONRY WORK SHALL BE TOOTHED IN.
ALL EXISTING STRUCTURE SHALL REMAIN, UNLESS NOTED OTHERWISE.
K 15. COORDINATE DEMOLITION OF ALL STRUCTURAL ITEMS (COLUMNS, BEAMS, SLABS, ET, ETC.) WITH
STRUCTURAL DWGS. EXTENT OF DEMOLITION AREA SHALL BE IN ACCORDANCE WITH STRUCTURAL
K
REQUIREMENTS AND COORDINATED WITH ALL NEW WORK.
16. TEMPORARILY SUPPORT ALL BEAMS, LINTELS, PORTIONS OF WALLS ETC., TO BE DISTURBED BY
DEMOLITION WORK, UNTIL THEY ARE RE-SUPPORTED BY NEW WORK.
17. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF EXISTING BUILDING
ELEMENTS TO REMAIN THROUGHOUT SEQUENCE OF WORK. ANY DAMAGE TO EXISTING BUILDING
CONDITIONS SHOWN TO REMAIN SHALL BE RESTORED TO NEW WORK CONDITION AT NO ADDITIONAL COST
TO THE OWNER.
18. WINDOWS SCHEDULED FOR REMOVAL SHALL BE REMOVED COMPLETELY. FASTENERS MAY BE CUT FLUSH
WITH HEAD, JAMBS, AND SILLS IF THE NEW WINDOW UNIT WILL CONCEAL FASTENER. PROTECT EXISTING
SILLS SCHEDULED TO REMAIN. ALL EXISTING WINDOW OPENINGS MUST BE FIELD MEASURED PRIOR TO
SUBMITTAL OF SHOP DRAWINGS.
19. WERE FINISHES ARE INDICATED TO BE REMOVED, REMOVAL SHALL INCLUDE ANY GROUT, ADHESIVES,
FASTENERS, AND ALL OTHER ITEMS USED TO ATTACH THE FINISHES TO THE SURFACES THAT THEY COVER.
20. ANY FLOOR AREAS DAMAGED BY THE DEMOLITION CONTRACTOR SHALL BE PATCHED TO MATCH EXISTING.
21. WHERE CEILINGS ARE TO BE REMOVED, REMOVE ALL CEILINGS SYSTEMS COMPLETE INCLUDING GRID,
J TRIM HANGER, CLIPS, ETC. WHERE NEW CEILINGS ARE SPECIFIED, NO DOUBLE CEILINGS PERMITTED.
REMOVE ALL ORIGINAL CONCEALED CEILINGS WHERE ENCOUNTERED.
J
EXISTING GYMNASIUM
TO BE DEMOLISHED 22. ALL EXISTING SURFACES TO REMAIN SHALL BE PROTECTED, PATCHED IF DAMAGED AND CLEANED PRIOR
TO APPLICATION OF FINISHES.
1 2 23. CONTRACTOR TO PROTECT ALL EQUIPMENT AND OTHER ELEMENTS IN AREA OF NEW OR DEMOLITION
WORK.
EXISTING DOORS 24. REMOVE ALL CURTAINS AND BLINDS IN AREAS OF RENOVATION OR DEMOLITION, UNLESS NOTED
5 TO BE REMOVED OTHERWISE.
ROOF
7 25. REMOVE MECHANICAL, ELECTRICAL AND PLUMBING ITEMS AS NOTED ON MECHANICAL, ELECTRICAL AND
BELOW
PLUMBING PLANS. COORDINATE WITH CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING, FOR
A7 ADDITIONAL DEMOLITION NOTES. REMOVAL WORK IS INTENDED TO INCLUDE ALL ASSOCIATED ITEMS SUCH
AS ELECTRICAL OUTLETS, SWITCHES, CONDUITS, CONTROLS, PIPING, MOUNTING BLOCKS, ETC., AS NOTED.
A-0.4H
THE CONTRACTOR SHALL REFER TO ALL CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL AND PLUMBING
DRAWINGS AND SPECIFICATIONS FOR PROCEDURES CONCERNING RELATED TRADES IN AREAS WHICH
REQUIRE DEMOLITION. REPAIR AND PATCH ANY AREAS DAMAGED DURING REMOVAL WORK.

UP
H H

www.grimmandparker.com
11720 Beltsville Drive

Calverton, MD 20705
Tel: 301.595.1000
DEMOLITION KEY NOTES
MECHANICAL

Suite 600
EQUIPMENT 1. REMOVE EXISTING STRUCTURE COMPLETELY, INCLUDING ROOF, WALLS, SLABS, DOORS, WINDOWS, FRAMES &
UPPER PART OF
UP FOUNDATION. REFER TO STRUCTURAL DWGS.
GYMNASIUM AUDITORIUM INFILL WALL
UPPER PART OF 2. REMOVE ROOF STRUCTURE, ROOFING AND FLASHING COMPLETELY.
TO BE DEMOLISHED
STAGE 3. REMOVE ALL FINISHES INCLUDING FLOORING, FIXTURES, CASEWORK, SHELVING, BASE, CHALK & TACK BOARDS,
A7
PROJECTION SCREEN, WINDOW TREATMENT, SINKS, PLUMBING FIXTURES, CHASES, MECHANICAL UNITS,
A-0.4H 1 ELECTRICAL ITEMS, CEILING & CEILING SUPPORT MEMBERS & ALL BULKHEADS. COORD. W/ M.E.P. FOR
ADDITIONAL DEMO.
4. REMOVE EXHAUST COORD. W/ M.E.P. DWGS. FOR EXISTING OPENINGS TO BE REUSED. ABANDONED
G PENETRATIONS SHALL BE INFILLED PER DETAILS. G
5. EXISTING FLOOR FINISH TO REMAIN. PROTECT DURING CONSTRUCTION. SEE NEW WORK PLANS FOR AREAS TO
PATCH.
6. EXISTING ROOF TO REMAIN
7. EXTENT OF EXISTING WALL TO BE PARGED
8. 8" CMU INFILL AT OPENING WITH PARGING
BALCONY PHASE 2 PHASE 1

PHASE LINE
STORAGE
ROOF EXSITING ROOF
STAIR BELOW
ROOF
GRAVEL STOP

F F
EXSITING
RIBBED SLAB STRUCTURE

GP# 21553
SELECTIVE DEMOLITION PLAN - SECOND FLOOR
E18 1/16" = 1'-0"
EXSITING
WALL
EXISTING METAL JOIST STRUCTURE
MECHANICAL TO BE REMOVED
EQUIPMENT ROOM

E 12' - 0" E
SECOND FLOOR | 93.0 DEMOLITION KEY
EXISTING WALL NEW / TEMPORARY
INFILL WALL
EXSITING
RIBBED SLAB STRUCTURE EXISTING WALL TO BE
DEMOLISHED

EXISTING DOOR & FRAME

CITY OF BALTIMORE, MARYLAND


TO BE REMOVED

SELECTIVE DEMOLITION PLAN


PARGE EXPOSED EXTERIOR SIDE OF WALL
EXISTING COLUMN
D REFER TO A12 / A-0.4H FOR
D

HOLABIRD ACADEMY PK-8


INFILL WALL: EXTENTS
8" CMU LOBBY EXISTING COLUMN TO
INSULATION BE DEMOLISHED
ELECTRICAL EXISTING AREA WAY COVERBOARD
ROOM PARGING

INFILL WALL
WHERE DOORS
DEMOLITION KEY PLAN
WERE DEMOLISHED
AND AT OTHER
OPENINGS 5
KEEP PORTION OF WALL PORTION OF EXISTING
AND FOUNDATION 0" SCHOOL TO BE REMOVED

C FIRST FLOOR | 81.0 C


CRAWL SPACE

1
A7 CRAWL SPACE
A-0.4H
CRAWL SPACE DATE DESCRIPTION

9' - 0"
EXISTING NEW
B 8
SCHOOL
TO REMAIN
SCHOOL
B
AT ALL BELOW SLAB OPENINGS

EXISTING
MODULAR

72.0

SELECTIVE DEMOLITION PLAN - BASEMENT OVERALL DEMOLITION PLAN - FIRST FLOOR TEMPORARY EXT. WALL @ GYM
PHASE 2 PHASE 1 TO BE REMOVED
SEE CIVIL DWGS. A-0.4H
A18 1/16" = 1'-0" A12 1/16" = 1'-0" A7 3/8" = 1'-0"
03/13/2017
BID SET
A N © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

279' - 4"

L18 G18
L18 G18 A-2.3G A-2.3G
A-2.3H A-2.3H
EXA A B C D D.7 E G G.7 G.9 H J K K.2 K.3 L L.6 M M.1 M.5 N P Q Q.2 R S T EXD
M M

A15 / A-1.3
A15 / A-1.2
J10
A-4.2

K18
14' - 0" 55' - 4" 140' - 8" A-4.1 55' - 4" 14' - 0"

EX1 EX1
PROTECTIVE COVER/CANOPY VESTIBULE
C15A

15' - 4"
EX2 EX2
1 KILN FLOOR MAT 1
1721A ENTRYWAY SUPPLY
GRADE 1 GRADE 1 GRADE 3 ART STUDIO SYSTEM TECH ED LAB STORAGE/IT PRE-K PRE-K PRE-K
1811 1807 1805 1721 1722 ADMIN 1905 1907 1909
L 1722A L
PK-2 TOILET
1807A PK-2 TOILET PK-2 TOILET
PK-2 TOILET 1805A 1909A
1811A ART STORAGE

32' - 8"
MECH 1721B PK-2 TOILET
1809 PK-2 TOILET 1907A
UP 1905A
2 2
UP
STAIR 2 MECH MECH STAIR 3
ST21 1801 1903A ST31
3 3

CORRIDOR CUSTODIAL CORRIDOR


D18 COLLABORATIVE 0" ELECTRICAL C172 CORRIDOR
1720

107' - 4"
A-2.2G 1804 C180 C190 0" COLLABORATIVE
LEARNING
LEARNING
1820

20' - 0"
1920
K RESOURCE PLANNING TELECOM/UTILITY
SP. ED.
STORAGE
PLANNING
RESOURCE K
D18 STORAGE
1806 1802 1800 1711A 1906
A-2.2H 1900 1904
STAFF TOILET
STAFF TOILET
1900A
4 1802B 4
ELEVATOR
MECH TOILET PK-2 TOILET PK-2 TOILET
STAFF TOILET E1
1812 1902A 1908A 1910A
1803A
5 SP. ED. 5
PK-2 TOILET PK-2 TOILET OFFICE
PK-2 TOILET PK-2 TOILET
5.1 1810A 1813A 1711 UP 1911A 5.1
1808A SPECIAL
FACULTY UP EDUCATION

39' - 4"
GRADE 2 GRADE 2 GRADE 3 LOUNGE STORAGE PK-2 KINDERGARTEN KINDERGARTEN KINDERGARTEN
OT/PT 1910 1911
1813 1810 1808 1803 1802A 1710 1902 1908
CORRIDOR
C171
J OT/PT
TOILET
1710A J
STAIR 1
5.8 STORAGE AA 5.8

EX3
X1 1710B
ST12

EX3
GENERAL NOTES (NOTES APPLY TO ALL DRAWINGS)

GENERAL NOTE APPLICABLE TO ALL DRAWINGS - ITEMS AND CONDITIONS DETAILED, NOTED OR OTHERWISE IDENTIFIED ON
6 EXPANSION JOINT WORKROOM/STORAGE 6 ONE OF THE SECTIONS OR DETAILS ARE APPLICABLE AND BINDING TO ALL OTHER SECTIONS AND DETAILS FOR IDENTICAL
1701 OR SIMILAR CONDITIONS.
EXA A B C D D.7 X2 EXPANSION JOINT P Q.2 R
SMALL 1. ALL CONSTRUCTION AND WORK SHOWN ON THE COMPLETE SET OF DRAWINGS IS ASSUMED TO BE NEW AND
REHEARSAL FURNISHED AND INSTALLED BY THE CONTRACTOR.
D18 D18 1705
D18 2. IF A CONFLICT EXISTS BETWEEN DRAWINGS (AND/OR SPECIFICATIONS), THE MORE STRINGENT AND MORE
A-2.1G A-2.1H D18
A-2.3G COSTLY REQUIREMENT SHALL APPLY. ITEMS SHOWN ON THE DRAWINGS, BUT NOT SPECIFIED, SHALL APPLY
A-2.3H D18 AND BE FURNISHED AND INSTALLED BY THE CONTRACTOR. IF AN ITEM IS SHOWN ON THE DRAWINGS, BUT IS
MEDIA A-2.4H NOT INCLUDED IN THE SPECIFICATIONS, PROVIDE ITEM OF A QUALITY LEVEL CONSISTENT WITH THE GENERAL

48' - 8"
X3 CENTER QUALITY LEVEL OF THE CONTRACT REQUIREMENTS. BRING CONFLICTS BETWEEN THE DRAWINGS AND
1700
56' - 0"

H H

www.grimmandparker.com
7 7 SPECIFICATIONS TO THE ATTENTION OF THE ARCHITECT IMMEDIATELY.
STORAGE 3. WRITTEN INFORMATION TAKES PRECEDENT OVER DRAWING LINES. BRING CONFLICTS BETWEEN WRITTEN
1704 INFORMATION AND DRAWN LINES TO THE ATTENTION OF THE ARCHITECT IMMEDIATELY.

11720 Beltsville Drive


BB

Calverton, MD 20705
D18 4. IF A CONFLICT EXISTS BETWEEN DRAWINGS OF DIFFERENT SCALES, CONSULT THE ARCHITECT FOR
CC
CLARIFICATION.

Tel: 301.595.1000
A13 EXB EXC A-2.4G
D10 5. IN THE ABSENCE OF A WRITTEN DIMENSION, OR IN CASE OF DOUBT AS TO THE PROPER MEASUREMENT,
A-4.2a D11 A-2.3H CONSULT THE ARCHITECT FOR CLARIFICATION.
LOCKERS/SHOWER/
LARGE A-2.3G 6. IF AN AREA OR SPACE IS SHOWN, BUT IS NOT CLEARLY DEFINED OR INDICATED BY NOTES, PROVIDE THE SAME
TOILET
D9 D9 REHEARSAL 1400 A15 / A-1.3 MATERIALS AND FINISHES AS SCHEDULED OR DETAILED FOR AREAS OF SIMILAR USE ELSEWHERE IN THE

Suite 600
A-2.1G 1703 BUILDING,
A-2.1H A16 / A-1.1 7. SECTIONS INDICATED ARE INTENDED TO SHOW THE SPECIFIC CONSTRUCTION WHERE REFERENCED AS WELL
WATER AS ESTABLISH THE GENERAL CONSTRUCTION DETAILS FOR SECTIONS THROUGHOUT THE PROJECT WHICH DO
FIRE PUMP
F SERVICE NOT HAVE SPECIFIC SECTIONS DRAWN. THE MOST SIMILAR SECTIONS SHALL BE ADAPTED TO ANY SECTIONS
1404
1402 NOT DETAILED. ANY SPECIFIC QUESTIONS CONCERNING CONSTRUCTION NOT ADEQUATELY COVERED BY THE
8 8
CUSTODIAL ABOVE SHOULD BE DIRECTED TO THE ARCHITECT DURING THE BIDDING.
339' - 9 5/8"

CORRIDOR
OUTDOOR DD 1403 8. TYPICAL DETAILS THROUGHOUT THE DRAWING SET SHALL APPLY FOR ALL APPLICABLE CONDITIONS EVEN IF
C140
STORAGE EE NOT SPECIFICALLY SHOWN OR REFERENCED.
8.2 A15 / A-1.2 CONFERENCE 8.2
G E101
1201
F12
PLATFORM
STORAGE
STAIR 5
ST51
EMERGENCY
ELECTRICAL ELECTRICAL
9. SEE STRUCTURAL DRAWINGS FOR ACTUAL STRUCTURAL STEEL AND BEARING ELEVATIONS. G
OUTDOOR 10. REFER TO ARCHITECTURAL SITE PLAN FOR THE LAYOUT OF CONCRETE WALKS, MOW STRIPS, PAVING
A16 / A-1.1 STORAGE
WAITING/RECEPTION 1304A 1405 1407 PATTERNS, ETC. IN THE BUILDING VICINITY. REFER TO CIVIL DRAWINGS FOR THE CONTINUATION OF THIS WORK.
1200 A-4.1 PLATFORM
E102 11. UNLESS NOTED OTHERWISE, WALLS SHALL EXTEND TO THE ROOF OR FLOOR DECK ABOVE AND BE SEALED IN
CORRIDOR 1304 FURNITURE CENTRAL FE
ACCORDANCE WITH GENERAL PLAN NOTE #2 ON SHEET A-1.1 AND WALL TERMINATION DETAILS ON WALL TYPE
C120 STORAGE STORAGE
SOCIAL SHEET.
HEAD END CUSTODIAL 1303 1406 RECEIVING
WORKER RAMP 2 12. AT ALL OUTSIDE CORNERS OF INTERIOR CMU WALLS, COLUMN ENCLOSURES, PIPE CHASES OR OTHER WALL
ROOM 1302A UP TOILET 1408x
1204 RA21 PROJECTIONS, PROVIDE MASONRY UNITS AND/OR GLAZED MASONRY UNITS WITH BULLNOSED (ROUNDED)

75' - 1 5/8"
1202 1410
RECORDS EDGES WITH 1" RADIUS, UNLESS OTHERWISE NOTED OR WHERE SCHEDULED TO RECEIVE CERAMIC TILE.
9 STORAGE 9 WHERE MASONRY CORNERS ALIGN WITH BULKHEADS, TRANSITION FROM BULLNOSE CORNER UNITS TO
PSYCHOLOGIST 1203 L18 SQUARE CORNER UNITS.
L18 1205 MEN DISH/TRAY CORRIDOR OPERATIONS A-2.4H
9.1 9.1 13. UNLESS SPECIFICALLY NOTED OTHERWISE, ENCLOSE ALL VERTICAL MECHANICAL PIPES, RAIN LEADERS, ETC.
A-2.2G MECH 1302 RETURN 1419 OFFICE WITH 4" CMU OR GYPSUM BOARD TO MATCH SURROUNDING FINISHES.
1206 1414 OFFICE 1408 14. REFER TO PLANS AND ELEVATIONS FOR LOCATIONS OF CONTROL JOINTS (C.J.) AND EXPANSION JOINTS (E.J.) IN
FLEX OFFICE 1409 EXTERIOR MASONRY WALLS. IF A CONFLICT EXISTS BETWEEN JOINT LOCATIONS SHOWN ON THE ELEVATIONS

FE
1207 ELECTRICAL L.6 M.1
1208 AND PLANS, CONSULT THE ARCHITECT FOR CLARIFICATION PRIOR TO CONSTRUCTION. REFER TO FLOOR PLANS
G18 WONDERWALL WALK-IN CAN WASH G18 FOR LOCATIONS OF CONTROL JOINTS (C.J.) IN INTERIOR MASONRY WALLS.
F A-2.2G
OFFICE WOMEN
REF: A6/A-6.3 AND K11A-6.4
SOAP
STORAGE COOLER E100 A-2.4H 15. ALL EXTERIOR CAVITY WALLS TO HAVE THRU-WALL FLASHING AT THE BOTTOM OF THE CAVITY WITH WEEP F
STAFF TOILET DINING 1415 HOLES TO THE OUTSIDE. ALL FLASHING BUILT INTO WALLS SHALL BE LAPPED AND SEALED. REFER TO FLASHING
1209 1301 1411
1210 STORAGE 1300 DETAILS INDICATED.
1010
116' - 0"

16. REFER TO BUILDING ELEVATIONS AND ELEVATION DETAILS FOR MASONRY PATTERNS.
L18 10 OFFICE WALK-IN 10 17. INCLUDE PROJECTIONS, BEAM ENCLOSURES, RECESSES, BULKHEADS, PILASTERS AND SIMILAR ENCLOSURES
LAUNDRY
A-2.2H 1211
STAFF TOILET
1011
EXAM/TREATMENT
PERSONAL
SERVING
1413
KITCHEN
1412
FREEZER
1416 L18
A-2.4G
18.
AS PART OF WALL AND CEILING FINISHES AS SCHEDULED.
ALL APPURTENANCES BUILT INTO OR THROUGH WALLS, INCLUDING DOORS, DUCTS, WINDOWS, LOUVERS,
GP# 21553
CARE GRILLES, MECHANICAL WORK, ETC. SHALL FIT TIGHT AND BE THOROUGHLY SEALED AROUND PERIMETERS.
FLEX OFFICE 1009 1104 1012 WORK AT EXTERIOR WALLS SHALL BE FLASHED OR OTHERWISE WATERPROOF SEALED.
G18 1008 HEALTH 19. SEE FURNISHING PLANS (A-9 SERIES) FOR CASEWORK, CABINETS, LOCKERS, DISPLAY BOARDS AND CASES
A-2.2H EXAM/TREATMENT AND SIMILAR ITEMS.
OFFICE CORRIDOR G18
FLEX OFFICE 1106 0" GYM 20. FIELD CHECK ROUGH AND/OR FINISHED DIMENSIONS FOR ACCURATE FITTING OF CABINETS, COUNTERS,
1102 C130 OFFICE A-2.4G
1007 DRY STORAGE LOCKERS, DOORS, WINDOWS, FIXTURES, SHELVING, GATES AND OTHER INSTALLATIONS PRIOR TO SHOP OR
WAITING 1503 STORAGE
CORRIDOR STORAGE 1805E FACTORY FABRICATION. PROVIDE FILLER STRIPS, SCRIBE STRIPS, BASES, CLOSURE FINISHES AND TRIM FOR A
A18 CORRIDOR 1100 STORAGE PANTRY 1504
C100 1417 COMPLETE INSTALLATION.
A-4.1 C110 1102A 1418
PRINCIPAL 21. PROVIDE APPROPRIATE TRANSITION STRIPS AT CHANGES IN FLOOR ELEVATIONS.
11 11
E 1006 WORKROOM REST AREA REST AREA STUDENT SECURITY P.E. OFFICE
22. EACH CONTRACTOR SHALL REFER TO MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS AND BE
RESPONSIBLE FOR WORK PERTAINING TO THEIR PARTICULAR TRADE. ALL CONTRACTORS SHALL COORDINATE
E
1105 1103 TOILET
1002 OFFICE 1511 THE WORK OF ALL TRADES AND FIELD CHECK AGAINST ANY CONFLICTS BETWEEN DRAWINGS. REPORT
1101
J.1 1501 CONFLICTS TO THE ARCHITECT FOR CLARIFICATION.
23. REFER TO PLUMBING, HVAC AND ELECTRICAL DRAWINGS FOR LOCATIONS AND DESCRIPTIONS OF ACCESS
11.4 PANELS, LOUVER OPENINGS, VENTILATORS, GRILLES, VALVE CABINETS, FIRE DAMPERS OR OTHER
CLOSET
SECURE APPURTENANCES AFFECTING WALLS, CEILINGS OR FLOORS. PROVIDE NECESSARY LINTELS, SUPPORT AND
1003
STORAGE ANCHORAGE. SEE STRUCTURAL NOTES FOR LINTEL REQUIREMENTS.
A18 1005 24. REFER TO MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR LOCATIONS OF CONCRETE PADS TO BE
VESTIBULE PROVIDED BELOW OR AROUND EQUIPMENT.

82' - 0"
A-4.2 CONFERENCE A.P. OFFICE RECEPTION GYMNASIUM
1004 1001 1000 V1806 25. INSTALL ELECTRIC SWITCHES, OUTLETS, THERMOSTATS, CONTROLS, CLOCKS, SPEAKERS, FLAGPOLE HOLDERS
1500 AND OTHER WALL-MOUNTED ACCESSORIES IN LOCATIONS WHICH ARE UNOBSTRUCTED BY CABINETS,
G.2 COUNTERS, RACKS, DISPLAY BOARDS, FIXTURES, SHELVING OR OTHER FURNISHINGS OR EQUIPMENT

CITY OF BALTIMORE, MARYLAND


12 UP LOCKERS/SHOWER/TOILET DESIGNATED FOR SPACES SHOWN ON DRAWINGS. THESE DEVICES ARE SHOWN ON THE ARCHITECTURAL
1805G DRAWINGS TO ALERT OTHER SUB-CONTRACTORS OF THEIR PRESENCE. COORDINATE INSTALLATION WITH THE

OVERALL PLAN - FIRST FLOOR


A1
ELECTRICAL DRAWINGS. ADVISE THE ARCHITECT OF CONFLICTS IN LOCATION OR TYPES OF DEVICES SHOWN
FLOOR MAT PRIOR TO INSTALLATION. DO NOT INSTALL WALL-MOUNTED ITEMS ON, THROUGH OR INTO ANY EQUIPMENT
D ENTRYWAY
SYSTEM
VESTIBULE
UNLESS INDICATED. D
26. MOUNT ELECTRIC SWITCHES, THERMOSTATS AND OTHER ELECTRONIC CONTROLS LOCATED IN THE SAME

HOLABIRD ACADEMY PK-8


A2 V100
33' - 6 5/8"

VICINITY AT THE SAME HEIGHT ABOVE FINISHED FLOOR IN A UNIFORM, ORDERLY FASHION UNLESS NOTED
ENTRANCE OTHERWISE.
CANOPY ABOVE
LOCKERS/SHOWER/TOILET
A3 1805H

13 A4
VESTIBULE
V1600
13
KEY PLAN
CORRIDOR CUSTODIAL TOILET
1609 1607
C160
A5 COMMUNITY
LEARNING
OFFICE PANTRY
26' - 11"

CENTER

26' - 8"
CORRIDOR 1608
C 1603
C161 FAMILY CONFERENCE 1600 C
RESOURCE 1601
OFFICE OFFICE ROOM
1602 1605 1604
EX4 EX4
FDC
AREA B AREA C
59' - 3 3/4" 13' - 2 7/8" 114' - 0" DATE DESCRIPTION
H18 L18 H18 L18
A-2.1G A-2.1G 197' - 10A-2.1H
5/8" A-2.1H

B EXB F G.2 G.9 H J J.1 K N Q EXC B


AREA A

FIRST FLOOR TOTAL AREA:

OVERALL FIRST FLOOR PLAN


61,994 SF
Scale: 1 inch = 16 feet A-0.5
A14 1/16" = 1'-0" 03/13/2017
BID SET
0 8' 16' 32' 48'
A N © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

279' - 4"
L18 G18
L18 G18 A-2.3G
M EXA A B C D D.7 E G
A-2.3H A-2.3H
G.7 H J
A-2.3G
K K.2 K.3 L L.6 M M.1 M.5 N P Q Q.2 R S T EXD
M

A15 / A-1.5

A15 / A-1.6
J10
A-4.2

K18
55' - 4" 140' - 8" A-4.1 55' - 4"

EX1 EX1

EX2
EX2
1 STORAGE 1
2204B STORAGE
L STAFF TOILET 2302A L
2204A STAFF TOILET
2302B
SPECIAL
EDUCATION
GRADE 5 GRADE 5 3-5 FLEX FLEX GRADE 6 GRADE 8 MECH GRADE 8
2214 MECH 2210 2206 2200 2300 2306 2308 2310 2312
2212 PLANNING PLANNING
2204 2302
2 2
UP STAIR 2 STAIR 3
ST22 ST32
3 3
COLLABORATIVE CORRIDOR CORRIDOR CORRIDOR
D18 LEARNING 14' - 8" C220 C210 C230 COLLABORATIVE
K K

107' - 4"
14' - 8"
A-2.2G 2220 LEARNING
2320
CUSTODIAL TOILET TOILET
2203B 2202 2300E
D18
A-2.2H RESOURCE
2208 WOMEN WOMEN MEN RESOURCE
MEN 2201 2305
2203 2301 2303
4 4
MECH ELEVATOR
2213 MECH/UTILITY E1 MECH
ELEVATOR 2100
2205 CONTROL
5 5
2207
5.1 SPECIAL MECH 5.1
STAIR 1 EDUCATION 2311
ST12 6-8 GRADE 6 GRADE 7 GRADE 7
GRADE 4 GRADE 4 FLEX SCIENCE LAB
J 2215 2211 2209 2000
STAIR 4
ST42
2304 2307 2309 2313
J
PREP/STORAGE

5.8
X1
2000A
DN DN
AA
5.8 GENERAL NOTES (NOTES APPLY TO ALL DRAWINGS)

EX3 GENERAL NOTE APPLICABLE TO ALL DRAWINGS - ITEMS AND CONDITIONS DETAILED, NOTED OR OTHERWISE IDENTIFIED ON
EX3 ONE OF THE SECTIONS OR DETAILS ARE APPLICABLE AND BINDING TO ALL OTHER SECTIONS AND DETAILS FOR IDENTICAL
6 OR SIMILAR CONDITIONS.
6 X2 1. ALL CONSTRUCTION AND WORK SHOWN ON THE COMPLETE SET OF DRAWINGS IS ASSUMED TO BE NEW AND
OUTDOOR FURNISHED AND INSTALLED BY THE CONTRACTOR.
EXA A B C D D.7 CLASSROOM M.5 P Q.2 R S T EXD 2. IF A CONFLICT EXISTS BETWEEN DRAWINGS (AND/OR SPECIFICATIONS), THE MORE STRINGENT AND MORE
EXPANSION JOINT COSTLY REQUIREMENT SHALL APPLY. ITEMS SHOWN ON THE DRAWINGS, BUT NOT SPECIFIED, SHALL APPLY
D18 D18 AND BE FURNISHED AND INSTALLED BY THE CONTRACTOR. IF AN ITEM IS SHOWN ON THE DRAWINGS, BUT IS
A-2.1G A-2.1H D18 D18 NOT INCLUDED IN THE SPECIFICATIONS, PROVIDE ITEM OF A QUALITY LEVEL CONSISTENT WITH THE GENERAL
EXPANSION JOINT A-2.3G A-2.3H QUALITY LEVEL OF THE CONTRACT REQUIREMENTS. BRING CONFLICTS BETWEEN THE DRAWINGS AND
X3 D18
H H

www.grimmandparker.com
A-2.4H SPECIFICATIONS TO THE ATTENTION OF THE ARCHITECT IMMEDIATELY.
3. WRITTEN INFORMATION TAKES PRECEDENT OVER DRAWING LINES. BRING CONFLICTS BETWEEN WRITTEN
ROOF INFORMATION AND DRAWN LINES TO THE ATTENTION OF THE ARCHITECT IMMEDIATELY.

11720 Beltsville Drive

Calverton, MD 20705
7 7 4. IF A CONFLICT EXISTS BETWEEN DRAWINGS OF DIFFERENT SCALES, CONSULT THE ARCHITECT FOR
MECHANICAL CLARIFICATION.

Tel: 301.595.1000
ROOM - 5. IN THE ABSENCE OF A WRITTEN DIMENSION, OR IN CASE OF DOUBT AS TO THE PROPER MEASUREMENT,
BB
CC CENTRAL D18 CONSULT THE ARCHITECT FOR CLARIFICATION.
A13 2101 EXC A-2.4G 6. IF AN AREA OR SPACE IS SHOWN, BUT IS NOT CLEARLY DEFINED OR INDICATED BY NOTES, PROVIDE THE SAME
D10
D11 MATERIALS AND FINISHES AS SCHEDULED OR DETAILED FOR AREAS OF SIMILAR USE ELSEWHERE IN THE
A-4.2a A-2.3H

Suite 600
A-2.3G BUILDING,
VEGATATIVE A15 / A-1.6 7. SECTIONS INDICATED ARE INTENDED TO SHOW THE SPECIFIC CONSTRUCTION WHERE REFERENCED AS WELL
D9 D9 AS ESTABLISH THE GENERAL CONSTRUCTION DETAILS FOR SECTIONS THROUGHOUT THE PROJECT WHICH DO
ROOF
A-2.1H A-2.1G NOT HAVE SPECIFIC SECTIONS DRAWN. THE MOST SIMILAR SECTIONS SHALL BE ADAPTED TO ANY SECTIONS
NOT DETAILED. ANY SPECIFIC QUESTIONS CONCERNING CONSTRUCTION NOT ADEQUATELY COVERED BY THE
ABOVE SHOULD BE DIRECTED TO THE ARCHITECT DURING THE BIDDING.
8. TYPICAL DETAILS THROUGHOUT THE DRAWING SET SHALL APPLY FOR ALL APPLICABLE CONDITIONS EVEN IF
8 8 NOT SPECIFICALLY SHOWN OR REFERENCED.
G DD
9. SEE STRUCTURAL DRAWINGS FOR ACTUAL STRUCTURAL STEEL AND BEARING ELEVATIONS. G
10. REFER TO ARCHITECTURAL SITE PLAN FOR THE LAYOUT OF CONCRETE WALKS, MOW STRIPS, PAVING
8.2 A15 / A-1.5 8.2 PATTERNS, ETC. IN THE BUILDING VICINITY. REFER TO CIVIL DRAWINGS FOR THE CONTINUATION OF THIS WORK.
EE STAIR 5 11. UNLESS NOTED OTHERWISE, WALLS SHALL EXTEND TO THE ROOF OR FLOOR DECK ABOVE AND BE SEALED IN
F12
ST52 ACCORDANCE WITH GENERAL PLAN NOTE #2 ON SHEET A-1.1 AND WALL TERMINATION DETAILS ON WALL TYPE
A-4.1 SHEET.
12. AT ALL OUTSIDE CORNERS OF INTERIOR CMU WALLS, COLUMN ENCLOSURES, PIPE CHASES OR OTHER WALL
PROJECTIONS, PROVIDE MASONRY UNITS AND/OR GLAZED MASONRY UNITS WITH BULLNOSED (ROUNDED)
EDGES WITH 1" RADIUS, UNLESS OTHERWISE NOTED OR WHERE SCHEDULED TO RECEIVE CERAMIC TILE.
WHERE MASONRY CORNERS ALIGN WITH BULKHEADS, TRANSITION FROM BULLNOSE CORNER UNITS TO
SQUARE CORNER UNITS.
9 9 13. UNLESS SPECIFICALLY NOTED OTHERWISE, ENCLOSE ALL VERTICAL MECHANICAL PIPES, RAIN LEADERS, ETC.
9.1 9.1 L18 WITH 4" CMU OR GYPSUM BOARD TO MATCH SURROUNDING FINISHES.
L18 A-2.4H 14. REFER TO PLANS AND ELEVATIONS FOR LOCATIONS OF CONTROL JOINTS (C.J.) AND EXPANSION JOINTS (E.J.) IN
A-2.2G EXTERIOR MASONRY WALLS. IF A CONFLICT EXISTS BETWEEN JOINT LOCATIONS SHOWN ON THE ELEVATIONS
AND PLANS, CONSULT THE ARCHITECT FOR CLARIFICATION PRIOR TO CONSTRUCTION. REFER TO FLOOR PLANS
FOR LOCATIONS OF CONTROL JOINTS (C.J.) IN INTERIOR MASONRY WALLS.
F 15. ALL EXTERIOR CAVITY WALLS TO HAVE THRU-WALL FLASHING AT THE BOTTOM OF THE CAVITY WITH WEEP F
205' - 6 5/8"

L.6 M.1
G18 G18 HOLES TO THE OUTSIDE. ALL FLASHING BUILT INTO WALLS SHALL BE LAPPED AND SEALED. REFER TO FLASHING
OPEN TO DETAILS INDICATED.
A-2.2G A-2.4H
BELOW 16. REFER TO BUILDING ELEVATIONS AND ELEVATION DETAILS FOR MASONRY PATTERNS.
ROOF BELOW 17. INCLUDE PROJECTIONS, BEAM ENCLOSURES, RECESSES, BULKHEADS, PILASTERS AND SIMILAR ENCLOSURES

L18 10 10
18.
AS PART OF WALL AND CEILING FINISHES AS SCHEDULED.
ALL APPURTENANCES BUILT INTO OR THROUGH WALLS, INCLUDING DOORS, DUCTS, WINDOWS, LOUVERS,
GP# 21553
A-2.2H GRILLES, MECHANICAL WORK, ETC. SHALL FIT TIGHT AND BE THOROUGHLY SEALED AROUND PERIMETERS.
L18 WORK AT EXTERIOR WALLS SHALL BE FLASHED OR OTHERWISE WATERPROOF SEALED.
A-2.4G 19. SEE FURNISHING PLANS (A-9 SERIES) FOR CASEWORK, CABINETS, LOCKERS, DISPLAY BOARDS AND CASES
AND SIMILAR ITEMS.
G18 20. FIELD CHECK ROUGH AND/OR FINISHED DIMENSIONS FOR ACCURATE FITTING OF CABINETS, COUNTERS,
A-2.2H LOCKERS, DOORS, WINDOWS, FIXTURES, SHELVING, GATES AND OTHER INSTALLATIONS PRIOR TO SHOP OR
G18 FACTORY FABRICATION. PROVIDE FILLER STRIPS, SCRIBE STRIPS, BASES, CLOSURE FINISHES AND TRIM FOR A
A-2.4G COMPLETE INSTALLATION.
21. PROVIDE APPROPRIATE TRANSITION STRIPS AT CHANGES IN FLOOR ELEVATIONS.
E A18
A-4.1
22. EACH CONTRACTOR SHALL REFER TO MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS AND BE
RESPONSIBLE FOR WORK PERTAINING TO THEIR PARTICULAR TRADE. ALL CONTRACTORS SHALL COORDINATE
E
11 11 THE WORK OF ALL TRADES AND FIELD CHECK AGAINST ANY CONFLICTS BETWEEN DRAWINGS. REPORT
CONFLICTS TO THE ARCHITECT FOR CLARIFICATION.
ELECTRIC DIVIDER CURTAIN 23. REFER TO PLUMBING, HVAC AND ELECTRICAL DRAWINGS FOR LOCATIONS AND DESCRIPTIONS OF ACCESS
PANELS, LOUVER OPENINGS, VENTILATORS, GRILLES, VALVE CABINETS, FIRE DAMPERS OR OTHER
APPURTENANCES AFFECTING WALLS, CEILINGS OR FLOORS. PROVIDE NECESSARY LINTELS, SUPPORT AND
11.4 ANCHORAGE. SEE STRUCTURAL NOTES FOR LINTEL REQUIREMENTS.
24. REFER TO MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR LOCATIONS OF CONCRETE PADS TO BE
PROVIDED BELOW OR AROUND EQUIPMENT.
25. INSTALL ELECTRIC SWITCHES, OUTLETS, THERMOSTATS, CONTROLS, CLOCKS, SPEAKERS, FLAGPOLE HOLDERS
A18 AND OTHER WALL-MOUNTED ACCESSORIES IN LOCATIONS WHICH ARE UNOBSTRUCTED BY CABINETS,

82' - 0"

OVERALL PLAN - SECOND FLOOR


A-4.2 COUNTERS, RACKS, DISPLAY BOARDS, FIXTURES, SHELVING OR OTHER FURNISHINGS OR EQUIPMENT

CITY OF BALTIMORE, MARYLAND


DESIGNATED FOR SPACES SHOWN ON DRAWINGS. THESE DEVICES ARE SHOWN ON THE ARCHITECTURAL
DRAWINGS TO ALERT OTHER SUB-CONTRACTORS OF THEIR PRESENCE. COORDINATE INSTALLATION WITH THE
MECHANICAL ELECTRICAL DRAWINGS. ADVISE THE ARCHITECT OF CONFLICTS IN LOCATION OR TYPES OF DEVICES SHOWN
12 UP ROOM - GYM PRIOR TO INSTALLATION. DO NOT INSTALL WALL-MOUNTED ITEMS ON, THROUGH OR INTO ANY EQUIPMENT
D A1
2501 UNLESS INDICATED. D
26. MOUNT ELECTRIC SWITCHES, THERMOSTATS AND OTHER ELECTRONIC CONTROLS LOCATED IN THE SAME

HOLABIRD ACADEMY PK-8


OPEN TO VICINITY AT THE SAME HEIGHT ABOVE FINISHED FLOOR IN A UNIFORM, ORDERLY FASHION UNLESS NOTED
BELOW OTHERWISE.
A2

A3
KEY PLAN
13 A4 13

138' - 1 5/8"
C A5
ENTRY CANOPY
C
BELOW
ROOF BELOW

AREA B AREA C

EX4 EX4
DATE DESCRIPTION

H18 L18 H18 L18


A-2.1G A-2.1G A-2.1H A-2.1H

B B
AREA A
EXB F G.2 G.9 H J J.1 K N Q EXC

SECOND FLOOR TOTAL AREA:


31,027 SF
Scale: 1 inch = 16 feet
A-0.6
OVERALL SECOND FLOOR PLAN 03/13/2017
A14 1/16" = 1'-0" BID SET
0 8' 16' 32' 48'
A N © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

8" SLAB - (6" CONCRETE ON 2" COMPOSITE DECK)


ACOUSTICAL SEPARATION BETWEEN CLASSROOM AND
MECHANICAL ROOM BELOW

M M

L L

UP
UP

K DN
K
DN

SOUND ISOLATION BETWEEN MEDIA CENTER


AND MUSIC ROOMS
A4
A-0.8 8" SLAB - (6" CONCRETE ON 2" METAL DECK) AT MECHANICAL FLOOR SLAB
AT SECOND FLOOR. REFER TO MECH DRAWINGS FOR SOUND ISOLATION
OF MECHANICAL EQUIPMENT
ACOUSTICAL ROOF
DECK ABOVE, TYPE 2
COMPOSITE

J ACOUSTICAL SEPARATION BETWEEN MUSIC ROOM,


PLATFORM AND MECHANICAL ROOM ABOVE
J
PARTITIONS AT REHERSAL ROOMS
NRC 50-55

UP
H H

www.grimmandparker.com
11720 Beltsville Drive

Calverton, MD 20705
Tel: 301.595.1000
ACOUSTICAL WALL PANEL ACOUSTICAL WALL PANEL TREATMENT AT
TREATMENT AT CORRIDORS (AWP2). DINING AND CORRIDOR. REFER TO ELEVATIONS

Suite 600
REFER TO ELEVATIONS.

G G

ACOUSTICAL ROOF DECK


IN GYMNASIUM
ACOUSTICAL ROOF
DECK ABOVE, TYPE 1 NON-COMPOSITE
UP UP

ACOUSTICAL SEPARATION BETWEEN OFFICES 8" SLAB - (6" CONCRETE ON 2" COMPOSITE METAL DECK) AT
F AND MECHANICAL ROOM ABOVE MECHANICAL FLOOR SLAB AT SECOND FLOOR. REFER TO MECH
DRAWINGS FOR SOUND ISOLATION OF MECHANICAL EQUIPMENT
F
ACOUSTICAL PANEL
TREATMENT AT WALLS (AWP1),
REFER TO ELEVATIONS

GP# 21553

E E
FDC

OVERALL FIRST FLOOR ACOUSTICAL PLAN OVERALL SECOND FLOOR ACOUSTICAL PLAN
E17 E9

ACOUSTICAL ATTENUATION DIAGRAMS


1" = 20'-0" 1" = 20'-0"

CITY OF BALTIMORE, MARYLAND


45-50 STC RATING

D D

HOLABIRD ACADEMY PK-8


A2
X4 X4

RECOMMENDED REVERATION RECOMMENDED STC VALUES FOR TYP. ACOUSTICAL LAY-IN


TIMES FOR UNOCCUPIED SPACES PARTITIONS N1
CEILING PANELS

ADJACENCY RECOMMENDED RT60 (SECONDS) ADJACENCY RECOMMENDED STC N1


RANGE
PRIVATE OFFICE 0.4 - 0.6
LOBBIES / RECEPTION AREAS 0.6 - 1.0 GYMNASIUM CORRIDOR 35 - 40
C GYMNASIUM
DINING ROOM
1.0 - 1.5
< 1.0
DINING ROOM 50 - 55
M1
C
COMMUNITY LEARNING CENTER CONFERENCE ROOM 50 - 55
RESOURCE ROOMS 0.4 - 0.6 CORRIDOR 35 - 40
CLASSROOMS 0.4 - 0.6 CONFERENCE ROOMS RECEPTION AREA 50 - 55 TYP. SOUND BLOCKING WALL
COLLABORATIVE LEARNING AREAS 0.6 - 0.9 PRIVATE OFFICE 50 - 55 CONSTRUCTION ASSEMBLY BETWEEN
MEDIA CENTER 0.6 - 0.9 N1 CLASSROOMS; TOP OF WALL
CORRIDOR 50 - 55 M1 :
REHEARSAL ROOMS 0.6 - 1.0 TERMINATES AT BOTTOM OF DECK. DOUBLE LAYER ABUSE
DINING ROOM PRIVATE OFFICE 50 - 55
CONFERENCE ROOMS 0.3 - 0.5 M1 SEE A-3.20 FOR WALL TYPES AND RESISTANT GYP. BD. WALL AS
RESTROOMS 50 - 55
COMMUNITY LEARNING CENTER 0.6 - 0.9 TERMINATION DETAILS SHOWN (STC RATING 55,
MECHANICAL* 60 - 65 DATE DESCRIPTION
LOUNGES 0.6 - 0.9 PRIVATE OFFICE PRIVATE OFFICE 45 - 50 MIN.) NOTE: STAGGER HORIZ.
STUDIOS AND LABORATORIES 0.5 - 0.9 RESOURCE ROOM 45 - 50 AND VERT. GYP. BD. JOINTS
CORRIDOR 40 - 45
RECEPTION AREA 45 - 50 REFER TO PARTITION TYPE
RESTROOMS 50 - 55
REHEARSAL ROOM REHEARSAL ROOM 50 - 55 X4 X4
CLASSROOMS/ LABS 45 - 50
B CLASSROOMS / LABS
CORRIDOR
CLASSROOMS/ LABS
50 - 55
45 - 50
B
RESTROOMS 50 - 55
CORRIDORS 45 - 50
RESOURCE ROOMS
MECHANICAL ROOMS*
45 - 50
60 - 65 TYPICAL CLASSROOM ACOUSTICAL TREATMENT
A4 1/8" = 1'-0"

DRAWINGS ON THIS PAGE GRAPHICALLY ILLUSTRATE AREAS OF


SPECIALIZED ACOUSTICAL TREATMENT. REFER TO
SPECIFICATIONS AND OTHER DRAWING SHEETS FOR DETAILED
A-0.8
INFORMATION. 03/13/2017
BID SET
A N © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

A15 / A-1.3
F1 X3 G.9 K18
A-4.2a A3 A-4.1 D10

A15 / A-1.2
EXB DD F J K L.6 AA M.1 N Q E18 A-2.3H EXC
F12 L6 A-4.2
A-4.2a A-5.5
32' - 9 1/8" 24' - 8 3/4" 13' - 5" 11' - 8 3/4" 22' - 4" A-6.1 E13 8' - 8" 8' - 0" 20' - 8" 28' - 3 1/2"
10

0"
EE A15 0.0 11' - 3 5/8" 11 5/8" 16' - 9 5/8" 14' - 5 5/8" 10' - 6 3/8"

10' -
SF12D 0°
D9 A-4.3
15
A15 / A-1.3
LARGE
A-2.1H A-6.1 REHEARSAL

3' - 4" 2' - 9 5/8"


A3 E4
A-6.4 1703
M 10' - 8" 4' - 0"
X23
C12 A3
WATER
M
A3 E10 LOCKERS/SHOWER/
° A2 A2 A2
.00 SERVICE FIRE PUMP

8' - 5 1/4"
1' - 1 3/4" 15 X12

6' - 8"
E11 TOILET
110 1703 A1 1404

8 1/4"
M1 1400 1402
SF6 A2

1' - 1 3/4"
A3 A2 NOTE 1
A3

10 7/8"
1402

5' - 0" 7 3/4"


8 1400 1404 8

6' - 0"
X2
9' - 6 1/4" 23' - 7 11/16" CORRIDOR NOTE 1
X2 A3 C140
7' - 0"

7' - 0"
L

24' - 8 7/8"
M1

9' - 1 5/8"
1' - 1 1/4" 42' - 10 1/4" C140 18' - 5 1/4" 6' - 11 5/8" 11' - 5 5/8" 13' - 10 1/4"
OUTDOOR A2

FEC
STORAGE CONFERENCE

4' - 4"
X24 1201 M1 ST51 1403
8.2 E101 8.2
1' - 4" STAIR 5 EMERGENCY

22' - 8"
A2 A2 CUSTODIAL

5' - 0"

1' - 4 1/4"
A15 / A-1.2 A3 ST51 ELECTRICAL

7' - 5 5/8"
3' - 4" 2' - 3"

A3 PLATFORM A3 1403 ELECTRICAL


N1 UP 1405 A2 1405
STORAGE A2 1407
OUTDOOR

9' - 0"
E2 N1 WAITING/RECEPTION 5' - 9 1/4"
L X25 STORAGE 12B 1200 1304A
1304A
A4 A4
NOTE 1
A2
NOTE 1 L

28' - 10"
E102 11 A2 A3
1201 PLATFORM CENTRAL

5' - 4 7/8"
12A A5
4' - 9"

1304 17' - 0" STORAGE

13' - 1 1/8"
A2 E2 RAMP 2 A-5.3 1407
21' - 10"

21' - 10"
4" 1200 A2 A3 NOTE 1 1406
RA21 A2 2' - 5 5/8" FE
A6 A4 A2
CORRIDOR NOTE 1 J15
A-3.8
4' - 0"

SOCIAL C120 5' - 0" 2' - 11 5/8" FURNITURE A-5.5


SF6 HEAD END A2

11' - 4 1/8"
WORKER RECEIVING X11
8' - 9 7/8"

STORAGE

14' - 4 1/8"
1204 ROOM A3

6' - 4"
1406

8' - 10 5/8"
1204 CUSTODIAL 1303 A2 A2 1408x
1202 1202 FLOOR MAT
2 A2 A2 1302A 1' - 4"

5' - 11 5/8"
NOTE 1 ENTRYWAY

13' - 11 5/8"
NOTE 1
5' - 4"

1302A UP
UP TOILET A2 SYSTEM,
A1 0"

5' - 0"
1410 6 LOCKERS SURFACE
RECORDS A3 A1 1412B 3
LOCKER

4' - 0"
STORAGE 1303 A5 1410 1408

1' - 6 1/8"
A12 9 D18 A2 1410A 9
2' - 0"

2' - 0"
1203 OPERATIONS
4' - 0"

SF6 A-5.6 1410A


A1
8' - 8 7/8"

1' - 7 1/8"
A-4.3 1205 OFFICE
K 9.1 PSYCHOLOGIST 9.1
K

8 1/4"
1203

8' - 1 5/8"
16' - 0 5/8" 17' - 7 5/8" 1' - 3 1/4"

4' - 0"
1205 A5 A2 1408 L18
A3 23' - 0" SF3
2 A-2.4H

5' - 0 7/8"
CORRIDOR
MEN A1 DISH/TRAY 1' - 9" A1 A2 A2
5' - 4"

UP 1419
MECH 1302 A2 1300A RETURN

4' - 0"
A5 NOTE 1

7' - 4 7/8"
1206 1409

10' - 5 5/8"
A1 A1 A4 WOOD STEPS 3 RISERS 1414 OFFICE

4' - 0"
TOILET 1414 SOAP CAN WASH
A-5.5 1409 E100
1206 1411 STORAGE

6' - 5 5/8"
FLEX OFFICE 1301A A2
4' - 0"

3' - 4"
8' - 8 7/8"

1207 1301A 1411 X10


SF6 1207 0" A2
A2 A1 A2

FE
5' - 0"
2 ELECTRICAL NOTE 1

27' - 11"
A-6.3 4' - 0"

26' - 4 7/8"
1208 1208 6' - 4 7/8" A1 F18 D18 A2
25' - 11"

25' - 11"
5' - 4"

15 A2
5' - 4 7/8" 7' - 5 7/8" WOMEN 31

5' - 10"
G5 G18
1301 1' - 4" 3' - 4" 3' - 9 5/8" 5' - 5 5/8"
A-4.6 A-2.4H
OFFICE
8' - 8 7/8"

1209 A1 5' - 5 5/8"


4' - 0"

SF6 1209

10' - 8"
1210 STAFF TOILET A2 2' - 6" 1413A
H5
J 2 1210 STORAGE A2 WALK-IN J
1010 WONDERWALL 3' - 0" WONDERWALL COOLER
X2

24' - 8"
116' - 0"

5' - 4"

14' - 6 7/8"

REF: D18/A-6.3 REF: K11A-6.4 A-6.4 1415


K11 H10
1' - 2"

W D KITCHEN

14' - 10"
PERSONAL 1412

1' - 3 1/2"
LAUNDRY CARE J6 K5
8' - 8 7/8"

L18 10 OFFICE 1211 STAFF TOILET 10


6' - 10 7/8"

X2

1' - 8"
1011 1012 A-5.5
4' - 0"

A-2.2H 1211 1009


2 A4
SF6
A-5.6 SERVING WALK-IN
C100A 30B
1009 1010 1011 1012 1413 FREEZER
5' - 4"

2 1413 1416

10' - 8"
CORRIDOR
5' - 4 7/8"

K1
C100 C100
FLEX OFFICE K1 D15
8' - 8 7/8"

1008 A3 A9 30A DINING


1008 A-5.5
1300 X9
4' - 0"

SF6 2 A-4.6
REF.

A3 2' - 0" 3' - 6" 11' - 2 3/4"


G18 A1
27' - 0 1/4"

4' - 11 1/2"

27' - 0 1/4"

27' - 0 1/4"
STORAGE
H H

26' - 4"

www.grimmandparker.com
6' - 5 1/2"
A-2.2H K1 EXAM/TREATMENT 1102A A2
X2 EXAM/TREATMENT HEALTH A2 A1
10' - 6 1/8"

1106 NOTE 1
5' - 4"

1104 OFFICE 1102A

11720 Beltsville Drive


12' - 0 1/8" 5' - 4 7/8"

Calverton, MD 20705
K1

8"
K1 1102 O.H. COUNTER DOOR 1417
FLEX OFFICE

REF.
8' - 8 7/8"

Tel: 301.595.1000
1007 2 A13 A2
20 DRY

14' - 0"
GYM
STORAGE
4' - 0"

SF6 1007 A-4.6 BUILDING AS A LEARNING 1271 PANTRY OFFICE STORAGE A1 NOTE 1 STORAGE

10' - 6 3/4"
9' - 9 1/4"
1106 1104 1102 LAB "CUTAWAY WALL" 1418 1503 1504 A2 1417 A5 1805E
A18 4 21 A5 1300B CONSTRUCTION DISPLAY

7' - 4 1/4"
WAITING A5
5' - 4 7/8"

K1 1504

Suite 600
CORRIDOR A-4.6 2' - 2" 2' - 0"
A-4.1 K1 CORRIDOR 1100
K1 1100B
5' - 4"

C100 E6 G2 1418 G2
C110 1100A
5"

1006 X2 7 5/8"
11 1300C 1503 1500B 11
12' - 8 7/8"

REF. REST AREA REST AREA 1101


PRINCIPAL 2 2
4' - 0"

10' - 2 7/8" FEC

SF6 WORKROOM 1105 1103

5"
1006 6' - 4" CW4
1002 X2 CORRIDOR
A15
11' - 6 7/8"

C131

6' - 5"
STUDENT
G G
11' - 9 3/4"

A-5.5 12' - 7 15/128" 1' - 3" 11' - 0 1/4" 8' - 4 7/8" 9' - 7 7/8" 35' - 5 1/2" A18 11 1/8"
5' - 4 7/8" 14' - 3 7/8" 17' - 7 3/16" TOILET
K1 1101 A18 7' - 6 7/8" 3' - 1 1/128" A-4.4 X8
6 7/8"

2' - 2 3/8"
1' - 2 3/16" X2 1500
K1 A-4.6 J.1 A2 A2
A2 3
3 G2
SECURE 1002 CORRIDOR 1501 1511
7' - 2 7/8"

11.4 STORAGE 2 A3 C130 BASKETBALL BACKSTOP BASKETBALL BACKSTOP

27' - 1 1/4"
1005 2' - 11 1/8" 5' - 6 5/8" 1000C 1000B
K1 1005 SECURITY
A4 A1 P.E. OFFICE

9' - 1 5/8"
SF13 2 2 16 OFFICE A1 A5
21 A2 1511
1004 1003 1001 RECEPTION A-4.5 C130A C130B 1501 9
CLOSET A-4.4
1000 A2 A2
1003

A18 18 BASKETBALL BACKSTOP BASKETBALL BACKSTOP


19' - 3"

21' - 4 1/2" 11' - 1 5/8" 7' - 6 3/4" 2' - 8 1/2" VESTIBULE


13' - 5"

A-4.2 SF14 1500D

F CONFERENCE
1004
A.P. OFFICE
1001
COUNTERTOP AND
MILLWORK FOR
RECEPTION DESK
21
V1806
KEY NOTES FOR PLANS F
ST6 1. WALLS EXTEND TO 10'-8" AFF
N1 18 FLOOR SLEEVE, TYP. J13
ACCESS FOR SHUT- 1000A STAIR 6

1 1/2"
GYMNASIUM
OFF VALVE ST6 1805G 1500
1' - 1 3/4"

A3 DEDICATION

61' - 11 3/4"

61' - 11 3/4"
A-6.2
G.2
GP# 21553

45' - 11"
UP LOCKERS/SHOWER/TOILET A9 A18
PLAQUE AND LEED
GENERAL PLAN NOTES
2' - 5 1/4"

12 1805G

25' - 2 7/8"
PLAQUE
7 1/4"

SF6 SF6 SF6 SF6 DS FROM CANOPY E13


SF7
GUTTER A15 A17
A1 GENERAL NOTE APPLICABLE TO ALL DRAWINGS - ITEMS AND CONDITIONS DETAILED, NOTED OR OTHERWISE IDENTIFIED ON
A-4.5 A-5.3 ONE OF THE SECTIONS OR DETAILS ARE APPLICABLE AND BINDING TO ALL OTHER SECTIONS AND DETAILS FOR IDENTICAL
1' - 1 3/4" 6' - 2 1/4" 4' - 0" 6' - 0" 4' - 0" 6' - 0" 4' - 0" 6' - 0" 4' - 0" 4' - 0" 12' - 0" A2 PAINTED WALL GRAPHIC OR SIMILAR CONDITIONS.
"RULER", SEE INTERIOR ELEVATIONS
VESTIBULE 1. REFER TO SHEET A-3.20 FOR WALL TYPES AS REFERENCED ON PLANS WITH THE DIAMOND SYMBOL. UNLESS
59' - 3 3/4" V100
X1 1805F REFERENCED OTHERWISE, ALL INTERIOR CMU WALLS ARE THE TYPE A2 AND ALL INTERIOR GYPSUM BOARD
A8 WALLS ARE TYPE K1.
0" LOCKERS/SHOWER/TOILET RESTORED AND
A-5.5 2. UNLESS NOTED OTHERWISE, WALLS SHALL EXTEND TO THE ROOF OR FLOOR DECK ABOVE AND BE SEALED IN
E A2
1805F
BASKETBALL BACKSTOP BASKETBALL BACKSTOP
RELOCATED RELIEF PANEL
ON THIS WALL IN HIGH
ACCORDANCE WITH THE WALL TERMINATION DETAILS. REFER TO THE CODE STUDY PLAN FOR IDENTIFICATION
OF ALL SMOKE AND FIRE WALL CONDITIONS. PERIMETER CORRIDOR AND LOBBY WALLS SHALL BE BUILT TO
E
PERFORMANCE PAINTED
RESIST THE PASSAGE OF SMOKE.
A12 WOOD FRAME
SEE NOTE ON A-0.5 3. REFER TO WALL SECTIONS AND DETAILS FOR EXTERIOR WALL TYPES AND CONSTRUCTION.
A-4.5 4. DIMENSIONS ON PLANS ARE FROM FACE OF MASONRY TO FACE OF MASONRY, FACE OF MASONRY TO FACE OF
A8 LOCKERS/SHOWER/TOILET GYPSUM BOARD OR FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD.
CW1A X2 1805H 5. COLUMN GRID LINES ARE FOR REFERENCE ONLY, REFER TO STRUCTURAL DRAWINGS FOR COLUMN LOCATIONS.
A-1.11
6. REFER TO FURNISHING PLANS FOR CASEWORK, MILLWORK DISPLAY BOARDS, SHELVING UNITS, TV MOUNTING
44' - 0"

PARTIAL FIRST FLOOR PLAN - AREA A


A3 BRACKETS, LOCKERS, FURNITURE, ETC. (A-9 SERIES).
DIVIDER CURTAIN 7. FEC - INDICATES A FIRE EXTINGUISHER WITH A RECESSED CABINET. FE - INDICATES A FIRE EXTINGUISHER
18' - 1"

A9 1805H WITH A WALL MOUNTING BRACKET.


8. UNLESS SPECIFICALLY INDICATED OTHERWISE, THE SAME WALL TYPE NEXT TO A DOOR OR OPENING SHALL

6' - 4"
A-4.5 CONTINUE OVER THE DOOR OR OPENING.
BLEACHERS

CITY OF BALTIMORE, MARYLAND


X3
A-6.5 VESTIBULE X7 9. PLAN LOCATION OF DOORS AND FRAMES RELATIVE TO THE PLANE OF THE WALL IS DIAGRAMMATIC ONLY. REFER
FLOOR MAT A8 TO THE REFERENCED JAMB AND HEAD CONDITION DETAILS TO DETERMINE ACTUAL PLACEMENT OF DOOR AND
V1600 1500C G2
ENTRYWAY G2 FEC FEC FRAME.
3' - 5 7/8"

SYSTEM, 2
10. REFER TO A-5 SERIES FOR TYPICAL MASONRY DETAILS.
D A4
RECESSED 1600
13
11. NOT USED D

HOLABIRD ACADEMY PK-8


12. ALL INTERIOR FACES OF ICF WALL (EPS FOAM) TO BE CONTINUOUSLY COVERED WITH 5/8" GYP. BOARD. ALL
FEC
1' - 7 5/8"

1600B PENETRATIONS SEALED.


CW1B CORRIDOR
ENTRY CANOPY ABOVE A13 13. PROVIDE CORNER GUARDS AT ALL OUTSIDE CORNERS OF STUD WALLS AND INTERIOR ICF WALLS WHERE
C160
4' - 0"

CLOSET ROD GYPSUM BOARD IS EXPOSED.


FIRE ALARM ANNUNCIATOR SF6 COUNTER OVERHEAD
AND SHELF A-4.4
PANEL AND PV REMOTE A18 COILING DOOR 2 N1 3 A9
18 2
SHUTDOWN BUTTON A-4.5 1606 CLOSET 1604 1609 1607 1601
4' - 0"

A5 A-4.4

STEEL COLUMNS AND ROOF OFFICE


1606 1608A
REF.
CUSTODIAL
1609
TOILET
1607
11' - 6 3/4"
COMMUNITY
KEY PLAN
7' - 10 1/8"

PANTRY J13
7' - 0"

1603

27' - 9 5/8"

27' - 9 5/8"
FRAMING WITH HIGH LEARNING
4' - 0"

SF6

25' - 10 3/4"
DS FROM CANOPY 1603 1608 A-5.5
PERFORMANCE EXTERIOR 1' - 10 1/4" N1 CENTER
COATING, TYPICAL AT CANOPY GUTTER 1608 1600
2 CONFERENCE
FAMILY
3' - 4"

1601
4' - 0"

CORRIDOR RESOURCE
C161 ROOM 5' - 9 3/4" 2' - 2 5/8"
C OFFICE
1604 C

2' - 8 1/4"
A16
4' - 0"

1602
10' - 8"

SF6 1605
19' - 2 1/4"

1602 OFFICE
8' - 10 1/4"

1605 A-4.4
2 2 X2
1' - 1 3/4"
REF.

10' - 3 5/8" 5' - 4 7/8" 29' - 6 5/8" 23' - 2 1/8"


5' - 4"

N1
AREA B AREA C
1' - 1 3/4"

1' - 1 3/4"
EX4
X5
1' - 1 3/4"
FDC X6 DATE DESCRIPTION
SF6 SF6 SF6 SF6 SF6 SF6 SF8
1' - 7 3/4"
59' - 9" 12' - 9 5/8" 12' - 8" 3' - 4" 6' - 0" 4' - 0" 6' - 0" 4' - 0" 6' - 0" 4' - 0" 6' - 0" 4' - 0" 6' - 0" 4' - 0" 6' - 0" 4' - 0" 6' - 0" 4' - 0" 6' - 0"

32' - 9 1/8" 10' - 3 3/4" 14' - 5" 13' - 5" 11' - 8 3/4" 22' - 4" 8' - 8" 8' - 0" 20' - 8" 28' - 3 1/2"
B B
18 H18 L18 AREA A
A-2.1G
F12
F12 A-2.1H A-2.1H
EXB F G.2 G.9 J J.1 K A-4.1
A-4.1 L.6 M.1 N Q EXC

PARTIAL FIRST FLOOR PLAN - AREA A


A16 1/8" = 1'-0" A-1.1
Scale: 1 inch = 8 feet 03/13/2017
BID SET
A 0 4' 8' 16' 24' 32' N © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

L18 G18
A-2.3H A-2.3H

EXA A B C D D.7 E G G.7 G.9 H

28' - 3 1/2" J10 15' - 5" 13' - 5" 9' - 0 3/4" 17' - 10" 6' - 2" 20' - 8" 13' - 11" 5' - 8" 2' - 5"
EXA
M J10 A-4.2
M

A15 / A-1.3
1' - 3 3/4" A-4.2
36' - 3 1/4"
A15
14' - 0" 55' - 4" 65' - 0"
A-4.9
14' - 0" 22' - 3 1/4" 5' - 4" 20' - 0" 20' - 0" 5' - 4" 4' - 0" 20' - 0" 6' - 0" 4' - 0" 6' - 0" 20' - 0" 5' - 0"

Sim A18
1' - 6 3/8" Sim

1' - 3 3/4"
A4 A8 A-4.8
SF1 SF2 SF2 SF1 A-4.3 A-4.3

1' - 3 3/4"
A15

1' - 7 1/4"
EX1 EX1 EX1
A-4.8

1' - 3 3/4"
3' - 0"
X2 1' - 3 3/4"
A18

6' - 8"
L A-4.9 A18
1' - 10 1/8" 24' - 6 9/16" ALIGN GYP. BOARD
SF1 SF2 SF5 SF2 SF1
CW3 L
A-4.3
15' - 4"

15' - 4"
GEOTHERMAL

3 1/4"
EX2 EX2

13' - 1 1/2"
3' - 0 1/4"
PUMP ROOM 1' - 3 3/4"
A18 A18
0001
1' - 7" A-4.9 X20

24' - 11 1/4"
A-4.3 1 1
M1

9' - 8 7/8"
7' - 0"

7' - 8 7/8"
25' - 9 1/8" 11' - 0 7/8" ALIGN GYP. BOARD 0"
-12' - 6" VESTIBULE
CW2 M1 C15A
FE KILN 1721A
GRADE 1
1811 1721A L17
4' - 0"

1' - 2" 5' - 7 1/2"


PK-2 TOILET 1807A

1' - 2"
5' - 0 5/8"
1807A SF15
7' - 11"

7' - 2 7/8"
CORRIDOR
001A ST21A A-6.4
F17 G17 C172D

5' - 7"
1805A PK-2 TOILET

29' - 4 1/4"
0001 0001A A3 X2

26' - 7 1/4"
1805A
48' - 0"

J17
K K

5' - 2"
-12' - 6" PK-2 TOILET GRADE 1 GRADE 3 ART STUDIO
1' - 0"

1811A 1811A J8 1721B 1721 3' - 7 5/8"


1807 1805
LINE OF SLAB ON GRADE A-5.5
TO COMPOSITE DECK ART STORAGE
STAIR 2 MECH
ST20 A5 TRANSITION 1809 N1 A11 1721B
32' - 8"

32' - 8"

14' - 8"
A-5.2 A-5.5
G1
E3

1' - 10 1/4"
A10 7' - 2 3/4" 10 1/4" X2 X2
UP X2
23' - 0 3/4"

N1
UP A-5.2 UP A2
X2

2' - 6 7/8"
2 A1 2
29
1811 1809 1807
UP

5' - 0"
6' - 10"
STAIR 2 3 3 N1 MECH A2 A1

1' - 2"
A2 A1 A1 1721

8' - 0"
1805

6' - 1 3/4"
4' - 0"
ST21 1801

6' - 0"
ST21 A2
SF4
J J

2' - 7 1/2"
27 1721C
3 3 3
1801

4' - 0"
A2 CORRIDOR

10' - 0"
1' - 9 7/8" 5 A2 A2 A2 6 A1 A2 A1 C172
15' - 3 1/4" 21' - 0" CORRIDOR
MECH. UNIT, SEE MECHANICAL K18

10' - 0"
1' - 9 7/8" 16' - 7" 1' - 5 1/8" 4' - 4" 1' - 10" C180 25' - 9" C172B 10' - 0" 7 7/8"
0"

1' - 6 1/2"
A9 6"
107' - 4"

A2 9" J3 A-6.3
A-4.8
13B A2 10 A1
COLLABORATIVE

20.00°
A2
25' - 7 1/4"

1802 1720 1800 H16


4' - 0" LEARNING
20' - 0"

A5 1820 A2 C172A
A-4.8 E2
PLANNING CUSTODIAL

FEC
11' - 3 3/4"
13A N1

12' - 3 3/4"
1802 E2 1720 A2

13' - 4 5/8"
RESOURCE ELECTRICAL TELECOM/UTILITY

1' - 1 7/8"
D18 1800 A3
H SF10 1804
H

www.grimmandparker.com
9' - 1"
A-2.2H A-6.3 1806 1804
H18 1806
A2 13' - 7 1/8" 5' - 11 5/8" 16' - 6 3/8" 5 5/8"

1' - 0 5/8"

11720 Beltsville Drive

Calverton, MD 20705
A2
PARTIAL BASEMENT FLOOR PLAN - AREA B

19' - 5 5/8"
2' - 3 1/8" A2

Tel: 301.595.1000
3 A2 3 3 X4 1803 DEMONSTRATION
G18 1/8" = 1'-0" 4
1813 1812 1810
FEC
1808
X4
X2 A2 X2
SP. ED.
WINDOW
INTO PIPE CHASE 4

7' - 5 1/2"
X2 G8
STORAGE ELEVATOR
A-5.5 32

1' - 11 1/2"
7' - 4 3/4"

Suite 600
X2 MECH X4 STAFF TOILET1803A N1 1711A E1

5' - 1 5/8"
9' - 3 3/4"
1812 X4 M1 1803A
N1 A4
N1 M1 1802B 1711A A-5.4
1802A
5 5

7' - 10 3/4"
1' - 7"

1' - 3 5/8" STAFF TOILET SP. ED. ST11A


PK-2 TOILET

9' - 6"
1808A 1802B OFFICE
PK-2 TOILET 1810A 1808A 1711
5.1 GRADE 2 5.1
G G
5' - 7" 1' - 2 1/2" 5' - 2"
1810A
1810 N1 1711 J18

REF.
A13
A-5.5 L18 G18
GRADE 2 A-5.5 A-6.5
GRADE 3 2' - 9 1/8" 5' - 4" 3' - 3 3/4" 4' - 8 5/8"
39' - 4"

Sim 1813 X2 1710 J5


A14 1808 OT/PT
PK-2 TOILET A-6.1 FACULTY
1813A L6 L15 1710

15' - 9 1/2"
A-5.6 1813A J9

13' - 10 5/8"
LOUNGE CORRIDOR
26' - 0 3/4"

A6
1803 C171 A-5.1
L10 A12 G15
STORAGE
5' - 8 3/8" A-5.5
1802A A-4.9 A3
2' - 4 5/8" 6' - 11 3/8"
F1 N1 N1
A-4.2a A8
1710A F12
M1 M1 N1 K1 1710B TOILET A-4.2a A-4.9
F F

6' - 3 7/8"
28' - 0 3/8" 26' - 0" 26' - 6 5/8" 14' - 6 1/8" 7' - 5 1/4" 3' - 2 5/8" OT/PT 8' - 4 1/4" 1710A
STORAGE
5.8 X4 1' - 8" 5.8
1710B
X1
1' - 3 3/4"
2' - 9"

EX3 ST11 EX3


GP# 21553

6 1/4"

2"
SF2
GENERAL PLAN NOTES

70.
1' - 3 3/4" SF1 SF2 SF1 CW5

00°
6 A18 6
BASE BID DOWNSPOUT GENERAL NOTE APPLICABLE TO ALL DRAWINGS - ITEMS AND CONDITIONS DETAILED, NOTED OR OTHERWISE IDENTIFIED ON
6' - 4" 8' - 0" 12' - 0" 6' - 8" 20' - 0" 6' - 8" 20' - 0" A-4.7 X2

"
8 5/8
TO BOOT AND ONE OF THE SECTIONS OR DETAILS ARE APPLICABLE AND BINDING TO ALL OTHER SECTIONS AND DETAILS FOR IDENTICAL
SIDEWALK PATH WORKROOM/STORAGE OR SIMILAR CONDITIONS.
ADD-ALTERNATE RAIN BUILDING EXPANSION JOINT 1701
CISTERN SYSTEM WITH J18 4 1701
A8 1. REFER TO SHEET A-3.20 FOR WALL TYPES AS REFERENCED ON PLANS WITH THE DIAMOND SYMBOL. UNLESS
REINFORCED SLAB A4 A-4.7 X2 REFERENCED OTHERWISE, ALL INTERIOR CMU WALLS ARE THE TYPE A2 AND ALL INTERIOR GYPSUM BOARD
A-4.3 A-4.3 X2 WALLS ARE TYPE K1.

"
1/2"

5' - 0
A3 2. UNLESS NOTED OTHERWISE, WALLS SHALL EXTEND TO THE ROOF OR FLOOR DECK ABOVE AND BE SEALED IN
E SF12B
E

1' - 8
ACCORDANCE WITH THE WALL TERMINATION DETAILS. REFER TO THE CODE STUDY PLAN FOR IDENTIFICATION
27' - 6"

F6 OF ALL SMOKE AND FIRE WALL CONDITIONS. PERIMETER CORRIDOR AND LOBBY WALLS SHALL BE BUILT TO
D18 1' - 1 MEDIA RESIST THE PASSAGE OF SMOKE.
A-2.1H A-4.2a 1" 3 3. REFER TO WALL SECTIONS AND DETAILS FOR EXTERIOR WALL TYPES AND CONSTRUCTION.
' - 5" CENTER K1 X1
4. DIMENSIONS ON PLANS ARE FROM FACE OF MASONRY TO FACE OF MASONRY, FACE OF MASONRY TO FACE OF

"
1700

2
A16

11 1/
A3 GYPSUM BOARD OR FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD.
A-4.7 21 5. COLUMN GRID LINES ARE FOR REFERENCE ONLY, REFER TO STRUCTURAL DRAWINGS FOR COLUMN LOCATIONS.

12' -
6. REFER TO FURNISHING PLANS FOR CASEWORK, MILLWORK DISPLAY BOARDS, SHELVING UNITS, TV MOUNTING

2"
E6 1700

PARTIAL FIRST FLOOR PLAN - AREA B


BRACKETS, LOCKERS, FURNITURE, ETC. (A-9 SERIES).

13' -
7. FEC - INDICATES A FIRE EXTINGUISHER WITH A RECESSED CABINET. FE - INDICATES A FIRE EXTINGUISHER
X3 C8 WITH A WALL MOUNTING BRACKET.

1/2"
A-6.4 8. UNLESS SPECIFICALLY INDICATED OTHERWISE, THE SAME WALL TYPE NEXT TO A DOOR OR OPENING SHALL
14B

1' - 8
CONTINUE OVER THE DOOR OR OPENING.

CITY OF BALTIMORE, MARYLAND


SF12B E17
7 7 9. PLAN LOCATION OF DOORS AND FRAMES RELATIVE TO THE PLANE OF THE WALL IS DIAGRAMMATIC ONLY. REFER
TO THE REFERENCED JAMB AND HEAD CONDITION DETAILS TO DETERMINE ACTUAL PLACEMENT OF DOOR AND
FRAME.
1' - 1 A12 X2 10. REFER TO A-5 SERIES FOR TYPICAL MASONRY DETAILS.
D 1"3' -
5 1/2
" A-4.7 11. NOT USED D

"
2

HOLABIRD ACADEMY PK-8


12. ALL INTERIOR FACES OF ICF WALL (EPS FOAM) TO BE CONTINUOUSLY COVERED WITH 5/8" GYP. BOARD. ALL

11 1/
14A PENETRATIONS SEALED.

13' -
13. PROVIDE CORNER GUARDS AT ALL OUTSIDE CORNERS OF STUD WALLS AND INTERIOR ICF WALLS WHERE

8"
A15 / A-1.3
GYPSUM BOARD IS EXPOSED.

14' -
A13
A3
A-4.2a

KEY PLAN
29' - 9 1/4"

32' - 9 1/8" 24' - 8 3/4"


0"

A15 X3
10' -

SF12D
A-4.3
15

A-6.4 A3
C12
C 10' - 8" 4' - 0"
X23 C
°
1' - 1 3/4" .00 E11 15
A16 / A-1.1 110
SF6 M1
1' - 1 3/4"

10 7/8"
8 8
6' - 0"

X2
9' - 6 1/4" 23' - 7 11/16"
X2
7' - 0"

M1 DATE DESCRIPTION

9' - 1 5/8"
OUTDOOR

FEC
STORAGE CONFERENCE
4' - 4"

X24 E101 1201 M1 AREA B AREA C


8.2 8.2
A2 A2
3' - 4" 2' - 3"

EXA A B C D EXB D.7 E F G G.7


N1
OUTDOOR E2 N1 WAITING/RECEPTION
B X25 STORAGE
E102
12B 1200
11
B
5' - 4 1201
"
12A
5' - 4 E2
" 1200
PARTIAL FIRST FLOOR PLAN - AREA B
A15 1/8" = 1'-0"
BB CC DD
EE AREA A

Scale: 1 inch = 8 feet


H
A-1.2
03/13/2017
0 4' 8' 16' 24' 32' BID SET
A N © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

G18
A-2.3H

G.9 H J K K.2 K.3 L L.6 M M.1 M.5 N P Q Q.2 R S T EXD

M M
2' - 5" 11' - 0" 11' - 8 3/4" 2' - 11 1/4"1' - 8" 9' - 6" 8' - 2 3/4" 7' - 7 1/4" 1' - 0 3/4"4' - 3 1/4" 3' - 8 3/4" 15' - 11 1/4" 4' - 8 3/4" 3' - 4" 12' - 9 1/4" 9' - 0 3/4" 7' - 8" 28' - 7 1/2"

A15 / A-1.2
Sim Sim
A15 A18
A-4.9 A-4.9
10' - 8" 65' - 0" 55' - 4" 14' - 0"

5' - 0" 5' - 0" 20' - 0" 6' - 0" 4' - 0" 26' - 0" 5' - 4" 20' - 0" 5' - 4"
K18 1' - 10"
Sim Sim Sim
A-4.1 A18 A8 A4
LINE OF PROTECTIVE 1' - 3 3/4" SF9 SF2 SF2 SF9
COVER/CANOPY A-4.8 A-4.3 A-4.3

1' - 3 3/4"

1' - 3 3/4"
A15

TYP.
ABOVE X18 X17
L EX1
A-4.8
EX1 L
1' - 3 3/4" 1' - 3 3/4"

15' - 4" 6' - 8"


SF2 SF9 1' - 1 7/8" 3' - 6 1/8"
CW3 ALIGN GYP. BOARD
X19
EX2 EX2

3' - 0 1/4"
X20 X2
1 1

24' - 5 1/4"
0" ALIGN GYP. BOARD 25' - 5" M1 26' - 9" 1' - 3 3/4"
VESTIBULE
CW2
C15A 3' - 9 1/2"
FLOOR MAT ENTRYWAY 1722A
SYSTEM, RECESSED 11' - 9 1/2" 27' - 10 7/8"
25' - 5 1/8"
SF15

19' - 5 3/4"
N1
K C172D K
SUPPLY D11
A17

26' - 7 1/4"
STORAGE/IT N1 A-5.5
ADMIN
A-6.4 1722A
3' - 7 5/8" A6 A14
PRE-K PRE-K PK-2 TOILET PRE-K
TECH ED LAB J11
E3 A9 1905 1907 1909A 1909
1722 A-5.5 M1
K1

11' - 0"
1909A

32' - 8"
G1

1' - 1 1/8"
E3 PK-2 TOILET PK-2 TOILET
5

8' - 10"
1907A 1907A

6' - 3"
1905A
1905A X2 X2

1' - 2"
A2 X2
2 2
29 X2
29
J J

2' - 7 1/2"
A2 1907 1909

1' - 9 1/8"
5' - 0"

6' - 10"
A2 A1 STAIR 3

3' - 8"
1721 A1 1722 A2 MECH 4 4
N1 X2 ST31

1' - 2" 4' - 10"


6' - 1 1/2"
A2

4' - 0"
1903A ST31
X2
10' - 5 1/4" 9' - 6 7/8" 1' - 0 7/8" 11 1/2" 21' - 0 3/4" SF4

2' - 7 1/2"
A1
3 3
1722B 1903 1905

4' - 0"
CORRIDOR 1' - 8 7/8" 4
A1 A2 A1 C172 A2 A1 A2

K18

9' - 2"

7' - 0"
10' - 0"

10' - 0"
7 7/8" CORRIDOR Sim
7 7/8" 10' - 0" 8' - 5 7/8" 1' - 2 3/8" 10' - 2 3/8" 4' - 4" 4' - 0" A5
C190
Sim A-5.2

1' - 6 3/4"

107' - 4"
9" J3 A-6.3 L3 9" A1 C172C A2 A2 A9
13B
A-4.8 MECH. UNIT, SEE MECHANICAL

20.00°
A2 A2 COLLABORATIVE

7 1/4"
H16 1904
A-6.3 LEARNING

25' -- 0"
E2 A2 K3 Sim
1920 A5
H H

www.grimmandparker.com
C172A

20'
1' - 1 7/8"
A2 PLANNING
FEC

1900 A-4.8
STORAGE RESOURCE 13A

11' - 4"
1900

12' - 11 7/8"
13' - 4 5/8"
13' - 5 5/8"

11720 Beltsville Drive

Calverton, MD 20705
A4 A3 1904 1906 SF10
3
A-5.4

Tel: 301.595.1000
7 1906
5 5/8" 18' - 10" 9' - 4 5/8" 1' - 3 3/4"
2
5 5/8" 7' - 1 3/8" 1' - 2" D18 A2 4' - 0" 10 1/4" A2 10' - 5 1/2" 9' - 4" 8' - 10 1/4" 1' - 1 3/4" 9' - 4" 1' - 8"

3' - 1"
1902 M1

3' - 1 1/4"

1' - 3 3/4"
DEMONSTRATION A-5.5 1910
FEC

Suite 600
WINDOW A2 1900A K1

8 3/4"
1908 1911
4 INTO PIPE CHASE 4
X2 4 4 4

1' - 0 5/8"
PK-2 TOILET

6' - 9 7/8"
PK-2 TOILET X2 1910A
32 X2 1910A

7' - 4 3/4"
1902A 1908A
STAFF TOILET TOILET N1 1908A
1900A 1902A
M1
G 5 M1 5
G

1' - 7"
ST11A PK-2 TOILET
5.1 N1 G6 1911A 1911A
A-5.5
5.1
STAIR 1 A10
1711 J18 ST12 A-5.1
UP N1 D13
SPECIAL
UP A-5.5
A-6.5 EDUCATION KINDERGARTEN

39' - 4"
1710 J5 J13 KINDERGARTEN KINDERGARTEN
PK-2 M1 1911
1902 1908 1910

30' - 1 1/2"
J9 4' - 10 1/2" 3' - 3 1/4"
CORRIDOR

26' - 0 3/4"
A6
C171
A-5.1 E18
G18

F A4
A-4.9
E6 A-6.5 E15
G6 A-6.1 G15
KEY NOTES FOR PLANS F
F12 1. WALLS EXTEND TO 10'-8" AFF
27' - 8 3/8" E9 27' - 5 1/2" 29' - 0" G10 28' - 10 3/4"
A-4.2a
2' - 2" 4' - 0"
X2

5.8
A14
A-5.1
5.8
GENERAL PLAN NOTES GP# 21553

1' - 3 3/4"
EE

2' - 9"
EX3 ST11 EX3
6 1/4"

X13 X14 X15 GENERAL NOTE APPLICABLE TO ALL DRAWINGS - ITEMS AND CONDITIONS DETAILED, NOTED OR OTHERWISE IDENTIFIED ON
2"

6' - 11 5/8" 10 1/4"

6 ONE OF THE SECTIONS OR DETAILS ARE APPLICABLE AND BINDING TO ALL OTHER SECTIONS AND DETAILS FOR IDENTICAL
°
.00

CW5 SF2 SF9 SF2 SF9 SF2 SF9


80

1' - 3 3/4" 6 OR SIMILAR CONDITIONS.


1705 X2 BUILDING EXPANSION JOINT
X2
Sim Sim 1. REFER TO SHEET A-3.20 FOR WALL TYPES AS REFERENCED ON PLANS WITH THE DIAMOND SYMBOL. UNLESS
10' - 7 1/2" 20' - 0" 6' - 8" A8 20' - 0" A4 6' - 8" 20' - 0" 6' - 9" REFERENCED OTHERWISE, ALL INTERIOR CMU WALLS ARE THE TYPE A2 AND ALL INTERIOR GYPSUM BOARD
21
X1 A8 A3 WALLS ARE TYPE K1.
C18 A-4.3 A-4.3
SF16 2. UNLESS NOTED OTHERWISE, WALLS SHALL EXTEND TO THE ROOF OR FLOOR DECK ABOVE AND BE SEALED IN
E A-4.9
A3
SMALL
REHEARSAL
ACCORDANCE WITH THE WALL TERMINATION DETAILS. REFER TO THE CODE STUDY PLAN FOR IDENTIFICATION
OF ALL SMOKE AND FIRE WALL CONDITIONS. PERIMETER CORRIDOR AND LOBBY WALLS SHALL BE BUILT TO
E
A-6.1
16' - 0 "

A3 1705 C4 RESIST THE PASSAGE OF SMOKE.


3. REFER TO WALL SECTIONS AND DETAILS FOR EXTERIOR WALL TYPES AND CONSTRUCTION.

27' - 6"
4. DIMENSIONS ON PLANS ARE FROM FACE OF MASONRY TO FACE OF MASONRY, FACE OF MASONRY TO FACE OF
GYPSUM BOARD OR FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD.
5. COLUMN GRID LINES ARE FOR REFERENCE ONLY, REFER TO STRUCTURAL DRAWINGS FOR COLUMN LOCATIONS.
A-6.1 C14 D18 6. REFER TO FURNISHING PLANS FOR CASEWORK, MILLWORK DISPLAY BOARDS, SHELVING UNITS, TV MOUNTING
A-6.1

PARTIAL FIRST FLOOR PLAN - AREA C


A-2.3H BRACKETS, LOCKERS, FURNITURE, ETC. (A-9 SERIES).
A3
7. FEC - INDICATES A FIRE EXTINGUISHER WITH A RECESSED CABINET. FE - INDICATES A FIRE EXTINGUISHER
21 "
X2 17' - 9 3/4 C10 D18 WITH A WALL MOUNTING BRACKET.
A-2.4H
6' - 2 3/8"
2"

1700 7 1/2" A3 8. UNLESS SPECIFICALLY INDICATED OTHERWISE, THE SAME WALL TYPE NEXT TO A DOOR OR OPENING SHALL
13' -

A3 CONTINUE OVER THE DOOR OR OPENING.

CITY OF BALTIMORE, MARYLAND


1704A

48' - 8"
A2 9. PLAN LOCATION OF DOORS AND FRAMES RELATIVE TO THE PLANE OF THE WALL IS DIAGRAMMATIC ONLY. REFER
6' - 11 5/8

TO THE REFERENCED JAMB AND HEAD CONDITION DETAILS TO DETERMINE ACTUAL PLACEMENT OF DOOR AND
1' - 9 5/8"

14B FRAME.
10. REFER TO A-5 SERIES FOR TYPICAL MASONRY DETAILS.
D D
"

F67
3' - 10 89/128"

STORAGE 7
11. NOT USED
A-4.2a 1704

HOLABIRD ACADEMY PK-8


12. ALL INTERIOR FACES OF ICF WALL (EPS FOAM) TO BE CONTINUOUSLY COVERED WITH 5/8" GYP. BOARD. ALL
A3 PENETRATIONS SEALED.
A12 A8
13. PROVIDE CORNER GUARDS AT ALL OUTSIDE CORNERS OF STUD WALLS AND INTERIOR ICF WALLS WHERE
A-4.7 A-4.7 3' - 0 1/2" A3 SF16 E18 GYPSUM BOARD IS EXPOSED.
1' - 8"

A3
1704B A-4.2
16' - 0 "

14A
X3 8
8"

E18
KEY PLAN
14' -

A13 EXC
A3 A5 D10
A15 / A-1.2

A-4.2a A-6.1 A-2.3H


A-4.7

29' - 9 1/4"
L6
13' - 5" 11' - 8 3/4" 22' - 4" A-6.1 E13 8' - 8" 8' - 0" A-5.5 20' - 8" 28' - 3 1/2"
A15 10
0.0 11' - 3 5/8" 11 5/8" 16' - 9 5/8" 14' - 5 5/8" 10' - 6 3/8"

C A-4.3
15 LARGE C
A-6.1 REHEARSAL

3' - 4" 2' - 9 5/8"


A3 E4
A3 1703

A3 E10 LOCKERS/SHOWER/ WATER


A2 SERVICE A2 FIRE PUMP A2
8' - 5 1/4"

15 X12
6' - 8"

TOILET A1
1703 1404 A16 / A-1.1
8 1/4"

1400 1402
A2 AREA B AREA C
A3 A2 NOTE 1
A3 1402 DATE DESCRIPTION
7 3/4"

8 1400 1404 8

C140

B B
J K L L.6 M M.1 AA M.5 N P Q Q.2 R S T EXD AREA A
G.9 H EXC

PARTIAL FIRST FLOOR PLAN - AREA C


A15 1/8" = 1'-0"

Scale: 1 inch = 8 feet


A-1.3
03/13/2017
BID SET
0 4' 8' 16' 24' 32'
A N © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

F1 F12
A-4.2a A-4.2a G.9
EXB F12 EXC
E18
A-4.1 A-4.2

DD EE J K K18 L L.6 M.1 N Q


A-4.1
M M
D9 A15 / A-1.6
A-2.1H A-6.1

J14
E10
A-4.7
A3
A2
F
4'0"W x 7'4"T G5
OPENING 8
A-5.3 8' - 8 13/16"

AA
A3 1' - 0 13/16"
ST52

L 8.2 LOCKABLE GATE IN 42" H GUARDRAIL TO ACCESS 8.2 L


A15 / A-1.5 LOW ADMIN ROOF FROM OUTDOOR CLASSROOM 6"
A4
ROOF
A4 A9
A-5.3
L1

8' - 0"
G9
STAIR 5
A3 A-5.3 ST52

10' - 9 1/4"
A3 A4
K 1' - 2" 1' - 1 1/4" 1' - 2 3/4" K

1' - 6 1/8"
3' - 6" K2

1' - 1 7/8"

75' - 1 5/8"
A5 A5
9 A12 9
9.1 A-4.3 9.1
L18
A-2.4H
A5

A-6.3
F18 D18

J OPEN TO BELOW G18 J


A-2.4H

VERTICAL SUNSHADES
ON CURTAINWALL MULLIONS H5

K11 A-6.4 H10

10 K5 10
48' - 10 3/4" 24' - 8"

H H

www.grimmandparker.com
A9

11720 Beltsville Drive

Calverton, MD 20705
A-4.6

Tel: 301.595.1000
LOW ROOF BELOW

Suite 600
A13
A-4.6
A18
A-4.1 E6 G2 A5 G2

G 11 G
116' - 1"

6' - 5"
BASKETBALL BACKSTOP DIVIDER CURTAIN BASKETBALL BACKSTOP CW4
G2 A18
A-4.4
J.1 A2

11.4

A4
A5
A-4.5
MECHANICAL A-4.4
ROOM - GYM
F 2501 F
A18 5240 SF
A18
A-4.2

82' - 0"
A-4.6
A2
J13
GENERAL PLAN NOTES GP# 21553
OPEN TO BELOW
BASKETBALL BACKSTOP GENERAL NOTE APPLICABLE TO ALL DRAWINGS - ITEMS AND CONDITIONS DETAILED, NOTED OR OTHERWISE IDENTIFIED ON
G.2 A9 A-6.2 A18 ONE OF THE SECTIONS OR DETAILS ARE APPLICABLE AND BINDING TO ALL OTHER SECTIONS AND DETAILS FOR IDENTICAL
UP
12 OR SIMILAR CONDITIONS.
BASKETBALL BACKSTOP E13 1. REFER TO SHEET A-3.20 FOR WALL TYPES AS REFERENCED ON PLANS WITH THE DIAMOND SYMBOL. UNLESS

53' - 11 5/8"
A15
A1 REFERENCED OTHERWISE, ALL INTERIOR CMU WALLS ARE THE TYPE A2 AND ALL INTERIOR GYPSUM BOARD
A-4.5 WALLS ARE TYPE K1.
2. UNLESS NOTED OTHERWISE, WALLS SHALL EXTEND TO THE ROOF OR FLOOR DECK ABOVE AND BE SEALED IN
E ACCORDANCE WITH THE WALL TERMINATION DETAILS. REFER TO THE CODE STUDY PLAN FOR IDENTIFICATION
OF ALL SMOKE AND FIRE WALL CONDITIONS. PERIMETER CORRIDOR AND LOBBY WALLS SHALL BE BUILT TO
E
RESIST THE PASSAGE OF SMOKE.
A13 3. REFER TO WALL SECTIONS AND DETAILS FOR EXTERIOR WALL TYPES AND CONSTRUCTION.
A-5.3 4. DIMENSIONS ON PLANS ARE FROM FACE OF MASONRY TO FACE OF MASONRY, FACE OF MASONRY TO FACE OF
A2 GYPSUM BOARD OR FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD.

PARTIAL SECOND FLOOR PLAN - AREA A


5. COLUMN GRID LINES ARE FOR REFERENCE ONLY, REFER TO STRUCTURAL DRAWINGS FOR COLUMN LOCATIONS.
A12 6. REFER TO FURNISHING PLANS FOR CASEWORK, MILLWORK DISPLAY BOARDS, SHELVING UNITS, TV MOUNTING
BRACKETS, LOCKERS, FURNITURE, ETC. (A-9 SERIES).
A-4.5 7. FEC - INDICATES A FIRE EXTINGUISHER WITH A RECESSED CABINET. FE - INDICATES A FIRE EXTINGUISHER
A8
WITH A WALL MOUNTING BRACKET.
A-1.11 BASKETBALL BACKSTOP BASKETBALL BACKSTOP 8. UNLESS SPECIFICALLY INDICATED OTHERWISE, THE SAME WALL TYPE NEXT TO A DOOR OR OPENING SHALL
CONTINUE OVER THE DOOR OR OPENING.

CITY OF BALTIMORE, MARYLAND


A3 9. PLAN LOCATION OF DOORS AND FRAMES RELATIVE TO THE PLANE OF THE WALL IS DIAGRAMMATIC ONLY. REFER
TO THE REFERENCED JAMB AND HEAD CONDITION DETAILS TO DETERMINE ACTUAL PLACEMENT OF DOOR AND
A9 FRAME.
CW1A 10. REFER TO A-5 SERIES FOR TYPICAL MASONRY DETAILS.
D ENTRY CANOPY BELOW A-4.5
11. NOT USED D
A18

HOLABIRD ACADEMY PK-8


12. ALL INTERIOR FACES OF ICF WALL (EPS FOAM) TO BE CONTINUOUSLY COVERED WITH 5/8" GYP. BOARD. ALL
A-1.9 PENETRATIONS SEALED.
13. PROVIDE CORNER GUARDS AT ALL OUTSIDE CORNERS OF STUD WALLS AND INTERIOR ICF WALLS WHERE
2' - 0 3/8"

2' - 3 3/8"
A4 13 GYPSUM BOARD IS EXPOSED.

1' - 5 3/4"
X30
3' - 6"

CW1B 1' - 4 3/8" SF17 SF17 SF17


1' - 5 3/4"
KEY PLAN
A18 A13 A9
A5 A-4.5 A-4.4 A-4.4

6" 22' - 0" 3' - 4" 13' - 4" 22' - 0" 4' - 0" 22' - 0" 4' - 0" 22' - 0"

C 138' - 1 5/8"
C
ENTRY CANOPY BELOW

LOW ROOF BELOW

A16
A-4.4 AREA B AREA C
DATE DESCRIPTION

EX4

B B
EXB F G.2 G.9 J J.1 K N Q EXC
AREA A

H18 L18
A-2.1H A-2.1H
PARTIAL SECOND FLOOR PLAN - AREA A
A18 1/8" = 1'-0" A-1.4
Scale: 1 inch = 8 feet 03/13/2017
BID SET
A 0 4' 8' 16' 24' 32' N © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

L18 G18
A-2.3H A-2.3H

EXA A B C D D.7 E G G.7 G.9 H

A15 / A-1.6
J10
A-4.2

M 14' - 0" 55' - 4"


A15 M
A-4.9 2"
5' - 4" 6' - 8" 5' - 4" 8' - 0" 12' - 0" 12' - 0" 8' - 0" 5' - 4" 4' - 0" 8' - 0" 12' - 0" 6' - 0" 4' - 0" 6' - 0" 12' - 0" 8' - 0"

A18
1' - 6 3/8" A-4.8
SF1 SF2 SF2 SF1

1' - 3 3/4"

1' - 3 3/4"
A15
EX1 EX1
A-4.8

6' - 8"
1' - 3 3/4"
6' - 8"
A18 M1 SF1 SF2 SF2 SF1
X2 X2
A-4.3

15' - 4"
EX2 EX2

3' - 0 1/4"
CW3
L A18
M1 X2 L
1 A-4.9 1
26' - 4 5/8" 26' - 4 1/8" 25' - 6 3/8" 15' - 0 7/8"

25' - 2 5/8"

12' - 10 1/4"
1' - 3 3/4" 7 7/8"
CW2 N1

1' - 6 3/8"
M1
7' - 8"
STORAGE
G13 2204B
N1
A-5.5
3' - 6 7/8" SPECIAL X2
EDUCATION

26' - 7 1/4"

7' - 5 5/8"
GRADE 5 3-5 STAFF TOILET FLEX
N1 9 1/8"
2214 GRADE 5 2206 2204A 2200 42 LOCKERS
2210

23' - 4"
K F5
2204A 2204B K
N1 MECH M1 K1 M1
A-5.2

11' - 0 7/8"
32' - 8"
2212 PLANNING
G1

1' - 10 1/4"
2204
X2
A1 N1

17' - 3 5/8"
7' - 1 5/8" 5 7/8" 1' - 0"
2 X2 2
A1
UP 2214 2212 2210 E3

4' - 0"
STAIR 2

6' - 10"

4' - 2"
3 3
ST22 ST22 A2 A2 2206 X2 X2 A1 A1 22
SF4

1/4"
27

1' - 9 83/8"
3 A2 3

1' - 2"

1' - 2"
2204 2200

1' - 6"
4 3
J A2
5 A2 4' - 4" 13' - 11" A2 A2
CORRIDOR
C210
J
1' - 9 7/8" 10 1/4" CORRIDOR 7 7/8" K18

10' - 0"

10' - 0"
14' - 8" C220
18' - 7 1/2" 6' - 1 5/8" 14' - 9 5/8" 4' - 6 5/8" 7' - 7 5/8" 4' - 6 SF
1202 5/8" 11' - 8 5/8" 5 5/8"
A9

29' - 6 3/8"
J3 A-6.3
A-4.8 13B
COLLABORATIVE 2202
25' - 7 1/4"
2205 2203B H16
LEARNING BUILDING AS A LEARNING

20' - 0"
A5 2220 CUSTODIAL TOILET LAB
A-4.8 2203B 2202 TOUCHSCREEN DISPLAY
SF10 13A

12' - 3 3/4"
MOUNTED
D18 1' - 6" 4' - 7 5/8" ON WALL K13
1' - 3 3/4" 8' - 10 1/2" 15' - 5"
A-2.2H A-6.3 MEN A-5.5
H18 2208 RESOURCE
2203 WOMEN
A1 11' - 9 3/4" 2208 2201

11 7/8"
H H

www.grimmandparker.com
A2

3' - 1"
E2 5" A2 A2 X2 A2

1' - 3 3/4"
3 3 FEC DEMONSTRATION
WINDOW

11720 Beltsville Drive


2215 2213 2211 2209

Calverton, MD 20705
4 X2 A2 INTO PIPE CHASE 4
3

Tel: 301.595.1000
ELEVATOR

2' - 1 1/2"
ELEVATOR
32
7' - 4 3/4"

MECH/UTILITY CONTROL E1
N1 MECH N1 X2 X2 8 1/8" 33' - 0 3/4" E2 5' - 7 5/8"
M1 2205 2207 D4
2213

12' - 0"
A2 A-5.4
E2 2207

Suite 600
5 5
1' - 7"

6 1/2"
ST12
5.1 5.1
A18 X2
BUILDING AS A LEARNING
GRADE 4 FLEX LAB "CUT-AWAY" WALL J18
N1 A-6.1
2215 3 A14 2209 CONSTRUCTION DISPLAY
G M1
G

18' - 11 3/8"
M1 A-6.5
39' - 4"

A9 J5
M1 J18
4' - 5 1/4" 2' - 4 1/4"
SCIENCE LAB
GRADE 4 2000 J9
26' - 0 3/4"

2211 A-6.2 A3
F18 L18
PREP/STORAGE CORRIDOR
2000A C200
H18

REF.
DOWNSPOUT
TO BOOT

2000A
F1 F12

7' - 7 3/8"
28' - 1 3/8" 25' - 9 7/8" 25' - 7 3/4" M1 8' - 7 5/8"
A-4.2a A-4.2a A8
A12
X2 A-4.9
A-4.9 2000
X2 1' - 1 5/8" 5.8
5.8
F X2 X1 X22 F

4' - 7 59/64" 1' - 11 3/4"


1' - 3 3/4"
2' - 9"

EX3 EX3

1' - 3 3/4" SF1 SF2 SF1 SF2 SF1 SF2 CW5 BUILDING

EXTERIOR WALL MOUNTED WITH FLASHING AND DRIP EDGE ABOVE


6 EXPANSION JOINT 6

6' - 4" 8' - 0" 12' - 0" 6' - 8" 8' - 0" 12' - 0" 6' - 8" 8' - 0" 12' - 0" 6' - 0 1/2" 4' - 0" 6' - 7" A18 12' - 0" 8' - 0" 7' - 9 1/8" 3' - 4"
GENERAL PLAN NOTES GP# 21553
1' - 3 1/4"
BUILDING EXPANSION JOINT A-4.7
EXA A B C D D.7 J18 G G.7 GENERAL NOTE APPLICABLE TO ALL DRAWINGS - ITEMS AND CONDITIONS DETAILED, NOTED OR OTHERWISE IDENTIFIED ON
A8 A4 ONE OF THE SECTIONS OR DETAILS ARE APPLICABLE AND BINDING TO ALL OTHER SECTIONS AND DETAILS FOR IDENTICAL
A-4.7

20'-0" L X 4'-0" H SLATE BOARD


A-4.3 PIPE RAILING AT PERIMETER X2 OR SIMILAR CONDITIONS.
A-4.3
RE: L4/A-1.10
E 1. REFER TO SHEET A-3.20 FOR WALL TYPES AS REFERENCED ON PLANS WITH THE DIAMOND SYMBOL. UNLESS
REFERENCED OTHERWISE, ALL INTERIOR CMU WALLS ARE THE TYPE A2 AND ALL INTERIOR GYPSUM BOARD
F6 WALLS ARE TYPE K1.
D18 18"D BENCH
A-4.2a 2. UNLESS NOTED OTHERWISE, WALLS SHALL EXTEND TO THE ROOF OR FLOOR DECK ABOVE AND BE SEALED IN
A-2.1H
E SEE A18/A-1.7 FOR MORE
INFORMATION ABOUT
ACCORDANCE WITH THE WALL TERMINATION DETAILS. REFER TO THE CODE STUDY PLAN FOR IDENTIFICATION
OF ALL SMOKE AND FIRE WALL CONDITIONS. PERIMETER CORRIDOR AND LOBBY WALLS SHALL BE BUILT TO
E
A16 OUTDOOR LEARNING
RESIST THE PASSAGE OF SMOKE.
A-4.7 AREA/SOLAR LAB
3. REFER TO WALL SECTIONS AND DETAILS FOR EXTERIOR WALL TYPES AND CONSTRUCTION.
BALLAST 4. DIMENSIONS ON PLANS ARE FROM FACE OF MASONRY TO FACE OF MASONRY, FACE OF MASONRY TO FACE OF
RAIL-MOUNTED WEATHER STATION GYPSUM BOARD OR FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD.

PARTIAL SECOND FLOOR PLAN - AREA B


5. COLUMN GRID LINES ARE FOR REFERENCE ONLY, REFER TO STRUCTURAL DRAWINGS FOR COLUMN LOCATIONS.
X3 6. REFER TO FURNISHING PLANS FOR CASEWORK, MILLWORK DISPLAY BOARDS, SHELVING UNITS, TV MOUNTING
GRAVEL STOP BRACKETS, LOCKERS, FURNITURE, ETC. (A-9 SERIES).
7. FEC - INDICATES A FIRE EXTINGUISHER WITH A RECESSED CABINET. FE - INDICATES A FIRE EXTINGUISHER
7 FIXED DEMONSTRATION PV 7 WITH A WALL MOUNTING BRACKET.
PANELS ON ADJUSTABLE
8. UNLESS SPECIFICALLY INDICATED OTHERWISE, THE SAME WALL TYPE NEXT TO A DOOR OR OPENING SHALL
ANGLE FRAMES CONTINUE OVER THE DOOR OR OPENING.

CITY OF BALTIMORE, MARYLAND


2'X2' PAVERS ON ELEVATOR A12
BB PEDESTALS, TOP SURFACE 9. PLAN LOCATION OF DOORS AND FRAMES RELATIVE TO THE PLANE OF THE WALL IS DIAGRAMMATIC ONLY. REFER
LEVEL AT 14'-8" A-4.7 TO THE REFERENCED JAMB AND HEAD CONDITION DETAILS TO DETERMINE ACTUAL PLACEMENT OF DOOR AND
CC REF: A18/A-1.7 FOR PAVER FRAME.
10. REFER TO A-5 SERIES FOR TYPICAL MASONRY DETAILS.
D LAYOUT
11. NOT USED D

HOLABIRD ACADEMY PK-8


12. ALL INTERIOR FACES OF ICF WALL (EPS FOAM) TO BE CONTINUOUSLY COVERED WITH 5/8" GYP. BOARD. ALL
A13 PENETRATIONS SEALED.
A-4.2a 13. PROVIDE CORNER GUARDS AT ALL OUTSIDE CORNERS OF STUD WALLS AND INTERIOR ICF WALLS WHERE
DUAL-AXIS PV TRACKER OPEN TO GYPSUM BOARD IS EXPOSED.
ON STEEL POST ANCHORED TO BELOW
CONCRETE SLAB BELOW
VEGETATIVE ROOF EXTENSIVE VEGETATIVE

D9
ROOF SYSTEM A15
A-4.3
KEY PLAN
A-2.1H

J14
A-4.7

C C
8 8

DD
EE AREA B AREA C

8.2 LOCKABLE GATE IN 42" H GUARDRAIL TO ACCESS 8.2 DATE DESCRIPTION


LOW ADMIN ROOF FROM OUTDOOR CLASSROOM
EXB F ROOF
A18 / A-1.4
L1

B B
AREA A

PARTIAL SECOND FLOOR PLAN - AREA B


A15 1/8" = 1'-0"

Scale: 1 inch = 8 feet

0 4' 8' 16' 24' 32'


A-1.5
03/13/2017
BID SET
A N © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

G18
A-2.3H

G.9 H J K K.2 K.3 L.6 M M.1 M.5 N P Q Q.2 R S T EXD

M M

A15 / A-1.5
L

65' - 0" 55' - 4" 14' - 0"


2" 10' - 8" 2" 8' - 0" 18' - 0" 4' - 0" 6' - 0" 12' - 0" 8' - 0" 4' - 0" 5' - 4 1/256" 8' - 0" 12' - 0" 12' - 0" 8' - 0" 5' - 4"

K18
A-4.1
LINE OF PROTECTIVE
SF1 SF2 SF2 SF1
COVER/CANOPY

1' - 3 3/4"

1' - 3 3/4"
A15 BELOW ANCHORED TO
EX1 CONCRETE WALL EX1
L A-4.8 L

3' - 0 1/2"

6' - 8"
X2 X2
SF1 X2 SF1 SF2 SF2 SF1

15' - 4"
EX2 CW3 EX2

2' - 9"
X2 X2 X2 6' - 8" 5' - 4 1/256"
1 1
X2

1' - 3 1/2"
7 7/8" X2 2300A 7' - 4 3/8" 7' - 8" 25' - 7" 26' - 3 15/16" 26' - 7 5/16" 1' - 3 3/4"
7 7/8" CW2

12' - 7"
1' - 1 1/8"
STORAGE
2302A M1
G5 G11
N1
A-5.5

K G9
A-6.5
G18
STAFF TOILET N1 GRADE 6
N1 K
GRADE 8 GRADE 8

26' - 7 1/4"
2302B

7' - 5 7/8"
FLEX 2306 2308 2312
2200 G13 X2
42 LOCKERS

33' - 5 1/4"
MECH

19' - 5 5/8"
42 LOCKERS FLEX 2302A 2302B 2310
2300 Sim
M1 F5

32' - 8"
A-5.2
N1 N1

11 1/8"
PLANNING

15' - 8 5/8"
G1
1' - 0" 1' - 2" 2302
X2 23 2310

4' - 0"
2 2
N1 M1 2308 2312
E3 E3 FEC 3

6' - 5 1/4"
J 3 SF4 J

4' - 2"
9 LOCKERS 11 LOCKERS STAIR 3
22 22 A1 2' - 8 1/4"
A2 A2 A2 A2 A2 ST32
1' - 3 1/2" 6' - 11 1/2"
ST32

1' - 6"

8' - 0"
4 3/4"
8 LOCKERS
3 1' - 2" 3

1' - 2"

1' - 2"
2302
2300 2306

1' - 6"
3 4 11 5/8" 11 1/8" 26 LOCKERS 3
CORRIDOR A2
A2 A2 A2 A2 4' - 4" 16' - 5 3/4" A2
C210
7 7/8" K18 7 7/8" 6' - 5 7/8" 6' - 8 1/4" 1' - 5 1/4" CORRIDOR
10' - 0"

10' - 0"

10' - 0"

10' - 0"
C230 14' - 8"
5 5/8" 5 5/8" 11' - 8 5/8" 4' - 6 5/8" 7' - 7 5/8" 4' - 6 5/8" 11' - 2 3/4" 6' - 7 5/8" 20' - 2" 1295 SF

107' - 4"
A-6.3 COLLABORATIVE
J3 L3 25A
A2 A2 LEARNING

1' - 1 1/2"

5' - 5 3/4" 1' - 1 1/2"


16 LOCKERS 16 LOCKERS 2320
H16 A2
BUILDING AS A LEARNING 2300E A-6.3

20' - 0"
K3

6' - 7 1/4"
A2 E2 25B
LAB TOILET
H A2
H

www.grimmandparker.com
TOUCHSCREEN DISPLAY 2300E 2305 SF10
MOUNTED A2
ON WALL RESOURCE 1' - 0" 7' - 9 1/4"

11720 Beltsville Drive

Calverton, MD 20705
D4 2304 2305 A2
K18
A-5.4 WOMEN MEN 3

Tel: 301.595.1000
A-5.5
2301 2303 8 LOCKERS
A2 9 1/2" 12' - 1 3/4"
M1

6' - 4"
X2 14 LOCKERS
DEMONSTRATION 3 3 3
WINDOW M1
2307 2309 2311 2313

Suite 600
4 INTO PIPE CHASE X2 X2 4

11 7/8"
24
2100

1' - 0 5/8"
ELEVATOR M1 A2
32 X2
E1
A3 X2
A2
MECH
FEC

2100 C18
5 ST12 5
G G

19' - 1 1/8"
5.1 GRADE 7 5.1
A-6.5 GRADE 7 MECH
STAIR 1 2313
2309 2311
ST12 M1 N1
J18
SPECIAL
EDUCATION GRADE 6
6-8 N1 N1
A-6.5 2307

39' - 4"
J5 J13 2304 J18

J9 4' - 11 7/8"
OPEN TO J6 A-6.1 J15
G5
BELOW A-5.1 M1 M1
CORRIDOR 2' - 7 7/8"
UP J10
C200

F F12
F
DN 24' - 7 3/8" 25' - 7 7/8" 26' - 11" 28' - 2 3/4"
A-4.2a

X2
5.8
X22
2101
5.8
GENERAL PLAN NOTES GP# 21553
4' - 7 59/64" 1' - 11 3/4"

1' - 3 3/4"
EX3 EE EX3
GENERAL NOTE APPLICABLE TO ALL DRAWINGS - ITEMS AND CONDITIONS DETAILED, NOTED OR OTHERWISE IDENTIFIED ON
CW5 SF2 SF1 1' - 3 3/4" ONE OF THE SECTIONS OR DETAILS ARE APPLICABLE AND BINDING TO ALL OTHER SECTIONS AND DETAILS FOR IDENTICAL
SF2 SF1 SF2 SF1
EXTERIOR WALL MOUNTED WITH FLASHING AND DRIP EDGE ABOVE

6 6 OR SIMILAR CONDITIONS.
7' - 7" 3' - 1" 12' - 0" 8' - 0" 6' - 8" 12' - 0" 8' - 0" 6' - 8" 12' - 0" 8' - 0" 6' - 9"
3' - 4" BUILDING AS A 3' - 6 3/8" 1. REFER TO SHEET A-3.20 FOR WALL TYPES AS REFERENCED ON PLANS WITH THE DIAMOND SYMBOL. UNLESS
1' - 3 1/4" A3 LEARNING LAB REFERENCED OTHERWISE, ALL INTERIOR CMU WALLS ARE THE TYPE A2 AND ALL INTERIOR GYPSUM BOARD
X1 A8 SIGNAGE GRAPHIC
A4 WALLS ARE TYPE K1.
M M.5 P Q.2 R EXD
A-4.9 2. UNLESS NOTED OTHERWISE, WALLS SHALL EXTEND TO THE ROOF OR FLOOR DECK ABOVE AND BE SEALED IN
E E
20'-0" L X 4'-0" H SLATE BOARD

A-4.9 ACCORDANCE WITH THE WALL TERMINATION DETAILS. REFER TO THE CODE STUDY PLAN FOR IDENTIFICATION
BUILDING EXPANSION JOINT OF ALL SMOKE AND FIRE WALL CONDITIONS. PERIMETER CORRIDOR AND LOBBY WALLS SHALL BE BUILT TO
RESIST THE PASSAGE OF SMOKE.
3. REFER TO WALL SECTIONS AND DETAILS FOR EXTERIOR WALL TYPES AND CONSTRUCTION.
4. DIMENSIONS ON PLANS ARE FROM FACE OF MASONRY TO FACE OF MASONRY, FACE OF MASONRY TO FACE OF
GYPSUM BOARD OR FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD.

PARTIAL SECOND FLOOR PLAN - AREA C


A-6.1 5. COLUMN GRID LINES ARE FOR REFERENCE ONLY, REFER TO STRUCTURAL DRAWINGS FOR COLUMN LOCATIONS.
A-6.1 C14 D18
6. REFER TO FURNISHING PLANS FOR CASEWORK, MILLWORK DISPLAY BOARDS, SHELVING UNITS, TV MOUNTING
A-2.3H
BRACKETS, LOCKERS, FURNITURE, ETC. (A-9 SERIES).
C10 D18 7. FEC - INDICATES A FIRE EXTINGUISHER WITH A RECESSED CABINET. FE - INDICATES A FIRE EXTINGUISHER
X2 A-2.4H WITH A WALL MOUNTING BRACKET.
8. UNLESS SPECIFICALLY INDICATED OTHERWISE, THE SAME WALL TYPE NEXT TO A DOOR OR OPENING SHALL
CONTINUE OVER THE DOOR OR OPENING.

48' - 8"

CITY OF BALTIMORE, MARYLAND


9. PLAN LOCATION OF DOORS AND FRAMES RELATIVE TO THE PLANE OF THE WALL IS DIAGRAMMATIC ONLY. REFER
MECHANICAL TO THE REFERENCED JAMB AND HEAD CONDITION DETAILS TO DETERMINE ACTUAL PLACEMENT OF DOOR AND
ROOM - FRAME.
F67 CENTRAL 7 10. REFER TO A-5 SERIES FOR TYPICAL MASONRY DETAILS.
D A-4.2a 2101
PRE- FINISHED METAL LOUVERS,
11. NOT USED D

HOLABIRD ACADEMY PK-8


12. ALL INTERIOR FACES OF ICF WALL (EPS FOAM) TO BE CONTINUOUSLY COVERED WITH 5/8" GYP. BOARD. ALL
A12 A8 SEE MECH. DWGS. PENETRATIONS SEALED.
A-4.7 A-4.7 19' - 4" E18 13. PROVIDE CORNER GUARDS AT ALL OUTSIDE CORNERS OF STUD WALLS AND INTERIOR ICF WALLS WHERE
A-4.2 GYPSUM BOARD IS EXPOSED.

X3
A13 EXC
KEY PLAN
8' - 0"

A5 D10
A-4.2a A-2.3H
A-4.7 L1
OPEN TO
BELOW
4' - 8"

A15
A-4.3
C A-6.1 C
A18 / A-1.4
E10
A3
A2
AREA B AREA C

4'0"W x 7'4"T
8 OPENING 8 DATE DESCRIPTION
8' - 8 13/16"

B B
AREA A
H J K L L.6 M.1 N Q EXC

AA
02C PARTIAL PLAN
A15 1/8" = 1'-0"

Scale: 1 inch = 8 feet


A-1.6
03/13/2017
BID SET
A 0 4' 8' 16' 24' 32' N A
© GRIMM AND PARKER, P.C. 2014

18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

GENERAL VIEW NOTE (NOTES APPLY TO ALL 3D VIEWS)

THIS AXONOMETRIC OR PERSPECTIVE VIEW IS TO AID IN THE GENERAL VISUALIZATION OF THE PROJECT.
SOME ELEMENTS MAY BE MISSING FOR CLARITY.

FOR CONSTRUCTION DETAILS, REFERENCE THE PLANS, SECTIONS, AND ENLARGED DETAILS AS WELL AS
ENGINEERING DRAWINGS.

EXA A B C D E G H J K L M M.1 N P Q R S T EXD


M M
B.O.D 29'-7" B.O.D 29'-7"
J.B. 29' 3-1/2" J.B. 29' 3-1/2"
T.O. ICF 35'-0" B.O.D 29' 7-1/2" B.O.D 29' 7-1/2" T.O. ICF 35'-0"
T.O. ICF 35'-0" J.B. 29' 4" A7 J.B. 29' 4" T.O. ICF 35'-0"
T.O.M. 32'-0" T.O.M. 32'-0"
T.O.M. 32'-0" A-1.10 6'-8"X12' PROTECTIVE T.O.M. 32'-0"
B.O.D 30'-0" A15 B.O.D 30'-0"
T.O. ICF 35'-0" COVER/CANOPY BELOW T.O. ICF 35'-0"
EX1 T.O.M. 32'-0" A-4.8 T.O.M. 32'-0" EX1 ROOF TYPES
EX2 EX2

ROOF TYPE-1 (TYPICAL): ADHERED MEMBRANE ROOF


1 1

L - ADHERED MEMBRANE TPO SHEET ROOFING


L
- COVER BOARD
B.O.D. 30' 7-1/2" B.O.D. 30' 7-1/2"
- ROOF INSULATION
- METAL DECK ON STRUCTURE
T.O. ICF 35'-0" B.O.D. 30' 5" B.O.D. 30' 5" T.O. ICF 35'-0"
J.B. 30' 1-1/2" J.B. 30' 1-1/2" R-VALUE: 30.78
T.O.M. 32'-0" T.O.M. 32'-0"
2 B.O.D. 30'-7" B.O.D. 30'-7" 2

SLOPE

SLOPE
SLOPE

SLOPE

SLOPE
J.B. 30' 3-1/2" J.B. 30' 3-1/2"

3 3
ROOF TYPE-2.1: VEGETATED ROOF

AXON ENTRY CANOPY - VEGETATIVE ROOF SYSTEM

K K18 (SEE VEGETATIVE ROOF PLAN FOR EXTENT)


- ADHERED MEMBRANE TPO SHEET ROOFING K
- COVER BOARD
B.O.D. 31'-1" ROOF TYPE 1 ROOF HATCH B.O.D. 31'-1" - ROOF INSULATION
J.B. 30' 9-1/2" TYPICAL TYPE 2 J.B. 30' 9-1/2" - CONCRETE SLAB ON METAL DECK ON STRUCTURE
HINGED GATE ON
4 4 R-VALUE: 32.66
GUARDRAIL
K12 SKYLIGHT SYSTEM ON
FLASHED CURB
5 A-1.9 5

SLOPE

SLOPE

SLOPE

SLOPE
T.O. ICF 35'-0" ADD ALTERNATE BIPV T.O. ICF 35'-0"
T.O.M. 32'-0" GLAZING T.O.M. 32'-0"

SLOPE
2 HR FIREWALL
SCUPPER TO METAL COLLECTOR 2" EXPANSION JOINT ASSEMBLY T.O. ICF 35'-0"
BOX AND DOWNSPOUT AND BOOT ROOF TYPE-2.2: WALKWAY ROOF PAVERS
AT GRADE ROOF LADDER
RE: A18/A-1.10 AND C13/A-1.10
J 6" DS
A7 - ROOF PAVER W/ HEIGHT ADJUSTABLE PEDESTAL J
F18 ROOF ACCESS DOOR - ADHERED MEMBRANE TPO SHEET ROOFING
A-1.10 5.8 - COVER BOARD
5.8 A-1.9 X1 AA
- ROOF INSULATION
- CONCRETE SLAB ON METAL DECK ON STRUCTURE

2' - 2 3/4"
EX3 EX3
R-VALUE: 32.66
6 B.O.D 29' 7-1/2" LOW B.O.D 29' 7-1/2" 6
J.B. 29'-4" B.O.D. 13'-2" T.O. ICF 35'-0" J.B. 29'-4"
ALTERNATE CISTERN AT GRADE EXA A B C D X2 M P R S T EXD
T.O. ICF 35'-0" T.O.M. 32'-0" T.O. ICF 35'-0"
WITH DIVERTER
T.O.M. 32'-0" 2 HR FIRE WALL AND BUILDING T.O.M. 32'-0"
EXPANSION JOINT ASSEMBLY
ROOF TYPE 2.2 SLOPE 2 HR FIRE WALL
A7 AND BUILDING
OUTDOOR LEARNING CLASSROOM EXPANSION

H
SCIENCE SOLAR LAB X3 A-1.10 JOINT ASSEMBLY
TYPICAL ROOF NOTES H

www.grimmandparker.com
7 7
GENERAL NOTE APPLICABLE TO ALL DRAWINGS - ITEMS AND CONDITIONS DETAILED, NOTED OR OTHERWISE
D5

11720 Beltsville Drive


T.O. ICF 35'-0"

MG

Calverton, MD 20705
B.O.D. 14' -3" SLO SLOP SLOPE IDENTIFIED ON ONE OF THE SECTIONS OR DETAILS ARE APPLICABLE AND BINDING TO ALL OTHER SECTIONS
BB PE E T.O.M. 32'-0"
A18 A-1.9 HIGH AND DETAILS FOR IDENTICAL OR SIMILAR CONDITIONS.

Tel: 301.595.1000
A-1.7 EXB B.O.D. 32'-11" B.O.D. 32'-11" EXC
1. DETAILS INDICATED ARE TYPICAL FOR ALL SIMILAR ROOFING CONDITIONS UNLESS OTHERWISE
B.O.D. 33'-3" INDICATED.
ROOF SLOPE B.O.D. 32'-8" 2. UNLESS OTHERWISE NOTED, MINIMUM ROOF SLOPE IS 1/4" PER FOOT. PROVIDE TAPERED
42"H RAILING WITH B.O.D. 29'-11 1/2"
INSULATION (EVEN IF NOT SHOWN ON THIS PLAN) AS REQUIRED TO MAINTAIN MINIMUM REQUIRED

Suite 600
TYPE 2.1
LOCKABLE GATE SLOPE TO ROOF DRAINS AND ELIMINATE ANY AREAS OF POTENTIAL STANDING WATER. PROVIDE
ROOF TYPE 1
TYPICAL TAPERED INSULATION (MINIMUM 1/4" PER FOOT SLOPE) AT ALL CRICKETS INDICATED TO DRAINS.
ROOF HYDRANT PER PLUMBING COORDINATE HEIGHTS OF ALL FLASHINGS AND EXPANSION JOINT CAPS WITH TAPERED INSULATION
TO MAINTAIN MINIMUM DIMENSIONS DETAILED.
8 SLOPE SLOPE 8 3. ALL ROOF PENETRATIONS AND ACCESSORIES (DRAINS, VENTS, ETC.) ARE TO BE INSTALLED AND
FLASHED IN COMPLIANCE WITH THE CURRENT EDITIONS OF N.R.C.A. ROOFING AND
DD B.O.D. 13'-2" STEP OVER SLOPE SLOPE WATERPROOFING MANUAL AND S.M.A.C.N.A. (ARCHITECTURAL SHEET METAL MANUAL)
EE PARAPET
G AT LOCKABLE
ROOF HATCH
FROM MECHANICAL
4. COORDINATE WITH MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR ITEMS (INCLUDING
UNIT SIZES AND LOCATIONS) NOT SHOWN OR SCHEMATICALLY SHOWN ON ROOF PLANS.
G
T.O. ICF 16'-8" GATE ROOM 5. CURBS FOR ROOF TOP MECHANICAL EQUIPMENT ARE PROVIDED BY THE MECHANICAL
T.O.M 16'-8"
CONTRACTOR. REFER TO TYPICAL CURB FLASHING DETAIL FOR BLOCKING AND FLASHING
SLOPE REQUIREMENTS. PROVIDE ALL BLOCKING NECESSARY TO ACHIEVE LEVEL MECHANICAL CURBS AT
A7 FE
ALL LOCATIONS. MAINTAIN MINIMUM 8" FROM TOP OF CURB TO ADJACENT ROOF. PROVIDE
B.O.D. 14' 3-1/2" LOW
AXON AERIAL J.B. 14'-0" B.O.D. 15'-8" A-1.10A15
ROOF HATCH TAPERED CRICKETS (MINIMUM 1/2" PER FOOT SLOPE) AROUND ALL MECHANICAL EQUIPMENT
G18 J.B. 15' 4-1/2"
SLOPE UP A-7.7 ROOF TYPE 1
TYPICAL
TYPE 1
HINGED GATE ON
GUARDRAIL
6.
CURBS.
THE ROOF DRAIN AND MECHANICAL UNIT LOCATIONS SHOWN ON THE ROOF PLAN ARE
APPROXIMATE. COORDINATE WITH MECHANICAL AND PLUMBING DRAWINGS FOR EXACT
9 9 LOCATIONS.
ROOF LADDER MECHANICAL EXHAUST 7. PRIOR TO FLASHING OVERFLOW ROOF SCUPPERS AND ROOF DRAIN, ROOFING CONTRACTOR
G6 SHALL BE REQUIRED TO CONFIRM MAXIMUM DRAIN PIPE HEIGHT OF 3" ABOVE ROOF IN
RE: A18/A-1.10 AND C13/A-1.10 EQUIPMENT
A-1.10 ACCORDANCE WITH PLUMBING DRAWINGS.
8. START TAPERED INSULATION AT SUMP PLATES. INSULATION SHALL BE TAPERED DOWN FROM ALL
CLERESTORY

FE
A8 SLOPE SLOPE (4) SIDES OF INDICATED SUMP. REFERENCE TYPICAL ROOF DRAIN DETAIL A15/A-1.9.
CURTAINWALL FRAMING M.1 SLOPE
TUBULAR SKYLIGHT TYPE 1 ON 9. IN ACCORDANCE WITH SPECIFICATION SECTION #07620 SHEET METAL, FLASHING AND TRIM,
F E G G.9 H A-4.9
TYP.
AT CORRIDOR BELOW METAL
ROOF FASCIA
SLOPE SLOPE TYP.
FLASHED CURB ROOFING CONTRACTOR SHALL BE REQUIRED TO PROVIDE RECEIVER FLASHING TO MASONRY F
TYP. AT 4 LOCATIONS IN DINING CONTRACTOR FOR INSTALLATION. ROOFER TO SOLDER JOINTS IN STAINLESS STEEL FLASHING.
10. PROVIDE WALKWAY PROTECTION WHERE INDICATED AND AT ALL SIDES OF MECHANICAL ROOF
HIGH B.O.D. 29'-8" TOP UNITS REQUIRING SERVICE AND AT TOP AND BOTTOM OF ALL ROOF STAIRS.
6' - 0" B.O.D. 29'-11" B.O.D. 30' 3-1/2" B.O.D. 29'-9" B.O.D. 30' 3-1/2" 10' - 3" J.B. 29' 4-1/2"
AT RIDGE J.B. 30'-0" 11. ALL ROOF TOP EQUIPMENT (EXCLUDING PREFINISHED ITEMS) SHALL BE FIELD PAINTED.

BB
CJ BENCH CJ
EE
ROOF ACCESS DOOR
10
MECHANICAL EXHAUST EQUIPMENT
10
T.O.M. 32'-0"
12. WHERE INDICATED, REFER TO PLUMBING DRAWINGS FOR RADON PIPE DETAIL. FLASHING SHALL BE
IN ACCORDANCE WITH TYPICAL DETAILS. GP# 21553
DD ROOF TYPE 1 T.O. ICF 32'-0" 13. CONTRACTOR IS RESPONSIBLE FOR PROVIDING FRT WOOD BLOCKING AS REQUIRED TO
X1 EJ 5.8
TYPICAL SLOPE SLOPE SLOPE ACCOMMODATE ALL PROFILES OF FINISHED ROOFING INCLUDING AT CRICKETS AND TAPERED
ROOF TYPE 1 INSULATION AT WALLS, PARAPETS AND GRAVEL STOPS. GRAVEL STOPS AT GUTTERS TO BE
EX3
TYPICAL STAINLESS STEEL WITH SOLDERED JOINTS.
EJ 6 14. COORDINATE HOSE BIB LOCATIONS ON ROOF WITH MEP PLANS.
SINGLE STORY LOW ROOF SLOPE
Sim B.O.D. 30'-4"
L4
G14 SLOPE SLOPE
SLOPE
G11
A-1.10
J.B. 30' 0-1/2"
ROOF SYMBOLS KEY
A-1.10
E A-1.10 11 11 ROOF DRAIN WITH TAPERED INSULATION - TYP. SUMP SHALL BE 4'-0" X 3'-0"
RE: A8/A-1.9 SIMILAR
E
X2
0"

J.B. 29'-3"
CH

TUBULAR SKYLIGHT ROOF DRAIN WITH TAPERED INSULATION - TYP. SUMP SHALL BE 4'-0" X 4'-0"
16' -

PIPE RAILING AT PERIMETER SLATE TEACHING WALL T.O.M. 32'-0"


BEN

CC 11.4 TYPE 2 ON FLASHED SEE DETAIL FOR OVERFLOW AT EACH DRAIN, RE: A8/A-1.9
RE: L4/A-1.10 20' L B.O.D. 29'-8" T.O. ICF 32'-0"
CURB
18"D BENCH, POST EXTENDED HIGH TYP. AT 8 LOCATIONS
HEIGHT TO WELD TO PLATE ON B.O.D. 29'-11" IN GYM DIRECTION OF SLOPE FROM HIGH POINT - ROOF SLOPES
CONCRETE SLAB BELOW ROOFING, 7' - 6 B.O.D. 30' 3-1/2"
" @ 1/4" PER FOOT, MINIMUM, UNLESS OTHERWISE NOTED
INSULATION, AND PAVERS 14' - 8" LOW J.B. 30'-0"

SLOPE
BEN T.O. ICF 16'-8" B.O.D. 15' 8"
3' - 5 1/4"

CH
T.O.M 16'-8" J.B. 15' 4-1/2" GYM ROOF T.O.M. X'-X"
BALLAST 1' - 6 TOP OF MASONRY

CITY OF BALTIMORE, MARYLAND


" CJ ROOF TYPE 1
RAIL-MOUNTED WEATHER STATION 1' - 0"
9' - 0 12 TYPICAL T.O. ICF X'-X"
" TOP OF ICF (INSULATED CONCRETE FORM WALL)
A1
"

SLOPE B.O.D. 30'-5" Sim


8' - 0

CH

X3 6' - 0
9' - 2 1/2"

" G11
D AT RIDGE
D
BEN

4" DOWNSPOUT TO T.O.S. X'-X" TOP OF STEEL


GRAVEL STOP A-1.10
BOOT AT GRADE

HOLABIRD ACADEMY PK-8


SLOPE
7 J.B. X'-X"
A2 SLOPE JOIST BEARING
BASE BID: TRANSPARENT GLASS/LAMINATE
FIXED DEMONSTRATION PV
9' - 2 1/2"

PV PANEL MODULES
PANELS ON ADJUSTABLE
WITH INTEGRATED RACKING SYSTEM. B.O.D. X'-X"
ANGLE FRAMES BOTTOM OF DECK
ADD ALTERNATE 1: TRANSPARENT PV A18 J.B. 29'-3" T.O.M. 32'-0"
A3
DUAL-AXIS PV TRACKER 2'X2' PAVERS ON ELEVATOR PANEL AND RAIL SYSTEM RE: SHEET A-8.1 T.O. ICF 32'-0"
9' - 2 1/2"

A-1.9 SIM
ON STEEL POST ANCHORED TO PEDESTALS, TOP SURFACE 1
CONCRETE SLAB BELOW LEVEL AT 14'-8" DETAIL @ TOP OF WALL
VEGETATIVE ROOF METAL PANEL ASSEMBLY A101
EXB 13 A4 13
9' - 2 1/2"

TRANSLUCENT PANEL SIM


Sim 1
SYSTEM SLOPE SLOPE ROOF ACCESS DOOR G11 DETAIL @ LOW ROOF WALL - FLASHING CONDITION
5' - 5"

ROOF PLAN
A5 B.O.D. 14'-10" A101
4" DOWNSPOUT TO SINGLE STORY LOW ROOF A-1.10 J.B. 14' 6-1/2"
C SLO
PE BOOT AT GRADE
C

SLOPE
ROOF HATCH
15' - 0"

CJ CONTINUOUS ROOF TYPE 1


GUTTER TYPICAL DOWNSPOUT DOWN TO CAST IRON DOWNSPOUT BOOT
SLOP DS
E AT GRADE - SEE CIVIL DRAWINGS FOR CONNECTION
EXTENSIVE VEGETATIVE ROOF F18
L6 A-1.11
J14 SYSTEM WITH EDGE ANGLE AT O.S. OVERFLOW SCUPPER - SEE DETAIL F6/A-1.9
EX4 EX4
1' - 6"

A-1.10 PERIMETER
A-4.7 FDC
T.O. ICF 16'-8"
ROOF HYDRANT PER PLUMBING T.O.M 16'-8" PHOTOVOLTAIC PANELS (PV)
T.O. ICF 16'-8" B.O.D. 14' 3-1/2" G6 DATE DESCRIPTION
T.O.M 16'-8" J.B. 14'-0"
2' - 2"

A-1.10
8 SIM. BALLAST AT PERIMETER OF VEGETATIVE ROOF

BB PIPE RAILING WITH GATE


DD ROOF WALKWAY - 36" WIDE CAPSHEET ADHERED TO ROOF PER
RE: L6/A-1.10
EE MANUFACTURER'S RECOMMENDATIONS AT LOW SLOPE ROOF.

B STEP OVER PARAPET TO WALKWAY MAT EXB F G.2 H J K N Q EXC B


EXTENSIVE VEGETATIVE ROOF

PV ARRAY ON ADMIN ROOF 24"x24" PAVERS ONE ADJUSTABLE ELEVATOR PEDESTALS AT OUTDOOR
CLASSROOM
Scale: 1 inch = 16 feet
EXB F G.9 H

A-1.7
TUBULAR SKYLIGHT, TYPES 1 AND 2

0 8' 16' 32' 48' 64'


ENLARGED ROOF PLAN DETAIL - SOLAR LAB/OUTDOOR LEARNING CLASSROOM ROOF PLAN
A18 1/8" = 1'-0" A11 1/16" = 1'-0"
03/13/2017
BID SET
A N © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

EXA A B C D E G H J K L M N P Q R S T EXD

M M

A15 PV ARRAY ON THIS ROOF

EX1 A-4.8 EX1

EX2 EX2

1 FE 1

L L

2 2

3 3

OUTDOOR CLASSROOM
SCIENCE SOLAR LAB/PORCH
K K

4 4

ROOF HATCH
5 TYPE 2 5

ENTRY CANOPY WITH


TRANSPARENT PV PANELS

BUILDING AXON
J AA J9 J
ROOF ACCESS DOOR ROOF LADDER
X1
EX3 EX3

6 BUILDING EXPANSION JOINT BUILDING EXPANSION JOINT 6


AT 2 HR FIREWALL
EXA A B C D X2 E M P R S T EXD

OUTDOOR LEARNING CLASSROOM


SCIENCE SOLAR LAB SLO
X3 PE
7 REFER TO PHOTOVOLTAIC
SLOP
E 7 TYPICAL ROOF NOTES
H H

www.grimmandparker.com
DRAWINGS FOR

MG
GENERAL NOTE APPLICABLE TO ALL DRAWINGS - ITEMS AND CONDITIONS DETAILED, NOTED OR OTHERWISE
INSTRUCTIONAL PV PANELS BB
IDENTIFIED ON ONE OF THE SECTIONS OR DETAILS ARE APPLICABLE AND BINDING TO ALL OTHER SECTIONS

11720 Beltsville Drive

Calverton, MD 20705
EXB EXC AND DETAILS FOR IDENTICAL OR SIMILAR CONDITIONS.

Tel: 301.595.1000
Sim 1. DETAILS INDICATED ARE TYPICAL FOR ALL SIMILAR ROOFING CONDITIONS UNLESS OTHERWISE
A18 INDICATED.
EXTENSIVE
A-1.7 2. UNLESS OTHERWISE NOTED, MINIMUM ROOF SLOPE IS 1/4" PER FOOT. PROVIDE TAPERED
VEGETATIVE STEP OVER
ROOF SYSTEM PARAPET INSULATION (EVEN IF NOT SHOWN ON THIS PLAN) AS REQUIRED TO MAINTAIN MINIMUM REQUIRED

Suite 600
AT LOCKABLE SLOPE TO ROOF DRAINS AND ELIMINATE ANY AREAS OF POTENTIAL STANDING WATER. PROVIDE
ROOF HATCH TYPE 1 TAPERED INSULATION (MINIMUM 1/4" PER FOOT SLOPE) AT ALL CRICKETS INDICATED TO DRAINS.
GATE PV PANELS OMITTED IN THIS AREA COORDINATE HEIGHTS OF ALL FLASHINGS AND EXPANSION JOINT CAPS WITH TAPERED INSULATION
8 8 TO MAINTAIN MINIMUM DIMENSIONS DETAILED.
3. ALL ROOF PENETRATIONS AND ACCESSORIES (DRAINS, VENTS, ETC.) ARE TO BE INSTALLED AND
DD FLASHED IN COMPLIANCE WITH THE CURRENT EDITIONS OF N.R.C.A. ROOFING AND
EE WATERPROOFING MANUAL AND S.M.A.C.N.A. (ARCHITECTURAL SHEET METAL MANUAL)
8.2 8.2
4. COORDINATE WITH MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR ITEMS (INCLUDING
G 5.
UNIT SIZES AND LOCATIONS) NOT SHOWN OR SCHEMATICALLY SHOWN ON ROOF PLANS.
CURBS FOR ROOF TOP MECHANICAL EQUIPMENT ARE PROVIDED BY THE MECHANICAL
G
FE CONTRACTOR. REFER TO TYPICAL CURB FLASHING DETAIL FOR BLOCKING AND FLASHING
REQUIREMENTS. PROVIDE ALL BLOCKING NECESSARY TO ACHIEVE LEVEL MECHANICAL CURBS AT
ALL LOCATIONS. MAINTAIN MINIMUM 8" FROM TOP OF CURB TO ADJACENT ROOF. PROVIDE
A15 TAPERED CRICKETS (MINIMUM 1/2" PER FOOT SLOPE) AROUND ALL MECHANICAL EQUIPMENT
UP CURBS.
A-7.7
6. THE ROOF DRAIN AND MECHANICAL UNIT LOCATIONS SHOWN ON THE ROOF PLAN ARE
9 9 APPROXIMATE. COORDINATE WITH MECHANICAL AND PLUMBING DRAWINGS FOR EXACT
LOCATIONS.
9.1 ROOF LADDER 9.1 7. PRIOR TO FLASHING OVERFLOW ROOF SCUPPERS AND ROOF DRAIN, ROOFING CONTRACTOR
SHALL BE REQUIRED TO CONFIRM MAXIMUM DRAIN PIPE HEIGHT OF 3" ABOVE ROOF IN
ACCORDANCE WITH PLUMBING DRAWINGS.

FE
8. START TAPERED INSULATION AT SUMP PLATES. INSULATION SHALL BE TAPERED DOWN FROM ALL
(4) SIDES OF INDICATED SUMP. REFERENCE TYPICAL ROOF DRAIN DETAIL A15/A-1.9.
9. IN ACCORDANCE WITH SPECIFICATION SECTION #07620 SHEET METAL, FLASHING AND TRIM,
ROOFING CONTRACTOR SHALL BE REQUIRED TO PROVIDE RECEIVER FLASHING TO MASONRY
F CONTRACTOR FOR INSTALLATION. ROOFER TO SOLDER JOINTS IN STAINLESS STEEL FLASHING. F
10. PROVIDE WALKWAY PROTECTION WHERE INDICATED AND AT ALL SIDES OF MECHANICAL ROOF
TOP UNITS REQUIRING SERVICE AND AT TOP AND BOTTOM OF ALL ROOF STAIRS.
10 10 11. ALL ROOF TOP EQUIPMENT (EXCLUDING PREFINISHED ITEMS) SHALL BE FIELD PAINTED.
12. WHERE INDICATED, REFER TO PLUMBING DRAWINGS FOR RADON PIPE DETAIL. FLASHING SHALL BE

13.
IN ACCORDANCE WITH TYPICAL DETAILS.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING FRT WOOD BLOCKING AS REQUIRED TO
GP# 21553
ACCOMMODATE ALL PROFILES OF FINISHED ROOFING INCLUDING AT CRICKETS AND TAPERED
INSULATION AT WALLS, PARAPETS AND GRAVEL STOPS. GRAVEL STOPS AT GUTTERS TO BE
STAINLESS STEEL WITH SOLDERED JOINTS.
14. COORDINATE HOSE BIB LOCATIONS ON ROOF WITH MEP PLANS.

11 11
ROOF SYMBOLS KEY
ROOF DRAIN WITH TAPERED INSULATION - TYP. SUMP SHALL BE 4'-0" X 3'-0"
E RE: A8/A-1.9 SIMILAR E
11.4 ROOF DRAIN WITH TAPERED INSULATION - TYP. SUMP SHALL BE 4'-0" X 4'-0"
SEE DETAIL FOR OVERFLOW AT EACH DRAIN, RE: A8/A-1.9

DIRECTION OF SLOPE FROM HIGH POINT - ROOF SLOPES


@ 1/4" PER FOOT, MINIMUM, UNLESS OTHERWISE NOTED

ROOF PLAN - PHOTOVOLTAIC ARRAY


T.O.M. X'-X"
TOP OF MASONRY
12

CITY OF BALTIMORE, MARYLAND


A1 T.O. ICF X'-X"
TOP OF ICF (INSULATED CONCRETE FORM WALL)

T.O.S. X'-X" TOP OF STEEL


D A2 D

HOLABIRD ACADEMY PK-8


J.B. X'-X"
POLYCARBONATE GLAZING

JOIST BEARING
PHOTOVOLTAIC PANELS

A18 B.O.D. X'-X"


A3 BOTTOM OF DECK
METAL A-1.9
ROOF SIM
FRAMING 1
13 A4 13 DETAIL @ TOP OF WALL
A101
ROOF ACCESS DOOR
SIM
1
A5 DETAIL @ LOW ROOF WALL - FLASHING CONDITION
A101

ROOF HATCH
C C
DS DOWNSPOUT DOWN TO CAST IRON DOWNSPOUT BOOT
AT GRADE - SEE CIVIL DRAWINGS FOR CONNECTION
EX4 EX4
FDC O.S. OVERFLOW SCUPPER - SEE DETAIL F6/A-1.9

ENTRANCE F12
CANOPY BELOW PHOTOVOLTAIC PANELS (PV)
A-4.1 DATE DESCRIPTION
BALLAST AT PERIMETER OF VEGETATIVE ROOF

ROOF WALKWAY - 36" WIDE CAPSHEET ADHERED TO ROOF PER


MANUFACTURER'S RECOMMENDATIONS AT LOW SLOPE ROOF.
EXB F G.2 G.9 H J J.1 K N Q EXC
B EXTENSIVE VEGETATIVE ROOF
B
GENERAL VIEW NOTE (NOTES APPLY TO ALL 3D VIEWS)

24"x24" PAVERS ONE ADJUSTABLE ELEVATOR PEDESTALS AT OUTDOOR


THIS AXONOMETRIC OR PERSPECTIVE VIEW IS TO AID IN THE GENERAL VISUALIZATION OF THE PROJECT. CLASSROOM
SOME ELEMENTS MAY BE MISSING FOR CLARITY.

FOR CONSTRUCTION DETAILS, REFERENCE THE PLANS, SECTIONS, AND ENLARGED DETAILS AS WELL AS TUBULAR SKYLIGHT, TYPES 1 AND 2

A18
ROOF PLAN - PV LAYOUT
1/16" = 1'-0"
ENGINEERING DRAWINGS.

Scale: 1 inch = 16 feet


A-1.8
03/13/2017
BID SET
0 8' 16' 32' 48'
A N © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

48" X 48" ROOF HATCH


4' - 0"
ROOF CURB.

M TYPICAL ROOFING
M

REF TO MANUF REQ.


SYSTEM ON EXISTING EXTERIOR FRT WOOD
AND NEW STEEL DECK BOCKING RE: D14/A-1.6
ROOF HATCH
LADDER -
SEE SPECS.

SEE STRUCT DWGS


FOR STEEL SUPPORT.

L L

70.
00°
8" 4" 1'-4" @ OPENING 4"

ROOF HATCH / LADDER SECTION


4"

K12 3/4" = 1'-0"


PROVIDE ANCHOR AS REQ'D INTO
METAL PANEL W/ FRT BLOCKING
PRE-FIN. ALUM DOWNSPOUT STRAP
GRAVEL STOP 3 STRAPS PER 10 FOOT SECTION
CONT. BEAD OF SEALANT, TYP.
RIVETED FASTENERS
K PRE-FIN. ALUM 6"x6" DOWNSPOUT
DRAW BAND K
HEMMED SCUPPER TRIM AT TOP AND WATERTIGHT STAINLESS STEEL SHEET METAL INSULATED METAL SLEEVE
SIDES - MATCH SCUPPER THICKNESS RAIN COLLAR - OVERLAP FLASHING COLLAR 4" SECURED TO STEEL DECK
SHEET METAL FLASHING COLLAR (EXTEND 8"
PRE-FIN. ALUM ROOF SCUPPER, ABOVE ROOF) PROVIDE MIN 1/4" CLEAR BETWEEN
FULLY WELDED HEMMED SCUPPER TRIM AT TOP AND COLLAR AND SUPPORT
SIDES - MATCH SCUPPER THICKNESS FULLY ADHERED TPO FLASHING
(EXTEND 8" MIN. ABOVE ROOF)
LOCK SCUPPER AROUND TRIM FASTENER AND SEAM PLATE,
AND PROVIDE SEALANT ACCEPTABLE TO ROOF MANUF.

2"
PRE-FIN. ALUM ROOF SCUPPER, T.P.O. ROOF SYSTEM WELD, TYP.
FULLY WELDED
FULLY ADHERED T.P.O. ROOF

SEE SECTION
SEALANT AT TRIM PERIMETER T.P.O. FLASHING MEMBRANE SYSTEM ON COVER
BOARD AND ROOF INSULATION
J 2" 1' - 4" 2"
LOCK SCUPPER AROUND CONDUCTOR J
LOCK SCUPPER AROUND TRIM HEAD AND PROVIDE SEALANT
AND PROVIDE SEALANT NOTE: CONTRACTOR TO COORDINATE HEIGHT OF
OVERFLOW ROOF DRAIN SCPPER WITH ARCHITECT

1"
PRE-FIN. ALUM CONDUCTOR HEAD,
1' - 8" FULLY WELDED SECURE WOOD SPACERS WITH 1/2" DIA
LOCK SCUPPER AROUND CONDUCTOR MACHINE BOLTS INTO 2 3/8" DOUBLE ACTING
STEEL ROOF DECK CUT INSULATION TO FIT EXPANSION SHEILDS SOLID CMU DRILL

8"
HEAD AND PROVIDE SEALANT 1 LAYER OF COVER BOARD INSULATION SNUGLY AROUND PIPE RECESS INTO 4"X4" WOOD SPACERS FOR
PROVIDE AND SECURE 16"x16" SQUARE RIGID INSULATION MECHANICALY
BRICK CLEARANCE
PRE-FIN. ALUM CONDUCTOR HEAD, PLATE SAME GAUGE AS STEEL DECK TO FASTENED TO DECK
FULLY WELDED PROVIDE SOLID SUPPORT FOR COMBRESSIBLE FILLER, TYP. SEAL ALL GAPS BETWEEN
INSULATION OVER OPEN STEEL DECK DOWNSPOUT NOZZLE - SEE PIPE & CMU
OVERFLOW NOZZLE - SEE
6" 7" FLUTE AT EDGES PLUMBING DWGS FOR SPECIFICATIONS (SIZE OF 1' - 0" +/-
PRE-FIN. ALUM 6"x6" DOWNSPOUT W/ 3 REQUIRED PIPE SIZE 8"
8"

NOZZLE TO FIT DRAIN PIPE)

H
STRAPS PER 10 FOOT SECTION
TYPICAL HOT STACK (TPO) 8" X 8" CUT OUT FOR 6" DIA PIPE, SAW CUT
H

www.grimmandparker.com
H13 1 1/2" = 1'-0"
INSTALL NOZZLE, SCUTCHEON
PLATE AND 2"-4"+/- LENGTH OF
BRICK & CMU TO EXACT DIMENSIONS

FOR 8" DIA PIPE

11720 Beltsville Drive

Calverton, MD 20705
. P OR
THREADED PIPE AS A SINGLE DRAIN PIPE (SEE
PRE-FIN. ALUM 6"x6" DOWNSPOUT W/ 3

D IA " F
IPE

8 3/8"
ASSEMBLED UNIT TO THE 4"X4" CL PIPE AND

Tel: 301.595.1000
PLUMBING DRAWINGS)

6 " 8 1 /4
STRAPS PER 10 FOOT SECTION

8"
TREADED WOOD SPACERS NOZZLE

D=

Suite 600
CONT. BEAD OF SEALANT, TYP. MANUFACTURE'S PRE-MOLDED
TPO FLASHING
BRICK COURSING ESCUTCHEON PLATE SECURED TO BRICK) THREAD 2"-4"+ LENGTH OF PIPE
DRAW BAND INTO DOWNSPOUT NOZZLE AND
FASTENER AND SEAM PLATE,
SCUPPER AND CONDUCTOR HEAD DETAIL ACCEPTABLE TO ROOF MANUF, TYP. INSTALL AS A UNIT THRU THE WALL,
DURING CONSTRUCTION OF
G18 1 1/2" = 1'-0"
T.P.O. ROOF SYSTEM WELD, TYP. FULLY ADHERED T.P.O. ROOF
MEMBRANE SYSTEM ON COVER
3 1/2" X 4" (3 1/2" + 1/2"
EXPOSURE 1 PLYWOOD) X 2'- 3 1/2" TYPICAL EXTERIOR WALL CONSTRUCTION MASONRY

G NOTE: PROVIDE ROOFING MANUF'S. APPROVED


BARRIER BETWEEN TPO MEMBRANES AND NON-
BOARD AND ROOF INSULATION 4" TREATED WOOD SPACERS,
CUT OUT 2" INSULATION AND 3 1/2" WIDE AND 4" DEEP (3 1/2" + G
COMPATIBLE AIR BARRIER. SECURE BARRIER BOLT TO CMU WALL BEHIND 1/2" EXPOSURE 1" PLYWOOD) X 1'-8"
11 1/8" TO AIR BARRIER. + LONG TREATED WOOD SPACED
FULLY ADHERED TPO MEMBRANE UP
PARAPET WALL OVER BLOCKING,
AND LAP VERTICAL WALL FLASHING 11 1/8" 0"
CONT. FRT. WOOD BLOCKING
AND MEMBRANE BARRIER
CONT. SEALANT

TPO MEMBRANE / FLASHING FULLY


ADHERED TO SUBSTRATE 1 LAYER OF COVER BOARD
OVERFLOW SCUPPER DETAIL
4"

CONT. BEAD OF SEALANT, TYP.


T.P.O. ROOF SYSTEM WELD STEEL ROOF DECK
RIGID INSULATION
MECHANICALY FASTENED
F9 1 1/2" = 1'-0"
CONT. SEALANT BY ROOF MANUF. PROVIDE AND SECURE 16"x16" SQUARE TO DECK

FASTENER PER ROOF MANUF. REQ. PLATE SAME GAUGE AS STEEL DECK TO COMBRESSIBLE FILLER, TYP. DRAIN CHAMBER PANELS FLUSH
METAL PANEL SCUPPER TRIM PROVIDE SOLID SUPPORT FOR INSULATION WITH TRAY SIDEWALLS DRAIN INSPECTION COVER W/
F ASSEMBLY WITH FLASHING 5/8" EXT. F.R.T. RATE OVER OPEN STEEL DECK FLUTE AT EDGES LOCKABLE LID CENTERED OVER F
AND SEALANT, TYP. PLYWOOD SHEATHING 5' - 0" TYP. ROOF DRAIN
METAL SCUPPER SLEEVE 1' - 0" 2' - 0" 1' - 0" INTERNAL OVERFLOW WATER
FASTENER PER ROOF MANUF. REQ.
TYPICAL PRE-MOLDED PIPE FLASHING DETAIL (TPO) VANDAL-PROOF DOME
24" X 24" RECEIVER
4'-0" X 4'-0" TAPERED INSULATION SUMP TO DRAIN
DAM

GP# 21553
T.P.O. ROOF SYSTEM WELD F13 1 1/2" = 1'-0"
SS PERFORATED GRAVEL GUARD
FLASHING CLAMP / GRAVEL STOP VEGETATIVE
METAL EDGE, PART OF
VEGETATIVE ROOF SYSTEM
AROUND PERIMETER OF
4LB PER SQ. FT. LEAD FLASHING - IN BED SYSTEM, BUILT-UP OVERFLOW DRAIN
FULLY ADHERED T.P.O. ROOF
CONT. SEALANT, TYP. MEMBRANE SYSTEM ON COVER OF ROOFING CEMENT ON COMPLETED
BOARD AND ROOF INSULATION ROOF MEMBRANES, PRIME TOP SURFACE
METAL COLLECTOR BOX, DOWN SPOUT TO BEFORE STRIPPING

3"
BOOT BASE BID, TO RAIN CISTERN ADD ALTERNATE
CONT. BEAD OF SEALANT, TYP.
DRAW BAND, TYP.

WATERTIGHT STAINLESS STEEL SHEET METAL


E CONT. 10" 16 Ga. BRIDGE PLATE - WHEN
DECK FLUTES ARE PARALLEl TO WALL
NOTE: AT SQUARE ROOF
RAIN COLLAR - OVERLAP FLASHING COLLAR 4" E
PENETRATION FOLLOW ROOF FULLY ADHERED TPO FLASHING
EXT. FRT. WOOD BLOCKING MANUFACTURES SQUARE (EXTEND 8" MIN. ABOVE ROOF)
PENETRATION DETAILS. MIN R-30 ROOF INSULATION TO SLOPED
STEEL BEAM(S), END PLATE(S), FASTENER AND SEAM PLATE, CRICKETS. SEE ROOF PLAN
ANGLE(S), AND STEEL DECK - T.P.O. ROOF SYSTEM WELD, TYP. ACCEPTABLE TO ROOF MANUF.
SEE STRUCTURAL DWGS. STEEL ANGLE SUPPORT FRAME - SEE STRUCT
FULLY ADHERED T.P.O. ROOF ROOF DRAIN & STORM WATER
ROOF DRAIN SUMP RECEIVER STORMWATER PIPING - SEE MECH
OF PERIMETER BEAM MEMBRANE SYSTEM ON COVER PIPING INSULATION - SEE PLMB
BOARD AND ROOF INSULATION UNDER DECK CLAMP ADJUSTABLE EXTENSION
NOTE: WHERE REQUIRED PROVIDE EXT. F.R.T. WD. BLOCKING COORD. ROOF DRAIN BODY
& PROVIDE SOLID BLOCKING TO MATCH THE DEPTH OF RF. INSULATION
AND TAPERED INSULATION WHERE APPLICABLE - ANCHOR TO BRIDGE
ROOF DRAIN DETAIL AT VEGETATIVE ROOF

CITY OF BALTIMORE, MARYLAND


PLATE W/ DOUBLE ROW OF FASTENERS @ 16" O.C. TYPICAL

D5 1" = 1'-0"
D STEEL ROOF DECK 1 LAYER OF COVER BOARD D
PARAPET @ METAL PANEL THRU WALL SCUPPER

HOLABIRD ACADEMY PK-8


PROVIDE AND SECURE 16"x16" SQUARE RIGID INSULATION
F18 1 1/2" = 1'-0"
13
PLATE SAME GAUGE AS STEEL DECK TO
PROVIDE SOLID SUPPORT FOR INSULATION
MECHANICALY FASTENED
TO DECK
OVER OPEN STEEL DECK FLUTE AT EDGES COMBRESSIBLE FILLER, TYP.

TYPICAL PIPE FLASHING DETAIL (TPO)


LINE OF WALL BEYOND
5/16" S.S. FORMED CHECKERED
C13 1 1/2" = 1'-0" 5' - 0" TYP.

ROOF DETAILS
STEEL PLATE - SLOPE TO EXTERIOR
DOOR AS AND INSTALL IN BED OF MASTIC & 1' - 0" 2' - 0" 1' - 0"
SCHEDULED COUNTERSINK EXP. BOLTS
PRE-FIN. ALUM. DOOR 4" SOLID CMU 4'-0" X 4'-0" TAPERED INSULATION SUMP TO DRAIN 24" X 24" RECEIVER NOTE: IECC REQUIRES R-30 CONTINUOUS
DOOR SILL VANDAL-PROOF DOME
INSULATION ABOVE ROOF DECK. INSULATION
THRESHOLD
C CONTINUOUS AIR BARRIER
CONT. BEAD OF SEALANT 2" 4" 1' - 6" SS PERFORATED GRAVEL GUARD THICKNESS MAY BE REDUCED PER IECCC § C
TRANSITION MEMBRANE DRAW BAND MIN MIN 30" X 30" LEAD FLASHING 402.2.2 EXCEPTION #1 PROVIDED THE AREA-
FLASHING CLAMP / GRAVEL STOP
BASE FLASHING UNDER CHECKERED WEIGHTED U-FACTOR IS EQUIVALENT TO THE
TPO ROOF SYSTEM MEMBRANE
STEEL PLATE TO WRAP OVER SILL FULLY ADHERED TPO FLASHING 4LB PER SQ. FT. LEAD FLASHING - IN BED SAME ASSEMBLY WITH THE MINIMUM
(EXTEND 8" MIN. ABOVE ROOF) INTERNAL OVERFLOW OF ROOFING CEMENT ON COMPLETED REQUIRED R-VALUE OVER TEH ENTIRETY OF
CANT WATER DAM THE ROOF, CONTRACTOR SHALL PROVIDE
1'-0" MIN.

ROOF MEMBRANES, PRIME TOP SURFACE


ROOF INSULATION WITH FASTENER AND SEAM PLATE, BEFORE STRIPPING CALCULATIONS VERIFYING IECC COMPLIANCE.
COVERBOARD ACCEPTABLE TO ROOF MANUF.
4" CONCRETE CURB - 4" AND TPO ROOF MEMBRANE
T.P.O. ROOF SYSTEM WELD DATE DESCRIPTION

2"
SEE STRUCTURAL
FULLY ADHERED T.P.O. ROOF
MEMBRANE SYSTEM ON COVER
CONCRETE SLAB, SEE
BOARD AND ROOF INSULATION
STRUCTURAL
4"

B B

MIN R-30 ROOF INSULATION TO SLOPED STEEL ANGLE SUPPORT FRAME - SEE STRUCT
STEEL DECK AND ANGLE, SEE STEEL ROOF DECK 1 LAYER OF COVER BOARD EXTEND ROOFING MEMBRANES,
STRUCTURAL CRICKETS. SEE ROOF PLAN LEAD FLASHING, & BASE
PROVIDE AND SECURE 16"x16" SQUARE RIGID INSULATION FLASHINGS / STRIPPINGS UNDER ROOF DRAIN SUMP RECEIVER
PLATE SAME GAUGE AS STEEL DECK TO MECHANICALY FASTENED STEEL DECK - SEE STRUCT
STEEL JOIST AND BEAM FLASHING CLAMP / GRAVEL STOP
PROVIDE SOLID SUPPORT FOR INSULATION TO DECK UNDER DECK CLAMP

A-1.9
OVER OPEN STEEL DECK FLUTE AT EDGES COMBRESSIBLE FILLER, TYP. ROOF DRAIN & STORM WATER ADJUSTABLE EXTENSION
GYP. BOARD CONTINUOUS TO PIPING INSULATION - SEE PLMB ROOF DRAIN BODY
STORMWATER PIPING - SEE MECH
UNDERSIDE OF DECK

DOOR SILL AT ROOF ACCESS TYPICAL ROOF VENT DETAIL (TPO) TYPICAL ROOF DRAIN DETAIL 03/13/2017
A18 1 1/2" = 1'-0" A13 1 1/2" = 1'-0" A8 1 1/2" = 1'-0" BID SET
A © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

EXTEND MEMBRANE FLASHING 8"


ABOVE ROOF J18 L10
BALLAST 1 1/2" O.D. GALV. A-1.10 A-1.10
STEEL RAIL, TYP.
1' - 2" STAINLESS STEEL HIGH CL
CONTINUOUS SEALANT METAL EDGE, PART OF CL
VEGETATIVE ROOF SYSTEM SECURITY HASPLOCK WITH CL CL 8 1/4" CL 3 '- 6" TYP.
DEADLOCK DESIGN LOCKING 3' - 4" ( 4' - 0" ) MAX.
1 1/2" O.D. GALV. 1 1/2" O.D. GALV.

MAX
4"
STEEL RAIL, TYP. STEEL GUARDRAIL, TYP. MECHANISM, MASTER KEYED
VEGETATIVE ROOF SYSTEM

MAX
MAX
CL CL CL CL

4"
4"
1 1/2" O.D. GALV. STEEL GUARDRAIL,
M TYP., SEE DETAIL A18/A-1.5 1 LAYER OF 1" COVER BOARD
INSULATION SET IN ASPHALT L14
1 1/2" O.D. GALV.
STEEL RAIL, TYP.
3/4" O.D. GALV. STEEL
PICKETS, TYP.
M
A-1.10 4" MAX. 4" MAX.
3/4" O.D. GALV. STEEL

3' - 6" MIN.


3/4" O.D. GALV. STEEL PICKETS, TYP.
VEGETATIVE ROOF SYSTEM
PICKETS @ 4" O.C.
MAX, TYP.

1 LAYER OF COVER BOARD


INSULATION SET IN ASPHALT TOP OF PAVERS VEGETATIVE ROOF
FIELD FABRICATED RIGID INSULATION MECHANICALY AND BALLAST AT
WATERTIGHT STAINLESS STEEL FASTENED TO DECK RIGID INSULATION GUARDRAIL
SHEET METAL RAIN COLLAR MECHANICALY

MAX
4"
CONCRETE ROOF DECK FASTENED TO DECK
BALLAST WELD PIPE TO 12" SQUARE BASE ELEV. 14'-8"
COMPRESSIBLE PLATE - BOLTED TO CONCRETE
FILLER, TYP. DECK WITH 3/8" J-BOLTS
METAL EDGE, PART OF CONCRETE ROOF DECK
L 1 1/2" O.D. GALV.
STEEL RAIL, TYP.
VEGETATIVE ROOF SYSTEM L
VEGETATIVE ROOF SYSTEM DETAIL AT RAILING BASE PLATE CONNECTION 2X4 EXT FRT WOOD BLOCKING
GUARDRAIL SECTION GATE @ SOLAR LAB ROOF GUARDRAIL @ SOLAR LAB ROOF
L14 1 1/2" = 1'-0"
AT ANCHOR BOLTS
2X4 EXT FRT WOOD
L10 3/4" = 1'-0" FULLY ADHERED TPO MEMBRANE UP PARAPET
L6 3/4" = 1'-0" L4 3/4" = 1'-0"
FRAMING @ 16" O.C. WALL OVER TRANSITION MEMBRANE BARRIER AND
1 LAYER OF 1" COVER BOARD CONT. 2X4 EXT FRT WOOD BLOCKING, AND EXTEND DOWN THE FRONT FACE EXB
INSULATION SET IN ASPHALT OF WALL THE MIN. DISTANCE REQUIRED BY THE FULLY ADHERED TPO MEMBRANE UP PARAPET
COMPRESSIBLE FILLER, TYP. ROOF MANUF. TYPICAL ALL PARAPETS. WALL OVER TRANSITION MEMBRANE BARRIER AND
PROVIDE ROOFING MANUF'S. BLOCKING, AND EXTEND DOWN THE FRONT FACE

2 1/2"
APPROVED BARRIER BETWEEN TPO CONT. 2X4 EXT FRT WOOD OF WALL THE MIN. DISTANCE REQUIRED BY THE
MEMBRANES AND NON-COMPATIBLE ROOF MANUF. TYPICAL ALL PARAPETS.
PRE-FINISHED 2 PIECE METAL
AIR BARRIER TRANSITION COPING WITH CONTINUOUS CLEAT PROVIDE ROOFING MANUF'S. APPROVED PRE-FINISHED METAL COPING

5"
MEMBRANE. SECURE BARRIER TO BARRIER BETWEEN TPO MEMBRANES AND NON-
TOP OF ICF / WITH CONTINUOUS CLEAT
AIR BARRIER TRANSITION COMPATIBLE AIR BARRIER TRANSITION
MEMBRANE. MASONRY MEMBRANE. SECURE BARRIER TO AIR BARRIER

1"
CONTINUOUS CLEAT TRANSITION MEMBRANE. TOP OF MASONRY
K 32' - 0" K

1' - 5 1/2"
5/8" FRT PLYWOOD SHEATHING

6"

8"
TPO MEMBRANE / FLASHING FULLY CONTINUOUS SEALANT
ADHERED TO SUBSTRATE

9"
COMPRESSIBLE FILLER, TYP.
6" PERIMETER FASTENING STRIP, WITH
PLATES AND FASTENERS SPACED @ 12" O.C. CONTINUOUS CLEAT
2 LAYERS CONT. 3/4" EXT. F.R.T. PLYWOOD
5/8" FRT PLYWOOD SHEATHING 2 LAYERS CONT. 3/4" EXT. F.R.T. PLYWOOD
T.P.O. ROOF MEMBRANE HOT GLUED & SCREWED AND BOLTED INTO PARAPET
GLUED & SCREWED AND BOLTED INTO
AIR WELD TPO MEMBRANE / FLASHING FULLY PARAPET
CONCRETE ROOF DECK RIGID INSULATION MECHANICALY CONT. 2X. EXT. FRT. WOOD BLOCKING ADHERED TO SUBSTRATE
FASTENED TO DECK CONTINUOUS SEALANT 6" PERIMETER FASTENING STRIP, WITH PLATES CONT. 2X. EXT. FRT. WOOD BLOCKING
AND FASTENERS SPACED @ 12"O.C.

1' - 6"
CONTINUOUS AIR BARRIER TRANSITION MEMBRANE FROM 4"
DOWN ICF EPS FOAM BEHIND BARRIER FOR TPO MEMBRANE, UP T.P.O. ROOF MEMBRANE HOT AIR WELD CONTINUOUS AIR BARRIER TRANSITION MEMBRANE FROM 4"
FULLY ADHERED T.P.O. ROOF DOWN CMU FACE BEHIND BARRIER FOR TPO MEMBRANE, UP
GUARDRAIL SECTION @ PICKETS BENCH POST EXTEND MEMBRANE FLASHING 8"
MEMBRANE ON COVER BOARD AND OVER PARAPET AND DOWN OVER WOOD BLOCKING,
EXTENDING 4" MIN. BEHIND ICF EPS FOAM
FULLY ADHERED T.P.O. ROOF OVER PARAPET AND DOWN OVER WOOD BLOCKING,

J J18 1 1/2" = 1'-0"


ABOVE ROOF
ROOF INSULATION
1/2" X 12" ANCHOR BOLTS @ 16"
O.C. STAGGERED COUNTERSINK
MEMBRANE SYSTEM ON COVER BOARD
AND ROOF INSULATION
EXTENDING 4" MIN. BEHIND SPRAY FOAM INSULATION
J
CONTINUOUS SEALANT BENCH POST EXTENDED TO 1/2" X 12" ANCHOR BOLTS @ 16"
METAL EDGE, PART OF
ACCOUNT FOR THICKNESS OF ANCHOR BOLTS INTO PLYWD. O.C. STAGGERED COUNTERSINK
VEGETATIVE ROOF SYSTEM
PAVER, PEDESTAL, AND ROOF AIR BARRIER ON EPS FOAM ANCHOR BOLTS INTO PLYWD.
PAVER ON PEDESTAL
VEGETATIVE ROOF SYSTEM MASONRY VENEER 2-5/8" EPS INSULATION
TAPERED INSULATION WHERE APPLICABLE -
MASONRY VENEER ANCHORS AT 16" O.C. SEE WALL SECTIONS AND ROOF PLAN MASONRY VENEER
CONT. 10" 16 Ga. BRIDGE PLATE - WHEN DECK
FLUTES ARE PARALLEL TO WALL AIR SPACE MASONRY VENEER ANCHORS AT 16" O.C.
1 LAYER OF 1" COVER ICF WALL SYSTEM: CONCRETE INFILL AND 2
BOARD INSULATION WHERE REQUIRED PROVIDE EXT. F.R.T. WD. BLOCKING AIR SPACE JOIST BEARNG
5/8" EPS FOAM EITHER SIDE (FORMS)
SET IN ASPHALT COORD. & PROVIDE SOLID BLOCKING TO MATCH THE CONCRETE SEE - SECTIONS & ROOF PLAN
DEPTH OF RF. INSULATION AND TAPERED INSULATION NOTE: PROVIDE TPO ROOF MANUF. CONT. 10" 16 Ga. BRIDGE PLATE - WHEN DECK
WHERE APPLICABLE - ANCHOR TO BRIDGE PLATE W/ INTERMEDIATE FASTENER AND WALL NOTE: PROVIDE TPO ROOF
FLUTES ARE PARALLEl TO WALL
DOUBLE ROW OF FASTENERS @ 16" O.C. TYPICAL FLASHING ATTACHEMENT AT HIGH MANUF. INTERMEDIATE
PARAPETS / WALLS AS DEFINED BY THE FASTENER AND WALL FLASHING
H H

www.grimmandparker.com
TPO ROOFING MANUF. ATTACHEMENT AT HIGH
STEEL DECK AND STRUCTURE - SEE STRUCTURAL
WHERE REQUIRED PROVIDE EXT. F.R.T. WD. BLOCKING PARAPETS / WALLS AS DEFINED

11720 Beltsville Drive

Calverton, MD 20705
RIGID INSULATION COORD. & PROVIDE SOLID BLOCKING TO MATCH THE BY THE TPO ROOFING MANUF.
MECHANICALY FASTENED TO DEPTH OF RF. INSULATION AND TAPERED INSULATION

Tel: 301.595.1000
DECK WHERE APPLICABLE - ANCHOR TO BRIDGE PLATE W/
CONCRETE ROOF DECK 5/8" 2 5/8" 10" 2 5/8" 3 5/8" DOUBLE ROW OF FASTENERS @ 16" O.C. TYPICAL
3' - 6"

WELD PIPE TO 12" SQUARE 2 5/8" SEE SECTION 2 5/8" 1 1/2" 3 5/8"
COMPRESSIBLE BASE PLATE - BOLTED TO 1' - 9" 1 1/2" 5/8"
FILLER, TYP. CONCRETE DECK WITH 3/8" STEEL DECK AND STRUCTURE - SEE STRUCTURAL

Suite 600
J-BOLTS
STEEL BEARING PLATE @ EACH JOIST - SEE
STRUCTURAL

DETAIL AT BENCH POST BASE PLATE CONNECTION PARAPET DETAIL @ GYM TYPICAL PARAPET DETAIL
G14 1 1/2" = 1'-0" G11 1 1/2" = 1'-0"
1' - 9"
G6 1 1/2" = 1'-0"
G G
3 5/8" 1 1/2" 2 5/8" 10" 2 5/8" 5/8"
1' - 3 1/4" 1/2" X 21/2" GALV. STEEL FLAT AIR BARRIER ON EPS INSULATION CONT. 3/4" EXT. F.R.T. PLYWOOD AND FULLY ADHERED TPO MEMBRANE ON 3/4" EXT. FRT.
BAR SIDERAILS SPACED @ 18" BRICK VENEER WOOD BLOCK ANCHORED TO METAL PLYWOOD AND EXT. FRT. WOOD BLOCKING, AND
7 5/8" SEE SECTION FRAMING EXTEND DOWN THE FRONT FACE OF WALL THE MIN.
CLEAR w/ EASED EDGES CAVITY MORTAR DIVERTER
DISTANCE REQUIRED BY THE ROOF MANUF.
GALV. STEEL FLAT BAR GRATING CONT. FLEXIBLE FLASHING TOP - 16 GA. MIN., 4" COLD
PLATFORM w/ NON-SLIP SURFACE 7 3/4"
FORMED METAL STUD FRAMING 16" O.C. EX3 6
- WELD TO SIDE RAILS CAVITY VENT AT 16" O.C.
MAX FRAMING SECURED AND
CONT. FLEXIBLE FLASHING ANCHORED TO STRUCTURAL METAL PRE-FIN METAL GRAVEL STOP W/
PRE-FINISHED PRE-FIN ALUM NOTE: PROVIDE TPO ROOF CONTINUOUS CLEAT

2"
BOND TO S.S. RECIEVER PLATES - SEE STRUCTURAL DRAWINS
COPING WITH CONTINUOUS MANUF. INTERMEDIATE 2' - 9 1/4" 1/2" 1 3/4"
CLEAT S.S. RECIEVER AND COUNTER FLASHING FASTENER AND WALL FLASHING TPO MEMBRANE / FLASHING FULLY T.O. PLYWD.

4"

2"

2 1/2"
ATTACHEMENT AT HIGH ADHERED TO SUBSTRATE
TERMINATION BAR WITH FASTENERS SPACED 6" PARAPETS / WALLS AS DEFINED
SLOPE & BLOCKING
O.C. MAX. WATER CUTOFF AND MASTIC AND BY THE TPO ROOFING MANUF. T.O. PLYWD.

7 1/2"
TOP OF MASONRY SEALANT 2 8 35' - 6"
F F

3/4"
26" MIN.

5"
CONTINUOUS TRANSITION MEMBRANE
FACE OF SHEATHING AT IFC PARAPET WITH

4"
30" MAX. CLEAR 2"

1 1/2"
TPO MEMBRANE / FLASHING FULLY ADHERED TO FROM BASE OF EXT. WALL TO T.O. ICF

1' - 5 1/2"
SUBSTRATE UP TO TERMINATION BAR AND FASTENER 8" CONCRETE CORE.

1"
TERMINATE AT THRU-WALL FLASHING

FLASHINGS SHALL BE EMBEDDED IN


PROVIDE BATT INSULATION AT EXPOSED 35' - 0"
CLOSED CELL BACKER 1/2" X 21/2" GALV. FLASHING ELEV. (8" MIN. ABOVE ROOF) HEAD AND SIDE OF ICF PARAPET WALL
GP# 21553

1/2" 6 3/4"
STEEL FLAT MORTAR JOINT

10"
ROD AT EJ WHERE
NEEDED BAR SIDERAILS w/ CONT. STEEL 6" X 1/4" PLATE AND HEAD
EASED EDGES STUDS, PROVIDE 8" X 1/4" STEEL PLATE
6" PERIMETER FASTENING STRIP, WITH PLATES AND AND HEAD STUDS AT 8" CONCRETE CORE
B.O. MTL. PANEL

1 3/4"
3/4" DIA. GALV. STEEL ROUND BAR FASTENERS SPACED AT 12" OC CONDITIONS SEE STRUCTURAL
10" CONCRETE AND 2-5/8" EPS INSULATION
1/2" X 21/2" GALV. STEEL FLAT BAR RUNGS @ 12" O.C., U.O.N.. w/ T.P.O. ROOF MEMBRANE HOT AIR ICF SYSTEM
BRACKETS, WELD TO SIDERAILS NON-SLIP SURFACE ON TOP 34' - 3"
GALV. STEEL FLAT WELD BOTTOM, VERTICAL, AND 1 1/2" PRE-FIN. METAL PANEL, TYPE 2 ON
12" MAX.

TYP. TPO. CONSTRUCTION 1/2" 1 3/4"


BAR GRATING CONT. STEEL ANGLE/PLATE AT MASONRY DIAGONAL - 18 GA. MIN., 4" COLD FORMED 1/4" SHIMS ON PRE-FIN. METAL FLASHING BY
LADDER ANCHOR POINT INTO PLATFORM w/ NON- METAL STUD FRAMING 16" O.C. MAX - AIR AND MOISTURE BARRIER ON
CONCRETE WALL VENEER SUPPORT - SEE STRUCTURAL METAL PANEL MANUF.
SLIP SURFACE FOR TYPE, SIZE, AND LOCATION SEE STRUCTURAL DRAWINS 1/2" EXT. FRT. PLYWD. SHEATHING ON
E - WELD TO SIDE
FULLY ADHERED T.P.O. ROOF MEMBRANE ON
4" METAL FRAMING E
RAILS
GALV. 5/8" DIA. HILTI HY150 ADHESIVE COVER BOARD AND ROOF INSULATION 5/8" ABUSE RESISTANT GYP BD 5/8" 2 5/8" 6" OR 8" 3 3/8" 1 1/2" 4 5/8" 1' - 7 3/4"
ANCHORS w/ 12" EMBEDMENT
TAPERED INSULATION WHERE APPLICABLE -
5' O.C., TYP.

LADDER RUNGS, TYP. VARIES 1/4"

2' - 0"
2' - 1 27/256" MIN.
B.O.D. SEE WALL SECTIONS AND ROOF PLAN JOIST BEARING
# RUNGS AND HEIGHT 1 1/2" PRE-FIN. METAL PANEL, TYPE 2 ON

OVERLAP
SEE - SECTIONS & VARIES
4 1/2" SEE - SECTIONS & ROOF PLAN 1/4" SHIMS ON
ROOF PLAN
3/4" GALV. VERTICAL GIRTS ON
MAX. SPACING

PROVIDE EXT. FRT. WOOD BLOCKING AT LOCATIONS WHERE NOTE: PROVIDE TPO ROOF MANUF. AIR AND MOISTURE BARRIER ON
THE TPO ROOFING SYSTEM'S PERIMETER FASTENERS ARE INTERMEDIATE FASTENER, WALL ICF WALL CONCRETE CORE VARIES
NOT LONG ENOUGHT TO ANCHOR TO THE METAL ROOF DECK FLASHING AND WELD ATTACHEMENT AT 5/8" EXT. FRT. PLYWD. SHEATHING
AND PERIMETER METAL BRIDGE PLATE. COORDINATE HEIGHT HIGH PARAPETS / WALLS AS DEFINED BY TPO ROOF MEMBRANE FLASHING SYSTEM

CITY OF BALTIMORE, MARYLAND


COL. OF EXT. FRT. WOOD BLOCKING WITH FASTENER LENGHT AND THE TPO ROOFING MANUF.
RUN SPACING NO LESS DEPTH OF TAPERED AND ROOF INSULTATION. ANCHOR EXT. METAL FLASHING BY METAL PANEL MANUF.
THAN 10", NO MORE FRT. WOOD BLOCKING TO BRIDGE PLATE W/ DOUBLE ROW
THAN 14" OF FASTENERS @ 16" O.C. TYPICAL
D 5.8 T.O. MASONRY D

3"
2"
STEEL ROOF DECK - SEE

HOLABIRD ACADEMY PK-8


STRUCTURAL 32' - 0"

8 1/2"
CONT. 10" 16 Ga. BRIDGE PLATE - WHEN TPO MEMBRANE / FLASHING FULLY

6 1/2"
6"
LADDER ANCHOR POINT TO DECK FLUTES ARE PARALLEl TO WALL ADHERED TO SUBSTRATE
OCCUR 8" ABOVE FLASHING STEEL BEARING PLATE @ EACH JOIST - FASTENER AND SEAM PLATE,
SEE STRUCT DWGS ACCEPTABLE TO ROOF MANUF.

2 5/8"
TERMINATION BAR WITH FASTENERS SPACED
6" O.C. MAX, WITH WATER CUTOFF MASTIC AT LOW ROOF FLASHING DETAIL T.P.O. ROOF WELD
COMPRESSION POINT BETWEEN TPO AND
WALL, AND SEALANT IN TOP TRAY (ICF C11 1 1/2" = 1'-0" FULLY ADHERED T.P.O. ROOF 2" 2 5/8" PRE-FIN METAL LEDGE CAP

ROOF DETAILS
COMPLIANT SEALANT) MEMBRANE ON COVER BOARD AND WITH CONT. CLEAT
ROOF INSULATION
ELEVATION. 6" COVERSTRIP ON HORIZONTAL BB CONT. EXT. FRT. 2X8 FRT WOOD BLOCKING
NOTE: PROVIDE TPO ROOF
FULLY ADHERED T.P.O. ROOF MEMBRANE
MANUF. INTERMEDIATE
ON COVER BOARD AND ROOF CONCRETE HAUNCH
FASTENER AND WALL FLASHING
INSULATION. EXTEND DOWN FRONT FACE
C ATTACHEMENT AT HIGH
PARAPETS / WALLS AS DEFINED ROOF LADDER ELEVATION TAPERED INSULATION WHERE
APPLICABLE - SEE WALL SECTIONS AND L14
OF WALL MIN. DISTRANCE REQUIRED BY 4" NOM BRICK VENEER
C
BY THE TPO ROOFING MANUF. C13 3/4" = 1'-0"
ROOF PLAN 6" A-1.10
ROOF MANUFACTURER. OVERLAP AIR
BARRIER TRANSITION MEMBRANE 1 1/2" AIR SPACE
FULLY ADHERED TPO MEMBRANE OVER
WOOD BLOCKING, AND EXTEND DOWN THE IFC SYSTEM'S 2-5/8" EPS INSULATION
FRONT FACE OF WALL THE MIN. DISTANCE TAPERED INSULATION WHERE APPLICABLE -
REQUIRED BY THE ROOF MANUF. SEE WALL SECTIONS AND ROOF PLAN
8 1/2"

CLOSED CELL BACKER AIR AND MOISTURE BARRIER


12" MAX.

ROD AT EJ WHERE DATE DESCRIPTION


TYP. TPO. NEEDED B.O.D. IFC SYSTEM'S CONCRETE CORE
CONSTRUCTION
14' - 4" SEE - SECTIONS & ROOF PLAN JOIST BEARING
PRE-FINISHED METAL FASICA
WITH CONTINUOUS CLEAT
CONT. 10" 16 Ga. BRIDGE PLATE - WHEN DECK 29' - 4"
CONTINUOUS SEALANT FLUTES ARE PARALLEL TO WALL 4 1/2"
CONT. 2X EXT. FRT. WOOD BLOCKING
PROVIDE EXT. FRT. WOOD BLOCKING AT LOCATIONS
B AND EXT. FRT. PLYWOOD STEEL ROOF DECK -
SEE STRUCTURAL WHERE THE TPO ROOFING SYSTEM'S PERIMETER B
1-1/2" PRE-FIN. METAL PANEL, TYPE 2 FASTENERS ARE NOT LONG ENOUGHT TO ANCHOR TO
1/4" SHIMS COMPRESSIBLE FILLER, , TYP.
THE METAL ROOF DECK AND PERIMETER METAL
3" HORIZ. GAV. Z-GIRTS BRIDGE PLATE. COORDINATE HEIGHT OF EXT. FRT.
AIR BARRIER STEEL BEAMS, SEE STRUCT WOOD BLOCKING WITH FASTENER LENGHT AND DEPTH
5/8" EXTERIOR SHEATHING DWGS FOR CONNECTIONS, OF TAPERED AND ROOF INSULTATION. ANCHOR EXT. 5/8" 2 5/8" 8" OR 10" 2 5/8" 1 1/2" 3 5/8"
TYP FRT. WOOD BLOCKING TO BRIDGE PLATE W/ DOUBLE
CONTINUOUS AIR BARRIER TRANSITION
MEMBRANE FROM TOP OF STEEL ROW OF FASTENERS @ 16" O.C. TYPICAL 3 1/4" VARIES 1' - 3 3/4"
PLATE, DOWN OVER WOOD BLOCKING,

A-1.10
STEEL DECK AND STRUCTURE - SEE STRUCTURAL
EXTENDING DOWN OVER EXTERIOR 1' - 7"
SHEATHING STEEL BEARING PLATE @ EACH JOIST -SEE
STRUCTURAL DWGS
03/13/2017
TYPICAL ROOF LADDER DETAIL (TPO) GRAVEL STOP DETAIL AT MEDIA PARAPET DETAIL AT CLASSROOM BID SET
A18 1 1/2" = 1'-0" A11 1 1/2" = 1'-0" A7 1 1/2" = 1'-0"
A © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

F G.2 G.9 H
F G.2 G.9 H PRE-FIN. EXTRUDED ALUM. FASCIA SUPPORT BRACKET

PRE-FIN. EXTRUDED ALUM. 4" FASCIA


G.2
PRE-FIN. EXTRUDED ALUM. FASCIA
CORNER SUPPORT ANGLE
4" PRE-FIN METAL 1-1/2" TRANSLUCENT
CANOPY ASSEMBLY PANEL ASSEMBLY
PRE- FIN. EXTRUDED ALUM. FLAT SOFFIT DECK SNAP
CAP CONNECTOR W/ SCREWS @ 24" O.C.
M M
12 12
3" X 6" WIDE FLAT SOFFIT EXTRUDED ALUM.
INTERLOCKING DECKING
DS FROM CANOPY
GUTTER
F4
5PT X 1 1/4" DECKING SCREW ( 3 PER
A-1.11 LOWER DECK MEMBER)
A1 A1

HSS TUBE PURLIN, SEE STRUCTURAL


POLYCARBONATE
PANEL BATTEN
12MM TRANSLUCENT STEEL BEAMS BEYOND
POLYCARBONATE PANELS

9' - 2 1/2"
L HSS TUBE PURLIN, SEE
STRUCTURAL
L
PRE-FIN. ALUM GUTTER

A2 A2 HSS TUBE BEAM, SEE STRUCTURAL

A12
A-4.5

9' - 2 1/2"
K A8 K
A-1.11
CANOPY- METAL DECK FLAT SOFFIT SECTION SECTION AT BATTEN BETWEEN PANELS
K9 3" = 1'-0" K5 3" = 1'-0"
44' - 0"

44' - 0"
A3 A3

REFER TO LIGHTING PLANS


FOR UNDER CANOPY
F9
STRIP LED LIGHTING
K5
A-1.11
12MM TRANSLUCENT
POLYCARBONATE PANELS, A-1.11 STEEL COLUMN BEYOND

9' - 2 1/2"
COLOR 2 PRE-FIN. EXTRUDED ALUM. 6" FASCIA, BEYOND

J A11 A18
PRE-FIN. EXTRUDED ALUM. FASCIA J
A15 SUPPORT BRACKET
4" RECTANGULAR DOWNSPOUT
A-1.11 A-1.11 A-1.11
PRE- FIN. EXTRUDED ALUM. FLAT SOFFIT DECK SNAP
CAP CONNECTOR W/ SCREWS @ 24" O.C. FOUNDATION, SEE STRUCTURAL
A4 13 A4 13

CAST IRON BOOT


12MM TRANSLUCENT 3" X 6" WIDE FLAT SOFFIT EXTRUDED ALUM.
POLYCARBONATE PANELS, INTERLOCKING DECKING
COLOR 3
TIE INTO STORM DRAIN

9' - 2 1/2"
5PT X 1 1/4" DECKING SCREW ( 3 PER
LOWER DECK MEMBER) FIRST FLOOR
0' - 0"

5"
H H

www.grimmandparker.com
HSS TUBE PURLIN, SEE STRUCTURAL
12MM TRANSLUCENT

1' - 8"
POLYCARBONATE PANELS,

11720 Beltsville Drive

Calverton, MD 20705
1' - 3"
COLOR 1, TYP. K9
STEEL ANGLE, SEE STRUCTURAL

Tel: 301.595.1000
A-1.11
A5 A5

DS FROM CANOPY

Suite 600
GUTTER

7 1/2"
STEEL COLUMNS WITH HIGH
PERFORMANCE EXTERIOR 7 1/2" 1' - 9 1/2"
1-1/2" TRANSLUCENT PANEL 4" PRE-FIN METAL CANOPY
ASSEMBLY ASSEMBLY COATING, TYPICAL AT CANOPY
G G
HSS TUBE BEAM, SEE STRUCTURAL
10' - 3 3/4" 14' - 5" 2' - 5"
10' - 9 7/8" 15' - 2 7/8"
14' - 9"

MAIN ENTRANCE CANOPY ROOF PLAN MAIN ENTRANCE CANOPY REFLECTED CEILING PLAN CANOPY - METAL DECK TO STRUCTURE SECTION MAIN ENTRANCE CANOPY SECTION @ DOWNSPOUT
F18 1/4" = 1'-0" F13 1/4" = 1'-0" F9 3" = 1'-0" F4 3/4" = 1'-0"

F H F

G.9

14' - 5"
G.2

10' - 3 3/4"
F
GP# 21553
PRE-FIN. EXTRUDED ALUM. FASCIA
SUPPORT BRACKET 1-1/2" TRANSLUCENT PANEL
G.9 G.2 ASSEMBLY
PRE-FIN. EXTRUDED ALUM. 6" FASCIA, BEYOND, 14' - 9"
DECKING IS EXPOSED TO ALLOW FOR DRAINAGE AT
7 1/2" K9 12 MM TRANSLUCENT PANEL
GUTTER END
2" 2"
7 1/2" 1' - 1 3/8" PRE-FIN. ALUM. CURTAINWALL 3" X 6" WIDE FLAT SOFFIT EXTRUDED ALUM. A-1.11 F9
A-1.11
E 13' - 7 1/2" FACE COVER INTERLOCKING DECKING A15
A-1.11
E
T.O. MULLION 1'-0"
1'-0" 12' - 4" T.O.S.
PRE-MANUFACTURED ALUM. BATTEN CLOSURE CAP 1"
CANOPY AND FLASHING 1"
METAL PANEL CLIP W/ (2) S.S. POP RIVETS 12' - 8" T.O.S. EQ
FOAM BAFFLE SET IN SEALANT
AND GLAZING EQ EQ
PANEL BATTEN @ 23 11/16" O.C. EQ
METAL PANEL CLIP W/ (2) S.S. POP RIVETS EQ EQ
A11
HEAT SEAL ENDS OF 12MM PANEL BATTEN @ 23 11/16" O.C. A18
A-1.11
TRANSLUCENT POLYCARBONATE A-1.11
3" 3" PANELS BATTEN CLOSURE 11' - 5 5/8" T.O.S.

CITY OF BALTIMORE, MARYLAND


3/8" D WEEP HOLES @ 12" O.C. HEAT SEAL ENDS OF 12MM HSS TUBE BEAMS, SEE
POLYCARBONATE PANELS STRUCTURAL
PRE-FIN. "J" CHANNEL
FORMED ALUM. HEAD FLASHING W/ 6"
D LAP JOINTS SET IN SEALANT AND POP
4" PRE-FIN METAL CANOPY
ASSEMBLY HSS TUBE PURLINS, SEE D
ALUMINUM GUTTER SLOPE TOWARDS

HOLABIRD ACADEMY PK-8


RIVETED AS REQ'D STRUCTURAL
DOWNSPOUT @ 1/8" PER FOOT,

ENTRY CANOPY DETAILS


EXTERIOR LIGHT FIXTURE
PROVIDE METAL STRAPS 3' 0.C. MAX. MOUNTED TO STEEL SUPPORT
FOR GUTTER SUPPORT PRE-FIN. "J" CHANNEL
EXTERIOR LINEAR LIGHT
B.O. BEAM 10' AFF FIXTURE MOUNTED TO
HSS TUBE PURLIN, SEE STRUCTURAL STEEL SUPPORT

HSS TUBE BEAM, SEE STRUCTURAL


HSS TUBE BEAMS, SEE STRUCTURAL HSS TUBE COLUMN,
SEE STRUCTURAL

HSS TUBE COLUMN, SEE STRUCTURAL HSS TUBE COLUMN, SEE STRUCTURAL

C METAL WINDOW PANEL 1 C


PRE-FIN. ALUM. CURTAIN WALL
W/ 1" INSULATED GLAZING

DATE DESCRIPTION

FIRST FLOOR
0' - 0"

1' - 0"
B B

MAIN ENTRANCE CANOPY FLASHING DETAIL MAIN ENTRANCE CANOPY - GUTTER DETAIL POLYCARBONATE CANOPY END DETAIL
A18 1 1/2" = 1'-0" A15 3" = 1'-0" A11 3" = 1'-0"

A-1.11
MAIN ENTRANCE CANOPY SECTION 03/13/2017
A8 1/2" = 1'-0" BID SET
A © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

M M

Scale: 1 inch = 16 feet


OVERALL NORTH ELEVATION
L
L18 1/16" = 1'-0" 0 8' 16' 32' K18
F12 48' 64' L
A-4.1
EXA J10 A B C D EXB D.7 E F G G.2 G.7 G.9 H J J.1 K K.2 K.3 L L.6 M M.1 M.5 N P Q Q.2 R S EXC T EXD
A-4.2
RAILING SYSTEM BEYOND
BRICK SOLDIER COURSE, COLOR #4 PRE-FIN METAL GRAVEL STOP
PRE-FIN METAL COPING, TYP. PRE-FIN METAL PANEL TYPE 2, COLOR #1
F1 F12
PRE-FIN METAL PANEL TYPE 2 PRE-FIN METAL PANEL TYPE 2, COLOR #1, TYP
COLOR #2, TYP A-4.2a A-4.2a
PRE- FIN METAL PANEL TYPE 3, COLOR #2, TYP BRICK COLOR #2. PRE-FINISHED ALUMINUM CURTAINWALL SYSTEM, TYP.
PRE-FIN METAL PANEL TYPE 2, COLOR #2, TYP BRICK SOLDIER COURSE, COLOR #1
BRICK COLOR #2 BRICK SOLDIER COURSE, COLOR #4, TYP. 10" HIGH CAST ALUM LETTERS TYP. FOR SCHOOL NAME, AND
PRE- FIN METAL PANEL TYPE 1, COLOR #1, TYP PRE-FIN METAL COPING, TYP.
12' - 7 3/8" 20' - 0" 20' - 0" 20' - 0" 11' - 0" 8" HIGH CAST ALUM LETTERS TYP. FOR STREET ADDRESS SILL COLOR #1
BRICK COLOR #1, TYP. BRICK COLOR #1, TYP
T.O. ICF 2 STORY C.J.
35' - 0"
K T.O. BRICK C.J. C.J. C.J. C.J. C.J.
K
32' - 0" EQ EQ - M.P. LENGTH

2' - 0"
3' - 2 1/4"
JB CLASSROOMS
29' - 4"
4' - 0"

SF17 SF17 SF17

BRICK COLOR #1
SF1 SF1 SF1
SF2 SF2

SECOND FLOOR 12' - 0" @ M.P. CW1B BRICK SOLDIER COURSE, COLOR #4, TYP.
J 14' - 8" 3' - 4" 3' - 4" 2' - 8" 2' - 8" J

25' - 4"
EQ EQ 3' - 4" BRICK COLOR #4 (SMOOTH)
STACK BOND, TYP.

SF6 SF6 SF6 SF6 SF6 SF6 SF6 SF6 SF6 SF6
EQ EQ SF1 SF1
SF2 SF7 SF8 EQ EQ

FIRST FLOOR
0' - 0"

BRICK COLOR #3 TYP


C.J. C.J. 14' - 0" C.J. 20' - 0" C.J. 25' - 4" C.J. 24' - 8" C.J. C.J.
C.J. SILL COLOR #1 C.J. C.J. C.J. C.J. C.J. BRICK COLOR #2 2' - 0"
OPERABLE VENT, TYP. SILL COLOR #2 BRICK COLOR #4 STACK BOND, TYP. 2' - 0"
BRICK COLOR #4 (SMOOTH) FIRE DEPARTMENT CONNECTION SILL COLOR #2, TYP
STACK BOND, TYP PRE-FINISHED ALUMINUM STOREFRONT BRICK COLOR #4 (SMOOTH) STACK BOND, ENTRY CANOPY BRICK COLOR #4 (SMOOTH) PRE-FINISHED ALUMINUM STOREFRONT
BRICK COLOR #2 TYP
H H

www.grimmandparker.com
TYP. WALL MOUNTED LIGHT FIXTURE, STACK BOND, TYP. SYSTEM, TYP.
SILL COLOR #3 SYSTEM, TYP. PRE- FIN METAL PANEL TYPE 1, B.O. FIXTURE @ 10' TYP. BRICK COLOR #2
BRICK COLOR #2 BRICK COLOR #2 TYP. COLOR 1

11720 Beltsville Drive


BRICK COLOR #1, TYP.

Calverton, MD 20705
ANTI-GRAFFITI COATING UP TO PRE-FIN METAL PANEL TYPE 1, COLOR #1, TYP

Tel: 301.595.1000
10 'AFF, TYP. @ MASONRY
NORTH ELEVATION
H18 1/8" = 1'-0"

Suite 600
F1 F12
A-4.2a A-4.2a
EXA J10 A B C D EXB D.7 E F G G.2 G.7 G.9 H
A-4.2
PRE-FIN ALUM COPING, TYP. WALL MOUNTED LIGHT FIXTURE,
B.O. FIXTURE @ 10', TYP.
PRE-FIN METAL PANEL TYPE 2, TYP., COLOR 2 PRE-FINISHED ALUMINUM
G STOREFRONT SYSTEM, TYP. 2HR FIRE WALL EXTENTS
1/2" SEPARATION JOINT
G
BRICK COLOR #4 (SMOOTH), TYP.
PRE-FIN METAL PANEL TYPE 1, COLOR 1 TYP
2HR RATED CURTAIN WALL SYSTEM
BRICK SOLDIER COURSE, COLOR #4,
12' - 7 3/8" 20' - 0" 20' - 0" 20' - 0" 11' - 0" 12' - 3" 20' - 0" 12' - 5"
TYP.
T.O. ICF 2 STORY
35' - 0"

JB CLASSROOMS E D.7 EXB D


29' - 4"
3' - 0 1/4"
GUARDRAIL SYSTEM

5' - 8"
PRE-FIN ALUM COPING
F F

14' - 8"
BRICK SOLDIER COURSE, COLOR #4
SF1 SF1 SF1 CW5 CW7
SF2 SF2 SF2 CW6

35' - 0"
BRICK COLOR #2, TYP

SECOND FLOOR EQ EQ SECOND FLOOR GP# 21553


14' - 8" C.J. C.J. 14' - 8"
PRE-FIN ALUM STOREFRONT SYSTEM, TYP
SILL COLOR #1, TYP

GREEN ROOF AND PAVER SYSTEMS

14' - 8"
2' - 0"
CW5 GUARDRAIL SF6
SF1 SF1 SF1
SF2 3' - 4" 3' - 4" SF2 SF2
E E
FIRST FLOOR
0' - 0" C.J. C.J. SILL COLOR #1, TYP C.J. 6' - 8" C.J. C.J. 6' - 8" C.J. C.J. C.J. 8" C.J.
FIRST FLOOR
0' - 0" ELEVATION NOTES (NOTES APPLY TO ALL ELEVATION SHEETS)
BRICK COLOR #3

ANTI-GRAFFITI COATING UP TO 10 'AFF,


SILL COLOR #3 TYP @ WATERTABLE SF FRAME COLOR 2, TYP. OPERABLE VENT, TYP. TYP. @ MASONRY GENERAL NOTE APPLICABLE TO ALL DRAWINGS - ITEMS AND CONDITIONS DETAILED, NOTED OR OTHERWISE IDENTIFIED
ON ONE OF THE SECTIONS OR DETAILS ARE APPLICABLE AND BINDING TO ALL OTHER SECTIONS AND DETAILS FOR
BRICK PRE-FIN METAL PANEL TYPE 2, COLOR 2, TYP SILL COLOR #1, TYP BRICK COLOR #4 (SMOOTH) IDENTICAL OR SIMILAR CONDITIONS.
ANTI-GRAFFITI COATING UP TO 10 'AFF, TYP. @ MASONRY OPERABLE VENT, TYP
COLOR #2 1. REFER TO STRUCTURAL DRAWINGS FOR FOOTING ELEVATIONS.
SILL COLOR #2 2. MASONRY BOND PATTERN SHALL BE RUNNING BOND UNLESS OTHERWISE INDICATED. REFER TO LARGE SCALE
PARTIAL NORTH ELEVATION PARTIAL SOUTH ELEVATION @ ADMIN ELEVATION DETAILS FOR MASONRY PATTERNS, BONDING, SPECIAL SHAPES AND MORTAR COLOR PATTERNS.

CITY OF BALTIMORE, MARYLAND


D18 1/8" = 1'-0" D9 1/8" = 1'-0"
3. PROVIDE SEALANT AT ALL INTERSECTIONS OF DISSIMILAR MATERIALS IN ACCORDANCE WITH THE
SPECIFICATIONS. ALL EXTERIOR SEALANTS TO BE A CUSTOM COLOR SELECTED BY THE ARCHITECT. MORE
THAN ONE SEALANT COLOR MAY BE SELECTED FOR USE ALONG THE HEIGHT OF THE SAME JOINT TO MATCH
ADJOINING MASONRY OR MORTAR.
D 4. ALL EXTERIOR EXPOSED STEEL TO BE FIELD PAINTED UNLESS NOTED OTHERWISE. COLOR TO BE SELECTED BY D
THE ARCHITECT.

HOLABIRD ACADEMY PK-8


5. REFER TO SHEET A-5.10 FOR TYPICAL EXTERIOR CONTROL JOINT DETAILS AND NOTES.
6. REFER TO DRAWING A-5.10 FOR TYPICAL MASONRY DETAILS AND SPECIAL MASONRY SHAPES.
7. REFER TO TYPICAL ROOF FLASHING DETAILS ON SHEET A-5.10 FOR FLASHING REQUIREMENTS.

KEY PLAN

ELEVATIONS
G18
A-2.3H
C C

AREA B AREA C G18


D18 A-2.4H
A-2.2H
DATE DESCRIPTION
D9 D10
D18
D18 A-2.1H A-2.3H
A-2.3H
A-2.1H

B AREA A
B
G18
D18
A-2.2H
A-2.4H

Scale: 1 inch = 8 feet

H18
A-2.1H
0 4' 8' 16' 24' 32' A-2.1H 03/13/2017
BID SET
A © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

. D18 / A-2.2G G18 / A-2.2G .

M M

OVERALL EAST ELEVATION


L18 1/16" = 1'-0"
L L
A18
EX3 6 7 8 8.2 9 9.1 10 A-4.1 11 11.4 12 A1 A2 A3 13
A4 A5 EX4
MATCHLINE

A13 A18
A-4.2a A-4.2
D18 / A-2.2H

5.8 PRE-FIN METAL COPING, TYP

E.J. @ INSIDE CORNER BRICK COLOR #1, TYP


PRE-FIN METAL PANEL TYPE 2, COLOR 2 PRE-FIN METAL PANEL TYPE 2, COLOR 3 PRE-FIN METAL COPING, TYP
PRE-FIN METAL PANEL TYPE 2, COLOR 1
T.O. ICF 2 STORY PRE-FIN METAL PANEL TYPE 2, COLOR 2, TYP
18' - 0" - M.P. LENGTH 18' - 0" 18' - 0" 18' - 0" 18' - 0" 18' - 0"
35' - 0" 20' - 0" @ M.P., TYP. 20' - 0" 20' - 0" 20' - 0" VERTICAL 14" D X 12' L - POLYCARBONATE
T.O. BRICK SUNSHADE DEVICE @ EVERY VERTICAL MULLION
K 32' - 0" K
C.J. C.J. C.J. C.J. PRE-FIN METAL PANEL TYPE 2,
JB CLASSROOMS
COLOR 3
29' - 4"
PRE-FINISHED ALUMINUM PRE-FIN METAL COPING, TYP
18' - 0" 25' - 4" 25' - 4" CURTAINWALL SYSTEM, TYP. ENTRY CANOPY

11' - 4"
L1 BRICK COLOR #2, TYP
WALL MOUNTED LIGHT FIXTURE
OUTDOOR LEARNING CLASSROOM
SCIENCE SOLAR LAB BRICK SOLDIER COURSE, COLOR #4
CW1A
ANTI-GRAFFITI COATING, UP TO 10' AFF TYP.

32' - 0"
SECOND FLOOR
14' - 8" EQ - M.P. LENGTH EQ EQ EQ EQ EQ 16' - 0" M.P. EQ EQ
J EQ EQ
J
SF12A SF12C SF12D

SF12B SF12B SF12D SF6 SF6 SF6 SF6 SF6 SF6 SF6 SF6 SF6 SF6 SF6

10' - 0"
SF13
4' - 0" 8"

7' - 6"
1' - 4"

2' - 0"
FIRST FLOOR
0' - 0" 2' - 0" C.J. 18' - 0" C.J. 23' - 4" C.J. 23' - 4" C.J. 23' - 4" C.J. 8' - 0" C.J. C.J. 2' - 0"
C.J.
PRE-FIN METAL PANEL SOFFIT BRICK COLOR #4 (SMOOTH), PRE- FIN METAL PANEL TYPE 1, TYP, COLOR 1
RAILING SYSTEM OPERABLE VENT, BRICK COLOR #4 (SMOOTH), STACK BOND TYP.
TYPE 4, COLOR 1 STACK BOND, TYP.
PRE-FIN METAL PANEL TYPE 2, TYP, BRICK COLOR #2, TYP. SF COLOR 2, TYP. PRE-FINISHED ALUMINUM
STOREFRONT SYSTEM, TYP. SILL COLOR #2(TBD), TYP
H H

www.grimmandparker.com
PRE-FINISHED ALUMINUM COLOR 1
BRICK COLOR #2, TYP SILL COLOR #2(TBD), TYP
PARTIAL EAST ELEVATION CURTAINWALL SYSTEM, TYP.
BRICK COLOR #2, TYP
BRICK COLOR #4, (SMOOTH)
STACK BOND, TYP. 31' - 1 3/8" 24' - 8"
G18

11720 Beltsville Drive

Calverton, MD 20705
1/8" = 1'-0"

Tel: 301.595.1000
Suite 600
EX1 EX2 1 2 3 4 5 5.1 5.8EX3 6

MATCHLINE
PRE-FIN METAL COPING, TYP

G18 / A-2.2H
PRE-FIN METAL PANEL TYPE 3, TYP.,
COLOR 2

G PRE-FIN METAL PANEL TYPE 2,


TYP., COLOR 2
E.J. @ INSIDE CORNER G
SF FRAME COLOR 3 PRE-FIN METAL PANEL TYPE 2, COLOR 2
METAL PANEL INFILL, ACCENT PRE-FINISHED ALUMINUM
SF FRAME COLOR 2 COLOR 2 STOREFRONT SYSTEM, TYP.
T.O. ICF 2 STORY
35' - 0"
3' - 0"

EQ @ M.P. EQ @ M.P.
T.O. BRICK
32' - 0" 20' - 0" @ M.P.

JB CLASSROOMS
29' - 4"
4' - 0"

SF4
17' - 4"

THROUGH-WALL
2' - 0"

SCUPPER AND
F CONDUCTOR BOX F
6' - 8"

4' - 0"

4' - 0"
SF4 SF10
35' - 0"

3' - 4"

GP# 21553
4' - 0"

SECOND FLOOR SF4 7' - 10" 12' - 2"


14' - 8" 9' - 10"
7' - 4"

BASE BID
DOWNSPOUT TO BOOT AT GRADE
14' - 8"

13' - 4"

4' - 0"
10' - 0"

SF4 SF10 2' - 0" Sim


A18
A-5.6
E E
3' - 4"

2' - 0"

FIRST FLOOR
0' - 0" C.J. C.J.
ELEVATION NOTES
BRICK COLOR #3

4' - 0" C.J. 24' - 8" C.J. 4' - 0" 4' - 0" EQ EQ 4' - 0" ADD ALTERNATE (NOTES APPLY TO ALL ELEVATION SHEETS)
2' - 0" METAL PANEL INFILL, ACCENT RAIN CISTERN SYSTEM ON
ANTI-GRAFFITI COATING UP TO 10 'AFF BRICK COLOR #3, TYP. COLOR 1 O.F.D. BRICK COLOR #3, TYP. REINFORCED SLAB FOR
WATERING GARDEN PLANTS GENERAL NOTE APPLICABLE TO ALL DRAWINGS - ITEMS AND CONDITIONS DETAILED, NOTED OR OTHERWISE IDENTIFIED
BRICK COLOR #1, TYP. ON ONE OF THE SECTIONS OR DETAILS ARE APPLICABLE AND BINDING TO ALL OTHER SECTIONS AND DETAILS FOR
BRICK COLOR #2, TYP. SILL COLOR #2, TYP FROM HOSE CONNECTION
BRICK COLOR #2 BRICK COLOR #1 IDENTICAL OR SIMILAR CONDITIONS.
BRICK COLOR #2
1. REFER TO STRUCTURAL DRAWINGS FOR FOOTING ELEVATIONS.
2. MASONRY BOND PATTERN SHALL BE RUNNING BOND UNLESS OTHERWISE INDICATED. REFER TO LARGE SCALE
ELEVATION DETAILS FOR MASONRY PATTERNS, BONDING, SPECIAL SHAPES AND MORTAR COLOR PATTERNS.

CITY OF BALTIMORE, MARYLAND


3. PROVIDE SEALANT AT ALL INTERSECTIONS OF DISSIMILAR MATERIALS IN ACCORDANCE WITH THE
PARTIAL EAST ELEVATION SPECIFICATIONS. ALL EXTERIOR SEALANTS TO BE A CUSTOM COLOR SELECTED BY THE ARCHITECT. MORE

D18 1/8" = 1'-0"


THAN ONE SEALANT COLOR MAY BE SELECTED FOR USE ALONG THE HEIGHT OF THE SAME JOINT TO MATCH
ADJOINING MASONRY OR MORTAR.
D 4. ALL EXTERIOR EXPOSED STEEL TO BE FIELD PAINTED UNLESS NOTED OTHERWISE. COLOR TO BE SELECTED BY D
THE ARCHITECT.

HOLABIRD ACADEMY PK-8


5. REFER TO SHEET A-5.10 FOR TYPICAL EXTERIOR CONTROL JOINT DETAILS AND NOTES.
6. REFER TO DRAWING A-5.10 FOR TYPICAL MASONRY DETAILS AND SPECIAL MASONRY SHAPES.
7. REFER TO TYPICAL ROOF FLASHING DETAILS ON SHEET A-5.10 FOR FLASHING REQUIREMENTS.

KEY PLAN

ELEVATIONS
G18
A-2.3H
C C

AREA B AREA C G18


D18 A-2.4H
A-2.2H
DATE DESCRIPTION
D9 D10
D18
D18 A-2.1H A-2.3H
A-2.3H
A-2.1H

B AREA A
B
G18
D18
A-2.2H
A-2.4H

Scale: 1 inch = 8 feet


H18
A-2.2H
A-2.1H 03/13/2017
0 4' 8' 16' 24' 32' BID SET
A © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

M M

OVERALL SOUTH ELEVATION


L L18 1/16" = 1'-0" L
EXD T EXC S R Q.2 Q P N M.5 M.1 M L.6 L K18
F12 K.3 K.2 K J.1 J G.9 F12 G.7 G.2 G F F1 E D.7 EXB D C B A EXA
A-4.1 A-4.2a A-4.2a J10
A-4.2
PRE-FIN ALUM SUNSHADES, TYP PRE-FIN METAL PANEL TYPE 3, TYP, COLOR 1
BRICK COLOR #2, TYP. PRE-FIN ALUM COPING, TYP. PRE-FIN METAL PANEL TYPE 2, TYP, COLOR 2
PRE- FIN METAL PANEL TYPE 3, TYP., COLOR 2 PRE-FINISHED ALUMINUM
H PRE-FIN ALUM COPING, TYP.
PRE-FIN METAL PANEL TYPE 3, TYP., COLOR 1 BRICK COLOR #2, TYP. PRE- FIN ALUM HORIZONTAL SUN SHADE, TYP. PRE- FIN METAL PANEL TYPE 2, TYP., COLOR 2 PRE- FIN METAL PANEL TYPE 3, TYP., COLOR 2 CURTAINWALL SYSTEM, TYP.
BRICK COLOR #2, TYP.
PRE-FINISHED ALUMINUM CURTAINWALL BRICK SOLDIER COURSE, COLOR #2 PRE-FINISHED ALUMINUM BRICK SOLDIER COURSE, COLOR #2
BRICK COLOR #4 (SMOOTH) BRICK COLOR #1, TYP.
SYSTEM, TYP. CURTAINWALL SYSTEM, TYP.
PRE-FIN METAL PANEL TYPE 1, COLOR 1 TYP. PRE-FIN METAL PANEL TYPE 1, COLOR 1, TYP. SILL COLOR #1
STEEL LENTIL CONTINUES, @ SOILDER 4' - 0" 20' - 0" 16' - 0" 20' - 0" 5' - 0" 10' - 8" 5' - 0" 20' - 0" 16' - 0" 20' - 0" 4' - 0"
BRICK COLOR #1, TYP.
COURSE, TYP., SEE STRUCTURAL
T.O. ICF 2 STORY
C.J. C.J. C.J. C.J. C.J.
35' - 0"
K T.O. BRICK K

5' - 8"
32' - 0"
JB CLASSROOMS
29' - 4"

SF5

14' - 8"
BRICK COLOR #2
SF1 SF1 SF1 SF1 SF1 SF1 SF1 SF1
SF2 SF2 SF2 SF2 SF2 SF2 SF2 SF2

35' - 0"
SECOND FLOOR CW3 CW2
J 14' - 8" BRICK COLOR #1 BRICK COLOR #1
PROTECTIVE COVER/CANOPY
BRICK COLOR #1
EQ EQ
J
CW2 EQ EQ EQ EQ
OPP
EQ EQ
SF5

14' - 8"
10' - 0"

EQ EQ

10' - 2"
10' - 0"

SF1 SF1 SF1 SF1 SF1


SF9 SF2 SF2 SF9 SF9 SF2 SF2 SF2 SF2 SF2 SF2

7' - 6"
EQ EQ

3' - 0"
2' - 0"

FIRST FLOOR
0' - 0" C.J. C.J. C.J. C.J. C.J. C.J. C.J. C.J. C.J. C.J. C.J. C.J. BRICK SOLDIER COURSE, COLOR #4 C.J. WALL MOUNTED LIGHT FIXTURE,
PRE-FINISHED ALUMINUM STOREFRONT

BRICK COLOR #3
OPERABLE VENT, TYP. SILL COLOR #3 SILL COLOR #3 BRICK COLOR #4 (GLAZED) OPERABLE VENT, TYP. B.O. FIXTURE @ 10' TYP.
SILL COLOR #3 SYSTEM, TYP.
BRICK COLOR #1, TYP. O.F.D. SILL COLOR #1 PRE-FINISHED ALUMINUM STOREFRONT SILL COLOR #3 BRICK COLOR #1, TYP. O.F.D.
SILL COLOR #1 SILL COLOR #3
H H

www.grimmandparker.com
ANTI-GRAFFITI COATING UP TO BRICK COLOR #3, TYP. SYSTEM, TYP. SILL COLOR #1
BRICK COLOR #1, TYP. BRICK COLOR #3, TYP. SILL COLOR #1
10 'AFF, TYP. @ MASONRY BRICK COLOR #2 BRICK COLOR #1 BRICK COLOR #2

11720 Beltsville Drive

Calverton, MD 20705
Tel: 301.595.1000
Suite 600
SOUTH ELEVATION
G18 1/8" = 1'-0"

L.6 M M.1 M.5 N P Q Q.2 R S T EXD

G T S R Q.2 Q P N M.5 M.1 M G


PRE-FIN METAL COPING, TYP
EXC EXC
PRE-FIN METAL PANEL TYPE 2, COLOR 2, TYP
2HR RATED CURTAINWALL SYSTEM BRICK SOLDIER COURSE, COLOR # 1 PRE-FIN METAL COPING, TYP
9' - 6 1/2" 5' - 11" 20' - 0" 20' - 0" 20' - 0" PRE-FIN METAL PANEL TYPE 1, COLOR 1, TYP. BRICK COLOR #1, TYP
TYP. PRE-FIN METAL PANEL TYPE 3, COLOR 2, TYP.
T.O. ICF 2 STORY SOLDIER COURSE, BRICK COLOR 1, TYP
35' - 0"
3' - 0"

T.O. BRICK T.O. BRICK


32' - 0" 32' - 0"

F F
17' - 4"

CW5

SF2
SF1
SF2
SF1
SF2
SF1
GP# 21553
35' - 0"

32' - 0"

32' - 0"
SECOND FLOOR
14' - 8" EQ EQ
EQ EQ EQ EQ EQ EQ
BRICK COLOR #3
14' - 8"

BRICK COLOR #3
E CW5
E

10' - 0"

10' - 0"
SF9 SF9
SF9
SF2 SF2 6' - 8" SF2
8' - 4" ELEVATION NOTES (NOTES APPLY TO ALL ELEVATION SHEETS)

FIRST FLOOR FIRST FLOOR GENERAL NOTE APPLICABLE TO ALL DRAWINGS - ITEMS AND CONDITIONS DETAILED, NOTED OR OTHERWISE IDENTIFIED
0' - 0" 0' - 0" C.J. C.J. ON ONE OF THE SECTIONS OR DETAILS ARE APPLICABLE AND BINDING TO ALL OTHER SECTIONS AND DETAILS FOR
C.J. OPERABLE VENT, TYP. C.J. 6' - 8" TYP. C.J. WALL MOUNTED LIGHT FIXTURE, C.J. O.F.D. C.J. C.J. C.J. 4' - 8" 20' - 0" 2' - 0" 25' - 0" C.J. 25' - 0" C.J. IDENTICAL OR SIMILAR CONDITIONS.
O.F.D.
B.O, FIXTURE @ 10'-0 AFF, TYP. BRICK COLOR #4 (GLAZED), TYP SILL COLOR #3 ANTI-GRAFFITI COATING UP
TO 10' TYP., AT MASONRY HM DOOR & FRAME SEE SCHEDULE BRICK COLOR #3, TYP BRICK COLOR #2, TYP 1. REFER TO STRUCTURAL DRAWINGS FOR FOOTING ELEVATIONS.
PRE-FINISHED ALUMINUM STOREFRONT BRICK COLOR #3, TYP
1/2" SEPARATION JOINT BRICK COLOR #1 SYSTEM, TYP. BRICK COLOR #2 WALL MOUNTED LIGHT FIXTURE, B.O, FIXTURE @ 10'-0 AFF, TYP. BRICK COLOR #1, TYP ANTI-GRAFFITI COATING UP TO 10 'AFF, 2. MASONRY BOND PATTERN SHALL BE RUNNING BOND UNLESS OTHERWISE INDICATED. REFER TO LARGE SCALE
SILL COLOR #1 ELEVATION DETAILS FOR MASONRY PATTERNS, BONDING, SPECIAL SHAPES AND MORTAR COLOR PATTERNS.
TYP. @ MASONRY

CITY OF BALTIMORE, MARYLAND


3. PROVIDE SEALANT AT ALL INTERSECTIONS OF DISSIMILAR MATERIALS IN ACCORDANCE WITH THE
SPECIFICATIONS. ALL EXTERIOR SEALANTS TO BE A CUSTOM COLOR SELECTED BY THE ARCHITECT. MORE
THAN ONE SEALANT COLOR MAY BE SELECTED FOR USE ALONG THE HEIGHT OF THE SAME JOINT TO MATCH
ADJOINING MASONRY OR MORTAR.
D 4. ALL EXTERIOR EXPOSED STEEL TO BE FIELD PAINTED UNLESS NOTED OTHERWISE. COLOR TO BE SELECTED BY D
PARTIAL NORTH ELEVATION PARTIAL SOUTH ELEVATION THE ARCHITECT.

HOLABIRD ACADEMY PK-8


D18 1/8" = 1'-0" D10 1/8" = 1'-0"
5.
6.
REFER TO SHEET A-5.10 FOR TYPICAL EXTERIOR CONTROL JOINT DETAILS AND NOTES.
REFER TO DRAWING A-5.10 FOR TYPICAL MASONRY DETAILS AND SPECIAL MASONRY SHAPES.
7. REFER TO TYPICAL ROOF FLASHING DETAILS ON SHEET A-5.10 FOR FLASHING REQUIREMENTS.

KEY PLAN

ELEVATIONS
G18
A-2.3H
C C

AREA B AREA C G18


D18 A-2.4H
A-2.2H
DATE DESCRIPTION
D9 D10
D18
D18 A-2.1H A-2.3H
A-2.3H
A-2.1H

B AREA A
B
G18
D18
A-2.2H
A-2.4H

H18
A-2.3H
A-2.1H 03/13/2017
BID SET
A N © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

E17/A-2.2H
G18 / A-2.4G
B12/A-2.2H
D18 / A-2.4G

M M

OVERALL WEST ELEVATION


L L18 1/16" = 1'-0" A18 L
A-4.1

EX4 A5 A4
13 A3 A2 A1 12 11.4 11 10 9.1 9 8.2 8 7 6

MATCHLINE
LOUVER - SEE MECH DWGS

A18 A13 PRE-FIN METAL COPING

D18 / A-2.4H
A-4.2 A-4.2a
SOLDIER COURSE, BRICK COLOR 1, TYP PRE-FIN METAL PANEL TYPE 2,
COLOR 2, TYP

21' - 4" 20' - 0" 19' - 4" 16' - 0" 3' - 4" 23' - 4" 24' - 8" 25' - 1 5/8" BRICK COLOR #1, TYP
T.O. ICF 2 STORY
35' - 0"
K K

3' - 0"
T.O. BRICK T.O. BRICK
32' - 0" 32' - 0"

12' - 8"
L1
PRE-FIN METAL COPING
WALL MOUNTED LIGHT FIXTURE, MECH. LEVEL
B.O. FIXTURE @ 10' TYP. CENTRAL
19' - 4"

35' - 0"
14' - 8"

14' - 8"
CW4
J EQ EQ EQ EQ EQ EQ 4' - 0" EQ EQ J
5' - 0"

19' - 4"
SF16 SF16

5' - 4"
SF3
2' - 8"
10' - 0"

1' - 6"

1' - 4" 3' - 4"


FIRST FLOOR FIRST FLOOR
0' - 0" C.J. C.J. C.J. C.J. C.J. C.J. 2' - 0" E.J. AT INSIDE CORNER 0' - 0"
C.J. 4' - 0" 6' - 4" 13' - 0" 20' - 0" 12' - 11" O.F.D C.J. C.J. C.J.
2' - 0" 24' - 8" 4' - 0" O.F.D BRICK COLOR #3, TYP
C.J. C.J. BRICK COLOR #2 ACCENT BAND
H H

www.grimmandparker.com
ANTI-GRAFFITI COATING UP TO 10 'AFF BRICK SOLDIER COURSE, COLOR #1 SILL COLOR #1 (TBD), TYP
PRE-FIN ALUM CURTAINWALL SYSTEM, TYP BRICK COLOR #3, TYP
BRICK COLOR #2 BRICK COLOR #1 PRE-FIN ALUM STOREFRONT SYSTEM, TYP

11720 Beltsville Drive

Calverton, MD 20705
SILL COLOR #3, TYP

Tel: 301.595.1000
HM DOOR & FRAME SEE SCHEDULE, TYP SOLDIER COURSE, BRICK COLOR 1, TYP

PARTIAL WEST ELEVATION


G18

Suite 600
1/8" = 1'-0"

6 EX35.8 5.1 5 4 3 2 1 EX2 EX1


MATCHLINE

G PRE-FIN METAL COPING, TYP


G
G18 / A-2.4H

PRE-FIN METAL PANEL TYPE 2, COLOR 2, TYP


SF FRAME COLOR 3
PRE-FIN METAL PANEL TYPE 3, COLOR 2, TYP
SF FRAME COLOR 2
EQ @ M.P. EQ @ M.P. PRE-FIN ALUM STOREFRONT SYSTEM, TYP
SILL COLOR #2, TYP
T.O. ICF 2 STORY
35' - 0"
3' - 0"

3' - 0"
T.O. BRICK
20' - 0" @ M.P. 32' - 0"

JB CLASSROOMS
F 29' - 4" F
4' - 0"

SF4
17' - 4"
2' - 0"

SF10
GP# 21553
4' - 0"

OPP SF4
35' - 0"

35' - 0"
2' - 0"
4' - 0"

SF4 SECOND FLOOR


12' - 0" 8' - 0"
14' - 8"
2' - 0"2' - 0"
7' - 4"

SF16
14' - 8"
BRICK COLOR #3
BRICK COLOR #3

13' - 4"

E E
4' - 0"

SF10
10' - 0"

SF4
2' - 0"
OPP
ELEVATION NOTES (NOTES APPLY TO ALL ELEVATION SHEETS)
3' - 4"

FIRST FLOOR
GENERAL NOTE APPLICABLE TO ALL DRAWINGS - ITEMS AND CONDITIONS DETAILED, NOTED OR OTHERWISE IDENTIFIED
C.J. C.J. C.J.
4' - 0" C.J. 24' - 8" C.J. 4' - 0" C.J. 2' - 0" 0' - 0" ON ONE OF THE SECTIONS OR DETAILS ARE APPLICABLE AND BINDING TO ALL OTHER SECTIONS AND DETAILS FOR
4' - 0" EQ EQ BRICK COLOR #3, TYP BRICK COLOR #3, TYP
4' - 0" TYP. IDENTICAL OR SIMILAR CONDITIONS.
O.F.D. BRICK COLOR #2, TYP
BRICK COLOR #1, TYP ANTI-GRAFFITI COATING UP TO 10'AFF 1. REFER TO STRUCTURAL DRAWINGS FOR FOOTING ELEVATIONS.
BRICK COLOR #2 2. MASONRY BOND PATTERN SHALL BE RUNNING BOND UNLESS OTHERWISE INDICATED. REFER TO LARGE SCALE
METAL PANEL INFILL, COLOR 1 ELEVATION DETAILS FOR MASONRY PATTERNS, BONDING, SPECIAL SHAPES AND MORTAR COLOR PATTERNS.

CITY OF BALTIMORE, MARYLAND


METAL PANEL INFILL, COLOR 2 3. PROVIDE SEALANT AT ALL INTERSECTIONS OF DISSIMILAR MATERIALS IN ACCORDANCE WITH THE
SPECIFICATIONS. ALL EXTERIOR SEALANTS TO BE A CUSTOM COLOR SELECTED BY THE ARCHITECT. MORE
PARTIAL WEST ELEVATION THAN ONE SEALANT COLOR MAY BE SELECTED FOR USE ALONG THE HEIGHT OF THE SAME JOINT TO MATCH

D D18 1/8" = 1'-0" 4.


ADJOINING MASONRY OR MORTAR.
ALL EXTERIOR EXPOSED STEEL TO BE FIELD PAINTED UNLESS NOTED OTHERWISE. COLOR TO BE SELECTED BY D
THE ARCHITECT.

HOLABIRD ACADEMY PK-8


5. REFER TO SHEET A-5.10 FOR TYPICAL EXTERIOR CONTROL JOINT DETAILS AND NOTES.
6. REFER TO DRAWING A-5.10 FOR TYPICAL MASONRY DETAILS AND SPECIAL MASONRY SHAPES.
7. REFER TO TYPICAL ROOF FLASHING DETAILS ON SHEET A-5.10 FOR FLASHING REQUIREMENTS.

KEY PLAN

ELEVATIONS
G18
A-2.3H
C C

AREA B AREA C G18


D18 A-2.4H
A-2.2H
DATE DESCRIPTION
D9 D10
D18
D18 A-2.1H A-2.3H
A-2.3H
A-2.1H

B AREA A
B
G18
D18
A-2.2H
A-2.4H

H18
A-2.4H
A-2.1H 03/13/2017
BID SET
A N © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

FINISH SCHEDULE FINISH SCHEDULE


TYPICAL FINISHES
SPACES NOT LISTED ON THE SCHEDULE SHALL HAVE THE TYPICAL FINISHES LISTED BELOW:
COLOR WALLS COLOR WALLS
SCHEM SCHEM FLOORS: BBT
BASE: RST
RM. NO. NAME E FLOOR BASE A B C D CLG. MATL. REMARKS RM. NO. NAME E FLOOR BASE A B C D CLG. MATL. REMARKS WALLS: PTD
0001 GEOTHERMAL PUMP ROOM CONC NONE PTD PTD PTD PTD EXP 2101 MECHANICAL ROOM - CENTRAL CONC NONE PTD PTD PTD PTD EXP CEILING: APC
001A CORRIDOR 2200 FLEX BBT RST PTD PTD PTD PTD APC
GYP. BD. ABOVE H.M. FRAMES AS INDICATED ON SECTIONS. DETAILS TO RECEIVE SAME TOP COATS AS ADJACENT
1000 RECEPTION BBT RST PTD PTD PTD PTD APC/GYP 2201 WOMEN PT CT CT CT CT CT GYP 15 WALLS UNLESS OTHERWISE NOTED.
1001 A.P. OFFICE CPT RST PTD PTD PTD PTD APC 2202 TOILET PT CT CT CT CT CT GYP

M
1002
1003
WORKROOM
CLOSET
BBT
BBT
RST
RST
PTD
PTD
PTD
PTD
PTD
PTD
PTD
PTD
APC
GYP
2203
2203B
MEN
CUSTODIAL
PT CT CT CT CT CT GYP 15
FINISH MATERIALS M
1004 CONFERENCE CPT RST PTD PTD PTD PTD APC3 2204 PLANNING CPT RST PTD PTD PTD PTD APC
1005
1006
SECURE STORAGE
PRINCIPAL
BBT
CPT
RST
RST
PTD
PTD
PTD
PTD
PTD
PTD
PTD
PTD
APC
APC
2204A
2204B
STAFF TOILET
STORAGE
PT
BBT
CT
RST
CT
PTD
CT
PTD
CT
PTD
CT
PTD
GYP
APC
FLOORS BASES
CONC CONCRETE WITH HARDENER CT CERAMIC TILE
1007 FLEX OFFICE CPT RST PTD PTD PTD PTD APC 2205 MECH/UTILITY CONC NONE PTD PTD PTD PTD EXP CONC2 SEALED CONCRETE EPOXY EPOXY BASE
1008 FLEX OFFICE CPT RST PTD PTD PTD PTD APC 2206 SPECIAL EDUCATION 3-5 BBT RST PTD PTD PTD PTD APC 15 CONC3 TROWELED CONCRETE NONE NO BASE
1009 STAFF TOILET PT CT CT CT CT CT GYP 15 2207 ELEVATOR CONTROL CONC NONE PTD PTD PTD PTD EXP CPT CARPET RST RESILIENT BASE
1010 STORAGE BBT RST PTD PTD PTD PTD APC 2208 RESOURCE BBT RST PTD PTD PTD PTD APC EPOXY EPOXY FLOORING VRB VENTED RUBBER BASE
PT PORCELAIN TILE
1011 LAUNDRY BBT RST PTD PTD PTD PTD APC 2209 FLEX BBT RST PTD PTD PTD PTD APC BBT BIOBASED TILE
1012 PERSONAL CARE PT CT CT CT CT CT GYP 4, 15 2210 GRADE 5 BBT RST PTD PTD PTD PTD APC RBR RUBBER TREADS
1100 WAITING BBT RST PTD PTD PTD PTD APC/GYP 2211 GRADE 4 BBT RST PTD PTD PTD PTD APC RM RECESSED MAT - WALK OFF
1101 STUDENT TOILET PT CT CT CT CT CT GYP 15 2212 MECH CONC NONE PTD PTD PTD PTD EXP WD WOOD FLOOR
1102 HEALTH OFFICE BBT RST PTD PTD PTD PTD APC 2213 MECH CONC NONE PTD PTD PTD PTD EXP

L 1102A STORAGE BBT RST PTD PTD PTD PTD APC 2214 GRADE 5 BBT RST PTD PTD PTD PTD APC CEILINGS WALLS L
1103 REST AREA BBT RST PTD PTD PTD PTD APC 2215 GRADE 4 BBT RST PTD PTD PTD PTD APC APC ACOUSTIC PANEL CLG. - 2'X4' - TYPE 1 AWP1 ACOUSTICAL WALL PANEL TYPE 1
1104 EXAM/TREATMENT BBT RST PTD PTD PTD PTD APC 2220 COLLABORATIVE LEARNING BBT RST PTD PTD PTD PTD APC2/APC4/GYP APC2 ACOUSTIC PANEL CLG. - 2'X4' - TYPE 2 AWP2 ACOUSTICAL WALL PANEL TYPE 2
1105 REST AREA BBT RST PTD PTD PTD PTD APC 2300 FLEX BBT RST PTD PTD PTD PTD APC APC3 ACOUSTIC PANEL CLG. - 2'X2' CMU UNPAINTED C.M.U.
APC4 SNAP IN METAL PAN CEILING - 2'X2' CT CERAMIC TILE
1106 EXAM/TREATMENT BBT RST PTD PTD PTD PTD APC 2300E TOILET PT CT CT CT CT CT GYP PTD PAINTED
ADP ACOUSTIC DIFFUSER CLG. PANEL - 2'X2'
1200 WAITING/RECEPTION BBT RST PTD PTD PTD PTD APC/GYP 2301 WOMEN PT CT CT CT CT CT GYP EXP EXPOSED CONSTRUCTION - PAINTED WCV WALL COVERING SYSTEM
1201 CONFERENCE CPT RST PTD PTD PTD PTD APC3 2302 PLANNING CPT RST PTD PTD PTD PTD APC FRP GLASS FIBER PANEL CEILING DWC DRY-ERASE WALL COVERING
1202 HEAD END ROOM CONC NONE PTD PTD PTD PTD EXP 2302A STORAGE BBT RST PTD PTD PTD PTD APC GYP GYPSUM BOARD, PAINTED
1203 RECORDS STORAGE BBT RST PTD PTD PTD PTD APC 2302B STAFF TOILET PT CT CT CT CT CT GYP GYP2 RATED SHAFTWALL CEILING (SEE CODE
STUDY FOR RATING REQUIREMENTS)
1204 SOCIAL WORKER CPT RST PTD PTD PTD PTD APC 2303 MEN PT CT CT CT CT CT GYP
1205 PSYCHOLOGIST CPT RST PTD PTD PTD PTD APC 2304 SPECIAL EDUCATION 6-8 BBT RST PTD PTD PTD PTD APC
1206 MECH CONC NONE PTD PTD PTD PTD EXP 2305 RESOURCE BBT RST PTD PTD PTD PTD APC
1207 FLEX OFFICE CPT RST PTD PTD PTD PTD APC 2306 GRADE 6 BBT RST PTD PTD PTD PTD APC
1208 ELECTRICAL CONC NONE PTD PTD PTD PTD EXP 2307 GRADE 6 BBT RST PTD PTD PTD PTD APC
K 1209 OFFICE CPT RST PTD PTD PTD PTD APC 2308 GRADE 8 BBT RST PTD PTD PTD PTD APC K
1210 STAFF TOILET PT CT CT CT CT CT GYP 15 2309 GRADE 7 BBT RST PTD PTD PTD PTD APC
1211 OFFICE CPT RST PTD PTD PTD PTD APC 2310 MECH CONC NONE PTD PTD PTD PTD EXP
1300 DINING BBT RST PTD PTD/AWP PTD PTD APC3/APC4/GYP/EX 2, 7, 20 2311 MECH CONC NONE PTD PTD PTD PTD EXP

1301 WOMEN PT CT CT
1
CT CT CT
P
GYP 15
2312
2313
GRADE 8
GRADE 7
BBT
BBT
RST
RST
PTD
PTD
PTD
PTD
PTD
PTD
PTD
PTD
APC
APC
WALL KEY
1301A TOILET PT CT CT CT CT CT GYP 15 WALLS ON FINISH SCHEDULE ARE DENOTED THUS:
2320 COLLABORATIVE LEARNING BBT RST PTD PTD PTD PTD APC2/APC4/GYP
1302 MEN PT CT CT CT CT CT GYP 15 2501 MECHANICAL ROOM - GYM CONC NONE PTD PTD PTD PTD EXP
1302A CUSTODIAL CONC NONE PTD PTD PTD PTD EXP C15A VESTIBULE RM RST PTD PTD PTD PTD APC2/GYP A
1303 FURNITURE STORAGE BBT RST PTD PTD PTD PTD APC C100 CORRIDOR BBT RST PTD PTD PTD PTD APC/GYP
1304 PLATFORM WD/BBT RST PTD PTD PTD PTD EXP 3, 7 C110 CORRIDOR BBT RST PTD PTD PTD PTD APC D A-X.X. B
1304A PLATFORM STORAGE BBT RST PTD PTD PTD PTD APC C120 CORRIDOR BBT RST PTD PTD PTD PTD APC
1304B PLATFORM STORAGE BBT RST PTD PTD PTD PTD EXP C130 CORRIDOR BBT RST PTD PTD PTD PTD/AW EXP/APC2/APC4/GY 2, 7, 17
1400 LOCKERS/SHOWER/ TOILET PT CT CT CT CT CT GYP 4, 15 P P C
J 1402 WATER SERVICE CONC NONE PTD PTD PTD PTD APC C131 CORRIDOR BBT RST PTD PTD PTD - APC2/GYP TYPICAL UNLESS OTHERWISE NOTED. J
1403 CUSTODIAL CONC NONE PTD PTD PTD PTD APC C140 CORRIDOR BBT RST PTD PTD PTD PTD APC
1404 FIRE PUMP CONC NONE PTD PTD PTD PTD GYP2 C160 CORRIDOR BBT RST PTD PTD PTD PTD APC
1405 EMERGENCY ELECTRICAL CONC NONE PTD PTD PTD PTD GYP2 C161 CORRIDOR BBT RST PTD PTD PTD PTD APC TYPICAL NOTES
1406 CENTRAL STORAGE BBT RST PTD PTD PTD PTD APC C171 CORRIDOR BBT RST PTD PTD PTD PTD APC2/APC4/GYP
1407 ELECTRICAL CONC NONE PTD PTD PTD PTD GYP2 C172 CORRIDOR BBT RST PTD PTD PTD PTD APC2/GYP 1. REFER TO FLOOR PLANS, CEILING PLANS, INTERIOR ELEVATIONS, SECTIONS AND DETAILS FOR
1408 OPERATIONS OFFICE BBT RST PTD PTD PTD PTD APC C180 CORRIDOR BBT RST PTD PTD PTD PTD APC2/APC4/GYP ADDITIONAL INFORMATION AND EXTENT OF EACH FINISH WHEN MORE THAN ONE FINISH IS
INDICATED FOR ANY SPACE.
1408x RECEIVING BBT RST PTD PTD PTD PTD APC C190 CORRIDOR BBT RST PTD PTD PTD PTD APC2/APC4/GYP 2. SEE CEILING PLANS FOR HEIGHTS OF CEILINGS AND LOCATIONS AND HEIGHTS OF BULKHEADS,
1409 OFFICE BBT RST PTD PTD PTD PTD APC C200 CORRIDOR BBT RST PTD PTD PTD PTD APC2/APC4/GYP SOFFITS, ETC.
1410 TOILET PT CT CT CT CT CT GYP 15 C210 CORRIDOR BBT RST PTD PTD PTD PTD APC2/GYP 3. PAINT ALL EXPOSED STEEL LADDERS, LINTELS, HUNG PLATES, HAND AND GUARD RAILS, STAIRS
1410A LOCKER PT CT CT CT CT CT GYP C220 CORRIDOR BBT RST PTD PTD PTD PTD APC2/APC4/GYP AND STRINGERS.
4. PAINT ALL EXPOSED STEEL COLUMNS, TRUSSES, JOISTS, BEAMS, DECK, AND MISCELLANEOUS
1411 SOAP STORAGE EPOXY EPOXY PTD PTD PTD PTD GYP C230 CORRIDOR BBT RST PTD PTD PTD PTD APC2/APC4/GYP BRIDGING, ANGLES, PLATES, ETC.
1412 KITCHEN EPOXY EPOXY PTD PTD PTD PTD FRP E1 ELEVATOR BBT NONE NONE/P NONE/PT NONE/PT NONE/PT SEE SPEC. 14 5. INSTALL CERAMIC TILE COVE BASE FLUSH WITH FLOOR TILE AND FLUSH WITH CERAMIC WALL
TD D D D
H H

www.grimmandparker.com
1413 SERVING EPOXY EPOXY PTD PTD PTD PTD FRP TILE.
1414 DISH/TRAY RETURN EPOXY EPOXY PTD PTD PTD PTD FRP E100 CAN WASH CONC NONE PTD PTD PTD PTD EXP 6. FIELD PAINT ALL EXPOSED, NON-FACTORY FINISHED STRUCTURAL, MECHANICAL, OR
E101 OUTDOOR STORAGE CONC NONE PTD PTD PTD PTD EXP ELECTRICAL COMPONENTS.

11720 Beltsville Drive


1415 WALK-IN COOLER SEE SPECIFICATION

Calverton, MD 20705
7. PROVIDE SEALANT AT INTERSECTIONS OF DISSIMILAR MATERIALS, COMPLYING WITH
1416 WALK-IN FREEZER SEE SPECIFICATION E102 OUTDOOR STORAGE CONC NONE PTD PTD PTD PTD EXP
SPECIFICATIONS.

Tel: 301.595.1000
1417 DRY STORAGE EPOXY EPOXY PTD PTD PTD PTD FRP RA21 RAMP 2 BBT RST PTD PTD PTD PTD EXP 3, 5 8. REFER TO INTERIOR ELEVATIONS AND SECTIONS FOR ADDITIONAL FINISH INFORMATION.
1418 PANTRY EPOXY EPOXY PTD PTD PTD PTD FRP ST6 STAIR 6 PROVIDE ALL FINISH MATERIALS SHOWN IN PLANS, ELEVATIONS OR SECTIONS AS NOTED OR
1419 CORRIDOR EPOXY EPOXY PTD PTD PTD PTD FRP ST12 STAIR 1 BBT/RBR/C RST PTD WCV PTD PTD GYP 19 DEPICTED ON THE DRAWINGS AND SPECIFICATIONS.
ONC3 9. BRING CONFLICTS TO THE ARCHITECTS ATTENTION DURING THE BIDDING PERIOD FOR
1500 GYMNASIUM WD VRB PTD/AW PTD/AWP PTD/AWP PTD/AW EXP 7, 9, 17

Suite 600
ST20 STAIR 2 BBT/RBR RST PTD PTD PTD PTD EXP 18, 19 CLARIFICATION.
P1 1 1 P1 10. WALL AND CEILING FINISHES SHALL INCLUDE ALL PROJECTIONS, BEAM ENCLOSURES,
1501 SECURITY OFFICE BBT RST PTD PTD PTD PTD APC ST21 STAIR 2 BBT/RBR RST PTD PTD PTD PTD EXP 18, 19 RECESSES, BULKHEADS, MATERIAL CHANGES, OR OTHER ENCLOSURES.
1503 OFFICE BBT RST PTD PTD PTD PTD APC ST22 STAIR 2 BBT/RBR RST PTD PTD PTD PTD EXP 18, 19 11. ELECTRICAL OUTLETS, CLOCKS, P.A. SPEAKERS OR OTHER DEVICES SHOWN ON THE
1504 STORAGE BBT RST PTD PTD PTD PTD APC ST31 STAIR 3 BBT/RBR RST PTD PTD PTD PTD EXP 18, 19 ARCHITECTURAL DRAWINGS SERVE TO CALL ATTENTION TO THE PRESENCE OF SUCH DEVICES.
ST32 STAIR 3 BBT/RBR RST PTD PTD PTD PTD EXP 18, 19 NOT ALL DEVICES MAY BE SHOWN ON ARCHITECTURAL DRAWINGS. CONSULT THE OTHER
1511 P.E. OFFICE BBT RST PTD PTD PTD PTD APC
DRAWINGS FOR FURTHER INFORMATION AND ADVISE ARCHITECT OF ANY CONFLICT OF
1600 COMMUNITY LEARNING CENTER BBT RST PTD PTD PTD PTD APC ST42 STAIR 4 CONC NONE PTD PTD PTD PTD EXP
LOCATION OR TYPE OF DEVICES SHOWN. COORDINATE ALL WORK, FINISHES AND DEVICES.
G 1601 CONFERENCE BBT RST PTD PTD PTD PTD APC ST51 STAIR 5 CONC NONE PTD PTD PTD PTD EXP 12. PROVIDE MOISTURE RESISTANT GYPSUM BOARD AT TOILET ROOMS, & SERVICE CLOSETS FOR G
1602 OFFICE BBT RST PTD PTD PTD PTD APC ST52 STAIR 5 CONC NONE PTD PTD PTD PTD EXP WALLS DESIGNATED AS GYPSUM BOARD WALL TYPES. PROVIDE TILE BACKER BOARD AT WALLS
1603 OFFICE BBT RST PTD PTD PTD PTD APC V100 VESTIBULE RM/VCT RST PTD PTD/WCV PTD PTD EXP/APC4/GYP 2 DESIGNATED AS GYPSUM BOARD WALL TYPES WITH TILE FINISH.
V1600 VESTIBULE CONC2 RST PTD PTD PTD PTD GYP 13. FIELD PAINT ELECTRICAL PANELS EXCEPT PANELS LOCATED IN ELECTRICAL CLOSETS AND
1604 FAMILY RESOURCE ROOM BBT RST PTD PTD PTD PTD APC MECHANICAL ROOMS.
1605 OFFICE BBT RST PTD PTD PTD PTD APC V1806 VESTIBULE CONC2 RST PTD PTD PTD PTD GYP 14. BRING CONFLICTS BETWEEN THE FINISH SCHEDULE AND MATERIALS SHOWN ON OTHER
1606 CLOSET BBT RST PTD PTD PTD PTD APC DRAWINGS (AND/OR SPECIFICATIONS) TO THE ATTENTION OF THE ARCHITECT IMMEDIATELY. IF A
1607 TOILET PT CT CT CT CT CT GYP 15 CONFLICT EXISTS IN/BETWEEN DRAWINGS (AND/OR SPECIFICATIONS), THE MORE STRINGENT
AND MORE COSTLY REQUIREMENT SHALL APPLY.
1608 PANTRY EPOXY EPOXY PTD PTD PTD PTD FRP
15. PAINT COLUMNS TO MATCH ADJACENT WALL PATTERN AND COLOR UNLESS NOTED OTHERWISE.
1609 CUSTODIAL
1700 MEDIA CENTER CPT RST PTD PTD PTD/DWC PTD EXP/APC2/APC4/GY 2, 7
P
1701 WORKROOM/STORAGE BBT RST PTD PTD PTD PTD APC
1703 LARGE REHEARSAL BBT RST PTD/AW PTD/AWP PTD/AWP PTD/AW APC3/DPC 7
P2 2 2 P2
F 1704 STORAGE BBT RST PTD PTD PTD PTD APC F
1705 SMALL REHEARSAL BBT RST PTD/AW PTD/AWP PTD/AWP PTD/AW APC3/DPC 7
P2 2 2 P2
1710 OT/PT BBT RST PTD PTD PTD PTD APC

ROOM SIGNAGE
1710A
1710B
TOILET
OT/PT STORAGE
PT
BBT
CT
RST
CT
PTD
CT
PTD
CT
PTD
CT
PTD
GYP
APC GP# 21553
1711 SP. ED. OFFICE BBT RST PTD PTD PTD PTD APC
1711A SP. ED. STORAGE BBT RST PTD PTD PTD PTD APC
1720 CUSTODIAL CONC NONE PTD PTD PTD PTD EXP
1721 ART STUDIO BBT RST PTD PTD PTD PTD APC
6"
1721A KILN CONC2 RST PTD PTD PTD PTD APC
1721B ART STORAGE BBT RST PTD PTD PTD PTD APC
1722 TECH ED LAB BBT RST PTD PTD PTD PTD/DW APC
C
E 1722A SUPPLY STORAGE/IT ADMIN BBT RST PTD PTD PTD PTD APC E
1800 TELECOM/UTILITY CONC NONE PTD PTD PTD PTD EXP
1801 MECH CONC NONE PTD PTD PTD PTD EXP
1802 PLANNING CPT RST PTD PTD PTD PTD APC
8"

MIN. 3/4" CAP. HEIGHT 1802A STORAGE BBT RST PTD PTD PTD PTD APC
TACTILE TEXT RAISED 1/32"
1802B STAFF TOILET PT CT CT CT CT CT GYP 15
FULL CAPS
SANS SERIF TYPE STYLE 1803 FACULTY LOUNGE BBT RST PTD PTD PTD PTD APC
STAIR 1 1803A STAFF TOILET PT CT CT CT CT CT GYP 15
STAIR 1 GRADE 2 BRAILLE 1804 ELECTRICAL CONC NONE PTD PTD PTD PTD EXP
1805 GRADE 3 BBT RST PTD PTD PTD PTD APC

CITY OF BALTIMORE, MARYLAND


1805A PK-2 TOILET PT CT CT CT CT CT GYP 15
6" 1805E GYM STORAGE BBT RST PTD PTD PTD PTD APC
1805F LOCKERS/SHOWER/TOILET PT CT CT CT CT CT GYP 4, 15
D GRADE 2 BRAILLE 1805G
1805H
LOCKERS/SHOWER/TOILET
LOCKERS/SHOWER/TOILET
PT
PT
CT
CT
CT
CT
CT
CT
CT
CT
CT
CT
GYP
GYP
4, 15
4, 15
D
100A

HOLABIRD ACADEMY PK-8


PICTOGRAM BORDER OR 1806 RESOURCE BBT RST PTD PTD PTD PTD APC
BACKGROUND FIELD, MIN.
100a 6" HEIGHT 1807 GRADE 1 BBT RST PTD PTD PTD PTD APC
1807A PK-2 TOILET PT CT CT CT CT CT GYP 15
1808 GRADE 3 BBT RST PTD PTD PTD PTD APC
MIN. 5/8" CAP. HEIGHT 1808A PK-2 TOILET PT CT CT CT CT CT GYP 15
8"

TACTILE TEXT RAISED 1/32" FULL

FINISH SCHEDULE
CAPS 1809 MECH CONC NONE PTD PTD PTD PTD EXP
SANS SERIF TYPE STYLE 1810 GRADE 2 BBT RST PTD PTD PTD PTD APC
1810A PK-2 TOILET PT CT CT CT CT CT GYP 15
RESTROOM 1811 GRADE 1 BBT RST PTD PTD PTD PTD APC
RESTROOM GRADE 2 BRAILLE 1811A PK-2 TOILET PT CT CT CT CT CT GYP 15
1812 MECH CONC NONE PTD PTD PTD PTD EXP

C 6" 3/4" CAP. HEIGHT


1813
1813A
GRADE 2
PK-2 TOILET
BBT
PT
RST
CT
PTD
CT
PTD
CT
PTD
CT
PTD
CT
APC
GYP 15
NUMBERED REMARKS C
TACTILE TEXT RAISED 1/32" FULL 1820 COLLABORATIVE LEARNING BBT RST PTD PTD PTD PTD APC2/APC4/GYP
WHEN SHOWN IN THE REMARKS COLUMN OF THE FINISH SCHEDULE:
CAPS 1900 PLANNING CPT RST PTD PTD PTD PTD APC
SANS SERIF TYPE STYLE 1900A STAFF TOILET PT CT CT CT CT CT GYP 15
100A 1902 SPECIAL EDUCATION PK-2 BBT RST PTD PTD PTD PTD APC
1. EXPOSED CONSTRUCTION (STRUCTURE, ROOF DECK, MECHANICAL EQUIPMENT, DUCTS (SUPPLY
AND RETURN), PLUMBING PIPING, SPRINKLER PIPING, CONDUIT, WIRE TRAYS) WILL EACH BE
100a GRADE 2 BRAILLE 1902A TOILET PT CT CT CT CT CT GYP 15 PAINTED SEPERATE COLORS TO BE SELECTED BY ARCHITECT.
MIN. 5/8" CAP. HEIGHT SIGN NOTES: 1903A MECH CONC NONE PTD PTD PTD PTD EXP 2. EXPOSED CONSTRUCTION PAINTED AND HANGING ACOUSTICAL CEILING TREATMENT
3. EXPOSED CONSTRUCTION PAINTED FLAT BLACK
6"

TACTILE TEXT RAISED 1/32" FULL


1904 STORAGE BBT RST PTD PTD PTD PTD APC DATE DESCRIPTION
CAPS 1. ROOM SIGNS TO BE PROVIDED AT EVERY DOOR. EXACT 4. PROVIDE FULL HEIGHT CERAMIC TILE AT SHOWER AND AT FLOOR OF SHOWER.
SANS SERIF TYPE STYLE ROOM NUMBER TO BE DETERMINED BY OWNER. 1905 PRE-K BBT RST PTD PTD PTD PTD APC 5. PROVIDE SLIP RESISTANT BBT @ RAMP.
CLASSROOM 2. SIGNS TO BE MOUNTED WITH DOUBLE STICK TAPE AND 1905A PK-2 TOILET PT CT CT CT CT CT GYP 15 6. SEE ALTERNATES FOR CERAMIC TILE ON WALLS AND FLOORS (NOT USED).
CLASSROOM GRADE 2 BRAILLE SILICONE ADHESIVE. SEAL PERIMETER WITH CLEAR 1906 RESOURCE BBT RST PTD PTD PTD PTD APC 7. SEE INTERIOR ELEVATIONS FOR ACOUSTIC PANEL LOCATIONS.
SILICONE CAULKING. 8. SEE REFLECTED CEILING PLAN FOR INTERACTIVE ACOUSTIC PANEL LOCATIONS.
1907 PRE-K BBT RST PTD PTD PTD PTD APC
3. PROVIDE BLANK SIGN FOR BACK WHERE MOUNTED ON 9. SEE INTERIOR ELEVATIONS FOR WALL SAFETY PADS.
GLASS SIDELITE. 1907A PK-2 TOILET PT CT CT CT CT CT GYP 15 10. NOT USED
B 6" 4. SIGNAGE PACKAGE SHALL BE COORDINATED WITH
OWNER'S DESIGN STANDARDS.
1908
1908A
KINDERGARTEN
PK-2 TOILET
BBT
PT
RST
CT
PTD
CT
PTD
CT
PTD
CT
PTD
CT
APC
GYP 15
11.
12.
FOUR COLORS OF BBT WILL BE USED IN A PATTERN IDENTIFIED BY ARCHITECT.
THREE COLORS OF BBT WILL BE USED IN A PATTERN IDENTIFIED BY ARCHITECT.
B
3/4" CAP. HEIGHT 5. INCLUDE SIGNS WITH TEXT AND GRAPHIC TO BE 1909 PRE-K BBT RST PTD PTD PTD PTD APC 13. TWO COLORS OF BBT WILL BE USED IN A PATTERN IDENTIFIED BY ARCHITECT.
TACTILE TEXT RAISED 1/32" FULL INSTALLED AT EACH ELEVATOR LANDING: 14. PAINT PIT FLOOR AND WALLS AND UPPER SECTION OF SHAFT FROM SECOND FLOOR DOOR HEAD TO
1909A PK-2 TOILET PT CT CT CT CT CT GYP 15 UNDERSIDE OF DECK WHITE.
CAPS 'IN CASE OF FIRE DO NOT USE ELEVATOR. USE FIRE
SANS SERIF TYPE STYLE EXIT STAIRWAY.' 1910 KINDERGARTEN BBT RST PTD PTD PTD PTD APC 15. PROVIDE FULL HEIGHT CERAMIC TILE ON ALL WALLS.
EXIT 6. TACTILE EXIT SIGNS TO BE PROVIDED AT EVERY EXIT 1910A PK-2 TOILET PT CT CT CT CT CT GYP 15 16. NOT USED
4"

EXIT GRADE 2 BRAILLE DOOR. 1911 KINDERGARTEN BBT RST PTD PTD PTD PTD APC 17. PAINTED GRAPHIC ON WALL
18. STAIR HAS APC AT UPPER EXTENTS OF STAIR. EXP AT INTERMEDIATE LEVELS. SEE REFLECTED
1911A PK-2 TOILET PT CT CT CT CT CT GYP 15
CLG. PLANS.
1920
2000
2000A
COLLABORATIVE LEARNING
SCIENCE LAB
PREP/STORAGE
BBT
BBT
BBT
RST
RST
RST
PTD
PTD
PTD
PTD
PTD
PTD
PTD
PTD
PTD
PTD
PTD
PTD
APC2/APC4/GYP
APC
APC
19.
20.
BBT 2 LANDINGS , RBR TREADS AND RISERS.
REFER TO SHEET A-5.6 FOR FINISH DETAILS AT WONDERWALL ON WEST SIDE OF DINING ROOM. A-3.1
2100 MECH CONC NONE PTD PTD PTD PTD EXP 03/13/2017
BID SET
A © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

DOOR SCHEDULE DOOR SCHEDULE TYPICAL DETAILS


DOOR FRAME DOOR DOOR FRAME DOOR DOORS NOT LISTED ON THE SCHEDULE SHALL HAVE THE TYPICAL FINISHES LISTED BELOW:
NOMINAL SIZE SECTIONS LABEL NOMINAL SIZE SECTIONS LABEL
DOOR: FRAME:
DOOR FIRE HARDWARE DOOR FIRE HARDWARE WIDTH: 3'-0" MATERIAL:HM
NO. ROOM WIDTH HEIGHT THK. TYPE MAT'L MAT'L TYPE JAMB HEAD SILL RATING SET REMARKS NO. ROOM WIDTH HEIGHT THK. TYPE MAT'L MAT'L TYPE JAMB HEAD SILL RATING SET REMARKS HEIGHT: 7'-0" TYPE: 1
THICKNESS: 1-3/4" JAMB: J1
6' - 3" 7' - 6" 1 3/4" FG2 ALUM ALUM CW2 2 1911 KINDERGARTEN 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 4 J1 H1 713
TYPE: F HEAD: H1
0001 STAIR 2 6' - 0" 7' - 0" 1 3/4" F HM HM 1 J11 H11 S2 60 MIN 321 1911A PK-2 TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 117 MATERIAL: SCWD SILL: NONE
0001A GEOTHERMAL PUMP 6' - 0" 7' - 0" 1 3/4" F HM HM 1 J1 H1 321 2000 SCIENCE LAB 3' - 0" 7' - 0" 1 3/4" NV SCWD HM 1 J1 H1 60 MIN 716 1 DOOR LABEL: NONE
ROOM 2000A PREP/STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 717 1
1000A RECEPTION 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 21 J1 H3 414 1, 24 2100 MECH 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S1 718 1, 14, 22
M 1000B RECEPTION 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 21 J1 H3 414 1, 24 2101 MECHANICAL ROOM - 5' - 0" 7' - 0" 1 3/4" F HM HM 1 J13 H13 S5 90 MIN 321 1 M
1000C
1001
RECEPTION
A.P. OFFICE
3' - 0"
3' - 0"
7' - 0"
7' - 0"
1 3/4"
1 3/4"
HG
HG
SCWD
SCWD
HM
HM
1
2
J2
J2
H2
H2 S3
111
510
1
2200
CENTRAL
FLEX 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713
TYPICAL DOOR NOTES
1002 WORKROOM 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J2 H2 110 2202 TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S2 117 1. COORDINATE AND PROVIDE HARDWARE AS DETAILED IN THE SPECIFICATIONS OR, IF NOT
1003 CLOSET 6' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 810 2203B CUSTODIAL 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S2 SPECIFIED, PROVIDE HARDWARE (OF EQUAL QUALITY TO THAT SPECIFIED, AND MOST SIMILAR IN
1004 CONFERENCE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J2 H2 110 2204 PLANNING 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 4 J1 H1 S3 712 FUNCTION TO TYPE OF DOOR) REQUIRED FOR DOORS TO OPERATE AND APPEAR AS INTENDED ON
DRAWINGS.
1005 SECURE STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 811 2204A STAFF TOILET 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 1 J2 H2 S2 112 2. PROVIDE BRUSHED STAINLESS STEEL KICK PLATES ON PUSH SIDE OF DOORS WITH PUSH BARS
1006 PRINCIPAL 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J2 H2 S3 510 2204B STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 812 1 AND/OR CLOSER DEVICES. KICK PLATE SHALL BE INSET 1/2" FROM EACH SIDE OF DOOR, AND
1007 FLEX OFFICE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J2 H2 S3 510 2205 MECH/UTILITY 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S1 718 22 MAXIMUM 8" HIGH OR 1/2" BELOW EDGE OF GLASS LIGHT (IF PRESENT).
1008 FLEX OFFICE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J2 H2 S3 510 2206 SPECIAL EDUCATION 3-5 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 27 J1 H1 713 3. PROVIDE EXPOSED HARDWARE WITH BRUSHED-IN FINISH AND "SILVER" METALLIC IN COLOR
(ALUMINUM, CHROME, OR STEEL).
1009 STAFF TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 112 2207 ELEVATOR CONTROL 3' - 6" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 90 MIN 812
4. WHEN EXPOSED CLEAR FINISHED WOOD DOORS ARE PAIRED, TAKE CARE TO SELECT MATCHING
1010 STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 811 1 2208 CORRIDOR 3' - 0" 7' - 0" 1 3/4" HG SCWD HM HM13A J1 H4 712 GRAIN TYPE AND COLOR FOR EACH DOOR IN PAIR.
1011 LAUNDRY 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 717 2209 FLEX 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713 5. IF CONFLICT EXISTS BETWEEN DOOR RATING AS SCHEDULED AND WALL/PARTITION TYPE FIRE
RATING AS SHOWN ON PLANS, PROVIDE DOOR(S) WITH THE GREATER FIRE RATING OF THE TWO.
L 1012
1100A
PERSONAL CARE
WAITING
3' - 0"
3' - 0"
7' - 0"
7' - 0"
1 3/4"
1 3/4"
F
HG
SCWD
SCWD
HM
HM
1
21
J2
J1
H2
H3
113
711 1
2210
2211
GRADE 5
GRADE 4
3' - 0"
3' - 0"
7' - 0"
7' - 0"
1 3/4"
1 3/4"
HG
HG
SCWD
SCWD
HM
HM
3
3
J1
J1
H1
H1
713
713 6. VERIFY ALL DIMENSIONS AND CLEARANCES, AND COORDINATE UNDERCUTTING REQUIRED TO L
CLEAR ADJACENT FLOOR MATERIALS.
1100B CORRIDOR 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 716 2212 MECH 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S1 718 1, 22 7. SEE FRAME ELEVATION SHEETS FOR FRAME TYPES. (BOTH H.M. AND ALUM. STOREFRONT) AND
1101 STUDENT TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 117 2213 MECH 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S1 718 1, 22 GLASS TYPE KEY.
1102 HEALTH OFFICE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 4 J2 H2 510 2214 GRADE 5 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713 8. IF A DISCREPANCY EXISTS BETWEEN THE DOOR SCHEDULE REMARKS AND THE HARDWARE
1102A STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 810 2215 GRADE 4 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713 SCHEDULE IN THE SPECIFICATIONS, PROVIDE THE HARDWARE NEEDED TO MEET THE MORE
STRINGENT OF THE REQUIREMENTS.
1104 EXAM/TREATMENT 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 1 J2 H2 110 2300 FLEX 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713
9. SEE SPECIFICATIONS FOR SCHEDULED HARDWARE SETS. SEE SPECIFICATIONS FOR HARDWARE
1106 EXAM/TREATMENT 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 1 J2 H2 110 2300A STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 812 1 SETS INDICATED FOR PACKAGED DOOR SYSTEM.
1200 CORRIDOR 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 11 J1 H3 713 1 2300E TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S2 117 10. PROVIDE CONTINUOUS WEATHERSTRIPPING AND DOOR BOTTOM SEALS AT EXTERIOR DOORS AS
1201 CONFERENCE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 12A J2/H10 H2 S3 110 2302 PLANNING 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 4 J1 H1 S3 712 SPECIFIED.
1202 HEAD END ROOM 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 718 1, 22 2302A STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S3 812 1
1203 RECORDS STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 811 1 2302B STAFF TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 112
1204 SOCIAL WORKER 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J2 H2 S3 510 2304 SPECIAL EDUCATION 6-8 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713
1205 PSYCHOLOGIST 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J2 H2 S3 510 2305 RESOURCE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 25B J1 H4 712
K 1206 MECH 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S1 718 1 2306 GRADE 6 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713 K
1207 FLEX OFFICE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J2 H2 S3 510 2307 GRADE 6 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713
1208 ELECTRICAL 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S1 60 MIN 718 1, 22 2308 GRADE 8 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713
1209 OFFICE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J2 H2 S3 510 2309 GRADE 7 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713
1210 STAFF TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 112 2310 MECH 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 1 J1 H1 S1 118 1
1211 OFFICE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J2 H2 S3 510 2311 MECH 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S1 118 1
1271 PANTRY 4' - 0" 4' - 8" 2" S J12 H12 S4 OVERHEAD COILING COUNTER 2312 GRADE 8 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713
DOOR 2313 GRADE 7 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713
1300A DINING 6' - 0" 7' - 0" 1 3/4" HG SCWD HM 1 J1 H3 445 2 C100 CORRIDOR 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 28 J1 H1 713 1
1300B
1300C
DINING
DINING
6' - 0"
3' - 0"
7' - 0"
7' - 0"
1 3/4"
1 3/4"
HG
F
SCWD
SCWD
HM
HM
1
1
J1
J13
H3
H13 S6
445
510
2 C100A
C130A
CORRIDOR
CORRIDOR
3' - 0"
6' - 0"
7' - 0"
7' - 0"
1 3/4"
1 3/4"
HG
FG2
SCWD
ALUM
HM
ALUM
2
SF14
J2
J16
H2
H17
716
421 1, 2, 23
NOTES FOR REMARKS COLUMN
1301A TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S2 117 C130B CORRIDOR 6' - 0" 7' - 0" 1 3/4" FG2 ALUM ALUM SF14 J16 H17 420 1, 2, 24
NOTE: NOT ALL NOTES MAY BE USED ON THIS PROJECT. SEE SPECIFICATIONS FOR ADDITIONAL DOOR
1302A CUSTODIAL 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S2 812 C140 CORRIDOR 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 213 1 INFORMATION. REFERENCE SPECIFICATIONS FOR DETAILED HARDWARE REQUIREMENTS.
1303 FURNITURE STORAGE 6' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J6 H5 822 1
J 1304A PLATFORM STORAGE 6' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 822 1
C172A
C172B
CORRIDOR
CORRIDOR
8' - 0"
8' - 0"
7' - 10"
7' - 0"
1 3/4"
1 3/4"
NV
NV
HM
SCWD
HM
HM
1
1
J1
J1
H1
H3 220 1,2, 6 1. PROVIDE ADA COMPLIANT CLOSER (ONE CLOSER FOR EACH DOOR OF PAIR).
J
1400 LOCKERS/SHOWER/ 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 113 C172C CORRIDOR 8' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H3 220 1, 2, 6 2. PROVIDE PANIC HARDWARE.
TOILET 3. PROVIDE ALARMED PANIC HARDWARE.
C172D VESTIBULE 7' - 0" 7' - 0" 1 3/4" F ALUM ALUM SF15 J16 H16 420 2 4. PROVIDE ADA AUTOMATIC SWING DOOR OPERATOR WITH PUSH BUTTON CONTROLS AND
1402 WATER SERVICE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S1 812 1 ST6 VESTIBULE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 811 1 ASSOCIATED SIGNAGE.
1403 CUSTODIAL 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S1 812 ST11 CORRIDOR 8' - 0" 7' - 10" 1 3/4" NV HM HM 1 J13 H13 S5 90 MIN 326 1,2, 5, 14 5. PROVIDE DOORS WITH ELECTROMAGNETIC HOLD OPEN DEVICES - CONNECT TO FIRE ALARM
1404 FIRE PUMP 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S1 90 MIN 812 1 ST11A CORRIDOR 8' - 0" 7' - 10" 1 3/4" NV HM HM 1 J1 H1 60 MIN 326 1, 2, 5, 14 SYSTEM TO CLOSE UPON ACTIVATION -- SEE ELECTRICAL DRAWINGS.
1405 EMERGENCY ELECTRICAL 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S1 90 MIN 311 1, 14 6. PROVIDE WITH HOLD OPEN FEATURE IN CLOSER.
ST12 CORRIDOR 8' - 0" 7' - 10" 1 3/4" NV HM HM 1 J1 H1 60 MIN 324 1, 2, 5, 14
1406 CENTRAL STORAGE 6' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 822 1 7. PROVIDE WEATHERSTRIPPING ON ALL SIDES, TOP AND BOTTOM OF DOOR.
ST21 STAIR 2 6' - 0" 7' - 0" 1 3/4" NV SCWD HM 1 J13 H13 60 MIN 324 2, 5, 14 8. PROVIDE DOOR WITH INSULATED CORE.
1407 ELECTRICAL 6' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S1 60 MIN 321 1,2, 14 ST21A STAIR 2 3' - 0" 7' - 0" 1 3/4" F HM HM 1 J1 H1 60 MIN 811 1 9. PROVIDE HARDWARE WITH PRIVACY SET.
1408 OPERATIONS OFFICE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 510 ST22 STAIR 2 6' - 0" 7' - 0" 1 3/4" NV SCWD HM 1 J13 H13 60 MIN 324 1, 5, 14 10. PROVIDE FLUSH BOLTS ON INACTIVE LEAF.
1409 OFFICE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 1 J1 H1 510 ST31 STAIR 3 6' - 0" 7' - 0" 1 3/4" NV SCWD HM 1 J13 H13 60 MIN 324 5, 14 11. PROVIDE SOUND SEALS ON TOP AND SIDES WITH DROP SEAL AT DOOR BOTTOM.
1410 TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S2 112 12. PROVIDE SOUND RATED DOOR SYSTEM COMPLETE WITH ALL ASSOCIATED HARDWARE - SEE
ST32 STAIR 3 6' - 0" 7' - 0" 1 3/4" NV SCWD HM 1 J13 H13 60 MIN 324 1, 5, 14 SPECIFICATIONS.
1410A LOCKER 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S2 215 ST51 STAIR 5 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 60 MIN 811 1, 14 13. PROVIDE WITH PUSH / PULL OPERATION.
H H

www.grimmandparker.com
1411 SOAP STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 710 14 ST52 STAIR 5 3' - 0" 7' - 0" 1 3/4" F HM HM 1 J1 H1 60 MIN 114 1 14. PROVIDE HARDWARE SO DOORS CAN OPEN 180 DEGREES.
1412B CORRIDOR 3' - 0" 7' - 0" 1 3/4" NV SCWD HM 1 J1 H1 512 X1 VESTIBULE 6' - 0" 7' - 6" 1 3/4" FG2 ALUM ALUM CW1A A18/A-5. 442 1, 2, 4, 22, 23, 24 15. DOUBLE EGRESS DOOR.
1413 SERVING 10' - 0" 8' - 0" J14 H14 OVERHEAD FOLDING GLASS 16. INSULATED COILING DOOR.

11720 Beltsville Drive


10

Calverton, MD 20705
DOOR 17. AUTOMATIC SLIDING DOORS WITH EMERGENCY BREAKOUT FEATURE.
X2 VESTIBULE 6' - 0" 7' - 6" 1 3/4" FG2 ALUM ALUM CW1A A18/A-5. 440 1, 2

Tel: 301.595.1000
1413A SERVING 10' - 0" 8' - 0" J14 H14 OVERHEAD FOLDING GLASS 18. DOUBLE ACTING DOOR FUNCTION.
10
DOOR 19. PROVIDE PACKAGE DOOR SYSTEM - SEE DIVISION 8 SPECIFICATION SECTION.
X3 VESTIBULE 6' - 0" 7' - 6" 1 3/4" FG2 ALUM ALUM CW1A A18/A-5. 440 1, 2 20. COILING SECURITY GRILLE.
1414 DISH/TRAY RETURN 4' - 0" 4' - 8" 2" S J12 H12 S4 OVERHEAD COILING COUNTER 10 21. PROVIDE WITH MECHANICAL PUSH BUTTON COMBINATION LOCK.
DOOR X5 CORRIDOR 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 1 J9 H9 A18/A-5. 319 2 22. PROVIDE WITH CARD READER AND ASSOCIATED HARDWARE.

Suite 600
1417 DRY STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 812 10 23. SECURITY SYSTEM DOOR SWITCH AT HM FRAME - COORDINATE WITH ELECTRICAL.
1418 PANTRY 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J6 H5 710 X6 COMMUNITY LEARNING 3' - 0" 7' - 6" 1 3/4" F ALUM ALUM SF8 A18/A-5. 319 2 24. ACCESS CONTROL SYSTEM - PROVIDE WITH MAGNETIC LOCKS AND OPEN RELEASE BUTTON -
1500 GYMNASIUM 8' - 0" 7' - 10" 1 3/4" HG HM HM 2 J13 H13 S6 325 2 CENTER 10 CONNECT TO FIRE ALARM SYSTEM TO OPEN UPON ACTIVATION - SEE ELECTRICAL DRAWINGS.
1500B GYM STORAGE 6' - 0" 7' - 0" 1 3/4" F HM HM 1 J13 H13 S6 822 1 X7 GYMNASIUM 6' - 0" 7' - 0" 1 3/4" HG HM HM 1 J9 H9 A18/A-5. 323 2
1500C GYMNASIUM 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J13 H13 S6 211 13 10
1500D VESTIBULE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J13 H13 S6 211 13 X8 GYMNASIUM 6' - 0" 7' - 6" 1 3/4" HG ALUM ALUM CW4 A18/A-5. 440
10
G 1501
1503
SECURITY OFFICE
OFFICE
3' - 0"
3' - 0"
7' - 0"
7' - 0"
1 3/4"
1 3/4"
HG
HG
SCWD
SCWD
HM
HM
3
2
J1
J13
H1
H13 S6
510
510 X9 KITCHEN 4' - 0" 7' - 0" 1 3/4" F HM HM 1 J9 H9 A18/A-5. 817 1, 8 G
10
1504 STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 812
X10 CAN WASH 3' - 0" 7' - 0" 1 3/4" F HM HM 1 J9 H9 A18/A-5. 817 8
1511 P.E. OFFICE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 510 10
1600 VESTIBULE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J13 H13 314 1
X11 RECEIVING 6' - 0" 7' - 0" 1 3/4" NV HM HM 1 J9 H9 A18/A-5. 621 22
1600B COMMUNITY LEARNING 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J2 H2 317 10
CENTER
X12 ELECTRICAL 3' - 0" 7' - 0" 1 3/4" F HM HM 1 J9 H9 A18/A-5. 316 2, 1, 8
1601 CONFERENCE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J2 H2 710 10
1602 OFFICE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J2 H2 510 X13 KINDERGARTEN 3' - 9" 7' - 8" 1 3/4" FG2 ALUM ALUM SF9 J9 H9 A18/A-5. 412 1
1603 OFFICE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J2 H2 510 10
1604 FAMILY RESOURCE ROOM 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J2 H2 317 X14 KINDERGARTEN 3' - 9" 7' - 8" 1 3/4" FG2 ALUM ALUM SF9 J9 H9 A18/A-5. 412 1
1605 OFFICE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J2 H2 510 10
1606 CLOSET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 110 X15 KINDERGARTEN 3' - 9" 7' - 8" 1 3/4" FG2 ALUM ALUM SF9 J9 H9 A18/A-5. 412 1
1607 TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 112 10
F 1608 PANTRY 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 710 X16
X17
STAIR 3 6' - 3"
3' - 9"
7' - 6"
7' - 8"
1 3/4"
1 3/4"
FG2
FG2
ALUM
ALUM
ALUM
ALUM
CW2
SF9
J9
J9
H9
H9 A18/A-5.
441
412
2
1
F
1608A PANTRY 4' - 0" 4' - 8" 2" S J15 H15 S8 OVERHEAD COILING COUNTER
DOOR 10
1609 CUSTODIAL 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 X18 PRE-K 3' - 9" 7' - 8" 1 3/4" FG2 ALUM ALUM SF9 J9 H9 A18/A-5. 412 1
10
1700 MEDIA CENTER 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 21 H3 915 2
1701 WORKROOM/STORAGE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 4 J2 H2 S3 710
X19 3' - 9" 7' - 8" 1 3/4" FG2 ALUM ALUM SF9 J9 H9 A18/A-5.
10
412 1
GP# 21553
1703 LARGE REHEARSAL 6' - 0" 7' - 0" 1 3/4" HG SCWD HM 1 J1 H3 445
X20 VESTIBULE 7' - 0" 7' - 6" 1 3/4" F ALUM ALUM CW3 J9 H9 A18/A5.1 422 2, 4, 22, 23
1704A STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 812 1 0
1704B STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 812 1 X22 CORRIDOR 3' - 0" 7' - 0" 1 3/4" HG HM HM 1 60 MIN 612 1, 8
1705 SMALL REHEARSAL 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 21 J1 H3 915 X23 MEDIA CENTER 3' - 0" 8' - 0" 1 3/4" FG2 ALUM ALUM SF12D A18/A5.1 412
1710 OT/PT 3' - 0" 7' - 0" 1 3/4" NV SCWD HM 1 J1 H1 60 MIN 511 1 0
1710A TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 117 X24 OUTDOOR STORAGE 4' - 0" 7' - 0" 1 3/4" F HM HM 1 J9 H9 A18/A5.1 817 8
1710B OT/PT STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 812 0
1711 SP. ED. OFFICE 3' - 0" 7' - 0" 1 3/4" NV SCWD HM 1 J1 H1 60 MIN 511 1 X25 OUTDOOR STORAGE 3' - 0" 7' - 0" 1 3/4" F HM HM 1 J9 H9 A18/A5.1 817 8
E 1711A SP. ED. STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 810 0 E
1720 CUSTODIAL 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 812 X30 MECHANICAL ROOM - GYM 3' - 0" 7' - 0" 1 3/4" F HM HM 1 J9 H9 A18/A-1. 612 1
9
1721 ART STUDIO 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 29 J1 H3 713
1721A KILN 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 717 1
1721B ART STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 717 1
1721C ART STUDIO 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713
1722 TECH ED LAB 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 29 J1 H3 713
1722A SUPPLY STORAGE/IT 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 1 J2 H2 812 1
ADMIN
1722B TECH ED LAB 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 1 J1 H1 713

CITY OF BALTIMORE, MARYLAND


1800 TELECOM/UTILITY 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S1 718 22
1801 MECH 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 1 J1 H1 S1 718 1, 22
1802 PLANNING 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 10 J1 H4 S3 712
1802A STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S3 812 1
D 1802B STAFF TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 112
D

HOLABIRD ACADEMY PK-8


1803 FACULTY LOUNGE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 1 J1 H1 712
1803A STAFF TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 112
1804
1805
ELECTRICAL
GRADE 3
3' - 0"
3' - 0"
7' - 0"
7' - 0"
1 3/4"
1 3/4"
F
HG
SCWD
SCWD
HM
HM
1
27
J1
J1
H1
H1
S1 718
713
1, 22
DOOR ELEVATION
1805A PK-2 TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 117
1805F LOCKERS/SHOWER/TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J13 H13 S6 211 1

DOOR SCHEDULE
1805G LOCKERS/SHOWER/TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S6 213 1, 13 6" 6" 6" 6"
1805H LOCKERS/SHOWER/TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S6 213 1, 13
1806 RESOURCE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 13A J1 H4 712

9"

9"
1807 GRADE 1 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713
1807A PK-2 TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 117
1808 GRADE 3 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713
C 1808A PK-2 TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 117 C

TO TOP OF GLASS STOP


1809 MECH 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S1 718 1, 22

1' - 0" 1' - 11" 7"


3' - 6" MAX.
1810 GRADE 2 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713
1810A PK-2 TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 117
1811 GRADE 1 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713

1' - 0"
1811A PK-2 TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 117
1812 MECH 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S1 718 1, 22
1813 GRADE 2 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 713 F FG FG2 DATE DESCRIPTION
1813A PK-2 TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 117 6" 6" 6" 4" KICKPLATE AT
1900 PLANNING 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 3 J1 H1 S3 712 EXTERIOR DOORS
1900A STAFF TOILET 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 1 J2 H2 S2 112

1' - 6"
1902 SPECIAL EDUCATION PK-2 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 2 J1 H1 713
1902A TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 117

9"
1903 MECH 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 S1 718 1, 22
B 1904 STORAGE 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 812 B

TO TOP OF GLASS STOP


1905 PRE-K 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 4 J1 H1 713

TO TOP OF GLASS STOP


1905A PK-2 TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 117

3' - 6" MAX.


3' - 6" MAX.
1906 RESOURCE 3' - 0" 7' - 0" 1 3/4" HG SCWD HM HM13A J1 H4 712
1907 PRE-K 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 4 J1 H1 713
1907A PK-2 TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 117
1908 KINDERGARTEN 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 4 J1 H1 713
1908A
1909
1909A
PK-2 TOILET
PRE-K
PK-2 TOILET
3' - 0"
3' - 0"
3' - 0"
7' - 0"
7' - 0"
7' - 0"
1 3/4"
1 3/4"
1 3/4"
F
HG
F
SCWD
SCWD
SCWD
HM
HM
HM
1
4
1
J2
J1
J2
H2
H1
H2
S2

S2
117
713
117
HG NV
s
OVERHEAD COILING
COUNTER DOOR
A-3.2
1910 KINDERGARTEN 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 4 J1 H1 713 SEE SCHEDULE FOR SIZE 03/13/2017
1910A PK-2 TOILET 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J2 H2 S2 117 NOTES:
1. FOR ALL GLASS IN EXTERIOR DOORS, PROVIDE GLASS TYPE G-1. BID SET
2. FOR ALL GLASS IN INTERIOR DOORS, PROVIDE GLASS TYPE G-7.
A 3. ALL GLASS IN FIRE-RATED DOORS TO BE GLASS TYPE G-9. © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

OVERHEAD DOOR TRACK


SEE PLAN 3"X3"X1/4" GALVANIZED STEEL
ANGLES W/ 3/4" DIA.X 6" LONG
STUDS W/ 1" @ 16" O.C.
OVERHEAD COILING
DOOR HOUSING
INTERIOR FACE
MOUNTING

M M
GYP BD ON METAL STUD,

SEE PLAN
SEE PLAN
COORD. W/ WALL TYPES LINE OF OVERHEAD
METAL STUD SUPPLIER TO COILING DOOR HOUSING
PROVIDE METAL STUD ABOVE
HEADER AS NEEDED TO
SEE PLAN SUPPORT COILING DOOR
SEE S8 FOR SS
SIDESPLASH AT JAMBS

TUBE STEEL IF NEEDED IN


JAMB BY BI-FOLD DOOR ACOUSTICAL TILE
SOLID GROUT CELLS PER MANUFACTURER
STRUCTURAL NOTES CEILING, ALIGN WITH
VERTICAL BI-FOLD FRAME AND GLASS BOTTOM OF OVERHEAD
DOOR AND TRACK SYSTEM COILING DOOR HOUSING
L VERTICAL BI-FOLD
DOOR
L
ACOUSTICAL TILE CEILING,
VERIFY HEIGHT ON RCP

JAMB DETAIL - OH BIFOLD DOOR HEAD DETAIL - ROLLING COUNTER SHUTTER JAMB DETAIL - ROLLING COUNTER SHUTTER
J14 1 1/2" = 1'-0" H15 1 1/2" = 1'-0" J15 1 1/2" = 1'-0"
VERTICAL BI-FOLD
DOOR SEE PLAN

CONCRETE U-LINTEL.
REF: STRUCTURAL DRAWINGS

K MOTOR BOX AND HEADER FRAME


OVERHEAD DOOR TRACK
3"X3"X1/4" GALVANIZED STEEL
K
SYSTEM BY BI-FOLD DOOR
OVERHEAD COILING DINING ANGLES W/ 3/4" DIA.X 6" LONG
MANUFACTURER HEAD HEIGHT DOOR HOUSING STUDS W/ 1" @ 16" O.C.
FOR 8'-0" DOOR ELECTRIC, VERTICAL BI-FOLD DOOR WITH INTERIOR FACE
FULL PERIMETER SEALS AND GLASS LITES MOUNTING

STEEL BOTTOM PLATE


CONNECTED TO STEEL BEAM
IN WALL ABOVE
SOLID GROUT CELLS PER
REF: STRUCTURAL
STRUCTURAL NOTES
LINE OF OVERHEAD
COILING DOOR HOUSING

SEE PLAN
ABOVE

SERVING CONCRETE U-LINTEL.


J 1403 REF: STRUCTURAL DRAWINGS
SEE S4 FOR SS
J
SIDESPLASH AT JAMBS

ACOUSTICAL TILE
CEILING, ALIGN WITH
BOTTOM OF OVERHEAD
COILING DOOR HOUSING
BORROWED LIGHT DETAILS

HEAD DETAIL - OH BI-FOLD DOOR HEAD DETAIL - ROLLING COUNTER SHUTTER JAMB DETAIL - ROLLING COUNTER SHUTTER COORD. W/ WALL

H14 1 1/2" = 1'-0" H12 1 1/2" = 1'-0" J12 1 1/2" = 1'-0"


THICKNESS
GLAZING (SEE
H H

www.grimmandparker.com
2 1/4" OR AS NOTED 2 1/4"
GROUT SOLID FRAME ELEVATIONS

1 15/16"
GLAZING (SEE CORRIDOR FOR GLASS TYPES)

11720 Beltsville Drive

Calverton, MD 20705
FRAME ELEVATIONS DOOR

W/ WALL THICKNESS
6 3/4" OR 8 3/4" FOR GLASS TYPES)

Tel: 301.595.1000
CORRIDOR

COORD.
COORD W/ WALL

5/8"
2 15/16"
GROUT SOLID THICKNESS 5/8" GLASS ROOM INTERIOR, U.O.N.
STOP, TYP. CORRIDOR

Suite 600
SEE PLAN FOR DOOR

2"
5/8" 2" 5/8"

1 1/2"
LOCATION

W/WALL THICKNESS
COORD W/ WALL
6 3/4" OR 8 3/4"

THICKNESS

5/8"
GLASS STOP, TYP.

COORD.
SEE FRAME TYPE
DOOR ROOM INTERIOR, U.O.N.
GLASS STOP, TYP. SEE PLAN FOR DOOR LOCATION
BRICK FACE BOTTOM PLATE
RE: STRUCTURAL
FLASHING 2" INTO CMU UNDER WALL REINFORCMENT

1 1/2"
G G
TRANSOM JAMB DETAIL

5/8"
CAVITY MORTAR CONTROL SEALANT TYP. GLAZING (SEE
2-1/2" FOAMED-IN-PLACE POLYURETHANE INSULATION ON CMU BOTH SIDES FRAME ELEVATIONS
FOR GLASS TYPES)
H3 1 1/2" = 1'-0" J5 1 1/2" = 1'-0"
3-1/2" FOAMED-IN-PLACE POLYURETHANE INSULATION AT OVERLAP. GROUT SOLID
CUT SMOOTH AS REQUIRED TO MAINTAIN 3-1/2". PROVIDE 1/2" GLAZING (SEE
TERMINATION BAR AT AIR BARRIER TRANSITION 2 15/16" COORD. 1 1/2" FRAME ELEVATIONS
CAVITY MORTAR CONTROL IN GAP TO FACE VENEER

5/8"
MEMBRANE AND FLASHING HEAD 1 15/16" 1 15/16" ROOM INTERIOR, U.O.N. FOR GLASS TYPES)
SOLID GROUT SLOPE AT FLASHING BED W/ WALL THICKNESS
4"

CORRIDOR
CONTINUOUS AIR BARRIER TRANSITION COORD. W/ WALL THICKNESS SEE H1 & H2 FOR WALL

1 15/16"
MEMBRANE FROM SEALANT AT BACK OF HM GROUT SOLID 2" GLAZING (SEE CORRIDOR
DETAILS

1 15/16"
FRAME SPRAY FOAM INSULATION FRAME ELEVATIONS
HEAD DETAIL JAMB DETAIL

W/ WALL THICKNESS
FOR GLASS TYPES)

COORIDNATE W/ WALL
H10 J10

COORD.
1 1/2" = 1'-0" 1 1/2" = 1'-0"

THICKNESS
CAVITY VENT AT 24" O.C.

F GALVANIZED STEEL ANGLE. AT OPENINGS GREATER THAN


SEE PLANS F

1 1/2"
4" OR 6" 5/8" GYP. BD. ON METAL 5/8"
6'-4" ANCHOR BOLT ANGLE TO U-LINTEL BACKUP
4"

STUDS 5/8" 1" 5/8"

1 1/2"
3" REF: STRUCTURAL GLASS STOP, TYP.
SOLID GROUT WALLS INFILL WITH BATT GLASS STOP, TYP. ROOM INTERIOR, U.O.N.
1-1/2" RIGID INSULATION WITH AND REINFORCE PER SEE PLAN FOR DOOR LOCATION
1 15/16" FILL VOIDS AT FRAME WITH ROCKWOOL INSULATION
GP# 21553
5/8"

SLOPED TOP. FIT TIGHT IN CAVITY STRUCTURAL ROOM INTERIOR, U.O.N.


1 15/16" SEALANT AND BACKER ROD AT FULL PERIMETER DRAWINGS 2 LAYERS 1/2" GYP. BD.
10" SOLID PRE-ENGINEERED CMU LINTEL 8 3/4" GROUT HM FRAME SOLID ON METAL STUDS
9/16" 9/16"
CEILING WHERE APPLICABLE INTERMEDIATE MULLION HEAD/JAMB/SILL DETAIL
HEAD REINF. BY HM MANUFACTURER
SEALANT BOTH
SEE RCP
CONT. SEALANT
J4 1 1/2" = 1'-0" J3 1 1/2" = 1'-0"
1' - 3 1/4" SIDES BOTH SIDES

5/8"
2"
WHERE GLASS OCCURS,
PROVIDE GLASS STOP ON
1 15/16" 1 15/16"
ROOM SIDE. REF: PLANS AND
E HEAD DETAIL - EXTERIOR
GROUT FRAME
SOLID COORD. W/
FRAME ELEVATIONS FOR E

5/8"
LOCATIONS
H9 1 1/2" = 1'-0" 1 15/16"
6 3/4"
1 15/16" WALL THICKNESS
TYPICAL INTERIOR PARTITION DETAILS
3-1/2" CONTFOAMED-IN-PLACE
STAINLESS STEEL ENDSPLASH 1-1/2" RIGID INSULATION OVERLAP
DINING (EACH SIDE)
POLYURETHANE INSULATION
TIGHT TO RIGID INSULATION SPRAY FOAM INSULATION 2" MIN.
HEAD DETAIL HEAD DETAIL
ROLLING SHUTTER DOOR AND
FRAME BRICK FACE
SEALANT BOTH SIDES
2" X 2" SOLID GROUT
H5 1 1/2" = 1'-0" H4 1 1/2" = 1'-0"
1/2" 45 DEG.

GYP BD ON METAL STUD,

CITY OF BALTIMORE, MARYLAND


3"

COORD. W/ WALL TYPES

SEE FRAME TYPE


CMU WALL. REF:

HEAD, SILL AND JAMB DETAILS


JAMB ANCHOR 9/16" 9/16" CONT. SEALANT
TREATED WOOD BLOCKING PLANS FOR TYPE
SOILD GROUT WALLS AND BOTH SIDES CONCRETE U-LINTEL,
JAMB ANCHOR JAMB ANCHOR 9/16"
D 9/16"
D
1 15/16"
SEE PLAN

SOLID CMU AND COLLAR JOINT. REINFORCE PER METAL STUD TRACK RE: STRUCTURAL
1 15/16"

5/8"
8 3/4"

2"
CUT TO ALLOW FOR 1" RIGID STRUCTURAL DRAWINGS
4"

HOLABIRD ACADEMY PK-8


5/8"

1 15/16"
INSULATION 5/8"

9/16"
GROUT SOLID SEALANT TYP.
WALL THICKNESS

11 5/8"
9 5/8"

1 15/16" 1 15/16" BOTH SIDES


COORD. WITH

GROUT FRAME SOLID


DOOR
1"
1 15/16"

GROUT SOLID
COORD. W/

6 3/4"
2"

STAINLESS STEEL

5/8"
1 15/16" 1 15/16"
SEE PLANS

CLOSURE ANGLE, FULL WALL THICKNESS


1 15/16"

WIDTH OF OPENING (BY 10" X 16" SOLID CMU W/ 1"


4 3/4"
8 3/4"

5/8"

1 15/16"
KITCHEN EQUIP. CONTR.) BULLNOSE AT OPENINGS TYPICAL COORD. W/ WALL THICKNESS
SOLID CMU UNDER 2 1/2" CONT. FOAMED-IN- CONTINUOUS AIR BARRIER GROUT FRAME SOLID
PLACE POLYURETHANE TRANSITION TAPE FROM SEALANT AT
HEAD DETAIL HEAD DETAIL
2"

SEE PLAN COUNTERTOP GROUT FRAME SOLID

COUNTER-TOP TRIM
INSULATION ON CMU BACKUP BACK OF HM FRAME JAMB TO
OVERLAP 4" BEHIND SPRAY FOAM
INSULATION
4"
SEALANT BOTH SIDES
SEALANT BOTH SIDES H2 1 1/2" = 1'-0" H1 1 1/2" = 1'-0"
C - SEE KITCHEN DWGS 5/8" 5/8" BULLNOSE CMU TYPICAL C
SILL DETAIL - ROLLING COUNTER SHUTTER JAMB DETAIL - EXTERIOR INTERMEDIATE MULLION JAMB DETAIL JAMB DETAIL WHERE GLASS OCCURS,
S4 J9 J8 J7 J6 PERP. WALL WHERE

COORD. W/ WALL THICKNESS


SHOWN ON PLANS WALL WHERE PROVIDE GLASS STOP ON
1 1/2" = 1'-0" S8 SIMILAR BUT METAL STUD AND GYP. BOARD WALL, SEE PLAN FOR DIMENSIONS 1 1/2" = 1'-0" 1 1/2" = 1'-0" 1 1/2" = 1'-0" 1 1/2" = 1'-0" 2" MIN.
SHOWN IN PLAN ROOM SIDE. REF: PLANS AND
PACK FRAME W/ FRAME ELEVATIONS FOR
SOUND INSULATION SEALANT BOTH SIDES LOCATIONS
VENTED RUBBER

9/16"
2" SCHEDULED DOOR
DOOR BASE BEYOND DATE DESCRIPTION

1 15/16"
9/16"
1/4" THICK ALUM. UON 2/08/17 BID SET

COOR W/WALL THICKNESS


HM FRAME
COVER PLATE W/

1 15/16"
ANCHOR TO SLAB BEVELED EDGES

4 7/8" OR 7 1/4"

6" OR 8 3/8"
(DO NOT ANCHOR TO DOOR
7" 4" WOOD FLOORING
WOOD BASE FLOOR) HM FRAME JAMB ANCHOR

1 15/16"
2 LAYERS 3/4" FRT PLYWOOD,

1 15/16"
1/4" MAX.

B FINISH FLOOR PER STAGGER JOINTS WALL BEYOND B

9/16"
SCHEDULE HM FRAME
VAPOR BARRIER

9/16"
BBT OR SCHEDULED EXPANSION JOINT COVER CARPET TO VCT ADAPTER, DOOR MARBLE THRESHOLD TILE TO CONC. ADAPTER 5/8" GROUT FRAME SOLID
FLOORING DOOR CENTERLINE ALIGNS WITH SLOPE 1:2 MAX, CENTERLINE ALIGNS WITH 2" 5/8" SOLID GROUT AT JAMBS.
3 1/8"

DOOR
CENTERLINE OF DOOR WHERE TYP. BOTH SIDES CENTERLINE OF DOOR WHERE SCHEDULED GYP BD WALL 5/8" x 5/8" GLAZING REF: STRUCTURAL
SEE FINISH
TRANSITION OCCURS AT DOOR TRANSITION OCCURS AT DOOR STOP AT SCHEDULED DRAWINGS FOR ADDITIONAL
1"

1/2" SCHEDULE FOR CONT. SEALANT


THRESHOLD TILE FLOORING, SEE THRESHOLD GLAZING LOCATIONS GROUTING REQUIREMENTS
1/4"
1/4"

SOLID WOOD BLOCKING VCT TILE, SEE FLOOR FINISH BOTH SIDES
FINISH SCHEDULE SEE FINISH
AT ALL DOORWAYS 2" FINISH SCHEDULE CARPET SCHEDULE CONC.
COMPRESSIBLE SAFING
JAMB DETAIL JAMB DETAIL
COMPRESSIBLE JOINT FILLER

A-3.3
MAX.
1/2"

SAW CUT SILL/LINTEL AND GRIND


SMOOTH, COORDINATE EXACT SIZE OF
RECESS WITH EXPANSION JOINT COVER
J2 1 1/2" = 1'-0" J1 1 1/2" = 1'-0"
GYM WOOD FLOOR THRESHOLD SILL AT EXPANSION JOINT SILL MARBLE THRESHOLD TRANSITION STRIP 03/13/2017
S6 1 1/2" = 1'-0" S5 1 1/2" = 1'-0" S3 1 1/2" = 1'-0" S2 1 1/2" = 1'-0" S1 1 1/2" = 1'-0" BID SET
A © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

CURTAINWALL ELEVATIONS STOREFRONT AND


87' - 0" CURTAINWALL NOTES
NOTES APPLY TO ALL FRAME ELEVATION SHEETS
3' - 0" 3' - 0" 6' - 0" 3' - 0" 3' - 0" 6' - 0" 3' - 0" 3' - 0" 6' - 0" 3' - 0" 3' - 0" 6' - 0" 3' - 0" 3' - 0" 6' - 0" 3' - 0" 3' - 0" 6' - 0" 3' - 0" 3' - 0" 6' - 0" 3' - 0" 2' - 9 1/2" 6' - 0" 2 1/2" 6' - 0" 2' - 11 3/8" 4"

2 1/2" 2 1/2" 1. VERIFY MASONRY & ROUGH OPENINGS, INCLUDING BUT NOT LIMITED TO STRUCTURAL LINTEL

2 1/2"
2 1/2"
LOCATIONS, PRIOR TO FABRICATION.
2. COORDINATE REQUIRED TOLERANCES IN ALL DIMENSIONS NEEDED TO MANUFACTURE AND INSTALL
WINDOWS, STOREFRONT AND CURTAINWALL INCLUDING SUBFRAMES, AS REQUIRED.
2' - 1" G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 G-2 3. CONTINUOUSLY SEAL ALL SIDES OF STOREFRONT AND SUBFRAMES ABUTTING DISSIMILAR MATERIALS

2 1/2"
AT JAMBS, HEADS, AND SILLS, TYPICALLY.
4. PROVIDE APPROPRIATE ANCHORAGE SYSTEM FOR ALL CONDITIONS TO SECURE WINDOWS IN
M ROUGH OPENINGS. PROVIDE SUBFRAMING AS SHOWN ON DETAILS AND/OR SPECIFIED. M
2' - 1"

G-1 G-4 G-1 G-1 G-1 G-1 G-5 G-1 G-1 G-1 G-4 G-1 G-5 G-1 G-1 G-4 G-1 G-1 G-5 G-1 G-1 G-1 G-1 G-1 G-5 G-1 G-1 G-1 G-4 5. SEE HEAD, JAMB, AND SILL DETAIL SHEET FOR MORE INFORMATION.
2 1/2"

6. PROVIDE FOR THERMAL EXPANSION AT ALL STOREFRONT SYSTEMS.


7. COORDINATE FRAMES WITH PLAN WHEN MORE THAN ONE CONSTRUCTION DETAIL IS REFERENCED.
8. AS REQUIRED FOR DESIGN LOADING, WINDOW MANUFACTURER SHALL PROVIDE MULLION
11' - 4"

2' - 1"

G-5 G-1 G-1 G-1 G-1 G-4 G-1 G-1 G-1 G-5 G-1 G-1 G-1 G-4 G-1 G-1 G-1 G-4 G-1 G-1 G-1 G-5 G-1 G-1 G-1 G-4 G-1 G-1 G-1 REINFORCING AND VERTICAL EXTENSIONS UP TO STRUCTURE ABOVE (ATTACHMENT TO STRUCTURE
2 1/2"

BY MANUFACTURER). SEE SECTIONS AND DETAILS FOR ADDITIONAL WORK RELATING TO


STOREFRONT SYSTEM.
9. IDENTIFICATION OF OPENING TYPES AS "CURTAINWALL" OR "STOREFRONT" IS BASED ON SYSTEM
REQUIREMENTS OF A PARTICULAR MANUFACTURER. CONTRACTOR IS TO DETERMINE BEST
APPLICATION OF PROPOSED MANUFACTURE AND SYSTEM BASED ON PERFORMANCE
4' - 0 1/2"

G-1 G-1 G-1 G-5 G-1 G-1 G-1 G-4 G-1 G-1 G-1 G-4 G-1 G-1 G-1 G-5 G-1 G-1 G-1 G-4 G-1 G-1 G-1 G-4 G-1 G-1 G-1 G-5 G-1 REQUIREMENTS, SIZE OF OPENING, AND INSTALLATION CONDITION.
10. OVERALL DIMENSIONS OF STOREFRONT ARE APPROXIMATE. CONTRACTOR TO COORDINATE
REQUIRED TOLERANCES IN ALL DIMENSIONS NEEDED TO MANUFACTURE AND INSTALL STOREFRONT,
INCLUDING SUBFRAMES, AS REQUIRED. CONTRACTOR SHALL VERIFY ACTUAL DIMENSIONS IN THE
FIELD WITH THOSE SHOWN ON ALL DRAWINGS, INCLUDING DETAILS SHOWN ON OTHER SHEETS,
L L
2 1/2"

PRIOR TO FABRICATION.

2' - 1"
G-1 G-1 G-5 G-1 G-1 G-1 G-1

2 1/2"
11. PROVIDE MANUAL SHADES AT ALL EXTERIOR WINDOWS, UNLESS OTHERWISE NOTED.
REFER TO WALL SECTIONS FOR LATERAL 12. COORDINATE STOREFRONT AND CURTAINWALL SYSTEMS WITH AIR BARRIER TRANSITION MEMBRANE
BRACING LOCATIONS BY CW MANU. SYSTEM AND MANUFACTURER-RECOMMENDED DETAILS FOR A COMPLETE AIR BARRIER SYSTEM.
PROVIDE ELECTRONICALLY OPERATED SHADE SYSTEM AT WINDOWS 13. PROVIDE TRANSLUCENT ROLLER SHADES AT ALL EXTERIOR OPENINGS UNLESS NOTED OTHERWISE.

29' - 4"
2' - 1"
G-4 G-1 G-1 G-1 G-4 G-1 G-1

2 1/2"
NOTE 2 DASHED LINE INDICATED ROUTING OF
CONDUITS FROM ADJACENT WALL WITHIN
HORIZONTAL CW MULLION, IE: EXIT LIGHTS.
COORDINATE WITH MEP DRAWINGS AND

3' - 5"
RE: INTERIOR ELEVATIONS G-8 G-8 G-8 G-8 G-8 G-8 G-8

2 1/2"
18' - 0"

2' - 1"
G-1 G-1 G-1 G-1 G-1 G-1 G-1

2 1/2"
K K
HOLLOW METAL FRAME NOTES

5' - 11 1/2"
1. CONTRACTOR SHALL VERIFY ALL MASONRY AND ROUGH OPENINGS WITH HOLLOW METAL FRAME

7' - 6" DOOR

7' - 6" DOOR


G-1 G-1 G-1 G-1 SIZES.
2. CONTRACTOR TO COORDINATE REQUIRED TOLERANCES IN ALL DIMENSIONS NEEDED TO
MANUFACTURER AND INSTALL HOLLOW METAL FRAMES. VERIFY ACTUAL DIMENSIONS IN THE FIELD
WITH THOSE SHOWN ON ALL DRAWINGS, INCLUDING DETAILS SHOWN ON OTHER SHEETS.

2 1/2"
3. CONTINUOUSLY SEAL ALL SIDES OF HOLLOW METAL FRAMES ABUTTING DISSIMILAR MATERIALS AT
JAMBS, HEADS, AND SILLS, TYPICALLY (EXCEPT AT DOOR SILLS UNLESS OTHERWISE NOTED).

1' - 1 1/2"
4. TYPICAL WIDTH OF RETURNS ON HOLLOW METAL FRAMES IS 1 15/16" AT HEADS, JAMBS, AND SILLS.
G-8 G-8 G-8 G-8
FIRST FLOOR CENTER SECTION OF FRAME VARIES IN WIDTH WITH RESPECTIVE WALL TYPE. SEE PLANS.
5. SEE HEAD, JAMB, AND SILL DETAIL SHEET FOR MORE INFORMATION.
0' - 0"

2 1/2"
3' - 0" 2 1/2" 6' - 0" DOOR EQ 6' - 0" DOOR EQ 6' - 0" DOOR 2' - 11 3/8" 4" 6. FILL ALL HOLLOW METAL (HM) FRAMES ABUTTING MASONRY WITH GROUT. FILL INTERMEDIATE
MEMBERS AS SHOWN IN DETAILS (TYPICAL).
J 12' - 9 5/8"
31' - 1 3/8" 2 1/2"
J
10' - 8"
4" EQ 2 1/2" EQ 2 1/2" EQ 2 1/2" CW1A
1' - 11 1/4" 7' - 0" DOOR 1' - 8 3/4"
NOTE 1, NOTE 5

2' - 4 3/4"
2' - 6"

G-2 G-2 G-2 G-2 G-2 G-2 6' - 5"


6' - 8"
EQ 2 1/2" EQ 2 1/2" 6' - 0" 2 1/2"
LOUVER ELEVATION

2' - 2 3/8"
2 1/2" 2 1/2"
2' - 3 1/2"

G-1 G-5 G-1 G-1 G-1 G-1

2' - 5 1/8"
2' - 4 1/4"
2' - 3 1/2"

G-1 G-1 G-1 8' - 0"

2' - 9"
G-1 G-1 G-4 G-1 G-1
H H

www.grimmandparker.com
G-1

11720 Beltsville Drive

Calverton, MD 20705
2' - 5"
G-1

Tel: 301.595.1000
4' - 2 3/4"

4' - 2"
10' - 3 3/8"
4' - 3"

G-5 G-1 G-1 G-1 G-1 G-1 G-1 G-1


REFER TO WALL
SECTIONS FOR
7' - 10 1/4"
LATERAL BRACING

2' - 5"
LOCATIONS BY CW G-1

Suite 600
8' - 0"
MANU.

1' - 4" 2' - 1 3/4"

2' - 1 3/4"
2' - 2 1/4"
2' - 3 1/2"

G-1 G-1 G-2 G-2 G-2


3' - 5 3/4"
G-1 G-4 G-1

2' - 5"
G-1
2' - 3 1/2"
29' - 4"

29' - 4"
G-1 G-1 G-5
4' - 1 3/4"

4' - 0"
G-1 G-1 G-2 G-2 G-2
G G

2' - 5"
G-1

8"
24' - 8"

24' - 8"
4' - 0"
3' - 7 1/2"

G-8 G-8 G-8 3' - 7 1/4" 2 3/8"


2 3/8"

2' - 5"
2' - 0"
G-2 G-2 G-2 G-1
2' - 0"

G-1 G-1

11 7/16" 2 3/8"
2' - 3 1/2"

2' - 6"

2' - 4"
2' - 3"

G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-9

1'2 -3/8"
2' - 3 1/2"

G-1 G-1 G-1


12' - 0"

3' - 11 5/8"

8' - 8"
10' - 2 1/2"

4' - 0"
G-1 G-1 G-9

10' - 0"
GLASS TYPE KEY

7' - 6" DOOR


7' - 6" DOOR

2 3/8"
F F
DOOR
7' - 6"
3' - 10 1/2"

19' - 4"
G-1 G-1 G-1

2 3/8" 1' - 11 7/16"


1' - 1 1/2" 2' - 2" G-9 G-1 1" INSULATING GLASS; CONSISTING OF
1' - 1 1/2"

1/4" TEMPERED EXTERIOR LITE WITH LOW E COATING ON SECOND SURFACE


GP# 21553
1' - 4"

1' - 4"
G-8 G-8 G-8 G-8 G-8 1/2" AIR SPACE
FIRST FLOOR 1/4" TEMPERED INTERIOR LITE
0' - 0"
2 1/2"

G-2 1" INSULATING GLASS; CONSISTING OF


2 1/2"

CW1B CW2 CW3 CW4 CW5 1/4" TEMPERED EXTERIOR LITE W/ LOW E COATING ON SECOND SURFACE
1/2" AIR SPACE,
NOTE 1 NOTE 1 NOTE 2 NOTE 3 1/4" TEMPERED INTERIOR LITE WITH SPANDREL COATING ON THIRD SURFACE
20' - 0"
NOTE 6
G-3 1" INSULATING GLASS; CONSISTING OF
8' - 0"
E 2 3/8" EQ 2 3/8" EQ 2 3/8"
1/4" TEMPERED EXTERIOR LITE WITH LOW E COATING ON SECOND SURFACE
1/2" AIR SPACE
E
1/4" HEAT STRENGTHENED LAMINATED GLASS W/ HORIZONTAL FRIT ON THIRD
2 3/8"

SURFACE
L1
G-4 1" INSULATING GLASS; CONSISTING OF
2' - 0"

2 3/8"

12' - 0" G-11 G-11

FRAMING ELEVATIONS - CURTAINWALL


1/4" TEMPERED TINTED EXTERIOR LITE
2 3/8" EQ 4' - 0" EQ 1/2" AIR SPACE
1/4" TEMPERED INTERIOR LITE WITH LOW E COATING ON THIRD SURFACE
6' - 8"

G-5 1" INSULATING GLASS; CONSISTING OF


4' - 0 7/8"

G-11 G-11

CITY OF BALTIMORE, MARYLAND


1/4" TEMPERED TINTED EXTERIOR LITE
G-11 G-11 G-11 1/2" AIR SPACE
1/4" TEMPERED INTERIOR LITE WITH LOW E COATING ON THIRD SURFACE
2 3/8"

D D
G-6 1/4" THICK CLEAR FLOAT GLASS

HOLABIRD ACADEMY PK-8


3' - 4"

G-7 1/4" THICK CLEAR TEMPERED SAFETY GLASS

G-8 INSULATED METAL PANEL INFILL BY STOREFRONT/CURTAINWALL MANUFACTURER


CW6 CW7
G-9 5/16" THICK LAMINATED FIRE RATED GLASS
NOTE 3 NOTE 3
G-10 1/8" THICK FIRE RATED POLYCARBONATE SHEET
NOTE 6 NOTE 6
G-11 2 - 5/16" FIRE RATED INSULATING GLASS; CONSISTING OF

1/4" TEMPERED EXTERIOR LITE WITH LOW E COATING ON SECOND SURFACE


1/2" AIR SPACE
1 9/16" FIRE RESISTANT GLAZING INTERIOR LITE
C STOREFRONT ELEVATIONS C
20' - 0"

8' - 0" 12' - 0" 4' - 0"


3' - 8" 2"
4' - 0"
3' - 8" 2" 3' - 9"
12' - 0"
3' - 10" 3' - 9" 2" 2" 3' - 0" 2" 4' - 7"
18' - 0"
2" 4' - 10" 2" 4' - 9" 2"
2" 3' - 9"
8' - 0"

3' - 9" 2"


NUMBERED REMARKS
2" 3' - 9" 2" 3' - 9" 2" 3' - 7" 2" 3' - 10" 2" 3' - 7" 4" 2" 2" 2"
2" 2" DOOR 2" DOOR NOTE 1: PROVIDE NO TRANSLUCENT ROLLER SHADES AT THIS FRAME OPENING.
2"

2"

2"
2"

4" 4' - 0"


2"

2"
2"

2"
DATE DESCRIPTION
4" 3' - 4" 4" NOTE 2: PROVIDE ELECTRIC MOTOR TRANSLUCENT ROLLER SHADES AT THIS FRAME OPENING.
2" 2' - 0"

2' - 0"

2' - 0"
2' - 2"

2' - 2"

2' - 2"
2' - 4"
2' - 8"

G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1
NOTE 3: PROVIDE PRE-FINISHED ALUMINUM SUNSHADES (HORIZONTAL LOUVERS IN VERTICAL FRAME) AS
SHOWN ON ELEVATIONS
4' - 8"

G-1
2"

2"
2"

2"
2"

NOTE 4: PROVIDE PRE-FINISHED ALUMINUM SUNSHADES, 24" PROJECTION HORIZONTALLY, AS SHOWN ON


2"

7' - 4"
4"

ELEVATIONS
3' - 10"

3' - 10"
8' - 8"

4' - 0"

8' - 8"
4' - 0"
B G-1 G-1 G-1
B
4' - 0"

G-1 G-1 G-1 G-1 G-1 G-1


10' - 0"

10' - 0"

10' - 0"
10' - 0"

10' - 0"
G-1
2' - 0"
2' - 8"

NOTE 5: NOT USED

7' - 8" DOOR


G-1 G-1 G-1 G-1 G-1
7' - 6" DOOR
2"

2"
G-1
2' - 2"

2"

2"
7' - 4"

G-1 NOTE 6: AT OPENINGS IN 2 HOUR FIREWALL, PROIVDE 2 HOUR FIRE RATED CURTAINWALL SYSTEM.
2' - 0" 2"

SEE BLDG ELEV


4"

2' - 0"

2' - 0"
G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1
VARIES

3' - 4"

2"
2"
3' - 4"

2' - 8"

1' - 2"
1' - 4"

1' - 4"
2"

G-8 G-8 G-8 G-8 G-8 G-8

2"
A-3.6
0"
2"

2"

SF1 SF2 SF3 SF4 SF5 SF6 SF7 SF8 SF2 SF9

NOT USED NOTE 3 03/13/2017


NOTE 3 NOTE 1 NOTE 1 NOTE 3 NOTE 4
BID SET
A © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

STOREFRONT ELEVATIONS 15' - 2" 24' - 8 1/2"


STOREFRONT AND
6" 4' - 7" 4' - 7" 4' - 8" 6" 6" 3' - 5" 2" 3' - 5" 3' - 5 1/4" 3' - 5 1/4" 3' - 2" 2" 3' - 2" 3' - 0" 2"

1' - 0" 3' - 5" 3' - 5"


20' - 0"
4' - 2" 4' - 0"
DEFLECTION TRACK
4' - 0" 4" 4' - 5" 2"
14' - 5 1/2"
4' - 5 1/4" 2" 4' - 5 1/4"
METAL PANEL INFILL

6" 6" 8"


5' - 1 1/2"
3' - 9 1/2"
2" 2" 2" 2" 2" 2" DOOR CURTAINWALL NOTES
NOTES APPLY TO ALL FRAME ELEVATION SHEETS

2"
2"
16' - 0"

2"
2"
2" 3' - 9" 2" 3' - 10" 2" 3' - 10" 2" 3' - 9" 2" 1. VERIFY MASONRY & ROUGH OPENINGS, INCLUDING BUT NOT LIMITED TO STRUCTURAL LINTEL
LOCATIONS, PRIOR TO FABRICATION.

2' - 3"
G-1 G-1 G-1 G-1 G-1 G-1 2. COORDINATE REQUIRED TOLERANCES IN ALL DIMENSIONS NEEDED TO MANUFACTURE AND INSTALL

4' - 0"

4' - 0"

3' - 8"
4' - 0"

4' - 0"

3' - 8"
G-8
ALIGN G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1 WINDOWS, STOREFRONT AND CURTAINWALL INCLUDING SUBFRAMES, AS REQUIRED.
3. CONTINUOUSLY SEAL ALL SIDES OF STOREFRONT AND SUBFRAMES ABUTTING DISSIMILAR MATERIALS

2"
G-1 G-1 G-1

2' - 2"
2' - 3"
G-1 G-1 G-1 G-1 G-1 G-1 G-1 AT JAMBS, HEADS, AND SILLS, TYPICALLY.
4. PROVIDE APPROPRIATE ANCHORAGE SYSTEM FOR ALL CONDITIONS TO SECURE WINDOWS IN
M M
1' - 0"

G-1

8' - 4"
ROUGH OPENINGS. PROVIDE SUBFRAMING AS SHOWN ON DETAILS AND/OR SPECIFIED.

2"
5. SEE HEAD, JAMB, AND SILL DETAIL SHEET FOR MORE INFORMATION.

2"

2"
SF10 6. PROVIDE FOR THERMAL EXPANSION AT ALL STOREFRONT SYSTEMS.

12' - 0"

12' - 0"

12' - 0"

12' - 0"

12' - 0"
2' - 6" 2' - 6"

4' - 4"
7. COORDINATE FRAMES WITH PLAN WHEN MORE THAN ONE CONSTRUCTION DETAIL IS REFERENCED.

3' - 10"
G-1 G-1 G-1
4' - 2"

4' - 2"
G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1 8. AS REQUIRED FOR DESIGN LOADING, WINDOW MANUFACTURER SHALL PROVIDE MULLION

10' - 0"
10' - 0"
8' - 0" DOOR
G-1 G-1 REINFORCING AND VERTICAL EXTENSIONS UP TO STRUCTURE ABOVE (ATTACHMENT TO STRUCTURE
ALIGN

2"
8' - 0"

8' - 0"

8' - 0"

8' - 0"
BY MANUFACTURER). SEE SECTIONS AND DETAILS FOR ADDITIONAL WORK RELATING TO

2"
STOREFRONT SYSTEM.
9. IDENTIFICATION OF OPENING TYPES AS "CURTAINWALL" OR "STOREFRONT" IS BASED ON SYSTEM
1' - 4" 1' - 1" 11"

G-1 G-1
G-1 G-1 G-1 G-1 G-1 G-1 G-1 G-1 REQUIREMENTS OF A PARTICULAR MANUFACTURER. CONTRACTOR IS TO DETERMINE BEST

3' - 4"

3' - 4"

3' - 4"
APPLICATION OF PROPOSED MANUFACTURE AND SYSTEM BASED ON PERFORMANCE

3' - 4"
REQUIREMENTS, SIZE OF OPENING, AND INSTALLATION CONDITION.
G-8 G-8 G-8 G-8 G-8 G-8 G-8 10. OVERALL DIMENSIONS OF STOREFRONT ARE APPROXIMATE. CONTRACTOR TO COORDINATE
REQUIRED TOLERANCES IN ALL DIMENSIONS NEEDED TO MANUFACTURE AND INSTALL STOREFRONT,

2"

2"

0"
20' - 0" INCLUDING SUBFRAMES, AS REQUIRED. CONTRACTOR SHALL VERIFY ACTUAL DIMENSIONS IN THE

2"
FIELD WITH THOSE SHOWN ON ALL DRAWINGS, INCLUDING DETAILS SHOWN ON OTHER SHEETS,
L 11.
PRIOR TO FABRICATION.
PROVIDE MANUAL SHADES AT ALL EXTERIOR WINDOWS, UNLESS OTHERWISE NOTED.
L
SF10 SF12A SF12B SF12C SF12D SF13 12. COORDINATE STOREFRONT AND CURTAINWALL SYSTEMS WITH AIR BARRIER TRANSITION MEMBRANE
SYSTEM AND MANUFACTURER-RECOMMENDED DETAILS FOR A COMPLETE AIR BARRIER SYSTEM.
13. PROVIDE TRANSLUCENT ROLLER SHADES AT ALL EXTERIOR OPENINGS UNLESS NOTED OTHERWISE.

6"
22' - 0"
2" 4' - 2 1/2" 2" 4' - 2 1/4" 2" 4' - 2 1/2" 2" 4' - 2 1/4" 2" 4' - 2 1/2" 2"

2"
SF12D
SF12B METAL PANEL INFILL
14' - 5 1/2" 24' - 2 1/2"

2' - 0"
5' - 5 1/4"
G-3 G-3 G-3 G-3 G-3
6"

K K

6' - 8"
HOLLOW METAL FRAME NOTES

2"
2 1/2"

4' - 2"
SF12C G-3 G-3 G-3 G-3 G-3
3' - 11 1/2"

SF12B 1. CONTRACTOR SHALL VERIFY ALL MASONRY AND ROUGH OPENINGS WITH HOLLOW METAL FRAME
5' - 4"

METAL PANEL INFILL SIZES.


2. CONTRACTOR TO COORDINATE REQUIRED TOLERANCES IN ALL DIMENSIONS NEEDED TO
MANUFACTURER AND INSTALL HOLLOW METAL FRAMES. VERIFY ACTUAL DIMENSIONS IN THE FIELD

2"
WITH THOSE SHOWN ON ALL DRAWINGS, INCLUDING DETAILS SHOWN ON OTHER SHEETS.
8"

16' - 0"
3. CONTINUOUSLY SEAL ALL SIDES OF HOLLOW METAL FRAMES ABUTTING DISSIMILAR MATERIALS AT
JAMBS, HEADS, AND SILLS, TYPICALLY (EXCEPT AT DOOR SILLS UNLESS OTHERWISE NOTED).
2"
4. TYPICAL WIDTH OF RETURNS ON HOLLOW METAL FRAMES IS 1 15/16" AT HEADS, JAMBS, AND SILLS.
6"

SF12A CENTER SECTION OF FRAME VARIES IN WIDTH WITH RESPECTIVE WALL TYPE. SEE PLANS.
5. SEE HEAD, JAMB, AND SILL DETAIL SHEET FOR MORE INFORMATION.

2"
6. FILL ALL HOLLOW METAL (HM) FRAMES ABUTTING MASONRY WITH GROUT. FILL INTERMEDIATE
MEMBERS AS SHOWN IN DETAILS (TYPICAL).

24' - 8"
J 12' - 8" 12' - 3 3/4"
J

3' - 10"
G-1 G-1 G-1 G-1
2" 6' - 0" 4" 6' - 0" 2" EQ 2" 7' - 0" 2" EQ 2"
2"

6' - 8"
2"

2"

2"

18' - 0"
2' - 4"
G-1 G-1 G-1 G-1
2' - 0"
G-7 G-7 G-7 G-7 G-7

2"
14' - 0"
2"
9' - 10"
9' - 8"

4' - 7"
9' - 4"

G-7 G-7
7' - 0" DOOR

7' - 0" DOOR

7' - 4"
H H
2"

www.grimmandparker.com
2' - 1"

11720 Beltsville Drive

Calverton, MD 20705
G-7 G-7

Tel: 301.595.1000
6' - 0" DOOR 6' - 0" DOOR
2"

7' - 0" DOOR


EQ EQ

Suite 600
SF14 SF15 SF16 SF17
NOTE 2

HOLLOW METAL FRAME ELEVATIONS


9' - 4"
G G

A-3.3
H1
6' - 0" 2" 3' - 1" 1" EQ 1" EQ 2"
4' - 8" 9' - 4" 12' - 8"

2"
6' - 0" 9' - 4"
6' - 0"
2" VARIES 2" 2" 3' - 0" 1' - 2" 2" 2" 3' - 0" 2' - 6" 2" 2" 3' - 0" EQ EQ 2" 2" 3' - 0" 2" EQ 1" EQ 1" EQ 2"
3' - 4"

A-3.3
2" EQ 1" EQ 2"

A-3.3
2" EQ 1" EQ 1" EQ 2"

H1

2' - 0"
2" EQ 1" EQ 2"

J1
1' - 4" G-7 G-7 G-6

A-3.3
A-3.3
2" 2" 1"
A-3.3

SEE SCHED
A-3.3
, A-3.3

A-3.3

H3
DOOR
2"

H1
2" DOOR DOOR
4"
H1

4"

H1

2" 3' - 0" 2"


H2 H1

2"

4"
DOOR
4"

2"
J1

1' - 0"
4"

2"
2"
H2,

J4
H2,

1"
2" 2"

A-3.3
J1 J4 J1 J5 J4

H1
J5 J1 , J2 J5 A-3.3
J1 , J2 J1 , J2 J1
1" 3' - 3"

1" 3' - 3"


A-3.3 A-3.3

1' - 4"
G-7 G-6 G-6 A-3.3 A-3.3 A-3.3
4' - 0"
3' - 8"

A-3.3 A-3.3 A-3.3 G-6 G-6 G-6 G-6 G-6 G-6


A-3.3 J5 A-3.3 A-3.3
4' - 11"

G-7

3' - 10"
G-6
5' - 4"

5' - 4"

9' - 4"
4' - 11"

4' - 11"

4' - 11"
3' - 6"

5' - 0"
J1 J4 G-7 G-6
SEE SCHEDULE

A-3.3 G-7 G-7 G-6 G-7


7' - 0" DOOR

J1
7' - 0" DOOR

7' - 0" DOOR

7' - 0" DOOR


1' - 0"
A-3.3 A-3.3 J1
7' - 4"
VARIES

J4
7' - 4"

7' - 4"

7' - 4"

7' - 4"

7' - 4"
J5 J4

DOOR
A-3.3
A-3.3

7' - 0"
A-3.3

G-6
A-3.3

A-3.3
J4

6' - 6"
J4

A-3.3
A-3.3
J4

A-3.3 A-3.3 A-3.3


1' - 8"

1' - 8"
A-3.3

J4
J4
A-3.3

D18 / A-6.3
J4

G-6 G-6 G-6 G-6 G-6

J4
2"

2"
1"
1"

1"
1"
A-3.3

SEE ELEV
VARIES -

2"
J1

GLASS TYPE KEY


3' - 4"

A-3.3

2' - 8"
1"

3' - 0" 2"


1' - 8"

2"

J1
G-7
1' - 8"

1' - 8"

1' - 8"

1' - 8"
2"

G-7 G-7 G-7 G-7 G-7


F F
2' - 0"

2' - 0"
SIM. G-7 G-7

A-3.3
A-3.3

J1

SIM.
J1

G-7 SIM. SIM. DOOR


4"
4"

4"
G-1 1" INSULATING GLASS; CONSISTING OF
4"

4"
1 2 3 4 5 6 7 8 9 10 11
1/4" TEMPERED EXTERIOR LITE WITH LOW E COATING ON SECOND SURFACE

16' - 0 1/2"
1/2" AIR SPACE
1/4" TEMPERED INTERIOR LITE
GP# 21553
3' - 2 3/4"
2" EQ 1" EQ 1" EQ 1" EQ 1" EQ 8 3/4" G-2 1" INSULATING GLASS; CONSISTING OF

FRAME ELEVATIONS - HM, STOREFRONT AND LOUVERS


8 3/4" 2' - 4" 2"
20' - 5 3/8" 10' - 4 1/2" 18' - 0 1/2"

A-3.3
3' - 4 3/8" 3' - 4" 1/4" TEMPERED EXTERIOR LITE W/ LOW E COATING ON SECOND SURFACE

H4
3' - 4"

2"

A-3.3
H4
2" 3' - 0" 2" 2' - 8 1/4" 1" 2' - 8 1/4" 1" 2' - 8 1/4" 1" 2' - 8 1/4" 1" 2' - 8 1/4" 1" 2' - 8 1/2" 6 5/8" 6 3/4" 3' - 2 1/4" 1" 3' - 2 1/2" 2" 3' - 0" 2" 2" 2' - 9 3/4" 1" 2' - 9 3/4" 1" 2' - 9 3/4" 1" 2' - 9 3/4" 1" 2' - 9 3/4" 1" 2' - 10" 6 3/4" 1/2" AIR SPACE,

1" 1' - 8" 2"


6 5/8" 2' - 7 3/4" 2" 2" 3' - 0" 2" 2" 3' - 0" 2" 1/4" TEMPERED INTERIOR LITE WITH SPANDREL COATING ON THIRD SURFACE

1" 1' - 8"


DOOR G-6 G-6 G-6 G-6 G-6 G-6
A-3.3

A-3.3

A-3.3
4"
A-3.3

A-3.3

H4

A-3.3

2"
H4

H1
4"

G-3 1" INSULATING GLASS; CONSISTING OF


H2

H2
4"

H1
2"
4"
4"

4"

E J1
A-3.3
J4
A-3.3
J10
G-6
J1 1/4" TEMPERED EXTERIOR LITE WITH LOW E COATING ON SECOND SURFACE E

A-3.3
J10 J10 J2 J1 J4 A-3.3 A-3.3 1/2" AIR SPACE

J4
J2 J5 J4

1" 3' - 6"


7' - 4"

3' - 6"
7' - 4"
J10 J5 J1 G-6 G-6 G-6 G-6 G-6 1/4" HEAT STRENGTHENED LAMINATED GLASS W/ HORIZONTAL FRIT ON THIRD

3' - 8"
4' - 0"
A-3.3
A-3.3 A-3.3 A-3.3 A-3.3 A-3.3 A-3.3 A-3.3 A-3.3 G-6

J4

4' - 4"
4' - 8"
A-3.3 A-3.3 A-3.3 J1 G-6 SURFACE

9' - 4"
J1
4' - 11"

4' - 11"

4' - 11"

4' - 11"
G-7 G-6 G-6 G-6 G-6 G-6 G-6 G-6 G-7 G-6 G-6 G-6 G-6 G-6 G-6 J10 A-3.3
7' - 0" DOOR

7' - 0" DOOR

A-3.3
A-3.3

7' - 4"
7' - 4"

7' - 4"
7' - 4"
7' - 4"

7' - 4"

G-4 1" INSULATING GLASS; CONSISTING OF

2" 1' - 8" 1"


J4 J4 J10

1' - 8"
A-3.3
G-6 G-6 G-6 G-6 G-6 G-6

J4

2"
A-3.3 A-3.3
1"
A-3.3 1/4" TEMPERED TINTED EXTERIOR LITE
1"

1"

A-3.3
J1
1/2" AIR SPACE
4" 1' - 8" 1"

3' - 4"

A-3.3

2"
A-3.3

2' - 8"
J1
1/4" TEMPERED INTERIOR LITE WITH LOW E COATING ON THIRD SURFACE
A-3.3

2"
A-3.3

1' - 8"
1' - 8"

1' - 8"
J4

2' - 0"

2' - 0"
A-3.3
J4

A-3.3
J4

G-7 G-7 G-7 G-7 G-7 G-7 G-7 G-7 G-7 G-7 G-7 G-7 G-7 G-7 G-7 SIM.
J4

A-3.3
J1
SIM.

J1
SIM. G-5 1" INSULATING GLASS; CONSISTING OF
0"

CITY OF BALTIMORE, MARYLAND


4"

4"
4"

1/4" TEMPERED TINTED EXTERIOR LITE


SIM. 13B 14A 14B 15 16 1/2" AIR SPACE
12A 12B 13A
1/4" TEMPERED INTERIOR LITE WITH LOW E COATING ON THIRD SURFACE

D 6' - 4"
6' - 0"
8' - 4"
D
G-6 1/4" THICK CLEAR FLOAT GLASS

HOLABIRD ACADEMY PK-8


2" 2' - 6" 2" 3' - 0" 2"
A-3.3
H1

2" EQ 1" EQ 2" 2" EQ 1" EQ 2"


3' - 4"
A-3.3

6' - 8 1/2" G-7 1/4" THICK CLEAR TEMPERED SAFETY GLASS


2"

DOOR
J1

2"
2"

4' - 0" 4' - 0" 3' - 0" 8' - 8" 9' - 0 1/2"
11' - 4"
2" 2' - 0" 2"

2" 3' - 0" 2" 2" 3' - 0" 2" 2' - 9 3/4" 6 3/4"
A-3.3

G-8 INSULATED METAL PANEL INFILL BY STOREFRONT/CURTAINWALL MANUFACTURER


2' - 0 1/2"

2" EQ 1" EQ 1" EQ 2"

A-3.3
A-3.3

H1

2" 3' - 8" 2" 2" 3' - 8" 2" 2" 2' - 8" 2" 6 3/4" EQ 1" EQ 1" EQ 2" J4
2' - 0"

2' - 0"
H4
2" EQ 1" EQ 1" EQ 1" EQ 2"
H2

A-3.3
A-3.3

H4

G-7 G-7 G-7 A-3.3 G-7

A-3.3
G-7 G-7
2"
H1

DOOR

A-3.3
H4
2"

2"

H3
A-3.3

G-9 5/16" THICK LAMINATED FIRE RATED GLASS


2"
H2
2"

2"

4"

4"
1"

2"
J4
2"

J1 J1 G-10 1/8" THICK FIRE RATED POLYCARBONATE SHEET


J10 J4 J1
A-3.3

A-3.3 A-3.3 J1 J10


A-3.3

A-3.3
H3

J1 A-3.3
H3
3' - 8"
4' - 0"

4' - 0"
3' - 8"

3' - 8"
4' - 0"

3' - 8"
4' - 0"
J4

G-6 G-7 G-6 G-6 G-6 G-6 G-6 G-6 G-6 A-3.3 A-3.3 A-3.3
A-3.3 G-11 2 - 5/16" FIRE RATED INSULATING GLASS; CONSISTING OF
3' - 8"
4' - 0"

A-3.3
4' - 11 1/2"

J2 G-6 A-3.3
9' - 4"

9' - 4"

9' - 4"
4' - 11"
5' - 1"

A-3.3 J2 G-7 G-6 G-6 G-6 G-6 G-7


J4

7' - 0" DOOR


A-3.3 1/4" TEMPERED EXTERIOR LITE WITH LOW E COATING ON SECOND SURFACE
7' - 4"

7' - 4"

7' - 4"
4' - 11"
DOOR

A-3.3
A-3.3
7' - 0"

7' - 0"

J5 1/2" AIR SPACE


J4
2"

2"

J5 A-3.3 1 9/16" FIRE RESISTANT GLAZING INTERIOR LITE


2"
2"

2"

1"

A-3.3
1"

C C
A-3.3
A-3.3

A-3.3

J1
J2

J1

4" 1' - 8" 1"

4" 1' - 8" 1"


3' - 4"

3' - 4"

3' - 4"

J1 J1
A-3.3

3' - 0"

SIM
J2

A-3.3

A-3.3
4" 1' - 8"

1' - 8"

SIM
A-3.3

A-3.3 A-3.3 SIM


J4

J4
G-7 G-7 G-7 G-7 G-7 G-7
J4

SIM

NUMBERED REMARKS
4"

17 18 19 20 21 22 23 24 25A 25B 26
3' - 4" 4' - 8"
NOTE 1: PROVIDE NO TRANSLUCENT ROLLER SHADES AT THIS FRAME OPENING.
2" 3' - 0" 2" 2"1' - 2"2" 3' - 0" 2" 7' - 3" DATE DESCRIPTION
1' - 5 1/2" 6' - 7 1/2" NOTE 2: PROVIDE ELECTRIC MOTOR TRANSLUCENT ROLLER SHADES AT THIS FRAME OPENING.
A-3.3

A-3.3

DOOR DOOR
H1

5' - 6"
H1
2"

2"

2" EQ 2" EQ 2" 2' - 0" 2' - 0"


NOTE 3: PROVIDE PRE-FINISHED ALUMINUM SUNSHADES (HORIZONTAL LOUVERS IN VERTICAL FRAME) AS
2" 2' - 0" 2"

2" 3' - 0" 2" 2' - 0" 2" 2" 11" 4 1/2" 4 1/2" 4' - 5 3/4" 2" 1' - 5 1/4" 2"
2' - 0 1/2"

2" 1' - 8" 2" SHOWN ON ELEVATIONS


2"
2' - 0"

2" 1' - 8" 2"


2"

G-7 G-7 G-7


A-3.3

DOOR
H1

2"

2" 1' - 9" 2"

2"

2' - 0" NOTE 4: PROVIDE PRE-FINISHED ALUMINUM SUNSHADES, 24" PROJECTION HORIZONTALLY, AS SHOWN ON
1' - 8" 2" 1' - 8" 2" 1' - 8"

1' - 8" 2" 1' - 8" 2" 1' - 8"


4"

G-7 G-7 G-7 G-7 ELEVATIONS


A-3.3

B B
2' - 0"
1' - 8"
2"

H1

2" 1' - 8" 2"


1"

J1 G-7
3' - 9"

J1 G-7
A-3.3
A-3.3

NOTE 5: NOT USED


A-3.3

A-3.3

2"
H3

H3

A-3.3 J1
J4

5' - 8"

5' - 8"

6' - 0"
4' - 11 1/2"

A-3.3 G-7 G-7 G-7 G-7


9' - 4"

9' - 4"

G-7
4' - 11"

2"

2"

J5 NOTE 6: AT OPENINGS IN 2 HOUR FIREWALL, PROIVDE 2 HOUR FIRE RATED CURTAINWALL SYSTEM.
7' - 0" DOOR

7' - 0" DOOR

7' - 0" DOOR

3' - 9"

G-7
2" 1' - 9" 2"
7' - 4"

A-3.3 G-7 J1
4' - 0"
3' - 8"

4' - 0"
3' - 8"

G-7 G-7 G-7 G-7 A-3.3 G-7


J7 J7 J5 G-7 G-7
5' - 4"
1"

A-3.3 A-3.3 A-3.3


2"
2"

2"

1' - 5 1/4" 2" 4' - 5 3/4" OPERABLE INTERIOR


4" 1' - 8"

4" 1' - 8"

2' - 4"

2' - 4"
1"

A-3.7
A-3.3

2' - 0"

G-7 G-7 EQ 2" 3' - 5 1/2" 2" EQ


J4

2"
2"
1' - 4"

1' - 4"
A-3.3

WINDOW, LOCKABLE
J1

SIM FRAME

27 28 29 30A 30B 31 32 33 34 03/13/2017


BID SET
A © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

EX3
EX3

10 1/4" 1' - 7" OR 1' - 5"


1 1/2" VERIFY W/ 3 1/4"
5/8" 6" 5/8" 2 1/2"1/2" 3/4" 1/4" MTL. PANEL MANUF. 5/8" 2 5/8" 8" OR 6" CONCRETE 2 5/8" 1 1/2" 3 5/8"
5/8" 2 5/8" 8" 2 5/8" 3/4" 1 1/2"

CONCRETE CORE, VARIES 1/4"

AIR BARRIER
3/4" SUBGIRT FURRING
1 1/2" METAL PANEL TYPE 3 CHANNEL AND 1/4" SHIM
CONT. S.S. TERMINATION MASONRY VENEER ANCHOR @
BAR & SEALANT PRE-FIN METAL PANEL, TYPE 2 16" O.C. VERT, TYP.
M 1/4" SHIM
DRILL INTO CONCRETE FOR M
EMBEDMENT
5/8" GYP BD ADHERED TO EPS FOAM,
CONTINUOUS ON INTERIOR TO TRANSITION MEMBRANE VERTICAL 4" MIN. OVERLAP
TRANSITION MEMBRANE 3" HORIZ. GALV. Z-GIRTS UNDERSIDE OF DECK AND AROUND FLASHING TERMINATION BAR
EXTEND HORIZONTALLY UNDER WOOD BUCK

10"
EXTEND MIN. 4" UP WALL AT AIR STRUCTURAL FRAMING AND ATTACHED TO ICF WEBBING, LATEX
BARRIER AND UNDER STEEL 3 1/2" HORIZ. GALV. Z-GIRTS PENETRATIONS SEALANT AT TOP OF BAR
LINTEL CONT. FLEXIBLE FLASHING, PROVIDE MORTAR DIVERTER
END DAMS AND TERMINATION BAR
SHIM
CLIP ANGLE BY METAL PANEL MANUF. BRICK VENEER
CONT. FLEXIBLE THROUGH WALL
FOR INSTALLATION, SUPPORT & PRE-FIN METAL TRIM BY METAL
FLASHING - SEAL TO ALUM.
ANCHORAGE OF THE STOREFRONT PANEL MANUF. CONT. THROUGHWALL FLASHING, SEAL
EXTRUSION, PROVIDE END DAMS
SYSTEM, THE INSTALLAING TO SS DRIP PLATE

OVERLAP
AND TERMINATION BAR SILL ELEV. - SEE

4" MIN.
CONTRACTOR SHALL PROVIDE
CONT. GALV. ANGLES OR BENT WALL SECTION RIGID INSULATION TO FILL SPACE
L PLATES TO FIT WITHIN THE CAVITY
2-PIECE PRE-FIN. ALUM. METAL
PANEL HEAD EXTRUSION w/
L
AS DESIGNED BY THE ENGINEERED WOOD OPENING BUCK
WEEPS BY METAL PANEL MANUF. CONT. SEALANT AND BACKER ROD TRANSITION MEMBRANE, 4"
STOREFRONT SYSTEM ENGINEER FASTENED TO CONCRETE PER
- COLOR TO MATCH STOREFRONT, OVERLAP MIN.

OR WALL SECTION
SEE FRAME ELEV
MANUFACTURER'S SPECIFICATIONS
TYP. CAVITY VENT/WEEPS AT 16" O.C.

R.O.
CONT. BACKER ROD & SEALANT 5/8" GYP BD ADHERED TO EPS FOAM, BRICK SOLDIER COURSE
- BOTH SIDES, COLOR TO CONTINUOUS ON INTERIOR TO
MATCH STOREFRONT, TYP. UNDERSIDE OF DECK AND AROUND
5/8" GYP BD
STRUCTURAL FRAMING AND
SEALANT ALUM. DEFLECTION TRACK AT HEAD OF MANUAL ROLLER SHADES, TYPICAL PENETRATIONS
WHERE SHOWN ON FRAME ELEVATIONS.
2" STOREFRONT BY STOREFRONT MANUF.
REFER TO ELEVATION FOR ELECTRIC
B.O. METAL LINTEL
ROLLER SHADES SHADE CALLOUT ENGINEERED WOOD OPENING BUCK
PRE-FIN. ALUM. STOREFRONT FASTENED TO CONCRETE PER S.S. DRIP PLATE WITH 1/2" HEMMED EDGE
SCHED. PRE-FIN. ALUM. W/ 1" INSULATED GLAZING MANUFACTURER'S SPECIFICATIONS SEALANT TAPE BETWEEN DRIP PLATE & ANGLE
STOREFRONT & 1"
K 6" 4 1/2" 2 1/4"
INSULATED GLAZING 10" 4 1/2" K
STEEL LINTEL ANGLE AND PLATE AT
CONCRETE HAUNCH, REF: STRUCTURAL
MANUAL ROLLER SHADES, TYPICAL CONT. SEALANT AND BACKER ROD -
WHERE SHOWN ON FRAME ELEVATIONS. COLOR TO MATCH STOREFRONT, TYP.
SF HEAD DETAIL @ METAL PANEL ON STUD BACK-UP SF HEAD @ ICF WALL W/ MTL PANEL TYPE 2 REFER TO ELEVATIONS FOR ELECTRIC

K15 3" = 1'-0" K11 3" = 1'-0"


SHADE SYSTEM CALLOUT AIR BARRIER TRANSITION MEMBRANE
EXTENDS MIN. 4" UNDER WOOD BUCK

10" @ 8" CONCRETE 4 1/2" 4 1/2"


SCHEDULED PRE-FIN. ALUM. STOREFRONT
8" @ 6" CONCRETE SYSTEM W/ 1" INSULATED GLASS
SCHED. PRE-FIN. ALUM. STOREFRONT

3/4" MAPLE VENEER PLYWOOD


& 1" INSULATED GLAZING EX3
SF HEAD @ ICF WALL W/ MASONRY
J BACKBOARD WITH CHAMFERED TOP 1' - 0 3/4" J6 3" = 1'-0" J
10" 4 1/2" 4 1/2"
FOR INSTALLATION, SUPPORT & EX3
ANCHORAGE OF THE STOREFRONT
STOREFRONT OR CURTAINWALL.
SYSTEM, THE INSTALLAING CONTRACTOR
W/ 1" INSULATED GLASS
SHALL PROVIDE CONT. GALV. ANGLES OR PRE-FIN. ALUM. STOREFRONT & FOR INSTALLATION, SUPPORT & REF: PLANS AND ELEVATIONS
BENT PLATES TO FIT WITHIN THE CAVITY INSULATED METAL PANEL ANCHORAGE OF THE STOREFRONT
AS DESIGNED BY THE STOREFRONT SYSTEM, THE INSTALLAING PRE-FIN. ALUM. STOREFRONT H.P. SILL
SYSTEM ENGINEER CONTRACTOR SHALL PROVIDE FLASHING W/ END DAM AND WEEPS -
PRE-FIN. ALUM. STOREFRONT SCHED. PRE-FIN. ALUM. STOREFRONT
CONT. GALV. ANGLES OR BENT EMBEDDED IN SEALANT
H.P. SILL FLASHING w/ WEEPS & 1" INSULATED GLAZING
PLATES TO FIT WITHIN THE CAVITY PRE-FIN. ALUM. STOREFRONT
3/4" MAPLE VENEER PLYWOOD, SEAT - EMBEDDED IN SEALANT

R.O.
AS DESIGNED BY THE SYSTEM W/ 1" INSULATED GLAZING

SEE WALL SECTION & FRAME ELEV


STOREFRONT SYSTEM ENGINEER PRE-FIN. ALUM. STOREFRONT 1/2"
H.P. SILL FLASHING w/ WEEPS SOLID SURFACE STOOL MASONRY SILL - SPECIAL SHAPE #1
6" - EMBEDDED IN SEALANT GYP BD RETURN @ GYM SEALANT
2-PIECE PRE-FIN. ALUM. METAL SOLID SURFACE STOOL ON PLYWOOD
PANEL SILL EXTRUSION SILL ELEV. - SEE
3/8" 1/2"
PRE-FINISHED ALUM. SF SILL
H H

www.grimmandparker.com
WALL SECTION FLASHING WITH WEEPS, EMBEDDED IN

R.O.
SEALANT

1/2"
SOLID SURFACE

11720 Beltsville Drive


GYPSUM BD. METAL REVEAL 10" 1/2"

Calverton, MD 20705
1/4" STOOL
2-PIECE PRE-FIN. ALUM. METAL EXTRUSIONS BY METAL PANEL

Tel: 301.595.1000
5/8" FINISHED ABUSE-RESISTANTGYPSUM BD, TYPICAL PANEL SILL EXTRUSION VERIFY WITH WALL WIDTH
MANUFACTURER

4" MIN.
1/2"

1/2"
3/4" PLYWOOD/ 1/2" PLYWOOD
SILL ELEV. - SEE

Suite 600
5/8" GYP. BOARD 1" CONT. THROUGH WALL FLASHING AND WALL SECTION
ADHERED TO EPS FOAM CAVITY VENT/WEEPS AT 16" O.C.
(2) 2X4 FRT WOOD STUDS, TYP. 1/2"
CONTINUOUS ON FOR INSTALLATION, SUPPORT, AND ANCHORAGE

MIN.
INTERIOR WALLS OF STOREFRONT SYSTEM, INSTALLING

4"
3" HORIZ. GALV. Z-GIRTS 3" HORIZ. GALV. Z-GIRTS CONTRACTOR SHALL COORDINATE WITH PRE-
5/8" GYP. BOARD ENGINEERED WOOD BUCK SYSTEM, TYPICAL
1 1/2" METAL PANEL TYPE 3 1 1/2" METAL PANEL TYPE 3 ADHERED TO EPS
G FOAM TRANSITION MEMBRANE
4" MIN. OVERLAP ON ICF AIR BARRIER
G
TRANSITION MEMBRANE TRANSITION MEMBRANE CONTINUOUS ON
INTERIOR WALLS TURN UP AND OVER BUCK UNDER SF
BRICK VENEER
5/8" FINISHED ABUSE- 1' - 4 3/8"
RESISTANTGYPSUM BD, TYPICAL TRANSITION MEMBRANE
4" MIN. OVERLAP ON ICF AIR BARRIER 5/8" 2 5/8" 8" 2 5/8" 3/4"1/4" 1 1/2"
TURN UP AND OVER BUCK, AND UNDER SF
3/4"
3 1/2" 5/8" 5 3/4" 1/4" 3 1/8" 1 1/2" 1 1/2" VERIFY W/ 5/8" 2 5/8" 8" 2 5/8" 1 1/2" 3 5/8"
5/8" 6" 3 1/8" 1/2"3/4" MTL. PANEL MANUF.
1/2" 1/4" 1' - 7" FINISHED BASE - SEE PRE-FIN METAL PANEL TYPE 2
1' - 4 1/4" 11" 1/4" FINISH SCHEDULE

COMPOSITE FLOOR SLAB -


SEE STRUCT DWGS
F SF SILL DETAIL @ WINDOW SEAT/ STUD BACK-UP SF SILL DETAIL @ METAL PANEL ON STUD BACK-UP SF SILL @ ICF WALL W/ MASONRY F
F18 3" = 1'-0" F15 3" = 1'-0" F11 3" = 1'-0"
SECOND FLOOR
14' - 8"

GP# 21553

STEEL BEAM, PLATE AND


ANCHORS, - SEE STRUCT DWGS
E E

SF SILL @ ICF WALL W/ MTL PANEL TYPE 2


D6 3" = 1'-0"

CORNER BEAD CONTINUOUS ABUSE RESISTANT 5/8" GYP. BOARD

CITY OF BALTIMORE, MARYLAND


ON INTERIOR WALLS ADHERED TO EPS FOAM
CONTINUOUS ON INTERIOR WALLS
ABUSE RESISTANT 5/8" GYP. BOARD
ENGINEERED WOOD OPENING BUCK
SILL
D FASE OF GYPSUM BD. BELOW
FASTENED TO CONCRETE PER
MANUFACTURER'S SPECIFICATIONS
D

HOLABIRD ACADEMY PK-8


STOREFRONT DETAILS
5/8"
2 5/8"
EXB

SEE DRAWINGS INCLUDING PLANS AND SECTS


6" OR 8"
C C

1' - 5" OR 1'-7"


4" 4" MIN.

2 5/8"
4 1/2"
OVERLAP

DATE DESCRIPTION

1 1/2"
1/8"
5"
4 1/2"

3 5/8"
B B
ALUMINUM STOREFRONT WITH
1" INSULATED GLASS MOISTURE BARRIER

1"
CONT. SEALANT AND BACKER TRANSITION MEMBRANE
ROD - COLOR TO MATCH 4" MIN. OVERLAP ON ICF MOISTURE BARRIER
STOREFRONT, TYP. TURN BACK OVER BUCK

SPECIAL SHAPED BRICK SILL BRICK RETURN AT JAMB

A-3.8
SF JAMB @ ICF WALL WITH MASONRY VENEER
A6 3" = 1'-0"
03/13/2017
BID SET
A © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

WALL TYPES TYPICAL WALL TYPE NOTES


TYP. NOTE: DECK OR GENERAL NOTE APPLICABLE TO ALL DRAWINGS - ITEMS AND CONDITIONS DETAILED NOTED OR OTHERWISE IDENTIFIED ON ONE OF
STRUCTURE ABOVE - SEE TYP. THE SECTIONS OR DETAILS ARE APPLICABLE AND BINDING TO ALL OTHER SECTIONS AND DETAILS FOR IDENTICAL OR SIMILAR
WALL TERMINATION DETAILS CONDITIONS.
TYP. NOTE: ACOUSTIC SEALANT
1. NOT ALL WALL TYPES ARE REPRESENTED IN THIS PROJECT.
(BOTH SIDES) AT WALLS WITH
CEILING VARIES - GYP. BOARD TO 2. WALLS SHALL EXTEND FULL HEIGHT FROM FLOOR SLAB TO THE FLOOR OR ROOF DECK ABOVE UNLESS SPECIFICALLY
TYP. NOTE: DECK OR STC SOUND RATING INDICATED
EXTEND TO UNDERSIDE OF DECK NOTED OTHERWISE. IN CORRIDORS, EXTEND COLUMN CHASE AND LOCKER FIN WALLS 4" ABOVE CEILING ONLY.
STRUCTURE ABOVE - SEE TYP. ACOUSTIC SEALANT (BOTH
3. REFER TO THE CODE STUDY AND FLOOR PLANS FOR IDENTIFICATION OF ALL SMOKE AND FIRE WALL CONDITIONS /
WALL TERMINATION DETAILS TYP. NOTE: PROVIDE STUD BRACING SIDES, TYP.)
LOCATIONS. IN ADDITION TO THE REQUIREMENTS INDICATED ON THE CODE STUDY AND FLOOR PLANS, ALL CORRIDOR AND
AS REQUIRED TO COMPLY WITH

4"
VESTIBULE WALLS SHALL BE BUILT TO RESIST THE PASSAGE OF SMOKE.

4"
TYPICAL WALL TYPE NOTE 11. 4. FIRE WALLS, FIRE SEPARATION WALLS, SMOKE BARRIER WALLS AND WALLS REQUIRED TO RESIST THE PASSAGE OF SMOKE
M CMU - WIDTH VARIES CMU - WIDTH VARIES INSULATED CONCRETE FORM (ICF) 3 5/8" METAL STUDS @ 16" O.C. 3 5/8" METAL STUDS @ 16" O.C.
SHALL EXTEND FULL HEIGHT FROM FLOOR SLAB TO THE FLOOR OR ROOF DECK ABOVE AND SHALL BE SEALED TIGHT TO M
3 5/8" METAL STUDS @ 16" O.C. 3 5/8" METAL STUDS @ 16" O.C. THE DECK OR STRUCTURAL MEMBER WITH AN APPROVED FIRE RESISTIVE JOINT SYSTEM. SEAL ALL PENETRATIONS AND
WALL: CONCRETE CORE (WIDTH

TYP: SEE REFLECTED CLG PLAN


VARIES) WITH EPS FOAM EACH SIDE TOPS OF WALLS IN ACCORDANCE WITH SPECIFICATION DIVISION 7 SECTION - FIRE RESISTIVE JOINT SYSTEMS. WALLS AT
3 1/2" SOUND ATTENUATION 3 1/2" SOUND ATTENUATION FIRE AND SMOKE CONDITIONS / LOCATIONS, LISTED ABOVE, SHALL BE BUILT TIGHT TO DUCTS, PIPES AND PENETRATIONS
(SEE SPEC) BLANKETS BLANKETS 5/8" ABUSE-RESISTANT GYP. BD. AND SHALL BE TERMINATED IN ACCORDANCE WITH WALL TERMINATION DETAILS ON THIS SHEET. FILL FLUTES IN FLOOR

CEILING HEIGHT
5/8" GYP. BD
5/8" ABUSE- RESISTANT GYP BD 5/8" GYP BD ON 5/8" GYP. BD. AND ROOF DECKS AS INDICATED. WHERE WALLS AT FIRE AND SMOKE CONDITIONS / LOCATIONS, LISTED ABOVE, ARE
5/8" ABUSE- RESISTANT GYP 5/8" GYP. BD ON EACH SIDE 5/8" ABUSE RESISTANT GYP. BD
3 1/2" SOUND ATTENUATION INTERRUPTED BY STRUCTURAL MEMBERS, PROVIDE FIRE RESISTIVE JOINT SYSTEM IN AREAS BETWEEN TOP AND/OR SIDE
BD ON EACH SIDE 3 1/2" SOUND ATTENUATION
CMU WALL 7/8" FURRING CHANNELS 3 5/8" METAL STUDS BLANKETS OF WALL AND STRUCTURAL MEMBER AND BETWEEN DECK ABOVE AND STRUCTURAL MEMBER IN ACCORDANCE WITH
FASTENED PER MANU. EACH BLANKETS
@ 16" OC @ 16" OC APPROVED FIRE RESISTIVE JOINT SYSTEM AND TYPICAL WALL TERMINATION NOTE #4 BELOW.
SIDE
5/8" ABUSE RESISTANT GYP. BD 5. SEE WALL SECTIONS AND DETAILS FOR EXTERIOR WALL TYPES.
TYP. NOTE: CONC. SLAB - SEE CMU WALL 6. THESE WALL TYPES ARE GENERAL IN NATURE AND DO NOT COVER EVERY VARIATION THAT MAY OCCUR THROUGHOUT THE
CMU WALL TYP. NOTE: CONC. SLAB - SEE
FINISH SCHEDULE FOR FLOOR PROJECT. SEE WALL SECTIONS AND DETAILS FOR ADDITIONAL INFORMATION.
FINISH SCHEDULE FOR FLOOR
FINISH AND WALL BASE 7. TYPICAL CMU INTERIOR PARTITION SHALL BE TYPE A3 UNLESS INDICATED OTHERWISE BY WALL TYPE SYMBOLS, WALL
FINISH AND WALL BASE
SECTIONS OR OTHER DETAILS.
8. TYPICAL GYPSUM BOARD/STUD WALL PARTITION SHALL BE TYPE 3-5/8" METAL STUDS AT 16" 0.C. WITH 5/8" ABUSE-RESISTANT
GYPSUM BOARD UNLESS INDICATED OTHERWISE BY WALL TYPE SYMBOLS , WALL SECTIONS OR OTHER DETAILS.
A1 AS SHOWN WITH 3 5/8" CMU E1 AS SHOWN WITH 3 5/8" CMU W/ 7/8" FURRING
L F1 AS SHOWN WITH 3 5/8" CMU W/ 3-5/8" STUDS
G1 AS SHOWN WITH 8" ICF J1 GYP BD WALL AS SHOWN K1 ABUSE RESISTANT GYP BD WALL AS SHOWN L1 GYP BD / ABUSE RESISTANT GYP BD WALL AS SHOWN M1 DOUBLE LAYER ABUSE RESISTANT GYP. BD. WALL AS
9. WALL TYPES MAY NOT HAVE BEEN INCLUDED IN THIS SCHEDULE FOR INTERIOR WALL TYPES WHICH ARE COVERED BY WALL
SECTIONS. L
A2 AS SHOWN WITH 5 5/8" CMU E2 AS SHOWN WITH 5 5/8" CMU W/ 7/8" FURRING F2 AS SHOWN WITH 5 5/8" CMU W/ 3-5/8" STUDS SHOWN (STC RATING 55, MIN.) NOTE: STAGGER HORIZ. 10. THESE WALL TYPES DO NOT SHOW LATERAL BRACING OR WALL REINFORCING. SEE STRUCTURAL AND OTHER DRAWINGS
G2 AS SHOWN WITH 10" ICF J2 GYP BD WALL AS SHOWN W/ 6" MET STUDS K2 ABUSE RESISTANT GYP BD WALL AS SHOWN W/ 6" MET STUDS L2 GYP BD / ABUSE RESISTANT GYP BD WALL AS SHOWN W/ 6" AND VERT. GYP. BD. JOINTS
MET STUDS FOR THAT INFORMATION.
A3 AS SHOWN WITH 7 5/8" CMU E3 AS SHOWN WITH 7 5/8" CMU W/ 7/8" FURRING F3 AS SHOWN WITH 7 5/8" CMU W/ 3-5/8" STUDS K3 M2 DOUBLE LAYER ABUSE RESISTANT GYP. BD. WALL 11. SEE FINISH SCHEDULE FOR FINISHES TO BE APPLIED TO THESE WALL TYPES.
ABUSE RESISTANT GYP BD WALL AS SHOWN W/ 8" MET STUDS
(STC RATING 55, MIN.) AS SHOWN W/ 6" MET STUDS. 12. ALL WALLS WITH FIRE RATING INDICATED SHALL BE BUILT IN STRICT CONFORMANCE WITH A UL TESTED ASSEMBLY OR
A4 AS SHOWN WITH 9 5/8" CMU E4 AS SHOWN WITH 9 5/8" CMU W/ 7/8" FURRING F4 AS SHOWN WITH 9 5/8" CMU W/ 3-5/8" STUDS J4 NOTE: STAGGER HORIZ. AND VERT. GYP. BD. JOINTS OTHER TESTED ASSEMBLY WHICH PROVIDES THE FIRE RATING INDICATED.
GYP BD WALL AS SHOWN BUT STOP GYP BD 4" ABOVE CLG
13. FURRING CHANNELS AND STUDS SHALL BE 16" O.C. MAXIMUM UNLESS SPECIFICALLY NOTED OTHERWISE.
A5 AS SHOWN WITH 11 5/8" CMU E5 AS SHOWN WITH 11 5/8" CMU W/ 7/8" FURRING F5 AS SHOWN WITH 11 5/8" CMU W/ 3-5/8" STUDS J5 14. THE GAGE OF ALL METAL STUDS SHALL BE SIZED SO THAT THE DEFLECTION OF THE WALL SHALL NOT EXCEED 1/240 PER
GYP BD WALL AS SHOWN BUT DELETE SOUND
ATTENUATIONS ASTM C645 UNLESS A HEAVIER GAGE IS INDICATED ON THE WALL TYPE OR DETAILS.
2' - 0" 15. IN ALL WALLS WITH SOUND ATTENUATION BLANKETS OR AN STC RATING LISTED; OUTLETS, SWITCHES, ETC., SHALL NOT BE
LOCATED BACK TO BACK. OUTLETS SHALL BE OFFSET AND SEALED. PERIMETERS OF WALLS (AT ADJACENT WALLS,
COLUMNS, CEILINGS, ETC.) SHOULD BE SEALED. ADDITIONALLY, WALL PENETRATIONS SHALL BE SEALED WITH
APPROPRIATE TYPE OF ACOUSTIC SEALANT.
16. PROVIDE SPACE FOR DEFLECTION OF BEAMS, JOISTS, AND STEEL DECK @ TOP OF ALL WALLS THAT RUN TO THE DECK. FILL
GAP WITH NON COMBUSTIBLE, COMPRESSIBLE FILLER ON NON RATED WALLS AND APPROVED FIRE SAFING ON RATED
WALLS - SEE TYP. DETAILS THIS SHEET.
K 17. FOR CASES WHEN WALLS ARE INDICATED TO EXTEND FULL HEIGHT TO THE DECK BUT STOP AT A STRUCTURAL MEMBER,
SEE THE TYPICAL DETAILS ON THIS SHEET FOR THE APPROPRIATE CLOSURE CONDITIONS. IF EXACT CONDITION IS NOT
K
ACOUSTIC SEALANT ACOUSTIC SEALANT
ACOUSTIC SEALANT ACOUSTIC SEALANT (BOTH 3 5/8" METAL STUDS @ 16" O.C. INDICATED, MODIFY CLOSEST CONDITION FOR SPECIFIC APPLICATION.
ACOUSTIC SEALANT (BOTH
SIDES, TYP.) 18. PROVIDE 4" HIGH X 18 GA. X LENGTH REQUIRED STEEL PLATE BLOCKING OR 2x FRT WD BLOCKING IN ALL IN ALL STUD
5/8" ABUSE-RESISTANT GYP. BD. SIDES, TYP.) TWO LAYERS OF 5/8" GYP. BD.
5/8" ABUSE-RESISTANT GYP. BD. WALLS WHERE REQUIRED TO ATTACH LOCKERS, CASEWORK, SHELVING, LIGHTS, ELECTRICAL DEVICES, TOILET
ON 5/8" GYP. BD. ON 5/8" GYP. BD. ACCESSORIES AND ANY OTHER ITEM WHICH REQUIRE SECURE ATTACHMENT TO THE WALLS.
19. IN ROOMS WHERE NO FINISHED CEILING IS PROVIDED, EXTEND ALL CHASE WALLS TO FLOOR OR ROOF DECK ABOVE.
20. PROVIDE CONT. SEALANT AT BASE OF ALL GYP. BD. WALLS (BOTH SIDES), TYPICAL.
3 5/8" METAL STUDS @ 16" O.C. 3 5/8" METAL STUDS @ 16" O.C. 3 5/8" METAL STUDS @ 16" O.C. 3 5/8" METAL STUDS @ 16" O.C.
3 5/8" METAL STUDS @ 16" O.C. 3 5/8" METAL STUDS @ 16" O.C.
5/8" ABUSE-RESISTANT GYP. BD. 3 1/2" SOUND ATTENUATION
3 1/2" SOUND ATTENUATION 3 1/2" SOUND ATTENUATION ON 5/8" GYP. BD.
BLANKETS BLANKETS
BLANKETS TWO LAYERS OF 5/8" GYP. BD. 5/8" GYP. BD
TWO LAYERS OF 5/8" GYP. BD.

5/8" ABUSE-RESISTANT GYP. BD. 5/8" GYP. BD. 3 1/2" SOUND ATTENUATION
5/8" GYP. BD.
3 1/2" SOUND ATTENUATION
5/8" ABUSE RESISTANT GYP. BD
ELECTRICAL BOXES IN FIREWALLS
BLANKETS BLANKETS
J ELECTRICAL BOXES IN FIRE RATED PARTITIONS SHALL NOT EXCEED 16 SQUARE INCHES IN AREA (IF 4"X4"), SHALL BE MADE OF STEEL, AND J
ROOM SIDE SHALL BE SPACED SUCH THAT THE CUMULATIVE AREA OF BOX CUTOUTS IN THE FIREWALL DOES NOT EXCEED 100 SQUARE INCHES PER
ROOM SIDE ROOM SIDE ROOM SIDE 100 SQUARE FEET OF WALL AREA. ELECTRICAL BOXES ON OPPOSITE SIDES OF THE SAME FIREWALL SHALL BE SEPARATED BY A
HORIZONTAL AND VERTICAL DISTANCE OF NOT LESS THAN 24". THE ELECTRICAL CONTRACTOR SHALL MAKE MINOR ADJUSTMENTS, AS
NECESSARY, TO ELECTRICAL BOX LOCATIONS TO ENSURE COMPLIANCE WITH THIS REQUIREMENT SINCE BOX LOCATIONS ARE TYPICALLY
NOT DIMENSIONED ON THE DRAWINGS. CONSULT ARCHITECT IF CLARIFICATION IS REQUIRED.
X1 GYP. BD. CHASE WALL AS SHOWN
S1 GYP BD WALL AS SHOWN T1 GYP. BD. WALL AS SHOWN U1 ABUSE RESISTANT GYP. BD. WALL AS SHOWN - 2'-0" TOTAL THICKNESS
N1 GYP BD / ABUSE RESISTANT GYP BD WALL AS SHOWN P1 GYP BD / ABUSE RESISTANT GYP BD WALL AS SHOWN R1 DOUBLE LAYER GYP. BD. / DOUBLE LAYER ABUSE
RESISTANT GYP. BD. WALL AS SHOWN NOTE: STAGGER HORIZ. AND VERT. GYP. BD. JOINTS X2 AS SHOWN W/ ABUSE RESISTANT GYP. BD.
S2 GYP BD WALL AS SHOWN W/ 6" MET STUDS U2 ABUSE RESISTANT GYP. BD. WALL AS SHOWN - ___ TOTAL THICKNESS
N2 GYP BD / ABUSE RESISTANT GYP BD WALL AS SHOWN W/ P2 GYP BD / ABUSE RESISTANT GYP BD WALL AS SHOWN W/ NOTE: STAGGER HORIZ. AND VERT. GYP. BD. JOINTS
6" MET STUDS 6" MET STUDS
U3 ABUSE RESISTANT GYP. BD. WALL AS SHOWN - 2'-0" TOTAL THICKNESS,
EXCEPT THE CORRDIOR WALL SHALL BE 6" CMU INPLACE OF GYP. BD. AND
X4

X5
AS SHOWN W/ 2 LAYERS 5/8" ABUSE RESISTANT GYP. BD.

6" METAL STUDS W/ 5/8" GYP. BD.


TYPICAL WALL TERMINATION NOTES
METAL STUD.
X6 6" METAL STUDS W/ 5/8" ABUSE RESISTANT GYP. BD. 1. USE THESE TYPICAL WALL TERMINATION DETAILS FOR ALL WALLS INDICATED TO EXTEND TO DECK ABOVE, UNLESS
SPECIFICALLY DETAILED OTHERWISE. COORDINATE WITH STRUCTURAL FRAMING PLANS.
X7 8" METAL STUDS W/ 5/8" ABUSE RESISTANT GYP. BD. 2. SEE WALL TYPES ABOVE FOR ACTUAL WALL CONSTRUCTION.
H H

www.grimmandparker.com
3. AT FIRE WALLS, FIRE SEPARATION WALLS, SMOKE BARRIER WALLS AND WALLS REQUIRED TO RESIST THE PASSAGE OF
X8 AS SHOWN W/ 2 LAYERS 5/8" GYP. BD. SMOKE, ALL 'COMPRESSIBLE, NON-COMBUSTIBLE' MATERIALS REFERENCED IN THE WALL TERMINATION DETAILS SHALL

11720 Beltsville Drive

Calverton, MD 20705
BE MATERIALS PROVIDED IN ACCORDANCE WITH THE APPROVED FIRE RESISTIVE JOINT SYSTEM.
4. IF A WALL REQUIRING A FIRE RATING IS LOCATED DIRECTLY UNDER A BEAM THE FIRE RATING OF THE WALL SHALL BE

Tel: 301.595.1000
WALL TERMINATION DETAILS MAINTAINED TO THE DECK BY EXTENDING WALL AROUND BEAM. CONSULT ARCHITECT FOR EXACT REQUIREMENTS TO
MAINTAIN RATING.

Suite 600
FILL FLUTES IN STEEL DECK IN AREA 18 GAUGE STL. PLATE, 8" LONG
FILL FLUTE ARE BETWEEN BOTTOM BETWEEN TOP OF STUDS AND BOTTOM BY WIDTH REQ'D. @ 24" O.C.
OF STEEL DECK AND TOP OF WALL OF DECK WITH NONCOMBUSTIBLE FIRE SCREWED TO ROOF DECK FOR
WITH NONCOMBUSTIBLE MATERIAL RATED MATERIAL SECURING RUNNER
FIRESTOP SEALANT AND BACKER ROD ROOF OR FLOOR DECK
G G

1"

OR AS REQ'D BY MFR
TOP OF CMU OR STUDS

6"
GYP. BD. APRON SECURED AS
DEFLECTION TRACK (SEE DETAILS RECOMMENDED BY MANUF.
THIS SHEET)
FIRE RATED DEFLECTION TRACK
PROVIDE SPART-IN EXPANDING SYSTEM TO ALLOW FOR 1"
NONCOMBUSTIBLE SEALANT, DEFLECTION UNLESS NOTED
TYP. OTHERWISE (APPROVED BY MTL.
BATT INSULATION WHERE STUD MANUF.)

F F

1" MIN.
PROVIDE 1" MINIMUM COMPRESSIBLE REQUIRED BY WALL TYPE GYPSUM BOARD, TYP., BOTH SIDES
NONCOMBUSTIBLE MATERIAL UNDER JOIST STL. STUD
OR BEAM TO ALLOW FOR MOVEMENT.
CMU OR GYP
WALL BEYOND

GP# 21553
JOIST OR BEAM. PERP. TO WALL JOIST OR BEAM. PERP TO DECK
E7 1 1/2" = 1'-0" E4 1 1/2" = 1'-0"

E E

WALL TYPES AND WALL TERMINATION DETAILS


FILL IN FLUTES IN STEEL DECK 18 GAUGE STL. PLATE, 8" LONG
WITH NONCOMBUSTIBLE BY WIDTH REQ'D. @ 24" O.C.
2X2X1/4" STL ANGLE BETWEEN
ROOF DECK ROOF DECK SMOKE SEAL MATERIAL SCREWED TO ROOF DECK FOR
ROOF DECK STL BEAMS OR JOISTS @ 6' OC
SECURING RUNNER
ROOF DECK
FILL IN FLUTES IN STEEL DECK
ROOF OR FLOOR DECK
WITH NONCOMBUSTIBLE SMOKE 4" MIN
SEAL MATERIAL
4" MIN

CITY OF BALTIMORE, MARYLAND


1"
1"

FILL IN FLUTES IN STEEL DECK IN AREA


FILL IN FLUTES IN STEEL DECK IN AREA BETWEEN OP OF TRACK AND BOTTOM OF
2 1/32" MIN

FILL IN FLUTES IN STEEL DECK IN AREA BETWEEN TOP OF BEAM AND BOTTOM DECK WITH COMPRESSIBLE
D FILL IN FLUTES IN STEEL DECK IN AREA
BETWEEN TOP OF BEAM AND BOTTOM
BETWEEN TOP OF TRACK AND BOTTOM OF
DECK WITH COMPRESSIBLE
OF DECK WITH COMPRESSIBLE NONCOMBUSTIBLE SMOKE SEAL MATERIAL D
NONCOMBUSTIBLE SMOKE SEAL

HOLABIRD ACADEMY PK-8


OF DECK WITH COMPRESSIBLE NONCOMBUSTIBLE SMOKE SEAL MATERIAL MATERIAL
NONCOMBUSTIBLE SMOKE SEAL PROVIDE COMPRESSIBLE STEEL JOIST - SEE STRUCT. DWGS.
STEEL BEAM - SEE STRUCT. DWGS. DEFLECTION TRACK SYSTEM TO
MATERIAL STEEL JOIST - SEE STRUCT. DWGS. NONCOMBUSTIBLE SMOKE SEAL
2 LAYERS OF 5/8" GYP. BD. DEFLECTION TRACK SYSTEM TO ALLOW FOR 1" DEFLECTION UNLESS
STEEL BEAM - SEE STRUCT. DWGS. MATERIAL BETWEEN TOP OF COMPRESSIBLE FILLER, TYP
W/ STAGGERED JOINTS ALLOW FOR 1" DEFLECTION UNLESS NOTED OTHERWOSE (APPROVED BY
2 LAYERS OF 5/8" GYP. BD. DEFLECTION TRACK SYSTEM TO MASONRY AND STEEL DECK
DEFLECTION TRACK SYSTEM TO NOTED OTHERWISE (APPROVED BY MET STUD MANUF)
W/ STAGGERED JOINTS ALLOW FOR 1" DEFLECTION UNLESS
3"x5"x1/4"x6" LONG BENT STL. PLATE WELDED ALLOW FOR 1" DEFLECTION UNLESS MTL. STUD MANUF.)
NOTED OTHERWISE (APPROVED BY 3"x4"x1/4"x6" LONG STL. ANGLE AT EA.
TO BEAM AT 4' O.C. AT ALTERNATING SIDES, NOTED OTHERWOSE (APPROVED BY GYP BD BOTH SIDES TYP, DO NOT
1" MIN

MTL. STUD MANUF.) SIDE OF WALL WELDED TO ANGLE


TYP., UNLESS INDICATED OTHERWISE ON MET STUD MANUF) ATTACH TO DEFLECTION TRACK
1" MIN.

BETWEEN STRUCTURE UNLESS


STRUCTURAL DWGS. 2 1/1" X 2 1/2" X 3/16" STL ANGLE OTHERWISE INDICATED ON
BRACING TO TOP CHORD OF STRUCTURAL DWGS.
1"
3"

STEEL STUDS

8"
ADJACENT JOIST OR BM GYP BD BOTH SIDES TYP, DO NOT
PROVIDE COMPRESSIBLE ATTACH TO DEFLECTION TRACK
NONCOMBUSTIBLE SMOKE SEAL DEFLECTION TRACK SYSTEM TO ALLOW FOR
BATT INSULATION WHERE

2"
MATERIAL BETWEEN TOP OF MASONRY 1" DEFLECTION UNLESS NOTED OTHERWISE
3"x5"x1/4"x6" LONG BENT STL. PLATE WELDED REQUIRED BY WALL TYPE
C AND STEEL STEEL STUDS (APPROVED BY MTL. STUD MANUF.) C
8"

TO BEAM AT 4' O.C. AT ALTERNATING SIDES,


TYP., UNLESS INDICATED OTHERWISE ON
STRUCTURAL DWGS.
BATT INSULATION WHERE
5/8" GYP BD SPACER STRIP REQUIRED BY WALL TYPE

2 ANCHOR POINTS, MIN.

DATE DESCRIPTION

CEILING AS SCHEDULED
CEILING AS SCHEDULED CEILING AS SCHEDULED
CEILING AS SCHEDULED CEILING AS SCHEDULED
CEILING AS SCHEDULED
B B

NON-RATED CMU WALL NON-RATED CMU WALL NON-RATED CMU WALL NON-RATED STUD WALL NON-RATED STUD WALL A-3.20
ALIGNED UNDER A BEAM ALIGNED UNDER A JOIST PARALLEL TO STRUCT. ALIGNED UNDER A BEAM ALIGNED UNDER A JOIST NON-RATED STUD WALL TO DECK
A18 1 1/2" = 1'-0" A16 1 1/2" = 1'-0" A13 1 1/2" = 1'-0" A10 1 1/2" = 1'-0" A7 1 1/2" = 1'-0" A4 1 1/2" = 1'-0"
03/13/2017
BID SET
A © GRIMM AND PARKER, P.C. 2014 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
© GRIMM AND PARKER, P.C. 2014

A13
A-4.2a
EX1 EX2 1 2 3 4 5 5.1 5.8 EX3 6 7 8 8.2
F12 / A-4.1

ROOF LADDER
PHOTOVOLTAIC ARRAY
PHOTOVOLTAIC A4
ARRAY BUILDING EXPANSION JOINT
A-4.9
M T.O. ICF 2 STORY M
35' - 0"
T.O. BRICK
32' - 0"
JB CLASSROOMS
29' - 4"
MECHANICAL
ACCESS STAIR TO ROOM -
ROOM 2101 CENTRAL
2101
WOMEN MECH MECH. LEVEL

10' - 4"
10' - 0"
CORRIDOR 2301 2100 CENTRAL

9' - 8"
FLEX

8' - 0"
2300 BEYOND
19' - 4"
L SECOND FLOOR