SHOP DRAWING

SUBMITTAL REVIEW COMMENTS


DATE REVIEWED: November 18, 2014
JOB NAME: Englewood Community Recreation Center
JOB NUMBER: 2014.01.0179 SPEC SECTION: 23 7200
DATE RECEIVED: November 17, 2014 SUBMITTED BY: Trane

This review was performed only for general conformance with the design concept of the project and
general compliance with the information given in the Contract Documents. Modifications or comments
made on the shop drawings during this review do not relieve the contractor from compliance with the
requirements of the plans and specifications. Approval of a specific item does not include approval of
the assembly of which the item is a component. Contractor is responsible for: dimensions to be
confirmed and correlated at the jobsite; information that pertains solely to the fabrication processes or
to the means, methods, techniques, sequences, and procedures of construction; coordination of the
work of all trades; and for performing all work in a safe and satisfactory manner. Deviations in submittal
copies from the copy located in the Engineer's Office are not acceptable.

Name: Aaron Zimmerman Date Reviewed: November 18, 2014

Signature:

ACTION CODE KEY: 1 – No Exceptions Taken 4 – Revise and Resubmit


2 – Not Acceptable 5 – Submit Specified Item
3 – Furnish as Corrected 6 – Not Reviewed
ITEM ACTION REMARKS
(see action code above)

HRU-1 1
HRU-2 1

Page 1 of 1
Submittal Checklist v1-0

Job Name: Englewood Community Rec Job Number: ____________


_________________ PR-13005

Submittal Checklist
In a continuing effort to improve the success and quality of our projects, this checklist is provided to
highlight potential issues. Engineers and Contractors please review to ensure that these items will not
affect this job.

Submittal
XeteX Approval
Initial Below Initial Below
Ref Dwgs
ALK Access Doors
Please confirm the location of access doors and panels. Are they against a
wall or off the side of the roof, etc…Ref: Unit Drawing.
N/A External Connections – Location and Path
Please confirm the job site power, voltage, and phase.
Ref: Electrical Diagram & Power Calculation.

Please confirm the routing of the power to the unit:


N/A • Outside the unit, i.e. exterior routing
• Internal to the unit, i.e. chase routing
• Location of the electrical panel(s).
Ref: Unit Drawing.

Please confirm the coil header location:


N/A • Extending outside of the unit, front or backside
• Internal to the unit with or without a chase
Ref: Unit Drawing.

Please confirm the routing of the drains from the unit.


External • Outside the unit, i.e. exterior routing
ALK
• Internal to the unit, i.e. chase routing
Ref: Unit Drawing.

On gas fired units, please confirm the routing (internal/external) of the gas
N/A line, type of gas (NG/LP), and the head pressure at the installation location.
Ref: Unit Drawing, Performance Specification, and Heater Cut Sheet.

On indirect gas fired units, please confirm the location of the combustion air
N/A and flue connections.
Ref: Unit Drawing.

End Duct Connections for Outside Air, Supply Air, Return/Relief Air, and
ALK Exhaust Air
Please confirm the ducting locations of the air streams leading to and
running from the unit. Ref: Unit Drawing.
• End
• Bottom
• Top
• Side

Z Continued on next page Z

1
Submittal Checklist v1-0

Submittal
XeteX Approval
Initial Below Initial Below
N/A Roof Top Units – Roof Curbs
Please confirm the source of the roof curbs, type, and size.
Ref: Construction Specification, Unit Drawing, & Curb Drawing.

Please confirm the duct connection is flush with the top of roof curb or 2” to
N/A 6” above the curb.
Ref: Construction Specification, Unit Drawing, & Curb Drawing.
N/A Please confirm the locations of intake and exhaust hoods.
Ref: Unit Drawing.

Sectioned Unit Size


ALK
Please confirm the building access points are large enough to pass the unit.
• Sectioned unit
• Single lift unit
Ref: Unit Drawing and Performance Specification.

Ref Dwg Please confirm the mounting location can accommodate the unit length,
ALK width, height, and weight.
Ref: Unit Drawing and Performance Specification.
HRU-1,2
ALK Unit Tagging
Please confirm the units are identified and tagged correctly.
Ref: Submittal Cover Sheet, and Performance Specification.

N/A Controls and Sequence


Please confirm the mode-of-operation: i.e. frost control, heating, cooling,
occupied, unoccupied, etc...
Ref: Electrical Drawing and Sequence of Controls Specification.

N/A Please confirm controls user-interface: central BMS, remote panel, or


standalone. If BMS, then does controller requires an network IP, MAC, or
device address
Ref: Sequence of Controls Specification, Wiring Diagram, & Construction Specification.

Engineer’s Approval Stamp Contractor’s Approval Stamp

11/18/2014 2014.01.0179

Other Approval Stamp Other Approval Stamp

2
Heat - - Changer
by XeteX
Air-to-Air Heat Recovery Systems

SUBMITTAL
Date: Thursday, November 13, 2014
Job Name: Englewood Comm. Rec Center Your PO #:
Location: , CO XeteX Project #: PR- 13005
Engineer:
Sales Rep: The Trane Company - Denver Mark Redman
445 Bryant St. Unit 5
Denver, CO 80204-
(303) 228-3300
Contractor:
Equipment: Tag Qty Model
HRU-1 1 XC - 40(35) - 72 - E
HRU-2 1 XC - 30(24) - 36 - E

The Equipment identified in this submittal is on production hold for


approval. The equipment will not be entered into production until XeteX
receives one complete copy of the approved submittals for our files.

XeteX, Inc.
9405 Holly Street NW
Minneapolis, MN 55433
(612) 724-3101
(612) 724-3372 (Fax)
Construction Spec v 3.0
Construction Specification
Unit Tag: HRU-1-2 (11-17-14)
Project Name: Englewood Community Rec Center
Project Location: CO

P: Provided by XeteX M: Mounted by XeteX


Unit Model Blowers/Motors
XC - Exchanger Only With Case P M
Modular (Indoor) Construction 33) SA Blower -
Air-to-Air Heat Exchanger 34) SA Motor - NEMA Frame
P M 35) SA Motor Efficiency -
1) Aluminum Flat Plate - Epoxy Coated 36) SA Drive -
2) 37) SA Isolators -
Unit Construction - Formed Sheet Metal 38) EA Blower -
P M 39) EA Motor - NEMA Frame
3) Heavy Duty Case - 18ga G90 Galv. 40) EA Motor Efficiency -
4) Double Wall Constr. - 16ga Alum 41) EA Drive -
5) Unit Wall Insulation - Mineral Wool - 1.0" 42) EA Isolators -
6) Unit Floor - .080" Alum (14ga) - 1.0" Ins. 43) Drive Service Factor -
7) Formed Sheet Metal Base Frame 44) Adjustable Motor Base
8) Access Doors w/Galvanized Hinges 45)
9) Access Door Windows - 46)
10) Lifting Lugs 47)
11) All Welded Drain Pan - 304 SS 48)
12) MPT Drains Heating and Cooling Equipment
13) Plumbing / Electrical Chase P M
14) Sloped Roof w/Capped Seams 49) Heating Coil -
15) w/Birdscreens 50) Cooling Coil -
16) Insulated Roof Curb – 51) Gas Fired Heater -
17) Misc. Options - 52)
18) Misc. Options - 53)
19) Misc. Options - 54)
20) Unit Electrical
21) Units will need to be put together on site P M
Filters 55) Non-Fused Disconnect -
P M 56) Branch Circuit Distribution Block
22) Outside Air - 57) Branch Circuit Circuit Breakers
23) Return Air - 58) Electrical Panel
24) 59) 120v GFI (Separate 120v Circuit Required)
25) 60) Service Lights (Separate 120v Circuit Required)
26) 61)
Dampers (Low Leakage) - Miscellaneous Options
P M 62) ETL Listed Unit
27) Outside Air Shut-off Dmpr 63) 1 Year(s) Limited Warranty
28) Exhaust Air Shut-off Dmpr 64) Extra Set(s) of Blower Belts
29) Outside Air Face & Bypass Dmpr 65) Extra Set(s) of Filters
30) Coil Face & Bypass Dmpr 66) Start Up - By Others
31) Recirculating Air Dmpr 67)
32) 68)

Notes:
1. Inner lining to be Aluminum
2. Units broken down to fit through door opening 36" by 78". Field reassembly required.
3. Filters provided by others.

11/17/2014 Page 1 of 3
Controls Spec v 3.0

Controls Specification
Unit Tag: HRU-1-2 (11-17-14)
Project Name: Englewood Community Rec Center
Project Location: CO

F: Provided/Controlled by XeteX O: Provided/Controlled by Others I: Provided by Others, Installed by XeteX


Controls Communication Heating Controls
Device Device Signal
1) DDC Controller - 32) Heating Coil Valve -
2) HMI - 33) Staging Relays -
3) 34) Burner Control -
Heat Exchanger Controls - 35)
Device Signal 36)
4) Frost Control - Cooling Controls
5) Warm Weather Economizer - Device Signal
6) Summer Mode Changeover - 37) Cooling Coil Valve -
7) Heat Wheel VFD - 38) Staging Relays - DX Coil
8) 39) Hot Gas Reheat -
9) 40)
Supply Air Motor Controls 41)
Device Signal Airflow Monitoring
10) Device Signal
11) VFD Options - 42) OA Airflow Monitor -
12) VFD Options - 43) RA Airflow Monitor -
13) VFD Panel 44) SA Airflow Monitor -
14) 45) EA Airflow Monitor -
15) 46)
Exhaust Air Motor Controls Control Sensors
Device Signal Device Signal
16) 47) Outside Air -
17) VFD Options - 48) Return Air -
18) VFD Options - 49) Supply Air (After HX) -
19) VFD Panel 50) Exhaust Air -
20) 51) Heating Discharge -
21) 52) Aux. Heating Discharge -
Filter Options 53) Cooling Discharge -
Device Signal 54) Room Sensor -
22) 55) Pressure Transducer -
23) 56) Programmable Remote Stat
Damper Actuators 57)
Device Signal 58)
24) Outside Air Shut-off Dmpr - Remote Panel Options
25) Exhaust Air Shut-off Dmpr - Device
59) On-Off Switch
26) Outside Air F&B Dmpr -
60) Fan Indicator Lights
27) Coil F&B Dmpr - 61) Fan Switches
28) Recirculating Air Dmpr - 62) Dirty Filter Lights
29) Occupied/Unoccupied Switch 63) Low Temp Limit Light
30) 64)
31)
Miscellaneous Options
Device Signal
65)
66)
Notes:
Controls, sensors provided by others.

11/17/2014 Page 2 of 3
PERFORMANCE SPECIFICATION
11/13/2014
UNIT TAG : HRU-1 PROJECT: Englewood Community Rec. Center
MODEL : XC- 40-72-E LOCATION: CO Elevation: 5375 ft

UNIT SPECIFICATIONS UNIT OPTIONS


AIRFLOW COOLING HEATING HEATING
SUPPLY EXHAUST COIL TYPE
AIRFLOW : 12000 SCFM 12000 BYPASS : 0% % 0% 0%
12000 12000 PERCENT GLYCOL :
EXTERNAL. S.P. : IN. WG ROWS :
TOTAL S.P. : 1.00 IN. WG 1.00 FINS : FPI
BLOWER TYPE : TYPE 0 HEIGHT : INCHES
DRIVE TYPE : DRIVE WIDTH : INCHES
BLOWER SIZE : DIAMETER AIR VELOCITY : FPM
MOTOR HP : HP AIR P.D. : IN. WG
BHP : BHP
RPM : RPM
VOLTAGE : VOLTS
PHASE : PHASE ENT. TEMP DB : °F
ENT. TEMP WB : °F
ELEMENT SIZE 40(35) LEAV. TEMP DB : °F
LENGTH (in.) : 72 LEAV. TEMP WB : °F
1 OR 2 PASS : 1 MIXED AIR DB : °F
Frost Ctrl Stpt (°F DB) : 35 MIXED AIR ABS HUMIDITY : grains/lb
Frost Ctrl SA (°F DB) : CAPACITY : MBH
Frost Bypass (%) : TONS COOLING : KW
IDEC (Y or N) : N SENS. HEAT RATIO :

EXCHANGER PERFORMANCE

SUPPLY AIR WINTER SUMMER


ENTERING TEMP : -5.0 °F DB 93.0
ENTERING WB : -5.0 °F WB 59.0
ENTERING % RH : 100.0% % RH 13.2%
ENT. ENTHALPY : -0.40 BTU/LB 28.18
LEAVING TEMP : 50.6 °F DB 88.9
LEAVING WB : 32.7 °F WB 57.7
LEAV. ENTHALPY : 12.97 BTU/LB 27.20
FACE VELOCITY : 652 FPM 781
AIR P.D. : 0.75 IN. WG 0.86
ENERGY RECOVERED : 721 MBH 53

EXHAUST AIR
ENTERING TEMP : 85.0 °F DB 85.0
ENTERING WB : 69.0 °F WB 69.0
ENTERING % RH : 47.4% % RH 47.4%
ENT. ENTHALPY : 36.89 BTU/LB 36.89
LEAVING TEMP : 51.9 °F DB 89.1 FILTERS
LEAVING WB : 51.8 °F WB 70.1
LEAV. ENTHALPY : 23.32 BTU/LB 37.89
FACE VELOCITY : 781 FPM 781
AIR P.D. : 0.86 IN. WG 0.88

DAMPERS ACUTATORS
Primary Energy Recovery Effectivnesses*
Winter Summer
Sensible : 62.0 % 51.0

*Effectiveness is calculated according to ASHRAE and AHRI 1060-2005. The occurrence of condensation
may cause values of greater than 100%. Contact Factory for further information.

Notes:

UNIT PHYSICAL DATA


HEIGHT (IN.) 64 LENGTH (IN.) 60 WIDTH (IN.) 74 WGT (lbs) 1800
           

 
                          

     ! " # # $ % ' ( ) * * * ! + , -

B 9 : ; < G K

     &   "  ' ( ) * * * ! + , -

C ; ? G K
= >

! " . .  ! " # # $ % ' ( ) * * * ! + , -

! " . .  &   "  ' ( ) * * * ! + , -

D ; G K
@ @ =

!   / $ 

O L P J F Q R P S G K H

0 1 2 2

9 : ; ? U
@ T

E F G H I J 9 A L M N
>

3 $  4 1   5  6 7 8 6 ,   

E G K J F V Q a b b F V

W X Y Y Z [ \ ] ^ X _ ` W X Y Y Z [ \ ] ^ X _ `

c d e f g h d i j g k l m n o p q r s t q r s u v r s t q r s w

c d e f g h d i x f e l m n o p q r s y u r s q u r s y u r s w

c d e f g h d i z f n { e h | f } m ~ h  h e k € s s r s s  ‚ ƒ r v y  € v r „ „  ‚ ƒ r v y 

c d e f g h d i j f … † ‡ h d e p q r s y „ r ƒ v q r ‚ y „ r ƒ w

c d e f g h d i } m ~ h  h e k z { e h ‡ q r € y € s ‚ r u s v ƒ r € s € s ‚ r u s i g { h d ˆ ‰ n o

c d e f g h d i c d e Š { n ‹ k p s r ‚ s v y r t u „ t r € t v y r t u l Œ  ‰ n o

Ž f { | h d i j g k l m n o q s r y q € r u t t r u t u r € w

Ž f { | h d i x f e l m n o v „ r ƒ q € r t q ƒ r ƒ ƒ s r € w

Ž f { | h d i z f n { e h | f } m ~ h  h e k ƒ r t s  u u r ‚ y  € q r s s  ‚ € r y v 

Ž f { | h d i j f … † ‡ h d e p q r s q € r ƒ v q r ‚ y „ r ƒ w

Ž f { | h d i } m ~ h  h e k z { e h ‡ q r € y y u r u u v ƒ r € s € s ‚ r u s i g { h d ˆ ‰ n o

Ž f { | h d i c d e Š { n ‹ k € „ r u ƒ „ v r v „ „ ƒ r „ s v ƒ r t u l Œ  ‰ n o

  e m { n w {  f ‘ f n ‡  h e k y q „ ƒ t € ƒ u „ ƒ t € ’ e ‰ ~ h d

  e m { n † g f ˆ ˆ m g f j g ‡ ‹ s r ƒ q s r t y s r t u s r t t h d r x “

”
Š { d d f n ‘ f n ‡  h e k • m e € – y ƒ ƒ € – t v q € – u € ƒ € – u s v ’ e ‰ ~ h d

”
‡ d  f d ˆ { e f „ ƒ € r v — ‰  n o ‰ Š g

”
‡ d  f d ˆ { e f Œ f ~ ‹ y „ r u — ‰  w

˜
f d ˆ h o n f c ’ ’ f  e h | f d f ˆ ˆ y „  q € 

Œ ‡ e { n c d f g i k z f  ‡ | f g f  ƒ „ € r t ‚ q v r s v ™ l }

˜
c ’ ’ f  e h | f d f ˆ ˆ h ˆ  { n  m n { e f  {   ‡ g  h d i e ‡  } z  c  — j

” ˜
w g ‡ ˆ e ‡ d e g ‡ n f e ‹ ‡ h d e v q r s w

 } z š € s y s p „ s s q p  ‡ d  f d ˆ { e h ‡ d ~ { k g f ˆ m n e h d | { n m f ˆ

”
w g ‡ ˆ e ‡ d e g ‡ n Ž f { | h d i j g k l m n o — ‰  w

”
i g f { e f g e Š { d € s s  r ‡ d e {  e e Š f w {  e ‡ g k ’ ‡ g ’ m g e Š f g

l k ‹ { ˆ ˆ — ‰  

h d ’ ‡ g ~ { e h ‡ d r

— ‡ e f ˆ  

O I › K F œ  ž P Ÿ œ

F b P G L œ
PERFORMANCE SPECIFICATION
11/13/2014
UNIT TAG : HRU-2 PROJECT: Englewood Community Rec. Center
MODEL : XC- 30-36-E LOCATION: CO Elevation: 5375 ft

UNIT SPECIFICATIONS UNIT OPTIONS


AIRFLOW COOLING HEATING HEATING
SUPPLY EXHAUST COIL TYPE
AIRFLOW : 3500 SCFM 4000 BYPASS : 0% % 0% 0%
3500 4000 PERCENT GLYCOL :
EXTERNAL. S.P. : IN. WG ROWS :
TOTAL S.P. : 0.90 IN. WG 1.15 FINS : FPI
BLOWER TYPE : TYPE 0 HEIGHT : INCHES
DRIVE TYPE : DRIVE WIDTH : INCHES
BLOWER SIZE : DIAMETER AIR VELOCITY : FPM
MOTOR HP : HP AIR P.D. : IN. WG
BHP : BHP
RPM : RPM
VOLTAGE : VOLTS
PHASE : PHASE ENT. TEMP DB : °F
ENT. TEMP WB : °F
ELEMENT SIZE 30(24) LEAV. TEMP DB : °F
LENGTH (in.) : 36 LEAV. TEMP WB : °F
1 OR 2 PASS : 1 MIXED AIR DB : °F
Frost Ctrl Stpt (°F DB) : 35 MIXED AIR ABS HUMIDITY : grains/lb
Frost Ctrl SA (°F DB) : CAPACITY : MBH
Frost Bypass (%) : TONS COOLING : KW
IDEC (Y or N) : N SENS. HEAT RATIO :

EXCHANGER PERFORMANCE

SUPPLY AIR WINTER SUMMER


ENTERING TEMP : -5.0 °F DB 93.0
ENTERING WB : -5.0 °F WB 59.0
ENTERING % RH : 100.0% % RH 13.2%
ENT. ENTHALPY : -0.40 BTU/LB 28.18
LEAVING TEMP : 57.3 °F DB 88.4
LEAVING WB : 36.1 °F WB 57.5
LEAV. ENTHALPY : 14.56 BTU/LB 27.07
FACE VELOCITY : 507 FPM 616
AIR P.D. : 0.68 IN. WG 0.80
ENERGY RECOVERED : 235 MBH 17

EXHAUST AIR
ENTERING TEMP : 85.0 °F DB 85.0
ENTERING WB : 69.0 °F WB 69.0
ENTERING % RH : 47.4% % RH 47.4%
ENT. ENTHALPY : 36.89 BTU/LB 36.89
LEAVING TEMP : 52.4 °F DB 89.0 FILTERS
LEAVING WB : 52.3 °F WB 70.0
LEAV. ENTHALPY : 23.64 BTU/LB 37.88
FACE VELOCITY : 694 FPM 694
AIR P.D. : 0.98 IN. WG 1.01

DAMPERS ACUTATORS
Primary Energy Recovery Effectivnesses*
Winter Summer
Sensible : 69.0 % 57.0

*Effectiveness is calculated according to ASHRAE and AHRI 1060-2005. The occurrence of condensation
may cause values of greater than 100%. Contact Factory for further information.

Notes:

UNIT PHYSICAL DATA


HEIGHT (IN.) 50 LENGTH (IN.) 50 WIDTH (IN.) 38 WGT (lbs) 1000
           

 
                          

      ! " " # $ & ' ( ) ) + , -

@ 7 8 9 : E I

      %   !   * ' ) ) ) + , -

A ; < E I

! . .   ! " " # $ & ' ( ) ) + , -

! . .   %   !   * ' ) ) ) + , -

B = > 9 ? E I

  / # 

M J N H D O P N Q E I F

0 1 2 2

7 = R < 9 S T

C D E F G H > ; < J K L

3 #  4 1   5  ( & 6 ( ,   

C E I H D U O ` a a D U

V W X X Y Z [ \ ] W ^ _ V W X X Y Z [ \ ] W ^ _

b c d e f g c h i f j k l m n o p q r s p q r t u q r s p q r v

b c d e f g c h w e d k l m n o p q r x t q r p t q r x t q r v

b c d e f g c h y e m z d g { e | l } g ~ g d j  r r q r r €  ‚ q u x €  u q ƒ ƒ €  ‚ q u x €

b c d e f g c h i e „ … † g c d o p q r x ƒ q ‚ u p q  x ƒ q ‚ v

b c d e f g c h | l } g ~ g d j y z d g † p q  x  r  q t r u ‚ q  r  r  q t r h f z g c ‡ ˆ m n

b c d e f g c h b c d ‰ z m Š j o r q  r u x q s t ƒ s q  s u x q s t k ‹ Œ ˆ m n

 e z { g c h i f j k l m n p ‚ q u p ƒ q  s s q  s t q r v

 e z { g c h w e d k l m n u x q  p ƒ q u p ‚ q p ‚ r q r v

 e z { g c h y e m z d g { e | l } g ~ g d j x q  ƒ € t t q  x €  p q ƒ x €   q x s €

 e z { g c h i e „ … † g c d o p q r p ƒ q ƒ u p q  x ƒ q ‚ v

 e z { g c h | l } g ~ g d j y z d g † p q  x ‚  q ƒ t u ‚ q  r  r  q t r h f z g c ‡ ˆ m n

 e z { g c h b c d ‰ z m Š j   q p x ƒ u q x  ƒ ‚ q r ‚ u ‚ q s s k ‹ Œ ˆ m n

Ž  d l z m v z  e  e m †  g d j p r ‚ x t  x  x x t  ‘ d ˆ } g c

Ž  d l z m … f e ‡ ‡ l f e i f † Š r q x s r q t s r q s r  q r  g c q w ’

“
‰ z c c e m  e m †  g d j ” l d  • u t u  • ‚ u ƒ  • p s   • ‚ t p ‘ d ˆ } g c

“
† c ~ e c ‡ z d e s ‚ q  – ˆ Ž m n ˆ ‰ f

“
† c ~ e c ‡ z d e ‹ e } Š x ƒ q t – ˆ Ž v

—
e c ‡ g n m e b ‘ ‘ e  d g { e c e ‡ ‡ x t € p ‚ €

‹ † d z m b c e f h j y e  † { e f e ~ ƒ u p q x x  ‚ q p u ˜ k |

—
b ‘ ‘ e  d g { e c e ‡ ‡ g ‡  z m  l m z d e ~ z   † f ~ g c h d † Ž | y Ž b Ž – i

“ —
v f † ‡ d † c d f † m e d Š † g c d u p q r v

Ž | y ™  r x r o ƒ r r p o  † c ~ e c ‡ z d g † c } z j f e ‡ l m d g c { z m l e ‡

“
v f † ‡ d † c d f † m  e z { g c h i f j k l m n – ˆ Ž v

“
h f e z d e f d ‰ z c  r r € q † c d z  d d ‰ e v z  d † f j ‘ † f ‘ l f d ‰ e f

k j Š z ‡ ‡ – ˆ Ž €

g c ‘ † f } z d g † c q

– † d e ‡ Ÿ

M G š I D › œ  N ž ›

D a N E J ›
Heat-X-Changer
Sequence of Controls Rev.#: 1.0
Date: 11-13-14
Job Name: Englewood Community Rec Center
Job#: PR-13005
Unit Tag: HRU-1,2
Unit Models: XC-40-72, XC-30-36

No controls are provided for these units.

Page 1 of 1
XeteX
XeteX
XeteX, Inc.’s Limited Warranty
Scope of Warranty
XeteX, Inc. (hereinafter “XeteX”) warrants to the original purchaser that all products sold or distributed by
XeteX will be free from defects in material and workmanship for a period of one year from the date of original
installation, but in no event, for longer than eighteen months from the date of shipment from our factory, if
installed, maintained, and operated under normal conditions of service in accordance with instructions of
XeteX. This warranty applies to all products sold or distributed by XeteX in the United States or Canada unless
XeteX contracts in writing for specific alternative warranty terms.
XeteX will repair or replace, at XeteX’s option, F.O.B. Minneapolis, Minnesota any of the XeteX products or
components that XeteX determines, after examination at its factory in Minneapolis, Minnesota, to have been
defective.
Exclusions
The foregoing warranty does not apply to or include:
 Costs involved in the identification or diagnosis of product defects or other problems.
 Labor costs incurred in the removal, replacement, or adjustment of defective products or components.
 Transportation costs incurred in returning products or components to XeteX in Minneapolis, MN or in
shipping replacement products or components.
 Correction of conditions arising from improper or incorrectly connected air duct piping, wiring, power
supply, blown fuses, freezing, or any other condition resulting from improper installation, operation or
maintenance by anyone other than an XeteX employee or authorized XeteX contractor.
 XeteX products or components that have been tampered with or altered, subject to misuse, abuse, or
inadequate maintenance, or upon which any serial number has been altered, defaced or removed.
 Damage resulting from any contingency beyond XeteX’s control.
Additional Terms and Conditions

This warranty may not be assigned or transferred without XeteX’s prior written authorization. THIS
WARRANTY CONSTITUTES THE OWNER’S SOLE REMEDY. In no event and under no
circumstances shall XeteX be liable to the original purchaser or any other party for any incidental,
indirect, special, contingent, consequential, or secondary damages due to or resulting from the design,
construction, installation, servicing, or operation of the XeteX products or components or for any other
cause whatsoever whether the theory be breach of this or any other warranty, negligence, strict liability
in tort, or any other theory. In no event shall XeteX be liable to the original purchaser or any other
person for any amount in excess of the amount paid to XeteX by the original purchaser. XeteX neither
assumes nor authorizes any person to assume for it any other obligation or liability in connection with the
warranted XeteX products or components. No change to this Warranty shall be effective unless specifically
agreed to by XeteX on the face of the XeteX invoice.

The warranties in this document are exclusive and in lieu of all other warranties and remedies of any
kind, expressed or implied, and all other obligations or liabilities on the part of XeteX. XETEX
HEREBY DISCLAIMS ANY AND ALL OTHER WARRANTIES FROM ANY CONTRACT OR
TRANSACTION RESULTING FROM XETEX’S QUOTATION OR FROM ANY SALE MADE TO
THE ORIGINAL PURCHASER, INCLUDING WITHOUT LIMITATION, ANY WARRANTY OF
MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. In no event
shall XeteX be liable to the original purchaser or any other person for any amount in excess of the
amount paid to XeteX by the original purchaser.

XeteX, Inc.’s Back Charge Notice


Back Charges of any kind will not be accepted unless pre-authorized in writing by XeteX. XeteX requires
written submission of proposed charges.