FCM1821-A1 Terminal Board

Product Manual

Overview
FCM1821-A1 terminal board is specially designed for FC18 series controllers,easy for
connection.

Technical data
Operation temperature 0 ~ +50℃
Storage temperature -20 ~ +60℃
Humidity ≤95% (40±2℃)
Size 250*50mm

Order information
Type Part No. Name Weight
FCM1821-A1 100734121 FC18 terminal board 0.094Kg

Connection diagram

To Floor repeater display、


To loop 1/2 To inerlocking panel To inerlocking panel channel
controller、NAC、Input/Output
channel1-4 5-8

To port J3
of FC18
main board

To port X601 of FC18 line To port J400 of FC18 inter- To power


card To port J200 of locking panel supply
To port X1 of FC18 line To port J1000 of FC18 FC18 interlocking
card main board panel To port J500 of FC18 inter-
locking panel

Building Technologies
Fire safety and security products
Fig-2 FRT connection diagram
Fig-1 Line card connection diagram (the same for
Line 2)
:As a loop, wires from BP1 must end at
Note:
AP1; wires from BS1 must end at AS1. The
connection of field devices (except
FDCL181 isolator) is polarity free

Fig-4 Interlocking panel connection diagram (the same


Fig-3 Network connection diagram
Note: The positive and negative connections for other channels)
must be right. Connect a 120Ω resistor at Note: Ω
:The load range of each input is 24VDC, 600Ω
the end of line. ( It can be set by the two-
digit Dip-switch on the main board, see Ω
– 1.2kΩ
“Dip-switch connection configuration” )

Fig-5 NAC connection diagram

IO-EOL-FC18
FC18 To Input/Output
Red Orange
IO+ 1K

Dry Contact
10K
IO-
Black Black

Output Input

Fig-6 Main board input/output connection diagram

Beijing Siemens Cerberus Electronics Limited © 2009 Copyright by


No.18,XinXi Road, ShangDi Information Industry Base, Beijing Siemens Cerberus Electronics Ltd.
HaiDian District, Beijing, 100085, China Data and design subject to change without notice.
Tel: +10 6296 2255
Fax: +10 6298 7387

Doc. No A6V10244862_b_-- Version b Manual FC18