BILL A: Extra Low Voltage


BILL MHAS OFFICES AT BASEMENT LEVEL, EVANS
1 BUILDING, VALLETTA
ELV INSTALLATIONS
ACCESS CONTROL SYSTEM
BILL OF QUANTITIES

Before materials are ordered, measurements are to


be taken on site and take-off's are to be done in
accordance with approved working drawings.

1.0 Supply and install access controller for the IT Room 1 no.
as specified, on the secure side and above the false
ceiling where possible,suitable to control 1 access
control reader including power supply unit(s), back-
up battery, 230 V power, control and communications
connections. Supply and installation of the cable
connection to the adjacent CAT6 RJ45 outlet shall be
included.
Access controllers controlling more than 1 door will
be considered subject that the price is all inclusive to
meet the specified requirements.

2.0 Supply, install and connect a biometric fingerprint 1 no.


and PIN code reader for the IT Room as specified
including cable and buried PVC conduit to the access
controller.

3.0 Supply and install exit button for protected side of the 1 no.
IT room including cable and pvc conduit to the
access controller.

4.0 Supply and install cable and conduit from the access 1 no.
control reader to the electric door lock of the IT
Room.

5.0 Supply and install conduit only from the future 3 no.
access control reader to the electric door lock.

6.0 Supply, install and connect a pair of magnetic 1 no.


contacts for access controlled door of the IT Room to
signal to the controller that the door is open.

7.0 Supply and install cable and conduit from the access 1 no.
control reader of the IT Room to the door magnetic
contacts.

8.0 Supply and install conduit only from the future access 3 no.
control reader to the door magnetic contacts.

Page 1
Rate (incl. Amount (incl.
Item Description Qty Unit
of VAT) of VAT)
Euro Euro
9.0 Supply and install cable from the access controller of 1 no.
the IT Room to the adjacent CAT6 RJ45 outlet of the
IT network of the building in order to connect it to the
host computer.

10.0 Supply and install conduit, wiring and fire alarm 1 Lump sum
interface to open all doors with fire alarm.

11.0 Set, programme, test, commission and certify the 1 Lump sum
Access Control System to MSA EN 50133 (all the
equipment and the whole installation) including the
supply of all software and software licenses. Test the
system also from the host computer.Train the system
users.

12.0 Supply one set of operation and maintenance 1 Lump sum


manuals for all the Access Control System.

13.0 Supply for approval 3 sets of working drawings in 1 Lump sum


accordance with the latest architectural layouts and
requirements before the order of materials and
before the start of installation works.

14.0 Supply 3 sets of as fitted drawings as prints and one 1 Lump sum
set on compact disk.

Total of Access Control System carried to


summary sheet

Page 2
Rate (incl. Amount (incl.
Item Description Qty Unit
of VAT) of VAT)
Euro Euro

BILL MHAS OFFICES AT BASEMENT LEVEL, EVANS


2 BUILDING, VALLETTA
ELV INSTALLATIONS
FIRE DETECTION AND ALARM SYSTEM
BILL OF QUANTITIES

Before materials are ordered, measurements are to


be taken on site and take-off's are to be done in
accordance with approved working drawings.

1.0 Supply 3 sets of Working Drawings, including a


schematic drawing, in accordance with the latest
architectural layouts, finishes and requirements for
approval before the installation is started. Amend and
correct the drawings in accordance with the
comments of the Engineer for issue of the drawings
for construction. 1 lump sum

2.0 Supply and install analogue addressable fire alarm


panel near the reception as specified including the
telephone dialler, telephone line connection and
power connection. 1 no.

3.0 Supply and install addessable optical type smoke


detector complete with base, below or above false
ceiling as shown on drawing. 37 no.

4.0 Supply and install addessable optical type smoke


detector complete with base, integral sounder and
flasher. 10 no.

5.0 Supply and install remote LED indicating unit on the


underside of false ceiling for the respective optical
smoke detector installed above false ceiling including
the interconnecting cable. 19 no.

6.0 Supply and install addressable heat detector


complete with base. 1 no.

7.0 Supply and install addressable manual call point. 3 no.

8.0 Supply and install external alarm sounder. 1 no.

9.0 Supply, install and connect short circuit isolators. 2 no.

10.0 Supply, install and connect input/output loop interface


units for the interface with other systems (lift and 2
VRV Systems). 3 no.

11.0 Supply and install fire resistant cable clipped to the


ceiling and in buried conduit for downdrops on walls
below the false ceiling:

Page 3
Rate (incl. Amount (incl.
Item Description Qty Unit
of VAT) of VAT)
Euro Euro
2 loops are designated for the basement floor, 1 for
the MHAS offices and one reserved for the future
extension to the rest of the offices in the basement.

11.1 Smoke detectors. 48 no.


11.2 Heat detectors. 1 no.
11.3 Manual call points. 3 no.
11.4 External sounder. 1 no.

12.0 Supply and install fire resistant cable for the following
interconnections from the main fire alarm panel to:

12.1 Lift interface unit. 1 no.


12.2 VRV System interface unit 2 no.

13.0 Inspect, set, programme, test, commission and


certify the fire alarm system as specified. Train the
system users. 1 Lump sum

14.0 Supply and install labels and markings on all devices


and equipment and a wall chart near the fire alarm
panel showing the whole fire alarm system layout.
1 Lump sum

15.0 Supply 3 sets of As Fitted Drawings, including a


schematic drawing, on print and one set on disk as
specified. 1 Lump sum

16.0 Supply one set of operation and maintenance


manuals as specified. 1 Lump sum

Total of the Fire Alarm System carried to


summary sheet

Page 4
Rate (incl. Amount (incl.
Item Description Qty Unit
of VAT) of VAT)
Euro Euro

BILL MHAS OFFICES AT BASEMENT LEVEL, EVANS


3 BUILDING, VALLETTA
ELV INSTALLATIONS
INTRUSION DETECTION AND ALARM SYSTEM
BILL OF QUANTITIES

Before materials are ordered, measurements are to


be taken on site and take-off's are to be done in
accordance with approved working drawings.

1.0 Supply and install an 8 zone control panel in the IT 1 no.


room as specified complete with power connection
and connection to the remote 2 channel automatic
dialler of the fire alarm system.

2.0 Supply and install remote wall mounted key-pad, 3 no.


minimum 4 digits.

3.0 Supply and install wall volumetric combined passive 25 no.


infrared and microwave detector as specified.

4.0 Supply and install internal sounder as specified. 2 no.

5.0 Supply and install external alarm sounder with strobe 1 no.
and battery back-up.

6.0 Supply and install protective key-holder, which will 4 no.


trigger the intrusion alarm, as specified for
emergency exit from an access controlled room by
use of the door key.

7.0 Supply and install cables on cable basket where


shown on drawings and in surface conduit above
false ceiling and in buried conduit below false ceiling
from the control panel to the following devices,
excluding cable basket but including PVC conduit :

7.1 Intrusion detector 25 no.


7.2 Internal sounder 2 no.
7.3 External sounder 1 no.
7.4 Remote key-pad 3 no.
7.5 Protective key holder 4 no.

PANIC ALARM SYSTEM


8.0 Supply and install under desk type panic button as 6 no.
specified complete with reassurance light.

9.0 Supply, install and connect an 8 channel desk type 3 no.


indication panel as specified.

10.0 Supply, install and connect an over door lamp 2 no.


indicator complete with red LED lamp as specified.

Page 5
Rate (incl. Amount (incl.
Item Description Qty Unit
of VAT) of VAT)
Euro Euro

11.0 Supply and install interconnecting cables on cable


basket where this is shown on drawings and in
surface conduit above false ceiling and in buried
conduit below false ceiling for the following devices,
excluding cable basket but including PVC conduit :

11.1 Panic button 6 no.


11.2 Indication panel 3 no.
11.3 Over door lamp indicator 2 no.

GENERAL ITEMS
12.0 Set, programme, test, commission and certify the 1 Lump sum
Intrusion Detection System and the Panic Alarm
System to MSA EN 50131. Train the system users.

13.0 Supply one set of operation and maintenance 1 lump sum


manuals as specified.

14.0 Supply for approval 3 sets of working drawings in 1 lump sum


accordance with the latest architectural layouts and
requirements before the order of materials and
before the start of installation works.

15.0 Supply 3 sets of As Fitted Drawings, including a 1 lump sum


schematic drawing, on print and one set on disk as
specified.

Total of Intrusion Detection and Alarm System


carried to summary sheet

Page 6
Rate (incl. Amount (incl.
Item Description Qty Unit
of VAT) of VAT)
Euro Euro

BILL MHAS OFFICES AT BASEMENT LEVEL, EVANS


4 BUILDING, VALLETTA
ELV INSTALLATIONS
IP VIDEO SURVEILLANCE SYSTEM
BILL OF QUANTITIES

Before materials are ordered, measurements are to


be taken on site and take-off's are to be done in
accordance with approved working drawings.

1.0 Provide a site survey for the IP Video Surveillance


System. 1 no.

2.0 Supply, install and connect an internal, fixed, colour,


true day/night, network (IP), dark dome camera, as
specified complete with varifocal lens, integral infra-
red lighting, local power supply unit, power and video
(CAT6 ) cable connections. 17 no.
The camera shall be mounted on the false ceiling or
ceiling or wall (according to the location) with
concealed wiring.
(Plug-in 230V/12V DC power supply adapters shall
not be accepted - refer to specification).

3.0 Supply, install and connect a rack mounting, 16


channel, network video recorder (NVR) in the 19 inch
security equipment cabinet of the IT room. 2 Lump sum
The price is to include the supply, installation and
connection of patch leads from the patch panels to
the NVR, camera and monitor inputs.

4.0 Supply, install and programme all software required


for the IP Video Surveillance System including the
video management software programme and
software license. 1 Lump sum

5.0 Set, programme, test, commission and certify IP


Video Surveillance System to MSA EN 50132 (all the
equipment and the whole installation). Train the
system users. 1 Lump sum
Commissioning of the IP Video Surveillance System
shall include local viewing of recorded and live
images from the NVR, remote PC viewing from the
MHSA offices and remote viewing via the internet.

6.0 Supply and install signage for the IP Video


Surveillance System as specified. 2 signs

7.0 Supply one set of operation and maintenance


manuals for all the IP Video Surveillance system. 1 Lump sum

Page 7
Rate (incl. Amount (incl.
Item Description Qty Unit
of VAT) of VAT)
Euro Euro
8.0 Supply for approval 3 sets of working drawings in 1 Lump sum
accordance with the latest architectural layouts and
requirements before the order of materials and
before the start of installation works.

9.0 Supply 3 sets of as fitted drawings as prints and one


set on compact disk. 1 Lump sum

Total for IP Video Surveillance System carried to


summary sheet

Page 8
Rate (incl. Amount (incl.
Item Description Qty Unit
of VAT) of VAT)
Euro Euro

MHAS OFFICES AT BASEMENT LEVEL, EVANS BUILDING, VALLETTA

PRICE SUMMARY SHEET

BILL A - ELV INSTALLATIONS


1 ACCESS CONTROL SYSTEM BOQ

2 IP VIDEO SURVEILLANCE SYSTEM BOQ

3 FIRE ALARM SYSTEM BOQ

4 INTRUSION ALARM SYSTEM BOQ

TOTAL PRICE FOR ELV INSTALLATIONS