You are on page 1of 7

Page : C1

Engineer :
© CADE Systems Pty. Ltd.
Ver: 2.50.2381, 4/12/2014

DL about the X-X Axis


Mark : FJ1 Floor Joist - WITH Ceiling (Single Span)
Section Properties for 300x42 SmartLVL 15
CSA = 12600 mm2 Zyy = 88.2 x103 mm3
Zxx = 630.0 x103 mm3 Iyy = 1.85 x106 mm4
Ixx = 94.5 x106 mm4 J = 6.76 x106 mm4
R = 0 m (Pre camber radius)
Crossing Members Properties
Depth/Thickness = 19 mm
0.34 0.34kN/m Width = 100 mm
0.0 5200 Grade = (3000MPa)
Spacing = 100 mm
15 Properties
SPC*FLL/3 (x 1.50 ) F'b F't F's F'c E G F'p F'sj
59 35 4.2 39 15500 775 11.1 5.2
Capacity Factors Ø for
F'b F't F's F'c F'p F'sj
.95 .95 .95 .95 .95 .95
0.26 0.26kN/m Normalisation Factors
0.0 5200 F'b F't F's F'c F'p F'sj MOE MOR
Depth .789 .872 1 1 1 1 1 1
Width 1 1 1 1 1 1 1 1
SPC*UFDL (x 1.20 )

Critical Load Combination is DL+FLL

0.09 0.09kN/m Shear_______________________________________________________


0.0 5200 ________Shear________ Load Type Derived From
BaseCase : 1 0.17 x 1.20 = 0.20
BaseCase : 2 0.47 x 1.20 = 0.56
BaseCase : 3 0.48 x 1.50 = 0.72
SW (x 1.20 ) Total = 1.49 kN
Critical Location at 467mm from the LHE
K1 = 0.57 Applied Lateral Shear 'V' = 1.49 kN
K2 = 1.00
K4 = 1.00
Characteristic strength for shear F's = 4.2 MPa
K5 = 1.00 Allowable Shear Force = 19 kN
K6 = 1.00 Stress Ratio (1.5/19) = 0.08
Design K = 0.54
Cap Fact Ø = 0.95

Moment______________________________________________________
________Moment_______ Load Type Derived From
1.81kN 1.81kN BaseCase : 1 0.27 x 1.20 = 0.32
BaseCase : 2 0.75 x 1.20 = 0.89
BaseCase : 3 0.76 x 1.50 = 1.14
Total = 2.36 kN.m
Critical Location at 2600mm from the LHE
35 mm 35 mm K1 = 0.57 From Analysis, Applied Moment 'M' = 2.36 kN.m
K2 = 1.00
5200 K4 = 1.00 Considering Member Stability
K5 = 1.00 (Temporary Load) / (Total Load) : r <= 0.25
K6 = 1.00
K9 = 1.00
giving Material constant : rho = 1.23
K12b = 1.00 Considering Member Stability
Design K = 0.54
Cap Fact Ø = 0.95 Using Complex Method Derivation (Append (E)) with [ Y-Y axis FREE ]
with Lay Eff = 200mm & h1 = 3.14 (Table E6) & then Eqn. E6(2), Mcr = 192.4 kN.m
Shear Using Cl. C3.2.3, (E6(1)) S1 = 7.47

1.81 with Characteristic strength for bending F'b = 47 MPa


gives an Allowable Moment = 16 kN.m

Stress Ratio = 0.15 <= 1.00 ... OK


0.00

Deflection__________________________________________________
______Deflection_____ Load Type Derived From
BaseCase : 1 0.5 x 1.00 x 2.0 = 1.0
-1.81 BaseCase : 2 1.4 x 1.00 x 2.0 = 2.9
f/F = 0.08 @ 467 BaseCase : 3 1.5 x 1.00 x 2.0 = 2.9
Moment Total = 6.8 mm
Critical Location at 2600mm from the LHE
KsysD = 1.00 Design Span = 5200 mm
Cap Fact Ø = 1.00
Deflection Limit = 15 mm (δ/∆ = 6.8/15 = 0.5 )
Allowable Ratio = 300 (def Ratio =6.8/(5200/300) = 0.39 )

2.36 Dynamics Details


f/F = 0.15 @ 2600 Static Point Load Check
Deflection Current Span = 5200 mm @ 450 mm c/c
Design Floor Width =5200 mm consisting of 19 mm Thick 3000 MPa flooring
Determination of Load Distribution:
Flooring : Ec = 3000 Mpa Tf = 19 mm, Wid = 100 & Space = 450 mm => hc =1.882
Joist : Eb = 15500 Mpa, Ib = 94.5 x106 mm4 => hb = 10.417
Now, with nc = 51
g41 = 0.883 - 0.34 x log(51 x 1.88/10.42 + 0.44) = 0.545
Calculated Deflection = 1.1 mm
Allowable Deflection = 2.0 mm
6.8 Deflection Ratio = 0.55 <= 1.00 therefore OK

δ/∆ = 0.45 @ 2600


Page : C2
Engineer :
© CADE Systems Pty. Ltd.
Ver: 2.50.2381, 4/12/2014

DL+FLL about the X-X Axis


Mark : FJ1 Floor Joist - WITH Ceiling (Single Span)
Section Properties for 300x42 SmartLVL 15
CSA = 12600 mm2 Zyy = 88.2 x103 mm3
Zxx = 630.0 x103 mm3 Iyy = 1.85 x106 mm4
Ixx = 94.5 x106 mm4 J = 6.76 x106 mm4
R = 0 m (Pre camber radius)
Crossing Members Properties
Depth/Thickness = 19 mm
1.01 1.01kN/m Width = 100 mm
0.0 5200 Grade = (3000MPa)
Spacing = 100 mm
15 Properties
SPC*FLL (x 1.50 ) F'b F't F's F'c E G F'p F'sj
59 35 4.2 39 15500 775 11.1 5.2
Capacity Factors Ø for
F'b F't F's F'c F'p F'sj
.95 .95 .95 .95 .95 .95
0.26 0.26kN/m Normalisation Factors
0.0 5200 F'b F't F's F'c F'p F'sj MOE MOR
Depth .789 .872 1 1 1 1 1 1
Width 1 1 1 1 1 1 1 1
SPC*UFDL (x 1.20 )

Critical Load Combination is DL+FLL

0.09 0.09kN/m
Shear_______________________________________________________
________Shear________ Load Type Derived From
0.0 5200 BaseCase : 1 0.17 x 1.20 = 0.20
BaseCase : 2 0.47 x 1.20 = 0.56
BaseCase : 4 1.44 x 1.50 = 2.16
Total = 2.93 kN
SW (x 1.20 )
Critical Location at 467mm from the LHE
K1 = 0.80 Applied Lateral Shear 'V' = 2.93 kN
K2 = 1.00
K4 = 1.00
Characteristic strength for shear F's = 4.2 MPa
K5 = 1.00 Allowable Shear Force = 27 kN
K6 = 1.00 Stress Ratio (2.9/27) = 0.11
Design K = 0.76
Cap Fact Ø = 0.95

Moment______________________________________________________
________Moment_______ Load Type Derived From
BaseCase : 1 0.27 x 1.20 = 0.32
3.57kN 3.57kN
BaseCase : 2 0.75 x 1.20 = 0.89
BaseCase : 4 2.28 x 1.50 = 3.42
Total = 4.64 kN.m
Critical Location at 2600mm from the LHE
K1 = 0.80 From Analysis, Applied Moment 'M' = 4.64 kN.m
35 mm 35 mm K2 = 1.00
5200 K4 = 1.00 Considering Member Stability
K5 = 1.00 (Temporary Load) / (Total Load) : r = 0.74
K6 = 1.00
K9 = 1.00
giving Material constant : rho = 1.23
K12b = 1.00 Considering Member Stability
Design K = 0.76
Cap Fact Ø = 0.95 Using Complex Method Derivation (Append (E)) with [ Y-Y axis FREE ]
with Lay Eff = 200mm & h1 = 3.14 (Table E6) & then Eqn. E6(2), Mcr = 192.4 kN.m
Shear Using Cl. C3.2.3, (E6(1)) S1 = 7.47
with Characteristic strength for bending F'b = 47 MPa
3.57 gives an Allowable Moment = 22 kN.m

Stress Ratio = 0.21 <= 1.00 ... OK


0.00
Deflection__________________________________________________
______Deflection_____ Load Type Derived From
BaseCase : 1 0.5 x 1.00 x 2.0 = 1.0
BaseCase : 2 1.4 x 1.00 x 2.0 = 2.9
-3.57 BaseCase : 4 4.4 x 1.00 x 1.0 = 4.4
f/F = 0.11 @ 467 Total = 8.3 mm
Moment Critical Location at 2600mm from the LHE
KsysD = 1.00 Design Span = 5200 mm
Cap Fact Ø = 1.00
Short Term Deflection = 4.4 mm
Deflection Limit = 9.0 mm (δ/∆ = 4.4/9.0 = 0.5 )
Allowable Ratio = 360 (def Ratio =4.4/(5200/360) = 0.30 )

4.64 Dynamics Details


f/F = 0.21 @ 2600
Deflection Static Point Load Check
Current Span = 5200 mm @ 450 mm c/c
Design Floor Width =5200 mm consisting of 19 mm Thick 3000 MPa flooring
Determination of Load Distribution:
Flooring : Ec = 3000 Mpa Tf = 19 mm, Wid = 100 & Space = 450 mm => hc =1.882
Joist : Eb = 15500 Mpa, Ib = 94.5 x106 mm4 => hb = 10.417
Now, with nc = 51
g41 = 0.883 - 0.34 x log(51 x 1.88/10.42 + 0.44) = 0.545
Calculated Deflection = 1.1 mm
Allowable Deflection = 2.0 mm
8.3
Deflection Ratio = 0.55 <= 1.00 therefore OK

δ/∆ = 0.49 @ 2600


Page : C3
Engineer :
© CADE Systems Pty. Ltd.
Ver: 2.50.2381, 4/12/2014

DL+FPL1 about the X-X Axis


Mark : FJ1 Floor Joist - WITH Ceiling (Single Span)
Section Properties for 300x42 SmartLVL 15
CSA = 12600 mm2 Zyy = 88.2 x103 mm3
Zxx = 630.0 x103 mm3 Iyy = 1.85 x106 mm4
Ixx = 94.5 x106 mm4 J = 6.76 x106 mm4
R = 0 m (Pre camber radius)
Crossing Members Properties
Depth/Thickness = 19 mm
Width = 100 mm
Grade = (3000MPa)
Spacing = 100 mm
15 Properties
F'b F't F's F'c E G F'p F'sj
2.04 kN 59 35 4.2 39 15500 775 11.1 5.2
2600 Capacity Factors Ø for
F'b F't F's F'c F'p F'sj
.95 .95 .95 .95 .95 .95
0.26 0.26kN/m Normalisation Factors
0.0 5200 F'b F't F's F'c F'p F'sj MOE MOR
Depth .789 .872 1 1 1 1 1 1
Width 1 1 1 1 1 1 1 1
SPC*UFDL (x 1.20 )

Critical Load Combination is DL+FLL

0.09 0.09kN/m
Shear_______________________________________________________
________Shear________ Load Type Derived From
0.0 5200 BaseCase : 1 -0.17 x 1.20 = -0.20
BaseCase : 2 -0.47 x 1.20 = -0.56
BaseCase : 5 -0.68 x 1.50 = -1.02
Total = -1.79 kN
SW (x 1.20 )
Critical Location at 4733mm from the LHE
K1 = 0.94 Applied Lateral Shear 'V' = -1.79 kN
K2 = 1.00
K4 = 1.00
Characteristic strength for shear F's = 4.2 MPa
K5 = 1.00 Allowable Shear Force = 32 kN
K6 = 1.00 Stress Ratio (1.8/32) = 0.06
Design K = 0.89
Cap Fact Ø = 0.95

Moment______________________________________________________
________Moment_______ Load Type Derived From
BaseCase : 1 0.27 x 1.20 = 0.32
1.96kN 1.96kN
BaseCase : 2 0.75 x 1.20 = 0.89
BaseCase : 5 1.77 x 1.50 = 2.66
Total = 3.87 kN.m
Critical Location at 2600mm from the LHE
K1 = 0.94 From Analysis, Applied Moment 'M' = 3.87 kN.m
35 mm 35 mm K2 = 1.00
5200 K4 = 1.00 Load Distribution Calculations
K5 = 1.00 Load Sharing Applied - Complex Method
K6 = 1.00
K9 = 1.00 for BLC = 5 & with Span (L) = 5200, Spacing (s) = 450
K12b = 1.00 Concentrated Load on Grid System Cl. E8.2
Design K = 0.89 now, hB = EB IB/L3 = 10.42 & hC = EC IC/s3 = 1.88
Cap Fact Ø = 0.95
g42 = 0.20log(hB/51hC) + 0.95 => 0.76
Shear
Considering Member Stability
1.96 (Temporary Load) / (Total Load) : r = 0.69
giving Material constant : rho = 1.23
1.02 Considering Member Stability
0.00 Using Complex Method Derivation (Append (E)) with [ Y-Y axis FREE ]
with Lay Eff = 200mm & h1 = 3.22 (Table E6) & then Eqn. E6(2), Mcr = 197.2 kN.m
Using Cl. C3.2.3, (E6(1)) S1 = 7.38
with Characteristic strength for bending F'b = 47 MPa
-1.96 gives an Allowable Moment = 26 kN.m
f/F = 0.06 @ 4733
Moment Stress Ratio = 0.15 <= 1.00 ... OK

Deflection__________________________________________________
______Deflection_____ Load Type Derived From
BaseCase : 1 0.5 x 1.00 x 2.0 = 1.0
BaseCase : 2 1.4 x 1.00 x 2.0 = 2.9
BaseCase : 5 2.7 x 1.00 x 1.0 = 2.7
Total = 6.6 mm
Critical Location at 2600mm from the LHE
KsysD = 1.00 Design Span = 5200 mm
Cap Fact Ø = 1.00
Short Term Deflection = 2.7 mm
3.87
f/F = 0.15 @ 2600 Deflection Limit = 9.0 mm (δ/∆ = 2.7/9.0 = 0.3 )
Deflection Allowable Ratio = 360 (def Ratio =2.7/(5200/360) = 0.19 )

Dynamics Details
Static Point Load Check
6.6 Current Span = 5200 mm @ 450 mm c/c
Design Floor Width =5200 mm consisting of 19 mm Thick 3000 MPa flooring
Determination of Load Distribution:
δ/∆ = 0.30 @ 2600 Flooring : Ec = 3000 Mpa Tf = 19 mm, Wid = 100 & Space = 450 mm => hc =1.882
Joist : Eb = 15500 Mpa, Ib = 94.5 x106 mm4 => hb = 10.417
Now, with nc = 51
g41 = 0.883 - 0.34 x log(51 x 1.88/10.42 + 0.44) = 0.545
Calculated Deflection = 1.1 mm
Allowable Deflection = 2.0 mm
Deflection Ratio = 0.55 <= 1.00 therefore OK
Page : C4
Engineer :
© CADE Systems Pty. Ltd.
Ver: 2.50.2381, 4/12/2014

DL+PERM FLL about the X-X Axis


Mark : FJ1 Floor Joist - WITH Ceiling (Single Span)
Section Properties for 300x42 SmartLVL 15
CSA = 12600 mm2 Zyy = 88.2 x103 mm3
Zxx = 630.0 x103 mm3 Iyy = 1.85 x106 mm4
Ixx = 94.5 x106 mm4 J = 6.76 x106 mm4
R = 0 m (Pre camber radius)
Crossing Members Properties
Depth/Thickness = 19 mm
0.34 0.34kN/m Width = 100 mm
0.0 5200 Grade = (3000MPa)
Spacing = 100 mm
15 Properties
SPC*FLL/3 (x 1.50 ) F'b F't F's F'c E G F'p F'sj
59 35 4.2 39 15500 775 11.1 5.2
Capacity Factors Ø for
F'b F't F's F'c F'p F'sj
.95 .95 .95 .95 .95 .95
0.26 0.26kN/m Normalisation Factors
0.0 5200 F'b F't F's F'c F'p F'sj MOE MOR
Depth .789 .872 1 1 1 1 1 1
Width 1 1 1 1 1 1 1 1
SPC*UFDL (x 1.20 )

Critical Load Combination is DL+FLL

0.09 0.09kN/m
Shear_______________________________________________________
________Shear________ Load Type Derived From
0.0 5200 BaseCase : 1 0.17 x 1.20 = 0.20
BaseCase : 2 0.47 x 1.20 = 0.56
BaseCase : 6 0.48 x 1.50 = 0.72
Total = 1.49 kN
SW (x 1.20 )
Critical Location at 467mm from the LHE
K1 = 0.57 Applied Lateral Shear 'V' = 1.49 kN
K2 = 1.00
K4 = 1.00
Characteristic strength for shear F's = 4.2 MPa
K5 = 1.00 Allowable Shear Force = 19 kN
K6 = 1.00 Stress Ratio (1.5/19) = 0.08
Design K = 0.54
Cap Fact Ø = 0.95

Moment______________________________________________________
________Moment_______ Load Type Derived From
BaseCase : 1 0.27 x 1.20 = 0.32
1.81kN 1.81kN
BaseCase : 2 0.75 x 1.20 = 0.89
BaseCase : 6 0.76 x 1.50 = 1.14
Total = 2.36 kN.m
Critical Location at 2600mm from the LHE
K1 = 0.57 From Analysis, Applied Moment 'M' = 2.36 kN.m
35 mm 35 mm K2 = 1.00
5200 K4 = 1.00 Considering Member Stability
K5 = 1.00 (Temporary Load) / (Total Load) : r <= 0.25
K6 = 1.00
K9 = 1.00
giving Material constant : rho = 1.23
K12b = 1.00 Considering Member Stability
Design K = 0.54
Cap Fact Ø = 0.95 Using Complex Method Derivation (Append (E)) with [ Y-Y axis FREE ]
with Lay Eff = 200mm & h1 = 3.14 (Table E6) & then Eqn. E6(2), Mcr = 192.4 kN.m
Shear Using Cl. C3.2.3, (E6(1)) S1 = 7.47
with Characteristic strength for bending F'b = 47 MPa
1.81 gives an Allowable Moment = 16 kN.m

Stress Ratio = 0.15 <= 1.00 ... OK


0.00
Deflection__________________________________________________
______Deflection_____ Load Type Derived From
BaseCase : 1 0.5 x 1.00 x 2.0 = 1.0
BaseCase : 2 1.4 x 1.00 x 2.0 = 2.9
-1.81 BaseCase : 6 1.5 x 1.00 x 2.0 = 2.9
f/F = 0.08 @ 467 Total = 6.8 mm
Moment Critical Location at 2600mm from the LHE
KsysD = 1.00 Design Span = 5200 mm
Cap Fact Ø = 1.00
Deflection Limit = 15 mm (δ/∆ = 6.8/15 = 0.5 )
Allowable Ratio = 300 (def Ratio =6.8/(5200/300) = 0.39 )

Dynamics Details
2.36 Static Point Load Check
f/F = 0.15 @ 2600
Deflection Current Span = 5200 mm @ 450 mm c/c
Design Floor Width =5200 mm consisting of 19 mm Thick 3000 MPa flooring
Determination of Load Distribution:
Flooring : Ec = 3000 Mpa Tf = 19 mm, Wid = 100 & Space = 450 mm => hc =1.882
Joist : Eb = 15500 Mpa, Ib = 94.5 x106 mm4 => hb = 10.417
Now, with nc = 51
g41 = 0.883 - 0.34 x log(51 x 1.88/10.42 + 0.44) = 0.545
Calculated Deflection = 1.1 mm
Allowable Deflection = 2.0 mm
Deflection Ratio = 0.55 <= 1.00 therefore OK
6.8

δ/∆ = 0.45 @ 2600


Page : C5
Engineer :
© CADE Systems Pty. Ltd.
Ver: 2.50.2381, 4/12/2014

DL+RLL about the X-X Axis


Mark : FJ1 Floor Joist - WITH Ceiling (Single Span)
Section Properties for 300x42 SmartLVL 15
CSA = 12600 mm2 Zyy = 88.2 x103 mm3
Zxx = 630.0 x103 mm3 Iyy = 1.85 x106 mm4
Ixx = 94.5 x106 mm4 J = 6.76 x106 mm4
R = 0 m (Pre camber radius)
Crossing Members Properties
Depth/Thickness = 19 mm
Width = 100 mm
Grade = (3000MPa)
Spacing = 100 mm
15 Properties
F'b F't F's F'c E G F'p F'sj
59 35 4.2 39 15500 775 11.1 5.2
Capacity Factors Ø for
F'b F't F's F'c F'p F'sj
.95 .95 .95 .95 .95 .95
0.26 0.26kN/m Normalisation Factors
0.0 5200 F'b F't F's F'c F'p F'sj MOE MOR
Depth .789 .872 1 1 1 1 1 1
Width 1 1 1 1 1 1 1 1
SPC*UFDL (x 1.20 )

Critical Load Combination is DL+FLL

0.09 0.09kN/m
Shear_______________________________________________________
________Shear________ Load Type Derived From
0.0 5200 BaseCase : 1 -0.17 x 1.20 = -0.20
BaseCase : 2 -0.47 x 1.20 = -0.56
Total = -0.77 kN
SW (x 1.20 ) Critical Location at 4733mm from the LHE
K1 = 0.94 Applied Lateral Shear 'V' = -0.77 kN
K2 = 1.00
K4 = 1.00
Characteristic strength for shear F's = 4.2 MPa
K5 = 1.00 Allowable Shear Force = 32 kN
K6 = 1.00 Stress Ratio (0.8/32) = 0.02
Design K = 0.89
Cap Fact Ø = 0.95

Moment______________________________________________________
________Moment_______ Load Type Derived From
BaseCase : 1 0.27 x 1.20 = 0.32
BaseCase : 2 0.75 x 1.20 = 0.89
0.93kN 0.93kN
Total = 1.22 kN.m
Critical Location at 2600mm from the LHE
K1 = 0.94 From Analysis, Applied Moment 'M' = 1.22 kN.m
K2 = 1.00
K4 = 1.00 Considering Member Stability
35 mm 35 mm K5 = 1.00 (Temporary Load) / (Total Load) : r <= 0.25
5200 K6 = 1.00
giving Material constant : rho = 1.23
K9 = 1.00
K12b = 1.00 Considering Member Stability
Design K = 0.89
Cap Fact Ø = 0.95 Using Complex Method Derivation (Append (E)) with [ Y-Y axis FREE ]
with Lay Eff = 200mm & h1 = 3.14 (Table E6) & then Eqn. E6(2), Mcr = 192.4 kN.m
Using Cl. C3.2.3, (E6(1)) S1 = 7.47
Shear with Characteristic strength for bending F'b = 47 MPa
gives an Allowable Moment = 26 kN.m
0.93
Stress Ratio = 0.05 <= 1.00 ... OK

0.00 Deflection__________________________________________________
______Deflection_____ Load Type Derived From
BaseCase : 1 0.5 x 1.00 x 2.0 = 1.0
BaseCase : 2 1.4 x 1.00 x 2.0 = 2.9
Total = 3.9 mm
Critical Location at 2600mm from the LHE
-0.93 KsysD = 1.00 Design Span = 5200 mm
f/F = 0.02 @ 4733 Cap Fact Ø = 1.00
Moment Deflection Limit = 9.0 mm (δ/∆ = 3.9/9.0 = 0.4 )
Allowable Ratio = 250 (def Ratio =3.9/(5200/250) = 0.19 )

Dynamics Details
Static Point Load Check
Current Span = 5200 mm @ 450 mm c/c
1.22 Design Floor Width =5200 mm consisting of 19 mm Thick 3000 MPa flooring
f/F = 0.05 @ 2600 Determination of Load Distribution:
Deflection Flooring : Ec = 3000 Mpa Tf = 19 mm, Wid = 100 & Space = 450 mm => hc =1.882
Joist : Eb = 15500 Mpa, Ib = 94.5 x106 mm4 => hb = 10.417
Now, with nc = 51
g41 = 0.883 - 0.34 x log(51 x 1.88/10.42 + 0.44) = 0.545
Calculated Deflection = 1.1 mm
Allowable Deflection = 2.0 mm
Deflection Ratio = 0.55 <= 1.00 therefore OK

3.9

δ/∆ = 0.43 @ 2600


Page : C6
Engineer :
© CADE Systems Pty. Ltd.
Ver: 2.50.2381, 4/12/2014

DL+WindUp about the X-X Axis


Mark : FJ1 Floor Joist - WITH Ceiling (Single Span)
Section Properties for 300x42 SmartLVL 15
CSA = 12600 mm2 Zyy = 88.2 x103 mm3
Zxx = 630.0 x103 mm3 Iyy = 1.85 x106 mm4
Ixx = 94.5 x106 mm4 J = 6.76 x106 mm4
R = 0 m (Pre camber radius)
Crossing Members Properties
Depth/Thickness = 19 mm
Width = 100 mm
Grade = (3000MPa)
Spacing = 100 mm
15 Properties
F'b F't F's F'c E G F'p F'sj
59 35 4.2 39 15500 775 11.1 5.2
Capacity Factors Ø for
F'b F't F's F'c F'p F'sj
.95 .95 .95 .95 .95 .95
0.20 0.20kN/m Normalisation Factors
0.0 5200 F'b F't F's F'c F'p F'sj MOE MOR
Depth .789 .872 1 1 1 1 1 1
Width 1 1 1 1 1 1 1 1
SPC*UFDL (x 0.90 )

Critical Load Combination is DL+FLL

0.07 0.07kN/m
Shear_______________________________________________________
________Shear________ Load Type Derived From
0.0 5200 BaseCase : 1 -0.17 x 0.90 = -0.15
BaseCase : 2 -0.47 x 0.90 = -0.42
Total = -0.58 kN
SW (x 0.90 ) Critical Location at 4733mm from the LHE
K1 = 1.00 Applied Lateral Shear 'V' = -0.58 kN
K2 = 1.00
K4 = 1.00
Characteristic strength for shear F's = 4.2 MPa
K5 = 1.00 Allowable Shear Force = 34 kN
K6 = 1.00 Stress Ratio (0.6/34) = 0.02
Design K = 0.95
Cap Fact Ø = 0.95

Moment______________________________________________________
________Moment_______ Load Type Derived From
BaseCase : 1 0.27 x 0.90 = 0.24
BaseCase : 2 0.75 x 0.90 = 0.67
0.70kN 0.70kN
Total = 0.91 kN.m
Critical Location at 2600mm from the LHE
K1 = 1.00 From Analysis, Applied Moment 'M' = 0.91 kN.m
K2 = 1.00
K4 = 1.00 Considering Member Stability
35 mm 35 mm K5 = 1.00 (Temporary Load) / (Total Load) : r <= 0.25
5200 K6 = 1.00
giving Material constant : rho = 1.23
K9 = 1.00
K12b = 1.00 Considering Member Stability
Design K = 0.95
Cap Fact Ø = 0.95 Using Complex Method Derivation (Append (E)) with [ Y-Y axis FREE ]
with Lay Eff = 200mm & h1 = 3.14 (Table E6) & then Eqn. E6(2), Mcr = 192.4 kN.m
Using Cl. C3.2.3, (E6(1)) S1 = 7.47
Shear with Characteristic strength for bending F'b = 47 MPa
gives an Allowable Moment = 28 kN.m
0.70
Stress Ratio = 0.03 <= 1.00 ... OK

0.00 Deflection__________________________________________________
______Deflection_____ Load Type Derived From
BaseCase : 1 0.5 x 1.00 x 2.0 = 1.0
BaseCase : 2 1.4 x 1.00 x 2.0 = 2.9
Total = 3.9 mm
Critical Location at 2600mm from the LHE
-0.70 KsysD = 1.00 Design Span = 5200 mm
f/F = 0.02 @ 4733 Cap Fact Ø = 1.00
Moment Deflection Limit = 30 mm (δ/∆ = 3.9/30 = 0.1 )
Allowable Ratio = 200 (def Ratio =3.9/(5200/200) = 0.15 )

Dynamics Details
Static Point Load Check
Current Span = 5200 mm @ 450 mm c/c
0.91 Design Floor Width =5200 mm consisting of 19 mm Thick 3000 MPa flooring
f/F = 0.03 @ 2600 Determination of Load Distribution:
Deflection Flooring : Ec = 3000 Mpa Tf = 19 mm, Wid = 100 & Space = 450 mm => hc =1.882
Joist : Eb = 15500 Mpa, Ib = 94.5 x106 mm4 => hb = 10.417
Now, with nc = 51
g41 = 0.883 - 0.34 x log(51 x 1.88/10.42 + 0.44) = 0.545
Calculated Deflection = 1.1 mm
Allowable Deflection = 2.0 mm
Deflection Ratio = 0.55 <= 1.00 therefore OK

3.9

δ/∆ = 0.15 @ 2600


Page : C7
Engineer :
© CADE Systems Pty. Ltd.
Ver: 2.50.2381, 4/12/2014

DL+WindDn about the X-X Axis


Mark : FJ1 Floor Joist - WITH Ceiling (Single Span)
Section Properties for 300x42 SmartLVL 15
CSA = 12600 mm2 Zyy = 88.2 x103 mm3
Zxx = 630.0 x103 mm3 Iyy = 1.85 x106 mm4
Ixx = 94.5 x106 mm4 J = 6.76 x106 mm4
R = 0 m (Pre camber radius)
Crossing Members Properties
Depth/Thickness = 19 mm
Width = 100 mm
Grade = (3000MPa)
Spacing = 100 mm
15 Properties
F'b F't F's F'c E G F'p F'sj
59 35 4.2 39 15500 775 11.1 5.2
Capacity Factors Ø for
F'b F't F's F'c F'p F'sj
.95 .95 .95 .95 .95 .95
0.26 0.26kN/m Normalisation Factors
0.0 5200 F'b F't F's F'c F'p F'sj MOE MOR
Depth .789 .872 1 1 1 1 1 1
Width 1 1 1 1 1 1 1 1
SPC*UFDL (x 1.20 )

Critical Load Combination is DL+FLL

0.09 0.09kN/m
Shear_______________________________________________________
________Shear________ Load Type Derived From
0.0 5200 BaseCase : 1 -0.17 x 1.20 = -0.20
BaseCase : 2 -0.47 x 1.20 = -0.56
Total = -0.77 kN
SW (x 1.20 ) Critical Location at 4733mm from the LHE
K1 = 1.00 Applied Lateral Shear 'V' = -0.77 kN
K2 = 1.00
K4 = 1.00
Characteristic strength for shear F's = 4.2 MPa
K5 = 1.00 Allowable Shear Force = 34 kN
K6 = 1.00 Stress Ratio (0.8/34) = 0.02
Design K = 0.95
Cap Fact Ø = 0.95

Moment______________________________________________________
________Moment_______ Load Type Derived From
BaseCase : 1 0.27 x 1.20 = 0.32
BaseCase : 2 0.75 x 1.20 = 0.89
0.93kN 0.93kN
Total = 1.22 kN.m
Critical Location at 2600mm from the LHE
K1 = 1.00 From Analysis, Applied Moment 'M' = 1.22 kN.m
K2 = 1.00
K4 = 1.00 Considering Member Stability
35 mm 35 mm K5 = 1.00 (Temporary Load) / (Total Load) : r <= 0.25
5200 K6 = 1.00
giving Material constant : rho = 1.23
K9 = 1.00
K12b = 1.00 Considering Member Stability
Design K = 0.95
Cap Fact Ø = 0.95 Using Complex Method Derivation (Append (E)) with [ Y-Y axis FREE ]
with Lay Eff = 200mm & h1 = 3.14 (Table E6) & then Eqn. E6(2), Mcr = 192.4 kN.m
Using Cl. C3.2.3, (E6(1)) S1 = 7.47
Shear with Characteristic strength for bending F'b = 47 MPa
gives an Allowable Moment = 28 kN.m
0.93
Stress Ratio = 0.04 <= 1.00 ... OK

0.00 Deflection__________________________________________________
______Deflection_____ Load Type Derived From
BaseCase : 1 0.5 x 1.00 x 2.0 = 1.0
BaseCase : 2 1.4 x 1.00 x 2.0 = 2.9
Total = 3.9 mm
Critical Location at 2600mm from the LHE
-0.93 KsysD = 1.00 Design Span = 5200 mm
f/F = 0.02 @ 4733 Cap Fact Ø = 1.00
Moment Deflection Limit = 50 mm (δ/∆ = 3.9/50 = 0.1 )
Allowable Ratio = 200 (def Ratio =3.9/(5200/200) = 0.15 )

Dynamics Details
Static Point Load Check
Current Span = 5200 mm @ 450 mm c/c
1.22 Design Floor Width =5200 mm consisting of 19 mm Thick 3000 MPa flooring
f/F = 0.04 @ 2600 Determination of Load Distribution:
Deflection Flooring : Ec = 3000 Mpa Tf = 19 mm, Wid = 100 & Space = 450 mm => hc =1.882
Joist : Eb = 15500 Mpa, Ib = 94.5 x106 mm4 => hb = 10.417
Now, with nc = 51
g41 = 0.883 - 0.34 x log(51 x 1.88/10.42 + 0.44) = 0.545
Calculated Deflection = 1.1 mm
Allowable Deflection = 2.0 mm
Deflection Ratio = 0.55 <= 1.00 therefore OK

3.9

δ/∆ = 0.15 @ 2600