You are on page 1of 1

12 11 10 9 8 7 6 5 4 3 2 1

N GENERAL NOTES

1. ALL DIMENSIONS ARE IN MM UNLESS OTHERWISE SPECIFIED.


TERMINAL 2
L 2. ALL PAS DRAWINGS SHALL BE READ IN CONJUNCTION WITH
ARCHITECTURAL/ STRUCTURAL & OTHER MEP SERVICES DRAWINGS.
Bangalore
3. EQUIPMENT DIMENSIONS FROM THE GRID LINES SHALL BE PART OF
International Airport
SHOP DRAWINGS.

4. ALL TYPICAL INSTALLATION, SUPPORTING DETAILS SHALL BE PART


OF SHOP DRAWINGS.

5. ALL SPEAKERS/SPEAKER CUM STROBES TO SHALL BE CLASS B. OWNER

6. STROBE CABLE SHALL BE 2C x 1.5 Sqmm, FIRE RESISTANCE


ARMOURED CABLE.

7. SPEAKER CABLE SHALL BE 2C x 1.5 Sqmm, FIRE RESISTANCE


ARMOURED CABLE.

8. TELEPHONE CABLE SHALL BE 2C x 1.5 Sqmm, FIRE RESISTANCE , Bangalore International Airport Limited
ARMOURED CABLE .

9. WALL MOUNTED SPEAKERS/SPEAKER CUM STROBES SHALL BE


Project Office
K MOUNTED AT 2290mm FROM THE FFL. Kempegowda International
Airport Bengaluru
E49 E50 E51 E52 E53 E54 E55 10. WALL MOUNTED TELEPHONE JACKS SHALL BE MOUNTED AT Devanahalli, Bangalore 560 300 India
1200mm FROM THE FFL.
EOL
11. FINAL ROUTING OF THE CABLE SHALL BE CLOSELY COORDINATE AT LEAD CONSULTANT
SITE WITH THE IT CABLE TRAY.
9000 9000 9000 9200 8800 12000
12. 25% SPARE FOR EACH ZONE IS PROVIDED.

13. BOB : BOTTOM OF BEAM.

14. HCP FOR SPEAKERS & STROBES SHALL BE CONNECTED WITH SOM India LLC
SEE: 1 / SEE: 1 / ADDRESSABLE DEVICE LOOP.
14 Wall Street, New York, NY 10005
KIA-B03-L&T-R_ KIA-B03-L&T-R_
15. HCP FOR FIRE TELEPHONE CIRCUIT SHALL BE CONNECTED WITH
FA-L1-SPD-1171 FA-L1-SPD-1171 SEPARATE DEVICE LOOP FROM FACP. MEPF ENGINEER BAGGAGE CONSULTANT

MATCHLINE MATCHLINE 16. THE LOCATION OF PROPOSED FIRE ALARM ARUP LTD. BNP Associate s
CONTROL PANEL IS FROM LEVEL - 1 TELECOM ROOM (1T54-09) & 77 Water Street P.O. Box 32746
TELEPHONE COMMUNICATION CABLE L1-SLC-FACP_03-TPS-ZONE-6 ELECTRICAL CLOSET (1T73-11). New York, NY 10005 Abu Dhabi, UAE
J 5x2C 1.5 SQ.MM FIRE RESISTANCE ARMOURED CABLE FROM
LIGHTING CONSULTANT LANDSCAPE
FACP_09 L0-AIRSIDE OPS 0T61-11 17. TOTAL 01 SPEAKER/STROBES FOR FACP - 07 (AMP-3), ZONE - 176
L1-PSU-91 FOR TELEPHONE POWER CIRCUIT
TOTAL 04 STROBES CONNECTED IN PSU-49 BPI Grant Associates
TELEPHONE COMMUNICATION CABLE L1-SLC-FACP_03-TPS-ZONE-5 TOTAL 04 STROBES CONNECTED IN PSU-50
DEVICE LOOP CABLE FROM FACP_03-TPS-03-HCP-03 302 5th Ave, 12th FL 22 Milk Street
AS PER DRAWING
New York, NY 10001 Bath, UK BA1 1UT
DEVICE LOOP CABLE TO FACP_03-TPS-03-HCP-01
L1-PSU-50-ZONE AREA-13-STROBE CIRCUIT 18. AS PER THE FINAL APPROVED RCP LAYOUT THE BELOW FALSE IT / SECURITY / PA / FAS SIGNAGE / WAYFINDING
L1-PSU-49-ZONE AREA 13-STROBE CIRCUIT CEILING SERVICES SHOULD BE CO-ORDINATED.
MBII MSD
44 Mobile Drive 2 Young Place
Toronto, ON M4A 2P2 East Kilbride, GLA G75 0TD
7100
PSU-49-ST_C-07
F F

5000 PSU-50-ST_C-06

N7 L1-FACP_07-AMP-1-Z188-SPEAKER CIRCUIT REFERENCE DRAWING:


BIAL DESIGN
CHECKED BY APPROVED BY

I L1-FACP_07-AMP-1-Z168-SPEAKER CIRCUIT 1. FOR TYPICAL INSTALLATION DETAILS REFER DWG: NO:


KIA-B03-L&T-R_GD-XX-SPD-0002.
L1-FACP_07-AMP-1-Z189-SPEAKER CIRCUIT
2. FOR TYPICAL INTERFACING DETAILS REFER DWG: NO:
L1-PSU-49-ZONE AREA 13-STROBE CIRCUIT
KIA-B03-L&T-R_GD-XX-SPD-0003. ARCHITECTS & ENGINEERS:
2
1TPA-01G 422 m
L1-FACP_07-AMP-1-Z190-SPEAKER CIRCUIT Engineering Design and Research Center (EDRC),
NORTH PIER INT L&T Construction - Buildings & Factories.
ARRIVAL CIRC
L1-FACP_07-AMP-1-Z191-SPEAKER CIRCUIT
LEGEND: DESIGN BY DRAWN BY CHECKED BY APPROVED BY
9000

SYMBOLS NAME UNIT QTY

12000

12000
AKR SP PSK PDR
S Evacuation Speaker (4 watt ) - False
Nos. 00 MAIN CONTRACTOR:
ceiling mounted.

S Evacuation Speaker cum Strobe (2 watt ) -


Nos. 01
False ceiling mounted.
B
H S Evacuation Speaker cum Strobe (2 watt ) - 00
Nos. FIRE CONTRACTOR:
True ceiling mounted.
B
S
N8 Evacuation Speaker (4 watt ) - True ceiling
mounted.
Nos. 00
Siemens Ltd.,
#49,Ground Floor, Jyothi Mahal,
ST.Marks Road, Bangalore -560001,
P:+91(080) 33299154
Evacuation Speaker cum Strobe (2 watt ) -
PSU-49-ST_C-06 S Nos. 00
Wall Mounted.
B
F F
PSU-50-ST_C-05 Evacuation Hooter cum Strobe (2 watt ) - DESIGN BY DRAWN BY CHECKED BY APPROVED BY
H Nos. 00
Wall Mounted.
B

Evacuation Speaker (4 watt ) - Wall 00


Nos. L&T RIYAZ RV PG
S Mounted.
9000

Evacuation Strobe - Wall Mounted. Nos. 00


KEYPLAN

G F
Evacuation Strobe - Ceiling Mounted. Nos. 08 T00 T10 T20 T30 T40 T50 T60 T70 T80

2 T01 T11 T21 T31 T41 T51 T61 T71 T81


1TPA-01G 422 m
Phone Jack - Wall Mounted. Nos. 01
NORTH PIER INT
ARRIVAL CIRC T02 T12 T22 T32 T42 T52 T62 T72 T82
PSU

12000

12000
Power Supply Unit. Nos. 00
T03 T13 T23 T33 T43 T53 T63 T83
T73

MM
N9 Analogue Addressable Monitor Module. Nos. 00 T04 T14 T24 T34 T44 T54 T64 T74 T84

T05 T15 T25 T35 T45 T55 T65 T75 T85


HCP
Intelligent Control Point Device Nos. 01
T06 T16 T26 T36 T46 T56 T66 T76 T86

230VAC UPS Power Outlet (Spur Outlet) Nos. 00 T07 T17 T27 T37 T47 T57 T67 T77 T87

2C x 1.5 Sqmm Fire T08 T18 T28 T38 T48 T58 T68 T78 T88
F resistance Armoured cable Mtrs.
APPROX
(Speaker) Zone cable 320

2C x 1.5 Sqmm Fire


APPROX
9000

PSU-49-ST_C-05 resistance Armoured cable Mtrs.


(Strobe) Power cable 150
F F
PSU-50-ST_C-04 2C x 1.5 Sqmm Fire
resistance Armoured cable APPROX
Mtrs.
(Telephone) Loop cable 150 SEAL & SIGNATURE

2C x 1.5 Sqmm Fire


APPROX
resistance Armoured cable
(Telephone) Power cable
Mtrs.
80 ISSUED FOR SHOP DRAWING
1TPA-01G 422 m
2 2C x 1.5 Sqmm Fire
resistance Armoured cable Mtrs.
APPROX
120
SUBMISSION
NORTH PIER INT (Telephone) Communication cable
ARRIVAL CIRC
CHECKED BY SIGN DATE CHECKED BY SIGN DATE
2C x 1.5 Sqmm Fire
APPROX ARCHITECTURE

7700
resistance Armoured cable FPS
N10 (FACP to FACP) Loop cable
Mtrs.
300 CIVIL & STRUCTURAL PIPING
ELECTRICAL PHE
E
APPROX ELV SYSTEM AIRPORT SYSTEM
Total
1120 HVAC VHT

12000
Revision Schedule

Revision
Revision Date Issued by Issued to
Number Revision Description
5x2C 1.5 SQ.MM FIRE RESISTANCE ARMOURED CABLE TO 0 FOR REVIEW 12 OCT SIEMENS L&T
FACP_07 L1-ELECTRICAL CLOSET 1T73-11
2020
9000

TELEPHONE COMMUNICATION CABLE L1-SLC-FACP_03-TPS-ZONE-5

DEVICE LOOP CABLE FROM FACP_03 L1-TELECOM ROOM 1T54-09 FACP_03-TPS-03-TJ-04


FACP_03-TPS-03-HCP-04
L1-PSU-49-ZONE AREA 13-STROBE CIRCUIT 1TPA-01G 422 m
2

2900
NORTH PIER INT
D PSU-49-ST_C-04 ARRIVAL CIRC PSU-50-ST_C-03
F F

900
FACP DETAILS:
N11 L1-PSU-50-ZONE AREA-13-STROBE CIRCUIT
DEVICE LOOP CABLE T0 FACP_03-TPS-03-HCP-05 ZONES PART PLANS
PANEL NO. PANEL LOCATION

3700
L1-PSU-91-TELEPHONE POWER CIRCUIT
L1-FACP_07-AMP-1-Z188-SPEAKER CIRCUIT
TELEPHONE COMMUNICATION CABLE L1-SLC-FACP_03-TPS-ZONE-6 FACP - 7 L1-ELECTRICAL CLOSET
L1-PSU-49-ZONE AREA 13-STROBE CIRCUIT ZONE 176 72, 73
1T72-04 27 m² (AMP-3) (1T 73-11)
L1-FACP_07-AMP-1-Z189-SPEAKER CIRCUIT MAITENANCE/
STORAGE
L1-TELECOM ROOM
L1-PSU-48-ZONE AREA-12-STROBE CIRCUIT PSU - 49 (1T 73-10) 71, 72, 73
L1-FACP_07-AMP-3-Z176-SPEAKER CIRCUIT
L1-FACP_07-AMP-1-Z190-SPEAKER CIRCUIT 1T72-03 7 m²
L1-TELECOM ROOM
L1-FACP_07-AMP-1-Z191-SPEAKER CIRCUIT FACP_07-AMP-3-Z176-ESSC-03 FAMILY TOILET PSU - 50 71, 72, 73
(1T 73-10)
B

C S

S
MATCHLINE

B
MATCHLINE 1T72-04 27 m²

SEE: 1 / MAITENANCE/
STORAGE
SEE: 1 /
KIA-B03-L&T-R_ KIA-B03-L&T-R_
FA-L1-SPD-1173 FA-L1-SPD-1173

B
QRCODE

DRAWING TITLE

EVACUATION SYSTEM - T2 -
LEVEL 1 -ARRIVAL
MEZZANINE - PART PLAN
LEVEL 1 - ARRIVALS MEZZANINE - T2 PART PLAN - 72 72_SHEET -2 OF 2
A
1 SCALE 1 : 100
DRAWING NUMBER

KIA-B03-L&T-R_FA-L1-SPD-1172
SCALE: 1:100 SHEET SIZE - A0

CONSULTANT JOB NO : O18180

© Copyright Bangalore International Airport


Limited

You might also like