ZXDT02–PU

Solar Power Unit


User Manual

Version: V2.5

ZTE CORPORATION
No. 55, Hi-tech Road South, ShenZhen, P.R.China
Postcode: 518057
Tel: +86-755-26771900
Fax: +86-755-26770801
URL: http://support.zte.com.cn
E-mail: support@zte.com.cn
LEGAL INFORMATION
Copyright © 2014 ZTE CORPORATION.
The contents of this document are protected by copyright laws and international treaties. Any reproduction or
distribution of this document or any portion of this document, in any form by any means, without the prior written
consent of ZTE CORPORATION is prohibited. Additionally, the contents of this document are protected by
contractual confidentiality obligations.
All company, brand and product names are trade or service marks, or registered trade or service marks, of ZTE
CORPORATION or of their respective owners.
This document is provided “as is”, and all express, implied, or statutory warranties, representations or conditions
are disclaimed, including without limitation any implied warranty of merchantability, fitness for a particular purpose,
title or non-infringement. ZTE CORPORATION and its licensors shall not be liable for damages resulting from the
use of or reliance on the information contained herein.
ZTE CORPORATION or its licensors may have current or pending intellectual property rights or applications
covering the subject matter of this document. Except as expressly provided in any written license between ZTE
CORPORATION and its licensee, the user of this document shall not acquire any license to the subject matter
herein.
ZTE CORPORATION reserves the right to upgrade or make technical change to this product without further notice.
Users may visit the ZTE technical support website http://support.zte.com.cn to inquire for related information.
The ultimate right to interpret this product resides in ZTE CORPORATION.

Revision History

Revision No. Revision Date Revision Reason

R1.0 2014-08-20 First edition

Serial Number: SJ-20140825101256-001

Publishing Date: 2014-08-20 (R1.0)

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


Contents
About This Manual ......................................................................................... I
Chapter 1 Overview .................................................................................... 1-1
1.1 Product Position ................................................................................................. 1-1
1.2 Product Features................................................................................................ 1-1
1.3 Product Functions .............................................................................................. 1-1

Chapter 2 Hardware Structure................................................................... 2-1


2.1 Dimensions........................................................................................................ 2-1
2.2 Components ...................................................................................................... 2-1
2.3 Status Display.................................................................................................... 2-2
2.4 Interfaces .......................................................................................................... 2-3

Chapter 3 Installation and Use .................................................................. 3-1


3.1 Installation and Removal..................................................................................... 3-1
3.2 Use of the PU .................................................................................................... 3-2

Chapter 4 Maintenance .............................................................................. 4-1


4.1 Routine Maintenance.......................................................................................... 4-1
4.2 Troubleshooting ................................................................................................. 4-2

Chapter 5 Specifications and Characteristics ......................................... 5-1


5.1 Technical Specifications...................................................................................... 5-1
5.2 Input and Output Characteristics ......................................................................... 5-3
5.3 Implementation Standard .................................................................................... 5-3

Appendix A Value Ranges of Parameters ............................................... A-1


Figures............................................................................................................. I
Tables ............................................................................................................ III
Glossary .........................................................................................................V

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


This page intentionally left blank.

II

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


About This Manual
Purpose
This manual describes the functions, features, specifications, hardware structure,
installation, use, and maintenance of the ZXDT02–PU (V2.5) solar power module.

Intended Audience
This manual is intended for:
l Device installation engineers
l Maintenance engineers

What Is in This Manual


This manual contains the following chapters and an appendix.

Chapter 1, Overview Introduces the application, features, and functions of the product.

Chapter 2, Hardware Introduces the components, indicators, interfaces, and dimensions


Structure of the product.

Chapter 3, Installation and Describes how to install, remove, and use the product.
Use

Chapter 4, Maintenance Describes the routine ways of maintaining and troubleshooting the
product.
Chapter 5, Specifications and Introduces the technical specifications, input and output
Characteristics characteristics, and implementation standard of the product.

Appendix A Value Ranges of Introduces the value ranges of the product’s parameters.
Parameters

Conventions
This manual uses the following convention.

Provides additional information about a topic.


Note

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


This page intentionally left blank.

II

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


Chapter 1
Overview
Table of Contents
Product Position .........................................................................................................1-1
Product Features........................................................................................................1-1
Product Functions ......................................................................................................1-1

1.1 Product Position


The ZXDT02–PU is a solar power unit with the photovoltaic input interface. It supports
DC/DC conversion to transform solar energy into DC. The rated output voltage of the
ZXDT02–PU is 53.5 V and its maximum output current is 55 A.

1.2 Product Features


The ZXDT02–PU solar power unit has the following features:
l High energy utilization ratio
The static precision of MPPT is up to 99.9% and the dynamic one to 99.5%, both of
which improve the power generation capability of the solar battery panel, and thus the
higher energy utilization ratio.
l Convenient expansion and flexible configuration
à The ZXDT02–PU uses the modular design and expansion can be achieved by
adding modules.
à The ZXDT02–PU can be inserted with the ZXD3000 (V5.0) rectifier in the same
cabinet to form the hybrid power supply system that allows flexible configuration.
l Front-side maintenance
The ZXDT02–PU has integrated the photovoltaic input interface at its front side for
easy front-side cable connection and maintenance.
l Handy operation
à By pressing the button on the front side, the real-time operation information and
alarm information of the solar power module can be queried.
à The module is hot swappable.

1.3 Product Functions


The ZXDT02–PU has the following functions:

1-1

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


ZXDT02–PU User Manual

MPPT Function
When the PU works in the MPPT mode, it can detect the generation voltage of the solar
battery panel in real time and track the maximum power point of the panel to improve
charging efficiency.

Interior Protection Functions


l Input overvoltage protection
When the input voltage exceeds the input overvoltage protection point, the PU starts
automatic shut-down protection and the alarm indicator turns ON. When the input
voltage falls to the value of overvoltage restoration, the PU automatically restores
work.
l Input undervoltage protection
When the input voltage is below the input undervoltage protection point, the PU starts
automatic shut-down protection and the alarm indicator turns ON. When the input
voltage rises to the value of undervoltage restoration, the PU automatically restores
work.
l Reverse input polarity protection

When the PU has a problem of reverse input polarity, it stops work. It will not return
to work until the polarity is corrected.
l Output overvoltage protection

When the output voltage exceeds the output overvoltage protection point, the PU
starts automatic shut-down protection and the fault indicator turns ON. The output
overvoltage protection point can be set with the monitoring unit.
l Output overcurrent protection
When the output current rises to 60–70 A, the PU starts automatic shut-down
protection and the fault indicator turns ON. After the fault is cleared, the PU
automatically restores work.
l Output fuse protection
Fuse protection is used at the output end. When an interior fault causes super large
output current, the fuse blows and the fault indicator turns ON.

l Overtemperature protection
When the ambient temperature rises constantly to 65 °C, the PU starts automatic
shut-down protection and the alarm indicator turns ON. After the ambient temperature
falls to a normal value, the PU automatically restores work.

l Back discharge protection


The solar panels are protected from back discharge performed by the battery.

l Fan fault protection

1-2

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


Chapter 1 Overview

When the fan has a problem, the PU starts automatic shut-down protection and the
fault indicator turns ON.

Monitoring and Communications Functions


l Address setting of the PU
The PU address can be set automatically (by default) or manually.
à In the automatic mode, all parallelly-connected PUs already in communications
are coded sequentially and allocated addresses automatically.
à In the manual mode, the PU addresses are set with the monitoring unit. The
address is "1" by default if no address is set.

l Automatic saving of operation parameters


If the communication between a running PU and the monitoring unit is interrupted, the
PU continues to operate with the parameters saved before the interruption.

l Detection of internal analog values


The internal detection circuit of the PU will detect the internal analog values including
input voltage, input current, output voltage, output current, and internal temperature.
l Three remote functions
The PU has three remote functions: telesignalisation, telemetry, and telecontrol.
l Automatic identification of the PU’s serial number
When the PU is inserted into the solar controller, its serial number can be automatically
identified or queried (with the monitoring unit).
l Adjustment of output voltage
The output voltage can be adjusted with the external monitoring device. The
adjustment range is 42–58 VDC and the minimum adjustment step is 0.1 VDC.
l "One–button query"
Press the button on the front panel of the PU for a long time and the operation and fault
information of the PU will be displayed on the monitoring unit. The module address
can be set in the parameter setting menu.

1-3

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


ZXDT02–PU User Manual

This page intentionally left blank.

1-4

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


Chapter 2
Hardware Structure
Table of Contents
Dimensions ................................................................................................................2-1
Components...............................................................................................................2-1
Status Display ............................................................................................................2-2
Interfaces ...................................................................................................................2-3

2.1 Dimensions
Figure 2-1 shows the dimensions of the ZXDT02–PU.

Figure 2-1 Dimensions of the ZXDT02–PU

Dimensions of the ZXDT02–PU are: 41.5 mm (H) × 132 mm (W) × 300 mm (D).

2.2 Components
Figure 2-2 shows the component distribution of the ZXDT02–PU.

Figure 2-2 Components

1. Status indicator 2. Button 3. Photovoltaic input interface

Table 2-1 lists the components of the ZXDT02–PU and their functions.
2-1

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


ZXDT02–PU User Manual

Table 2-1 Function Description of Components

Component Function Description


Name

Status Indicator Indicates the working status of the PU.

Button Pressed for long to quickly display the menu interface of the PU in the
monitoring unit.

Photovoltaic Input Used to connect to the photovoltaic component.


Interface

2.3 Status Display


Figure 2-3 shows the status indicators of the ZXDT02–PU.

Figure 2-3 Status Indicators of the PU

Table 2-2 lists the status indicators and their description of the ZXDT02–PU.

Table 2-2 Description of Status Indicators of the PU

Identifier Status Status Description Remarks

Power Off There is no input or the auxiliary -


indicator power supply inside the PU fails.
(green) On There is input and the auxiliary
power supply inside the PU is
normal.

2-2

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


Chapter 2 Hardware Structure

Identifier Status Status Description Remarks

Running Off The PU is powered off. -


indicator Flashes The PU is in the MPPT scanning
(green) slowly and tracking status.
(flashes
once every
2 seconds)

Flashes The PU is in the current limitation


quickly status.
(flashes
once every
1 second)

On The PU is in the stabilized voltage


status.

Alarm Off There is no alarm. The alarms are often caused by


indicator external factors or other devices,
Flashes The communication of the PU is
(yellow) not necessarily by damages of
interrupted.
the PU itself.
On There is an input overvoltage,
input undervoltage,
overtemperature, or address
conflict problem.

Fault On There is an output overvoltage, The alarms are often caused by


indicator (red) output overcurrent, fan, or blown damages of the PU itself.
output fuse problem.

2.4 Interfaces
Figure 2-4 shows the integrated interface at the back of the PU. The electrical and signal
connections of the PU are made to the solar controller through this interface without the
need of extra cable connections. Table 2-3 lists the signal definitions of interface pins.

Note:
Interfaces not defined in the Table 2-3 are reserved interfaces.

2-3

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


ZXDT02–PU User Manual

Figure 2-4 Interface Distribution of the PU

Table 2-3 Definitions of Interface Pins of the PU

Interface Pin No. Signal Definition Function Description

Protective 18–20 PE This interface is connected to the protective


grounding ground.
interface

CAN 16 CAN (-) The PU transmits data to and receives


communication commands from the monitoring unit through this
17 CAN (+)
detection interface.
interface

DC output 21–28 Output (+) The interface provides DC to the outside.


interface
29–36 Output (-)

Hot swappable 37, 38 Hot swappable The pin prevents the output terminal from arcing
pin pin (+) when the PU is inserted into the subrack.

39, 40 Hot swappable


pin (-)

2-4

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


Chapter 3
Installation and Use
Table of Contents
Installation and Removal ............................................................................................3-1
Use of the PU.............................................................................................................3-2

3.1 Installation and Removal


The ZXDT02–PU is installed in the 19–inch power unit subrack. This section describes
how to install and remove the ZXDT02–PU.

Installation of the ZXDT02–PU


Figure 3-1 shows the steps of inserting the ZXDT02–PU into the 19–inch power unit
subrack.

Figure 3-1 Installation of the ZXDT02–PU

Removal of the ZXDT02–PU


Figure 3-2 shows the steps of removing the ZXDT02–PU from the 19–inch power unit
subrack.

3-1

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


ZXDT02–PU User Manual

Figure 3-2 Removal of the ZXDT02–PU

3.2 Use of the PU


The ZXDT02–PU is usually inserted to the solar subrack. It connects to the system through
its integrated socket at the back. Only the photovoltaic input cable needs to be connected
when the PU is being used. Figure 3-3 shows a typical application of the PU.

Figure 3-3 Typical Application

Figure 3-3 shows that the PU can be used by performing the following two steps:

1. Insert the PU into its subrack.


2. Connect the photovoltaic input cable to the PU.

3-2

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


Chapter 4
Maintenance
Table of Contents
Routine Maintenance .................................................................................................4-1
Troubleshooting..........................................................................................................4-2

4.1 Routine Maintenance


Daily Routine Maintenance
Table 4-1 lists the items for daily routine maintenance.

Table 4-1 Daily Routine Maintenance of the PU

Inspection Item Inspection Fault Judgement Maintenance Method


Method Criteria

Rotation of the fan Visual inspection The fan has stopped Clean up foreign matters in
rotation or is rotating too the fan and if this cannot
slowly. solve the problem, replace
the PU with a new one.

Status of the Visual inspection There is a fault if one of Refer to " Troubleshooting"
indicators the following happens: for troubleshooting methods.
l The power indicator If the problem persists, seek
is Off. help from ZTE technical
l The alarm indicator support engineers.
flashes or is On.
l The fault indicator is
On.

Alarm information To query the alarm Alarm information related


information in the with the PU is shown in
monitoring unit the monitoring unit.

Annual Routine Maintenance


The maintenance test should be done once every year by a professional electrical
engineer. Refer to Table 4-2 for the test items.

Table 4-2 Annual Maintenance of the PU

Test Item Test Status

Input overvoltage/undervoltage protection

4-1

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


ZXDT02–PU User Manual

Test Item Test Status

Current limitation protection

Fan alarm test

4.2 Troubleshooting
Refer to Table 4-3 for troubleshooting of the PU.

Table 4-3 Troubleshooting

Fault Symptom Troubleshooting

The alarm or fault indicator 1. Check the fan’s rotation status. If it cannot rotate properly, clean
is On. up foreign matters (if any) in it.
2. Check the photovoltaic input. If the photovoltaic input is not a normal
value, troubleshoot the photovoltaic components and photovoltaic
input cable.
3. If the problem persists, replace the PU with a new one.

The running indicator 1. Check whether the PU battery is being charged. If yes, it is normal
flashes. to see the running indicator flash.
2. Check whether the power indicator is flashing. If yes, it means that
the PU is staying in the "one-button query" status and it is normal to
see the running indicator flash.
3. Check whether the output current is too high due to a load reason. If
a load has a problem, disconnect the power circuit from this load.
4. If the problem persists, refer to the symptom of "The alarm or fault
indicator is On" for troubleshooting.

The PU has no output. The troubleshooting method varies with the indicator status:
l If the power indicator is Off, it means that the PU is not powered
on. Check the photovoltaic input.
l If the power indicator if On and the running indicator is Off,
refer to the symptom of "The alarm or fault indicator is On" for
troubleshooting.

The PU fails to be 1. Check whether the photovoltaic input voltage is below 45 V. If yes,
powered on. and the alarm indicator is On, it means that the PU is staying in the
power-off protection status due to the input undervoltage.
2. Install the PU to another slot and power it on again. If now the PU
can work properly, it means that the PU is normal.
3. If the problem persists, it means that the PU has a problem. Replace
the PU with a new one.

4-2

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


Chapter 5
Specifications and
Characteristics
Table of Contents
Technical Specifications .............................................................................................5-1
Input and Output Characteristics ................................................................................5-3
Implementation Standard ...........................................................................................5-3

5.1 Technical Specifications


Photovoltaic Input
Table 5-1 Photovoltaic Input Specifications

Parameter Index

Nominal input voltage 60–150 VDC

Input voltage range 0–150 VDC

Maximum input current 35 A

DC Output
Table 5-2 Output Specifications

Parameter Index

Maximum output current 55 A

Rated output voltage 53.5 VDC

Adjustable range of the output 42–58 VDC


voltage

Peak efficiency 97.5%

Self loss 5W

MPPT precision l Static tracking precision: 99.9%


l Dynamic tracking precision: 99.5%

5-1

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


ZXDT02–PU User Manual

Safety Protection
Table 5-3 Safety Protection Specifications

Parameter Index

Insulating strength Routine test:


l Applying a 707 V DC voltage between the DC output
terminal and the housing for one minute. There should be no
breakdown or electric arcing, and the steady-state leakage
current is less than 1 mA.
l Applying a 707 V DC voltage between other interfaces and
the housing for one minute. There should be no breakdown
or electric arcing, and the steady-state leakage current is
less than 1 mA.

Safety standard Conforming to IEC60950-1 and EN60950-1.

Electromagnetic compatibility Conforming to EN55022 class A and IEC61000.

Structure and Environment


Table 5-4 Structure and Environment Specifications

Parameter Index

Working temperature -25–65 °C

Storage temperature -40–85 °C

Working humidity 5%–95% RH

Heat dissipation mode Fan

Dimensions 41.5 mm (H) × 132 mm (W) × 300 mm (D)

Weight 1.65 kg

Protection class IP20

Internal Protection
Table 5-5 Internal Protection Specifications

Parameter Index

Input undervoltage protection 45±5 VDC


point

Input undervoltage protection 8–12 VDC


recovery return difference voltage

Input overvoltage protection point 155±5 VDC

Input overvoltage protection 8–12 VDC


recovery return difference
voltage

5-2

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


Chapter 5 Specifications and Characteristics

Parameter Index

Output overvoltage point 56.5–61 VDC

Over-temperature protection 65 °C
point

Over-temperature protection 8–15 °C


recovery return difference
temperature

5.2 Input and Output Characteristics


The PU has the following input and output characteristics:
l When the input voltage range is 50–65 VDC, the PU works in the MPPT mode if it is
connected to a battery.
l When the input voltage range is 65–120 VDC, the PU has the MPPT function and it
outputs full voltage when the following conditions are met:
à The maximum input current is 35 A.
à The ambient temperature range is -25–+65 °C.
à The output voltage range is 42–58 VDC.
l When the input voltage range is 120–150 VDC, the PU has the MPPT function and its
maximum load value is 25 A.

5.3 Implementation Standard


This product conforms to the following standards:
l IEC60950–1 and EN60950-1 (for safety protection).
l IEC61000 and EN55022 (for electromagnetic compatibility performance)

5-3

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


ZXDT02–PU User Manual

This page intentionally left blank.

5-4

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


Appendix A
Value Ranges of Parameters
Refer to Table A-1 for value ranges of the PU’s internal parameters.

Table A-1 Value Ranges of Parameters

Parameter Default Value Minimum Value Maximum

Output voltage 53.5 VDC 42 VDC 58 VDC

Overvoltage protection point of the output 60 VDC 56.5 VDC 61 VDC


voltage

Output current limitation value 55 A - -

Speed regulation function of the fan Enabled - -

Automatic setting of the PU address Automatic - -

Address code of the PU 1 1 20

• If the speed regulation function of the fan is disabled, the fan rotates at full speed.

A-1

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


ZXDT02–PU User Manual

This page intentionally left blank.

A-2

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


Figures
Figure 2-1 Dimensions of the ZXDT02–PU ............................................................... 2-1
Figure 2-2 Components ............................................................................................ 2-1
Figure 2-3 Status Indicators of the PU ...................................................................... 2-2
Figure 2-4 Interface Distribution of the PU ................................................................ 2-4
Figure 3-1 Installation of the ZXDT02–PU................................................................. 3-1
Figure 3-2 Removal of the ZXDT02–PU.................................................................... 3-2
Figure 3-3 Typical Application ................................................................................... 3-2

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


Figures

This page intentionally left blank.

II

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


Tables
Table 2-1 Function Description of Components ......................................................... 2-2
Table 2-2 Description of Status Indicators of the PU.................................................. 2-2
Table 2-3 Definitions of Interface Pins of the PU ....................................................... 2-4
Table 4-1 Daily Routine Maintenance of the PU ........................................................ 4-1
Table 4-2 Annual Maintenance of the PU .................................................................. 4-1
Table 4-3 Troubleshooting......................................................................................... 4-2
Table 5-1 Photovoltaic Input Specifications ............................................................... 5-1
Table 5-2 Output Specifications................................................................................. 5-1
Table 5-3 Safety Protection Specifications ................................................................ 5-2
Table 5-4 Structure and Environment Specifications ................................................. 5-2
Table 5-5 Internal Protection Specifications............................................................... 5-2
Table A-1 Value Ranges of Parameters.....................................................................A-1

III

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


Tables

This page intentionally left blank.

IV

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential


Glossary

SJ-20140825101256-001|2014-08-20 (R1.0) ZTE Proprietary and Confidential

You might also like