730 730 NOTES:

1. PANEL INSPECTION IS REQUIRED PRIOR


A MTS-G
TO DELIVERY AT SITE.
2. FABRICATION OF PANELBOARD IS UPON
MAIN A MAIN B

D APPROVAL OF SHOP DRAWING.


B 3. CB RATING SHALL BE ON APPROVED
E DDD.

C:\Users\NOEMI\Desktop\PDF Images\mts3257653c.png

C:\Users\NOEMI\Desktop\PDF Images\mts3ea0a921.png

C:\Users\NOEMI\Desktop\PDF Images\mts1c512ef4.png

C:\Users\NOEMI\Desktop\PDF Images\mtsbee1614a.png
4. PANEL DIMENSION SHALL BASE ON
ACTUAL CB REQUIREMENT AND PEC
1105 1105
C STANDARD.
F 5. PROVIDE PHASE BARRIER ON ALL CBS.
6. APPROVED AS NOTED/REDLINED
REMARKS MUST BE INCORPORATED ON
THIS SHEET.
DOCUMENTS HOLDER @
THE BACK OF PANEL 7. REVALIDATE TYPE OF MOUNTING,
COVER
BASED ON THE SIZE THESE ARE WALL
MOUNTED.

GENERAL NOTES:
INTERNAL VIEW
FRONT VIEW W/ DEADFRONT TYPE: Nema 1 enclosure surface wall
SCALE NTS SCALE NTS SHEET METAL: 2.0mm G.I
COLOR: Powder coated wrinkled gray
finished
BUSBAR TYPE: Copper w/ ins. sleeves
PANEL PARTS, COMPONENTS & SPECIFICATION NOTE:
Nameplates shall be stainless steel with
BUSBAR SIZE:
A NAME PLATE black letters mounted by rivets.
MAIN: 350A- 1" x 38"
B PILOT LAMPS Font: Arial bold
Height: 50mm
GROUND: 34" x 41"
C PUSH LOCK Computation basis is area of busbar (Thick &
D CONCEALED HINGES SYSTEM VOLTAGE: 230 V Width in inches)*1000 = Current Capacity.
ENCLOSURE TYPE: NEMA-1, SURFACE MOUNTED
E SWING TYPE DEADFRONT : BOX Ga #14 G.I SHT Proposed Busbar width of busbar can fit per
: COVER GA #14 G.I SHT
F PUSH LOCK FINISH : POWDER COATED, WRINKLED pole of circuit breaker. See Product sheet of
GRAY
3 Schneider EZC400H.
G MAIN BUSBAR (1" x 8") QUANTITY : 1 ASSY

GROUNDING BUSBAR - 50% OF MAIN BUSBAR WITH LUGS (TOTAL NO. OF LUGS SHALL BE N+1)
H
-34" x 41" L1 L2 L3 L1 L2 L3

I MECHANICAL INTERLOCK, WALKING BEAM PIVOTAL TYPE AT THE BACK OF 2 CBS 350AT, 3P 350AT, 3P
DESCRIPTION BUSBAR CATALOGUE BRAND
J 350AT,3P,22 KAIC 1" x 38" EZC400H SCHNEIDER 1" x 38"
MAIN 3 Main Busbar
K 350AT,3P,22 KAIC 1" x 8" EZC400H SCHNEIDER
ENCLOSURE TYPE: NEMA 1 GA.14 G.I SHEET 3
4" x 41"

GROUNDING BUSBAR IS 50% OF MAIN BUSBAR

CONTRACTOR: OPERATOR: PROJECT NAME: TECH REFRESH DDD PROJECT DRAWN BY: JEHAN ENGINEERING TEAM SHEET CONTENT: SHEET NO.
PROJECT DESCRIPTION: SHOP DRAWING PROFESSIONAL ELECTRICAL ENGINEER CHECKED BY:
PROPOSED 350AT,3P MTS-G PANEL SHOP DRAWING SD-05
CORPORATION
SITE NAME: PLDT ISULAN PRC No: PTR No: REVIEWED BY:

SITE ADDRESS:
CALAWAG2 ISULAN, SULTAN KUDARAT
DATE ISSUE: TIN: DATE SUBMITTED: APPROVED BY: SD-16
SCALE: REVISION NUMBER.:
LONGITUDE: 6°38'17.88"E LATITUDE: 124°36'3.88"N PLACE ISSUE: DATE APPROVED: NTS .