You are on page 1of 14

DESIGN CALCULATION

Mechanical & Industrial Department SHEET


CAIRO - EGYPT
Subject Medical gases
Building Adapazari Hospital

M EDICAL GASES

CO M P RE S S ED V A CU UM N ITRO G E N OXYGEN
G A S ES

PRACTICAL PLUMBING DESIGN GIUDE


Project No. Date
ULATION 15/1/2002
Sheet No. Computed by
of Y.G.
Checked by Approved by
T.Z.

OXYGEN NITRO US O X ID E
Project No. Date
DESIGN CALCULATION 15/1/2002
Mechanical & Industrial Department SHEET Sheet No. Computed by
CAIRO - EGYPT of Y.G.
Subject Checked by Approved by
Building

LABORATORY SYSTEMS

GENERAL BUILDING COMPRESSED AIR AND VACUUM AIR


SYSTEMS SYSTEMS CLINICAL SYSTEMS

DENTAL SYSTEMS

CLINICAL SYSTEMS
COMPRESSED AIR SYSTEM
VOLUME/ ENTER NO.
OUTLET NUMBER OF USE OF TOTAL
LOCATION (CFM) OUTLETS FACTOR OUTLETS CFM
Major operating rooms 2 2(3bar)+1(7bar) 100 8 16
Trauma rooms 2 1/bed 100 8 16
Plaster room 1 1/bed 50 1 0.5
Delivery rooms 2 1/room 100 0
Endoscopy 1/room
Recovery 2 1/bed 50 10 10
ICU rooms 2 1/bed 50 18 18
Nurseries 1 1/4 bassinets 20 3 0.6
Special care Nurseries 1 3/bassinet 100 6 6
Pre-OP room 1 1/bed 10 0
CT Scan 1 1/room 10 1 0.1

then you get 67.2 cfm of compressed air

VACUUM AIR SYSTEM

CFM/INLET NUMBER OF USE ENTER NO. OF


LOCATION (@15-IN HG) OUTLETS FACTOR ROOMS OR BEDS TOTAL CFM
Operating room open heart, organ
transplant, etc. (2/room) 3.5 100 0
Major operating room (2/room) 2 6/room 100 0
Minor operating room 2 3/room 100 4 0 72
Cystoscopy and special procedures
(2/room) 1 40 0
Emergencya 2 1/bed 100 51 0 102
Emergencya (Isolation) 2 3/bed 100 6 0 36
Trauma room 1 2/bed 100 8 8
Plaster (fracture room) 1 1/room 100 0
Delivery room 2 6/room 100 0
Recovery first inlet/bed 3 2/bed 100 2 6
Recovery second inlet/bed 1 2/bed 50 2 1
Recovery additional inlet/bed 1 2/bed 10 16 1.6
ICU&CCU first inlet/bed 3 2/bed 100 1 3
ICU&CCU second inlet/bed 1 2/bed 50 1 0.5
ICU&CCU additional inlet/bed 1 2/bed 10 16 1.6
Patient rooms surgicalb 0
Sometimes one inlet/bed 1 50 0
Sometimes one inlet/2 beds) 1 50 0
Patient rooms medicalb 1/bed 0
Sometimes one inlet/bed 1 10 1 188 19.8
Sometimes one inlet/2 beds) 1 10 0
Labor rooms 1 20 0
Nurseries 1 1/4bassinet 10 1 3 1.3
Special care Nurseries 1 2/bassinet 40 1 3 2.2
Endoscopy rooms 1 1/room 10 1 6 1.6
256.6

Number of outlets is 1/room except as noted

a
All outlets in the emergency department (area) should have 100%
simultaneous use factor
b
Where patient rooms are interchangeable (surgical or medical), use 50%
simultaneous use factor for the first 4 rooms on the far end of the section of pipping and 20% thereafter

Then you get 256.6 cfm of vacuum air

Go to O2&N2O
15/1/2002
Computed by
Y.G.
Approved by
DESIGN CALCULATION
Mechanical & Industrial Department SHEET
CAIRO - EGYPT
Subject CFM Estimation
Building Adapazari Hospital

OXYGEN

ENTER
SIMULTA NO. OF
NEOUS ROOMS
USE NUMBER OF OR
LOCATION FACTOR PER ROOM PER OUTLET PER BED OUTLETS OUTLETS TOTAL
Operating rooms 2/room
First room (far end of a section of piping 100 50 1 50
and all individual branches to rooms)
Second room (on a section of piping) 100 30 1 30
Each additional room (on a section of 100 20 2 40
piping)
Emergency roomsb 1/bed
First outlet 100 20 1 20
2nd&3rd 100 10 2 20
4--12 75 10 8 60
13--20 50 10 8 40
21--40 33 10 20 66
40 & up 25 10 17 42.5
Trauma rooms 2/bed
First room (far end of a section of piping 100 50 1 50
and all individual branches to rooms)
Second room (on a section of piping) 100 30 1 30
Each additional room (on a section of 100 20 2 40
piping)
Delivery rooms 6/room
First room (far end of a section of piping 100 50 0
and all individual branches to rooms)
Second room (on a section of piping) 100 30 0
Each additional room (on a section of 100 20 0
piping)
Recovery rooms 2/bed
1--8 outlets 100 20 8 160
9--12 60 20 4 48
13--16 50 20 4 40
and up 45 20 4 36
ICU rooms 100 20 2/bed 18 360
CCU rooms 100 20 0
Other spaces such as 20
Patient rooms (Medical and surgical)(beside outlets) 1/bed
First outlet 100 20 6 120
2nd&3rd 100 10 12 120
4--12 75 10 51 382.5
13--20 50 10 30 150
21--40 33 10 69 227.7
40 & up 25 10 23 57.5
Labor rooms 1/room
Sometimes one outlet/bed
First outlet 100 20 0
2nd&3rd 100 10 0
4--12 75 10 0
13--20 50 10 0
21--40 33 10 0
40 & up 25 10 0
Nurseries 1/4 bassinet
First outlet 100 20 1 20
2nd&3rd 100 10 2 20
4--12 75 10 0
13--20 50 10 0
21--40 33 10 0
40 & up 25 10 0
Special care nurseries 2/bassinet
First outlet 100 20 1 20
2nd&3rd 100 10 2 20
4--12 75 10 3 22.5
13--20 50 10 0
21--40 33 10 0
40 & up 25 10 0
Dyalisis 1/bed
First outlet 100 20 1 20
2nd&3rd 100 10 2 20
4--12 75 10 1 7.5
13--20 50 10 0
21--40 33 10 0
40 & up 25 10 0
Anesthesia work rooms 1/bed
First outlet 100 20 1 20
2nd&3rd 100 10 0
4--12 75 10 0
13--20 50 10 0
21--40 33 10 0
40 & up 25 10 0
***added MRI 1/bed
First outlet 100 20 1 20
2nd&3rd 100 10 1 10
4--12 75 10 0
13--20 50 10 0
21--40 33 10 0
40 & up 25 10 0
CT-Scan 1/room
First outlet 100 20 1 20
2nd&3rd 100 10 0
4--12 75 10 0
13--20 50 10 0
21--40 33 10 0
40 & up 25 10 0
Endoscopy rooms
First outlet 100 20 1/room 2 40
2nd&3rd 100 10 0
4--12 75 10 0
13--20 50 10 0
21--40 33 10 0
40 & up 25 10 0

a
Where Oxygen is used to power fluidicaly controlled anesthesia ventilators, increase LPM volume
by 40%
b
All outlets in the emergency dept. (area) should have 100% simultaneous use factors
c Where Oxygen is used to power fluidically controlled ventilators, volume should be 40 LPM
d
Simultaneous-use factor for other spaces: the first outlet on the end section of piping 20 LPM,
100% use factor. For additional outlets on the section of piping 10 LPM with the use-factors
used in the above table.

Then you get 2450.2 LPM of Oxygen

NITROUS OXIDE
SIMULTA
NEOUS
USE VOLUME, LPM/
LOCATION FACTOR ROOM TOTAL
First operating room (far end of piping and 30 1 30
all individual branches to operating rooms
Second operating room (on a section of piping) 20 1 20
Each additional operating rom (on a 15 2 30
section of piping)
Delivery rooms 20 0
Emerency rooms 20 0
Trauma rooms 20 4 80
Aneshtesia work room 15 1 15
Plaster (fracture room) 20 1 20
Endoscopy room 15 1 15

Then you get 210 LPM of Nitrous Oxide

Go to GO TO FINAL COMPARAISON SHEET


Project No. Date
TK0191 15/1/2002
Sheet No. Computed by
of Y.G.
Checked by Approved by
Project No. Date
TK0191 15/1/2002
Mechanical & Industrial Department Sheet No. Computed by
CAIRO - EGYPT of Y.G.
Subject Medical Gases CFM estimation Checked by Approved by
Building Adapazari Hosptial

PPDG
CFM LPM

COMPRESSED AIR 67.20 1902.89

VACUUM 200.00 5663.37

OXYGEN 86.53 2450.20

NITROUS OXIDE 7.42 210.00

Oxygen Tank Calculations

Go to Schedule of Equipment

Pipe Sizing
Project No. Date
J0274 30/11/2003
Mechanical & Industrial Department Sheet No. Computed by
CAIRO - EGYPT of Y.G.
Subject Oxygen tank capacity and reserve Checked by Approved by
Building King Hussein Hospital

Total number of
269 beds
beds =

Following the Practical plumbing guide for bulk systems:


Allow 500 cu.ft/bed/month+reserve manifold for one day supply:

# of beds*500= 134500 cu.ft/month

Convert to liquid status= 156.39535 cu.ft/momth Final Tank


capacity
The reserve for one day is:
montn reserve/30 4483.3333 cu.ft./day
1 cylinder= 244 cu.ft so
# of cylinders= 18.374317 cylinders
so 20 cylinders

Schedule of Equipment
Go to

Pipe Sizing
Project No. Date
TK0191 15/1/2002
Mechanical & Industrial Department Sheet No. Computed by
CAIRO - EGYPT of Y.G.
Subject Schedule of equipment Checked by Approved by
Building Adapazari Hosptial

Medical Vacuum Unit Medical Compressed Air Unit


Column NO. 1 Column NO. 1
Unit NO. Unit NO.
System served Medical Vacuum System served Medical Air
Building Hospital Building Hospital
Floor Basement Floor Basement
Room Room
Reciprocating packaged oil-less
Specification type Packaged duplex Specification type Quadraplex
Pressure (mm Hg) 381 Discharge pressure Kpa 345
Capacity l/s per unit 45 Capacity l/s per unit 20
Quantity 1 Quantity 1

L/S is the expanded flow at 510 mm Hg

Oxygen Tank Calculations


Go to
Pipe Sizing
Project No. Date
DESIGN CALCULATION TK0191 15/1/2002
Mechanical & Industrial Department SHEET Sheet No. Computed by
CAIRO - EGYPT of Y.G.
Subject Pressure loss/100 ft calculations Checked by Approved by
Building Adapazari Hospital

Oxygen

Distance to the farthest outlet 170 m


Taking fittings and elbows into accounts 170 m x 1.25 = 212.5 m
Converting to ft 697.178 ft

If 697.178 shouldn't exceed 5 PSI of total pressure drop


Then the pressure drop per 100 ft will be 0.71718 .7 PSI/100ft
Pressure drop = 34.85892 PSI

in
1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4
50 0.04
250 0.99 0.11
500 0.45 0.11
1500 0.95 0.3
2500 0.83 0.34
LPM 4000 0.88 0.2
7500 0.71 0.22
15000 0.89 0.35
25000 0.98 0.23
50000 0.92

Vacuum

Distance to the farthest outlet 170 m


Taking fittings and elbows into accounts 170 m x 1.25 = 212.5 m
Converting to ft 697.178 ft

If 697.178 shouldn't exceed 4 in Hg


Then the pressure drop per 100 ft will be 0.57374 .6 in Hg
Pressure drop across pipe = 14.9352 PSI
in
3/4 1 1-1/4 1-1/2 2 2-1/2 3 4 5 6
1 0.02
8 0.76 0.2
15 0.6 0.18
30 0.68 0.3
50 0.74 0.2
CFM 100 0.76 0.24
175 0.7 0.3
250 0.58 0.13
450 0.45 0.13
700 0.3 0.1
1000 0.24

Sizing the Vacuum pump discharge piping to the roof


3/4 1 1-1/4 1-1/2 2 2-1/2 3 4 5 in
CFM 325

Medical air

Distance to the farthest outlet 170 m


Taking fittings and elbows into accounts 170 m x 1.25 = 212.5 m
Converting to ft 697.178 ft

If 697.178 shouldn't exceed 5 in Hg


Then the pressure drop per 100 ft will be 0.71718 .7 PSI/100ft

in
1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4
5 0.3 0.03
20 0.69 0.2
40 0.8 0.18
90 0.93 0.41
140 1 0.27
250 0.85 0.33
CFM 400 0.84 0.27
750 0.94 0.22
1600 1

Nitrous Oxide

Distance to the farthest outlet 87 m


Taking fittings and elbows into accounts 87 m x 1.25 = 108.75 m
Converting to ft 356.791 ft

If 356.79 shouldn't exceed 5 in Hg


Then the pressure drop per 100 ft will be 1.40138 1 PSI/100ft
in
1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4
50 0.04
250 0.99 0.11
500 0.45 0.11
1500 0.95 0.3
LPM 2500 0.83 0.34
4000 0.88 0.2
7500 0.71 0.22
15000 0.89 0.35
25000 0.98 0.23
50000 0.92

Oxygen Tank Claculations


Go to

Schedule of Equipment

You might also like