CONTRACT: CD-1
SUBMISSION OF
CALCULATION NOTE
- EARTHING TRANSFORMER
FOR APPROVAL
CONTENT
2.2 Calculation........................................................................................................................................ 4
3 Conclusion...................................................................................................................................................6
CLIENT & PROJECT DERBA MIDROC CEMENT & Derba - Chancho 132kV Power Expansion Project
CONTRACTOR SINOHYDRO CORPORATION LTD.
CONTRACT NO. CD-1 DOCUMENT NO. DEBA-EL-CC-3143 REV B PAGE 3/6
normally. In such good condition, the neutral point electric potential is earthing potential, so EO 0 . At the same
time phase voltage is UR ER , US ES , UT E T , correspondingly ICO.R , ICO.S , ICO.T are capacitance current to the
ground which are ahead of the voltage 90°. Phasor diagram as follow:
ER UR
R UR
ES US
O S I CO.S
ET UT I CO.R
T
I CO.T I CO.S I CO.R UT I CO.T US
voltage is earthed and equal to zero. The voltage of non-fault phase R and S to the ground were raised to line -to
-line voltage,
So :
UR 3ER , US 3ES , UT 0
According to Kirchhoff’s Current Law, the currents of single phase ground capacitance is:
ICO.R ICO.S IC 0
UR 3ER
ICO.R ICO.S
XC XC
Then:
CLIENT & PROJECT DERBA MIDROC CEMENT & Derba - Chancho 132kV Power Expansion Project
CONTRACTOR SINOHYDRO CORPORATION LTD.
CONTRACT NO. CD-1 DOCUMENT NO. DEBA-EL-CC-3143 REV B PAGE 4/6
3ER E
IC 3ICO.R 3 3 R 3ICO
XC XC
Thus it can be seen that short circuit current to the ground is 3 times capacitance current under normal
UR
ER UR
R
IC
ES US I CO.S
O S
I CO.R
ET UT =0 US
T
I CO.S I CO.R UT
IC
I CO.R + I CO.S = - I C
earth
For DERBA Substation, earthing transformer should withstand capacitive currents of 1 outgoing line, one
capacitor bank line and one transformer cable incoming line under bus bar “C”. So:
Length from transformer to the incoming 6.6kV busbar is about 70m, we take 0.1km for calculation. And 6.6kV
cable length of capacitor bank is about 40m, we also take 0.1km for calculation, 6.6kV outgoing line cable is 3km
assumed and 6.6kV overhead transmission line is about 100km assumed, So:
In this project, the size of cable we selected is YJV-6/10-4x630 per phase for transformer incoming cable and for
the 6.6kV outgoing line cables and YJV-6/10-2x240 per phase for capacitor bank. According to the parameter
0.6481uF/km. So:
C240=0.429uF/km , C630=0.6481uF/km.
2.2 Calculation
CLIENT & PROJECT DERBA MIDROC CEMENT & Derba - Chancho 132kV Power Expansion Project
CONTRACTOR SINOHYDRO CORPORATION LTD.
CONTRACT NO. CD-1 DOCUMENT NO. DEBA-EL-CC-3143 REV B PAGE 5/6
The short circuit current of fault point is from three capacitance current sources which are 1 outgoing line cable,
1 capacitor bank and 1 transformer incoming cable. Each capacitance current is as followed:
ER 6.6
IC.L.1 = nl × L l1 × 3 × 2 × π × f × C 630 × × 10 3 = 1× 3 × 3 × 2 × 3.14 × 50 × 4 × 0.6481× × 10 3 = 27.92 A 1
3 3
ER 6.6
IC.T. = nT × L T × 3 × 2πf × C 630 × × 10 3 = 1× 0.1× 3 × 2 × 3.14 × 50 × 4 × 0.6481× × 10 3 = 0.930A
3 3
ER 6.6
IC.C. = nC × L C × 3 × 2πf × C 240 × × 10 3 = 1× 0.1× 3 × 2 × 3.14 × 50 × 2 × 0.429 × × 10 3 = 0.308A
3 3
IC. = K × (IC.L.1 + IC.T. + IC.L.2 + IC.C ) = 1.3 × (27.92 + 0.930 + 0.308 + 16) = 58.71A
K is a additional factor for substation, which is in the consideration of other equipment equivalent capacitance
such as main transformer bushing to ground, voltage transformer to ground, lightning arrester to ground etc.
should be more than 21.31kVA and correspondingly the short circuit capacity of earthing transformer for 10second
UN 6600 / 3
Z0 = = = 10.4Ω
IN.10 s 1100 / 3
Note:
According to the Schedule of guaranteed characteristics, the Rated voltage of earthing transformer is 6.6/0.4kV,
but in the Contract document of B1.3.2-II) 6.6kV EARHITNG TRANSFORMER, it mention that The earthing
transformer shall be rated, 50Hz, 6.6kV, outdoor, oil immersed with all necessary accessories,..., which means
It is ZN type earthing transformer without second winding through checking the manufacturer’s drawing and its
test report, which is proved that the guaranteed characteristics was wrong. And finally, we suppose the earthing
transformer to be provided is 50Hz, 6.6kV, 400kVA, ZN type and oil immersed with all necessary accessories