Project:
Project
Scenario:
Scenario 1
Design Inputs
Table5 System
Frequency (Hz) 50
Figure1 CASE 1 - Two subs., Cables SC, Solid bonded, Local 1ph-e fault
Table10 Results
Top layer soil resistivity (Ohm.m) 39.525
Top layer depth (m) 15.735
Bottom layer soil resistivity (Ohm.m) 7865.432
Reflection factor, k 0.99
Goodness of Fit (R-square) 6.574
Table11 Segments
Table13 Results
Allowable Touch Voltage Limit (V) 200.069
Allowable Step Voltage Limit (V) 430.535
Permissible body current (A) 0.098
Body resistance - 1 hand to both feet
(Ohms) 2076.378
Body resistance - 1 foot to other foot
(Ohms) 2076.378
Table14 Results
Grid Impedance, Z (Ohms) 1.813
Grid Impedance Angle (degrees) 0.096
Grid Potential Rise, GPR (V) 74.616
Grid Potential Rise Angle (degrees) -12.376