You are on page 1of 1

FIX BOTH ENDS

BEAM ANALYSIS GIRDER BEAM BEAM # 1621


Section = W610X285 I = 2610000
SECTION
ry = 78 E = 200000 tw = 20.6 rts = 91.4
PROPERTIES Sx = 8050000 Zx = 9160000 h = 573.8 tf = 37.1
J = 1.3E+07 bf = 330 Fy = 450 ho = 610

Lb = 10000 Lp = Lr =
Limiting Lengths
= 2894.116515 = 9774.53236
bf
Flange λ = = 4.4474 < λp = = 8.011103406 Therefore: COMPACT
Check if 2tf
Compact
h
Web λ = = 27.85436893 < λp = = 79.26776001 Therefore: COMPACT
tw
Comparing Lb, Lp, Lr Lp = 2894.116515 < Lb = 10000 > Lr = 9774.53236

Mn Calculation

Lb ≤ Lp Mn = = 4122 kN-m

For Cb Support to Mmax = 1565.5 MA = 1148.53


Cb = 1.147
Support MB = 1565.5 MC = 1148.53

Lp < Lb ≤ Lr
= 2848.883518 < Mp = 4122

For Fcr
= 350.4883671
Lb>Lr

= 2821.431355 < Mp = 4122


bf
0 λp < λr = = 21.082
2tf

b) For section with slenderness


a) For Section with not compact flanges
For Non Compact flanges
tr
Sections

Mn = 0 Mn = 0

Conclusion for Use Mn = 2821.431355


ՓMn > Mu = 1565.496 SATISFACTORY
ՓMn = 2539.28822
Flexure
kdes = 49.8 h = d-2kdes = 548.4 d = 648

Note 26.62135922 < 47.22334639

kv = 5
SHEAR
26.62135922 < 51.85449729

51.85449729 > 26.62135922 < 64.58241935

Therefore Use Cv = 1
= 3604.176

ՓVn = 3604.176 > Vu = 537.822 SATISFACTORY

5𝑊𝐿4 𝐿
DEFLECTION 𝛿= = 3.9E-07 𝛿𝑚𝑎𝑥 = = 41.6667 mm
384 𝐸𝐼 240

Therefore use W610X285=W24X192


Final Conclusion