1 - The dimension of the spout coming down from the telecom tray must be obtained by subtracting the height

of the tray from


the top mounting height of each particular cabinet.
2 - The 2AWG ground wire must be grounded to the trays at both ends and to each accessory along the way to equipotentialize
the tray to ground and must be connected at least three points to the existing or new ground installation to be installed.
3 - It should be used as a minimum for TELECOM networks, UTP Cat 5e cable.
4 - Double joints should be added in electric tubing routes, which allow the pipeline to be disassembled if the maintenance staff
thinks it will be needed in the future.
5 - The communication cables must not be assembled requiring an additional effort to the simple sliding through the ducts, since
these can cut their interior wires.
6 - Communications cables must not be subjected to radius curves less than 10 times their diameter.
7 - In the transition from tray to electric piping, it should be sealed with a soft foam, which can be removed. This is to prevent
moisture from entering the pipes and insects or vermin.
8 - The UTP cables must be tied with plastic strapping to the trays from a minimum separation between ties of 1 m to 2 m. These
should not over-tighten the cable so as not to modify the factory dielectric clearances.

DETAIL ENGINEERING

1200
3950 DATA CABLE ROUTES
TPS18001-000-TEL-CRR-0001
N/S
3950-1200-DG30-PLN-003-001
2-

DETAIL ENGINEERING

1200
3950 DATA CABLE ROUTES
TPS18001-000-TEL-CRR-0001
N/S
3950-1200-DG30-PLN-003-001
1 - The dimension of the spout coming down from the telecom tray must be obtained by subtracting the height of the tray from
the top mounting height of each particular cabinet.
2 - The 2AWG ground wire must be grounded to the trays at both ends and to each accessory along the way to equipotentialize
the tray to ground and must be connected at least three points to the existing or new ground installation to be installed.
3 - It should be used as a minimum for TELECOM networks, UTP Cat 5e cable.
4 - Double joints should be added in electric tubing routes, which allow the pipeline to be disassembled if the maintenance staff
thinks it will be needed in the future.
5 - The communication cables must not be assembled requiring an additional effort to the simple sliding through the ducts, since
these can cut their interior wires.
6 - Communications cables must not be subjected to radius curves less than 10 times their diameter.
7 - In the transition from tray to electric piping, it should be sealed with a soft foam, which can be removed. This is to prevent
moisture from entering the pipes and insects or vermin.
8 - The UTP cables must be tied with plastic strapping to the trays from a minimum separation between ties of 1 m to 2 m. These
should not over-tighten the cable so as not to modify the factory dielectric clearances.