You are on page 1of 1

Application & Reference Data SECTION 200

Fire Pump Types, Services and Accessories 015

GENERAL of f10w includes the number of fire hoses, the number of


sprinklers, the required sprinkler density, the number of
Fairbanks Morse fire pumps, horizontal split case, vertical standpipes or risers in the building to be protected, and
in-Iine and vertical turbine designs, are specifically the area (in square feet) of the protected property. The
manufactured to meet the strict listing and approval testing criteria which the sprinkler designer uses to determine the
requirements of Underwriters Laboratories, Underwriters required pressure includes static head required to deliver
Laboratories of Canada and Factory Mutual. The water to the highest elevation, pressure requirements at
following describes the various types of fire pump the sprinkler heads, and calculated friction head losses in
services, requirementsllimitations that must be satisfied, the piping. In addition, the pump bowl assembly must be
and the accessories (drivers, controls and fiUings) that selected to include the "Iift below" datum which is the
must be supplied. static head required to raise the water from the lowest
pumping water level to the center line of discharge.
HORIZONTAL SPLlT CASE ANO IN-UNE
SERVICE PUMPS NFPA #20 specifies that the performance curve of a
vertical turbine fire pump meet the rated primary design
Horizontal split case and in-line fire pumps are used only point and meet or exceed the secondary point which is a
when the water supply provides positive pressure to the minimum of 150% of rated capacity at 65% of rated head.
pump suction (including secondary f10w rate) (e.g. ground The maximum head (shut-off or churn head) shall not
storage tank, elevated tank, or a city water main, etc.). A exceed 140% of the rated head.
f10w test is first performed to determine if the water supply
provides sufficient flow to satisfy the requirement, to Surface type discharge heads are recommended for ea se
measure the residual pressure at that rate of flow, and to of gauge reading and ease of access to the other required
determine the NPSH(A). The fire pump is selected based piping equipment. However, NFPA #20 does not preclude
on the sprinkler designer's calculated requirements for other types. Column section lengths shall not exceed 10
rate of f10w (GPM) and pressure (PSI). The criteria which feet. Open line shaft may be used where the distance
the sprinkler designer uses to determine the required rate from the pump head to the static water level does not
of f10w includes the number of fire hoses, the number of exceed 50 feet. In cases where this distance is greater
sprinklers, the required sprinkler density, the number of than 50 feet, enclosed line shaft is required. Fire pumps
standpipes or risers in the building to be protected, and shall not be installed in a well when the pumping water
the area (in square feet) of the protected property. The level exceeds 200 feet from the surface of the ground
criteria which the sprinkler designer uses to determine the when pumping at 150% of rated capacity. A conical or
required pressure includes sta tic head required to deliver basket type strainer of non-ferrous material with a free
water to the highest elevation, pressure requirements at area of not less than 4 times the suction area is required.
the sprinkler heads, calculated friction head losses in the For installations in sumps or pits, NFPA #20 requires that
piping, and residual suction pressure available to the the second impeller from the boUom of the bowl assembly
pump. be below the lowest pumping water level in the open body
of water supplying the sump or pit. This assumes no
NFPA #20 specifies that the performance curve of obstructions exist between the open body of water and the
horizontal split case and in-line fire pumps meet the rated sump. If an obstruction exists which reduces the water
primary design point and meet or exceed the secondary level in the sump, the second impeller should be set below
point, which is a minimum of 150% of rated capacity at not the lowest sump water leve!. This submergence guide
less than 65% of rated head. The maximum head (shut- outlines the minimum requirements. The pump
off or churn head) shall not exceed 140% of the rated manufacturer's installation drawings should be consulted
head. to determine the actual submergence required which
provides sufficient NPSH(A) and vortex suppression in a
NFPA #20 specifies that horizontal split case and in-Iine
properly designed sump. For well installations, NFPA #20
fire pumps shall not be applied where a static suction lift is
requires that the second impeller from the bottom of the
involved. If the pump suction source of fire water is a city
bowl assembly be 10 feet below the pumping water level
water main, the residual pressure should be not less than
at 150% of rated capacity. In all cases, the submergence
10 to 20 PSI at the 150% capacity rating in order to avoid
shall be increased one foot for each 1000 feet of elevation
contamination of the drinking water.
above sea leve!.
VERTICAL TURBINE SERVICE PUMPS

A vertical turbine fire pump is used when the source of the


water is a body of water which is below grade (e.g. lake,
river, pond, aquifer, etc.). The fire pump is selected based
on the sprinkler designer's calculated requirements for
rate of f10w (GPM) and pressure (PSI). The criteria which
the sprinkler designer uses to determine the required rate

Fairbanks Morse Pump 11/15101

You might also like