Professional Documents
Culture Documents
Article
Minimum Short Circuit Ratio Requirement for
MMC-HVDC Systems Based on Small-Signal
Stability Analysis
Zheren Zhang 1 , Liang Xiao 2 , Guoteng Wang 1 , Jian Yang 1 and Zheng Xu 1, *
1 College of Electrical Engineering, Zhejiang University, Hangzhou 310027, China
2 China Southern Grid Power Dispatching and Control Center, Guangzhou, Guangdong 510700, China
* Correspondence: xuzheng007@zju.edu.cn; Tel.: +86-0571-8795-2074
Received: 26 June 2019; Accepted: 18 August 2019; Published: 26 August 2019
Abstract: This paper determines the minimum short circuit ratio (SCR) requirement for a modular
multilevel converter based high-voltage direct current (MMC-HVDC) transmission systems. Firstly,
a simplified model of MMC is introduced; the MMC is represented by its AC and DC side equivalent
circuit. Next, by linearizing the MMC subsystem and the DC network subsystem, the deduction of the
small-signal models of MMC subsystem, the small-signal model of the DC network and MMC-HVDC
are carried out successively. Thirdly, the procedure for determining the minimum SCR requirement
of MMC-HVDC is described. Finally, case studies are performed on a two-terminal MMC-HVDC
system under four typical control schemes. The results show that the restraint factors for the rectifier
MMC is predominantly the voltage safety limit constraint, and the restraint factors for the inverter
MMC are mainly the phase locked loop (PLL) or the outer reactive power controller. It is suggested
that the minimum SCR requirement for the sending and the receiving systems should be 2.0 and 1.5
in the planning stage.
Keywords: modular multilevel converter (MMC-HVDC); small signal stability; minimum SCR;
control scheme
1. Introduction
Recently, the modular multilevel converter based high-voltage direct current (MMC-HVDC)
system has drawn significant attention from both the industry and academia. As a new breed of
voltage-sourced converter (VSC), MMC outperformed the Line Commutated Converter (LCC) thanks to
the decoupled control of active and reactive powers, the low harmonic voltages, the flexible scalability
and the elimination of commutation failure [1–4]. MMC-HVDC has been widely used in transmission
and distribution applications, such as wind farm connection, multi-terminal operation, and passive
network power supply [5–7].
In the planning stage, one of the most important characteristics for the connected AC system is
the short circuit ratio (SCR). For the LCC-HVDC, detailed research has been carried out by CIGRE
and IEEE in which the AC system strength is categorized by the SCR [8,9]. The AC systems with
SCR less than two are defined as very low SCR systems because the connected LCC cannot operate
in a consistently stable manner [8]. For MMC-HVDC, there is no commonly accepted quantitation
standard for describing the strength of the connected AC system, and there are no commonly accepted
answers to the following two questions: (1) What are the minimum SCR requirements for the rectifier
and the inverter MMC-HVDC station to transmit rated active power, respectively? and (2) Does the
minimum SCR requirement vary with different control schemes?
As pointed out in [10], the steady-state power flow constraint, the small-signal stability constraint
and the transient stability constraint should be all satisfied if MMC-HVDC (VSC-HVDC) could operate
stably. To determine the minimum SCR under the third constraint, a time-domain simulation of certain
faults is the conventional method, given the lack of a mature analytical method. Therefore, research on
the minimum SCR is usually based on the former two constraints.
By using a Thevenin voltage source, the maximum available power (MAP) of VSC is plotted,
and determines how the MAP is influenced by the SCR of the connected AC system, the angle of
AC system impedance, the limitation on the internal voltage of the converter, and the reactive power
support [11,12]. In [13], the minimum SCR for MMC-HVDC is calculated based on the steady-state
power flow constraint. Because the dynamics of the converter is neglected, the results using the
steady-state power flow constraint tend to be optimistic, and the results of [11–13] are only the
ideal theoretical minimum SCR requirements. Recently, the small-signal stability analysis has drawn
great attention in academia, with which a stricter minimum SCR requirement could be calculated.
An eighth-order small-signal model of a VSC connected to weak AC system is derived in [14]; the results
illustrate that the dynamics of PLL and the AC filter are crucial components for system stability. On the
basis of the small-signal model, the influence of SCR and the phase-locked loop (PLL) on VSC was
studied, and the connected AC systems with a SCR lower than 1.3 are defined as weak systems [15].
By studying the stability difference between MMC and VSC, the maximum power transmission
capability of MMC could approach VSC by adjusting the PI parameters of PLL [16]. The small-signal
stability of MMC is analyzed under the rectifier and the inverter mode, and the calculated minimum
SCR of rectifier/inverter is 1.28–1.72/2.84–3.04 [17]. The explicit mathematical expression for the
VSC system eigenvalues is derived based on reduced order model in [18], and result shows that the
small signal stability of the system is significantly affected by the AC system strength (SCR) and PLL
parameters. It is pointed out in [19] that the connected AC system could be considered weak if its SCR
is less than 2.0 for VSCs with the classic vector current control scheme, while the virtual synchronous
generator control scheme is especially suitable for weak system connections.
Generally speaking, existed small-signal stability analysis based method has the space for
improvement considering the following three aspects: First, detailed high-order, small-signal model
of MMCs with internal dynamics were usually adopted [20], which are not suitable for system-level
planning studies. The high-order, small-signal model necessitates substantial requirements for
modeling and computation resources, and its applicability in the system planning stage is limited.
Second, one-terminal MMC with ideal DC source was usually adopted for calculating the minimum
SCR, regardless of the dc network and other converter stations. Third, existed work mainly focused on
the influence on small signal stability by controller parameters under single control scheme, influence
on small signal stability by different control schemes has not been considered.
To overcome the aforementioned shortness of the existed research, improvements of this paper
are made according to the following three aspects: (1) Derive the small-signal model of MMC-HVDC
based on the simplified model of MMC; the internal dynamics of the MMC such as the circulating
current is ignored to achieve computational efficiency; (2) Analysis is carried out using a two-terminal
MMC-HVDC; the DC side of an MMC is connected to another MMC through the DC line as opposed to
an ideal DC voltage source; in comparison with the MMC with an ideal DC voltage source, the model
in this paper is more realistic and provides more reasonable results; (3) Four different control schemes
are analyzed and compared, which provides more comprehensive results than a single control scheme.
The outline of this paper is as follows: Section 2 discusses the theory and introduces the simplified
model of MMC for determine the minimum SCR requirement. Section 3 discusses the deduction of a
small-signal model for MMC-HVDC. Section 4 describes the procedure of the proposed methodology.
The case studies have been conducted on a 2-terminal MMC-HVDC system with four typical control
schemes in Section 5. Section 6 is the concluding section.
u pa = m pa ⋅ u pa
una = mna ⋅ una
Figure 1.
Figure Basic structure
1. Basic structure of
of modular
modular multilevel
multilevel converter
converter (MMC).
(MMC).
As seen inthe
Dividing sum1,ofu(1)
Figure andirj(2)
rj and arebythe
2, arm
the AC voltage
side and modeltheof armMMC current, where j (j = a, b, c) denotes
P could be derived as:
phase and r (r = p, n) denotes the upper or lower arm. mrj and urj are the arm average switching
Larm divj [21]. i R isarm theMMC AC output current in phase j.
u gj − Lt + 2 dt − Rt +vj 2 ivj = uvj
function and the sum of armSM capacitor voltage
of common coupling (PCC) in phase
ugj is the AC voltage at the point j. udc is the DC voltage, and idc(3)is
the DC current. u vj = u( nk − u )
pk 2
According to Kirchhoff’s voltage law, the mathematical model in phase j could be derived
By subtracting (2) from (1), the DC side model of phase j in MMC could be derived as:
as follows:
divj dipj udc
u gj − Lt − Rdi t ivj
cirj− Larm − Rarm ipj + udcupj = 2 (1)
dt Larm
+ R i
dt
arm cirj = u comj −
divj
dt dinj
2
u (4)
u gj − Lt − Rt ivj +u L + unj + Rarm
pjarm i pjinj+ −
injunj = − dc (2)
dt comj u = ,
dt cirji = 2
2 2
Dividing the sum of (1) and (2) by 2, the AC side model of MMC could be derived as:
A summation (4) of allthree phases, and the DC side model of MMC could be concluded as
u gj − Lt + Larm divj − Rt + Rarm ivj = uvj
follows:
2 dt
2 (3)
uvj = unk − upk /2
By subtracting (2) from (1), the DC side model of phase j in MMC could be derived as:
dicirj
u
Larm dt + Rarm icirj = ucomj − 2dc
upj + u nj i + i
pj nj
(4)
comj = , icirj = 2
u
2
A summation (4) of all three phases, and the DC side model of MMC could be concluded as follows:
didc
2 2
3 Larm Pdt + 3 Rarm idc = uCeq − udc
i = 2 P
icirj , uCeq = 3 ucomj (5)
dc
j=a,b,c j=a,b,c
3 dt 3
2
(5)
idc
=
j = a ,b , c
icirj , uCeq = ucomj
3 j = a ,b , c
Because each arm of the MMC consists of a large number of SMs, it is common practice to
Energies 2019, 12, 3283 4 of 20
evaluate the average voltage and current quantities of all the SMs in one arm. Suppose the average
arm SM capacitor voltage and the SM capacitor are denoted as u rj and Csm, the dynamics of SM
Because
capacitor couldeach arm of the as:
be concluded MMC consists of a large number of SMs, it is common practice to evaluate
the average voltage and current quantities of all the SMs in one arm. Suppose the average arm SM
capacitor voltage and the SM capacitor are = mrj urj =asmurjrjNu
urj denoted andrj Csm , the dynamics of SM capacitor could
be concluded as: durj durj
mrj (6)
= = − i
P
u
dt = m u = m Nurj
NrjdtPrj Csmrj rj
rj
durj
(6)
durj mrj
dt = Ndt
According to [21], the arm average switching = − Csmcould
function irj be denoted as in (7):
switching
According to [21], the arm average (ωg t + ϕcould
function
1 − M cos j)
be denoted as in (7):
mpj =
2 (ω g t+ϕ j )
1−M cos (7)
mnj = 1 + M cos (ωg t + ϕ j )
m =
pj
2
(7)
mnj =
1+M cos(ω g t+ϕ j )
22
where
whereM,M,ωωg and φj are the modulation index [13], the fundamental angle frequency and the initial
g and ϕj are the modulation index [13], the fundamental angle frequency and the initial
phase
phase of armaverage
of arm averageswitching
switchingfunction.
function.
conditionsuunj ≈≈u pju , u
P P
Note
Note that, in normal operationconditions
that, in normal operation u inin
, Ceq (5)(5)could
couldbebesimplified
simplifiedasas(8)(8)byby
nj pj Ceq
substituting
substituting(7)
(7)into
intoit:it:
2 X X 1 P P
uCeq = 2 ucom j = 1 upj+ unj (8)
uCeq =3 j=
3 j =a,b,c
u
a,b,c comj
= j=a,b,c pj
j = a,b,c 6
(
u6 + unj ) (8)
On the basis of (5), (6), and (8), the DC side model of MMC could be derived as in (9):
On the basis of (5), (6), and (8), the DC side model of MMC could be derived as in (9):
duCeq
Ceq duCeq =
X
u i /u − i = i − i (9)
Ceq dt = uvjvjivj vj/ uCeqCeq− idcdc= idcsdcs− idc dc (1)
dt j=a,b,c
j = a ,b , c
whereCCeqeq= =6C6C
where /N./N.
smsm Therefore,the
Therefore, theACACand
andDC DCside
side model
model ofof MMC
MMC could
could bebe respectively
respectivelydescribed
describedas
asinin(3),
(3),(5),
(5),and
and(9).
(9).The
Theequivalent
equivalentcircuit
circuitofofMMC
MMC is is
plotted inin
plotted Figure 2, 2,
Figure where
where uv uisv is
thethe
phasor of of
phasor the
three-phase voltage u (j = a, b,
the three-phase voltagevjuvj (j = a, b, c). c).
AC
Figure2.2.AC
Figure and
and DCDC side
side equivalent
equivalent circuitofofthe
circuit themodular
modularmultilevel
multilevelconverter
converter(MMC).
(MMC).
2 3Rarm 2 3 Larm
Δidcs1 idc
idcs Ceq
uCeq udc
Δθ g Δu gq
Δivd、Δivq ΔuCeq1 idcs =Pv / uCeq
Δu gd、Δu gq Δuvdref Δuvqref
Figure 3.
Figure BasicStructure
3. Basic Structure of
of aa small-signal
small-signal model.
model.
Here in
Here in Figure
Figure 3,3, u uss,, LLss and
andRRssare
arethe
theequivalent
equivalentvoltage
voltagesource
source phasor,
phasor, the
the equivalent
equivalent inductor,
inductor,
and the
and the equivalent
equivalent resistor
resistor of of the
the connected
connected ACAC system,
system, respectively.
respectively. PPgg and
and Q Qgg isis the
the active
active and
and
reactive power injecting into the MMC; P and Q are the active and reactive
reactive power injecting into the MMC; Pvv and Qvv are the active and reactive power injecting into power injecting into
the voltage
the voltage source
source u uvv;; uugg and
and iivvdenote
denotethe
the phasor
phasor of
of the
the three-phase voltage uugjgj and
three-phase voltage and the the three-phase
three-phase
current i (j = a, b, c); L and R are the connecting reactor and resistor between PCC
current ivj (j = a, b, c); L and R are the connecting reactor and resistor between PCC and uv, which
vj and u v , which could
be calculated according to Figure
could be calculated according to Figure 2a: 2a:
Figure
Energies 4.
The2019, 12, x FOR PEER REVIEW
block diagram of the MMC AC side model together with the inner controller is plotted 6 of 21
in
Figure 4.
Figure 4.
Figure 4. Basic
Basic structure
structure of
of MMC
MMC AC
AC side
side and
and the
the inner
inner controller.
controller.
Here in
Here inFigure
Figure4,4,ivd
ivdand
andivq ivq are
arethe
thed-axis
d-axisand
andthe
theq-axis
q-axiscomponent
componentofofivi;vi;vdref
ivdrefand
andivqref
ivqref are
are the
the
referencevalues
reference valuesof
ofivd
ivd and
andiivqvq; ugd
gd and
and ugq
gq are
are the
the d-axis
d-axis and the q-axis component
component of of uugg; uvd andand uvq
uvq
are the d-axis and the q-axis component of uv; uvdref and uvqref are the reference value of uvd and uvq; Kpd
(Kpq) and Kid (Kiq) are the proportional gain and the integral gain of the inner controller d-axis
(q-axis); ωg is the instantaneous fundamental angular speed; Considering the small time-delay of
modulation process, uvdref (uvqref) is supposed the same as uvd (uvq) in this paper.
In deducing the small-signal model, the prefix Δ and subscript 0 mean the small deviation and
Figure 4. Basic structure of MMC AC side and the inner controller.
Here in Figure 4, ivd and ivq are the d-axis and the q-axis component of iv; ivdref and ivqref are the
reference values of ivd and ivq; ugd and ugq are the d-axis and the q-axis component of ug; uvd and uvq
are the 2019,
Energies d-axis12, and
3283 the q-axis component of uv; uvdref and uvqref are the reference value of uvd and uvq6;of K20
pd
(Kpq) and Kid (Kiq) are the proportional gain and the integral gain of the inner controller d-axis
(q-axis); ωg is the instantaneous fundamental angular speed; Considering the small time-delay of
are the d-axis and the q-axis component of uv ; u and uvqref are the reference value of uvd and uvq ; Kpd
modulation process, uvdref (uvqref) is supposed thevdref same as u vd (uvq) in this paper.
(Kpq ) and Kid (Kiq ) are the proportional gain and the integral gain of the inner controller d-axis (q-axis);
In deducing the small-signal model, the prefix Δ and subscript 0 mean the small deviation and
ωg is the instantaneous fundamental angular speed; Considering the small time-delay of modulation
initial value of each variable. Based on the block diagram in Figure 4, the small-signal model of the
process, uvdref (uvqref ) is supposed the same as uvd (uvq ) in this paper.
MMC AC side model together with the inner controller could be derived as (12).
In deducing the small-signal model, the prefix ∆ and subscript 0 mean the small deviation and
initial value of each variable. dBased
Δivd onRthe block K pddiagram in Figure 1 4, the small-signal model of the
dt = − Δivd + ( Δivdref − Δivd ) + ΔM id
MMC AC side model together with theLinner controller L L
could be derived as (12).
d Δivq
d∆i R K pq 1
= −R Δivq + Kpd ( Δivqref − Δivq )+ 1ΔM iq
dt
vd
= − L∆i vd + L ∆i vdre f − ∆i vd + L ∆Mid
d∆i
dt L L L
(12)
Δ
d vqM Kpq
dt =
id − ∆i ∆iivdvqre f − ∆ivq + L ∆Miq
R 1
= ( )
LKid vqΔ+ivdrefL − Δ
d∆Mdtid (12)
= Kid ∆ivdre f − ∆ivd
d ΔM iq
dt
d∆Miq ==KK iq∆i
( Δvqre
ivqref −− ∆i
Δivq )
dtdt iq f vq
Here in
Here in (12), Midid (M
(12), M (Miqiq) )isisthe
thestate
statevariable
variableofofthe
theinner
innercontroller
controllerd-axis
d-axis(q-axis)
(q-axis)integral
integralpart.
part.
3.2.2. Small-Signal
3.2.2. Small-Signal Model
Model of
of Phase-Locked
Phase-Locked Loop
Loop (PLL)
(PLL)
In this paper,
In paper,the
thewidely
widelyused
usedsingle
singlesynchronous
synchronous reference frame
reference phase-locked
frame looploop
phase-locked (SRF-PLL) [23]
(SRF-PLL)
is studied,
[23] and its
is studied, andblock diagram
its block is plotted
diagram in Figure
is plotted 5. As plotted
in Figure in Figure
5. As plotted 5, ugx and
in Figure 5, ugxugy areuthe
and x-axis
gy are the
and y-axis component
x-axis and y-axis componentof u in common network frame
g of ug in common network frame [24]; K and K
pθ[24]; iθ are the proportional gain
pθ and Kiθ are the proportional and
the integral
gain and thegain of the
integral PI controller;
gain θg is the output
of the PI controller; θg is theofoutput
PLL. of PLL.
ωg 0
Kiθ ωg θg
K pθ
θg
Figure 5.
Figure Basicstructure
5. Basic structure of
of phase-locked
phase-locked loop
loop (PLL).
(PLL).
Suppose M
Suppose Miθiθ isisthe state
the variable
state of the
variable ofintegral part inpart
the integral the PIincontroller of SRF-PLL,
the PI controller ofthe respectively
SRF-PLL, the
small-signal model of PLL could be expressed as (13):
respectively small-signal model of PLL could be expressed as (13):
ddtΔM =
d∆Miθ
iθ Kiθ ∆u gq
= K iθ Δu gq
d∆θ gdt (13)
∆ω g = Kpθ ∆u gq + ∆Miθ
dt = (13)
d Δθ g = Δω g = K pθ Δu gq + ΔM iθ
On the basis of Kirchhoff’s voltage dt law, the dynamics of the AC system and MMC AC side
equivalent circuit could be described as (14):
divd u gd −uvd −Rivd +ω g Livq usd −u gd −Rs ivd +ω g Ls ivq
dt = L = Ls (14)
divq u gq −uvq −Rivq −ω g Livd usq −u gq −Rs ivq −ω g Ls ivd
= =
dt L Ls
On the basis of the linearized small-signal model of (14), ∆ugd and ∆ugq could be derived as (15):
Ls RLs −Rs L
∆u gd = Ls +L ∆usd + Ls +L ∆uvd + Ls +L ∆ivd
L
Ls RLs −Rs L (15)
∆u gq = Ls +L ∆usq + Ls +L ∆uvq + Ls +L ∆ivq
L
On the basis of Figure 4, the linearized small-signal model of the inner controller could be derived
as (16):
∆uvd = ∆u gd + ω g0 L∆ivq + Livq0 ∆ω g − Kpd ∆ivdre f − ∆ivd − ∆Mid
(16)
∆uvq = ∆u gq − ω g0 L∆ivd − Livd0 ∆ω g − Kpq ∆ivqre f − ∆ivq − ∆Miq
Energies 2019, 12, 3283 7 of 20
Note that the relationship of us in the dq-frame and the common network frame as in (17), ∆usd
and ∆usq could be represented by usx0 , usy0 and ∆θg as in (18):
usd + jusq = usx + jusy e−jθ g (17)
∆usd = −usx0 sin θ g0 + usy0 cos θ g0 ∆θ g = Ud0 ∆θ g
(18)
∆usq = −usx0 cos θ g0 − usy0 sin θ g0 ∆θ g = Uq0 ∆θ g
where usd and usq are the d-axis and the q-axis component of us in the dq-frame; usx and usy are the x-axis
and the y-axis component of us in the common network frame; Ud0 and Uq0 is the intermediate variables.
On the basis of (12)–(18), the small-signal model of the MMC AC side model, the inner controller
and the PLL could be derived as (19):
d∆x0v
= A0v ∆x0v + B0r ∆r0 + B0u ∆uCeq (19)
dt
h iT h iT
where ∆x0v = ∆ivd ∆ivq ∆Mid ∆Miq ∆Miθ ∆θ g , ∆r0 = ∆ivdre f ∆ivqre f , B0u = [0]6×1 ; the detailed
expressions of A0v and B0r of which are referred to the Appendix A.
The linearized small-signal model of (20) could be written as (21); (21) could be further simplified
into (22) after eliminating ∆uvd and ∆uvq :
where the detailed expressions of C0v , D0r and D0u of which are referred to the Appendix A.
d∆x0v
= A0v ∆x0v + B0r ∆r0 + B0u ∆uCeq
dt (23)
∆idcs = C0v ∆x0v + D0r ∆r0 + D0u ∆uCeq
For the active power controller, the small-signal model is outlined as (25), where MiPg , KiPg , and
KpPg are the state variable of the integral part, the proportional gain, and the integral gain of the
outer controller.
∆i ∆P ∆P + ∆MiPg
vdre f = KpPg gre f − g
d∆MiPg
dt = KiPg ∆P gre f − ∆P g (25)
∆P g = u gd0 ∆ivd + u gq0 ∆ivq + ivd0 ∆u gd + ivq0 ∆u gq
For the reactive power controller, the small-signal model is outlined as (26), where MiQg , KiQg ,
and KpQg are the state variable of the integral part, the proportional gain, and the integral gain of the
outer controller.
∆i ∆Q + ∆MiQg
vqre f = K pQg −∆Q gre f + g
d∆MiQg
dt = KiQg −∆Q gre f + ∆Q g (26)
∆Q g = u gq0 ∆ivd − u gd0 ∆ivq − ivq0 ∆u gd + ivd0 ∆u gq
For the AC voltage controller, the small-signal model is outlined as (27), where MiUac , KiUac , and
KpUac are the state variable of the integral part, the proportional gain, and the integral gain of the
outer controller. d∆MiUg
dt = K iUg ∆U gre f − ∆U g
∆i ∆U ∆U + ∆MiUg
vqre f = K pUg gre f − g (27)
∆u ∆u
u gd0 gd + u gq0 gq
∆U
g = q
u2 + u2
gd0 gq0
After eliminating the intermediate variables such as ∆ugd and ∆ugq in (25)–(27), the small-signal
model of MMC subsystem could be derived as (28) by substituting (24)–(27) into (23):
d∆xv
= Av ∆xv + Br ∆r + Bu ∆uCeq
(
dt (28)
∆idcs = Cv ∆xv + Dr ∆r + Du ∆uCeq
where Av , Br , Bu , Cv , Dr , and Du differ with different outer control schemes; the small deviation of state
variables ∆xv and the small deviation of outer controller reference value ∆r also differ with different
outer control schemes. For example, if the MMC controls the DC voltage and the reactive power, ∆xv
and ∆r could be written as (29):
h iT
∆xv = ∆ivd ∆ivq ∆Mid ∆Miq ∆Miθ ∆θ g ∆MiUdc ∆MiQg
h iT (29)
∆r = ∆u ∆Q
dcre f gre f
n1 b1 n3
b1 b2 b3 b4 b5 b6
1 1 0 00 0 n1
b6 0 -1 1 0 0 0 n2
b2
b5
T = -1 0 0 0 1 0 n3
n4
0 0 0 1 0 -1
0 0 -1 -1 -1 0 n5
n2 b3 n5 b4 n4
d∆xMMC
= AMMC ∆xMMC + BMMCr ∆rre f + BMMCu ∆uCeq
dt (32)
∆idcs = CMMC ∆xMMC + DMMCr ∆rre f + DMMCu ∆uCeq
Energies 2019, 12, 3283 10 of 20
∆xv1 ∆r1
Av1 Br1
= ...
. . .
where ∆xMMC , ∆rre f = .. , AMMC = diag .. , BMMCr = diag .. , BMMCu =
∆xvm ∆rm Avm Brm
Bu1 Cv1 Dr1
Du1
.. .. ..
diag . , CMMC = diag . , DMMCr = diag . , DMMCu = diag M .
Bum
Cvm
Drm
Dum
The linearized small-signal model of the whole MMC-HVDC could be derived after merging (31)
and (32):
d∆xsys
= Asys ∆xsys + Bsys ∆rre f (33)
dt
∆xMMC
" # " # " #
AMMC BMMCu CG BMMCr
where ∆xsys = , Asys = , Bsys = .
∆xG BG CMMC AG + BG DMMCu CG BG DMMCr
On the basis of the eigenvalues of matrix Asys , the minimum SCR for MMC-HVDC could be
determined considering the small-signal stability.
4. Procedure for Determining Minimum Short Circuit Radio (SCR) Based on Small-Signal
Stability Analysis
Step 2: Calculating the steady-state power flow of the DC net subsystem by setting the DC voltage
as 1.0 pu for the MMC that controls the DC voltage and the DC power, supplied by current source idcs
as seen in Figure 3, as Pv0 for the MMC that controls the active power.
Step 3: Calculate the steady-state power flow of the MMC subsystem that controls the DC voltage
described by (34) with the Newton–Raphson method. For the MMC station that controls the DC
voltage, the known variables in (34) are Pv0 (already calculated in Step 2), Qg0 (0.0 pu), Ug0 (1.0 pu)
and usy0 (0.0 pu). After solving (34), θg0 equals arctan(ugy0 /ugx0 ).
Energies 2019, 12, 3283 11 of 20
Step 4: Transform the calculated results from the common network frame to the dq-frame with
θg0 for concerned MMC subsystems.
In most studies that use small-signal analysis, the magnitude of us were supposed as a constant
(usually around 1.0 pu) to determine the initial values of the state variables. However, for AC systems
with small SCR, there would be a great deviation between the calculated voltage and the rated voltage
at the point of common coupling (PCC) with the above assumption, and it would eventually affect the
rationality of the small-signal analysis results. In accordance with LCC-HVDC, the PCC voltage is set
as its rated value [25].
Flowchart for
Figure 7. Flowchart for determining
determining the minimum SCR requirement of MMC-HVDC.
5. Case Study
5. Case Study
Root locus
Figure 9. Root
Figure locus of
of test
test system
system with
with Control
Control Scheme 1.
When SCR
When SCR decreases
decreasestoto1.95,
1.95,the calculated
the calculated eigenvalues
eigenvalues of matrix Asys A
of matrix are
sys listed in Table
are listed 4. It could
in Table 4. It
be concluded that the small-signal stability is satisfied. However, the equivalent
could be concluded that the small-signal stability is satisfied. However, the equivalent voltage voltage source of the
sending system is 1.2006 pu, which exceeds the voltage safety limit. Therefore,
source of the sending system is 1.2006 pu, which exceeds the voltage safety limit. Therefore, the the active power of the
rectifier
active couldofnot
power thereach 1.0 pu
rectifier if SCR
could of sending
not reach 1.0 pusystem
if SCRisoflower than
sending 1.95. The
system equivalent
is lower voltage
than 1.95. The
source of receiving system is 1.036 pu, which is within the voltage safety limit.
equivalent voltage source of receiving system is 1.036 pu, which is within the voltage safety limit.
Then, decrease
Then, decreasethe theSCR
SCRofof thethereceiving
receiving system while
system maintaining
while the SCR
maintaining the ofSCR
the of
sending system
the sending
as 1.95; as
system the1.95;
system will be will
the system unstable when the
be unstable SCRthe
when of SCR
the receiving system system
of the receiving decreases to 1.36 to
decreases or 1.36
less.
The calculated eigenvalues of matrix A , the state variable with the participation
or less. The calculated eigenvalues of matrix Asys, the state variable with the participation factor of
sys factor of the largest
absolute
the largestvalue (denoted
absolute as ‘SVLPF’)
value (denotedand the respective
as ‘SVLPF’) participation
and the respectivefactor (denotedfactor
participation as ‘LPF’) are listed
(denoted as
in Table 5.
‘LPF’) are listed in Table 5.
original
Next, value to two times
the robustness its on
analysis original value (0.053–0.212).
the procedure is conductedThe calculated
by changing minimum
KiQg2 from half SCRits
requirement of the receiving end, together with the 23-th eigenvalue, is plotted
original value to two times its original value (0.053–0.212). The calculated minimum SCR requirement in Figure 10. The
results show that
of the receiving thetogether
end, calculated withminimum
the 23-th SCR remainsisunchanged
eigenvalue, with the
plotted in Figure 10. decrease
The results step of 0.01,
show that
although the 23-th eigenvalue changes a little with the variation of K iQg2. The robustness of the
the calculated minimum SCR remains unchanged with the decrease step of 0.01, although the 23-th
procedure
eigenvalueischangesproved.a little with the variation of K . The robustness of the procedure is proved.
iQg2
1.40
0.014
1.38
23-th eigenvalue
0.012
Minimum SCR
1.36 0.010
0.008
1.34
0.006
Minimum SCR
1.32 23-th eigenvalue 0.004
1.30 0.002
0.06 0.08 0.10 0.12 0.14 0.16 0.18 0.20
KiQg2
Figure 10.
Figure 10. Minimum SCR and 23-th eigenvalue
eigenvalue of
of test
test system
system with
with different
differentKKiQg2
iQg2. .
5.2.2. Time-Domain
5.2.2. Time-Domain Validation
Validation
The time-domain
The time-domain validation
validation was
was performed
performed on
on PSCAD/EMTDC.
PSCAD/EMTDC. The The simulation
simulation results
results of
of the
the
minimum sending end SCR and the minimum receiving end SCR are plotted in Figures 11 and
minimum sending end SCR and the minimum receiving end SCR are plotted in Figures 11 and 12. 12.
Energies 2019, 12, 3283 15 of 20
Energies
Energies2019,
2019,12,
12,xxFOR
FORPEER
PEERREVIEW
REVIEW 16
16 of
of 21
21
1.04
1.04 0.06
0.06
Rectifier
Rectifier
power/pu
Reactive power/pu
power/pu
Active power/pu
Inverter
Inverter 0.03
0.03
Rectifier
Rectifier
1.00
1.00
Inverter
Inverter
0.96
SCR
SCRfrom
from1.95
1.95to
to1.91
1.91 0.00
0.00
0.96
Reactive
Active
-0.03
-0.03
0.92
0.92
-0.06
-0.06
1.2
1.2 1.6
1.6 2.0
2.0 2.4
2.4 2.8
2.8 3.2
3.2 3.6
3.6 4.0
4.0 1.2
1.2 1.6
1.6 2.0
2.0 2.4
2.4 2.8
2.8 3.2
3.2 3.6
3.6 4.0
4.0
1.04
1.04 Time/s
Time/s 1.04
1.04 Time/s
Time/s
Rectifier
Rectifier
1.02
1.02
Voltage/pu
PCC Voltage/pu
Inverter
Inverter
Voltage/pu
DC Voltage/pu
1.00
1.00 1.00
1.00
0.98
0.98 Rectifier
Rectifier
0.96
0.96 0.96
0.96 Inverter
Inverter
0.94
0.94
PCC
DC
0.92
0.92 0.92
0.92
0.90
0.90
1.2
1.2 1.6
1.6 2.0
2.0 2.4
2.4 2.8
2.8 3.2
3.2 3.6
3.6 4.0
4.0 1.2
1.2 1.6
1.6 2.0
2.0 2.4
2.4 2.8
2.8 3.2
3.2 3.6
3.6 4.0
4.0
Time/s
Time/s Time/s
Time/s
1.4 UUcpa_av
cpa_av UUcna_av
cna_av UUcpb_av
cpb_av 1.4 UUcpa_av
cpa_av UUcna_av
cna_av UUcpb_av
cpb_av
capacitor
1.4 1.4
SM capacitor
inverter/pu
of inverter/pu
rectifier/pu
of rectifier/pu
UUcnb_av
cnb_av UUcpc_av
cpc_av UUcnc_av
cnc_av UUcnb_av
cnb_av UUcpc_av
cpc_av UUcnc_av
cnc_av
1.2
1.2 1.2
1.2
1.0
1.0 1.0
1.0
Average SM
1.1
1.1 1.1
1.1
0.8
0.8 0.8
0.8
voltage of
1.0
1.0 1.0
voltage of
1.0
Average
voltage
0.9
0.9 0.9
0.9
0.6 0.6
voltage
Figure
Figure 11.
Figure 11.Simulation
11. Simulationresults
Simulation results of
results of minimum
of minimum sending
minimum sending end
sending end SCR.
end SCR.
SCR.
1.0
1.0 0.0
0.0
Power/pu
Active Power/pu
power/pu
Reactive power/pu
-0.5
-0.5
0.5
0.5
Rectifier
Rectifier
-1.0
-1.0
Inverter
Inverter
0.0 -1.5
-1.5
0.0
Rectifier
Rectifier
Active
Reactive
-2.0
-2.0
-0.5
-0.5 -2.5 Inverter
Inverter
SCR
SCRfrom
from1.37
1.37to
to1.32
1.32 -2.5
-3.0
-3.0
1.2
1.2 1.6
1.6 2.0
2.0 2.4
2.4 2.8
2.8 3.2
3.2 3.6
3.6 4.0
4.0 1.2
1.2 1.6
1.6 2.0
2.0 2.4
2.4 2.8
2.8 3.2
3.2 3.6
3.6 4.0
4.0
3.5
3.5 Time/s
Time/s 3.5
3.5 Time/s
Time/s
voltage/pu
PCC voltage/pu
voltage/pu
DC voltage/pu
3.0
3.0 3.0
3.0
2.5
2.5 2.5
2.5 Rectifier
Rectifier
2.0
2.0
Rectifier
Rectifier 2.0
2.0 Inverter
Inverter
Inverter
Inverter
PCC
1.5
DC
1.5
1.5 1.5
1.0
1.0 1.0
1.0
1.2
1.2 1.6
1.6 2.0
2.0 2.4
2.4 2.8
2.8 3.2
3.2 3.6
3.6 4.0
4.0 1.2
1.2 1.6
1.6 2.0
2.0 2.4
2.4 2.8
2.8 3.2
3.2 3.6
3.6 4.0
4.0
3.5
3.5
Time/s
Time/s 3.5
3.5
Time/s
Time/s
UUcpa_av UUcna_av UUcpb_av UUcpa_av UUcna_av UUcpb_av
capacitor
/pu
capacitor
/pu
SM capacitor
voltage of rectifier /pu
SM capacitor
inverter /pu
1.1 1.1
of inverter
1.1
2.5
2.5 1.0
1.0 2.5
2.5 1.0
1.0
2.0
2.0 0.9
0.9 2.0
2.0 0.9
0.9
Average SM
Average SM
1.60
1.60 1.62
1.62 1.64
1.64 1.60
1.60 1.62
1.62 1.64
1.64
of
voltage of
1.5
1.5 1.5
1.5
Average
Average
voltage
voltage
1.0
1.0 1.0
1.0
1.2
1.2 1.6
1.6 2.0
2.0 2.4
2.4 2.8
2.8 3.2
3.2 3.6
3.6 4.0
4.0 1.2
1.2 1.6
1.6 2.0
2.0 2.4
2.4 2.8
2.8 3.2
3.2 3.6
3.6 4.0
4.0
Time/s
Time/s Time/s
Time/s
Figure
Figure 12.
12. Simulation
Simulation results
resultsof
of minimum
minimum receiving
receiving end
end SCR.
SCR.
As seen
As seen inin Figures
Figures11 11and
and12,
and 12,U
12, U is average
crj_av is
Ucrj_av
crj_av average SM capacitor voltage,
SM capacitor wherejj(j(j=
voltage,where == a,a, b,
b, c) denotes
c) denotes
denotes
phase
phase and r (r = p, n) denotes the upper
phase and r (r == p, n) denotes the upper or lower arm. or lower arm.
As seen
As seenin
seen inFigure
in Figure
Figure 11,11,
thethe
11, rectifier
the rectifierMMC
rectifier MMC
MMC could not transmit
could
could not 1.0 pu1.0
not transmit
transmit active
1.0 pu power
pu active if
active the SCR
power
power decrease
ifif the
the SCR
SCR
from 1.95from
decrease
decrease to 1.91.
from 1.95When
1.95 to SCRWhen
to 1.91.
1.91. is lessSCR
When thanis
SCR 1.95,
is lessthe
less thanAC1.95,
than system
1.95, theequivalent
the AC systemvoltage
AC system source
equivalent
equivalent is limited
voltage
voltage sourceto the
source is
is
voltage
limited safety
limited to
to the limit
the voltage (1.2 pu),
voltage safety and
safety limit the
limit (1.2 decrease
(1.2 pu),
pu), and would
and the cause
the decrease the voltage
decrease would
would causedrop
cause theat PCC.
the voltageIn consideration
voltage dropdrop at at PCC.
PCC.
of
In the
In current constraint
consideration
consideration of the [13],
of the current
current the constraint
active
constraint power of rectifier
[13],
[13], the
the activewould
active power
powerinevitably
of decrease.
of rectifier
rectifier would
would The relevant
inevitably
inevitably
MMC-HVDC
decrease.
decrease. TheThecould
relevantoperate
relevant MMC-HVDCstably under
MMC-HVDC could
could thisoperate
circumstance.
operate stably The
stably under
undersimulation
this results areThe
this circumstance.
circumstance. consistent
The simulation
simulationwith
results
results are
are consistent
consistent withwith thethe analytical
analytical results,
results, andand prove
prove that
that the
the rectifier
rectifier could
could not
not transmit
transmit 1.0 1.0
pu
pu active
active power
power withwith anan SCR
SCR lowerlower than
than 1.95 1.95 when
when considering
considering thethe voltage
voltage safety
safety limit
limit constraint.
constraint.
Energies 2019, 12, 3283 16 of 20
the analytical results, and prove that the rectifier could not transmit 1.0 pu active power with an SCR
lower than 1.95 when considering the voltage safety limit constraint.
As seen in Figure 12, the MMC-HVDC could not operate stably if the SCR of the receiving
system decreases from 1.37 to 1.32. The simulation results are consistent with the analytical results by
small-signal analysis and demonstrate that the MMC-HVDC could not operate stably with an SCR
lower than 1.36 when transmitting 1.0 pu active power.
Although certain errors exist between the simulation results and the analytical results, the error
is relatively small enough and is acceptable. Therefore, the validity of the proposed procedure to
determine the minimum SCR is proved.
Rectifier Inverter
Impedance
Angle/◦ Minimum SCR Restraint Factor Minimum SCR Restraint Factor
80 1.95 VSLC 1.36 MiQg2
82 1.85 VSLC 1.37 MiQg2
86 1.67 VSLC 1.38 MiQg2
90 1.51 VSLC 1.46 VSLC
(1) The calculated minimum SCR is concerned with MMC operation mode and the AC system
impedance angle. For the rectifier MMC, the minimum SCR varies 1.51–1.95, and the increase of
the AC system impedance angle would make the minimum SCR decrease. For the inverter MMC,
the minimum SCR varies 1.36–1.46, and the increase of the AC system impedance angle would
make the minimum SCR increase.
(2) The minimum SCR requirement for the rectifier is larger than for the inverter, which means that
the SCR requirement for the connected AC system is stricter for the rectifier MMC.
(3) For transmitting 1.0 pu active power, the restraint factor for rectifier is the voltage safety limit
constraint while the restraint factor for the inverter is mainly the outer reactive power controller.
(1) The calculated minimum SCR is concerned with MMC operation mode and the AC system
impedance angle. For the rectifier MMC, the minimum SCR varies 1.51–1.95, and the increase of
AC system impedance angle would make the minimum SCR decrease. For the inverter MMC,
the minimum SCR varies 1.51–1.40, and the increase of AC system impedance angle would make
the minimum SCR increase.
(2) The minimum SCR requirement for the rectifier is larger than that for the inverter, indicating that
the SCR requirement for the connected AC system is stricter for the rectifier MMC.
Energies 2019, 12, 3283 17 of 20
(3) For transmitting 1.0 pu active power, the restraint factor for rectifier is the voltage safety
limit constraint; in contrast, the restraint factor for the inverter is mainly the outer reactive
power controller.
Rectifier Inverter
Impedance
Angle/◦ Minimum SCR Restraint Factor Minimum SCR Restraint Factor
80 1.95 VSLC 1.40 MiQg2
82 1.85 VSLC 1.41 MiQg2
86 1.67 VSLC 1.42 MiQg2
90 1.51 VSLC 1.51 VSLC
(1) The calculated minimum SCR is concerned with MMC operation mode and the AC system
impedance angle. For the rectifier MMC, the minimum SCR varies 1.51–1.95, and the increase of
AC system impedance angle would make the minimum SCR decrease. For the inverter MMC,
the minimum SCR varies 1.46–1.34, and the increase of the AC system impedance angle would
make the minimum SCR increase.
(2) The minimum SCR requirement for the rectifier is larger than that for the inverter, indicating that
the SCR requirement for the connected AC system is stricter for the rectifier MMC.
(3) For transmitting 1.0 pu active power, the restraint factor for rectifier is the voltage safety limit
constraint; however, the restraint factor for the inverter is mainly the PLL.
Rectifier Inverter
Impedance
Angle/◦ Minimum SCR Restraint Factor Minimum SCR Restraint Factor
80 1.95 VSLC 1.34 Miθ2 , θg2
82 1.85 VSLC 1.35 Miθ2 , θg2
86 1.67 VSLC 1.36 Miθ2 , θg2
90 1.51 VSLC 1.46 VSLC
(1) The calculated minimum SCR is concerned with MMC operation mode and the AC system
impedance angle. For the rectifier MMC, the minimum SCR varies 1.51–1.95, and the increase of
AC system impedance angle would make the minimum SCR decrease. For the inverter MMC,
the minimum SCR varies 1.51–1.39, and the increase of AC system impedance angle would make
the minimum SCR increase.
(2) The minimum SCR requirement for the rectifier is larger than that for the inverter, indicating that
the SCR requirement for the connected AC system is stricter for the rectifier MMC.
(3) For transmitting 1.0 pu active power, the restraint factors for the rectifier are the voltage safety
limit constraint; however, the restraint factor for the inverter is mainly the PLL.
Energies 2019, 12, 3283 18 of 20
Rectifier Inverter
Impedance
Angle/◦ Minimum SCR Restraint Factor Minimum SCR Restraint Factor
80 1.95 VSLC 1.39 MiQg2
82 1.85 VSLC 1.40 MiQg2
86 1.67 VSLC 1.41 MiQg2
90 1.51 VSLC 1.51 VSLC
(1) For transmitting 1.0 pu active power, the minimum SCR requirement for rectifier varies 1.51–1.95,
and the increase of AC system impedance angle would make the minimum SCR decrease.
The minimum SCR requirement of rectifier has nothing to do with the control scheme of
rectifier MMC.
(2) For transmitting 1.0 pu active power, the minimum SCR requirement for inverter varies 1.34–1.51,
and the increase of AC system impedance angle would make the minimum SCR increase.
The minimum SCR requirement is the largest when the inverter MMC controls the active power
and the reactive power. The minimum SCR requirement is the lowest when the inverter MMC
controls the DC and the AC voltage.
(3) The minimum SCR requirement is higher for the rectifier MMC than for the inverter MMC.
The restraint factor for the rectifier MMC is voltage safety limit constraint while the restraint
factors for inverter are mainly the PLL or the outer reactive power controller.
(4) The MMC-HVDC could keep operating stably if the SCR of the sending system is slightly lower
than the minimum SCR requirement. The MMC-HVDC could not operate stably if the SCR of
receiving system is slightly lower than the minimum SCR requirement.
6. Conclusions
On the basis of a small-signal stability analysis, the minimum SCR requirement for MMC-HVDC
system is studied in this paper. The results show that the restraint factors for the rectifier MMC is
mostly the voltage safety limit constraint, and the minimum SCR requirement of the sending system
has nothing to do with the control scheme of rectifier MMC. The restraint factors for inverter MMC is
mainly the PLL or the outer reactive power controller; the minimum SCR requirement is the lowest
when the inverter MMC controls the DC and AC voltage. The minimum SCR requirement for the
connected AC system is stricter for the rectifier; the minimum SCR requirements for the sending and
the receiving systems are suggested to be 2.0 and 1.5 in the planning stage. Note that the concerned
MMC-HVDC consists of half bridge SMs and adopts vector current control scheme. Future research
on this topic could focus on the minimum SCR requirement for MMC-HVDC with full bridge SMs
and minimum SCR requirement for MMC-HVDC with other control schemes such as the virtual
synchronous generator control scheme or the power synchronization control scheme.
Author Contributions: Conceptualization, Z.X.; Methodology, Z.X. and Z.Z.; Validation, Z.Z. and G.W.;
Formal Analysis, Z.Z.; Investigation, L.X., J.Y. and Z.Z.; Writing-Review & Editing, Z.Z., L.X., G.W. and
J.Y.; Supervision, Z.X.
Funding: This research received no external funding.
Conflicts of Interest: The authors declare no conflict of interest.
Energies 2019, 12, 3283 19 of 20
Appendix A
The detailed mathematical expression of the matrix A0v , B0r , C0v , D0r and D0u are as follows:
R+K ωn
− L pd ωn 0 L 0 0 0
R+Kpq ωn
0 − L ωn 0 0 0
L
0
−K id 0 0 0 0 0
Av = (A1)
0 −Kiq 0 0 0 0
Kiθ Ls F
−K ω L F Kiθ FF1 0 − −Kiθ Ls ivd0 F Kiθ FUq0
iθ g0 s L
Kpθ Ls F
−Kpθ ω g0 Ls F Kpθ FF1 0 − L F Kpθ FUq0
Kpd
T
L ωn 0 Kid 0 0 0
B0r = Kpq Kiθ Kpq Ls F Kpθ Kpq Ls F
(A2)
L ωn
0 0 Kiq − L − L
F = 1+K 1Ls i
pθ vd0
Kpq Ls +RLs −LRs
(A3)
F1 = L
F2 = Kpd Ls +RLs −LRs
L
C1 C2 ivd0 (1+Ls /L) ivq0 (1+Ls /L) Ud0 ivd0 +Uq0 ivq0
C0v = uCeq0 uCeq0 − uCeq0 − uCeq0 0 uCeq0 (A4)
Kpd ivd0 (1+Ls /L) Kpq ivq0 (1+Ls /L)
D0r = − uCeq0 − uCeq0
(A5)
References
1. Eriksson, K. Operational Experience of HVDC Light/TM. In Proceedings of the Seventh International
Conference on AC-DC Power Transmission, London, UK, 28–30 November 2001; pp. 205–210.
2. Friedrich, K. Modern HVDC PLUS application of VSC in Modular Multilevel Converter topology. IEEE Int.
Symp. Ind. Electron. 2010, 3807–3810.
3. Peralta, J.; Saad, H.; Dennetiere, S.; Mahseredjian, J.; Nguefeu, S. Detailed and Averaged Models for a
401-Level MMC-HVDC System. IEEE Trans. Power Deliv. 2012, 27, 1501–1508. [CrossRef]
4. Allebrod, S.; Hamerski, R.; Marquardt, R. New Transformerless, Scalable Modular Multilevel Converters for
HVDC-Transmission. In Proceedings of the IEEE Power Electronics Specialists Conference, Rhodes, Greece,
15–19 June 2008; pp. 174–179.
5. Zhang, G.; Xu, Z.; Liu, H. Supply Passive Networks with VSC-HVDC. In Proceedings of the Power
Engineering Society Summer Meeting, Vancouver, BC, Canada, 15–19 July 2001.
6. Dong, H.; Xu, Z.; Song, P. Optimized Power Redistribution of Offshore Wind Farms Integrated VSC-MTDC
Transmissions after Onshore Converter Outage. IEEE Trans. Ind. Electron. 2016, 64, 8948–8958.
7. Tang, G.; Xu, Z.; Dong, H. Sliding Mode Robust Control Based Active-Power Modulation of Multi-Terminal
HVDC Transmissions. IEEE Trans. Power Syst. 2015, 31, 1614–1623. [CrossRef]
8. IEEE. IEEE Guide for Planning DC Links Terminating at AC Locations Having Low Short-Circuit Capacities; IEEE
press: Piscataway, NJ, USA, 1997.
9. CIGRE WG 14.07. IEEE WG 15.05. Guide for Planning DC Links Terminating at AC Locations Having Low
Short-Circuit Capacities, Part 1: AC/DC Interaction Phenomena; CIGRE: Paris, France, 1992.
10. Liu, S.; Xu, Z. Study on stable operating region of VSC-HVDC connected to weak AC systems. Proc. CSEEE
2016, 36, 133–144. (In Chinese)
11. Zhou, J.; Gole, A. VSC Transmission Limitations Imposed by Ac System Strength and Ac Impedance
Characteristics. In Proceedings of the 10th IET International Conference on ac and DC Power Transmission,
Birmingham, UK, 4–5 December 2012.
Energies 2019, 12, 3283 20 of 20
12. Zhou, J.; Gole, A. Rationalization of DC Power Transfer Limits for VSC Transmission. In Proceedings of the
11th IET International Conference on ac and DC Power Transmission, Birmingham, UK, 10–12 February 2015.
13. Zhang, Z.; Xu, Z.; Jiang, W.; Bie, X. Operating Area for Modular Multilevel Converter Based High-Voltage
Direct Current Systems. Proc. IET Renew. Power Gener. 2016, 10, 776–787. [CrossRef]
14. Durrant, M.; Werner, H.; Abbott, K. Model of a VSC HVDC Terminal Attached to a Weak AC System.
In Proceedings of the 2003 IEEE Conference on Control Applications, Istanbul, Turkey, 25 June 2003;
pp. 178–182.
15. Zhou, J.; Ding, H.; Fan, S. Impact of short-circuit ratio and phase-locked-loop parameters on the small-signal
behavior of a VSC-HVDC converter. IEEE Trans. Power Deliv. 2014, 29, 2287–2296. [CrossRef]
16. Yuan, B.; Li, T.; Xu, J.; Yuan, Y.; Zhao, C.; Zhang, F. Small-signal Stability Analysis of Modular Multilevel
Converter Connected to a Weak AC System. Proc. CSEE 2017, 37, 5339–5349. (In Chinese)
17. Guo, C.; Yin, Z.; Zhao, C. Comparative Study on Small-signal Stability of MMC-HVDC System under
Rectification and Inversion Modes. Proc. CSEE 2018, 38, 7349–7358. (In Chinese)
18. Ding, H.; Fan, S.; Zhou, J. Parametric Analysis of the Stability of VSC-HVDC Converters. In Proceedings of
the 11th IET International Conference on AC and DC Power Transmission, Birmingham, UK, 10–12 February
2015; pp. 1–6.
19. Lu, S.; Xu, Z.; Xiao, L. Evaluation and enhancement of control strategies for VSC stations under weak grid
strengths. IEEE Trans. Power Syst. 2017, 33, 1836–1847. [CrossRef]
20. Jamshidifar, A.; Jovcic, D. Small Signal Dynamic DQ Model of Modular Multilevel Converter for System
Studies. In Proceedings of the 2016 IEEE Power and Energy Society General Meeting, Boston, MA, USA,
17–21 July 2016.
21. Song, Q.; Liu, W.; Li, X. A Steady-State Analysis Method for a Modular Multilevel Converter. IEEE Trans.
Power Electron. 2013, 28, 3702–3713. [CrossRef]
22. Guan, M.; Xu, Z. Modeling and Control of a Modular Multilevel Converter-Based HVDC System Under
Unbalanced Grid Conditions. IEEE Trans. Power Electron. 2012, 27, 4858–4867. [CrossRef]
23. Kaura, V.; Blasko, V. Operation of a phase locked loop system under distorted utility conditions. IEEE Trans.
Ind. Appl. 1997, 33, 58–63. [CrossRef]
24. Kundur, P. Power System Stability and Control; McGraw-Hill: New York, NY, USA, 1994.
25. Gole, A.; Zhou, J. Rationalisation and validation of dc power transfer limits for voltage sourced converter
based high voltage DC transmission. IET Gener. Transm. Distrib. 2016, 10, 1327–1335.
26. Xiao, L.; Xu, Z.; Xiao, H.; Zhang, Z.; Wang, G.; Xu, Y. Electro-mechanical transient modeling of MMC
based multi-terminal HVDC system with DC faults considered. Int. J. Electr. Power Energy Syst. 2019, 113,
1002–1013. [CrossRef]
© 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).