SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Concrete Fireproofing Final Inspection SAIC-B-1004 15-Nov-17 CIVIL-


PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

All cementitious fireproofing (whether dense or lightweight concrete) shall


be provided with a top coat under any of the following conditions:
1. When coating is required by the manufacturer;
2. When fireproofing is installed within 9 meters vertically from grade. SAES-B-006
A1
3. When fireproofing is installed on equipment that is protected by a Sec. 8.5.1
fixed firewater spray or deluge system;
4. When fireproofing is installed below atmospheric drains or vents that
are used during normal operations.

Prior to top coating, the surface shall be dry, free from defects and loose
SAES-B-006
A2 contaminants shall have been removed by brushing with a stiff bristle
Sec. 8.5.2
brush and vacuuming.

Fireproofing must be fully cured in accordance with the manufacturer's SAES-B-006


A3
technical requirements, prior to top-coat application. Sec. 8.5.2

• First top coat, Saudi Aramco Stock Number 1000194629 shall be


SAES-B-006
A4 thinned 10% to 15% and applied to a dry-film thickness of 50 to
Sec. 8.5.2
90 micrometers.

• Second top coat, Saudi Aramco Stock Number 1000194797 shall be SAES-B-006
A5
applied to dry-film thickness of 75 to 125 micrometers. Sec. 8.5.2

The minimum thickness of dense concrete is 50mm from reinforcing wire SASD
A6
mesh and the material complies with 09-SAMSS-097 and SAES-Q-001. AC-036711

The minimum thickness of fireproofing materials for structural members


and vessel supports, other than qualifying dense concrete, provide a
SAES-B-006
A7 minimum fire-resistance rating of two (2) hours when subjected to a test
Sec. 7.2
furnace environment in accordance with UL 1709 or an equivalent fire
exposure test procedure accepted by the Chief Fire Prevention Engineer.

REMARKS:

REFERENCE DOCUMENTS:
1- SAES-B-006 -- Fireproofing for Plants, 20 November 2011
2- SASD-AD-036711 -- Concrete Fireproofing for Structural Members, 1 September 2000

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

Saudi Aramco: Company General Use


QC Supervisor Proponent and Others
Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

Saudi Aramco: Company General Use