Fuel Application type Foam Pan Size Nozzle Test App Design Built-in
Application (m2) Flow rate App rate Safety
time (l/min) (lpm/m2) (lpm/m2) Factor
(minutes)
Hydrocarbons UL-162 Type III Heptane Direct 5 4.65 11.4 2.45 6.5* 166%
(Water Immiscible SFFF (Synthetic)
Fuels)
UL-162 Type III Heptane Direct 3 4.65 7.6 1.63 4.1* 151%
AFFF category
EN1568-3 Heptane Direct 3 4.50 11.4 2.53 4.0** 58%
1A Rated Products
Polar Fuels UL-162 Type II IPA Gentle 5 4.65 19.0 4.10 6.9* 67%
(Water Miscible All Products Acetone
Fuels)
EN1568-4 IPA Gentle 3 1.73 11.4 6.58 8.0** 21%
1A Rated Products Acetone
Significant Pan size reduction in EN on Heptane * As per UL or NFPA
versus Polar fuels ~ 1/3 ** As per EN13565-2
VS Key Benefits from UL-162 Approach versus EN1568 = Increased Safety Factor
from test rates to design rates!!
1. Passes UL 162 Type III test protocol on heptane fuel at the same
design application rate (0.10 gpm/ft2 / 4.1 lpm/m2 ) as AR-AFFF
▪ Test Application rate at 0.04 gpm/ft2 (1.63 lpm/m2 )
▪ Test results 3rd party witnessed by UL
▪ Similar time to control the fire as a high-quality AR-AFFF
3%x3% AR-NFF
Test Standard Application / Fuels Test App rate Listed App Rate Status *
lpm/m2 lpm/m2
Type III Hydrocarbon Hydrocarbons (AFFF) 1.6 4.1 UL Witnessed
Forceful Application Hydrocarbons (Synthetic) 2.4 6.5 UL Tested
Premium Gasoline 2.4 6.5 UL Witnessed
E15 (15% Ethanol / 85% Gasoline) 4.1 6.9 UL Tested
Type II Hydrocarbon
Hydrocarbons 1.6 4.1 UL Tested
UL-162 Gentle Application
Type II Polar Fuels Alcohols 4.1 6.9 UL Tested
Gentle Application Ethanol 2.4 4.1 UL Tested
Ketones 4.1 6.9 UL Tested
E85 (85% Ethanol / 15% Gasoline) 3.7 6.1 UL Tested
Methanol 2.4 4.1 Internal testing
Part 3 – Heptane Water immiscible Fuels - Low Expansion 2.5 1A / 1A MPA Tested
EN1568:2018 Part 4 – Acetone Water miscible Fuels – Low Expansion 6.5 1A / 1A MPA Tested
Part 4 – IPA Water miscible Fuels – Low Expansion 6.5 1B / 1A MPA Tested
IMO Msc 1312 Pass Internal testing
LASTFIRE Batch test protocol on Hydrocarbons Good / Good / Good Internal testing
# 250%
JCI 3x3 AR-NFF has been evaluated internally against the latest LastFire test protocol
* Despite Overall fail result on Semi-Aspirated Salt Water test, the 90% Control times on the 2 test runs were
well within the other testing. Remaining flickers at the end of the test prevented to qualify for better results.
Pump Pump Prop. Foam Pump Dike & Float roof Monitors
Proportioners Wide Range Foam Pourers FLR
11
JCI Hardware used with NFF