FAN COIL
THERMOSTATS
AN OVERVIEW
Fan Coil Thermostats

TABLE OF CONTENTS
FEATURES....................................................................................................3

EDGE T-STAT CODE BREAKDOWN............................................................4

PROGRAMMING.........................................................................................5

WIRING DIAGRAMS...................................................................................6
Fan Coil Thermostats

FEATURES
The table below describes the thermostats that will be provided.

T-STAT CODE PRODUCT OVERVIEW STANDALONE MODEL BACNET MODEL DESCRIPTION


N03H
N03C
N05
N07
N08
N11 Digital & BACnet Capable
F03H
User or BAS Occupancy Schedule
F03C
F05 Color LCD Touchscreen Display
Johnson Controls Johnson Controls
F07 TEC3312 TEC3612
USB Configuration Available
F08
Built-In Occupancy & Humidity Sensors
F11
V03H Plug/Play: Verasys BAS, MAP Access Tool
V03C
V05
V07
V08
V11
P03H
LCD Display
P03C
P05 Time Display
Johnson Controls
P06 FCP-PA-701-L (Lux)
Frost and Overheat Protection
P08
User Set 7-Day Schedule: Occupied/Unoccupied
P11
N/A
D03H
LCD Display
D03C
D05 Non-Programmable
Johnson Controls
D06 FCP-NA-701-L (Lux)
Frost and Overheat Protection
D08
Unoccupied Mode via Sensor
D11
NOTES: For more information, reach out to Krueger Application Engineering at kruegerterminalunits-equip@krueger-hvac.com or (972) 680–9136, ext. 3.
Installation manuals are available.

3
Fan Coil Thermostats

EDGE T-STAT CODE BREAKDOWN


The table below describes the thermostat to be provided based on the code chosen.

COOL/HEAT
T-STAT TYPE SYSTEM TYPE T-STAT CODE CONTROL TYPE C FAN CONTROL WATER CONTROL AVAILABLE
CHANGEOVER
N03H Heat Only None
“N-SERIES”
N03C Cool Only None
Thermostat/BAS Auto
DIGITAL 2-pipe ON/OFF Actuator Only
N05 Heat/Cool Auto (H-M-L, or based on demand),
or set by user (H-M-L)
NETWORKING N07 Heat/Cool with Auxiliary Electric Heat Auto
COMPATIBLE N08 Cool with Electric Heat Auto
4-pipe N11 Heat/Cool Auto Same as above Same as above
F03H Heat Only None
“F-SERIES”
F03C Cool Only None
Thermostat/BAS Auto
DIGITAL 2-pipe
F05 Heat/Cool Auto (H-M-L, or based on demand), Floating Point Actuator Only
or set by user (H-M-L)
NETWORKING F07 Heat/Cool with Auxiliary Electric Heat Auto
COMPATIBLE F08 Cool with Electric Heat Auto
4-pipe F11 Heat/Cool Auto Same as above Same as above
P03H Heat Only Nonea
“P-SERIES”
P03C Cool Only Nonea
Thermostat can switch fan speeds
DIGITAL 2-pipe
P05 Heat/Cool Autob (H-M-L) based on demand, ON/OFF Actuator Only
or manually by user*
7-DAY P06 Heat/Cool with Auxiliary Electric Heat Autob
PROGRAM P08 Cool with Electric Heat Autob
4-pipe P11 Heat/Cool Autoc Same as above Same as above
D03H Heat Only None
“D-SERIES”
D03C Cool Only None
Thermostat can switch fan speeds
DIGITAL 2-pipe
D05 Heat/Cool Auto (H-M-L) based on demand, ON/OFF Actuator Only
or manually by user*
NO 7-DAY D06 Heat/Cool with Auxiliary Electric Heat Auto
PROGRAM D08 Cool with Electric Heat Auto
4-pipe D11 Heat/Cool Auto Same as above Same as above
V03H Heat Only
“V-SERIES” None
V03C Cool Only
Thermostat/BAS auto
DIGITAL 2-pipe
V05 Heat/Cool (H-M-L, or based on demand), Proportional Actuator Only
or set by user (H-M-L)
NETWORKING V07 Heat/Cool with Auxiliary Electric Heat Auto
COMPATIBLE V08 Cool with Electric Heat
4-pipe V11 Heat/Cool Auto Same as above Same as above
NOTES: Fan and valves are controlled with a 24VAC signal sent from the thermostat to the relay board via the appropriate terminal.
* Manual fan setting would force fan OFF, or into continuous operation at set speed.
a. Can be programmed to turn ON/OFF based on schedule desired
b. Changeover can occur based on room temperature demand, or operation can be automated based on user schedule.
c. OFF mode is available for all thermostats.
EDGE will automatically prevent the user from selecting something that is not compatible with the current configuration. This means that the code may seem
unavailable (greyed out), at first.
This could be due to the actuator type (ON/OFF or Floating) or a fan speed control option chosen.
For “N”,”F” and “V” series specifically, this is also due to the requirement to specify networking capability. Under “Network Capability” choose either
Standalone or BACnet Enabled to then see the available N-series , V-series or F-series thermostats.

4
Fan Coil Thermostats

PROGRAMMING
Below are some of the common defaults the thermostats are programmed with at the factory. These are subject to change
with each order based on the configuration.

THERMOSTAT VARIABLE N-SERIES F-SERIES V-SERIES


N03H N03C F03H F03C V03H V03C
PARAMETER DESCRIPTION N05 N07 F05 F07 V05 V07
N08 N11 F08 F11 V08 V11
Occ Cool Setpoint Occupied Cooling Setpoint 72
Occ Heat Setpoint Occupied Heating Setpoint 68
Unocc Cool Setpoint Unoccupied Cooling Setpoint 80
Unocc Heat Setpoint Unoccupied Heating Setpoint 60
Schedule Source Determines Schedule: Set at Thermostat (Schedule), or BAS (External) Based on Order
Time Zone Time Zone Central
Language Language English
Control Mode See Control Type column above Based on Order
Fan Mode See Fan Control column above Based on Order
Fan ON/OFF Delay After a call for fan operation, delay for it to turn ON 30 seconds
Deadband Zone is satisfied in this temperature range around setpoint, up to 6°F 2°F
FC Comm Mode Network communication type (if applicable) BACnet/MSTP
Device Address Individual thermostat identifier for network (if applicable) 4
BACnet Encoding Type Standard for network communication (if applicable) ISO 10646 (UCS-2)
Unit Type See System Type Column above Based on Order
Heat/Cool Dev Type See Water Control Available column above Based on Order
Actuator Stroke Time Time duration for damper to go from closed to fully open 30 seconds

THERMOSTAT VARIABLE P-SERIES D-SERIES *


P03H P03C D03H D03C
PARAMETER DESCRIPTION P05 P06 D05 D06
P08 P11 D08 D11
Key Lock Locks/Unlocks access to thermostat Button Combination
Time and Day For 7-day schedule purposes 12AM, Mon N/A
Configuration Profile Determines how thermostat runs thru sequence of operations Based on order
Temperature Scale Default temperatures scale °F
System Type Based on the number of coils and cooling/heating configuaration Based on order
Fan Speed Determines how the fan speed is controlled, see Fan Control Based on order
Deadband Zone is satisfied in this temperature range around setpoint, up to 5°F 4°F
Unoccupied Heat Zone Setpoint in Heating Mode while Unoccupied 55°F
Unoccupied Cool Zone Setpoint in Cooling Mode while Unoccupied 85°F
* Thermostat is not programmable. Depending on options needed, a different thermostat will be provided.

For more information, reference the documents listed below.

TEC3000 Series
Catalog Page: LIT-1901109
Product Bulletin: LIT-12013193

FCP
Product Bulletin: LIT-12013641
User Guide: LIT-12013635

5
Fan Coil Thermostats

WIRING DIAGRAMS
Below are examples of wiring the thermostat to the factory provided control board.

TEC THERMOSTAT WIRING


P5

230v P9
P4

208v P8
P3

155v P7
P2

P1
277v P10

NEUT
JP2
L2

LINE VOLTAGE IN S1
TS1 S2
MTR R TS1 (R)
PWR T1 C 24V-HOT TB4
TS2 C TS1 (S1)
TRANSFORMER Y1
BO5-AUX TB6
NEUT TS2 (Y1) 6
25 VA W1
24V-COM TB5
TO FAN MTR

JP3

TS3 Y2 TS3 (W1)5


HIGH BO26 TB11
G BO45 TB9
MED FCU RELAY BOARD H UI3 TB16
PATENT PENDING TS4 M
LOW L BO5-AUX TB7
SPEED (LOW)
EH RELAY FAN-L TB3
24 VAC SELECT COIL (MED) FAN-M TB2
HIGH

(HIGH)
HEAT
COM

COM
LOW
MED

FAN-H TB1
R
R

RS TB13

FAN COIL REMOTE MOUNTED


RELAY BOARD THERMOSTAT

GENERIC THERMOSTAT WIRING


FRBII3,4
FAN CONTROL
REALY BOARD

TB1.H
1 FAN-H
TB1.M
2 FAN-M
TB1.L
3 FAN-L
TB1.R
EARTH 4 24V~HOT
TP1 S1 TH1.5 TB1.S1
5 24V~COM
S2
TP2
R TH1.4 6 B05 AUX
C 7 B05 AUX
C 8 B03
G TB1.W1
10 9 BO4
H TH1.1
1 10 BO1
M TH1.2 TB1.Y1
11 BO2
L TH1.3
12 BI1
W1 TH1.9
13 RS
Y2
14 SCOM
Y1 TH1.11
15 BI2
16 UI3

LUX THERMOSTAT WIRING

NOTES: BO4 and BO2 are the heating and cooling terminals, respectively. For wiring peripheral devices (window switches, auxiliary heat, etc.) and
programming of the thermostat, see the installation manual and/or reach out to Krueger Application Engineering.

6
CONNECT WITH US!

YOUR RESOURCE FOR AIR DISTRIBUTION AND EQUIPMENT SOLUTIONS

Let us know how we can assist you in your next building application. For more information, contact
your local Krueger representative or visit us on the web at www.krueger-hvac.com.

CRITICAL ROOM SOLUTIONS TERMINAL UNITS DIFFUSERS GRILLES & REGISTERS


Single Duct Plaque & Architectural Supply
CHILLED BEAMS Fan Powered Louvered Return
Dual Duct Perforated Linear Bar
DISPLACEMENT VENTILATION Bypass & Retrofit Modular Core Security
Linear Slot Industrial
UNDERFLOOR FAN COILS & BLOWER COILS Plenum Slot Duct Mounted
Underfloor Diffusers Horizontal Round Transfer
Underfloor Terminal Units Vertical / Stack Air Nozzles Stainless Steel

1401 N. Plano Rd.


Richardson, TX 75081
tel: 972.680.9136
www.krueger-hvac.com
kruegerinfo@krueger-hvac.com
Fan Coil Thermostats: 08/17/2021
©Krueger 2021. All Rights Reserved.