Preliminary remarks
lum
Content
Cover page.....................................................................................................................................................................1
Preliminary remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Content............................................................................................................................................................................3
Description......................................................................................................................................................................4
Luminaire list..................................................................................................................................................................5
Street 1 · Alternative 1
Description......................................................................................................................................................................7
Summary (according to EN 13201:2015) ..........................................................8
Roadway 1 (M4)....................................................................................................................................................................11
Glossary.................................................................................................................................................................................20
lum
Description
4
lum
Luminaire list
28 Gewiss GWR5774
ROAD [5] MEDIUM - 4M - WIDE LED 730 0.7A DIM. 108.0 W 11000 lm 101.9 lm/W
M30K
1- 10V - I
5
lum
Gewiss - ROAD [5] MEDIUM - 4M - WIDE LED 730 0.7A DIM. 1-10V - I
P 108.0 W
ΦLuminaire 11000 lm
CCT 3259 K
CRI 70
Polar LDC
6
lum
Street 1
Description
7
lum
Street 1
Summary (according to EN 13201:2015)
8
lum
Street 1
Summary (according to EN 13201:2015)
ROAD [5] MEDIUM - 4M - WIDE LED 730 0.7A DIM. 1-10V - I (both sides opposite)
9
lum
Street 1
Summary (according to EN 13201:2015)
Uo 0.95 ≥ 0.40
Ul 0.95 ≥ 0.60
TI(3 ) - ≤ 15 % -
A maintenance factor of 0.67 was used for calculating for the installation.
1
lum
Street 1
Roadway 1 (M4)
Uo 0.95 ≥ 0.40
Ul 0.95 ≥ 0.60
TI(3 ) - ≤ 15 % -
Ul 0.95 ≥ 0.60
TI(3 ) - ≤ 15 % -
Ul 0.95 ≥ 0.60
TI(3 ) - ≤ 15 % -
1
lum
Street 1
Roadway 1 (M4)
1
lum
Street 1
Roadway 1 (M4)
m 0.550 1.650 2.750 3.850 4.950 6.050 7.150 8.250 9.350 10.450
4.500 122.17 122.85 116.69 110.59 108.23 108.23 110.59 116.69 122.85 122.17
3.900 118.17 117.68 110.25 105.23 102.22 102.22 105.23 110.25 117.68 118.17
3.300 114.55 112.46 105.84 100.56 97.10 97.10 100.56 105.84 112.46 114.55
2.700 114.55 112.46 105.84 100.56 97.10 97.10 100.56 105.84 112.46 114.55
2.100 118.17 117.68 110.25 105.23 102.22 102.22 105.23 110.25 117.68 118.17
1.500 122.17 122.85 116.69 110.59 108.23 108.23 110.59 116.69 122.85 122.17
Observer 1: Maintenance value, luminance with dry roadway [cd/m²] (Iso-illuminance curves)
1
lum
Street 1
Roadway 1 (M4)
Observer 1: Maintenance value, luminance with dry roadway [cd/m²] (Value grid)
m 0.550 1.650 2.750 3.850 4.950 6.050 7.150 8.250 9.350 10.450
4.500 8.17 8.15 8.02 7.93 7.95 7.95 7.94 8.00 8.13 8.23
3.900 8.54 8.46 8.23 8.17 8.19 8.18 8.24 8.25 8.40 8.54
3.300 8.66 8.48 8.25 8.20 8.15 8.08 8.17 8.22 8.35 8.58
2.700 8.64 8.50 8.27 8.19 8.16 8.09 8.16 8.20 8.32 8.54
2.100 8.71 8.60 8.36 8.29 8.29 8.27 8.32 8.35 8.52 8.66
1.500 8.55 8.50 8.36 8.27 8.30 8.32 8.31 8.37 8.48 8.57
Observer 1: Maintenance value, luminance with 8.30 cd/m² 7.93 cd/m² 8.71 cd/m² 0.95 0.91
dry roadway
1
lum
Street 1
Roadway 1 (M4)
1
lum
Street 1
Roadway 1 (M4)
m 0.550 1.650 2.750 3.850 4.950 6.050 7.150 8.250 9.350 10.450
4.500 12.20 12.17 11.98 11.83 11.86 11.86 11.85 11.94 12.14 12.28
3.900 12.75 12.62 12.28 12.19 12.22 12.21 12.29 12.31 12.54 12.74
3.300 12.92 12.66 12.32 12.23 12.16 12.07 12.19 12.27 12.46 12.80
2.700 12.90 12.68 12.35 12.23 12.17 12.08 12.18 12.24 12.41 12.74
2.100 13.00 12.84 12.48 12.38 12.37 12.34 12.41 12.46 12.71 12.92
1.500 12.77 12.69 12.47 12.34 12.39 12.41 12.40 12.49 12.66 12.80
Lav
Lmin Lmax g1 g2
Observer 1: Luminance with new 12.4 cd/m² 11.8 cd/m² 13.0 cd/m² 0.95 0.91
installation
Observer 2: Maintenance value, luminance with dry roadway [cd/m²] (Iso-illuminance curves)
1
lum
Street 1
Roadway 1 (M4)
Observer 2: Maintenance value, luminance with dry roadway [cd/m²] (Value grid)
m 0.550 1.650 2.750 3.850 4.950 6.050 7.150 8.250 9.350 10.450
4.500 8.55 8.50 8.36 8.27 8.30 8.32 8.31 8.37 8.48 8.57
3.900 8.71 8.60 8.36 8.29 8.29 8.27 8.32 8.35 8.52 8.66
3.300 8.64 8.50 8.27 8.19 8.16 8.09 8.16 8.20 8.32 8.54
2.700 8.66 8.48 8.25 8.20 8.15 8.08 8.17 8.22 8.35 8.58
2.100 8.54 8.46 8.23 8.17 8.19 8.18 8.24 8.25 8.40 8.54
1.500 8.17 8.15 8.02 7.93 7.95 7.95 7.94 8.00 8.13 8.23
Observer 2: Maintenance value, luminance with 8.30 cd/m² 7.93 cd/m² 8.71 cd/m² 0.95 0.91
dry roadway
1
lum
Street 1
Roadway 1 (M4)
1
lum
Street 1
Roadway 1 (M4)
m 0.550 1.650 2.750 3.850 4.950 6.050 7.150 8.250 9.350 10.450
4.500 12.77 12.69 12.47 12.34 12.39 12.41 12.40 12.49 12.66 12.80
3.900 13.00 12.84 12.48 12.38 12.37 12.34 12.41 12.46 12.71 12.92
3.300 12.90 12.68 12.35 12.23 12.17 12.08 12.18 12.24 12.41 12.74
2.700 12.92 12.66 12.32 12.23 12.16 12.07 12.19 12.27 12.46 12.80
2.100 12.75 12.62 12.28 12.19 12.22 12.21 12.29 12.31 12.54 12.74
1.500 12.20 12.17 11.98 11.83 11.86 11.86 11.85 11.94 12.14 12.28
Lav
Lmin Lmax g1 g2
Observer 2: Luminance with new 12.4 cd/m² 11.8 cd/m² 13.0 cd/m² 0.95 0.91
installation
1
lum
Glossary
Background area The background area borders the direct ambient area according to DIN EN 12464- 1
and reaches up to the borders of the room. In larger rooms, the background area is at
least 3 m wide. It is located horizontally at floor level.
Allocation of the light colours to the colour temperature ranges acc. to EN 12464-1:
Clearance height The designation for the distance between upper edge of the floor and bottom edge of
the ceiling (in the completely furnished status of room).
The general colour rendering index Ra (or CRI) is a dimensionless figure that describes
the quality of a white light source in regards to its similarity with the remission spectra of
defined 8 test colours (see DIN 6169 or CIE 1974) to a reference light source.
Daylight factor Ratio of the illuminance achieved solely by daylight incidence at a point in the inside
to the horizontal illuminance in the outer area under an unobstructed sky.
2
lum
Glossary
Daylight quotient effective area A calculation surface within which the daylight quotient is calculated.
Unit: %
Illuminance Describes the ratio of the luminous flux that strikes a certain surface to the size of this
surface (lm/m² = lx). The illuminance is not tied to an object surface. It can be
determined anywhere in space (inside or outside). The illuminance is not a product
feature because it is a recipient value. Luxometers are used for measuring.
Unit: Lux
Abbreviation: lx
Formula symbol: E
Illuminance, adaptive For the determining of the middle adaptive illuminance on a surface, this is rastered
"adaptively". In the area of large illuminance differences within the surface, the raster is
subdivided finer; within lesser differences, a rougher classification is made.
Illuminance, horizontal Illuminance that is calculated or measured on a horizontal (level) surface (this can be for
example a table top or the floor). The horizontal illuminance is usually identified by the
formula letter Eh.
Illuminance, perpendicular Illuminance that is calculated or measured plumb-vertical to a surface. This needs to be
taken into account for tilted surfaces. If the surface is horizontal or vertical, then there is
no difference between the perpendicular and the horizontal or vertical illuminance.
2
lum
Glossary
Illuminance, vertical Illuminance that is calculated or measured on a vertical surface (this can be for example
the front of some shelves). The vertical illuminance is usually identified by the formula
letter Ev.
Luminance Dimension for the "brightness impression" that the human eye has of a surface. The
surface itself can emit light thereby or light striking it can be reflected (emitter value). It
is the only photometric value that the human eye can perceive.
Luminous efficacy Ratio of the emitted luminous flux Φ [ lm] to the absorbed electrical power P [W]
Unit: lm/W.
This ratio can be formed for the lamp or LED module (lamp or module light output), the
lamp or module with control gear (system light output) and the complete luminaire
(luminaire light output).
2
lum
Glossary
Luminous flux Dimension for the total light output that is emitted from one light source in all directions.
It is thus an "emitter value" that specifies the entire emitting output. The luminous flux of
a light source can only be determined in a laboratory. A difference is made between the
lamp or LED module luminous flux and the luminaire luminous flux.
Unit: Lumen
Abbreviation: lm
Formula symbol: Φ
Luminous intensity Describes the intensity of the light in a certain direction (emitter value). The luminous
intensity is a matter of the luminous flux Φ that is emitted in a certain spherical angle Ω.
The radiation characteristics of a light source are presented graphically in a light
distribution curve (LDC). The luminous intensity is an SI base unit.
Unit: Candela
Abbreviation: cd
Formula symbol: I
P (Engl. power)
Electric power consumption
Unit: watt
Abbreviation: W
Reflection factor The reflection factor of a surface describes how much of the striking light is reflected
back. The reflection factor is defined by the colour of the surface.
2
lum
Glossary
Surrounding area The ambient area directly borders the area of the visual task and should be planned with
a width of at least 0.5 m according to DIN EN 12464-1. It is at the same height as the
area of the visual task.
UGR observer Calculation point in the room, for the DIALux the UGR value is determined. The
location and height of the calculation point should correspond to the typical observer
position (position and eye level of the user).
Visual task area The area that is needed for carrying out the visual task in accordance with DIN EN 12464
-1. The height corresponds with the height at which the visual task is executed.
Wall zone Circumferential area between working plane and walls which is not taken into
account for the calculation.
Working plane Virtual measuring or calculation surface at the height of the visual task that generally
follows the room geometry. The working plane may also feature a wall zone.