You are on page 1of 11

Received 6 June 2020; revised 9 July 2020; accepted 15 July 2020.

Date of publication 20 July 2020;


date of current version 4 August 2020. The review of this article was arranged by Associate Editor Lina He.
Digital Object Identifier 10.1109/OJPEL.2020.3010227

A Single Stage Common Ground Three-Level


PV Inverter With Integrated Power Decoupling
YINGLAI XIA 1 (Member, IEEE), JINIA ROY 2 (Member, IEEE),
AND RAJA AYYANAR 1 (Senior Member, IEEE)
1
Arizona State University, Tempe, AZ 85287 USA
2
National Renewable Energy Laboratory, Golden, CO 80401-3393 USA
CORRESPONDING AUTHOR: YINGLAI XIA (e-mail: yinglaixia@gmail.com)
This work was supported in part by the Office of Energy Efficiency and Renewable Energy and in part by the U.S. Department of Energy with North Carolina State
University, PowerAmerica Institute, under Award DE-EE0006521.

ABSTRACT In this paper, a T-type common ground transformer-less single phase inverter with dynamic
swing of the dc-link voltage is presented for photovoltaic (PV) application. The topology is a combination
of a bi-directional, partial-power-processing boost stage and an asymmetric half-bridge inverter stage along
with a T-branch. It takes advantage of the three-level switching states with reduced voltage stress on the
main switches to achieve lower switching loss and almost one-half the inductor current ripple w.r.t. two level
implementation. The double line frequency power decoupling is addressed by a dynamic dc-link approach,
which allows a large swing of the dc-link to reduce the decoupling capacitor requirement, enabling an all-film
capacitor implementation. This topology also significantly reduces the high-frequency capacitive coupled
ground current by directly connecting the PV negative terminal to the grid neutral. Moreover, an adaptive dc-
link voltage control scheme that optimally changes the average value of the dc-link voltage as the operating
conditions (load and power factor) vary, has been proposed and thoroughly investigated from the perspective
of better utilization of passive components and further reduction of switching losses. A SiC MOSFETs-
based 1 kVA laboratory prototype has been built to validate the converter’s operation at 200 V dc nominal
input and 120 V/60 Hz ac nominal output with a wide range of power factor and load operations. Extensive
experimental results validate the superior performance of the topology with the adaptive dc-link voltage
control implementation showing a peak efficiency of 98.22% and a CEC efficiency of 98.03% at 50 kHz
switching frequency.
INDEX TERMS DC-AC power converters, leakage currents, wide band gap semiconductors.

I. INTRODUCTION three-level inverters have also been considered in the low


Power electronic converters are the key components in a grid and medium voltage domain due to their improved harmonic
connected photovoltaic (PV) system for interfacing the solar and efficiency performances and reduced ac filter components
panels to the grid and extracting the maximum power from the compared to their two-level counterparts [2]. Among them
PV source. The single phase PV systems can be implemented the T-type topology stands out due to its advantages of lower
with or without galvanic isolation, with transformer-less in- conduction and switching loss and lower passive and active
verters gaining larger market share due to their advantages component count over the nuetral point clamped (NPC) ap-
in terms of reduced cost, higher efficiency, and higher power proach [3].
density. Recently T-type inverter has been studied for the grid-
State-of-the-art single phase inverters mostly use two-level tied application [4]. It has an additional bi-directional switch
topologies. However, multi-level converters offer better power connected between the neutral point and the switching pole.
density, higher efficiency, and improved harmonic perfor- Though the voltage rating of the main switches is not re-
mance which have already proven beneficial in high volt- duced, their commutating voltage is halved, thus decreas-
age and high power applications [1]. In recent years, the ing their switching loss. Also through improved modulation

This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see https://creativecommons.org/licenses/by/4.0/
VOLUME 1, 2020 227
XIA ET AL.: SINGLE STAGE COMMON GROUND THREE-LEVEL PV INVERTER WITH INTEGRATED POWER DECOUPLING

techniques, the effective switching frequency can be reduced bidirectional T-branch helps in significant reduction in the
while still maintaining the output harmonic performance same size of the filter inductor (or reduction in THD for similar
as the two-level implementation, thereby further lowering the inductors). This paper presents an in-depth analysis of the
switching loss. The commutation voltage and the voltage T-type common ground voltage swing inverter topology as
stress on the bi-directional T-branch switches are both half applicable to the single-phase PV inverters with significant
the dc-link so the associated losses with T-branch are not performance gains, analytical design complexity, and wider
significant. range of specifications, especially in terms of power factor
In the conventional T-type inverter, the grid neutral is con- (pf) operation in comparison to [19]. To satisfy the emerging
nected to the mid-point of the half-bridge (HB) capacitors. grid support features, the design of the optimal switching se-
It is an attractive feature for applications in transforme-less quences for the converter has also been explored considering
PV inverters. The HB derived structure ensures the mitigation a wide range of power factor (pf), with extensive modulation
of the capacitive coupled ground current through the stray scheme analysis for both unity pf and non-unity pf.
capacitance between the PV terminals and ground (and there- Additionally, an adaptive dc-link voltage control scheme
fore grid neutral) as a low-frequency (typically fundamental is studied from the perspective of the dynamic dc-link active
frequency) or constant potential of the PV negative terminal power decoupling and thus maximizing the utilization of the
relative to the grid neutral is maintained. However, T-type passive components (effectively designed for the worst case
inverter has voltage balancing challenge and one of the mod- operating condition) over the entire operating range to im-
ulation freedom of the inverter stage is lost as it is employed prove on the overall converter efficiency performance, which
for voltage balancing of HB capacitors. was not previously considered in [19]. This adaptive dc-link
The other challenge associated with single phase PV appli- scheme has similar concept to [20], [21], however, as they
cation (which is independent of whether a two-level or three- are implemented in ac-dc application these consider only the
level topology is used) is addressing the double line frequency variation in active power. The range of different operating
power ripple, which is a common issue for all the single phase conditions include the variation in the input voltage, varia-
inverters and rectifiers [5], [6]. Large electrolytic capacitors tion in output power, and 0.7 leading pf to 0.7 lagging pf
(e-caps) are predominantly used for decoupling purposes, but for the output power accounting for reactive power support.
they have known failure mechanisms that lead to reliability Further, [20], [21] consider a two-stage topology (an ac-dc
challenges to the PV inverter system. Alternatively, by de- stage followed by dc-dc stage) to implement the variable dc-
creasing the capacitance requirement through active power link and thus is straightforward to design the controller. Our
decoupling techniques, e-caps can be replaced with highly re- proposed converter is a single stage (a boost stage and a HB
liable film capacitors as has been reviewed in [7], [8]. This can inverter stage parallelly processing power for both the power
be achieved by either adding an auxiliary power decoupling decoupling and dc-ac conversion) and thus the implementa-
stage connected in series [9] or parallel [10] to the main in- tion of the adaptive dc-link controller is more complicated.
verter, or allowing higher ripple on the main dc-link [11], [12]. The rest of the paper is organized as follows. Section II
However, in the later case the control needs to be properly presents the basic converter topology, its operating princi-
designed such that the ripple on the dc-link does not impact ples, and T-type modulation strategy. The performance of the
the output grid current [13]. converter is compared with the state-of-the-art PV inverters
With the goal of achieving a simple, reliable, and effi- in the next Section III. A brief discussion on component
cient PV system, in this paper, a T-type common ground selection and the common mode analysis for this common
voltage swing inverter is presented for transformer-less PV ground T-type inverter is provided in Section IV. The follow-
inverter application. The ac neutral is directly connected to the ing Section V discusses the simulation results including the
PV negative terminal, thus completely eliminating the high- double line frequency power decoupling with the adaptive dc-
frequency capacitive coupled common-mode ground current. link voltage control requirement and implementation. A brief
This is commonly termed as the doubly grounded or common discussion on the controller design is given in Section VI.
ground structure as adopted in a few recent works both related Finally, the experimental results for the laboratory prototype
to string inverter [14]–[16] as well as microinverter [17], [18] of transformer-less string inverter with Silicon Carbide (SiC)
applications. The presented circuit is a topological enhance- devices are provided in Section VII.
ment to [13] leading to a significant improvement in the con-
verter efficiency. Unlike the conventional T-type converters, it II. CIRCUIT CONFIGURATION
does not pose any HB voltage balancing issue, as the voltage Fig. 1 shows the topology of the T-type common ground
is inherently balanced without losing any modulation freedom voltage swing inverter for transformer-less string inverter ap-
in the inverter stage. It integrates a bi-directional boost and plication. The converter has an input boost stage followed by
HB stages coupled with a T-branch. A large voltage swing an asymmetric HB inverter stage coupled with a bi-directional
of the dc-link capacitor address the power decoupling with T-branch. As opposed to the conventional boost converter
a reduced capacitor value of only 55 μF with peak voltage which shares a common negative, here the boost input and
of 500 V leading to a μF*kV/kW metric [13] of 27.5. The output shares a common positive terminal. The bi-directional
three-level waveform obtained by the implementation of the boost converter comprises of inductor Lb , dc-link capacitor

228 VOLUME 1, 2020


TABLE I Gate Signal & Operating States of Inverter Stage∗

*ON state of T-branch correspond to one of three switching patterns de-


pending on the current direction - both Q5 and Q6 ON, Q5 ON and Q6
OFF, or Q5 OFF and Q6 ON.

FIGURE 1. T-type common ground voltage swing inverter for


transformer-less PV application. CPV shown correspond to the parasitic
capacitances between the PV terminals and ground. both Q3 and Q4 being OFF and either or both of Q5 and Q6
being ON, depending on the voltage polarity. NEG state has
a pole voltage of vin − vlink with Q4 being ON and Q3 and
Clink , and switches Q1 and Q2 . The three-level T-type inverter T-branch being OFF.
stage is comprised of two main switches Q3 and Q4 , with an Different combinations of these three operating states gen-
additional bi-directional T-branch comprising of switches Q5 erate the output grid voltage at different operating pf. The
and Q6 which switches at line frequency for unity pf (UPF) corresponding modulation strategy is discussed in the next
operation, thus having limited contribution to the converter’s section. The operating states of the presented T-Type inverter
switching loss. stage is shown in Fig. 2 for UPF operation where the unhigh-
The grid neutral is connected directly to the PV nega- lighted part in gray color denotes the devices with OFF gate
tive terminal, commonly referred to as a doubly grounded signal. When switching, the switch voltage stress on Q3 and
or common ground structure, thus inherently eliminating the Q4 is around half of the dc-link (vin for Q3 and vlink − vin
common-mode, high-frequency ground currents through the for Q4 ). But when they are not switching, the voltage across
PV module capacitance, which is a common problem in most them changes between vlink and vin for Q3 and between vlink
of the transformer-less inverters. A dynamic dc-link approach and vlink − vin for Q4 . This is shown in Fig. 3 for both the
provides the 120 Hz power decoupling as discussed in a later switching transition between POS and ZERO states (Fig. 3(a)
section. For grid connected implementation LCL (Linv , Cg, Lg) and between NEG and ZERO states (Fig. 3(b).
filters are considered. In Fig. 1 iinv is the current through Linv , Thus though the commutation voltage and hence the
and ig is the current through Lg, which is also the grid current. switching loss are reduced for Q3 and Q4 , the absolute stress
on them is still the full dc-link voltage. On the other hand,
the commutation voltage and the absolute switch stress on
A. OPERATING PRINCIPLES
Q5 and Q6 are both half the dc-link voltage. However, the
The boost stage steps up the input PV voltage vin to a higher main disadvantage of T-type implementation with the conven-
nominal dc voltage vlink of around 400 V. It is particularly tional modulation scheme (i.e., the T-branch switching at line
designed to have a large 120 Hz swing of around 140 V peak- frequency) is the additional conduction loss in the T-branch
peak. The combination of higher nominal voltage of vlink and body diode, as any one of the two diodes of Q5 or Q6 always
a very large swing is used to address the power decoupling conducts.
with a greatly minimized dc-link capacitance.
The input voltage vin and the difference voltage vlink − vin
constitute two asymmetric voltage levels of the HB. db (gen- B. MODULATION SCHEME
erates gate signals for Q1 and Q2 ) and dinv (generates gate The modulation of the boost stage is straightforward with top
signals for the rest of the switches) are respectively the boost switch Q1 complementary to the bottom one Q2 irrespective
and inverter stage duty ratio. It is to be noted that being a HB of the operating pf. However, the scheme is complex for the
derived topology, compared to the traditional full bridge (FB) inverter stage. Table II gives the modulation strategy for the
inverter, all the switches Q1 , Q2 , Q3 , Q4 need to be rated at HB inverter stage with the T-branch for different pf opera-
higher voltage vlink . However, w.r.t. the conventional HB in- tions. Scheme I and II respectively correspond to the T-branch
verter the switch voltage rating of this topology is comparable. switching at line and carrier frequency.
In every grid cycle the T-type asymmetric HB inverter has For UPF operation, the modulation scheme is simple.
three operating states - POS, ZERO, and NEG as shown in The T-branch switches at line frequency, while the effective
Table I. The pole voltage VMN with respect to a neutral-point switching frequency of Q3 and Q4 is half of the carrier signal
voltage N can be one of vin , 0, or vin − vlink according to frequency as they are OFF for half the grid cycle as shown in
the operating state. The first operating state POS is generated Fig. 4(a). During the positive half cycle (dinv > 0), operating
with Q3 being ON and Q4 and T-branch being OFF with pole states POS and ZERO (Q4 and Q6 being always OFF, Q5 being
voltage being vin . The operating state ZERO corresponds to always ON, and only Q3 switching) are used to modulate the
both Q3 and Q4 being OFF and T-branch being ON with pole output (interval A in Fig. 4(a). And in the negative half cycle
voltage being 0. Essentially, ZERO state is generated with (dinv < 0), operating states NEG and ZERO (Q3 and Q5 being

VOLUME 1, 2020 229


XIA ET AL.: SINGLE STAGE COMMON GROUND THREE-LEVEL PV INVERTER WITH INTEGRATED POWER DECOUPLING

FIGURE 2. Operating states of the T-Type half-bridge inverter stage for the topology at UPF condition showing the current path while it switches between
(a) POS and (b) ZERO in positive half cycle and between (c) NEG and (d) ZERO in negative half cycle corresponding to modulation Scheme I.

TABLE II Modulation Scheme of the T-Type Inverter Stage for the Converter ∗

*The gate drives for Q1 and Q2 are similar to a standard boost converter regulating its average output voltage, and hence is not elaborated here. The gate drive is not synchronized
to that of the inverter stage and is independent.

to generate NEG or ZERO states (interval D in Fig. 4(b).


Here, the T-branch switches at the line frequency as shown in
Scheme I of Table II. The effective switching frequency of Q3
and Q4 is remains same as before. But this approach is very
sensitive to iinv detection, and if not properly implemented,
can lead to shoot-through of the HB inverter leg.
Further for non-UPF operation, this disadvantage can be
addressed by switching the T-branch throughout at the carrier
frequency as shown in scheme II of Table II with the T-branch
(Q5 and Q6 ) having the same gate signal. For dinv > 0, Q3
switches complementary to the T-branch, while for dinv < 0,
Q4 switches complementary to the T-branch as shown in
Fig. 4(c). This results in increased turn-on loss of only one
FIGURE 3. Switch voltage stress for all the switches in the inverter stage of the T-branch switches, since depending on the current di-
when switching between (a) POS and ZERO states, (b) NEG and ZERO rection either Q5 or Q6 will have soft turn-ON. Also in this
states.
scheme the conduction loss associated with the T-branch body
diode occurs only during dead-time transition, and thus car-
rier frequency switching of T-branch would not significantly
always OFF, Q6 being always ON, and only Q4 switching) are impact the overall converter efficiency. Table III compares
used to modulate the output waveform (interval C in Fig. 4(a). the converter’s performance in terms of the inductor current
On the contrary for non-UPF operation, the modulation is ripple, diode conduction, control complexity, and power loss
more involved as it is dependent on the switch pole current for both the switching schemes.
iinv direction [see Fig. 4(b)]. For iinv > 0, modulation scheme
is same as with p f = 1 in the positive half cycle (interval A
in Fig. 4(b), and for iinv < 0 modulation scheme is same as III. TOPOLOGY COMPARISON
with p f = 1 in the negative half cycle (interval C in Fig. 4(b). A. COMPARISON WITH CONVENTIONAL BOOST
But in the positive half cycle, for iinv < 0, Q4 and Q5 are OFF, CASCADED T-TYPE INVERTER
Q6 is ON, and Q3 switches to generate POS or ZERO states The presented topology is very different from the conventional
(interval B in Fig. 4(b). And in the negative half cycle, for boost cascaded T-type inverter topology shown in Fig. 5. In
iinv > 0, Q3 and Q6 are OFF, Q5 is ON, and Q4 switches this topology, the boost stage is an integral part of the power

230 VOLUME 1, 2020


FIGURE 4. Switching signals for the T-branch and the half-bridge inverter stage for (a) UPF operation, (b) non-UPF operation in scheme I, (c) non-UPF
operation in scheme II.

TABLE III Modulation Scheme Comparison TABLE IV Converter Specification

higher peak of Vlink requiring switching devices with


higher voltage rating, and voltage balancing between VC1
and VC2 will be more complex.
r In the topology of Fig. 5 the boost stage processes the
complete, rated power, whereas in this topology part
of the power flows directly from the PV panels to the
grid through the HB dc-ac stage, without having to go
through the boost stage.
r However, one advantage that the topology of Fig. 5 has
FIGURE 5. Conventional boost cascaded T-type inverter topology. over the T-type voltage swing inverter is wider range
allowable in the input voltage due to the front end boost
stage.
decoupling which operates in parallel to the HB inverter. The
basic differences between the presented and conventional in- B. PERFORMANCE COMPARATIVE SUMMARY
verter shown in Fig. 5 are: Table IV shows the specification of the converter. In Table V
r Topology in Fig. 5 is not common ground, M and N are this topology is compared with the state-of-the-art inverters
not connected. M is the negative terminal of the grid, implemented for PV application in terms of the number of
while N is the negative terminal of the PV panel. active components, power decoupling metric, output filter re-
r Topology in Fig. 5 needs additional two capacitors C1 quirement, peak efficiency, and common grounding capabil-
and C2 . It also has voltage balancing challenge and the ity. The average
 device voltage stress normalized by the input
one of the modulation freedom of the T-type stage is voltage [ ni=1 Vi /(nVin ), where Vi is the voltage stress of the
lost as it needs to be used to maintain voltage balancing ith device and n is the total number of devices in converter] is
between VC1 and VC2 . also compared.
r Topology in Fig. 5 conventionally has no dynamic power Similar to the conventional FB inverter and its derivatives
decoupling, Vlink is dc with very small ripple and Clink such as H5, H6 and HERIC, the presented topology with
is very large. However, Clink can be made smaller by the integrated power decoupling also has the constraint that
accommodating larger ripple on dc-link, but it entails the input voltage should be higher than the peak of the grid
additional considerations such as the minimum of the dc- voltage to avoid over-modulation. An additional boost stage,
link to be higher than the twice of the output ac voltage, or a partial power processing stage that adds a series voltage

VOLUME 1, 2020 231


XIA ET AL.: SINGLE STAGE COMMON GROUND THREE-LEVEL PV INVERTER WITH INTEGRATED POWER DECOUPLING

TABLE V Performance Comparisons With Various Other Topologies

NR∗ : not reported

to the input will be needed for applications where the above Finally the capacitance is optimized for the range of operating
constraint cannot be met. Moreover, unlike the conventional condition as given in Table IV with an objective of minimizing
topologies, the T-type voltage swing inverter has an upper the capacitance volume as outlined in [13].
limit on vin for a given vlink given by the instantaneous re- As the 120 Hz ripple is controlled to be present only in
quirement vlink − vin > |vg|, which can also be met by the use the dc-link capacitor, Cin is designed based on the maximum
of the boost or the partial power processing stage mentioned allowable high-frequency voltage ripple at the input. The
above. boost inductor (Lb ) is designed based on the allowed current
From Table V it can be further seen that the T-type voltage ripple of 20% the nominal value. Conventional LCL design
swing inverter offers a competitive efficiency and common approach [31] is used to design the values of inverter output
grounding capability while using decoupling capacitor of only filter (Linv , Cg, Lg).
55 μF with peak voltage of 500 V leading to a μF*kV/kW
metric [13] of 27.5. The number of active and passive compo-
B. COMMON MODE BEHAVIOR
nents is also comparable to the other topologies considered.
Fig. 6 shows the equivalent circuit of the T-type common
ground voltage swing inverter for analyzing common-mode
IV. DESIGN PRINCIPLE
voltage and leakage current. In this model the parasitic ca-
A. COMPONENT SELECTION
pacitance CPV is equally distributed at the positive and the
Clink is designed based on the requirement to support the
negative terminal of the PV module. It can be seen that at
120 Hz power pulsation under the worst case operating condi-
the negative terminal it is short-circuited by the common ac
tion at leading pf as given by (1). where, Vg and Ig are the grid
and dc ground leading to (2). This ideally eliminates the
voltage and current peak, Vavg is the dc-link average voltage,
common-mode current icm1 . Further, the positive terminal is
2Vr is the peak-peak dc-link ripple voltage varying at double
connected to the grid neutral through the parallel combination
line frequency, and Sg is the grid VA.
of the parasitic capacitance and the input capacitance Cin . The
VgIg Sg typical value of CPV is 60-110 nF/kW in standard PV modules
Clink = = (1)
4ωVavgVr 2ωVavgVr and 100-160 nF/kW in thin-film PV modules, which is much

232 VOLUME 1, 2020


for Vr from (1), (5) is obtained.
Sg sin(2ωt + θ )
Vavg + − vin > |Vg sin(ωt )| (5)
2ωVavgClink
Further, pf dependence can be analysed from the steady state
simulation results given in Fig. 7. It gives the dc-link voltage,
input voltage, the difference of dc-link and input voltages
along with grid current and grid voltage waveforms corre-
sponding to different operating pf - unity, 0.7 lagging, and 0.7
leading. Fig. 7(c) shows that the leading pf gives the worst
FIGURE 6. Equivalent circuit of the T-type common ground voltage swing voltage margin [13] and thus needs a higher dc-link mean,
inverter for analyzing common-mode voltage and leakage current.
whereas, lagging pf [see Fig. 7(b)] gives the best margin
requiring minimum dc-link mean. It has been accomplished
by the adaptive dc-link scheme with the voltage margin Vm
less than Cin . Thus icm2 is negligibly small as iripple is mostly always being barely around 20 V at the critical point (Fig. 7).
bypassed through Cin . In practice due to the non-idealities It can be further seen that the constraints given in (3) have
of the components, both icm1 and icm2 are non-zero but very been satisfied in all three cases.
small.
B. ADAPTIVE DC-LINK SCHEME
vcm1 = 0; vcm2 = vin (2)
With the dynamic dc-link approach, once the passive compo-
nents are designed for the worst operating condition (leading
V. ADAPTIVE DC-LINK VOLTAGE CONTROL pf at full rated VA), the dc-link average Vavg can be adjusted
The instantaneous values of each of the HB voltage levels (vin at other operating conditions instead of a fixed value. As over
and vlink − vin ) needs to satisfy the constraint in (3) at any a grid cycle, the semiconductor switching loss is dependent
operating pf, where vg = Vg sin(ωt ). These two constraints on Vavg, it is beneficial to operate the inverter at the minimum
place a limit on the minimum value of the PV voltage and the dc-link average (implying lower switch voltage stress), which
maximum voltage swing allowed at the dc-link. This ensures can be decided based on the constraint in (4). Also with lower
that the HB inverter stage does not operate at modulation Vavg, the inductor current ripple can be decreased accounting
index more than 1, which would otherwise distort the output for lower high frequency copper and core loss.
waveforms and impact the total harmonic distortion (THD). It can be seen that for different values of Sg, vin , and p f ,
 different minimum Vavg is required to satisfy (5). However,
vin > vg if vg ≥ 0
(3) deriving the analytical solutions of the optimal Vavg for differ-
vlink − vin > |vg| if vg < 0 ent Sg, vin , and p f values is a complex assignment. Therefore,
numerical method is used to find the minimum Vavg in MAT-
As vin has no double line frequency ripple, the constraint in (3)
LAB by sweeping the dc-link voltage average value over the
is instantaneously satisfied by ensuring the voltage margin, Vm
specified operating range. 3-D plots showing the dependence
[given in (4)] is greater than 0 only in the negative half of the
of minimum Vavg required are given in Fig. 8 for various
grid cycle.
combination of Sg (swept from 0 to 1000 VA), vin (swept
Vm = vlink − vin − |vg| > 0 (4) from 180 to 260 V), and p f angle (swept from −45◦ to 45◦
corresponding to 0.7 lagging and 0.7 leading pf respectively).
It is worth noting that to have an optimal dc-link capacitance Implementation of the adaptive dc-link scheme does not
value, it is enough to satisfy (4) instantaneously, rather than interfere with the basic inverter control design. Instead of
keeping the Vm always higher than 0 [13]. Again Vm is a providing a constant dc-link average as conventionally done,
function of the input voltage, operating pf, and VA of the the Vavg is decided based on the converter’s operating point
inverter, which leaves room for improving converter efficiency and provided as an input to the dc-link controller. To save the
by the adaptive dc-link voltage control, as discussed shortly. computational time and resource, for different combinations
of Sg, vin , and p f , Vavg is computed off-line apriori, and is
A. DEPENDENCE OF THE VOLTAGE MARGIN ON saved in an LUT for controller implementation.
OPERATING PARAMETERS
The dependence of Vm on the operating kVA is clear from VI. CONTROLLER IMPLEMENTATION
(1) and (4), where with a fixed dc-link capacitance Clink , Vavg For the PV inverter operation in grid connected mode, the
and Vr , and thus Vm are dependent on Sg. Also its dependence objective of the controller is to control the input voltage ac-
on vin is obvious from its definition in (4). Finally, the de- cording to the MPPT voltage reference which fixes the input
pendence of Vm on operating pf can be studied from (5). As power, control the grid current depending on the input power
discussed already, with ideally no ripple on vin , (3) can be (with the fixed grid voltage), and control the average of the
modified for only the negative grid cycle, and by substituting dc-link voltage. Without the input PV panel, the input of the

VOLUME 1, 2020 233


XIA ET AL.: SINGLE STAGE COMMON GROUND THREE-LEVEL PV INVERTER WITH INTEGRATED POWER DECOUPLING

FIGURE 7. Steady state waveforms at 1 kVA showing dc-link voltage, input voltage, grid voltage, grid current, and the difference of the dc-link voltage and
input voltage at (a) unity pf, (b) 0.7 lagging pf, (c) 0.7 leading pf operations highlighting the voltage margin of 20 V fixed for each operating point by
implementation of adaptive dc-link voltage control scheme.

FIGURE 8. Relationship between the minimum Vavg required to satisfy (5) for various combinations of Sg , vin , and pf (a) for different Sg and pf at
vin = 190 V, (b) for different vin and Sg at pf angle = 0◦ (UPF), (c) for different vin and pf at Sg = 1000 VA.

FIGURE 9. Controller block diagram of T-type common ground voltage


swing inverter.

FIGURE 10. 1 kVA experimental prototype of T-type common ground


voltage swing inverter for transformer-less PV application.
converter comes from a dc source in series with a resistor
to closely mimic the PV characteristic, and the input voltage
reference is manually provided.
Fig. 9 shows the overall controller block diagram with the Both dc-link and inverter control loops in the dc-ac stage
MPPT control block. The objective of the dc-dc stage con- employ simple PI controllers with appropriate feed forward
troller is to regulate the input voltage such that vin is free terms added as shown. The dc-link control loop regulates the
of any double line frequency ripple, which would otherwise average of the dc-link voltage to a reference value generated
disrupt the MPPT efficiency when connected across the PV by the adaptive dc-link control scheme. A first-order low-
source. To ensure this, input voltage controller has a high pass-filter (LPF) with cutoff frequency of 10 Hz is used to
bandwidth to generate the boost stage duty db as shown. filter out the 120 Hz component in the dc-link voltage before

234 VOLUME 1, 2020


FIGURE 11. Steady state waveforms at 1 kVA, UPF operation with 180 V input, 410 V DC-link average, and 120 V/60 Hz output (time : 5 ms/div). (a) Input
and output voltage and current (voltage: 100 V/div, ig : 20 A/div), (b) Magnified input voltage and converter currents (vin : 10 V/div, iin : 2 A/div, ib , iinv :
20 A/div), (c) Cycle-by-cycle averaged duty ratios of the boost and inverter stages (ig : 10 A/div).

TABLE VI Component Details

comparing it with the reference. It is to be noted that due to a


lower bandwidth of the dc-link controller, the response of the FIGURE 12. Steady state device drain-to-source voltage for T-type HB
inverter stage at 1 kVA, UPF operation (voltage: 200 V/div, time : 5 ms/div).
dc-link to the transients is slower.
The output current controller is designed to control the
grid current with the current peak reference derived from the
dc-link voltage control loop and the phase and frequency of
Table IV. Fig. 11(a) shows the experimental results of input
the sinusoidal waveform determined by a phase-locked loop
voltage vin , grid voltage vg, output current ig, dc-link voltage
(PLL) and an external p f command. The output of the con-
vlink , and the difference voltage vlink − vin . The grid current
troller decides the inverter stage duty dinv , which further gen-
has a THD of 2.3% calculated by using fast Fourier transform
erates the gate signals for Q3 to Q6 with appropriate dead-time
(FFT) in MATLAB on the measured ig data. Fig. 11(b) shows
based on the algorithm discussed in Section II.
the magnified input voltage and different converter currents -
input, boost stage inductor, and inverter stage inductor (iin , ib ,
VII. HARDWARE PROTOTYPE AND EXPERIMENTAL and iinv respectively).
RESULTS Fig. 11(c) shows the duty ratios of the boost stage and
A hardware prototype rated at 1 kVA has been built to vali- the HB inverter stage. The T-branch stage switches at line
date the performance features of the T-type common ground frequency, and hence, is not shown here. The duty ratio is ob-
voltage swing inverter for transformer-less PV application as tained by cycle-by-cycle averaging of measured gate voltage
shown in Fig. 10 (the overall converter size is 10.93 inch x Vgs of the two stages. As Vgs is 20 V when turned ON and
5.52 inch x 1.38 inch including the heat-sink). The input is -6 V when turned OFF, the 0 and 1 of the duty ratio can be
derived from a dc source of 210 V in series with a 6.5  established from Fig. 11(c) accordingly. It is to be noted that,
resistor to mimic a PV panel input. LeCroy 6200 A oscillo- dQ3 is purely sinusoidal as it modulates the input voltage vin
scope is used to capture the relevant waveforms and power with no ripple component to generate positive half of vg. On
analyzer YOKOGAWA WT3000 is used to measure the effi- the contrary, dQ4 which modulates vlink − vin , has double line
ciency. Table VI gives the detail of all the active and passive frequency component to mitigate the influence of large 120 Hz
components. CREE C2M0040120D wide bandgap SiC MOS- dc-link ripple on the grid output. Also in order to regulate the
FETs are used for all the switches including the T-branch. The input voltage to be a pure dc, the boost duty ratio (dQ1 = db )
controller is implemented in a customized DSP board built should contain 120 Hz component as shown.
with TMS320F28335. Fig. 12 shows the drain-to-source voltage of the MOSFETs
in the HB inverter stage with the T-branch (Vds_Q3 , Vds_Q4 ,
A. STEADY STATE EXPERIMENTAL RESULTS Vds_Q5 , and Vds_Q6 ). As Q3 modulates the input voltage vin
The results represented in this section correspond to 1 kVA, (which has negligibly small ripple component) to generate
UPF operation at steady state with specifications given in positive half of vg, Vds_Q3 profile is a constant while it is

VOLUME 1, 2020 235


XIA ET AL.: SINGLE STAGE COMMON GROUND THREE-LEVEL PV INVERTER WITH INTEGRATED POWER DECOUPLING

FIGURE 13. Dynamic response of the converter with the adaptive dc-link control implementation, (a) 500 W to 1 kW step-up load, (b) step change from
0.7 pf leading to 0.7 pf lagging at 1 kVA, (c) ramp change of input voltage from 205 V to 190 V (voltage: 100 V/div, current: 20 A/div, time : 20 ms/div).

switching (interval A). On the contrary, as Q4 modulates


vlink − vin which has double line frequency component to
mitigate the influence of dc-link ripple on the grid output,
Vds_Q3 profile also contains 120 Hz ripple while it is switching
(interval B). Profiles of Vds_Q5 and Vds_Q6 can be similarly
explained.

B. ADAPTIVE DC-LINK WAVEFORMS


Fig. 13(a) shows the transient waveforms of the inverter in
the grid-connected configuration when the active-power com-
FIGURE 14. Efficiency of T-type common ground voltage swing inverter
mand is given a step change from 500 W to 1 kW with with adaptive dc-link implemented.
vin = 190 V, at UPF operation, i.e., p f = 0◦ . As can be
seen, average value of vlink changes from 389 V to 409 V
dynamically, as calculated from the adaptive dc-link control
block. Fig. 13(b) shows the transient waveforms of the inverter switching specifically, the converter was operated with Q5
when the pf command has a step change from 0.7 leading to and Q6 operating at switching frequency at UPF and the peak
0.7 lagging, i.e., p f angle changing from 45◦ to −45◦ with efficiency obtained under this scenario was 97.83% at 50 kHz
vin = 190 V at 1 kVA. With the implementation of the adap- switching frequency. The converter efficiency for 0.7 lagging
tive dc-link scheme, Vavg is noticed to change from 431 V to pf at 1 kVA is 96.82%, while that for 0.7 leading pf at 1 kVA
377 V dynamically. It is also seen that vlink − vin waveform is is 96.35%.
just above the instantaneous vg at the critical point as expected
with adaptive dc-link implementation. VIII. CONCLUSION
Finally, Fig. 13(c) gives the transient waveforms of the This paper proposes a high-efficiency novel T-type common
inverter when the input voltage has a ramp change from 205 V ground transformer-less single phase inverter with dynamic
to 190 V at 1 kVA UPF operation. With the the adaptive swing of the dc-link voltage which addresses the main chal-
dc-link scheme, Vavg is noticed to change from 435 V to 420 V lenges of transformer-less inverters. The presented converter
dynamically. Further, no change in the grid current waveforms topology is a combination of a bi-directional boost and an
is noticed proving good performance of the controller. asymmetric HB stage coupled with a bi-directional T-branch
to reduce the switching loss and minimize the inductor current
C. EFFICIENCY ripple of the HB inverter stage. The capacitance required for
Fig. 14 shows the efficiency measured at UPF for different power decoupling is significantly reduced to 55 μF/kW at a
power levels based on California Energy Commission (CEC) peak of 500 V dc-link through an active power decoupling
requirement for PV inverters. The weighted CEC efficiency scheme with a large swing of the dc-link voltage. Extensive
at switching frequency of 50 kHz is obtained to be 98.03% experimental results from the 1 kVA SiC MOSFETs-based
and a peak of 98.22%, without considering the controller and laboratory prototype are presented to validate the concept,
auxiliary power consumption including the power for gate design, and superior performance of the topology. Moreover,
drivers, DSP controller, and other ICs which is around 2.7 W. the adaptive dc-link voltage control is implemented leading to
It is to be noted that for UPF operation the efficiency is a better utilization of the passive components and switching
measured while switching the T-branch (Q5 and Q6 ) at line scheme under different operating (load and pf) conditions
frequency as suggested in Table II. However, for non-UPF which finally results in a peak efficiency of 98.22% and a
operations, Q5 and Q6 will switch at carrier frequency as given CEC efficiency of 98.03% at 50 kHz switching frequency in
in Table II. In order to study the impact of this additional the experimental prototype.

236 VOLUME 1, 2020


REFERENCES [17] J. Roy, Y. Xia, and R. Ayyanar, “High step-up transformerless inverter
[1] E. Samadaei, A. Sheikholeslami, S. A. Gholamian, and J. Adabi, “A for AC module applications with active power decoupling,” IEEE Trans.
square T-type (ST-type) module for asymmetrical multilevel inverters,” Ind. Electron., vol. 66, no. 5, pp. 3891–3901, May 2019.
IEEE Trans. Power Electron., vol. 33, no. 2, pp. 987–996, Feb. 2018. [18] V. Gautam and P. Sensarma, “Design of CUK-derived transformerless
[2] T. B. Soeiro and J. W. Kolar, “The new high-efficiency hybrid neutral- common-grounded PV microinverter in CCM,” IEEE Trans. Ind. Elec-
point-clamped converter,” IEEE Trans. Ind. Electron., vol. 60, no. 5, tron., vol. 64, no. 8, pp. 6245–6254, Aug. 2017.
pp. 1919–1935, May 2013. [19] Y. Xia, J. Roy, and R. Ayyanar, “A high performance T-
[3] Y. Shi, L. Wang, R. Xie, Y. Shi, and H. Li, “A 60-kW 3-kW/kg five-level type single-phase doubly grounded transformer-less photovoltaic in-
T-type SiC PV inverter with 99.2 peak efficiency,” IEEE Trans. Ind. verter with active power decoupling,” in Proc. IEEE Energy Con-
Electron., vol. 64, no. 11, pp. 9144–9154, Nov. 2017. vers. Congr. Expo., Milwaukee, WI, USA, 2016, pp. 1–7, doi:
[4] A. Anthon, Z. Zhang, M. A. E. Andersen, D. G. Holmes, B. McGrath, 10.1109/ECCE.2016.7854693.
and C. A. Teixeira, “The benefits of SiC mosfets in a T-type inverter [20] J. Lu, A. Mallik, S. Zou, and A. Khaligh, “Variable DC-link control
for grid-tie applications,” IEEE Trans. Power Electron., vol. 32, no. 4, loop design for an integrated two-stage AC/DC converter,” IEEE Trans.
pp. 2808–2821, Apr. 2017. Transp. Electrific., vol. 4, no. 1, pp. 99–107, Mar. 2018.
[5] S. Pervaiz, A. Kumar, and K. K. Afridi, “GAN-based high-power- [21] S. Bolte, A. Speerschneider, N. Fröhleke, and J. Böcker, “A comparison
density electrolytic-free universal input led driver,” IEEE Trans. Indus- of on-board chargers for electric vehicles with variable dc-link volt-
try Appl., vol. 54, no. 4, pp. 3890–3901, Jul. 2018. age,” in Proc. IEEE Int. Conf. Smart Energy Grid Eng., Aug. 2015,
[6] S. Qin, Y. Lei, C. Barth, W. Liu, and R. C. N. Pilawa-Podgurski, “A pp. 1–5.
high power density series-stacked energy buffer for power pulsation [22] A. K. Gupta, M. S. Joshi, and V. Agarwal, “Improved transformer-
decoupling in single-phase converters,” IEEE Trans. Power Electron., less grid-tied PV inverter effectively operating at twice the switch-
vol. 32, no. 6, pp. 4905–4924, Jun. 2017. ing frequency with constant CMV and reactive power capability,”
[7] Y. Sun, Y. Liu, M. Su, W. Xiong, and J. Yang, “Review of active power IEEE J. Emerg. Sel. Topics Power Electron., to be published, doi:
decoupling topologies in single-phase systems,” IEEE Trans. Power 10.1109/JESTPE.2019.2943773.
Electron., vol. 31, no. 7, pp. 4778–4794, Jul. 2016. [23] G. V. Bharath, A. Hota, and V. Agarwal, “A new family of 1-phase five-
[8] H. Zhang, X. Li, B. Ge, and R. S. Balog, “Capacitance, dc voltage uti- level transformerless inverters for solar PV applications,” IEEE Trans.
lizaton, and current stress: Comparison of double-line frequency ripple Industry Appl., vol. 56, no. 1, pp. 561–569, Jan./Feb. 2020.
power decoupling for single-phase systems,” IEEE Ind. Electron. Mag., [24] H. Li, Y. Zeng, B. Zhang, T. Q. Zheng, R. Hao, and Z. Yang, “An
vol. 11, no. 3, pp. 37–49, Sep. 2017. improved H5 topology with low common-mode current for transformer-
[9] W. Liu, K. Wang, H. S. H. Chung, and S. T. h. Chuang, “Modeling less PV grid-connected inverter,” IEEE Trans. Power Electron., vol. 34,
and design of series voltage compensator for reduction of DC-link no. 2, pp. 1254–1265, Feb. 2019.
capacitance in grid-tie solar inverter,” IEEE Trans. Power Electron., vol. [25] M. Meraj, S. Rahman, A. Iqbal, and L. Ben-Brahim, “Common
30, no. 5, pp. 2534–2548, May 2015. mode voltage reduction in a single-phase quasi Z-source inverter
[10] P. T. Krein, R. S. Balog, and M. Mirjafari, “Minimum energy and for transformerless grid-connected solar PV applications,” IEEE J.
capacitance requirements for single-phase inverters and rectifiers using Emerg. Sel. Topics Power Electron., vol. 7, no. 2, pp. 1352–1363,
a ripple port,” IEEE Trans. Power Electron., vol. 27, no. 11, pp. 4690– Jun. 2019.
4698, Nov. 2012. [26] H. Watanabe, T. Sakuraba, K. Furukawa, K. Kusaka, and J. Itoh, “De-
[11] D. G. Lamar, J. Sebastian, M. Arias, and A. Fernandez, “On the limit of velopment of DC to single-phase AC voltage source inverter with active
the output capacitor reduction in power-factor correctors by distorting power decoupling based on flying capacitor DC/DC converter,” IEEE
the line input current,” IEEE Trans. Power Electron., vol. 27, no. 3, Trans. Power Electron., vol. 33, no. 6, pp. 4992–5004, Jun. 2018.
pp. 1168–1176, Mar. 2012. [27] M. Hadi Zare, M. Mohamadian, and R. Beiranvand, “A single-phase
[12] J. Roy, Y. Xia, and R. Ayyanar, “Performance evaluation of single-phase grid-connected photovoltaic inverter based on a three-switch three-port
transfomer-less PV inverter topologies,” in Proc. IEEE Appl. Power flyback with series power decoupling circuit,” IEEE Trans. Ind. Elec-
Electron. Conf. Expo., Mar. 2018, pp. 3250–3255. tron., vol. 64, no. 3, pp. 2062–2071, Mar. 2017.
[13] Y. Xia, J. Roy, and R. Ayyanar, “A capacitance-minimized, doubly [28] J. F. Ardashir, M. Sabahi, S. H. Hosseini, F. Blaabjerg, E. Babaei, and G.
grounded transformer less photovoltaic inverter with inherent active- B. Gharehpetian, “A single-phase transformerless inverter with charge
power decoupling,” IEEE Trans. Power Electron., vol. 32, no. 7, pump circuit concept for grid-tied PV applications,” IEEE Trans. Ind.
pp. 5188–5201, Jul. 2017. Electron., vol. 64, no. 7, pp. 5403–5415, Jul. 2017.
[14] A. Kadam and A. Shukla, “A multilevel transformerless inverter em- [29] H. Vahedi, P. Labbé, and K. Al-Haddad, “Sensor-less five-level packed
ploying ground connection between PV negative terminal and grid neu- U-cell (PUC5) inverter operating in stand-alone and grid-connected
tral point,” IEEE Trans. Ind. Electron., vol. 64, no. 11, pp. 8897–8907, modes,” IEEE Trans. Ind. Informat., vol. 12, no. 1, pp. 361–370,
Nov. 2017. Feb. 2016.
[15] Y. P. Siwakoti and F. Blaabjerg, “Common-ground-type transformerless [30] X. Lyu, N. Ren, Y. Li, and D. Cao, “A SiC-based high power density
inverters for single-phase solar photovoltaic systems,” IEEE Trans. Ind. single-phase inverter with in-series and in-parallel power decoupling
Electron., vol. 65, no. 3, pp. 2100–2111, Mar. 2018. method,” IEEE J. Emerg. Sel. Topics Power Electron., vol. 4, no. 3,
[16] N. Vazquez, J. Vazquez, J. Vaquero, C. Hernandez, E. Vazquez, and pp. 893–901, Sep. 2016.
R. Osorio, “Integrating two stages as a common-mode transformerless [31] M. Liserre, F. Blaabjerg, and S. Hansen, “Design and control of an LCL-
photovoltaic converter,” IEEE Trans. Ind. Electron., vol. 64, no. 9, filter-based three-phase active rectifier,” IEEE Trans. Industry Appl.,
pp. 7498–7507, Sep. 2017. vol. 41, no. 5, pp. 1281–1291, Sep. 2005.

VOLUME 1, 2020 237

You might also like