NOTES :

1. ALL THE DIMENSIONS ARE IN MILLIMETRES.


2. ALL DETAILS OF BOUNDARY WALL PRECAST WORK ARE
INDICATIVE ONLY.
3. ALL THE PRECAST ELEMENTS IN CONTACT WITH SOIL AND
GRAVEL SHALL RECEIVE BITUMINIOUS PROTECTION OF 1mm
MINIMUM THICKNESS. THE PLY WOOD PROTECTION BOARD
TO THE BITUMINOUS COATING NEED NOT BE PROVIDED
FOR THIS PRECAST WORK IN BOUNDARY WALL.
MAX. 4000mm
4. THE DIMENSIONS OF FOOTINGS, COLUMNS, WALL PANELS
(MAX. 4000mm FOR ECCENTRIC FOOTINGS)
ETC. SHOWN ON THIS DRAWING ARE MINIMUM AND MAY
X (DEFERENCE IN LEVELS WITH HAVE TO BE INCREASED TO MEET THE DESIGN REQUIREMENTS.
ADJACENT COLUMN FOOTING TOP) 10x10 CHAMFER (TYP.) FOOTING DIMENSIONS AS SHOWN ARE TENTATIVE
CONTRACTOR MAKE SURE THE BEARING CAPACITY OF SOIL
SHOULD NOT EXCEED 100kPa.
GROUTING

105
EXPOSED AGGREGATE

115
5. FOOTINGS TO BE VERIFIED AS PER THE CONFIRMED
2150 ON PIGMENTED CEMENT
(STD EWA DESIGN) SAFE BEARING CAPACITY OF SOIL AT SITE.

300
6. THE BASIC WIND SPEED FOR THE DESIGN OF THE BOUNDARY

10

160
400
150

150
300 T10-200
(VERTICAL)
WALL ELEMENTS SHALL BE 50m/s AND TO DESIGN IN
ACCORDANCE WITH BS 6399: PART-2: 1997

3800

150
15 7. THE CORNER/END COLUMNS ARE TO SUITABLY DESIGNED

700

125
IN SHAPE AND STRENGTH TO MATCH ALSO WITH SITE
4500

T12-200 REQUIREMENTS.
50 300 50 8T20,T8-175 (HORIZONTAL)
(MINIMUM SHOWN 8. LOCATION AND ARRANGEMENT OF BARBED WIRE TO BE
400

100
TO BE DESIGNED BY P.C DISCUSSED WITH S.O AND EWA(PROJECT)
CONCRETE SUPPLIER) WALL PANEL REINF'T DETAIL
100mm WIDE, 10mm DEEP
SCALE :- 1:20 9. CONTRACTOR SHOULD PROVIDE DESIGN CALCULATIONS
GROOVE SMOOTH FINISH SCALE 1:10 FOR PRECAST BOUNDARY WALL ALONG WITH SHOP DRAWINGS
FOR CONSULTANT REVIEW AND APPROVALS.

700
250
X

400
400X250mm CONCRETE PAD
OF THICKNESS 'X'
GROUTING
900
WELL COMPACTED GROUND

LBBT DOUBLE COIL CONCERTINA RAZOR

PROPERTY LINE
TYPE-S.S. 304 +
DIA. 600 AND 750mm
(ALL AROUND BOUNDARY WALL+
SECURITY KIOSK AS SHOWN ON DWG.)

900

100
PROPERTY LINE

1500 1500

900
1800

500
2500

2500

ECCENTRIC FOOTING ECCENTRIC FOOTING


CORNER ECCENTRIC
1800

FOOTING

400 400 BRACKET MADE OF 50X50X6mm GALVANISED ANGLE


FIXED TO BOUNDARY WALL AT
COLUMN & WALL 2.5m C/C MAX.
400

400
150

PROPERTY LINE
4000 (MAXIMUM) 4000 (MAXIMUM)

4000 (OUT SIDE)


400

WALL PANEL (PRECAST)


150mm THICK

GROOVED COLUMN (PRECAST)

0 26.07.2021 ISSUED FOR CONSTRUCTION HM


1000

+0.150 GRAVEL SURFACING INSIDE KINGDOM OF BAHRAIN


SUBSTATION COMPOUND
ELECTRICITY AND WATER AUTHORITY
PLANNING & STUDIES
30°

-0.350

500
ECCENTRIC FOOTING

EXISTING G.L.
TWO COATS OF BTU PAINT
THE CONNECTION DETAILS SHOWN THIS DRAWING &1000GUAGE POLYTHENE
INTERNATIONAL

400
SHEET (TYP.)
ARE TENTATIVE , THE PRECAST SUPPLIER SHOULD PROPOSE
Consulting Engineers to the Energy Sector
BETTER ALTERNATIVE PRECAST SUPPLIER TO
PROVIDE CONNECTION
P.O. Box 5922, Manama, Kingdom of Bahrain
DETAIL OF PRECAST Tel: (+973) 1770 8118 Fax: (+973) 1770 0115
COLUMN TO FOOTING
APRROVED BY THE
CONSULTANT 2500
1000GUAGE POLYTHENE SHEET
ISMAIL KHONJI ASSOCIATES
2 COATS OF BITU PAINT TYP.
50mm BLINDING
WELL COMPACTED TYPE-B FILL 300THK.

220/66 KV TRANSMISSION DEVELOPMENT

SUBSTATION CIVIL WORK

66 kV CITY TYPE SUBSTATION


AT NEW EAST RIFA'A
BOUNDARY WALL DETAILS

HM IYP MAY'21 AS SHOWN

Rev
HM TMS 1154 ST-NERF-29
c