You are on page 1of 2

1 2 3 4 5 6 7 8 9 10 11 12

NOTES:
1. FOR GENERAL NOTES REFER DRAWING NO.1JNG10374D0X782
A 2. FOR TYPICAL R.C.DETAIL REFER DRAWING NO. 1JNG10374D0X783 A
3. THE FOUNDATION HAS BEEN DESIGNED FOR 100KPA BEARING
CAPACITY .

5906 8272 8672

MANHOLE
(FOR DETAILS REFER TO DRG. RETAINING WALL
No. 1JNG10374D2X759(1 to 4)
A

300

NORTH
50

TRUE
300
127.2

NORTH
PLANT
KEYPLAN

N
SC1 SC1 SC1 SC1
B HERE B
GB1

GB1
GB1
H1 H1 H1 H1
GB1 GB1

TS

TS

CONTROLLER
JOCKEY - 2
BFV

50mm

50mm
TS
T0 FACP

JP-2

JP-1
CONTROLLER
JOCKEY - 1
+0.110
DN

TS

TS
DN

CONTROLLER
DIESEL PUMP
+0.110
STAND BY PUMP MAIN PUMP
SILENCER
ELECTRIC
MOTOR

ELECTRIC PUMP
MONO RAIL

CONTROLLER

TS
UP
TS TS

MINIMAX CABINET
FOR INTERFACING
MODULES
+0.110 (TOC) (TOC)
FOAM TANK- 3

UP UP UP
FOAM TANK- 2 FOAM TANK- 1

+0.110 +0.11

+16.358 LVL =+0.00 LVL


900
+0.110 +0.110 +0.110

ROAD LEVEL
(TOC) H3 (TOC)
(TOC) (TOC) (TOC) (TOC)
F1 FFL
+0.050

F5 H2 H2 H2 H2 WALK WAY

5400

3100

5950
6550

+0.110 220V BATTERY BANK 2

+0.110 (TOC)
220V BATTERY BANK 1

F2 +0.110 +0.110 +0.110 (TOC) +0.110 UPS BATTERY BANK

F1 (TOC) F2 (TOC) (TOC)


UPS BATTERY BANK

(TOC)

900
H3
a cb
yn

F5
FFL
A B C
+0.01

F3 F3 F3 F3 F4 F4 F4 F4
C GB1 GB1 C
+0.110
(TOC)
H3

1226
H3
GB1 GB1
F6 LEVEL +0.000 = +16.358
SC1 SC1 SC1 SC1
300

500

1000 576 1200 1515 1200 1300 1200 1555 1200 1300 1200 1300 1200 1650 1200 1515 1200 576 1000
A 265 85 179 179 74
181

D
THE BASE PLATE DETAILS FOR
STRUCTURAL GENERAL ARRANGEMENT PLAN AT GROUND LEVEL D

COOLER STRUCTURE SHOULD


REFER TO VENDOR DRAWINGS

E E

3 EQUALS = 5906 8272 8672

REVISIONS
EQ. EQ. EQ. 2068 2068 2068 2068 2168 2168 2168 2168

A
A 03.01.2023 ISSUED FOR APPROVAL Shams HM TMS
B1 B1 B1
REV DATE DESCRIPTION PREP. CHECK. APPR.
CLIENT:

F BAHRAIN ELECTRICITY & WATER AUTHORITY F


(EWA) KINGDOM OF BAHRAIN

ENGINEER:
GCCIA
Kingdom of Saudi Arabia,
P.O. Box 3894, Dammam 31481
5950

B1 UB-406x140x39

SUB-CONSULTANT:
Consulting Engineers,
P.O. Box 5922,
B1

B1

B1

B1

B1

B1

B1

B1

B1

B1

B1
Manama, Kingdom of Bahrain

CONTRACTOR: Hitachi Energy Technologies W.L.L


12 Floor, Gulf Executive Offices
G Office 1023, Entrance 15 G
Road # 3801, Al-Qudaybiyah 338
2 1 2 1 2 Post Box : 2774, Manama, Kingdom of Bahrain.
Tel : +97317810666, Fax : +97317725332
B1 CR NO : 166001
CIVIL DESIGNER:
B1 B1 B1
A 2 1 2 1 LOVERS FRAME AS PER VENDOR DESIGN
2
(SHOP DRAWINGS & DESIGN SHOULD BE
SUBMITTED FOR ENGINEER'S REVIEW)
PROJECT TITLE:
STRUCTURAL GENERAL ARRANGEMENT PLAN AT EL. +6.010 LEVEL DYNAMIC REACTIVE POWER COMPENSATION PROJECT

NAME DATE DOCUMENT TITLE:


H 03-01-2023 COOLER FOUNDATION AND ROOF SHED H
PREPARED Shams
STRUCTURAL GENERAL ARRANGEMENT
CHECKED MA 03-01-2023
PLANS AT FOUNDATION & ROOF LEVELS
APPROVED HM 03-01-2023 AT RIFFA STATCOM
STANDARD: A1 SCALE:
DRG. NO: REV. SHEET
1JNG10374D2X755 A 1 OF 2
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

NOTES:
1. FOR GENERAL NOTES REFER DRAWING NO.1JNG10374D0X782
A ALUMINIUM A
EL. +6.010 2. FOR TYPICAL R.C.DETAIL REFER DRAWING NO. 1JNG10374D0X783
(TOS)
3. THE FOUNDATION HAS BEEN DESIGNED FOR 100KPA BEARING
CAPACITY .
SCHEDULE OF ROOF STEEL MEMBER

12 THK. STIFF. PLATE @ 2.0m c/c MARK TYPE REMARKS STEEL GRADE
B1 B1 BOTH SIDES FOR B1
SC1 UC 203x203x46 STEEL COLUMN S275

B1 UB 406x140x39 STEEL BEAM S275

NORTH
TRUE
SC1

NORTH
PLANT
KEYPLAN

N
(MINIMUM)
HERE

5500
B B
SCHEDULE OF FOOTING

TOP BOTTOM
FOOTING SIZE
(L x W x D) SIDE FACE REMARKS
SHORT SPAN LONG SPAN SHORT SPAN LONG SPAN

TS

TS

CONTROLLER
JOCKEY - 2
BFV

50mm

50mm
TS
T0 FACP

JP-2

JP-1
CONTROLLER
JOCKEY - 1
300
DN

TS

TS
DN

CONTROLLER
DIESEL PUMP
STAND BY PUMP MAIN PUMP
SILENCER
ELECTRIC
MOTOR

ELECTRIC PUMP
MONO RAIL

CONTROLLER

TS
UP
TS TS

MINIMAX CABINET
FOR INTERFACING
MODULES
FOAM TANK- 3 FOAM TANK- 2 FOAM TANK- 1

UP UP UP

50MIN F1 6550x1000x600 T16-200 T16-150 T16-200 T16-200 2T16 UBARS

+16.358 LVL =+0.00 LVL


RETAINING WALL

ROAD LEVEL
25 THK. GROUT VARYING (+16.600 TOC)
300 SC1 F2 6550x1300x600 T16-200 T16-150 T16-200 T16-200 2T16 UBARS
FFL
+0.050

WALK WAY
360

EL. +0.110 F3 5400x1200x500 T16-200 T16-200 T16-200 T16-200 2T16 UBARS


220V BATTERY BANK 2

220V BATTERY BANK 1

(TOC) UPS BATTERY BANK

EL. +0.000
UPS BATTERY BANK

EL. -0.25 (VARY) F4 3100x1200x500 T16-200 T16-200 T16-200 T16-200 2T16 UBARS

350
600

a cb
yn

FFL
A B C
+0.01

F5 1300x900x500 T16-200 T16-200 T16-200 T16-200 2T16 UBARS

358
C C
+16.358 = F6 1300x1226x500 T16-200 T16-200 T16-200 T16-200 2T16 UBARS
75

+0.000 LVL
6550

LEVEL +0.000 = +16.358


TYPICAL

2 COATS BITUMINOUS PAINT


1000 GAUGE POLYTHENE SHEET
75 THK. BLINDING CONCRETE

* SUBGRADE SHOULD BE WELL COMPACTED UP TO 95% MDD

SECTION A-A

D D

250X100X10 THK. FIN PLATE WITH 300X100X10 THK. FIN PLATE WITH
3 NOS. 22Ø BOLT HOLES 3/M20 3 NOS. 22Ø BOLT HOLES 3/M20
Y X 6/M20 GR 8.8 BOLTS 60 60 GR 8.8 BOLTS WITH STANDARD NUT, GR 8.8 BOLTS WITH STANDARD NUT,
WITH STANDARD NUT, 12 THK. STIFF. PLATE UB 406x140x39 UB 406x140x39 LOCK NUT & WASHER LOCK NUT & WASHER 12 THK. STIFF. PLATE
LOCK NUT & WASHER @ 2.0m c/c BOTH SIDES @ 2.0m c/c BOTH SIDES

40
85

40
140

10 10

110
85
450

85

110
8
140

E E

40
85

40
450x180x16 THK. 50 50 UB 406x140x39
UB 406x140x39 UB 406x140x39 50 50 UB 406x140x39
UB 406x140x39 180
END PLATE WITH 8
6 Nos. 22Ø BOLT HOLES UB 406x140x39

REVISIONS
Y X FOR M20 BOLTS
6
SC1 SC1 SC1
A 03.01.2023 ISSUED FOR APPROVAL Shams HM TMS
REV DATE DESCRIPTION PREP. CHECK. APPR.

VIEW 1-1 VIEW X-X VIEW Y -Y VIEW 2-2 CLIENT:

F BAHRAIN ELECTRICITY & WATER AUTHORITY F


(EWA) KINGDOM OF BAHRAIN

ENGINEER:
GCCIA
Kingdom of Saudi Arabia,
P.O. Box 3894, Dammam 31481

GROUND BEAM -GB


(300x500) EL. +0.110 SUB-CONSULTANT:
(TOC) Consulting Engineers,
VARIES P.O. Box 5922,
FGL Manama, Kingdom of Bahrain
300
400

4/20Ø ANCHOR BOLTS, M20 CONTRACTOR: Hitachi Energy Technologies W.L.L


50 150 150 50 STANDARD NUT, LOCK STD.NUT , LOCK 12 Floor, Gulf Executive Offices
NUT & WASHER NUT & WASHER 3T16 (T)
125

G Office 1023, Entrance 15 G


50

2 COATS
6 BITUMINOUS PAINT
Road # 3801, Al-Qudaybiyah 338
1T16 EF Post Box : 2774, Manama, Kingdom of Bahrain.
BASE PLATE

Tel : +97317810666, Fax : +97317725332

500
150

400X400X16 THK. BASE PLATE CR NO : 166001


WITH 4/22Ø BOLT HOLES FOR 2 COATS BITUMINOUS PAINT
350

T10-200 LINKS
400

4/20Ø ANCHOR BOLTS 1000 GAUGE POLYTHENE SHEET CIVIL DESIGNER:


75 THK. BLINDING CONCRETE
150

3T16 (B)
WELL COMPACTED
SC1 SUBGRADE FILL UP TO 95% MDD
100X100x10MM thk PLATE
TACK WELDED IN 3 LOCATION PROJECT TITLE:
SECTION THROUGH
50

DYNAMIC REACTIVE POWER COMPENSATION PROJECT


DETAILS OF BASE PLATE TYPICAL ANCHOR BOLT DETAIL GROUND BEAM GROUND BEAM - GB
NAME DATE DOCUMENT TITLE:
H 03-01-2023 COOLER FOUNDATION AND ROOF SHED H
PREPARED Shams
G.A. SECTION, STRUCTURAL SECTIONS
CHECKED MA 03-01-2023
AND DETAILS
APPROVED HM 03-01-2023 AT RIFFA STATCOM
STANDARD: A1 SCALE:
DRG. NO: REV. SHEET
1JNG10374D2X755 A 2 OF 2
1 2 3 4 5 6 7 8 9 10 11 12