SLAB ANALYSIS AND DESIGN REPORT Orion Building Design System 18.0 (04.2012) / Page: DSM-1

SLAB ANALYSIS AND DESIGN REPORT

NOTATION:
d/h = Effective/Total Depth of Slab (d=h-conc.cover)
g/q = Dead/Live Load (not factored)
L1 = Width of the Slab Along the Strip Direction
L2 = Width of the Slab Perpendicular to the Strip Direction
C = Moment Coefficient M=C p / L^2
M-spn = Ultimate Design Span Moment
M-sup = Ultimate Design Support Moment
Mc = Balanced Support Moment
As = Steel Area (Required/Supplied)

Material: C20/25 / Grade 410 (Type 2)

Slab Strip: X1 -- Storey: 1


---------------------------

TYPE g L1 C-sup C-span As


Slab d/h q L2 M-sup M-span Req/Prov S T E E L B A R S
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
Support Mc = 0.6Support As = 323.14/646.27 Top:Y12-175(T1)

1S3 1 4.800 4325.20 0.0320 0.0240 254.4/646.27


112/150 1.500 4237.74 5.2 3.9 Bottom: Y12-175(B2)

Support Mc = 4.6Support As = 323.14/646.27 Top:Y12-175(T1)

1S1 1 4.800 1624.56 0.0630 0.0630 254.4/646.27


124/150 1.500 7675.24 1.5 1.5 Bottom: Y12-175(B1)
Deflection Check: L/d = 13.1 < 52.0 *** Sufficient ***

Support Mc = 7.3Support As = 323.14/646.27 Top:Y12-175(T1)

1S14 4 4.800 1500.00 0.5000 0.0000 254.4/646.27


124/150 1.500 5625.00 10.3 0.0 Bottom: Y12-175(B1)
Deflection Check: L/d = 12.1 < 14.0 *** Sufficient ***

Support Mc = 0.0

Slab Strip: X2 -- Storey: 1


---------------------------

TYPE g L1 C-sup C-span As


Slab d/h q L2 M-sup M-span Req/Prov S T E E L B A R S
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
Support Mc = 0.7Support As = 323.14/646.27 Top:Y12-175(T1)

1S12 2 4.800 3425.00 0.0592 0.0447 254.4/646.27


124/150 1.500 4293.37 6.3 4.8 Bottom: Y12-175(B1)
Deflection Check: L/d = 27.62 < 52.0 *** Sufficient ***

Support Mc = 8.6Support As = 323.14/646.27 Top:Y12-175(T1)

1S8 8 4.800 1525.00 0.5000 0.0000 254.4/646.27


124/150 1.500 4293.37 10.6 0.0 Bottom: Y12-175(B1)
Deflection Check: L/d = 12.3 < 14.0 *** Sufficient ***

Support Mc = 0.0

Slab Strip: X3 -- Storey: 1


---------------------------

TYPE g L1 C-sup C-span As


Slab d/h q L2 M-sup M-span Req/Prov S T E E L B A R S
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
Support Mc = 0.4Support As = 323.14/646.27 Top:Y12-175(T1)

1S2 1 4.800 4325.20 0.0320 0.0240 254.4/646.27


112/150 1.500 3437.50 3.4 2.6 Bottom: Y12-175(B2)

Support Mc = 3.3Support As = 323.14/646.27 Top:Y12-175(T1)

Project: Proposed_Residential_Development_michael
Project: Proposed_Residential_Development_michael - Proposed Residential Development for WT
Mr. (*1KE-QB46-HVAE-G8DF)
Michael
SLAB ANALYSIS AND DESIGN REPORT Orion Building Design System 18.0 (04.2012) / Page: DSM-2

1S1 1 4.800 1624.56 0.1000 0.0860 254.4/646.27


124/150 1.500 7675.24 2.4 2.1 Bottom: Y12-175(B1)
Deflection Check: L/d = 13.1 < 52.0 *** Sufficient ***

Support Mc = 0.3Support As = 323.14/646.27 Top:Y12-175(T1)

Slab Strip: X4 -- Storey: 1


---------------------------

TYPE g L1 C-sup C-span As


Slab d/h q L2 M-sup M-span Req/Prov S T E E L B A R S
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
Support Mc = 0.3Support As = 323.14/646.27 Top:Y12-175(T1)

1S5 1 4.800 1624.56 0.1000 0.0860 254.4/646.27


124/150 1.500 5952.87 2.4 2.1 Bottom: Y12-175(B1)
Deflection Check: L/d = 13.1 < 52.0 *** Sufficient ***

Support Mc = 3.6Support As = 323.14/646.27 Top:Y12-175(T1)

1S6 1 4.800 2900.24 0.0517 0.0387 254.4/646.27


124/150 1.500 4228.11 4.0 3.0 Bottom: Y12-175(B1)
Deflection Check: L/d = 23.39 < 52.0 *** Sufficient ***

Support Mc = 0.4Support As = 323.14/646.27 Top:Y12-175(T1)

Slab Strip: X5 -- Storey: 1


---------------------------

TYPE g L1 C-sup C-span As


Slab d/h q L2 M-sup M-span Req/Prov S T E E L B A R S
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
Support Mc = 0.5Support As = 323.14/646.27 Top:Y12-175(T1)

1S10 1 4.800 2025.00 0.1000 0.0860 254.4/646.27


124/150 1.500 6293.30 3.7 3.2 Bottom: Y12-175(B1)
Deflection Check: L/d = 16.33 < 52.0 *** Sufficient ***

Support Mc = 3.7Support As = 323.14/646.27 Top:Y12-175(T1)

1S11 1 4.800 3425.00 0.0320 0.0247 254.4/646.27


124/150 1.500 3481.93 3.4 2.6 Bottom: Y12-175(B1)
Deflection Check: L/d = 27.62 < 52.0 *** Sufficient ***

Support Mc = 0.4Support As = 323.14/646.27 Top:Y12-175(T1)

Slab Strip: X6 -- Storey: 1


---------------------------

TYPE g L1 C-sup C-span As


Slab d/h q L2 M-sup M-span Req/Prov S T E E L B A R S
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
Support Mc = 0.3Support As = 323.14/646.27 Top:Y12-175(T1)

1S4 1 4.800 1724.76 0.0860 0.0860 254.4/646.27


124/150 1.500 4325.20 2.3 2.3 Bottom: Y12-175(B1)
Deflection Check: L/d = 13.91 < 52.0 *** Sufficient ***

Support Mc = 4.7Support As = 323.14/646.27 Top:Y12-175(T1)

1S3 1 4.800 4237.74 0.0322 0.0248 254.4/646.27


124/150 1.500 4325.20 5.3 4.1 Bottom: Y12-175(B1)
Deflection Check: L/d = 34.18 < 52.0 *** Sufficient ***

Support Mc = 5.3Support As = 323.14/646.27 Top:Y12-175(T1)

1S2 1 4.800 3437.50 0.0443 0.0337 254.4/646.27


124/150 1.500 4325.20 4.8 3.6 Bottom: Y12-175(B1)
Deflection Check: L/d = 27.72 < 52.0 *** Sufficient ***

Support Mc = 0.5Support As = 323.14/646.27 Top:Y12-175(T1)

Project: Proposed_Residential_Development_michael
Project: Proposed_Residential_Development_michael - Proposed Residential Development for WT
Mr. (*1KE-QB46-HVAE-G8DF)
Michael
SLAB ANALYSIS AND DESIGN REPORT Orion Building Design System 18.0 (04.2012) / Page: DSM-3

Slab Strip: X7 -- Storey: 1


---------------------------

TYPE g L1 C-sup C-span As


Slab d/h q L2 M-sup M-span Req/Prov S T E E L B A R S
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
Support Mc = 0.0Support As = 323.14/646.27 Top:Y12-175(T1)

1S5 1 4.800 5952.87 0.0000 0.0000 254.4/646.27


112/150 1.500 1624.56 0.0 0.0 Bottom: Y12-175(B2)

Support Mc = 0.0Support As = 323.14/646.27 Top:Y12-175(T1)

1S1 1 4.800 7675.24 0.0000 0.0000 254.4/646.27


112/150 1.500 1624.56 0.0 0.0 Bottom: Y12-175(B2)

Support Mc = 0.0Support As = 323.14/646.27 Top:Y12-175(T1)

Slab Strip: X8 -- Storey: 1


---------------------------

TYPE g L1 C-sup C-span As


Slab d/h q L2 M-sup M-span Req/Prov S T E E L B A R S
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
Support Mc = 0.3Support As = 323.14/646.27 Top:Y12-175(T1)

1S6 1 4.800 4228.11 0.0320 0.0240 254.4/646.27


112/150 1.500 2900.24 2.5 1.8 Bottom: Y12-175(B2)

Support Mc = 2.5Support As = 323.14/646.27 Top:Y12-175(T1)

1S14 4 4.800 5850.00 0.0000 0.0000 254.4/646.27


112/150 1.500 1500.00 0.0 0.0 Bottom: Y12-175(B2)

Support Mc = 0.0Support As = 323.14/646.27 Top:Y12-175(T1)

Slab Strip: X9 -- Storey: 1


---------------------------

TYPE g L1 C-sup C-span As


Slab d/h q L2 M-sup M-span Req/Prov S T E E L B A R S
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
Support Mc = 0.3Support As = 323.14/646.27 Top:Y12-175(T1)

1S6 1 4.800 4228.11 0.0000 0.0240 254.4/646.27


112/150 1.500 2900.24 0.3 1.8 Bottom: Y12-175(B2)

Support Mc = 0.3Support As = 323.14/646.27 Top:Y12-175(T1)

Slab Strip: X10 -- Storey: 1


----------------------------

TYPE g L1 C-sup C-span As


Slab d/h q L2 M-sup M-span Req/Prov S T E E L B A R S
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
Support Mc = 0.0

1S14 4 4.800 1308.00 0.5000 0.0000 254.4/646.27


124/150 1.500 6500.24 7.8 0.0 Bottom: Y12-175(B1)
Deflection Check: L/d = 10.55 < 14.0 *** Sufficient ***

Support Mc = 7.8Support As = 323.14/646.27 Top:Y12-175(T1)

1S15 4 4.800 1302.00 0.5000 0.0000 254.4/646.27


124/150 1.500 5112.74 7.7 0.0 Bottom: Y12-175(B1)
Deflection Check: L/d = 10.5 < 14.0 *** Sufficient ***

Support Mc = 0.0

Slab Strip: X11 -- Storey: 1


----------------------------

Project: Proposed_Residential_Development_michael
Project: Proposed_Residential_Development_michael - Proposed Residential Development for WT
Mr. (*1KE-QB46-HVAE-G8DF)
Michael
SLAB ANALYSIS AND DESIGN REPORT Orion Building Design System 18.0 (04.2012) / Page: DSM-4

TYPE g L1 C-sup C-span As


Slab d/h q L2 M-sup M-span Req/Prov S T E E L B A R S
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
Support Mc = 0.6Support As = 323.14/646.27 Top:Y12-175(T1)

1S3 1 4.800 4325.20 0.0320 0.0240 254.4/646.27


112/150 1.500 4237.74 5.2 3.9 Bottom: Y12-175(B2)

Support Mc = 4.6Support As = 323.14/646.27 Top:Y12-175(T1)

1S1 1 4.800 1624.56 0.0630 0.0630 254.4/646.27


124/150 1.500 7675.24 1.5 1.5 Bottom: Y12-175(B1)
Deflection Check: L/d = 13.1 < 52.0 *** Sufficient ***

Support Mc = 1.5Support As = 323.14/646.27 Top:Y12-175(T1)

1S14 4 4.800 6725.24 0.0000 0.0000 254.4/646.27


112/150 1.500 1308.00 0.0 0.0 Bottom: Y12-175(B2)

Support Mc = 0.0Support As = 323.14/646.27 Top:Y12-175(T1)

Slab Strip: X12 -- Storey: 1


----------------------------

TYPE g L1 C-sup C-span As


Slab d/h q L2 M-sup M-span Req/Prov S T E E L B A R S
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
Support Mc = 0.4Support As = 323.14/646.27 Top:Y12-175(T1)

1S12 2 4.800 4293.37 0.0370 0.0280 254.4/646.27


112/150 1.500 3425.00 4.0 3.0 Bottom: Y12-175(B2)

Support Mc = 4.0Support As = 323.14/646.27 Top:Y12-175(T1)

1S11 1 4.800 3481.93 0.0320 0.0240 254.4/646.27


112/150 1.500 3425.00 3.4 2.6 Bottom: Y12-175(B2)

Support Mc = 0.4Support As = 323.14/646.27 Top:Y12-175(T1)

Slab Strip: X13 -- Storey: 1


----------------------------

TYPE g L1 C-sup C-span As


Slab d/h q L2 M-sup M-span Req/Prov S T E E L B A R S
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
Support Mc = 0.0Support As = 323.14/646.27 Top:Y12-175(T1)

1S10 1 4.800 6293.30 0.0000 0.0000 254.4/646.27


112/150 1.500 2025.00 0.0 0.0 Bottom: Y12-175(B2)

Support Mc = 0.0Support As = 323.14/646.27 Top:Y12-175(T1)

Slab Strip: X14 -- Storey: 1


----------------------------

TYPE g L1 C-sup C-span As


Slab d/h q L2 M-sup M-span Req/Prov S T E E L B A R S
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
(mm) (kN/m2) (mm) (kN.m) (kN.m) (mm2)
Support Mc = 0.0Support As = 323.14/646.27 Top:Y12-175(T1)

1S8 8 4.800 4293.37 0.0000 0.0000 254.4/646.27


112/150 1.500 1412.50 0.0 0.0 Bottom: Y12-175(B2)

Support Mc = 0.0Support As = 323.14/646.27 Top:Y12-175(T1)