You are on page 1of 5

Control for Grid-Connected and Stand-Alone

Operations of Three-Phase Grid-Connected Inverter


Thanh-Vu Tran*, Tae-Won Chun*, Hong-Hee Lee*, Heung-Geun Kim**, Eui-Cheol Nho***
*Dept. of Electrical Engineering, University of Ulsan, Ulsan, KOREA
**Dept. of Electrical Engineering, Kyungpook National University, Daegu, KOREA
***Dept. of Electrical Engineering, Pukyong National University, Busan, KOREA

Abstract—This paper describes a simple grid current control resonance damping [7]. When the main grid is disconnected
method for the grid-connected operation, and inverter voltage by faults such as voltage sags/swell, outage (intentional
control method based on the phase locked loop (PLL) for the islanding operation), the inverter changes its controller from
intentional islanding operation at the three-phase grid-connected current control mode to voltage control mode to supply a
inverter. The PLL controller based on the pq theory with a desired voltage to the sensitive load. When the grid
simple P-controller is used to synchronize the phase of inverter disconnection cause disappears, the DG system is switched to
output voltage with a grid voltage at the grid-connected the grid-connected operation.
operation or generate a desired inverter output voltage at the
islanding operation. The outputs of current controller are This paper describes a grid current control method for the
connected together to those of voltage controller, in order to grid-connected operation, and inverter voltage control method
prevent a sudden change of the outputs of both controllers based on the phase locked loop (PLL) for the intentional
during the transfer instant. The simulation and experimental islanding operation at the three-phase grid-connected inverter.
results are carried out to verify the effectiveness of the proposed At the mode transfer between the current controller and
control strategies. voltage controller, the outputs of both controllers may be not
equal, which will cause the rush current or voltage spike
Keywords-Distributed generation (DG), grid-connected during the transfer process. For the smooth transition between
operation, islanding operation, phase locked loop (PLL), three-
both modes, the outputs of current controller are connected
phase inverter.
together to those of voltage controller. The simulation and
experimental results are carried out to verify the effectiveness
I. INTRODUCTION of the proposed control strategies.
The need for reduction of the generation of electricity
using fossil fuels and the increasing demand of energy have II. CONTROL STRATEGY OF THREE-PHASE GRID-
prompted a interest in the use of renewal energy such as solar CONNECTED INVERTER
energy, wind energy, and hydrogen energy, which presents an
opportunity for distributed generation (DG) systems [1]. A. System Structure
Compared with large centralized power plants, the DG system Fig. 1 shows the configuration of three-phase grid-
provides improved power quality and more reliable power for connected inverter system, which consists of a power circuit
industries that require uninterrupted service. Developments of and control system. The power circuit contains the PV array or
power converters along with its sophisticated high- fuel cell represented by the dc source, three-phase PWM
performance controllers make it possible to integrate different
inverter, LCL filter with a damping resistor, three-phase critical
types of renewable energy sources to the grid.
load connected to output of LCL filter, and static transfer
The PWM inverters have been usually used for interfacing switch (STS) for grid-on or grid-off control. The control
the renewable energy source to the utility grid. It should system consists of the grid current controller for grid-connected
operate in grid-connected operation mode and islanding operation, the voltage controller for islanding operation, and
operation mode. During the grid-connected operation, the PLL controller. The outputs of current controller are connected
grid-connected inverter in the DG system is usually operated together to those of voltage controller, in order to prevent a
to inject preset real- and reactive-powers to the main grid, sudden change of the outputs of both controllers during the
which is the current control mode in synchronization with the transfer instant. A PLL controller is used to synchronize the
grid voltage. Some strategies of predictive current controllers, phase of inverter output voltage with a grid voltage or generate
which are robust to component parameter variations, a desired inverter voltage.
computation delay time are introduced in a grid-connected
inverter with LCL filter [2]-[5]. A current feedback method B. PLL controller
for a proportional-resonant (PR) controller is proposed for Fig. 2 shows the PLL controller based on the pq theory,
minimum current harmonic distortion as well as stability [6]. which is used to synchronize the phase of inverter output
A PI state space current controller is addressed based on pole voltage with a grid voltage at the grid-connected operation or
placement approach with respect to rise time, overshoot, and
If the error between the grid voltage phase and inverter
voltage phase at (1) is small, the error between two voltage
phases can be approximated as

Δω = VP sin(θ g − θ ) ≈ θ g − θ . (3)

The simplified block diagram of the linearized PLL is


shown in Fig. 3. From Fig. 3, the error between two voltage
phases Δω can be derived as follows.

s
Figure 1. A control structure of three-phase grid-connected inverter. Δω = θg (4)
s + KP

When the phase of grid voltage is in a step change, the


steady-state error of Δω is given by

s 1
ess = lim Δω = s × × =0. (5)
s →0 s + KP s

It can be seen that the P-controller used at PLL has not any
steady-state phase error.

C. Grid-connected operation mode


Figure 2. Structure of PLL controller.
Fig. 4 shows the grid current control loop at a grid-
connected operating mode. When the main grid is in normal
situation, a STS is closed, and the three-phase inverter with
LCL filter is connected to the main grid through the STS.
When the desired active and reactive powers are defined as P*
and Q*, respectively, the reference d-q grid currents can be
calculated as follows.

Figure 3. Small signal block diagram of PLL. (2 / 3) ⋅ ( P*Vgd − Q*Vgq )


i *gd = 2 2
(6)
generate a desired inverter output voltage at the islanding Vgd + Vgq
operation [8][9]. Two feedback signals labeled as fα and fβ are
obtained by the cosine and sine of the PLL output angle θ. By (2 / 3) ⋅ ( P *V gq + Q *V gd )
i *gq = (7)
the sum of products of the feedback signals and α-β input 2
V gd 2
+ V gq
voltages, which are two-axis voltages in the stationary
reference frame, a variation of angular frequency Δω
corresponding to a phase detector (PD) can be calculated as The PI controller is used to regulate the d-q grid currents.
follows. The outputs of PI controller Δ Vgd and Δ Vgq, which denote a
variation of the inverter voltage, are added to d-q grid voltages
in order to obtain a good dynamic response with the
Δω = Vα ⋅ f β + Vβ ⋅ fα = VP sin(θ g − θ ) (1) feedforward of grid voltage. As the outputs of voltage
controller Vdmv, Vqmv at the instant of transfer from the voltage
control mode to the current control mode are kept constant
Where Vp, θg are a peak and phase angle of input voltage, during a grid-connected operation and the outputs of both
respectively. Through the P-controller and the feedforward of controllers are connected together, the grid current can be
base angular frequency ωb=2π¯60Hz (or 50Hz) and integrator, controlled by the outputs of current controller Vdmc, Vqmc
the PLL output angle θ can be obtained from around the fixed Vdmv, Vqmv. The three-phase reference voltages
for generating PWM pulses can be calculated by adding a
fixed output voltage of voltage controller to an adjustable

θ = ( K P Δω + ωb )dt . (2) output voltage of current controller.
In order to synchronize the PLL output angle θ with the
grid voltage angle θg, the α and β components of input voltage
TABLE I. CIRCUIT RATING AND PARAMETERS USED IN SIMULATION
AND EXPERIMENT.

Rated power 5 kW
Grid voltage (Line-to-Line) 110 V / 60 Hz
Switching frequency 8 KHz
Lf1 1.3 mH
Lf2 0.24 mH
Cf 10 uF
Rd 1.5 Ω

Figure 4. Block diagram of grid current control loop.

Figure 6. Simulation result for grid current control at grid-connected


Figure 5. Block diagram of voltage control loop. operation.

at the PLL can be transformed from the measured grid line


voltages Vgab, Vgbc, Vgcab.

D. Islanding operation mode


When the main grid voltage is in fault situations, a STS is
tripped, the PWM inverter is operated in the voltage control
mode for regulating the voltage across a sensitive load with
110Vrms, 60Hz. Fig. 5 shows block diagram of the voltage
control loop at an islanding operation.

The reference d-q voltages are assigned as 220 6 V and


0V, respectively for controlling the magnitude of voltage
across the sensitive load to 110Vrms. The voltage magnitude
can be controlled by the outputs of PI controller Vdmv, Vqmv
with the fixed Vdmc, Vqmc, which are the outputs of current
controller at the instant of transfer from the current control
mode to the voltage control mode.
The input voltages of PLL are assigned to the same as
reference d-q voltages at the voltage control loop. From (1),
the output of PD, Δω can be calculated as

Δω = 220 6 cos θ ⋅ (− sin θ ) + 220 6 sin θ ⋅ cos θ = 0 . (8) Figure 7. Simulation result for inverter voltage control at the islanding
operation.
(a)

Figure 8. Photograph of experimental setup.

As Δω is always equal to 0, the angle θ with 60Hz


frequency can be generated by integrating a fixed angular
frequency ωb=2π¯60Hz. Through the voltage control and PLL
operation, a PWM inverter can supply the constant voltage
with 110Vrms, 60Hz into the sensitive load.

III. SIMULATION AND EXPERIMENTAL RESULTS

A. Simulation studies (b)


To verify the validity of the proposed control strategies for
the grid-connected operation and islanding operating, a Figure 9. Experimental results for the grid current responses : (a) D- and q-
simulation has been performed by using PSIM program. The axis grid current, (b) Grid voltage and inverter output current.
circuit rating and parameters used at simulation and experiment
is shown in Table I. Fig. 6 shows the outputs of d-q current
and voltage controllers, a-phase grid current and inverter output
current, when reference d-q grid currents are increased from
5A and -3A to 10A and -8A, respectively at gird-connected
operation. The d-q grid currents are quickly tracked to their
reference values. As increasing the grid current, the outputs of
current controller are slightly increased while the outputs of
voltage controller Vdmv, Vqmv remain constant. Fig. 7 shows the
outputs of d-q voltage and current controllers, a-phase grid
voltage and current, inverter output voltage and current at the
islanding operation. The inverter provides constant voltage
with 110Vrms, 60Hz, and supplies the current to the sensitive
load. The grid current becomes zero, because the main grid is
disconnected by STS.

B. Experimental results
Figure 10. Waveform and FFT analysis of grid current.
Fig. 8 shows the photograph of the experimental setup
with 5kW grid-connected inverter. The control system for the
analysis of a grid current, and the measured THD of the grid
grid connected and islanding operations is implemented by 32-
current is 1.92%.
bit DSP TMS320F28335. The three-phase AC switch is used
as the STS, and a grid-on/grid–off signal for AC switch is Fig. 11 shows the experimental results at the transfer from
generated by the DSP controller. Fig. 9 shows the the grid-connected operation to islanding operation when the
experimental results for responses of d-q grid currents and grid voltage is in fault situation. When 50% voltage sag at the
inverter output current at the grid-connected operation when main grid is occurred, STS is tripped by a fault signal. The
the reference d-q currents are changed from 3A and -1A to 5A grid-connected inverter changes its controller from grid
and -3A, respectively. Fig. 10 shows the waveform and FFT current control to inverter voltage control. It can be seen that
which has no steady-state phase error, was used to synchronize
the phase of inverter output voltage with a grid voltage or
generate a desired voltage. As the outputs of current controller
are connected together to those of voltage controller, the grid-
connected inverter was able to change smoothly from the grid-
connected operation to islanding operation. The experimental
results showed that the proposed control schemes are capable
of obtaining the good grid current response and also
maintaining the inverter voltage within the desired level. The
measured THDs of grid current and output voltage of inverter
are only 1.92% and 1.89%, respectively.

ACKNOWLEDGMENT
This work was supported by the Power Generation &
Electricity Delivery of the Korea Institute of Energy Technology
Evaluation and Planning (KETEP) grant funded by the Korea
government Ministry of Knowledge Economy (No.
Figure 11. Experimental results at the transfer from grid-connected operation 2010T100100465).
to islanding operation.

REFERENCES
[1] B. Kroposki, R. Lasseter, T. Ise, S. Morozumi, S. Papathanassiou, and N.
Hatziargyriou, “Making Microgrids Work.” IEEE Power & Energy
Mag., vol.6, no.3, pp.41-53, May/June, 2008.
[2] H. M. Kojabadi, B. Yu, I. A. Gadoura, L. Chang, and M. Ghribi, “A
Novel DSP-Based Current-Controller PWM Strategy for Single Phase
Grid Connected Inverters,” IEEE Trans. Power Electron., vol.21, no.4,
pp.985-993, July 2006.
[3] I. J. Gabe, V. F. Montagner, and H. Pinheiro, “Design and
Implementation of a Robust Current Controller for VSI Connected to the
Grid Through an LCL Filter,” IEEE Trans. Power Electron., vol.24,
no.6, pp.1444-1452, June 2009.
[4] J. C. Moreno, J. M. Espi. Huerta, P. G. Gil, and S. A. Geonzalez, “A
Robust Predictive Current Control for Three-Phase Grid-Connected
Inverters,” IEEE Trans. Ind. Electron, vol.56, no.6, pp.1993-2004, June
2009.
[5] K. J. Lee, B. G. Park, R. Y. Kim, and D. S. Hyun, “Robust Predictive
Current Control Based on a Disturbance Estimation in a Three-Phase
Figure 12. Waveform and FFT analysis of inverter output voltage. Grid-Connected Inverter,” IEEE Trans. Power Electron., vol.27, no.1,
pp.276-283, Jan. 2012.
the inverter provides a desired voltage to sensitive load after [6] G. Shen, X. Zhu, M. Chen, and D. Xu, “A New Current Feedback PR
mode transfer, and the grid current becomes zero. Fig. 12 Control Strategy of Grid-Connected VSI with an LCL Filter,” in Proc.
shows the waveform and FFT analysis of an inverter output IEEE APEC, 2009, pp.1564-1569.
voltage at the islanding operation, and the measured THD of [7] J. Dannehl, F. W. Fuchs, and P. B. Thogersen, “PI State Space Current
the inverter output voltage is 1.89%. Control of Grid-Connected PWM Converters with LCL Filters,” IEEE
Trans. Power Electron., vol.25, no.9, pp.2320-2330, Sept. 2010.
[8] P. Blaabjerg, R. Teodorescu, M. Liserre and A. V. Timbus, “Overview
IV. CONCLUSION of Control and Grid Synchronization for Distributed Power Generation
Systems,” IEEE Trans. Ind. Electron., vol.32, no.5, pp.1398-1609, Oct.
This paper described a simple grid current control method 2006.
for the grid-connected operation, and output voltage control [9] L.G. B. Rolim, D. R. da Costa, and M. Aredes, “Analysis and Software
method based on the PLL for the intentional islanding Implementation of a Robust Synchronization PLL Circuit Based on the
operation at the three-phase grid-connected inverter. The PLL pq theory,” IEEE Trans. Ind. Electron., vol.53, no.6, pp.1919-1926, Dec.
controller based on the pq theory with a simple P-controller 2006.

You might also like