Utility Bulding - NB-UTS-LVS-0002
Utility Bulding - NB-UTS-LVS-0002
1. GENERAL INSPECTION
2. EARTH CONTINUITY TEST
3. CONTACT RESISTANCE MEASUREMENT (CRM)
4. INSULATION RESISTANCE TEST (BEFORE HV TEST)
5. HIGH VOLTAGE (HI-POT) TEST
6. INSULATION RESISTANCE TEST (AFTER HV TEST)
7. AMMETER CALIBRATION TEST REPORT
8. VOLTMETER CALIBRATION TEST REPORT
9. UNDER VOLTAGE (UV)/OVERVOLTAGE (OV) RELAY TEST
10. CURRENT TRANSFORMER TEST
11. VOLTAGE TRANSFORMER TEST
12. ENERGY METER (MULTIFUNCTION METER) TEST
13. BREAKER TEST REPORT (INCOMER & OUTGOING)
14. RELAY TEST (SBEF, REF RELAY)
15. FUNCTIONAL TEST
16. ENERGIZE PROCEDURE
Note: **When applying HV voltage to Rϕ, short and ground the other Phases and Neutral. Also, similarly
vice versa for other Phases as mentioned in the above table.
7. AMMETER CALIBRATION:
250 250
% of Error = (Actual Reading – Expected Reading) / (Full scale Reading) *100
Ammeter Found Healthy : YES / NO
200 200
250 250
% of Error = (Actual Reading – Expected Reading) / (Full scale Reading) *100
Ammeter Found Healthy : YES / NO
7.16 OUTGOING T6M5- Ammeter Calibration:
Make : HOBUT CT Ratio : 250/5 A
Type : D96LMC Range : 0-250 A
Injected Primary Current Expected Meter Current Ammeter Reading
% Error
in Amps ( R,Y,B) in Amps in Amps ( R,Y,B )
50 50
100 100
150 150
200 200
250 250
% of Error = (Actual Reading – Expected Reading) / (Full scale Reading) *100
Ammeter Found Healthy : YES / NO
8.VOLTMETER CALIBRATION:
8.1 INCOMER -M1 Voltmeter Calibration:
Make : HOBUT VT Ratio :-
Type : D96LMC Range : 0-500 V
Measured Voltage Frequency
Phase Injected Voltage Injected
U12 U23 U31 (HZ)
R-N 240
Y-N 240
B-N 240
R-Y-B-N 415
Voltmeter Found Healthy : YES / NO
B-N 240
R-Y-B-N 415
Voltmeter Found Healthy : YES / NO
INCOMER ACB :
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag Incomer – M1
Rated Current (In) 1600A
In
IR
Overload
tr
(L)
Temp
L Trip time (Sec)
Isd
Selective
Isd * t = Flat
Short
tsd
Circuit (S)
S Trip Time (mSec)
Ig
Earth Fault I*t
( G) tg
G Trip Time (mSec)
Instantaneo
I= Non NA
us (i)
Manual Close/Trip from Push Button
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag Incomer – M2
Rated Current (In) 1600A
In
IR
Over load
tr
(L)
Temp
L Trip time (Sec)
Isd
Selective
Isd * t = Flat
Short
tsd
Circuit (S)
S Trip Time (mSec)
Ig
Earth Fault I*t
( G) tg
G Trip Time (mSec)
Instantaneo
I= Non NA
us (i)
Manual Close/Trip from Push Button
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T3-M1
Rated Current (In) 63A
IR Range 0.63 -1.0
Long IR Setting 1.0
Time Current Injected (A) 315A
L Trip time (Sec)
Short Ii Range 6-12
Time Ii Setting 12
Current Injected (A) 800A
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T3-M2
Rated Current (In) 63A
IR Range 0.63 -1.0
Long IR Setting 1.0
Time Current Injected (A) 315A
L Trip time (Sec)
Ii Range 6 - 12
Short Ii Setting 12
Time Current Injected (A) 800A
S Trip Time (m Sec)
Manual Close/Trip from Push Button Found is ok
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T3-M3
Rated Current (In) 63A
IR Range 0.63 -1.0
Lo
IR Setting 1.0
ng
Current Injected (A)
Ti 315A
0.63*20*5=63 A
me
L Trip time (Sec)
Ii Range 6 - 12
Sh
Ii Setting 12
ort
Current Injected (A)
Ti 800A
(20*0.63)*6*3=567 A
me
S Trip Time (m Sec)
Manual Close/Trip from
Found is Ok
Push Button
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T3-M4
Rated Current (In) 125A
IR Range 0.63 -1.0
Long IR Setting 0.63
Time Current Injected (A) 0.63*20*5=63 A 394A
L Trip time (Sec)
Ii Range 6-12
Ii Setting 10
Short
Current Injected (A) (20*0.63)*6*3=567
Time 1300
A
S Trip Time (m Sec)
Manual Close/Trip from Push Button Found Ok
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T3-M5
Rated Current (In) 400A
In 1.0
IR 1.0
Over load tr 30.00
(L) Temp Cold
Injected Current (A) 1600A
L Trip time (Sec)
Isd 1.0 ( For Test Reference Setting)
Selective Isd * t = Flat FLAT
Short tsd 0.30
Circuit (S) Injected Current (A) 500
S Trip Time (mSec)
Ig 0.2
I*t flat
Earth Fault
tg 0.2
( G)
Injected Current (A) 90A
G Trip Time (mSec)
Instantaneo
I= Non NA
us (i)
Manual Close/Trip from Push Button Found is ok
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T3-M6
Rated Current (In) 400A
In 1.0
IR 1.0
Overload tr 30.00
(L) Temp Cold
Injected Current (A) 1600A
L Trip time (Sec)
Isd 1.0 ( For Test Reference Setting)
Selective Isd * t = Flat FLAT
Short tsd 0.30
Circuit (S) Injected Current (A) 500 A
S Trip Time (mSec)
Ig 0.2
I*t flat
Earth Fault
tg 0.2
( G)
Injected Current in A 90A
G Trip Time (mSec)
Instantaneo
I= Non NA
us (i)
Manual Close/Trip from Push Button Found ok.
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T4-M1
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T4-M2
Rated Current (In) 250A
IR Range 0.63 – 1.0
Long IR Setting 0.8
Time Current Injected (A) 1000 A
L Trip time (Sec)
SC Curve Range 1 -12
Short SC Curve Setting 5
Time Current Injected (A) 1300
S Trip Time (m Sec)
Manual Close/Trip from Push Button Found Ok
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T4-M3
Rated Current (In) 250A
IR Range 0.63 – 1.0
Long IR Setting 0.8
Time Current Injected (A) 1000 A
L Trip time (Sec)
Ii Range 1 -12
Short Ii Setting 5
Time Current Injected (A) 1300
S Trip Time (m Sec)
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T4-M4
Rated Current (In) 50A
IR Range 0.63 – 1.0
Long IR Setting 0.8
Time Current Injected (A) 200A
L Trip time (Sec)
Ii Range 6 – 12
Short Ii Setting 12
Time Current Injected (A) 600
S Trip Time (m Sec)
Manual Close/Trip from Push Button Found Ok
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T4-M5
Rated Current (In) 630A
In 0.63 – 1.0
IR 0.63
Overload
Injected Current ( A) 1580 A
(L)
Temp Cold
L Trip time (Sec)
Selective SC.Curve Range 1 -12
Short SC Curve Charac. Setting 2 ( For Testing reduced Setting)
Circuit (S) Injected Current 1300
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T4-M6
Rated Current (In) 630A
In 0.63 – 1.0
IR 0.63
Overload
Injected Current ( A) 1580 A
(L)
Temp Cold
L Trip time (Sec)
SC.Curve Range 1 -12
Selective
SC Curve Charac. Setting 2 ( For Testing reduced Setting)
Short
Injected Current 1300
Circuit (S)
S Trip Time (mSec)
Manual Close/Trip from Push Button Found ok
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T5-M1
Rated Current (In) 63A
IR Range 0.63 – 1.0
Long IR Setting 0.63
Time Current Injected (A) 199 A
L Trip time (Sec)
Short Ii Range 6 - 12
Time Ii Setting 12
Current Injected (A) 800 A
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T5-M2
Rated Current (In) 250A
IR Range 0.63 – 1.0
Overloa IR Setting 0.63
d (L) Current Injected (A) 790
L Trip time (Sec)
SC curve charc. Range 1 – 12
Short
SC Curve Setting 2 ( For Testing purpose reduced setting)
Circuit
Current Injected (A) 600 A
(S)
S Trip Time (m Sec)
Manual Close/Trip from Push Button Found Ok
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T5-M3
Rated Current (In) 250A
IR Range 0.63 – 1.0
Overloa IR Setting 0.63
d (L) Current Injected (A) 790
L Trip time (Sec)
SC curve charc. Range 1 – 12
Short
SC Curve Setting 2 ( For Testing purpose reduced setting)
Circuit
Current Injected (A) 600 A
(S)
S Trip Time (m Sec)
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T5-M4
Rated Current (In) 250A
IR Range 0.63 – 1.0
Overloa IR Setting 0.63
d (L) Current Injected (A) 790
L Trip time (Sec)
SC curve charc. Range 1 – 12
Short
SC Curve Setting 2 ( For Testing purpose reduced setting)
Circuit
Current Injected (A) 600 A
(S)
S Trip Time (m Sec)
Manual Close/Trip from Push Button Found Ok
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T5-M6
Rated Current (In) 63A
IR Range 0.63 – 1.0
Long IR Setting 1.0
Time Current Injected (A) 315 A
L Trip time (Sec)
Ii Range 6- 12
Short Ii Setting 12
Time Current Injected (A) 800 A
S Trip Time (m Sec)
Manual Close/Trip from Push Button Found Ok
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T5-M8
Rated Current (In) 250A
IR Range 0.63 -1.0
Long IR Setting 1.0
Time Current Injected (A) 1250 A
L Trip time (Sec)
Ii Range 0.63 -12
Short Ii Setting 12
Time Current Injected (A) 3000
S Trip Time (m Sec)
Manual Close/Trip from Push Button Found Ok
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T6-M1
Rated Current (In) 125A
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T6-M2 ( SPARE)
Rated Current (In) 125A
IR Range 0.63 – 1.0
Long IR Setting 1.0
Time Current Injected (A) 625 A
L Trip time (Sec)
Ii Range 6 – 12
Short Ii Setting 12
Time Current Injected (A) 1500
S Trip Time (m Sec)
Manual Close/Trip from Push Button Found Ok
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T6-M3 ( NB-LF-LVS-0001)
Rated Current (In) 400A
Overload In 0.63
(L) IR 1.0
tr 30 s
Temp Cold
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T6-M4 (NB-LF-LVS-0001-F2)
Rated Current (In) 400A
In 0.63
IR 1.0
Overload tr 30 s
(L) Temp Cold
Injected Current ( A) 1260A
L Trip time (Sec)
Isd 1.0 ( for Testing Purposes reduced Setting )
Selective Isd * t = Flat
Short tsd 0.30
Circuit (S) Injected Current ( A) 500A
S Trip Time (mSec)
Ig 0.20
I*t Flat
Earth Fault
tg 0.20 S
( G)
Injected Current ( A) 90A
G Trip Time (mSec)
Instantaneo
I= Non NA
us (i)
Manual Close/Trip from Push Button Found Ok
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T6-M5 (SPARE)
Rated Current (In) 400A
In 0.63
IR 1.0
Overload tr 30 s
(L) Temp Cold
Injected Current ( A) 1260A
L Trip time (Sec)
Isd 1.0 ( for Testing Purposes reduced Setting )
Selective Isd * t = Flat
Short tsd 0.30
Circuit (S) Injected Current ( A) 500A
S Trip Time (mSec)
Ig 0.20
Earth Fault
I*t Flat
( G)
tg 0.20 S
Injected Current ( A) 90A
G Trip Time (mSec)
Instantaneo
I= Non NA
us (i)
Manual Close/Trip from Push Button Found Ok
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T7-M1 (SPARE)
Rated Current (In) 63A
IR Range 0.63 – 1.0
Long IR Setting 1.0
Time Current Injected (A) 315 A
L Trip time (Sec)
Ii Range 6-12
Short Ii Setting 12
Time Current Injected (A) 800 A
S Trip Time (m Sec)
Manual Close/Trip from Push Button Found Ok
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T7-M2 ( SPARE)
Rated Current (In) 50A
IR Range 0.63 -1.0
Long IR Setting 1.0
Time Current Injected (A) 250 A
L Trip time (Sec)
Ii Range 6- 12
Short Ii Setting 12
Time Current Injected (A) 700A
S Trip Time (m Sec)
Manual Close/Trip from Push Button Found Ok
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T7-M3 ( NB-PW-LVS-0001-F1)
Rated Current (In) 400A
In 0.50
IR 1.0
Overload tr 30.00
(L) Temp Cold
Injected Current ( A) 1000A
L Trip time (Sec)
Isd 1.0 ( For Testing Purposes reduced Setting )
Selective Isd * t Flat
Short tsd 0.30
Circuit (S) Injected Current ( A) 400A
S Trip Time (mSec)
Ig 0.20
I*t Flat
Earth Fault
tg 0.2
( G)
Injected Current (A) 50A
G Trip Time (mSec)
Instantaneo
I= Non NA
us (i)
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T7-M4 ( NB-PW-LVS-0001-F2)
Rated Current (In) 400A
In 0.50
IR 1.0
Overload tr 30.00
(L) Temp Cold
Injected Current ( A) 1000A
L Trip time (Sec)
Isd 1.0 ( For Testing Purposes reduced Setting )
Selective Isd * t Flat
Short tsd 0.30
Circuit (S) Injected Current ( A) 400A
S Trip Time (mSec)
Ig 0.20
Earth Fault
I*t Flat
( G)
tg 0.2
Injected Current (A) 50A
G Trip Time (mSec)
Instantaneo
I= Non NA
us (i)
Manual Close/Trip from Push Button Found Ok
PHASE REFERENCE R Y B
Panel Tag NB-UTS-LVS-0002
Breaker Tag T7-M5 (NB-UTS-PFC-0002)
Rated Current (In) 400A
In
IR
Overload
tr
(L)
Temp
L Trip time (Sec)
Isd
Selective
Isd * t = Flat
Short
tsd
Circuit (S)
S Trip Time (mSec)
Earth Fault Ig
( G) I*t
tg
G Trip Time (mSec)
Instantaneo
I= Non NA
us (i)
Manual Close/Trip from Push Button
15.FUNCTIONAL TEST
INCOMER M1 INCOMER M2
BREKAER
CLOSE
16.ENERGIZATION PROCEDURE:
Ensure LVAC Incomer -1,2, Bus Coupler Breakers are in Open Position, then Energies Auxiliary
Transformer -1,2 by closing the respective HV Circuit Breakers.
1. Check supply connected at both incoming, Voltage level and phase sequence.
2. Check the presence of the mechanical protectors preventing any accidental contact with
Live Parts.
3. Open the outgoing circuit breakers.
4. Supply Distribution Board via the Auxiliary Transformers check for voltage and correct
phase sequence and Polarities.
5. Upstream of all circuit breakers indictors and protections.
6. Check the distribution board alarm information return up to the output terminal blocks.
PHASE SEQUENCE CHECK:
Phase Sequence Remarks
R–Y–B
Y–B–R
B–R-Y
PLACING INTO SERVICE:
1. Energization of the LVAC board after closing of the main circuit-breaker.
2. Check that all necessary protective and signaling devices are in services.
3. Close all outgoing circuit-breaker, when necessary, after checking of the corresponding power
cable.
4. Phase out supplies with reference supply.