Professional Documents
Culture Documents
Introduction
Components of Power System
Generator Transformer
Generator Transformer
(Covered in: Electrical Machines I & II)
(Covered in: Electrical Machines I & II)
Transmission Line
Transmission Line
Power Transformer
3 4
Transmission Line
Sub-transmission
System
Distribution Transformer
Load
Power Transformer
3 4
Transmission Line
Sub-transmission
System
Distribution Transformer
Load
Power Transformer
3 4 1 3
2 4
Transmission Line
Sub-transmission
System
Distribution Transformer
5 6
Load
KISHENGANGA
AMARGARH
0
URI-II
367 0
URI
R 28 0 44
85 40 2
50.1
WAGOORA
-65 I 50.1
R 41 379 161 189 PAMPORE 0
45 40 -65 S 195 0
21 II DULHASTI
45 166 162
NETWORK DIAGRAM (INDIA) 34
S 400
jamma
300 308 WAMPOH 691
135 140 7 689 145
5 BAGALIHAR
U ev
II -57R 400
S 0
Mirbazar
I Remban S 0S
aM k
DATE DAY TIME SALAL-I&II
II
129 0
73 I S 0
0
SmaIr
II
212 65
25-Dec-2012 Tuesday 23:18:59 77 50.1
64
304
69
41
49
304 40
21 125 76
49 44
131 49 43 -57 50.1
115 403
43 KISHENPUR
S 0 CHAMERA-III
127 404
44 8
112 100281
116 CHAMBA
216
114 288
204 UDHAMPUR
50.2 44 64
101
JAMMU
0 -55
36 CHAMERA-II
S
0 225 50.1
209 34
50.2 22540 -14
Hiranagar 113 200 403 BAIRASIUL
35
34
76
Ranjit Sagar
12
115 405
CHAMERA-I 0
(RSD)
-28 JASSORE 36
0 13 -54 50.1 34
S
S
85 220
120
29
248
ihmaacala p`doSa
38 50.1 228
PONG 28 BASPA -46
SARNA 47 51
47 KARCHAM
41
50.1 417
30
I II 0 KOLDAM 7
2 421
40
0 137 -41
21
0 6N.JHAKRI
421 1I
R
7 DEHAR 3 38
HAMIRPUR 2
106
163 II 125
116
229 45 1 I 45-47 1
50.2 63 6 0
DASUYA 54 II 416
406 II 53
59
I 0 Q S 16395
83
0
AMRITSAR 208
0
0
-53
54
7 -49 50.1
211 NALLAGARH 5
54
2 69
22 44 36
50.2 3 I
JALANDHAR-53
229
17
78 II
227
170 411 68
17
36 71 94 39
55
76 I
246S
-40
51
170
0 0
251S
II 408 -51 II TEHRI
LUDHIANA 415 4 414
S
36
I
36
50.2
S
82 84 I
pMjaaba 2
207 PANCHKULA
S
S
7
S
102 4
198
II
201
Q S S 403
17
207 102 0 S 0
S
3
II 0
S
82 0
50.2 I
S
S 50.0 24 I
-48 410 30 50.1 7 71 IIKOTESHWAR
MOGA 37 -49 194 S 407 DEHRADUN
-51 MALERKOTLA 0 71 14 (THDC)
S
PATIALA S
KOTESHWAR
489 200
411
2811
95
136
144
S
N -45 96
]<araKMD R
S
S
caI
195 50.1
ABDULLAPUR
78
36 DHAULIGANGA
75
415
II I
na
0 I S 406 0
S 53 68 R 120 -50
7
189 R II RISHIKESH
NUHIYAWALI 101 I 23 64 225
-46
168
41 39 46 II 35
KIRORI 187
414 0
-48 14 -40 S 400
413 56 FATEHABAD 333 0 VISHNU PRAYAG
-45 256 I ROORKEE S 0
49 51 66 -44 78 205 S 0
21 0 II S 0
411 87 0
67
72 KAITHAL I 40 403 213 I S 0
2
21 43
256
II S S
24 0 0
19
50.0 85 0 0II
0
7
66
I 22 245 137 S TANAKPUR
hiryaaNaa
3
334 121 278
101
I 156 S
S
-40
44
94 263 S 0 17
420
285
MUZAFARN'R
18 49
114 0 50.1 56 273 S 0
6 50.2
46
50.1 PANIPAT -45
294
45 585-43 223 410
17
HISSAR KASHIPUR 223
58 620 415 -40
169
6
KHEDAR -44 406 929
1706
(RGTPS) MEERUT
209
S 197 -44 S
50.1 0
17
416 21 33 Q SONIPAT I LOHIA
20317
175
S
1
S II
37 0 HEAD
0
0
63 9
1701
33
S 37 310 48 DEEPALPUR I
175 2906
nao
S 22 283 161
S 0 S 10 -43 104II 40
531 0 50.1 408
S
217
R 374 359
349 418-41 MANDAULA -39 50.1
247
BHIWANI(PG) (BB) DHANONDA R 158 BAWANA
1
-41 CCGTB MURADNAGAR
1
153
Q Q R 299 0 456 R 100 MORADABAD 415S-34
pa
II -43 0 560 200 21 148
I 450 564 108
6
S
26 109 419 60
342
18
16 418
S 179
S
-42 1425 365
339
26
178
MUNDAKA 16 KITCHCHA
50
143 -41 8 298 119I II DADRI 416
R
50B'GARH 83
S
S 115S B'NAULI -37 CB GANJ- I
69
M'GARH 105-40 129 536 I
400
la
41 S 145 43 50.2 50.1
oSa
408 288 II 22
69
S 413 S
146 JHAJJAR 105 I 413 -29 193
S 49.8 S 134 I -39 417 131 83 280
454 549 40 R BAREILLY ALONG
a p`d
KABULPUR M. BAGH R 411
392 30
S 132 -37 36 340 (UP) 197
29 70 II68 S JHATIKARA
3 G.NOIDA 25 203
II 198 21 ROSA
405
FOG I 64 I
397
Q 999
J CLP 600 256S 779 S 414 II
S
navaada 280 203 R 30
Naacal
1122 DAPORIJO
13
Q 999
SURATGARH NAVADA 40 477 R
57 256
393
321
LOWER
144
DL'BAD 418 28 BAREILLY(PG) R
1196 49.1 TO DADRI BALLABGARH 586 SUBANSIRI
S
6 -39 143148
318
412
143
46 -29 415 313 63
593
S
ZIRO
A$
75 53 14
427
221 GURGAON 14 29 TANGMACHU
557
493
50.1
527
S
56 9 150 10
oSa
KHETRI DIBRUGARH 50.2TINSUKIA
231 BADARPUR S YAZAL_AP
-494
S
65 MANESAR 53 I 50.0 237
166
S
S
13 Q 999 Q 999
104
30
240
R
1
GAT
p`d
BIKANER 226 34 416 -25
34
17 0
77
13
II KAMENG 135 0 R S
13 S
0
S 0 II 37 15 0
78
1 I S 4
FOG
48.6 I R 400 7 -19 RANGANADI 3
79
S
999 II CHUMDO
S
II
Q 999 BARSINGSAR I
S 15 ALWAR 18 50.1
32 7 50.1
KILIKHAR 53 3
ar
-22 50.3
77
0 Q TEESTA-V
43 47 31 SIKAR(PG)
999 49 BHIWADI 281 398 35 II 364 LUCKNOW (PG) NAHARLAGUN 0 S
16 12 50.0
227232
S
]<
30 -46 416 R
75
Q Q 0S
Q 26 94 165 S 0 123 KATHALGURI(AGBPP)
75
31 S 3
63
3
235 76 84 132 109 416 S
22 217 S 109 -38 127 7S 0 27 MORAN
S 91 413 14 0 250 53 172 -19 KANGLUNG
32
0
S 0S
0.0 3
S
S
48 85 53 S S 11936 I CHUKHA 2 kucau- 0
365 6
132 II
2
S
SIKAR S 110 AGRA(UP) I TALA
59 161 217 144 I 127 ITANAGAR S
2
2 0 80S 0 26
S 305
KHEENSWAR 39 17
6
82
4
II 417 -35 178 KURCHU 50.1 (NIRJULI)
20 GANGTOK
358
59 CHOMU 17 24 286 II I II DHEMAJI KV
S
NAMRUP
60 S 119 S 119 NEEMRANA
56 S
19
0
Q 999 BHARATPUR 283 133 MAINPURI R 135 I RANGIT (NHPC) 21
RATANGARH I Q S -46 91 I 62 999 220
0
220 S 0 90 DEOMALI
190 -45 127
74
17 R 400 II 21 I II Q999
0
-45 50.2 REENGUS S 307 361 50.1 197 198 0 at
38
50.1 191 0 0 III S S 134 Q 999 ed 0 LAKWA
BHOPALGARH S 0 237 18 0 21 157
S
60
151
0 6
404 522 LUCKNOW II S
0
156 13 50.3 I Q NORTH
Q 999
NAGAUR S 0 187 S 133S 50.1 II I S 125 MELLI
187 231 (UP) 0
123
charg S
S
9 S -38 III 31 TINTIBI 21 R
40
-26
S
356
222 S JAIPUR 165 S 50.1 I
BaUTana
0
160
88 III II IV DEOTHANG R 70
224 36 3
S
999 4 NANGKHOR BALIPARA
0 (BASSI) R 229 30 R
0
PHULERA
36136
50.0 I 50.1
PHALODI 26 134 -23 IV 81 Bishwanath
R
JAIPUR S 166S 35 148 AGRA 224 42 0 -19 III MALBASE II R 400
36
Chariali 0 130 50.1
1746
77
416 50.1 4 curre MOKOKCHUNG
44
15
24 27
30
15
0 66 (RSEB) 50.1 0 (PG) S 31 7 S 0
42
157 424
8
JAIPUR(SOUTH) 35 228 32 311 II I 87 S 346 50.3 S
3 39 50 49 S 0
0
70 0 GOHPUR
250
0
-46 S MARIANI R
100
18
86 407 S NANGLAM 39 Line, 8
212
I Q Q S Q
S
I I GORAKHPUR GELEPHU 100 38 15
71 MAHUWA 999Q 403 31 S 225
255 346
15
S
HARDOI
74
699 10 38 5R
76
415 S 385 29 KV
251
0
S
999 213 33 II 42 0
Asama
RAMMAM 14
8
S
70 ROAD 46 I 50.2
19
S
-24 18
214 75 110 400
41
II S
7
0 37 -18 419 50.1
3
MERTA
111
AJMER S
0.0 95
69
51 0 II 31 0 100
S
50.2
0 18 -24 34
47 II
KHUP STG_F BRAHMAPUTRA
I GATE 0
is 133
136 BINAGURI
S
R 42
raja
HINDAUN
E
-46 Q 999 DAUSA 13 52 0 S GOLAGHAT 50.1 0
258 86 32 50.1 SULTANPUR 65 15 II This
GAT
I SALAKATI 405 49 DEPOTA
99 154 50.2 222 18 239 47 248 50.1 I DOYANG
115 53 1 UNNAO 18 17 33 228 15 I 29 37
0
TINWARI 78 II 35
60 S 50.1 220 60 286 688 SOHAWAL 405 235 S 135 50.1 SIPAJ SAMAGURI
7
ATI
0 0 DHOLPUR 4 S 0 S 0 R 10 40S 40 78 20 33 II 34
S
0.0 97
0
14 II 29 BONGAIGAON
80
Q 999 0 GAURI
sqaan
21
76 999
8 261 89 S 420 I 3 48 31
GOM
0 142
21
34
220
Q 0 BEAWAR S 138 88 61 I II TAJ GATE 7 0 88 50.2
I BIRPARA 55 7
3
50.1 GOSAI 999
64
-46 S
49.8 2 UPPCL S 0 31
11 127 338 6 CHINHAT 250 -17 SILIGURI 64 15 93 Q 134
S
BOKAJAN
64
0 S 226 S 50.1 279 104 29 14839-18 0 Rowata 55 49
12
82 -30 S 404 703
286 9
JODHPUR 110 350 III 50.2 Bornagar 50.1
204
236
MEHGAON II
0
50.1 S 31 S.CEMENT 6 65 64 -32 PANKI 407 S S
24 418
18 89 II Q 999
0
RANGIA -26 417
a
14 S 50.0 228 328 S RAIBAREILLY(PG) 0 II IV 94 55 I 1 50.1
65 62 400
0
DHALIGAON
124
16 Narangi
S
R 16 S
5 -16 MUZAFFARPUR 13 56 MISA
0 74 76 36 I 7
D
R
S 0
244 0
R
AURAIYA 110
380
III 13 26
31
118
S 121 S 80 50 50.1 I 25 57
S
S 0 7
21
408 68
147 0 26 54.4
7
4 MALANPUR 410 350 50.1 CHANDRAPUR
63
Sisugram
laON
0
43 419 SWAI 6 18
78
I 45
33
423
75
R 0 106 50.1 50.1 40 II 114 296 117 GOPALGANJ 0 S 0 18138 Q 999 NALBARI Kahelipara 25 25
BILARA KANPUR(UP) 0
71
36 S RAJWEST KOTA UNCHAHAR 11 II 38 Dispur
0
79S -45 231 MADHOPUR GWALIOR II 96 374 AZAMGARH
S
211 78
S S
10
227 226 204 41 50.1 S
0 IS Q 999 APM 11 26
0R
59 S 138 KOTA (MPSEB) 0 I 0
0
33
0
naagaa
33
0Q 75 72 109 305 29 0
33
96 1112 TPS -30 LANGPI 223
2090
999 196 -16 0 S 245 0 Q9999
406 JODHPUR 18 Q 999 44 118 82 50.1 95 1001 141
409 56 0 S
20S S
49.6 Sarusajai S 220 10
212
0
GWALIOR-34 38 195 BTPS R
88 KANPUR 169 S S
148 197
0
87 50.2 45 6 50.1
BARMER S 0 R25 25 25 50S 49.8KILLING DIMAPUR
49
209 S
II S R
9
Q9999 37 (PG) 49.8 101 (BONGAIGAON) S 25 44
AKAL 26
0 Q 999
71 67 80 105 Motijheel
409 96 50.1 FATEHPUR(UP) 62 S 0.0 39 46 S
0.0
0
141 40 0 II
PURNEA
71
Conductor disconnected from Dalkhola end. AGIA S
0
BOKO
R 10 S
0
R
25
(PG) 48R
0
11
(NA) MELURI
0 S I BHILWARA 44 230 339 96 607 -14 MAU 166 0 0 MTPS 144 194 50.1 101
Idle charged from Siliguri end. 0 S
25 0 (BYRNIHAT) 0
10
70 24 55 60 384 I 0 DARBHANGA S
Kaumf
R
R
0R 132
KIPHIRL
0
10
S
0 2
NURBONG(EPIP-2)
0
5
II 135 0 0 S
46
64 50.2 13 0
68 137 24 RAJABAGAN R 132 R 50.0
2
50.1
76 85 45 216 ANTA 352 FATEHPUR S 331
43 0 0 95 0
N 24 50.0 95 9
0
56 26 UMIAM-IV 2 KOHIMA
62
S
18
51
19
8 343 (PG) Q 9 43 31 208 0 51 8 KOPILI
14
234 0 2 134 UMTRU
18
S
68
0
Q 999KOTA 73 4 315 II 9999
130
III 0R 0 42 65
SAMASTIPUR 389 50.1 UMIAM-III 8
S
0 E 17
R
32
S
S 0 49 58 8 5 I II Q
366
Q S Q S Q -14 232 II
9 48
-11 386 53 DALKHOLA(PG) 50.1 134
137 UMIAM 35
0
57 1 -20 50.1285 I 17 (MESEB)
35 36 35
S
50.0 Q 999 9 BALIA 132 0 II 231 27
BALI 65 87 120 234 29
35
51 BARH
35
412 KHANDONG
maoGaalaya
35 35
BALOTRA 97 413 204 50.8 138 426 50.1 0 27
40
S 99 -44 I S
0 192 20 0 129 135 50.0
13 50.2 1 I S R
0
76 69 PATNA GANGA 43
415 RAPP-C&D 78 ALLAHABAD 83 16 44
S
0 NEHU Khliehriat
14
JALORE 0
91
0 KANKROLI I 116 37 17 57 39 76 286 135 I 234 233 196 II BARAUNI GATE II 42 0 (PG) 134
DHAURIMANNA 116 38 50 3 12 SILCHER
-45 222 410 97 66 0 50.1 NEIGRIHM
85
42 229 SHILLONG 50.1 R
SANCHORE 0 116 38 120 37 46 205 97 II KHAGAUL 0 0 I I 16 398 0 0 0
136 13 MAWLAI GATE
21
89
1
26
80
II 82 FATUHA 363 -7
77 R.P.Sagar 22 515 81 TURA NANGALBIBRA 133 50.1
S
BHINMAL 0.0 416 SAHUPURI
S
0 SIROHI 0 420 50.1 397
90
44
80
412 MALDA
S
216 104 RAPP-B I II R 197 55 134 142 50.1 136 -9 11 R 132
422
456 376 43
100 7
55
66 II 357 KAHALGAON 135 KARONG
55
BHINMAL
R
50.1 213 S 691 33 -16 175 416 ARRAH
123 128 521 417 50.1 CHERRAPUNJI LUMSNONG
196
374
36 I 23
R
50 40 82
R
-46 450 50.0
50 CHITTORGARH 118 101 SARNATH 69 PUSAULI 143 50.1 0 I 69 453 1638 130 34 I 521 37
HAFLONG(PG) (AS)
S
16
102 527 50.1 4
R 0 S 38 S 280 R 400 S 17
102 I 111 8 454 10 II 68 463 33 37 4
S
141 44 52 82 S 121 S 684 213 50.1 178
124 121 8
BIHARSHARIFF
-14 384 27 394 78 122 II 100 122
126 421 II
531 44 7
44
1
baaMglaa
S 80
I
S 97 12027 1371 FARAKKA
0S
II 120II 51 387
pur
98III 4
408 496 -11 383
213 S 226 0 27
0
50.2 118 S 69 379 4
0
UDAIPUR III S -7 S 406
236 26 98 116 50.1
S
49.5
75 453
9
-43 II 47 384 218 S
50.1 77
0
OBRA SRIKONA
52 RAPP-A 50.2 Bansagar I I 120 453 390 41 IV S 130 Q 999
maiNa
114 SILCHAR
141 52 8 R
457
ZERDA 416 53 229 378 26 251 Yangangpokpi 0
(KANSARI) 78 355 349 (TONS) 269 I 66 110 Q Q
286
S S
ASEB
412
117
16
16
15
50.1 MORAK Rajghat II II S 343 40 BANKA 18
S
50.0 14 (PG) Pailapool R 132R 19 SR 132
65 55 98 Q 9999 218 BADARPUR 50.1
56
53 PALANPUR 29 14 445
50.0
0 92 56 GAYA 170 KODERMA (Hyd) 135
R
7 91 134 IMPHAL (MAN) 25R
S 0.0
55
16 S NEMBAHERA 139 415 91 21 ANPARA-C 380
R 106 I 49 2
3 BINA POWER 42 58 MAITHON Q 9999 II 117 132(PG) 18
11
50.1 R
475414
0 8 0 4 II 0 33
THARAD S 0 50.1 0(G) MAITHON-RB 65
R 69 2 JIRIBAM 50.1 40
doSa
7
S 1 515 411 -9
384
0
50
12
E
S
6 CHABRA 32 7 S 0 BODHGAYA 66 32 S
2
379
Neemuch Rewa S
0.0 0 220
59 387
DEHRI S 228 725 187 219 I R 132R 50.0
S
189 1 Lalithpur 485 Q S 5 5 R
10
50.1 31 11 416 316 50.2 BOKARO A 0 DHARMANAGAR S S 16 32 R 132 Kakching
454
50.1 65AKRIMOTA 500 184 112 14 S 0 8 S 422 0
221 S KHERALU VIJAPUR 50.2 -24 S 98 320 S 0 S 232 50.1 140 I R 3 49.6 13 56 45 Ningthoukhong
444Q 999
79
324 DEODHAR 36 SANKHARI I II MEHSANA 229 380 407 201 241 -5 S
10
78
62 BINA(MP) 3 50.1 0 235 S
226 49.8 15 R R
50.0 R
330 I K'SWARIII 206 R 7 S 129
139
63 226 4 4 Gandhisagar S 1961 SINGRAULI -8 NABINAGAR S S
49.9
50.1 -41 124
75
S
50.1 50.1 50.1 14 P K BARI 14 106 10
25
17 Q 2
R 25
S S 225 Kuch Lignite(KLTPS) Q 999 NARDIPUR 86
S
Q 88 74 380 BOKARO B 183 Q 11 8228 Q 999 Q 999 422 50.1 SAGARDIH 134 KAILASHR DULLAUCHERRA
121
62 60
10
10 20 96
44
449 50.1
3
-17 50.1
550
137 228 151 126 19
45
0 (PANENDRO) 67 (SOJA) 87 48 9999 Q 485 LOKTAK
S
310
10
139 S 64 BINA(PG) 82 S 999 Q 999 MAITHON 10
9
S
144
II 326 68 442 I 41 TENUGHAT CHANDRAPURA -4 135 R 132
19
328
-40 Guna
58
S 58 18149 -24 50.2 Q
999 20 50.1
121
S 2 89 -500 S 558 413 415 50.3 Q Q S I100II TPS R 95 (CTPS) AMBASA 133KUMARGHAT 5 S
37
S S 81 185 24 II 0 421 S 0 95
R
58 306
0 21
25 67
43
1 S
0 304 2 CHURACHANDPUR
37
299DEHGAM Himmatnagar 50.1 100
128
50.1 114 I 66 S 45.0 R
62 23 10
62
339
KMLPR
177
53 25 68
8
S 453 III 39
Mitha S S
i~pura
226 604 563 (AGIOL)
176
61
8 45 23 108 425 65
0
20
3 28 Ramgarh 0
42
6 S 1S 304 66 SATNA -6 RIHAND 66 71
339
S 73 3 I 66 29 II 325 VINDHYACHAL 208 40 S 409 21
-8 1913
55 54
NAKHATRANA 50.0 GOKORNA 132
66
603 RANCHODPURA 0 15 IV DHALABJIS
67
S
45 303
S 63 319 55 451 S
50.1 50.2 BAKRESWAR
87
60
S
II -38 6 I 0 66 229 50.1
96
0
ANJARSS50.1 S 400 KOLASIB
34
S
190 (VADAVI) I III 319 72 DSP
17
88 BANSWARA 191 PATRATU 9 Q S
90 72
94 I 67
22
6
401
32
32 902
43
3 BACHHAU Q 50.1 51 320 57 450 II 66 50.1
179 I 187 183 83 53 II 321 63 saasana (PTPS) S 135 5
51
134
32
S 219 IV 66 GAMAITILLA
59
4
0
DSTPS 21
53
59 84 424 95
84
I S 206 S JAMLA 215
180
68 S II I 54 II 72 AGARTALA 50.1
85 248
50.2 NAGDA 321 74 3325 R 339
86 28
I 50.1
S 53 1 94 52 (PG) AIZWAL
22
50.2 -41 136 Khanpur Burnpur
II S 206 Badod SUJ'NGR
ADANI 413 S 73 S -10R 342
0
(TE) 27
163
181 S 216 2 390 II
0
0
223 0 223 50.0 70 332 272
54
31 0
160
5
S S
341 81 II
S
50.1 46Parulia(DV) 9999 PALLATANA
15
S
47 S 1 DHANSURA 86
S I S 425 58
190
MUNDRA 81 CHHATRAL 134 18 7 S 0S 0 298 49.9 S
27 26 S
0
49
157
84
181
246
60
11 1
NANIKHAKAR VARSANA S II 400 0 79 135 425
S
53 2913 0 0 18 0 0 421 SASAN II 46
91
S
6
144 I 14 52 27 9
S
(Chitrod) SHUJALPUR
gaumaTIBJNAGAR R 400
200
KADANA 0 121
278
10
53 62 S 9 (PG) S 98 401 I S 124 Muchipara 9 DURGAPUR BAIRABI R 16 AIZWAL
200
I
gaujarat
S 44 HATIA(N) 75
220
9
JIRANIA
445 320
9
MORBI UJJAIN
63 -26 313 7
1
411 II 4 PIRANA 30 31 320 90 267 III S 0 MEJIA B 7 (PARULIA) (AGTPP)
175
I
5
50.1 MORWA -5
0 114
II GANDHI NAGAR Shujalpur 50.1
0
Barjora
107
74 179 AECo 101 BHOPAL II DAMOH(PG) 101 GUMTI UDAIPUR
5
43
43
219 Dhangadhra 81 RATLAM 315 322 7 (R.C.NAGAR) (Zembawk)
21
40
88
123
50.1 20 0 51
10
180
1
62 288
R
MRSS 138 S 220 S 50.0 VIRAMGAM I (MP) 50.1 I 22 65 S
49.9
0
S S 220
89
283 421
30
275
0
4
138 70 50 Krish'ngr 9
50.1 421 21BARAMURA
S
S S 469 0
S
26 230 0
238
100
117
202 103 S 3 230 419 50.1 82 II Bairagarh 52 II 660 75 229 (WB) S 6
219
50.0
13
S 27 102 GODHRA
78
0
678 I S
96
50.1 S
0 24 PARULIA S 130 50.0
102
0 RANASAN (TORRENT) 82 806WANAKBORI 54 KATNI 433 SANTALDIH 50.1 0
maQyap`doSa
TAPPAR 16 16 50 SAGAR S
1 II 9
imajaaorma
39 50.0 7 IV Mahan(ESSAR) 233 25 MEJIA A 36 9
CGPL 415 S 0 3 429 III 50.1 73 21 75 8 50.0
94
4
25 324
52
S 220 DAMOH(MP) 88
0
36
3 50 0 75 134
0
7 5 21 56ROKHIA
93
80 3 41 88 66 R'PUR Asansol 11
52
23
MUNDRA50.1 3 20 24 RAJGARH 233
6
Halvad S RANCHI
PLEA
50.1 59 12 405 105 BIDHAN
0 NAGAR 71
23
STPS 46 47
31
S S
71 4 0 82
216
12
CHORANIA Kapadwanj 50.0
S
S
3 295 -7 251
0
419 407 22
-7 50.1
0 0 63SATGACHIA
0
68 18 17
14
233 Chandrapura INDORE I II W3-W1 AXIS 56
0
(LIMBDI) -39 133 2 KASOR PITHAMPUR 0
SE
417 18 423 24 105 50.1 -260424 251 0
0
130 32 (Halol) -38 3 43 0 999 WARIA(DV)
12
420 -35 475
171
288
107
333 R
9
38 II 19
187 41
228 -40 89 DPL
170
24 0 0
CHEC
231 50.1 50.1 PURULIA
142
53
24 227
S
0 00
66
18 1111 1 II -10
0
39
76
KARAMSAD 50.2 327 26 (PPSP)
67
24
104 45 333 60
549
67 100
0
420 355
0
90
0
119 50.1 24 I 24 114 4 113 36 50.1
9
20 342 I I 54 RAMCH'PUR I
36
167 0 S
8
NAGHEDI VADINAR 0 23 I 79 34 40 45 I 0 CHANDIL S
422 257
AGRA
46
S
22 JABALPUR 307 99 0 II 1516 BTPS 415
S
0
0
23 344 11 33 324 50 68 331 -20 49 115 S 12 232 15 -9 0
946 37
55 I 167 346 SGTPS1175
Hasdeo
231 0 JEERAT
S
72 38
135
484 20 II 132 60 3 25
26
S 50.0
198
-40 30 R 63 RISRA
168 34 Bango
-GWA
SIKKA
69
21 II 111 25 S
148
273 6 0 346 48 328 BIRSINGHPUR 38 10
58
S
780
135 II 109 II 324 67 20 93 337 BALCO 239 S 64 50 34
98 I
22
232 ASOJ I 420 49.9 Balco W3-ER AXIS 79 CESC GEN.= 762 25
0
50.1 111
74
2015
217 30 27 186
69
0
III ARAMBAG
79 II 78 6
LIOR
50.2 481 417 ITARSI S
KORBA(E) J'PUR(DVC) 0
II
178 85
221
227 50.1 DHUVARAN 50.1 133 VANDANA I -11 S 0
S
461 Handia 54 65 331 12 50.1 35 DOMJUR 0
32
319 100
55
II
S
222
30 91 113 6
JAMNAGAR Paliad I 50.1 -1 S
0 233 SUBHASGRAM S
53
II 50.1 243 IV 350 98 63 21 0
563
248
68
88
9
S II -6
S
66
Q S S 0
0
122 322 45 236 238
&
Reliance
42
0
421 91
49
II S 117 14
32
10
65
0
RAJKOT 95
piScama baMgaala
0 Bargi (PG)
S
20 88 93
3
98 50.1
36
Amarkantak
SOJA
0 456 136 129 S 0 295 -27 59 420
60
431 50.0
37
235 50.1
83
S1
(HADALA) 90 119 230 104 LANCO 97
15
10
27
15
23 0 109
10
104
20 415 0 72 Barwaha INDIRA Korba 218
73
204
71
DHANDUKA
107
Narsinghpur 50.1 794 431
13
-ZER
0
7
40 I JAMSHEDPUR
10786
127
40
105
S
300 361
S
235 (Ext.) 0 91 S
269
94
50.1 93 50.0
S
50.1 69 SAGAR 50.1
S
139
39
10 S
13
9
0
S
52 42 -20 515 983 50.1 Pendra DHARMA
0
224 503 50.1 I
1003 205 I 237
54
18
DA
82 288 50.1
105107
16
91 102 (DVC) 236
515
69
SEONI
367
HOWRAH
11
167 -12
16
16
Q 999 68 22 62 425 74
GONDAL 220 VARTEJ
13 199 23 I 95
FLOW
96 50.1
106
RANAVAV 125 227 SIPAT 0
1
67 74
221
52
95
137
S
1003 202 329 945 1582 -3 23 14
S 50.0 48 127 GANDHAR S.SAROVAR Nirmani
28 600 20 69 S
47
S
50.1 88 50.1 I S KASBA
388
987
0 115 8 II TARKERA 35
95
25 (GPEC) 229 KORBA
1031
BUDHIPADAR 109 II 44
174
5
0 AMRELI 50.1 257 SATPURA
45 634 42 42 2023 STPS 50.1 234 APNRL -9
18
497 73
S
Jambuva -39 430 340 II
9
25
Q
2 50.1
21
133 -25 50.1 KORBA(W) 240 112 50.2
0
760 420
999
221
0
3739
KOLAGHAT 74 S
0 405 147 -40 50.1 774 958 416
155
78
126
8
427 33 0 -3 103 KHARAGPUR
78 77
50.1 NEPANAGAR 131 18 1018 423 50.1 37 227
422 297 136 122 39
Q
5 0 -41 67 291 48 555 11
S
380 241
999
S
372 66 0
75
322
105
75
413
80
19 50.1 Sarni 125 40 43 LAKH'PUR
107
S
334
23
1
77
50.1 GANDHAR I II S 765 403 0 II
58
426 50.0
100
2
93 423
509
24 1
139
Pandurna 118
13
314 387 16
109
228
0
JETPUR -18 412 209 Pench S
56 107 427 -8 230
52843
73
42S 96 Balaghat 40
74
74
74
23 SAVARKUNDLA -32 ACBL 50.1
6
Achhalia
GAT6
E
1
S
57 16 JODA 50.2 42
8
8
52 IBTPS
210
574 230 VEDANTA ROURKELA
263
0
19 106 173
9 336 KHANDWA
18
57
Sardargarh Zagadia 7 48 I 0
210
73
143 BILASPUR 16 Barkot 40
94
313
S
S
TIRORA
393
Kanhan S 220 20
SPUR
0
S
41
108
146 II RAIGARH 239
330
C<aIsagaZ
PALITHANE 435 I 9 I Bilaspur 10 137 STERLITE 428 64 76 228 239
49
35 -8 50.1 I 21
HALDARWA 339 II
134
220 217 228 0 New HALDIA
BILA
415 91 367 73
11 R
BURLA 71
S
50.1 Surat-LPP 35 22 431 17 S S
28 2
R 47 Kalmeshwar 268 10 Burla 50 49 93 50.2 0.0
60
6 KOSAMBA 74 96 Q9999S 218 II RENGALI
0
KESOD I 4 JINDAL 34
40
130 BARIPADA
1
DHOKADWA 0 178 II 426 68 285 750 II 65 SW. Stn. 53
50.1 76 409
430
KAKRAPAR
22 11
W
S 104
R I 64 17 35
27 IV 31 104
29 0 50.1 0 1
RENGALI(PS) -15
S
50.1 211 KAWAS 0 49
50.1 S MAUDA 26 302 363 376 85 0 MAHANADI GATE 5 425
453 374 101 236 41
TIMBDI 308 209 BHATAPARA 0 27 I 0 50.1 75
500
0
102 209 0
37
0
222 41 1 SUGEN S S 220 Bhandara 0 II
30
S -37 426 312 65 98 KEONJHAR 0
84
339 27 77
152
S 84
503
0 II I I 237
26 45Utran 70 III
151
S
0
S BHUSAWAL S KORADI 169
53 27 28 Ichhapur 40
0S 53446.8 108 0
0
S -22 50.0
0
GSEG
1 393
S
34 S 50.1 386 15 312 37 0
19
77
19
S 81 68 0 II 122 118 0
46 1 0 S S 424
152 417 221 415 42 192 414 31 85 50.1
0
S 172 249 251
0
1 0 80
48
S
46 146 113 152 UKAI(H)
S S
146 10 444 IV 66
884
RENGALI
(PG) -13 21
149 Essar 152 336 BHILAI-10 -10 0
98
62 169 406
260
KIM 410
61
0
105 S S 108
NAVSARI S AMRAVATI 61 456 148 III I
79
100 RAIPUR
100
58
54 S Ambazari 230 61 838 I II
109
55
0
39 148 50.1
429 II
97
106
Navsari 48 S 50.0 S 81 17
0
59 61 89
885
106257
S 0 DEEPNAGAR Q 999
55
S
177
0
22 339 KSK
56
410 S 430 116 68
412 1667
69
71
48
90 50.0
0
0 Malegaon
86
S 0 S 296 21
2
Sachin S 103 33577 46.5 S S 382
S
50.0 109 230 101 126 15 69
Urla MAHANADI -12 69
S
DHULE S 311
S
43
122
108 1773 342
S
maharaYT/,
14
S
VAV 26UKAI(T)
105
S 0 Bhilad -40 56 S 73 80 555 232 TALCHER 0 50.2
84
288
112
45
S
S 16
130 80 89 332 STPS 64 64 238
110
125
66 -41 408 32 Khaparkheda 492 77 I II 73
385 232 50.1
S
0 BALASORE
199
S 212
S 25338
S
S
345
148
7
146
Amravati
Magarwada
W3 AREA
S
288
S
S 452 3
S
S 251 50.1 WARDHA KHAPARKHEDA S 80 50.0
0
S
(D&D) S 39 NSPCL 33 232
7
259 135
55
0
Talcher(GR) DUBURI
68
152 S Q S
Q S
422 17
S
S 74 S I Bhugaon 105
70 II PARAS -33 S 418 S S 0-47 GKEL 156
Karadpada 33 -10 0 96
0
58 I 0 I 30 S
0
369 160 50
(DNH) S 394
VAPI S
70 Chalisgaon 219 AKOLA S 403 S 0 0 36 EMCO S
S
S
295
159 379 0 422 MERAMUNDALI
160 123 100
S 49.6 390 36 II
-47 S
S 158 157 60 S
97 24 S 99
4S S Badnera
AaoiD,Xaa
75 405 439 24
67 0 I S 36 II 95 Warora 11 57 6 Gurur NALCO
S
94 54 -13
281
I
220 390 2 343 III
7
0
96
S
164
22 102 308 54
0
-43 390 S 0 50.1
488 Nasik 6 85 -17 II 50.1 -17
S
66 II 45 BHADRAWATI
10
31 Q 999
102
1
30
S
AURANGABAD S I
34 392 54 433 68 MENDHASAL
99
391 19
62
999
0
Q
0 31 59
74
78 S 10 22 0
20 353
157
418 390 55
5
284285 0
15
0 0
-44 S 19 BOLANGIR
S
S
45
90 0 275
884
0
44
S
TARAPUR
152 188 111 26 343 80 R
43
50.1
0
55 43
101 366
S
90 45 97 0
244
Pusad
56
1125
249
S
S
S 116S BIDANASI
101
S
56
81 44
S 420 197 410 S 206 CHANDRAPUR 1827 41 336 97
33
105
S 0 AXIS S 0
0
428
S
S S 99300 S 81 26 35 34 0 0
S S
S
50.0 197 S W3-W2 235 7
S
S
S 43 S 50.1 -32 NAYAGARH
19
1S 308 BOISAR
S -45 S 0 I 7
68
885
SS S
234 II -18 50.1 INDRAVATI
89
0
40 I BHANJANAGAR 50.1 232
0 840 418
280 0 4491 (PG) 22
S
S
Dhanu 0 S Jalna 410
280 II 50.1
S
503 S
34 50.1
80
104 S I II 51
167
S
41 0 S
S
1 III
7
26
0
290
435
I
S
15
6 I 84 Parbhani 336 229 53
BARASUR 107
405
Borivali S 400 50 0
S
PADGHE S 217 S 30 53
7
254 5 GODAVARI GATE
-I
286 S-44
50.0
0
S
II 38
S
-46 0
POLE
251 282 84 BABLESHWAR 38 THERUBALI
135
106
50.1 44 121 NIRMAL 50.1
52
I
51
-48 414 2 II S 0
279 286 46
408
S
-117 955
114
12
0
175
KALWA Ramagundam(B) II
74
-II
111
282 0 S
9
0S
68
277 270 22 12
84
291 BBSLR-1 Nanded 0 237 10
POLE
63 281 347 0S 220 135
406
270 14 0
Trombay 423 0SS 0
S
61 238
201
9 32 Ahmadnagar 353 S
S
12
137
S JAGTIYAL
344
50 21 50.0
S
131 S 17
95
-48 I
KHARGHAR II 419 0S MALAYALAPALLY 18
11 9 NARENDRAPUR
50.1
S
S 47 S 405 58 220 134
S
0
S 31 S 47 43 PUNE (PG) 422 S BHIMGAL 121 298 S
S 48 178 50 23 JAYANAGAR
50 292 44 VW PARLI(NEW) 234
884
2430 50.0
S S
51 S 7 CHAKANBosari 239 77 79 34 409 -36 50.1
240 50.1
S
54 3 49.9 413 -3 12 0
Uran S
55 0 47.8 64 33 JEYPORE 30 0
2
S
43 RAMAGUNDAM 12
34 1 55 64 220 214 74 50.1 U.KOLAB
222
72 105 29
50.1 S
410 50 75 285
8 S 21 Apta Mahindra 133 0 408 S 400 SS 50.0 282 22 0
219
105 LONIKHAND 49.9 8 0
S -6 DURSHED 30
885
-45
S 49.8 S 404
S 14 S 0 S
0 94
65 I S 0 S 0
I 62II PARLI-II -28
00 538 21 DICHPALLY 30 29 234 138 Manuguru
1
0
51
S
S
50.0 0 95 422 S 0 399 10 236 HWP 3
0S S
101
II
367 108
38 Chinchwad
S
293 0 II 0 0 S S 535 68 34
32 82 50.0 8
119
NAGOTHANE 176 KAKATIYA BALIMELA 0 I
0S S 0
PARLI-I 224 22 KOTHAGUDEM
124
-46 S 124 S 127 S
Theur
0
92
0S 0 7 5 416 50.0 397 495 23 19 239 0 2
50.0 228
S 42 S 43 0 S
0 91 28 S SIDDIPET 86 234 56 50.0 S
49.7
445
S 229 LONAND Satara 0 GARIVIDI
S 0
S
S S 74 233 1455 9 Araku
389
0
S
24 97 50.0 0
402
II S
76 79 S MALKARAM
114
I Kandalgaon S 0 S
39 SHANKARPALLY 78 WARANGAL 128 Machkund
99
0 420 260 411
0
S
230
0
Murud -1 0
1
R 0 83 292
S
0
1 55
S
285 S JEJURI SOLAPUR-III 50.0 III
S
R 1 KOYNA-IV 0 150 Usmanabad 271 116 KTPS 7
2
1
96
21
45
S SLPR-I 92 224
47
0 MINPUR GJVL
115
14
S 50.0 63
258
35 -32
11
258 257
28
S 48.0 11 71 -9 476 190 232
400 300 RS S 0 0 0 S 17 50.0 U.SILERU 50.0 49.9 223
400 IS Koyana-1&2 0 13 HUMNABAD 51 51 IV Sitarampatnam 563 PENDURTHI
388
384
179S
-45 DHABOL S
0 96 13 75 6 17 16
258
0 0
0
0
rpur 92
S
0 0 Koyana-3 291 14 SOLAPUR-II Wade Kothapally 80
0 5
104
0
66
11
103
DFARM
240
0 188 S
230 50.0
S
II S S 20S 400 50.0 Pandha 0 14 406 128 S 82
131 16 3
235
R S 400S 0 254
0
22 60 Bhogiri 234 50.0
S
10 403 S 207 49.9
66
Donkarai
102
22 KARAD
S
NEW KOYNA 0 16 S 60 Shapurnagar 38
102
91 19 40 159 L.SILERU BSES 49 GAZUWAKA 410
5
S
232 0MALKARAM 55
5
24 294 50.0 4 84 229
8 22 Vita 230
33 218 49(VIZAG)
179I -45 S 50.0 1 S
-44 231 114 S
189 34 57
0 S
159 58 Visakhapatnam
0
1
0
49.9
61
II 42 SOLAPUR(PG) 50.0 125 0 0S 188 S
S
39 S
13 21 50.0
179 I 81 Gachibowli AP 22 301
00
-6
53
0 1 91 S
I 0 71 0
1
7
421 2 50.0
17
237 PD Puram 43
40
949 61
S
87 Maulali KHAMMAM PG 4 97
2
S
69 15 SIMHADRI
0
0
49 I 48
II 498 418 2 S
67 II 419 287 1 1 31 49.9 TPS
0
S
977
R
79 10 9
S
61 Y.MAILARAM 40 286 308
0
-12 GHANAPURAM 49.9
JAIGAD 34 49.9 (HYDERABAD) 424 Chandrayengutta I 272 101
49.9 35 II 294 89 30 24
3 KALPAKA 310
3
487
1
83 24 410 314
0
I BOMMUR
0
63
S
II Miraj II 76 76 12 15 49.9 274 21
208 220 214 130 130
33 49.9 277 0 310
59
SEDAM 127 130 229 96 LANCO 233 85 VEMAGIRI
S
35
9
S
S
425 24 50.0
229 50.0 I NARKETPALLI 85 85 21 Spectrum
33
54
26
GULBARGA 49.9 TANDUR Sivarampally 67
161 324
59
S
0 40 87
1 422 331 335
S 324 50 227 49.9
0 KOLHAPUR III II 62 49.9
98 101
S
7 230 96 261 0 50
128
50.1 S 63Icchalkaranji SHAHABAD 0 101 68 S MIRYALGUDA 50.0
65 74 III S 47.0 49.9 Kakinada
31
S 143 269 II 23 48 0
0S 231 271
52 Kondapalli 379
GVK EXT.
196 R 89 Shamshabad
25 57 57 52 KONASEEMA
35
0
27
220 422 8 50.2 207 305 7 IV 35 VEMAGIRI(GMR)
45.0 88 50.0 230 57 4
1277 VTS 384 1 0
0
396 55 1
484
0 MAMIDAPALLI 50.0 56 54 0 GOTHAMI
-12 256 2 22 1
0
97
Q 999
75 I
289
Chillakallu
S
80 LANCO 32 33 94 50.0
158
172 50.0 101JEGRUPADU
70
0 118
52
77 0 II 220
17
S 38 396 Chellakurthi
0 372 43 233
174
16
182
36
ALMATTI 149 29 Vijjeswaram-I&II
157 0 368
14
63
79
S
67
155
SHAHAPUR
0 2
181
0
0
B.BAGEWADI Nunna 68
I -7 VTPS 51 31 83
I 224 TALLAPALLYS
171
BAGALKOT 71 149
II S
50.0 Q 999 49.9 S 424 -15 Gunadala 3 BHIMADOLE 20 NIDADAVOLU
DINDI 74 S 49.9 Nagar.Sagar 427 49.9 20 18
22
51
0
S
227 S 0 II
CHIKKODI S S Q 999 232 17 95 55
S 49.9 23
209
BHOOTPUR 2 49.8 247 50.0 228 I S
2
S
89
18
82
S
86
100
22
90 35 103 VIJAYAWADA Gudivada
93
18 MAHALINGPUR 23 -4
86
S
38 II
186
179
S
81 76
23 17 277 112
Tillari 19 90 KALWAKUTRTHY 28
S
S
90
277
S
S
18 Raichur
86
3
93
93
404
S
87
73
50.0
31
114 50.0
224 -36
55
BELGAUM
0 LINGASUGUR 69 Q 999 -22 251 SRISALEM TADIKONDA
49.9 69 RAICHUR SRISALEM RBPH 404 98 230
R
69
S 1099 417 83 LBPH 422 220 50.0
1 63 69 4
140
0.0
114
69
11
82 50.2 -1
14
999
S 220 Q 0 50.0
543 32
2 SS 112 48 69
82 -21
R 400 -13
440
999
KUSHTAGI 32
219 0 50.0
MAHBOOB NAGAR 76 242 64
267
64 18 23349.9
0
Q
TIVIM 7
Markapur 4
0
193 193
S S 49.8
0.0 S 200 (KE) -27 146 452 59
0
0 S 414 NARENDRA 31 PODILI
192
S
S
-19
57
AMBEWADI (PG) 418
192
0
S
0
62 62
MAPUSA
S
0 S
545
59
8 KURNOOL
70
65 49.8 56
111
GADAG 26
6 111
S
50.0 430
0
80 I 59 218
65 35 0 II
1
S
S
220 153 I
S
S
0 0 45.0 45.0 HAMPI ONGOLE
S 18 66
S
LINGAPUR 0
71
14 18 II 484 231 44 50.0
0
S
0 S
413 -25 45 S 9 50 II
0
S
50.0 65 S
0 0 0 66 50.0
PONDA SUPA 64 S 0 220
MUNIRABAD KV 50 Somayajulapally
S 220 XELDEMS 50.0 26 S
S 0 98 I
220 26 S
99
Line 45
62
S
0
43
0 21 S
ALIPUR
knaa-Tk
60
I 38
254
27 S
191
21 HUBLI S 210 50.0 S
189
57
S
NAGJHARI
45
110 II 480
61 0 S Nandyal
41
(NJPH) 111 113 -21
S
AanQa` p`doSa
0 S
68
229
117
112
73
112
418
40
46 220 0 49.9 33 S
13
S
KADRA 49.9
Bellary TPS 32 GOOTY MYDUKUR
220 54 KODASALLI I -24
50.0 107 S
388
71
55 Q 999
171
104 MUDDANUR
0
II 473
31
90 Tadipatri
KARWAR Q 999 HAVERI 0 172 63 95 MEPL
290 0 49.9 326 50.0 623(RayalseemaTPS)
-25 267 45.0 19 66 978 ANANTPUR
104 108 452 15
60 220 76 Anantpur 226
105 107
388
71
423 KAIGA 29 JINDAL 82
433
69
91
220 R 400 85 SEPL
50.0 0
29
0 50.0
312
-21 RAMAGIRI 447 84 84 49.9
I 78 62 416
79
68
0
76
61 50.0 49
226 (AP) (CS)NELLORE
21
II
41 50.0 418 -26 RAJAMPET
412 YERRAGUNTLA CUDAPPAH 62 -22
53 68
21
62
312 73 (CHINAKAMPALLY)
42
63
0
HINDUPUR
S
KODUR
53 377
32 41
S GATE
355
3891
50
GUTTUR
31
224 429
-26
49.9
42
441
GOLDEN 4082
R 109
33
371
63
72
50.0
72
S
24 83 85
66
71
38
45.0 0 S II I
28 8
69
RANIBENNUR
0 84 I 86
107
29 KAVERI
GATE
220
0 220 DAVANGERE 220
399 406 361 RENINGUTTA
50.0
373
49.9
46 84 49.9 MadhugiriGowribidanur 3036 104
34
59
18
59
II
65
33
220 S 0 HOODY -33 56
61
18 45.0 229 49.9
50.0
178
46 84 D B Pura 0 KALIKIRI 206 50.0
61
0 HIRIYUR(KE) 0 59
28
66 0 413
147
26 SULURPET
-30 422 HIRIYUR
67
233
34
53
11.3 304
62
-27 49.9 0
378
Q 9999 50.0 214(AP) 53
14 34
27 S
320 4
422
277
S
3313
Q 9999 I 14
87 ITPL
276 55 50 II HSR ALAMANTHI
0
0
236
68 68 208
0
14 -30
323
S
62
324
NORTH
7 0 -32 49.9 107 233 KOLAR 93 79 126 566MADRAS
S
0 0
0 SHIMOGA 0 0 49.9 414
0 29 S NRS-BG 49.9 PG 92
G.POONDI 33 2
71 1 413 Q 999 THIRUVALEM S
3
112
S
0 120 0 41 26 79
220 54 117 92
76 123
61 0 SUBRAMA- KE 2 114 77
0 236
S
1
TAIL RACE 42 30ENNORE
2
0 19 40 101
74 21817 51 533 MOSUR
S
0
S
55 34 3 NELAMANGALA TPS
0
150 219 220 532 75
VARAHI 35
100 44 18 S
-34 S'PUR Q 999
VALLUR Q 82
S
S 44 218 409 18 2 3 178 1 999
420 S 110
S
II 99 150 34 (MADRAS) 82 TONDIARPET
0 0 HASSAN SOMANAHALLI Yerandahalli I 15 122 413 7KORATTUR
45.0 UDUPI 0 50.0 418 11 (BANGALORE) 0 6 5
50.0 CS TN 6162
L E G E N D KEMAR
220 0
S
0
KUDREMUKH
-28
0 0
KUNIGAL
(Anchepalya)
109
11 -34
516S
19533
529
49.9
KALAVINDAPATTU
-35
37 KOYAMBEDU
87 66
57
0 BIDADI Harohalli 64
348 68S VINNAMANGALAM MYLAPORE
Q 999 MANGALORE
50.0 53
I II -36 405 -36 98 KADAPPERI
S S
I 43 77
KASARAKODE HOSUR 94
103
ARANI
S
S S
208 II 54
0TANIR BHAVI
S
S
11 THARAMANI
588
70
49.9 110
EXISTING 220 12 40
25
S
1 50.0 11 Tubinekere 62
S
SINGARAPET
S
44 SUNGUVARCHATRAM S P KOIL
42
S
0 KARIMANGALAM VILLUPURAM
11 56 13 129
49.9 220 Q 999
20
TV 0 113
S
53 0
765 KV LINES
122
41 0 344 130
45
0
215 S
METTUR MALAI KALPAKKAM
KANHIRODE 50.1 S 220Hootagalli
0
26
S (Mysore(KE)) Maduvanahalli 04 516 84 20 49.9 410
(Charged at 765 KV) 44 S
50.0 72 PONDICHERRY -40
43 Kadakola
0 4 23 575
43
S
METTUR 196 BAHOOR
S S
C R Nagar TUNNEL 20
99 KUTTIYADI KANIYAMPETAH 110
43
KUNDAH 1 METTUR CS 45 27 47
TPS 154 123 127 405 NEYVELI
89 73
22 76 78 453 27 CUDDALORE
220 KV LINES 2 126 16
111
DPP 18 II 33 28 2 4
67 50.0 85
483
39 35 115
20NEYVELI(EXP-2) 3 -42
132 KV LINES 0
162
94 83 158
118 DEVIAKURICHI 82 0 69
274
-53
HVDC B-TO-B 0 412 112 47
81
ARASURTIRUPPUR I 49.9
timalanaaDU
49
118 I 417 EACHENGADU STCMS 0
128 THUDIYALUR 387NEYVELI TPS 46
93 107 270
26
66
57 58 II 0
271
411
45
62
266
60
268
28
271
56
HVDC BIPOLE TRICHY-47THANJAVUR
36
-52 48 54
17 180 70 409 23
478
I 97 20
S
0 17 51 318UDUMALPET 50.0 24 0
144 144 45 0 47
56
PALAKKAD 35 THIRUVARUR
II 405 62 60
215
KALAMASSERI
138
220 68
57
93
L PERIYAR 10 3 I II PUDUKOTTAI
-1 70 3 48 PONAPURAM
THERMAL/GAS GENERATION : BRAHMAPURAM 31 49.9
0 7 S
S
50 47 0 N.MADURAI
222
S
140
43
68 -1 46 16 17 61 117
10
0
57
0
58
143
222
33S
134 -49
NUCLEAR GENERATION : 106 43 KADAMPARAI 65
31S
56
35
KARAIKUDI
31
korla
53
45
55 0KOCHI
81 139
9
MUVATTAPUZHA
25
21
THIRUVALEM Q
110
HYDRO GENERATION :
8
231
THENI
LINE FLOW LIMITS 70
S
II I I PARAMAKUDI
59
PALLOM 72
85 126
130 111
128
9
13
SABARGIRI
6
222
9
64
S
78
41
11 SATHUR
33
11
LINES CROSSES LIMIT-1 I II
0
125 126
105
327 230
65
75
29
KAYAMKULAM VEERANAM
LINES CROSSES LIMIT-2 223 68
24
49.3 7
46 7 KODIKURCHY 12 9
S
127
23
161
4 143
128
999 97 98
49.9
955
154
12 11 46
49.9 419 AUTO
5 I 100
46 8 UDAYATHUR
10 11 100 II
6
POTHENCODE 55 0 4
KOODANKULAM
S 234 98 IV III 0SANKANERI
S
50.0
TRIVENDRUM I
44
-56 411 II 56
49.9 13
S 619
6
12 S.R.PUDUR
418 230 49.9
KUDANKULAM
Figure: Power Map of India: 3771 Bus (upto 132 kV), 7077 Lines, 428 Transformers, 432 Generators
Power Map of India
Course Contents
1 Preliminary
Per-Unit Representation
150 M W 150 M W
1 ¯ = ?
V ¯ = ?
V 3
1 3
¯ = ?
V ¯ = ?
V
2 2 4 4
?
=
P 45
5 6
¯ = ?
V ¯ = ?
V
5 6
100 M W 200 M W
(Ignoring loss)
Course Contents
1 Preliminary
Per-Unit Representation
150 M W 150 M W
2 Load Flow Analysis
1 ¯ = ?
V 1
¯ = ?
V 3
3 Gauss-Seidel, NRLF, Decoupled and FDLF Analysis
¯ = ?
V ¯ = ?
V
2 2 4 4
?
=
P 45
5 6
¯ = ?
V ¯ = ?
V
5 6
100 M W 200 M W
(Ignoring loss)
Course Contents
1 Preliminary
Per-Unit Representation
2 Load Flow Analysis
1 V
f
¯ = ?
1
V
f
¯ = ?
3
3 Gauss-Seidel, NRLF, Decoupled and FDLF Analysis
¯ = ?
V
f
¯ = ?
3 Short Circuit Analysis
2 2 V 4 4
¯
I = ?
5 fault 6
f f
¯ = ?
V ¯ = ?
V
5 6
Course Contents
1 Preliminary
Per-Unit Representation
f1 (t) = ? 150 M W 150 M W f2 (t) = ? 2 Load Flow Analysis
1 ¯ (t) = ?
V 1
¯ (t) = ?
V 3
3 Gauss-Seidel, NRLF, Decoupled and FDLF Analysis
¯ (t) = ? ¯ (t) = ?
3 Short Circuit Analysis
2 V V 4 4
2
¯ (t) = ?
V ¯ (t) = ?
V
5 6
5 6
500 M W
200 M W
100 M W 200 M W
time
Course Contents
1 Preliminary
Per-Unit Representation
150 M W and 150 M W ?
or
2 Load Flow Analysis
1
100 M W and 200 M W ?
3 Gauss-Seidel, NRLF, Decoupled and FDLF Analysis
or
⋮
3 Short Circuit Analysis
2 4
5
Maximum Profit ? 6
5 Economic Dispatch of Generation
Scheduling of Generations
(Ignoring loss)
100 M W 200 M W
Course Contents
1 Preliminary
Per-Unit Representation
2 Load Flow Analysis
1 3 Gauss-Seidel, NRLF, Decoupled and FDLF Analysis
3 Short Circuit Analysis
2 4
5 6
5 Economic Dispatch of Generation
5 6
Scheduling of Generations
6 Automatic Control
Automatic Control of Frequency and Voltage
Grid Management in India
Course Contents
Pm
1
= ? Pm
3
= ?
1 Preliminary
1 3
Per-Unit Representation
2 Load Flow Analysis
2 4
Gauss-Seidel, NRLF, Decoupled and FDLF Analysis
1.0 Introduction
3 Short Circuit Analysis
By definition, electrical demand is the rate at which electrical power is being consumed over
a given time interval by all the defined loads of a well-defined area. For all the practical Balanced and Unbalanced Fault
purposes, demand is measured in megawatts (MW).
(Figure 1). If it is plotted for a week, month or a year it is named as weekly, monthly and Small Signal and Transient Stability
yearly load curve respectively.
Pd The load curve reflects the activity of a population
Pdof society
5 6
6 Automatic Control
GW->
Module A
Preliminary:
Per Unit Representation, Network Equation
z̄ 12 = (20 + j40)Ω
¯ o ¯ o
V 1 = 32∠ − 2 kV V 2 =? z̄ d = 400∠ − 20 Ω
z̄ 12 = (20 + j40)Ω
¯ o ¯ o
V 1 = 32∠ − 2 kV V 2 =? z̄ d = 400∠ − 20 Ω
1 2 3
z̄ 12 = (20 + j40)Ω
¯ o ¯ ¯
V 1 = 10.5∠0 kV V 2 =? V 3 =?
o
z̄ d = 400∠ − 20 Ω
11 kV /33 kV
¯ o
V 1 = 10.5∠0 kV
z̄ 12 = (20 + j40)Ω
1 2
z̄ 12 = (20 + j40)Ω
¯ o ¯ o
V 1 = 32∠ − 2 kV V 2 =? z̄ d = 400∠ − 20 Ω
z̄ 13 = (25 + j60)Ω
z̄ 23 = (22 + j50)Ω
3
1 2 3
11 kV /33 kV
z̄ 12 = (20 + j40)Ω
z̄ t = j16 Ω on H.V. side
¯ o ¯ ¯
V 1 = 10.5∠0 kV V 2 =? V 3 =?
o
z̄ d = 400∠ − 20 Ω
11 kV /33 kV o
z̄ d = 400∠ − 20 Ω
4
If base power = SB
Base voltage = VB
If base power = SB
Base voltage = VB
SB
Then base current IB = VB
(assuming single phase)
2
VB VB
Base impedance ZB = IB
= SB
G1 T1 T2
G3
Sd1 Sd4
4
1 2 3 G2
G1 T1 T2
G3
Sd1 Sd4
ZB = 36.3 Ω ZB = 1.2813 Ω
ZB = 4.033 Ω
4
1 2 3 G2
G1 T1 T2
G3
Sd1 Sd4
ZB = 36.3 Ω ZB = 1.2813 Ω
ZB = 4.033 Ω
Base Conversion
2
VB,old
SB,new
Zpu,new = Zpu,old × × 2
SB,old VB,new
4
1 2 3 G2
G1 T1 T2
Sd1 Sd4
Ratings:
Base Conversion G1 : 30 MVA 10.5 kV x = 0.435 pu
2 G2 : 15 MVA 6.6 kV x = 0.413 pu
SB,new VB,old
Zpu,new = Zpu,old × × 2 G3 : 25 MVA 6.6 kV x = 0.3214 pu
SB,old VB,new T1 : 15 MVA 33/11 kV x = 0.209 pu
T2 : 15 MVA 33/6.2 kV x = 0.220 pu
Base current:
SB3ϕ
IB = √
3VB3ϕ
Base impedance:
2
VB3ϕ
ZB =
SB3ϕ
Base current:
SB3ϕ
IB = √
3VB3ϕ
Base impedance:
2
VB3ϕ
ZB =
SB3ϕ
Per-unit values of impedance, voltage and current of a transformer are same regardless of whether they are referred
to the primary or the secondary side.
Per-unit voltage × per-unit current = per-unit power; which simplifies the calculations.
Network Equation
¯ ¯
I d1 I d2 ¯ ¯
I 1 I 2
¯ ¯
I g I g
1 2
1 2
1 2
¯ ¯
¯ I 12 I 21 ¯
I 13 I 23
¯ ¯
I 31 I 32
3
¯ 3
I d3
¯
I 3
Current Injection I¯i = I¯gi − I¯di Power Injection S̄i = S̄gi − S̄di
Network Equation
¯ ¯
I d1 I d2
ȳ 120
¯ ¯
V 1 V 2
2 ¯
¯ ȳ 120 I
I g
g 2
1
1 2 2
ȳ 12
ȳ 130
ȳ 13 ȳ 230
ȳ 23
2
2
ȳ 230
ȳ 130
2
3 ¯
V 3
¯
I d3
Network Equation
¯ ¯
I d1 I d2
ȳ 120
¯ ¯
V 1 V 2
2 ¯ 1 2 3
¯ ȳ 120 I
I g
g 2
1
2
ȳ t
1 2
ȳ 12
ȳ 12
ȳ 130
ȳ 13 ȳ 230
ȳ 23
2
2
¯
V ¯
V ¯
1 2 V 3
ȳ 230
2
(Ignore line charging capacitance)
ȳ 130
2
3 ¯
V 3
¯
I d3
Network Equation
I¯1 Ȳ11 Ȳ12 · · · Ȳ1n V̄1
I¯2
Ȳ21 Ȳ22 · · · Ȳ2n V̄2
. =
. .. .. . . .. ..
. . . . . .
I¯n Ȳn1 Ȳn2 · · · Ȳnn V̄n
Yij : Negative of the total admittance connected between bus i and bus j
ȳ 120
¯ ¯
V 1 V 2
2 ¯
¯ ȳ 120 I
I g
g 2
1
1 2 2
ȳ 12
ȳ 130
ȳ 13 ȳ 230
ȳ 23
2
2
ȳ 230
ȳ 130
2
3 ¯
V 3
¯
I d3
ȳ 120
¯ ¯
V 1 V 2
2 ¯
¯ I
I g
1
ȳ 120 g 2
Algorithm
1 2 2
7:
8: Ȳji = Ȳji − ȳk ;
Sl. From bus To bus R X ȳ0
1 1 2 0.02 0.08 j0.15 9: end for
2 2 3 0.05 0.10 j0.30
3 1 3 0.08 0.16 j0.35
Power System Operation and Control ©Ananyo Sengupta 24 / 256
Load Flow Analysis
Short Circuit Analysis Course Contents
Power System Stability Per Unit Representation
Economic Dispatch of Generation Network Equation
Automatic Control of Generation
i j
′ ȳ k
¯
I ¯ ¯
ij I ij
I ji
1 : ā ′
¯
V
i
i j
′ ȳ k
¯
I ¯ ¯
ij I ij
I ji
1 : ā ′
¯
V
i
" # " #
I¯ij ā∗ āȳk −ā∗ ȳk V̄i
=
I¯ji −āȳk ȳk V̄j
i j
′
¯
I ij
¯
I ij
ȳ k ¯
I ji
Y-Bus Building Algorithm
1: for transformer k = 1 to nt do
1 : ā ′
¯
V
i 2: i = from bus of transformer k;
3: j = to bus of transformer k;
4: Ȳii = Ȳii + a2 ȳk ;
5: Ȳij = Ȳij − ā∗ ȳk ;
ā : off-nominal turns ratio
6: Ȳji = Ȳji − āȳk ;
7: Ȳjj = Ȳjj + ȳk ;
" # " #
I¯ij ā∗ āȳk −ā∗ ȳk V̄i 8: end for
=
I¯ji −āȳk ȳk V̄j
1 2 3
1 : a (1)
z̄ = j0.1 pu
23
(2)
z̄ = j0.1 pu
23
z̄ t = j0.02 pu
a = 0.98
3
1 2
−j48.02 j49.0
1 : a (1)
z̄ = j0.1 pu
23
j49.0 −j50.0
(2)
z̄ = j0.1 pu
23
z̄ t = j0.02 pu
a = 0.98
3
1 2
−j48.02 j49.0
1 : a (1)
z̄ = j0.1 pu
23
j49.0 −j50.0
z̄
(2)
= j0.1 pu
Y-bus matrix of the system
23
z̄ t = j0.02 pu
a = 0.98
−j48.02 j49.0 0
j49.0 −j70.0 j20.0
1 Form Y-bus matrix of the system. 0 j20.0 −j20.0
3
1 2
−j48.02 j49.0
1 : a (1)
z̄ = j0.1 pu
23
j49.0 −j50.0
z̄
(2)
= j0.1 pu
Y-bus matrix of the system
23
z̄ t = j0.02 pu
a = 0.98
−j48.02 j49.0 0
j49.0 −j70.0 j20.0
1 Form Y-bus matrix of the system. 0 j20.0 −j20.0
Module 1
X
n
Pi = Vi Vk {Gik cos(δi − δk ) + Bik sin(δi − δk )}
k=1
Xn
Qi = Vi Vk {Gik sin(δi − δk ) − Bik cos(δi − δk )}
k=1
PV 1 2 Slack
PQ PQ
4 3
2 PV Bus
Known: P and V
Unknown: δ and Q
PQ PQ Example: Bus 1 (P1sp , V1sp known, δ1 , Q1 unknown)
4 3
3 Slack Bus
Known: V and δ
Objective: To obtain the voltage magnitude and angle of Unknown: P and Q
all buses from given power injections. Example: Bus 2 (V2sp , δ2 known, P2 , Q2 unknown)
PV Bus Data
Bus No.. V sp Qmin Qmax
2 1.02 -20 100
Voltage in pu, reactive power in MVAR.
PQ 3
100 MVA Base
x1 = F1 (x1 , x2 , · · · , xn )
x2 = F2 (x1 , x2 , · · · , xn )
..
.
xn = Fn (x1 , x2 , · · · , xn )
Gauss-Seidel Method
Multi-dimensional equations
Solving iteratively
f1 (x1 , x2 , · · · , xn ) = 0
(r+1) (r) (r) (r)
f2 (x1 , x2 , · · · , xn ) = 0 x1 = F 1 x1 , x 2 , · · · , x n
..
(r+1) (r+1) (r) (r)
. x2 = F 2 x1 , x2 , · · · , xn
fn (x1 , x2 , · · · , xn ) = 0 ..
.
(r+1) (r+1) (r+1) (r)
xn = F n x1 , x2 , · · · , xn
Rewriting
Initialization: Flat start (Vi = 1, δi = 0) for all PQ buses. Vi = Visp , δi = 0 for slack bus and all PV buses.
1 Pisp − jQi X
n
new
V̄i = − ȳ V̄
ik k
ȳii V̄i∗
k=1,k̸=i
new new
V̄i = V̄i + α V̄i − V̄i
PV Bus Data
Bus No.. V sp Qmin Qmax
2 1.02 -20 100
Voltage in pu, reactive power in MVAR.
PQ 3
100 MVA Base
f1 (x1 , x2 , · · · , xn ) = c1
f2 (x1 , x2 , · · · , xn ) = c2
..
.
fn (x1 , x2 , · · · , xn ) = cn
T
Let the solution be x̄∗ = x∗1 x∗2 · · · x∗n .
h i
(0) (0) (0) T
If we start with an initial guess x̄(0) = x1 x2 · · · xn , we require to find the correction
h iT
to make x̄(0) + ∆x̄(0) = x̄∗ .
(0) (0) (0)
∆x̄0 = ∆x1 ∆x2 · · · ∆xn
∗ ∗ ∗ ∂f1 ∂f1 ∂f1
(0) (0) (0)
f1 (x1 , x2 , · · · , xn ) =f1 x1 , x2 , · · · , xn + (0) (0) (0)
(0) ∆x1 + ∆x2 + .. + ∆xn
∂x1 x̄ ∂x2 x̄(0) ∂xn x̄(0)
∗ ∗ ∗ ∂f2 ∂f2 ∂f2
(0) (0) (0)
f2 (x1 , x2 , · · · , xn ) =f2 x1 , x2 , · · · , xn + (0) (0) (0)
(0) ∆x1 + ∆x2 + .. + ∆xn
∂x1 x̄ ∂x2 x̄(0) ∂xn x̄(0)
.
.
.
∗ ∗ ∗ ∂fn ∂fn ∂fn
(0) (0) (0)
fn (x1 , x2 , · · · , xn ) =fn x1 , x2 , · · · , xn + (0) (0) (0)
(0) ∆x1 + (0) ∆x2 + .. + ∆xn
∂x1 x̄ ∂x2 x̄ ∂xn x̄(0)
In matrix form
∆x(0)
∂f1 ∂f1 ∂f1 f1 (x̄∗ ) − f1 x̄(0)
∂x1 x̄(0) ∂x2 x̄(0)
··· ∂xn x̄(0)
1
∂f2 ∂f2 ∂f2 ∆x(0) f (x̄ ∗) − f x̄ (0)
∂x1 x̄(0) ∂x2 x̄(0)
· · · ∂x (0) 2 2
2
n x̄
= .
.. .. .. .. .
. .
. .
. . . .
(0) ∗
∂fn ∂fn ∂fn ∆x f n (x̄ ) − f n x̄ (0)
∂x1 ∂x2
· · · ∂x (0) n
x̄(0) x̄(0) n x̄
In matrix form
∆x(0)
∂f1 ∂f1 ∂f1 c1 − f1 x̄(0)
∂x1 x̄(0) ∂x2 x̄(0)
··· ∂xn x̄(0)
1
∂f2 ∂f2 ∂f2 ∆x(0) c − f x̄ (0)
∂x1 x̄(0) ∂x2 x̄(0)
· · · ∂x (0) 2 2
2
n x̄
= .
.. .. .. .. .
. .
. .
. . . .
(0)
∂fn ∂fn ∂fn ∆x c n − f n x̄ (0)
∂x1 ∂x2
· · · ∂x (0) n
x̄(0) x̄(0) n x̄
∆x(0)
∂f1 ∂f1 ∂f1 ∆f1 x̄(0)
∂x1 x̄(0) ∂x2 x̄(0)
··· ∂xn x̄(0)
1
(0)
∂f2 ∂f2 ∂f2 ∆x2 ∆f2 x̄(0)
∂x1 x̄(0) ∂x2 x̄(0)
··· ∂xn x̄(0)
. =
.. .. .. .. . ..
. .
. . . .
(0)
∆fn (0)
∂fn ∂fn ∂fn ∆xn x̄
∂x1 ∂x2
· · · ∂x
x̄(0) x̄(0) n x̄(0)
where, ∆fi x̄(0) = ci − fi x̄(0) is the mismatch.
x̄ is updated as
x̄(1) = x̄(0) + ∆x̄(0)
Power System Operation and Control ©Ananyo Sengupta 41 / 256
Load Flow Analysis Problem Formulation
Short Circuit Analysis Gauss-Seidel Method
Power System Stability Newton Raphson Load Flow Analysis
Economic Dispatch of Generation Decoupled Load Flow Analysis
Automatic Control of Generation Fast Decoupled Load Flow Analysis
x̄ is updated as
x̄(r+1) = x̄(r) + ∆x̄(r)
Convergence criterion n o
max ∆fi x̄(r) ≤ϵ
i=1:n
X
n
Vi Vk {Gik cos(δi − δk ) + Bik sin(δi − δk )} = Pisp , i = 1, 2, . . . , n; i ̸= s
k=1
X
n
Vi Vk {Gik sin(δi − δk ) − Bik cos(δi − δk )} = Qsp
i , i ∈ NP Q
k=1
PQ 3
100 MVA Base
Unknown: x̄ = [δ2 δ3 V3 ]T
In iterative form
PQ 3
100 MVA Base
∂P2 ∂P2 ∂P2
∂δ2 ∂δ3 ∂V3 ∆δ2 ∆P2
∂P3 ∂P3 ∂P3 ∆δ = ∆P
∂δ2 ∂δ3 ∂V3 3 3
Given: P2sp = 0.8 pu, P3sp = −1.5 pu, ∂Q3 ∂Q3 ∂Q3
∆V3 ∆Q3
∂δ2 ∂δ3 ∂V3
Qsp
3 = −1.0 pu
Alternatively
PQ 3
100 MVA Base
∂P2 ∂P2 ∂P
∂δ2 ∂δ3 V3 ∂V2 ∆δ2 ∆P2
3
∂P3 ∂P3
V3 ∂V3
∂P ∆δ = ∆P
∂δ2 ∂δ3 3 3
3
Given: P2sp = 0.8 pu, P3sp = −1.5 pu, ∂Q3 ∂Q3 ∂Q3
V3 ∂V
∆V3
∆Q3
∂δ2 ∂δ3 3 V 3
Qsp
3 = −1.0 pu
T
Unknown: x̄ = [δ2 δ3 V3 ] where, ∆P2 = P2
sp
− P2cal , ∆P3 = P3
sp sp
− P3cal , ∆Q3 = Q3 − Qcal
3
where,
∂Pi ∂Pi
Hij = ∂δj
, Nij = Vj ∂V
j
∂Qi
Jij = ∂δj
, Lij = Vj ∂Q
∂Vj
i
Limits on Qi of PV Bus i
Q limit check
Qmin , if Qi < Qmin
i i
Qi = Qmax , if Qi > Qmax
i i
Q , otherwise
i
If limit is violated, the PV bus is treated as the PQ bus and the voltage magnitude is changed accordingly.
Vi X X ∆Vj
n
∆Vi = ∆Qi − Jij ∆δj − Lij
Lii j=1,j̸=s ∀j∈N
Vj
PQ
Vi = Vi + ∆Vi
Assumption
In a power system, P − δ and Q − V are strongly coupled, whereas couplings between P − V and Q − δ are very weak.
Concept
¯
S1
¯ 1
V1
¯
Z = jX
¯ ¯ 2
I V2
P + jQ
Concept
X
− Q
¯
S1 V1
¯ 1
V1
¯
Z = jX
¯
V1
¯ ¯ 2
I V2
¯ X
V2
−j P
V1
P + jQ
Concept
X
− Q
V1
¯
S1
¯ 1
V1
¯ ¯
Z = jX V1
¯ ¯ 2
I V2
X
¯ −j P
V2
V1
P + jQ
1 Bus 1 is voltage controlled (and ref.) bus Figure: Phasor diagram for increasing P
2 Lossless line
Concept
X
− Q
¯
S1 V1
¯ 1
V1
¯
Z = jX
¯
V1
¯ ¯ 2
I V2
X
−j P
¯
V2 V1
P + jQ
∂Qi
Jij = ∂δj
≈0
H 0 ∆δ ∆P
=
∆V
0 L V
∆Q
∂Qi
Jij = ∂δj
≈0
H 0 ∆δ ∆P
=
∆V
0 L V
∆Q
∂Qi
For Q limit violated voltage controlled bus
Jij = ∂δj
≈0
Vi X ∆Vj
∆Vi = ∆Qi − Lij
Lii ∀j∈N
Vj
PQ
H 0 ∆δ ∆P Vi = Vi + ∆Vi
=
∆V
0 L V
∆Q
Convergence Criteria
1 Active power equation: [H] [∆δ] = [∆P ]
max {∆Pi }i=1,2,...,n;i̸=s ≤ ϵP
h i
2 Reactive power equation: [L] ∆VV
= [∆Q] max {∆Qi }∀i,i∈N ≤ ϵQ
PQ
1 For a transmission line X/R ≫ 1. So Gij ≪ Bij . B ′ is the matrix having elements −Bij ;
(i, j = 1, 2, . . . , n; i ̸= s)
2 Under normal operating conditions, angle difference (δi − δj )
B ′′ is the matrix having elements −Bij ; (i, j ∈ NP Q )
across transmission lines are small.
cos(δi − δj ) ≈ 1
sin(δi − δj ) ≈ 0
1 For a transmission line X/R ≫ 1. So Gij ≪ Bij . B ′ is the matrix having elements −Bij ;
(i, j = 1, 2, . . . , n; i ̸= s)
2 Under normal operating conditions, angle difference (δi − δj )
B ′′ is the matrix having elements −Bij ; (i, j ∈ NP Q )
across transmission lines are small.
cos(δi − δj ) ≈ 1
sin(δi − δj ) ≈ 0 Additional Assumptions and Simplifications
3 Magnitude wise Qi ≪ Bii Vi2 . Omitting the elements of B ′ that predominantly affect reactive
power flows, i.e. shunt reactances and transformer off-nominal
tap ratios.
Active Power Equation
′ ∆P Omitting from B ′′ the angle shift effect of the phase shifter that
B [∆δ] =
V predominantly affects reactive power flows.
Reactive Power Equation
Ignoring the series resistance in calculating the elements of B ′ .
′′ ∆Q
B [∆V ] =
V
Module 2
f f
1 ¯
V = ? ¯
V = ? 3
1 3
f
¯ = ?
V ¯
2 2 V = ? 4
4
f ?
¯ =
I 45
¯
I fault = ?
5 6
f f
¯
V = ? ¯
V = ?
5 6
f
Faults on Transmission Lines
¯ = ?
V ¯
2 2 V = ? 4
4
Most common (60-70%): lines are exposed to elements of nature
Lightning strikes: over-voltage causes insulators to flash over
¯
f
=
? High winds: topple tower, tree falls on line
I 45
Wind and Ice loading: mechanical failure of insulator
¯
I fault = ?
Short circuit in other elements
5 6
f f
Less common: cables (10-15%), circuit breakers (10-12%), generator, motor
¯
V = ? ¯
V = ?
5 6 transformer etc. (10-15%)
Overloading for extended periods, deterioration of insulation,
mechanical failure
b b b LG Fault
c c c
(75-80%)
a a a
LL Fault Asymmetrical
b b b
c c c
(5-7%) Fault
a a a
b b b LLG Fault
c c c
(10-12%)
a a
3 ϕ Fault Symmetrical
b b
c c (8-10%) Fault
Balanced Fault
1 2 3
G1 T1 T2 G2
50%
o
¯ = 1.0∠0o pu
V 1
o o
¯ = 0.95∠ − 5o pu ¯ = 0.98∠ − 2o pu
V
V 2 3
¯
I d
jXd ȳ d =
¯
V i
¯
Ē = E∠δ V t
¯
I d
¯
Internal Emf Terminal Voltage I d ȳ d
¯ + I
¯ (jX )
Ē = V t g d
jXd
¯
V
Ē = E∠δ t
¯ + I
¯ (jX )
Ē = V t g d
jXd
¯
V
Ē = E∠δ t
¯ + I
¯ (jX )
Ē = V t g d
f
¯ ¯
Zg I
g
Ē
t Time
Internal Emf Terminal Voltage a
o
o
¯ + I
¯ (jX ) E
Ē = V t g d
E i Actual envelope
a
Extrapolationof
steady valrre
f Extrapolationof transientenvelope
¯ ¯ where
Zg I
g
(a) Symmetricalshort circuit armature current in synchronousmachine l1l =
!//l =
Fig. 9.4 (Contd.)
lltl =
*Unity turn ratio is assumedhere.
Xa =
Ē
t Time
Internal Emf Terminal Voltage a
o
o
¯ + I
¯ (jX ) E
Ē = V t g d
E i Actual envelope
a
Extrapolationof
steady valrre
f Extrapolationof transientenvelope
¯ ¯ where
Zg I
g
(a) Symmetricalshort circuit armature current in synchronousmachine l1l =
′′ ′
Xd Fig.
< 9.4
X(Contd.)
d < Xd
!//l =
lltl =
*Unity turn ratio is assumedhere.
Xa =
1 Sub-transient period: continues for first 2-3 cycles, I¯gf = Ē
jX ′′
.
Ē d
Balanced Fault
1 2 3
G1 T1 T2 G2
50%
o
¯ = 1.0∠0o pu
V 1
o o
¯ = 0.95∠ − 5o pu ¯ = 0.98∠ − 2o pu
V
V 2 3
¯
I d
jXd ȳ d =
¯
V i
¯
Ē = E∠δ V t
¯
I d
¯
Internal Emf Terminal Voltage I d ȳ d
¯ + I
¯ (jX )
Ē = V t g d
ȳ g ȳ g
i i
i i
o
¯
V ¯
f
i m V m
i
o
¯
V ¯
f
o
j ¯ V f
ȳ g j V ȳ g j j ¯
j
m
j
V m
o
¯
V k ¯
f
k
k V k
S̄ d
m
o
¯ : pre-fault voltage at bus i
V i
ȳ g ȳ g
i i
i i
o
¯
V i m m
o
¯
V o
j ¯
ȳ g j V m
ȳ g j
j j
o
¯
V k k
k
S̄ d
m
o
¯ : pre-fault voltage at bus i
V i
ȳ g
i
i
ȳ g j
j
o
¯
−V k
f
¯
I
Z̄ f
¯
ΔV i
m
¯
ΔV m
ȳ g j
j
¯
ΔV j
k
ȳ d
m
o
¯
−V k
f
¯
−I
Z̄ f
o
¯
−V k
f
¯
−I
Z̄ f
∆V̄1 z̄11 · · · z̄1k · · · z̄1n 0
. . . . .
. . . . .
o
. . .
. .
¯
−V k
f
¯
−I ∆V̄k = z̄k1 · · · z̄kk · · · z̄kn −I¯f
Z̄ f . . . . .
. . . . .
. . . . .
∆V̄n z̄n1 · · · z̄nk · · · z̄nn 0
∆V̄1 z̄11 · · · z̄1k · · · z̄1n 0
. . . . .
. . . . .
o
. . .
. .
¯
−V k
f
¯
−I ∆V̄k = z̄k1 · · · z̄kk · · · z̄kn −I¯f
Z̄ f . . . . .
. . . . .
. . . . .
∆V̄n z̄n1 · · · z̄nk · · · z̄nn 0
Fortescue’s Theorem
¯
Vb Three unbalanced phasors of a three phase system can be
resolved into three balanced system of phasors.
¯
Vc
¯ ¯
V a1 V b2
¯
V a0
¯
V b0
¯
V a2
¯
V c0
¯
V c2
¯ ¯
V c1 V b1
Symmetrical Components
¯ ¯
V a1 V b2
¯
V a0
¯
V b0
¯
V a2
¯
V c0
¯
V c2
¯ ¯
V c1 V b1
¯ ¯
¯ Va Va
V a0
¯
V a2
¯ ¯
¯ Vb Vb
V a1
¯
V b0
¯
V c1
¯
V b2
¯
V b1
¯
V c2
¯ ¯
Vc Vc
¯
V c0
Symmetrical Components
Sequence to Phase Transformation
V̄a 1 1 1 V̄a0
V̄b = 1 α2 α V̄a1
V̄c 1 α α2 V̄a2
α = 1∠120o
In matrix form
V̄p = AV̄s
V̄p : vector of original phasors
V̄s : vector of symmetrical components
Symmetrical Components
Sequence to Phase Transformation Phase to Sequence Transformation
V̄a 1 1 1 V̄a0 V̄a0 1 1 1 V̄a
V̄b = 1 α2 α V̄a1 V̄a1 = 1 1 α α2 V̄b
3
V̄c 1 α α2 V̄a2 V̄a2 1 α2 α V̄c
Symmetrical Components
Sequence to Phase Transformation Phase to Sequence Transformation
V̄a 1 1 1 V̄a0 V̄a0 1 1 1 V̄a
V̄b = 1 α2 α V̄a1 V̄a1 = 1 1 α α2 V̄b
3
V̄c 1 α α2 V̄a2 V̄a2 1 α2 α V̄c
a
¯
I c
c
Z̄ y Z̄ y
¯
V ag
¯
I n
¯
V cg Z̄ y
¯
I b Z̄ n
b
¯
V bg
g
a
¯
I c
c
Z̄ y Z̄ y
¯
V ag
¯
I n
¯
V cg Z̄ y
¯
I b Z̄ n
b
¯
V bg
g
¯
V̄ag Z̄y + Z̄n Z̄n Z̄n Ia
V̄bg = Z̄n Z̄y + Z̄n Z̄n I¯b
V̄cg Z̄n Z̄n Z̄y + Z̄n I¯c
¯
a V̄a0 Z̄y + 3Z̄n 0 0 Ia0
¯
I c V̄a1 = 0 Z̄y 0 I¯a1
c V̄a2 0 0 Z̄y I¯a2
Z̄ y Z̄ y
¯
V ag
¯
I n
¯
V cg Z̄ y
¯
I b Z̄ n
b
¯
V bg
g
¯
V̄ag Z̄y + Z̄n Z̄n Z̄n Ia
V̄bg = Z̄n Z̄y + Z̄n Z̄n I¯b
V̄cg Z̄n Z̄n Z̄y + Z̄n I¯c
¯
a V̄a0 Z̄y + 3Z̄n 0 0 Ia0
¯
I c V̄a1 = 0 Z̄y 0 I¯a1
c V̄a2 0 0 Z̄y I¯a2
Z̄ y Z̄ y
¯
I a
¯
V
0
ag
¯ ¯
I a I a
¯
I
1 2
n
¯
V cg Z̄ y
¯
¯
I
Zy
b Z̄ n
¯
b ¯ ¯
V a0
V a1 ¯ ¯ V a2 ¯ ¯
¯
V Z1 = Zy Z2 = Zy
bg
g ¯
3Z n
Z̄ m ¯
Z̄ m Z̄ s I b
′
¯ ¯
V a ¯
I Va
Z̄ m Z̄ s c
′
¯
V ¯
b Vb
′
¯
V ¯ ¯ ¯ ¯ ¯
I Vc
n = I a + I b + I c
c
Z̄ m ¯
Z̄ m Z̄ s I b
′
¯ ¯
V a ¯
I Va
Z̄ m Z̄ s c
′
¯
V ¯
b Vb
′
¯
V ¯ ¯ ¯ ¯ ¯
I Vc
n = I a + I b + I c
c
′ ¯
V̄a V̄a Z̄s Z̄m Z̄m Ia
V̄b − V̄ ′ = Z̄m Z̄s Z̄m I¯b
b
V̄c V̄c′ Z̄m Z̄m Z̄s I¯c
′ ¯ ¯
V̄a0 V̄a0 Z̄s + 2Z̄m 0 0 Ia0 Z̄0 0 0 Ia0
V̄a1 − V̄ ′ = 0 Z̄s − Z̄m 0 I¯a1 = 0 Z̄1 0 I¯a1
a1
V̄a2 ′
V̄a2 0 0 Z̄s − Z̄m I¯a2 0 0 Z̄2 I¯a2
′ ¯ ¯
V̄a0 V̄a0 Z̄s + 2Z̄m 0 0 Ia0 Z̄0 0 0 Ia0
V̄a1 − V̄ ′ = 0 Z̄s − Z̄m 0 I¯a1 = 0 Z̄1 0 I¯a1
a1
V̄a2 ′
V̄a2 0 0 Z̄s − Z̄m I¯a2 0 0 Z̄2 I¯a2
¯ ¯ ¯
I a I a I a
1 2 0
¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯
Z1 = Zs − Zm Z2 = Zs − Zm Z 0 = Z s + 2Z m
′ ′
¯ ¯
′
¯ ¯ ¯ ¯
Va V Va V Va V
2 a2 0 a0
1 a1
Since a transformer is a static device, leakage reactance does not change with alternation of phase sequence of the
applied voltage. Hence, negative sequence impedance is also equal to its leakage impedance.
Different combination of ∆ and Y windings decides the flow of zero sequence currents.
1 When magnetizing current is is neglected, transformer primary would carry current only if there is current flow on the secondary
side.
2 Zero sequence current flows in the windings of star connection only if the neutral point is grounded which provides the
necessary return path for zero sequence currents.
3 No zero sequence current can flow in the line connected to delta connection as no return path is available.
Zero sequence current can, however, flow in the windings of the delta connection.
¯ ¯
Zn Zn
¯ ¯
Zn Zn
¯
Zn
¯
Zn
Figure: Yg − Yg transformer
¯
Zn
¯
Zn
Figure: Yg − Yg transformer
¯
Zn
Figure: Yg − Y transformer
Power System Operation and Control ©Ananyo Sengupta 71 / 256
Load Flow Analysis
Short Circuit Analysis Balanced Fault Analysis
Power System Stability Unbalanced Fault Analysis
Economic Dispatch of Generation Z-bus Building Algorithm
Automatic Control of Generation
¯
Zn
¯ ¯
Zn Zn
Figure: Yg − Yg transformer
Figure: Yg − ∆ transformer
¯
Zn
Figure: Yg − Y transformer
Power System Operation and Control ©Ananyo Sengupta 71 / 256
Load Flow Analysis
Short Circuit Analysis Balanced Fault Analysis
Power System Stability Unbalanced Fault Analysis
Economic Dispatch of Generation Z-bus Building Algorithm
Automatic Control of Generation
¯
Zn
¯ ¯
Zn Zn
Figure: Yg − Yg transformer
Figure: Yg − ∆ transformer
¯
Zn
Figure: ∆ − ∆ transformer
Figure: ∆ − ∆ transformer
close the switch close the switch
if primary is Yg if Secondary is Yg
¯
Z0
Primary Secondary
¯
I a
a
¯
I c
c Z̄ g Z̄ g
Ē c Ē a
¯
V a
Ē b
¯
V c
¯
I Z̄ g ¯
b I n
Z̄ n
b
¯
V b
g
¯
I a
a
+ ¯
I c
c Z̄ g Z̄ g
+ -
+
Ē c
- Ē a
¯
V a
Ē b
¯
-
V c
¯
I Z̄ g ¯
b I n
Z̄ n
b
- ¯
V b
+
g
a
+ ¯
I c
c Z̄ g Z̄ g
+ -
+
Ē c
- Ē a
¯
V a
Ē b
¯
-
V c
¯
I Z̄ g ¯
b I n
Z̄ n
b
- ¯
V b
+
g
¯
V̄a Ēa Z̄g + Z̄n Z̄n Z̄n Ia
V̄b = Ēb − Z̄n Z̄g + Z̄n Z̄n I¯b
V̄c Ēc Z̄n Z̄n Z̄g + Z̄n I¯c
Power System Operation and Control ©Ananyo Sengupta 73 / 256
Load Flow Analysis
Short Circuit Analysis Balanced Fault Analysis
Power System Stability Unbalanced Fault Analysis
Economic Dispatch of Generation Z-bus Building Algorithm
Automatic Control of Generation
¯ ¯ ¯
I a I a I a
1 2 0
¯ ¯ ¯ ¯ ¯ ¯
Z1 = Zg Z2 = Zg Zg 3Z n
Ē a ¯ ¯
V a1 V a2 ¯
V a0
¯ ¯ ¯
Z 0 = Z g + 3Z n
M1
G1 T1 T2
M2
Network Data
G1 T1 T2
M1
Network Data
(a) Draw positive, negative and zero sequence network diagram. (b) Reduce the sequence networks to their Thevenin equivalents as viewed
from bus 2. Pre-fault voltage is 1∠0o pu. Pre-fault load current is neglected.
Power System Operation and Control ©Ananyo Sengupta 76 / 256
Load Flow Analysis
Short Circuit Analysis Balanced Fault Analysis
Power System Stability Unbalanced Fault Analysis
Economic Dispatch of Generation Z-bus Building Algorithm
Automatic Control of Generation
phase a
f
¯
I a
Z̄ f
phase b
f
¯
I b
phase c
f
¯
I c
phase a
f
¯
I a
Z̄ f
phase b
f
¯
I b
phase c
f
¯
I c
phase a
f
¯
I a
Z̄ f
phase b
f
¯
I b
phase c
f
¯
I c
I¯af
I¯af1 = I¯af2 = I¯af0 =
3
V̄kf + V̄kf + V̄kf = 3Z̄f I¯af1
a1 a2 a0
Power System Operation and Control ©Ananyo Sengupta 77 / 256
Load Flow Analysis
Short Circuit Analysis Balanced Fault Analysis
Power System Stability Unbalanced Fault Analysis
Economic Dispatch of Generation Z-bus Building Algorithm
Automatic Control of Generation
phase a
f
¯
I ¯
a Z kk
1
0
Z̄ f ¯
V ¯
f
ka
V
ka1
phase b
f
¯
I b f
¯
I
a2
phase c
¯
Z kk
2
f
¯
I ¯
c
f 3Z f
¯
V
ka2
I¯af ¯
V
f
=
3
V̄kf + V̄kf + V̄kf = 3Z̄f I¯af1
a1 a2 a0
Power System Operation and Control ©Ananyo Sengupta 77 / 256
Load Flow Analysis
Short Circuit Analysis Balanced Fault Analysis
Power System Stability Unbalanced Fault Analysis
Economic Dispatch of Generation Z-bus Building Algorithm
Automatic Control of Generation
G1 T1 T2
M1
Network Data
Find fault current, voltages at all three phases of bus 1 and bus 2, and current flow through the three phases of line 1-2 for a LG fault at bus
2. Assume, system was operating at no-load prior to the fault (pre-fault voltage is 1∠0o pu).
Fault voltage at bus k in sequence domain Fault voltage at bus i in sequence domain
Positive seq. voltage: V̄kfa = V̄k0a − Z̄kk1 I¯af Positive seq. voltage: V̄ifa = V̄i0a − Z̄ik1 I¯af
1 1 1 1
Negative seq. voltage: V̄kfa = −Z̄kk2 I¯af Negative seq. voltage: V̄ifa = −Z̄ik2 I¯af
2 2 2 2
Zero seq. voltage: V̄kfa = −Z̄kk0 I¯af Zero seq. voltage: V̄ifa = −Z̄ik0 I¯af
0 0 0 0
Fault voltage at bus k in sequence domain Fault voltage at bus i in sequence domain
Positive seq. voltage: V̄kfa = V̄k0a − Z̄kk1 I¯af Positive seq. voltage: V̄ifa = V̄i0a − Z̄ik1 I¯af
1 1 1 1
Negative seq. voltage: V̄kfa = −Z̄kk2 I¯af Negative seq. voltage: V̄ifa = −Z̄ik2 I¯af
2 2 2 2
Zero seq. voltage: V̄kfa = −Z̄kk0 I¯af Zero seq. voltage: V̄ifa = −Z̄ik0 I¯af
0 0 0 0
Line-to-Line Fault
Bus k
phase a
f
¯
I a
phase b
Z̄ f
f
¯
I b
phase c
f
¯
I c
Line-to-Line Fault
Bus k
phase a
f
¯
I a
phase b
Z̄ f
f
¯
I b
phase c
f
¯
I c
Line-to-Line Fault
Fault condition in sequence domain
Bus k
phase a
I¯af0 = 0
I¯af1 = −I¯af2
f
¯
I a
phase c
f
¯
I c
Line-to-Line Fault
Fault condition in sequence domain
Bus k
phase a
I¯af0 = 0
I¯af1 = −I¯af2
f
¯
I a
phase c ¯ ¯
Z kk Z kk
1 2
f
¯
I 0
c ¯
V ¯
f
¯
f
ka
V V
ka1 ka2
¯
Z kk
Fault condition in phase domain 0
G1 T1 T2
M1
Network Data
Find fault current, voltages at all three phases of bus 1 and bus 2, and current flow through the three phases of line 1-2 for a LL fault at bus 2.
Assume, system was operating at no-load prior to the fault (pre-fault voltage is 1∠0o pu).
f phase a
¯
I a
phase b
f
¯
I b
f
phase c
¯
I c
¯
f ¯f
Z̄ f (I + I c)
b
f phase a
¯
I a
phase b
f
¯
I b
f
phase c
¯
I c
¯
f ¯f
Z̄ f (I + I c)
b
f phase a
Fault condition in sequence domain
¯
I a
f
phase b
V̄kfa = V̄kfa
¯
I 1 2
b
¯
f ¯f
Z̄ f (I + I c)
b
f phase a
Fault condition in sequence domain
¯
I a
f
phase b
V̄kfa = V̄kfa
¯
I 1 2
b
¯
f ¯f f f
Z̄ f (I + I c) ¯
I ¯
I
b
¯ a1 ¯ a0
Z kk 3Z f
1
f
¯
I
a2
ka ka1 ka2 2
ka0
G1 T1 T2
M1
Network Data
Find fault current, voltages at all three phases of bus 1 and bus 2, and current flow through the three phases of line 1-2 for a LLG fault at bus
2. Assume, system was operating at no-load prior to the fault (pre-fault voltage is 1∠0o pu).
2 1
j0.1
j0.25 j0.20
j0.1 j0.1
j1.6
2 1
j0.1
j0.25 j0.20
j0.1 j0.1
j1.6
New Bus 2 1
j0.1
j0.25 j0.20
1 Type 1: z̄b is added from a new bus to the reference bus. j0.1 j0.1
j1.6
Old Bus 2 1
j0.1
New Bus
2 1
j0.1
2 Type 2: z̄b is added from a new bus to an old bus. j0.1 j0.1
Reference
Old Bus
j0.1
Dimension of Z bus matrix increases by one.
2 1
1 Type 1: z̄b is added from a new bus to the reference bus.
j0.1
A new loop is formed and the dimension of Z bus does not change.
j1.6 Old Bus
4 Type 4: z̄b is connected between two old buses.
A new loop is formed and the dimension of Z bus does not change.
2 1
j0.1
j0.25 j0.20
j0.1 j0.1
j1.6
New Bus 2 1
j0.1
j0.25 j0.20
j0.1 j0.1
Reference
3
j1.6
New Bus 2 1
j0.1
¯
I 1
j0.25 j0.20
¯
V ¯
j0.1 j0.1 1 I 3
¯
V 2
Reference
3 Z̄ b
¯
V 3
j1.6
Reference Bus
Z̄ b
¯
V 3
Reference Bus
¯
Z̄ b In general, if a branch with impedance Z̄b is added between a new
V 3
bus k and the reference bus, then,
Reference Bus Z̄ki = Z̄ik = 0 (i = 1, 2, . . . , n; i ̸= k)
Z̄kk = Z̄b
Old Bus 2 1
j0.1
j0.25 j0.20
j0.1 j0.1
j1.6
New Bus
Old Bus 2 1
j0.1
¯
I 1
j0.25 j0.20
¯
I 2
¯
V
j0.1 j0.1 1
Z̄ b
¯
I
¯
V 3
2
3
¯
V 3
j1.6
¯
I 1
V̄3 = V̄2 + Z̄b I¯3
Z̄ b
¯
I
¯
V 3
2
¯
V 3
Reference Bus
¯
I 1
V̄3 = V̄2 + Z̄b I¯3
Z̄ b
¯
¯
V
I 3 In general, if a branch with impedance Z̄b is added between a new
2
Z̄ik = Z̄ij (i = 1, 2, . . . , n; i ̸= k)
Reference Bus
Z̄ki = Z̄ji (i = 1, 2, . . . , n; i ̸= k)
Z̄kk = Z̄b + Z̄jj
2 1
j0.1
j0.25 j0.20
j0.1 j0.1
j1.6
Old Bus
Reference
2 1
j0.1
¯
I 1
j0.25 j0.20
¯
I 2
¯
V
j0.1 j0.1 1
Z̄ b
¯
V 2
3 ¯
I 3
j1.6
Reference
Z̄ b
¯
V 2
¯
I 3
Reference Bus
Z̄ b
Type-3 modification can be derived from Type-2 modification
¯
V 2 taking V̄3 = 0.
¯
I 3
Reference Bus
Z̄ b
Type-3 modification can be derived from Type-2 modification
¯
V 2 taking V̄3 = 0.
¯
I 3
2 1
j0.1 ¯
I 1
j0.25 j0.20 ¯
I
¯
V 2
1 Z̄ b
j0.1 j0.1
¯
I ¯
¯ 3 I 4
V 2
3 ¯ − I
(I ¯ )
¯
V 3 4
3
j1.6
Reference Bus
¯
¯
V
I 2 V̄3 = V̄2 + Z̄b I¯4
1 Z̄ b
¯
I ¯
¯ 3 I 4
V 2
¯ − I
(I ¯ )
¯
V 3 4
3
Reference Bus
¯
¯
V
I 2 V̄3 = V̄2 + Z̄b I¯4
1 Z̄ b
¯
I ¯
¯ 3 I 4
V 2
¯ − I
¯ )
In general, if a branch with impedance Z̄b is added between bus k
¯ (I
V 3
3 4
and bus l, then,
Reference Bus
T
Z̄1k − Z̄1l Z̄k1 − Z̄l1
1
..
..
Znew = Zold −
P . .
A branch with impedance Z̄b is added between Z̄nk − Z̄nl Z̄kn − Z̄ln
two old buses 2 and 3.
where, P = Z̄b + Z̄kk + Z̄ll − Z̄lk − Z̄kl
Module 3
Short Term Short Term Long Term Short Term Long Term
Case Studies
2 7 8 9 3
Large Disturbances
Self-clearing fault
Fault following by opening of line
5 6
Line outage
4
Sudden large change or loss of load
Sudden large change or loss of generation
Outage, followed by islanding
1
Small Disturbances
5 6
Fault bus: 9, Fault initiation time: 1.0 s, Fault removed after: 10 cycles (0.2 s)
1 40
Bus voltage magnitude (in pu)
20
0.6
10
0.4
0
0.2
-10
0
0 5 10 15 20 25 -20
0 5 10 15 20 25
40 Time (in s) 51.5 Time (in s)
30
51
Bus voltage angle (in degree)
50.5
10
0
50
-10
49.5
-20
-30 49
0 5 10 15 20 25 0 5 10 15 20 25
Time (in s) Time (in s)
Power System Operation and Control ©Ananyo Sengupta 97 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
5 6
Fault bus: 9, Fault initiation time: 1.0 s, Fault removed after: 35 cycles (0.7 s)
Power System Operation and Control ©Ananyo Sengupta 98 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
1 2.5
Bus voltage magnitude (in pu)
0.6 1.5
0.4 1
0.2 0.5
0 0
0 5 10 15 20 25 0 5 10 15 20 25
Time (in s) Time (in s)
1000 57
56
500
Bus voltage angle (in degree)
55
52
-500
51
-1000 50
49
-1500 48
0 5 10 15 20 25 0 5 10 15 20 25
Time (in s) Time (in s)
Power System Operation and Control ©Ananyo Sengupta 99 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
5 6
Fault line: 8-9 (near bus 9), Fault initiation time: 1.0 s, Fault removed after: 10 cycles (0.2 s)
Power System Operation and Control ©Ananyo Sengupta 100 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
0.6 20
0.4
0
0.2
0 -20
0 5 10 15 20 25 0 5 10 15 20 25
Time (in s) Time (in s)
60 51.5
Bus voltage angle (in degree)
20 50.5
0 50
-20 49.5
-40 49
0 5 10 15 20 25 0 5 10 15 20 25
Time (in s) Time (in s)
Power System Operation and Control ©Ananyo Sengupta 101 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
5 6
1
10
0.95
5
0.9
0.85 0
0 5 10 15 20 25 0 5 10 15 20 25
Time (in s) Time (in s)
10 51
Bus voltage angle (in degree)
0
50.6
-5
50.4
-10
50.2
-15
-20 50
0 5 10 15 20 25 0 5 10 15 20 25
Time (in s) Time (in s)
Power System Operation and Control ©Ananyo Sengupta 103 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
5 6
1.02 10
1.01
5
1
0.99 0
0 5 10 15 20 25 0 5 10 15 20 25
Time (in s) Time (in s)
10 50.6
Bus voltage angle (in degree)
0 50.3
50.2
-5
50.1
-10 50
0 5 10 15 20 25 0 5 10 15 20 25
Time (in s) Time (in s)
Power System Operation and Control ©Ananyo Sengupta 105 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
5 6
1.02 10
1.01
5
1
0.99 0
0 5 10 15 20 25 0 5 10 15 20 25
Time (in s) Time (in s)
10 50
Bus voltage angle (in degree)
49.6
0
49.4
-5
49.2
-10
49
-15 48.8
0 5 10 15 20 25 0 5 10 15 20 25
Time (in s) Time (in s)
Power System Operation and Control ©Ananyo Sengupta 107 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
5 6
56
52
50
48
0 2 4 6 8 10
Time (in s)
Figure 53: Voltage profile at Vindhyachal indicating the probable operation of LBB protection
Figure: Voltage profile observed at Vindhyachal during fault Rihand STPS on 1st June, 2010
Power System Operation and Control ©Ananyo Sengupta 110 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
SYNCHROPHASORS - INITIATIVE
Automatic Control ofINGeneration
INDIA Dynamics of Multi-Machine Systems JUNE 2012
The graph above shows voltage profile at 400kV Kanpur Bus during tripping of HVDC Rihand-
Dadri
Power System Bipole. and
Operation Some rise and
Control dip in
©Ananyo voltages were observed during tripping of HVDC pole-1 &
Sengupta 111 / 256
from figure that the initial swing in angle is 6 to 7 degrees and the angle settles down to at the
Load Flow Analysis Definition, Examples
same value as the antecedent angle. In this case there is decrease in power due to load loss
Short Circuit Analysis Rotor Angle Stability: Swing Equation
due to which angle Power
should System
decrease but due
Stability to counter action the angle
Small Disturbance settles down near to the
Stability
antecedent value. Dispatch of Generation
Economic Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
Figure 46: Swing observed in angles during multiple trippings at 400 kV Greater Noida
Angle difference between 400 kV buses in Northern Region during loss of load at Greater Noida, 2nd April, 2012
EXHIBIT – 2.1
Disturbance in NEW Grid, India on 30th and 31st July 2012
2.1.1 Map indicating the IR links between NR, WR, ER and NER
Due to power swing distance relays in NR-ER and ER-WR tie lines
tripped resulting isolation of NR.
120000
115000
110000
105000
100000
95000
90000
85000
80000
20:30
20:35
20:40
20:45
20:50
20:55
21:00
21:05
21:10
21:15
21:20
21:25
21:30
21:35
21:40
21:45
21:50
21:55
22:00
Power System Operation and Control ©Ananyo Sengupta POSOCO
115 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
50.3
50.2
50.1
50
49.9
49.8
Frequency within the band 10.86 %
49.7 Frequency above the band 67.05 %
Frequency below the band 22.09 %
49.6
20:29:59.520
20:32:29.520
20:34:59.520
20:37:29.520
20:39:59.520
20:42:29.520
20:44:59.520
20:47:29.520
20:49:59.520
20:52:29.520
20:54:59.520
20:57:29.520
20:59:59.520
21:02:29.520
21:04:59.520
21:07:29.520
21:09:59.520
21:12:29.520
21:14:59.520
21:17:29.520
21:19:59.520
21:22:29.520
21:24:59.520
21:27:29.520
21:29:59.520
21:32:29.520
21:34:59.520
21:37:29.520
21:39:59.520
21:42:29.520
21:44:59.520
21:47:29.520
21:49:59.520
21:52:29.520
21:54:59.520
21:57:29.520
Power System Operation and Control ©Ananyo Sengupta 116 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
Swing Equation
Nomenclature Neglecting frictional and damping torques, from the law rotation, we
have
Tm Mechanical torque (input) d 2 θm
J = Tm − Te
Te Electromagnetic torque (output) dt2
J Combined moment of inertia of prime mover Taking θm = ωsm t + δm ,
and generator d 2 δm d 2 δm
θm Angular displacement of the rotor w.r.t. J 2
= Tm − Te and Jωm = Pm − Pe
dt dt2
stationary ref. axis on stator 2Wk 2Wk
From Wk = 1 2
2 Jωm , we have M = ωm ≈ ωsm
ωsm Synchronous angular velocity
ωm Angular velocity of the rotor d 2 δm
M = P m − Pe
δm Rotor position before disturbance measured dt2
from the synchronously rotating ref. frame p p
Taking δ = 2 δm and ω = 2 ωm
Wk Kinetic energy of the rotating mass
2 d2 δ
M Inertia constant (= Jωm ) M 2 = Pm − Pe
p dt
p No. of poles
δ, ω Electrical power angle and angular velocity
SB Base power
H Per unit inertia constant (= Wk /SB )
Power System Operation and Control ©Ananyo Sengupta 118 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
Swing Equation
Nomenclature Neglecting frictional and damping torques, from the law rotation, we
have
Tm Mechanical torque (input) d 2 θm
J = Tm − Te
Te Electromagnetic torque (output) dt2
J Combined moment of inertia of prime mover Taking θm = ωsm t + δm ,
and generator d 2 δm d 2 δm
θm Angular displacement of the rotor w.r.t. J 2
= Tm − Te and Jωm = Pm − Pe
dt dt2
stationary ref. axis on stator 2Wk 2Wk
From Wk = 1 2
2 Jωm , we have M = ωm ≈ ωsm
ωsm Synchronous angular velocity
ωm Angular velocity of the rotor d 2 δm
M = P m − Pe
δm Rotor position before disturbance measured dt2
from the synchronously rotating ref. frame p p
Taking δ = 2 δm and ω = 2 ωm
Wk Kinetic energy of the rotating mass
2 d2 δ
M Inertia constant (= Jωm ) M 2 = Pm − Pe
p dt
p No. of poles
Expressing all variables in per-unit, and writing in terms of H
δ, ω Electrical power angle and angular velocity
SB Base power H d2 δ
= Pm − Pe
H Per unit inertia constant (= Wk /SB ) πf0 dt2
Power System Operation and Control ©Ananyo Sengupta 119 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
′
jX
d Z̄ L
EV
Pe = sin δ = Pmax sin δ
X12
Infinite Bus
1 3 2
Z̄ s
X12 : Transfer reactance between bus 1 and 2
Pmax : Steady state stability limit
¯ ȳ 12 ¯
I I 2
1
1 2
ȳ 10 ȳ 20
¯ = 1∠0o pu
V
Ē x12 = 0.3 pu
∞
x12 = 0.3 pu
′
x = 0.3 pu xt = 0.2 pu
d
A 50 Hz synchronous machine having inertia constant 8 MJ/MVA and transient reactance x′d = 0.3 pu is connected to an
infinite bus through a purely reactive circuit as shown. Reactances are marked on the diagram on a common system base.
The generator is delivering real power of 1.5 pu, 0.8 power factor lagging to the infinite bus at a voltage V̄ = 1∠0o pu.
1 Calculate the internal emf Ē and the steady state stability limit Pmax .
¯ = 1∠0o pu
V
Ē x12 = 0.3 pu
∞
x12 = 0.3 pu
′
x = 0.3 pu xt = 0.2 pu
d
A 50 Hz synchronous machine having inertia constant 8 MJ/MVA and transient reactance x′d = 0.3 pu is connected to an
infinite bus through a purely reactive circuit as shown. Reactances are marked on the diagram on a common system base.
The generator is delivering real power of 1.5 pu, 0.8 power factor lagging to the infinite bus at a voltage V̄ = 1∠0o pu.
1 Calculate the internal emf Ē and the steady state stability limit Pmax .
2 Assume the per unit damping coefficient D = 0.138. Consider a small disturbance of ∆δ = 10o . Obtain equations
describing the motion of the rotor angle and the generator frequency.
H d2 ∆δ d∆δ
+D + Ps ∆δ = 0
πf0 dt2 dt
2
In terms of the standard second order differential equation ddt∆δ d∆δ 2
2 + 2ζωn dt + ωn ∆δ = 0
q q
πf0 πf0
where, ωn = H
Ps and ζ = D2 HPs
. For normal operating condition ζ < 1, and the roots of the characteristics
equation
are complex s2 + 2ζωn s + ωn
2
=0
p
s1 , s2 = −ζωn ± jωn 1 − ζ 2
p
ωn 1 − ζ 2 = ωd is the damped frequency of oscillation.
For positive damping, roots of the characteristics equation have negative real part if Ps is positive. The response is
bounded and the system is stable.
x1 (t) = δ(t)
d∆δ(t)
x2 (t) = ẋ1 (t) = ∆ω(t) =
dt
d2 ∆δ(t)
ẋ2 (t) = = −ωn
2
x1 (t) − 2ζωn x2 (t)
dt2
In matrix form
ẋ1 (t) 0 1 x1 (t)
= or, ẋ(t) = Ax(t)
ẋ2 (t) −ωn2 −2ζω
n x2 (t)
s + 2ζωn 1
x(0)
−ωn2 s
Taking Laplace transform, we get X(s) = (sI − A)−1 x(0) = .
s2 + 2ζωn s + ωn
2
(s + 2ζωn ) ∆δ0
∆δ(s) =
s2 + 2ζωn s + ωn2
2 ∆δ
ωn 0
∆ω(s) = −
s2 2
+ 2ζωn s + ωn
∆δ0
∆δ(t) = p e−ζωn t sin (ωd t + θ)
1 − ζ2
ωn ∆δ0 −ζωn t
∆ω(t) = − p e sin ωd t
1 − ζ2
∆δ0
δ(t) = δ0 + p e−ζωn t sin (ωd t + θ)
1 − ζ2
ωn ∆δ0 −ζωn t
ω(t) = ω0 − p e sin ωd t
1 − ζ2
¯ = 1∠0o pu
V
Ē x12 = 0.3 pu
∞
x12 = 0.3 pu
′
x = 0.3 pu xt = 0.2 pu
d
A 50 Hz synchronous machine having inertia constant 8 MJ/MVA and transient reactance x′d = 0.3 pu is connected to an
infinite bus through a purely reactive circuit as shown. Reactances are marked on the diagram on a common system base.
The generator is delivering real power of 1.5 pu, 0.8 power factor lagging to the infinite bus at a voltage V̄ = 1∠0o pu.
1 Calculate the internal emf Ē and the steady state stability limit Pmax .
2 Assume the per unit damping coefficient D = 0.138. Consider a small disturbance of ∆δ = 10o . Obtain equations
describing the motion of the rotor angle and the generator frequency.
If the mechanical input power Pm is increased by a small amount ∆P , the the linearized swing equation becomes
H d2 ∆δ d∆δ
+D + Ps ∆δ = ∆P
πf0 dt2 dt
d2 ∆δ
In terms of the standard second order differential equation dt2
+ 2ζωn d∆δ
dt
2 ∆δ = ∆u
+ ωn
q q
πf0 πf0 πf0
where, ωn = H
Ps , ζ = D
2 HPs
and ∆u = ∆P .
H
Simplifying, we obtain
∆u
∆δ(s) =
s (s2 + 2ζωn s + ωn
2)
∆u
∆ω(s) = 2 2
s + 2ζωn s + ωn
πf0 ∆P
∆ω(t) = p e−ζωn t sin ωd t
Hωn 1 − ζ2
1 2
¯ = 1∠0o pu
V
Ē x12 = 0.3 pu
∞
x12 = 0.3 pu
′
x = 0.3 pu xt = 0.2 pu
d
A 50 Hz synchronous machine having inertia constant 8 MJ/MVA and transient reactance x′d = 0.3 pu is connected to an
infinite bus through a purely reactive circuit as shown. Reactances are marked on the diagram on a common system base.
The generator is delivering real power of 1.5 pu, 0.8 power factor lagging to the infinite bus at a voltage V̄ = 1∠0o pu.
Assume the per unit damping coefficient D = 0.138.
1 Obtain equations describing the motion of the rotor angle and the generator frequency for a small change ∆P = 0.1
per-unit.
To ensure stability, relative speed w.r.t. synchronously rotating reference frame has to be zero.
Z δmax
(Pm − Pe ) dδ = 0
δ0
Power System Operation and Control ©Ananyo Sengupta 132 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
1 2
¯ = 1∠0o pu
V
Ē x12 = 0.3 pu
∞
x12 = 0.3 pu
′
x = 0.3 pu xt = 0.2 pu
d
A 50 Hz synchronous machine having inertia constant 8 MJ/MVA and transient reactance x′d = 0.3 pu is connected to an
infinite bus through a purely reactive circuit as shown. Reactances are marked on the diagram on a common system base.
The generator is delivering real power of 1.5 pu, 0.8 power factor lagging to the infinite bus at a voltage V̄ = 1∠0o pu.
1 Determine the maximum power input that can be applied without loss of synchronism.
Ē = E∠δ
Ē = E∠δ
Ē = E∠δ
Ē = E∠δ
Pm
cos δc = (δmax − δ0 ) + cos δmax
Pmax
Ē = E∠δ
Ē ¯ = 1∠0o pu
x12 = 0.3 pu V
∞
x12 = 0.3 pu
xt = 0.2 pu
′
x = 0.3 pu
d
A 50 Hz synchronous machine having inertia constant 8 MJ/MVA and transient reactance x′d = 0.3 pu is connected to an
infinite bus through a purely reactive circuit as shown. Reactances are marked on the diagram on a common system base.
The generator is delivering real power of 1.5 pu, 0.8 power factor lagging to the infinite bus at a voltage V̄ = 1∠0o pu.
1 A temporary three-phase fault occurs at the sending end of the line 1-2. When the fault is cleared, both lines are intact.
Determine the critical clearing angle and the critical fault clearing time.
1 2
Ē = E∠δ
Ē = E∠δ
1 2
¯ = 1∠0o pu
V
Ē x12 = 0.3 pu
∞
x12 = 0.3 pu
′
x = 0.3 pu xt = 0.2 pu
d
A 50 Hz synchronous machine having inertia constant 8 MJ/MVA and transient reactance x′d = 0.3 pu is connected to an
infinite bus through a purely reactive circuit as shown. Reactances are marked on the diagram on a common system base.
The generator is delivering real power of 1.5 pu, 0.8 power factor lagging to the infinite bus at a voltage V̄ = 1∠0o pu.
1 A three-phase fault occurs at the middle of one of the circuits of line 1-2. The fault is cleared by isolating the faulted
line. Determine the critical clearing angle.
¯ = 1∠0o pu
V
Ē x12 = 0.3 pu
∞
x12 = 0.3 pu
′
x = 0.3 pu xt = 0.2 pu
d
3 1 2
0.3
0.5
∞
0.15 0.15
Objective: To obtain
t0 t1 t2 ···
x0 x1 x2 ···
Objective: To obtain
t0 t1 t2 ···
x0 x1 x2 ···
Euler’s Method
dx(t)
x1 ≈ x0 + ∆t
dt t0
Objective: To obtain
t0 t1 t2 ···
x0 x1 x2 ···
Euler’s Method
dx(t)
x1 ≈ x0 + ∆t
dt t0
= x0 + f (x0 )∆t
Objective: To obtain
t0 t1 t2 ···
x0 x1 x2 ···
Euler’s Method
dx(t)
x1 ≈ x0 + ∆t
dt t0
= x0 + f (x0 )∆t
dx(t)
x2 ≈ x1 + ∆t
dt t1
= x1System
Power + f Operation
(x1 )∆t and Control ©Ananyo Sengupta 143 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
Objective: To obtain
t0 t1 t2 ···
x0 x1 x2 ···
Euler’s Method
dx(t)
x1 ≈ x0 + ∆t
dt t0
= x0 + f (x0 )∆t
dx(t)
x2 ≈ x1 + ∆t
dt t1
= x1System
Power + f Operation
(x1 )∆t and Control ©Ananyo Sengupta 143 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
Objective: To obtain
t0 t1 t2 ···
x0 x1 x2 ···
Euler’s Method
dx(t)
x1 ≈ x0 + ∆t
dt t0
= x0 + f (x0 )∆t In general
dx(t) dx(t)
x2 ≈ x1 + xk+1 ≈ xk + .∆t
dt t
∆t
dt t1 k
= x1System
Power + f Operation
(x1 )∆t and Control ©Ananyo Sengupta 144 / 256
Load Flow Analysis Definition, Examples
Short Circuit Analysis Rotor Angle Stability: Swing Equation
Power System Stability Small Disturbance Stability
Economic Dispatch of Generation Large Disturbance Stability or Transient Stability
Automatic Control of Generation Dynamics of Multi-Machine Systems
dx(t) p
= f (xk+1 )
dt t
k+1
dx(t) p
= f (xk+1 )
dt t
k+1
!
1 dx(t) dx(t)
xk+1 ≈ xk + + ∆t
2 dt t dt t
k k+1
d2 δ πf0
= (Pm − Pmax sin δ)
dt2 H
d2 δ πf0
= (Pm − Pmax sin δ)
dt2 H
d2 δ πf0
= (Pm − Pmax sin δ)
dt2 H
d2 δ πf0
= (Pm − Pmax sin δ)
dt2 H
d2 δ πf0
= (Pm − Pmax sin δ)
dt2 H
1 2
¯ = 1∠0o pu
V
Ē x12 = 0.3 pu
∞
x12 = 0.3 pu
′
x = 0.3 pu xt = 0.2 pu
d
A 50 Hz synchronous machine having inertia constant 8 MJ/MVA and transient reactance x′d = 0.3 pu is connected to an
infinite bus through a purely reactive circuit as shown. Reactances are marked on the diagram on a common system base.
The generator is delivering real power of 1.5 pu, 0.8 power factor lagging to the infinite bus at a voltage V̄ = 1∠0o pu.
A three-phase fault occurs at the middle of one of the circuits of line 1-2 at 0.1s. The fault is cleared at 0.2s by isolating the
faulted line. Obtain the numerical solution of the swing equation for 1.0 s using modified Euler’s method with a step size
of ∆t = 0.01 s.
55
50
45
(in degree)
40
35
30
Fault initiated
25
Fault removed
20
15
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
Time (in s)
H = 8 MJ/MVA, , D = 0, Pm = 1.5 pu, Pmax1 = 3.0568 pu, Pmax2 = 1.1038 pu, Pmax3 = 2.4837 pu, δ0 = 0.5129 rad = 29.3872o
45
(in degree)
40
35 Fault removed
30
Fault initiated
25
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
Time (in s)
H = 8 MJ/MVA, , D = 0.138, Pm = 1.5 pu, Pmax1 = 3.0568 pu, Pmax2 = 1.1038 pu, Pmax3 = 2.4837 pu, δ0 = 0.5129 rad = 29.3872o
ȳ g
3 Loads are represented by constant impedances.
k
ȳ d
m
k
4 Mechanical rotor angle of a machine coincides with the
n + ng
angle of the voltage behind transient reactance.
n-bus power system
′ ′
i l
x = 0.05 x = 0.05
d d
ȳ g ȳ d
j l 1 3
j
z̄ 13 = j0.10
n+2
ȳ g
k z̄ 12 = 0.12 + j0.16 z̄ 23 = 0.12 + j0.16
ȳ d
m
k
n + ng
n-bus power system
Pre-disturbance voltage:
V̄10 = 1.0∠0o pu,
V̄20 = 0.98∠ − 5o pu,
V̄30 = 1.02∠2o pu.
i l
ȳ g ȳ d 4 5
′ ′
j l x = 0.05 x = 0.05
d d
1 3
n+2
m z̄ 13 = j0.10
ȳ g
k
ȳ d
m
k
ȳ d
2
0 Ȳnn Ȳnm V̄
i l
=
I¯g Ȳmn Ȳmm Ē
ȳ g ȳ d
j l
m
0 = Ȳnn V̄ + Ȳnm Ē
−1
ȳ g
k
V̄ = −Ȳnn Ȳnm Ē
ȳ d
m
k
!
1 dδi dδi
δi (tk+1 ) = δi (tk ) + + .∆t
2 dt t dt t
k k+1
!
1 d∆ωi d∆ωi
∆ωi (tk+1 ) = ∆ωi (tk ) + + .∆t
2 dt t dt t
k k+1
Correct
Dynamics of Multi- δ, Δω
Find first Machine System for next time
slope: predict
instant
δ, Δω
Find second
slope
Solve network
equation, find
p p
¯
I , Pe
g
z̄ 13 = j0.10
Inertia Constant
H1 = 8 MJ/MVA
H2 = 6 MJ/MVA
z̄ 12 = 0.12 + j0.16 z̄ 23 = 0.12 + j0.16
Module 4
Problem Formulation
100 M W ≤ Pg ≤ 400 M W 100 M W ≤ Pg ≤ 400 M W
1 2
z̄ 13 = 0.12 + j0.16 z̄ 23 = 0.15 + j0.22 Under normal operating conditions, generation capacity is more
than total load and losses.
Evening Peak
1 2
z̄ 12 = j0.10
Morning Peak
GW->
z̄ 13 = 0.12 + j0.16 z̄ 23 = 0.15 + j0.22 Day Lean
Night Lean
3
Problem Formulation
100 M W ≤ Pg ≤ 400 M W 100 M W ≤ Pg ≤ 400 M W
1 2
Objective of economic dispatch problem is to find an optimal
combination of generations by minimizing the total cost of
generating real power (production cost) while satisfying the loads
and losses in a system.
1 2
z̄ 12 = j0.10
500 M W
Problem Formulation
100 M W ≤ Pg ≤ 400 M W 100 M W ≤ Pg ≤ 400 M W
1 2
Objective of economic dispatch problem is to find an optimal
combination of generations by minimizing the total cost of
generating real power (production cost) while satisfying the loads
and losses in a system.
1 2
z̄ 12 = j0.10
or,
3
500 M W
min max
P g1 = 100 MW, P g2 = 400 MW ? OR, Pg Pg
i i
Problem Formulation
100 M W ≤ Pg
1
≤ 400 M W 100 M W ≤ Pg
2
≤ 400 M W Economic Dispatch Problem
X
ng ng
X
2
minimize F i P gi = a i Pg + bi Pg i + c i
P̄g i
i=1 i=1
1 2
z̄ 12 = j0.10
Subject to:
X
ng
Pgi = PD + PL
i=1
min max
z̄ 13 = 0.12 + j0.16 z̄ 23 = 0.15 + j0.22 Pg ≤ Pg i ≤ Pg i = 1, 2, . . . , ng
i i
Vector
Real valued vector x̄ ∈ Rn
x1
x2
x3
x̄ =
.. , where xi ∈ R, i = 1, 2, . . . , n
. x2
xn
0
x1
Vector Norm
1
P
n p
Lp norm of a vector x̄ ∈ Rn : ||x̄||p = |x|pi where p ∈ R+
i=1
Vector
Real valued vector x̄ ∈ Rn
x1
x2
x3
x̄ =
.. , where xi ∈ R, i = 1, 2, . . . , n
. x2
xn
0
x1
Vector Norm
1
P
n p
Lp norm of a vector x̄ ∈ Rn : ||x̄||p = |x|pi where p ∈ R+
i=1
Vector
Real valued vector x̄ ∈ Rn
x1
x2
x3
x̄ =
.. , where xi ∈ R, i = 1, 2, . . . , n
. x2
xn
0
x1
Vector Norm
1
P
n p
Lp norm of a vector x̄ ∈ Rn : ||x̄||p = |x|pi where p ∈ R+
i=1
" #
2 (x1 − 1)
∇x̄ f (x̄) =
2x2
" #
2 (x1 − 1)
∇x̄ f (x̄) = f (x̄ + ∆x̄) ≈ f (x̄) + (∆x̄)T ∇f (x̄)
2x2
60
First order Taylor Series expansion
50
f(x)
30
10
f(x)
−2 2
Check Taylor Series at x̄ = , ∆x̄ = h̄ = . (x+h)
0 0 0 f(x+h)
5
x h 4
0 2
0
x2 -5 -4
-2 x1
Unconstrained Optimization
60 2.5
Problem Statement
50
minimize f (x̄) where f : Rn → R 2
x̄
40
Alternative form 1.5
f(x)
f(x)
30
0.5
10
f is called the objective function (or cost function) and 0 0
x̄∗ is the minimizer. 5 5
5
0
x2 0 x1 x2
-5 -5
1
Suppose f (x̄) = (x1 − 1)2 + x22 + 10. From observation, f (x̄) is minimum at x̄∗ = .
0
Power System Operation and Control ©Ananyo Sengupta 165 / 256
Load Flow Analysis
Problem Formulation
Short Circuit Analysis
Mathematical Background: Optimization Technique
Power System Stability
Economic Dispatch Neglecting Losses
Economic Dispatch of Generation
Economic Dispatch Including Losses
Automatic Control of Generation
Local Minimizer
x̄∗ is a local minimizer for f : Rn → R if for all x̄ ∈ Rn and ||x̄ − x̄∗ || ≤ ϵ, (ϵ ≈ 0)
f (x̄∗ ) ≤ f (x̄)
Local Minimizer
x̄∗ is a local minimizer for f : Rn → R if for all x̄ ∈ Rn and ||x̄ − x̄∗ || ≤ ϵ, (ϵ ≈ 0)
f (x̄∗ ) ≤ f (x̄)
2
f(x)
-1
-1 0 1 2 3
x
Power System Operation and Control ©Ananyo Sengupta 166 / 256
Load Flow Analysis
Problem Formulation
Short Circuit Analysis
Mathematical Background: Optimization Technique
Power System Stability
Economic Dispatch Neglecting Losses
Economic Dispatch of Generation
Economic Dispatch Including Losses
Automatic Control of Generation
Local Minimizer
x̄∗ is a local minimizer for f : Rn → R if for all x̄ ∈ Rn and ||x̄ − x̄∗ || ≤ ϵ, (ϵ ≈ 0)
f (x̄∗ ) ≤ f (x̄)
4
4
60
3 50
3
40
2
2
f(x)
30
f(x)
f(x)
1 20
1
10
0 0
0
x* 5
5
0
-1 -1 0
-1 0 1 -1 2 03 1 2 3 -5 -5
x2 x1
Power System Operation and Control ©Ananyo x
x Sengupta 166 / 256
Load Flow Analysis
Problem Formulation
Short Circuit Analysis
Mathematical Background: Optimization Technique
Power System Stability
Economic Dispatch Neglecting Losses
Economic Dispatch of Generation
Economic Dispatch Including Losses
Automatic Control of Generation
Proof: Suppose x̄∗ is the local minima and ∆x̄ ∈ Rn is an arbitrary vector such as ||x̄ − x̄∗ || ≤ ϵ, (ϵ ≈ 0). Now,
Since ∆x̄ is an arbitrary vector, (∆x̄)T ∇f (x̄) can take any sign. To ensure f (x̄∗ ) ≤ f (x̄∗ + ∆x̄), ∇f (x̄) has to be zero at
x̄∗ .
Proof: Suppose x̄∗ is the local minima and ∆x̄ ∈ Rn is an arbitrary vector such as ||x̄ − x̄∗ || ≤ ϵ, (ϵ ≈ 0). Now,
Since ∆x̄ is an arbitrary vector, (∆x̄)T ∇f (x̄) can take any sign. To ensure f (x̄∗ ) ≤ f (x̄∗ + ∆x̄), ∇f (x̄) has to be zero at
x̄∗ .
Proof: Suppose x̄∗ is the local minima and ∆x̄ ∈ Rn is an arbitrary vector such as ||x̄ − x̄∗ || ≤ ϵ, (ϵ ≈ 0). Now,
Since ∆x̄ is an arbitrary vector, (∆x̄)T ∇f (x̄) can take any sign. To ensure f (x̄∗ ) ≤ f (x̄∗ + ∆x̄), ∇f (x̄) has to be zero at
x̄∗ .
subject to : h(x̄) : x1 + 3 − x2 = 0
80
70
60
50
f(x)
40
30
20
10
0
12 10 8 12 14
6 8 10
4 2 6
0 2 4
x2 x1
subject to : h(x̄) : x1 + 3 − x2 = 0
80
70
60
50
f(x)
40
30
20
10 15
10
0
5
18 16 14 12 10 8 6 4 0
2 0
x1
x2
subject to : h(x̄) : x1 + 3 − x2 = 0
80
70
60
50
f(x)
40
30
20
10 15
10
0
5
18 16 14 12 10 8 6 4 0
2 0
x1
x2
subject to : h(x̄) : x1 + 3 − x2 = 0
80
70
60
50
40
f(x)
30
20
10
0
15
10
5
4 2 0
10 8 6
0 16 14 12
x1 18
x2
subject to : h1 (x̄) = 0
h2 (x̄) = 0
.
.
.
hp (x̄) = 0
The method of Lagrange multiplier converts this problem to the following unconstrained
Xp optimization problem as
minimize L(x̄, λ̄) = f (x̄) + λi hi (x̄)
x̄,λ̄
i=1
The unconstrained function L(x̄, λ̄) is called Lagrangian function, and λ̄ = [λ1 , λ1 , · · · , λp ]T is called Lagrangian multiplier which
is unspecified and can take any value.
subject to : h(x̄) : x1 + 3 − x2 = 0
80
70
60
50
f(x)
40
30
20
10
0
15
10
5 0
8 6 4 2
0 16 14 12 10
18
x1
x2
X
ng ng
X h iT
2
minimize F i Pg i = a i P g + b i Pg i + c i where, P̄g = Pg1 , Pg2 , . . . , Pgng
P̄g i
i=1 i=1
X
ng
subject to : Pg i = PD
i=1
X
ng ng
X h iT
2
minimize F i Pg i = a i P g + b i Pg i + c i where, P̄g = Pg1 , Pg2 , . . . , Pgng
P̄g i
i=1 i=1
X
ng
subject to : Pg i = PD
i=1
ng
P P
ng
Lagrangian function: L(P̄g , λ) = ai Pg2 + bi Pgi + ci +λ PD − Pg i
i
i=1 i=1
At optimal point
∂L
= 0, (i = 1, 2, . . . , ng)
∂Pgi
∂L
= 0
∂λ
ng
P P
ng
Lagrangian function: L(P̄g , λ) = ai Pg2 + bi Pgi + ci +λ PD − Pg i
i
i=1 i=1
At optimal point ∂L
= 2ai Pgi + bi − λ = 0, (i = 1, 2, . . . , ng) (1)
∂Pgi
!
∂L Xng
= PD − Pg i = 0 (2)
∂λ i=1
P
ng λ − b
i
Replacing Pgi in (2), PD − =0
i=1 2ai
P
ng b
i
PD +
i=1 2ai λ∗ − bi
Simplifying above equations, optimal solution can be found as: λ∗ = , Pg∗ = , (i = 1, 2, . . . , ng)
P
ng 1 i 2ai
i=1 2a i
Power System Operation and Control ©Ananyo Sengupta 176 / 256
Load Flow Analysis
Problem Formulation
Short Circuit Analysis
Mathematical Background: Optimization Technique
Power System Stability
Economic Dispatch Neglecting Losses
Economic Dispatch of Generation
Economic Dispatch Including Losses
Automatic Control of Generation
)h W M/sR( C I
IC of Generator-1
∗
λ
IC of Generator-2
∗ ∗
Pg Pg
1 2
Pg
Example
The fuel-cost functions for three thermal plants in Rs/h are given by
where Pg1 , Pg2 , and Pg3 are in MW. The total load, PD , is 800 MW. Neglecting losses and generator limits, find the
optimal dispatch and the total cost in Rs/h by analytical approach.
λ is updates as
Starting with an initial lambda (λk ), we wish to to find
λk+1 = λk + ∆λk
appropriate ∆λk that will satisfy the above equation.
until the mismatch
Expanding f (λ) around λk , we can write
|PD − f (λk )| ≤ ϵ
∂f
f (λk ) + ∆λk = PD P
ng
∂λ λ which indicates PD ≈ Pg i .
k
i=1
PD − f (λk )
or, ∆λk =
∂f
∂λ
λk
Example
The fuel-cost functions for three thermal plants in Rs/h are given by
where Pg1 , Pg2 , and Pg3 are in MW. The total load, PD , is 800 MW. Neglecting losses and generator limits, find the
optimal dispatch and the total cost in Rs/h using lambda iteration technique. Assume initial value of λ = 6.0 Rs/MWh.
X
ng ng
X h iT
2
minimize F i Pg i = a i P g + b i Pg i + c i where, P̄g = Pg1 , Pg2 , . . . , Pgng
P̄g i
i=1 i=1
X
ng
subject to : Pg i = PD
i=1
min max
Pg ≤ Pg i ≤ P g i = 1, 2, . . . , ng
i i
Update lambda as
∆P
∆λk = , λk+1 = λk + ∆λk
∂f
∂λ
λk
∂f X 1
where, =
∂λ λ ∀i,i∈I
2ai
k
The fuel-cost functions for three thermal plants in Rs/h are given by
where Pg1 , Pg2 , and Pg3 are in MW. Find the optimal dispatch and the total cost in Rs/h when the total load, PD , is 950
MW with the following generator limits (in MW).
X
ng
subject to : Pg i = PD + P L
i=1
min max
Pg ≤ Pg i ≤ P g i = 1, 2, . . . , ng
i i
X
ng X
ng
where, PL = Pgi Bij Pgj (George’s Loss Formula)
i=1 j=1
X
ng X
ng X
ng
or, PL = Pgi Bij Pgj + B0i Pgi + B00 (Kron’s Loss Formula)
i=1 j=1 j=1
Rearranging
X
ng
ai 1 B0i bi
+ Bii Pg i + Bij Pgj = − − , i = 1, 2, . . . , ng (4)
λ j=1,j̸=i
2 2 2λ
a1 Pg 1 − B01 −
b1
+ B11 B12 ··· B1ng 1 λ
λ
a2 P
1 − B02 −
b2
B21 + B22 ··· B2ng g 2
λ
λ
1
=
. (5)
2
. . .. . . .
. . . . .
. . . . .
Pg
ang bng
Bng1 Bng2 ··· λ + Bngng ng 1 − B0ng − λ
P
ng
λ (1 − B0i ) − bi − 2λ Bij Pgj
j=1,j̸=i
P gi = , i = 1, 2, . . . , ng (6)
2 (λBii + ai )
The fuel-cost functions for two thermal plants in Rs/h are given by
where Pg1 and Pg2 are in MW. Total loss of the network can be found from B-coefficients
8.3831 −0.0494 0.3750
Bij = × 10−3 , B0i = × 10−3 , B00 = 0.0901 × 10−3
−0.0494 5.9635 0.1949
if generations are expressed in per-unit (100 MVA base). The total load, PD , is 500 MW. Ignoring generator limits, find the
optimal dispatch and the total cost in Rs/h.
Module 5
Previous module (economic dispatch of generation) dealt with the optimal scheduling of generation for forecasted steady load.
However, both active and reactive power demands are never steady and continuously change over time.
Mismatch between demand and mechanical input is always compensated through change in electrical power output of a generator at
the expense of machine’s kinetic energy, resulting fluctuation of frequency.
Steam input to turbo-generator (or water input to hydro-generator) must, therefore, be continuously regulated to match the active
power demand.
To automatically control speed of synchronous generator (and therefore frequency), a device must sense either speed or frequency in
such a way that comparison with a desired value can be used to create an error signal to take corrective action.
A fly ball speed sensor with ideal linkage to a hydraulic amplifier and piston for turbine valve opening control is such a device that
regulates mechanical input of the machine sensing frequency of the system.
l1 : length of AB
l2 : length of BC
l3 : length of CD
l4 : length of DE
Hydraulic Amplifier
Speed Changer
The position of the pilot valve can be affected via linkage system in
three ways:
This excess power will cause an increase in generator speed and hence in
frequency.
This will increase the velocity of fly ball and hence lower point B.
Lowering point C must either lower D (if E does not change) or raise E (if D
does not change).
If point D is lowered, high pressure fluid will enter the hydraulic amplifier
through the lower channel and exert a force on the main piston to move
up point E.
Decrease in steam input will eventually stop the increase in speed that
initiated the movement of point B.
Power System Operation and Control ©Ananyo Sengupta 197 / 256
Load Flow Analysis
Automatic Load Frequency Control
Short Circuit Analysis
Grid Management in India
Power System Stability
Scheduling and Dispatch Procedure
Economic Dispatch of Generation
Availability Based Tariff (ABT)
Automatic Control of Generation
The movement ∆yD depending upon its sign opens one of the
channels of the pilot valve admitting high pressure oil into the cylinder
thereby moving the main piston and opening the steam valve.
Assumptions
1 Inertial reaction forces of main piston and steam valve are negligible
compared to the forces exerted on the piston by high pressure oil.
The volume of oil admitted to the cylinder is, thus, proportional to the
time integral of ∆yD .
The movement ∆yE is obtained by dividing the oil volume by the area
of the cross-section of the piston.
Z
∆yE (t) = k5 (−∆yD (t))dt
+
Eliminating ∆YC (s) and ∆YD (s), we can write Ksg
ΔPC (s) ΔYE (s)
1 + Tsg s
−
Change in speed Change in turbine
k1 k3 kC ∆PC (s) − k2 k3 ∆F (s) changer setting Speed Governor valve position
∆YE (s) = Transfer Function
s 1
k4 + R
k5 Speed Regulation Change in
frequency
1 Ksg
= ∆PC (s) − ∆F (s) × ΔF (s)
R 1 + Tsg s
Block diagram representation
Turbine Model
Output power of turbine changes due to change in valve opening ∆YE
HP LP
Stage Stage
Kt
Steam Valve ΔYE (s) ΔPt (s)
1 + Tt s
Change in turbine Change in
valve position Turbine turbine output
Reheater Transfer Function
By connecting additional load to the system the load demand increases by ∆PD . The generator will immediately increases its output
∆PG to match the new load, i.e., ∆PG = ∆PD .
There will be now an imbalance between input and output power, ∆Pt − ∆PD . This mismatch will be accounted for in two ways.
1 Kinetic energy of the generator rotor will decrease resulting change in speed or frequency.
As the kinetic energy is proportional to the square of the speed, new kinetic energy of the rotor will be
!2
0 f 0 + ∆f 0 2∆f
Wke = Wke ≈ Wke 1 +
f0 f0
2 Most of the practical power system loads are frequency dependent in nature. Thus, if the frequency changes, load will also vary to
some extend.
∂PD
Let the frequency dependency of load be expressed as: D = , i.e., ∆PD = D∆f .
∂f
d 2H
∆Pt − ∆PD = (Wke ) + D∆f ∆Pt (s) − ∆PD (s) = s∆F (s) + D∆F (s)
dt f0
0
2Wke d Kps
= (∆f ) + D∆f or, ∆F (s) = [∆Pt (s) − ∆PD (s)] ×
f 0 dt 1 + sTps
1
Dividing by the generator rating Pr , we get Kps = (power system gain, Hz/pu MW)
D
0
2Wke d D 2H
∆Pt(pu) − ∆PD(pu) = (∆f ) + ∆f Tps = (time constant of power system)
0
f Pr dt Pr Df 0
2H d ΔPD (s)
= (∆f ) + D(pu) ∆f
f 0 dt Change in load
−
+ Kps
ΔPt (s) ΔF (s)
H: inertia constant (unit: MW.s/MW or s) 1 + Tps s
Change in load
ΔPD (s)
Change in turbine Change in
Change in speed valve position turbine output
changer setting
ΔYE (s) −
+ ΔPt (s)
Ksg Kt + Kps
ΔPC (s) ΔF (s)
1 + Tsg s 1 + Tt s 1 + Tps s
−
Change in
Speed Governor Turbine frequency
Power System
Transfer Function Transfer Function
Transfer Function
Speed Regulation
The theory discussed so far assumes a single generator feeding power to an isolated load which is a rare situation.
For a practical system with number of generating stations and load, it is possible to divide an extended power system (say, national
grid) into subareas (e.g. State Electricity Boards) in which all generator in a region are tightly coupled together so as to form a
coherent group, i.e. all the generators respond in unison to change in load or speed changer settings.
Such a coherent area is called a control area in which the frequency is assumed to be same throughout in static as well as dynamic
conditions.
For purposes of developing a suitable control strategy, a control area can be modeled as an equivalent single generator load system.
Assume that the load-frequency dependency is linear, meaning the the load would increase one percent for one percent frequency increase.
Assume that the load-frequency dependency is linear, meaning the the load would increase one percent for one percent frequency increase.
∂PD 10 20
D= = = 20 MW/Hz = = 0.01 pu MW/Hz.
∂f 0.50 2000
2×5
Tps = = 20s
50 × 0.01
1
Kps = = 100 Hz/pu MW
0.01
The generator power increment ∆PG depends entirely upon the changes ∆PD in the load being fed from the generator. Generator
always adjusts its output to meet the change in demand ∆PD . These adjustments are essentially instantaneous, certainly in
comparison with the slow changes in PT , and therefore, ∆PG = ∆PD .
An increase in ∆Pt results from an increase in ∆PC and a decrease in ∆f . Therefore, for small increments
1
∆Pt = ∆PC − ∆f
R
The generator power increment ∆PG depends entirely upon the changes ∆PD in the load being fed from the generator. Generator
always adjusts its output to meet the change in demand ∆PD . These adjustments are essentially instantaneous, certainly in
comparison with the slow changes in PT , and therefore, ∆PG = ∆PD .
An increase in ∆Pt results from an increase in ∆PC and a decrease in ∆f . Therefore, for small increments
1
∆Pt = ∆PC − ∆f
R
Example 2: Consider a 100 MW generator with a regulation parameter R of four percent (i.e. 0.04 pu). By how much will the turbine power
increase if the frequency drops by 0.1 Hz with the reference unchanged?
The generator power increment ∆PG depends entirely upon the changes ∆PD in the load being fed from the generator. Generator
always adjusts its output to meet the change in demand ∆PD . These adjustments are essentially instantaneous, certainly in
comparison with the slow changes in PT , and therefore, ∆PG = ∆PD .
An increase in ∆Pt results from an increase in ∆PC and a decrease in ∆f . Therefore, for small increments
1
∆Pt = ∆PC − ∆f
R
Example 2: Consider a 100 MW generator with a regulation parameter R of four percent (i.e. 0.04 pu). By how much will the turbine power
increase if the frequency drops by 0.1 Hz with the reference unchanged?
A 0.04 pu regulation parameter means that the turbine power will increase 1 pu, or 100 MW for a 0.04 pu, or 2 Hz drop in frequency
∆f
in general, R = − .
∆Pt
Therefore, for a frequency change of 0.1 Hz, i.e. 0.002 pu, turbine power will thus experience a static change of
1
∆Pt = − (−0.002) = 0.05 pu = 5 MW
0.04
Suppose speed changer has a fixed settings (∆PC = 0) and load demand changes. This is known as free governing operation.
For such an operation, the steady state change in system frequency for a sudden change in load demand by an amount ∆PD , i.e.
∆P
∆PD (s) = sD is obtained as follows:
− Kps
ΔPD (s) ΔF (s)
1 + Tps s
+
Kt Ksg 1
−
1 + Tt s 1 + Tsg s R
Kt Ksg 1
−
1 + Tt s 1 + Tsg s R
Kps ∆PD
∆F (s)|∆P = − ×
C (s)=0 Ksg Kt Kps /R s
(1 + sTps ) + (1+sTsg )(1+sTt )
Kps
∆f (t)|t→∞ = lim s ∆F (s)|∆P = ∆PD
s→0 C (s)=0 1 + (Ksg Kt Kps /R)
While Kt and Kps are fixed, Ksg can be easily adjusted by changing the length of various links of a speed governor system. Thus,
assuming Ksg is so adjusted that Ksg Kt ≈ 1 and replacing Kps = (1/D), we get
1
∆f (t)|t→∞ = − ∆PD
D + (1/R)
Power System Operation and Control ©Ananyo Sengupta 211 / 256
Load Flow Analysis
Automatic Load Frequency Control
Short Circuit Analysis
Grid Management in India
Power System Stability
Scheduling and Dispatch Procedure
Economic Dispatch of Generation
Availability Based Tariff (ABT)
Automatic Control of Generation
+
Ksg Kt Kps
ΔPC (s) ΔF (s)
1 + Tsg s 1 + Tt s 1 + Tps s
−
Ksg Kt Kps ∆PC
∆F (s)|∆P = ×
D (s)=0 (1 + sTsg )(1 + sTt )(1 + sTps ) + Ksg Kt Kps /R s
Ksg Kt Kps
∆f (t)|t→∞ = lim s ∆F (s)|∆P (s)=0 = ∆PC
s→0 D 1 + (Ksg Kt Kps /R)
1
= ∆PC , taking Ksg Kt ≈ 1
D + (1/R)
Power System Operation and Control ©Ananyo Sengupta 212 / 256
Load Flow Analysis
Automatic Load Frequency Control
Short Circuit Analysis
Grid Management in India
Power System Stability
Scheduling and Dispatch Procedure
Economic Dispatch of Generation
Availability Based Tariff (ABT)
Automatic Control of Generation
ΔPD (s)
Change in turbine Change in
Change in speed valve position turbine output
changer setting
ΔYE (s) −
+ ΔPt (s)
Ksg Kt + Kps
ΔPC (s) ΔF (s)
1 + Tsg s 1 + Tt s 1 + Tps s
−
Change in
Speed Governor Turbine frequency
Power System
Transfer Function Transfer Function
Transfer Function
Speed Regulation
If the speed changer setting is changed by ∆PC while the load changes by ∆PD , the steady state frequency change can be obtained by
PRIMARY ALFC LOOP
superposition, as
1
∆f (t)|t→∞ = (∆PC − ∆PD )
D + (1/R)
Power System Operation and Control ©Ananyo Sengupta 213 / 256
Load Flow Analysis
Automatic Load Frequency Control
Short Circuit Analysis
Grid Management in India
Power System Stability
Scheduling and Dispatch Procedure
Economic Dispatch of Generation
Availability Based Tariff (ABT)
Automatic Control of Generation
Typical values of the times constants of load frequency control system are related as
Tsg < Tt ≪ Tps
Letting Tsg = Tt = 0 and Ksg Kt ≈ 1, ALFC block diagram can be reduced to:
ΔPD (s)
−
+ ΔPt (s)
+ Kps
ΔPC (s) 1 ΔF (s)
1 + Tps s
−
−
+ ΔPt (s)
+ Kps
ΔPC (s) 1 ΔF (s)
1 + Tps s
−
Kps ∆PD Kps /Tps
∆F (s)|∆P = − × =− × ∆PD
C (s)=0 (1 + Kps /R) + sTps s R+Kps
s s + RTps
(
R+Kps
)
RKps − t
∆f (t) = − 1−e Tps R
∆PD
R + Kps
-0.005
First order approximation
-0.01
-0.015
Exact response
-0.02
f (Hz)
-0.025
-0.03
-0.035
-0.04
-0.045
-0.05
0 2 4 6 8 10 12 14
Time (s)
−1.7167t
∆PD = 0.01 pu, ∆f (t) = −0.029 1 − e Hz
Power System Operation and Control ©Ananyo Sengupta 216 / 256
Load Flow Analysis
Automatic Load Frequency Control
Short Circuit Analysis
Grid Management in India
Power System Stability
Scheduling and Dispatch Procedure
Economic Dispatch of Generation
Availability Based Tariff (ABT)
Automatic Control of Generation
ΔPD (s)
ΔYE (s) −
+ ΔPt (s) x1
Ksg Kt + Kps
ΔPC (s) ΔF (s)
1 + Tsg s 1 + Tt s 1 + Tps s
− x3 x2
Speed Regulation
Kps
− T1ps
Kps
0
0 − Tps
ẋ1 (t) x1 (t)
Tps
∆PC (t)
x2 (t) 0 0
ẋ2 (t) =
Kt
0 − T1
+
t Tt
∆P (t)
Ksg D
ẋ3 (t) Ksg
− RTsg 0 − T1sg x3 (t) Tsg 0
-0.04
0 2 4 6 8 10 12 14
Time (s)
0.02
Y e (pu)
0.01
0
0 2 4 6 8 10 12 14
Time (s)
0.02
P t (pu)
0.01
0
0 2 4 6 8 10 12 14
Time (s)
Power System Operation and Control ©Ananyo Sengupta 218 / 256
Load Flow Analysis
Automatic Load Frequency Control
Short Circuit Analysis
Grid Management in India
Power System Stability
Scheduling and Dispatch Procedure
Economic Dispatch of Generation
Availability Based Tariff (ABT)
Automatic Control of Generation
-0.1
-0.3
-0.4
f (Hz)
-0.5
-0.6
-0.7
without ALFC
-0.8
-0.9
-1
0 50 100 150
Time (s)
Since load change is an external stochastic event, steady state frequency error can not be nullified using above condition. It leads to
the natural suggestion that the speed changer setting be adjusted automatically by monitoring frequency changes.
This can be achieved by feeding ∆f (t) through an integrator to the speed changer to make zero steady state error.
Z
∆PC (t) = −Ki ∆f (t)dt
Negative polarity must be chosen for the integrator to cause a positive frequency error to give rise to a negative or decrease
command.
The signal (∆f ) fed to into the integrator is referred to as Area Control Error (ACE).
As long as an error remains, the integrator output will increase, causing speed changer to move. The integrator output, and thus
the speed-changer position, attains a constant value only when the frequency error has been reduced to zero.
Kps ∆PD
∆F (s) = − Kps Ksg Kt
×
Ki s
(1 + sTps ) + 1
R + s × (1+sTsg )(1+sTt )
Hence,
Power ∆f (t)|t→∞
System Operation = lim
and Control s∆F
©Ananyo (s) =
Sengupta 0 222 / 256
Load Flow Analysis
Automatic Load Frequency Control
Short Circuit Analysis
Grid Management in India
Power System Stability
Scheduling and Dispatch Procedure
Economic Dispatch of Generation
Availability Based Tariff (ABT)
Automatic Control of Generation
−
Ki ΔPC (s) Ksg ΔYE (s) ΔPt (s) Kps ΔF (s)
Kt +
−
s + 1 + sTsg 1 + sTt 1 + sTps
x4 x3 x1
− x2
ps K Kps
ẋ1 (t) − 1 0 0 x1 (t) − Tps
Tps Tps
ẋ2 (t) 0 x2 (t) 0
K
0 − T1 t
Tt
=
t
K + ∆PD (t)
ẋ (t) − sg Ksg x (t)
3 RTsg 0 − T1sg 0
Tsg
3
ẋ4 (t) −Ki 0 0 0 x4 (t) 0
-0.01
-0.02
-0.03
-0.04
-0.05
0 5 10 15 20 25 30 35 40
Time (s)
Dynamic Response of Load Frequency Controller with Integral Control Action (Ki = 0.1)
0.02 Ki = 0.1
0.01
f (Hz)
-0.01
-0.02
-0.03
Ki = 0.05 Ki = 0.01
-0.04
-0.05
0 5 10 15 20 25 30 35 40
Time (s)
Dynamic Response of Load Frequency Controller with Integral Control Action with different Ki settings
1 2
Tie Line
Assume that two control areas are interconnected via a relatively weak tie-line. These areas are generally of different size and
characteristics.
In the single-area case we have represented frequency deviation by a single variable ∆f . In the present case it is assumed that each
area is individually strong. Having interconnected them with a weak tie-line therefore lead us to the assumption that the frequency
deviations in the two areas can be represented by two variables ∆f1 and ∆f2 respectively.
Any change in demand from the forecasted one will cause change in power flow through out the entire network. However, more
energy will be shared by the larger area as it possesses more kinetic energy.
This may cause a static error in tie-line power flow, referred to as inadvertent exchanges, indicating one area would have to support the
other on a steady-state basis.
A basic guiding principle in pool operation is that each area, in normal steady state, must supplies its own load.
Objective of two-area load frequency control is thus to regulate the frequency of each area and to simultaneously regulate the line power as
per inter-area power contracts.
Modelling of Tie-Line
In normal operation, power flow through the tie-line, from Area 1 to Area 2, can be written as
V 0V 0
0 0 0
Ptie,12 ≈ 1 2 sin δ1 − δ2
X12
where, V10 ∠δ10 , V20 ∠δ20 are the nominal voltages of bus 1 and 2 respectively.
For small deviation in the angles δ1 and δ2 , the tie-line power will change to
V 0V 0
0 0
Ptie,12 = 1 2 sin δ1 + ∆δ1 − δ2 − ∆δ2
X12
V10 V20 V 0V 0
0 0 0 0
≈ sin δ1 − δ2 + 1 2 cos δ1 − δ2 (∆δ1 − ∆δ2 )
X12 X12
0
= Ptie,12 + ∆Ptie,12
V10 V20
0 0
T12 = cos δ1 − δ2 (synchronizing coefficient)
X12
Modelling of Tie-Line
d∆δ R
Now, = ∆ω = 2π∆f . Hence, change in angle can be written as ∆δ = 2π ∆f dt.
dt
By expressing tie-line power deviations in terms of incremental change in frequency ∆f rather than ∆δ, we thus get
Z Z
∆Ptie,12 = 2πT12 ∆f1 dt − ∆f2 dt
2πT12
∆Ptie,12 (s) = (∆F1 (s) − ∆F2 (s))
s
2πT21
Similarly, ∆Ptie,21 (s) = (∆F2 (s) − ∆F1 (s))
s
2πT12
ΔPtie,12 (s) −1 ΔPtie,21 (s)
s
+ −
ΔF1 (s) ΔF2 (s)
− −
+ Kps + Kps
1 2
− −
In case of an isolated control area, ACE is the change in area frequency which when used in integral control loop forced the steady
state frequency error to zero.
In order that the steady state tie-line power error in a two-area control be made zero, another integral control loop (one for each area)
must be introduced to integrate the incremental tie-line power signal and feed it back to the speed changer.
This is accomplished by a single integrating block by redefining ACE as a linear combination of incremental frequency and tie-line
power.
1 ΔPD1 (s)
b1
R1
Control Area 1
− −
ACE1 ΔPC1 (s) Ksg Kps
Ki1 1
Kt + 1
1
∑
− ΔF1 (s)
s 1 + sTsg 1 + sTt 1 + sTps
+ 1 1 ΔPt1 (s) 1
ΔPtie,12 (s)
+
2πT12
s
−
−1
ΔPtie,21 (s)
Control Area 2
−
ACE2 ΔPC2 (s) Ksg Kps
Ki2 2
Kt + 2
2
∑ −
s + 1 + sTsg 1 + sTt 1 + sTps
2
−
2 2
ΔPt2 (s) ΔF2 (s)
−
1
b2
R2
ΔPD2 (s)
Load Flow Analysis
Automatic Load Frequency Control
Short Circuit Analysis
Grid Management in India
Power System Stability
Scheduling and Dispatch Procedure
Economic Dispatch of Generation
Availability Based Tariff (ABT)
Automatic Control of Generation
Transmission and Grid Management are essential functions for smooth evacuation of power from generating stations to the
consumers.
Transmission Management
Grid Management
involves taking care of the overall reliability, security, economy and efficiency of the power system.
Grid Structure
The power grid of India is geographically divided in the five regions:
The first four out of five regional grids are operating in synchronous
mode.
implies that power across these regions can flow seamlessly as per
the relative load generation balance.
called NEW Grid.
789
ÿ56
ÿÿ56ÿ
ÿ
5ÿ5ÿ
9
Defines the rules, guidelines and standards to be followed to plan, develop, maintain and operate the power system in the most
secure, economic and efficient manner, while facilitating healthy competition in the generation and supply of electricity.
Documentation of the principles and procedures which defines the relationship between the various users of the Inter-State
Transmission System (ISTS), National, Regional and State Load Dispatch Centres.
Facilitation of the optimal operation, coordination, maintenance planning of the grid and facilitation of development and
planning of economic and reliable National/Rational Grid.
Facilitation for development of power markets by defining a common basis of operation of ISTS, applicable to all the users of the
ISTS.
Facilitation of the development of renewable energy sources by specifying the technical and commercial aspects for integration of
these resources into the grid.
erolagnaB @
atakloK @
RLDC
gnollihS @
iabmuM @
NRLDC ERLDC WRLDC NERLDC SRLDC
In line with the federal structure of governance in the country, every state has a State Load Dispatch Centre (SLDC), which is the apex
body to ensure integrated operation of the power in the state.
Each of the five regions has a Regional Load Dispatch Centre (RLDC), which is the apex body, as per the Electricity Act 2003, to ensure
integrated operation of the power system in the concerned region.
1 be responsible for optimum scheduling and dispatch of electricity within the region, in accordance with the contracts entered
into with the licensees or generating companies operating in the region.
2 monitor grid operations.
3 keep accounts of the quantity of electricity transmitted through the regional grid.
4 exercise supervision and control over the inter-state transmission system.
5 be responsible for carrying out real-time operations for grid control and dispatch of electricity within the region through secure
and economic operation of the state grid in accordance with the grid standards and state grid code.
The RLDC may give such directions and exercise such supervision and control as may be required for ensuring stability of grid
operations and for achieving the maximum economy and efficiency in the operation of the power system in the region under its
control.
Every licensee, generating company, generating station, substation and any other person connected with the operation of the power
system shall comply with the direction issued by the RLDC.
All directions ordered by the RLDCs shall be issued through the SLDC and the SLDC shall ensure that such directions are duly complied
with by the licensees or generating company or sub-station.
1 System operation and control including inter-state / inter-regional transfer of power, covering contingency analysis and
operational planning on real-time basis.
2 Scheduling / re-scheduling of generation.
3 System restoration following grid disturbances.
4 Metering and data collection.
5 Compiling and furnishing data pertaining to system operation.
6 Operation of regional UI pool account, regional reactive energy account and congestion charge account.
7 Operation of ancillary services.
Role of NLDC
1. Night Lean
2. Morning Peak
3. Day Lean or AfternoonPower
trough System Operation and Control ©Ananyo Sengupta 243 / 256
Load Flow Analysis
Automatic Load Frequency Control
Short Circuit Analysis
Grid Management in India
Power System Stability
Scheduling and Dispatch Procedure
Economic Dispatch of Generation
Availability Based Tariff (ABT)
Automatic Control of Generation
50.5 50.5
48.5 48.5
49.5 49.5
47.5 47.5
00
02
04
06
08
10
12
14
16
18
20
22
00
02
04
06
08
10
12
14
16
18
20
22
48.5 48.5
Tim e Tim e
02
04
06
08
10
12
14
16
18
20
22
00
02
04
06
08
10
12
14
16
18
20
22
Tim e Tim e
Figures 1 & 2 : Frequency Profiles of Western and Eastern regional grids in 2002 prior to ABT
Northe rn Region
Southern Region
Hz Hz
51.5 51.5
50.5
48.5 50.5
48.5
49.5
47.5 49.5
47.5
00
02
04
06
08
10
12
14
16
18
20
22
00
02
04
06
08
10
12
14
16
18
20
22
48.5 Tim e 48.5
Tim e
47.5 47.5
00
02
04
06
08
10
12
14
16
18
20
22
00
02
04
06
08
10
12
14
16
18
20
22
Figures 3 & 4 : Frequency Profiles
Figure:
Tim e ofFrequency
Southern and Northern
profile regionalgrids
in regional grids in
in 2002
2002prior
Tim e
to ABT.
Figures 3 & 4 : Frequency Profiles of Southern and Northern regional grids in 2002 prior to ABT.
Power System Operation and Control ©Ananyo Sengupta 245 / 256
Load Flow Analysis
Automatic Load Frequency Control
Short Circuit Analysis
Grid Management in India
Power System Stability
Scheduling and Dispatch Procedure
Economic Dispatch of Generation
Availability Based Tariff (ABT)
Automatic Control of Generation
High frequency is a result of insufficient backing down of generation when the total customer load has been fallen
during off-peak hours.
Prior to 2002, grid used to follow a simplistic, single-part, constant (Rs./kWh) tariffs, which disregarded drawal
pattern, deviation from schedules, system conditions (surplus/deficit) etc.
State utilities were not being discouraged from overdrawing, even when generation was inadequate (during peak-load hours).
Both the Central generating companies and State utilities were being encouraged to go on generating, even when the consumer
load had come down (during off-peak hours).
In ABT mechanism, the fixed cost and the variable cost components are treated separately.
Components of ABT
1 Capacity Charge
Fixed cost of a plant.
Based on the plant, i.e., its capability to deliver MWs one a day-to-day basis.
2 Energy Charge
Variable cost of a plant.
Paid for generating energy as per the given schedule for the day.
3 Charge for Unscheduled Interchange
Payment for deviation from schedule, at a rate dependent on system condition (frequency).
(State) 6 am - 10 pm 10 pm - 6 am
A 270 270
B 270 270
State A State B State C C 360 200
(30% share) (30% share) (40% share)
(State) 6 am - 10 pm 10 pm - 6 am
A 270 270
B 270 270
State A State B State C C 360 200
(30% share) (30% share) (40% share)
Unscheduled Interchange
Frequency Linked Tariff
Unscheduled Interchange
Frequency Linked Tariff
ISGS will have to pay for the energy shortfall, at the same
frequency dependent rate.
> 50 Hz
Frequency
Under-Supply Over-Supply
< 50 Hz
Under-Supply Over-Supply
Figure 7: Present DSM Vector w.e.f 17 February.2014
Figure: UI Rate
The present Deviation Settlement Mechanism in India came into force with effect from 17th
February, 2014 [3]. The salient features are as follows:
Operational Frequency Band has been tightened to 49.90 - 50.05 Hz.
Step size changed from 0.02 Hz to 0.01 Hz.
Power
The charges for deviation System
for each Operation
0.01 Hz andPaise/kWh
step is 35.60 Controlin©Ananyo Sengupta
the frequency 250 / 256
Load Flow Analysis
Automatic Load Frequency Control
Short Circuit Analysis
Grid Management in India
Power System Stability
Scheduling and Dispatch Procedure
Economic Dispatch of Generation
Availability Based Tariff (ABT)
Automatic Control of Generation
1 Over Supply
if f > 50.05 Hz, UI rate is zero.
means generating station may over-supply, but will not get any
payment for extra energy supply.
for 50 ≤ f ≤ 50.05 Hz, they will get payment at much lower rate.
2 Under Supply
in this case, generating station will still be paid for scheduled energy
(at its energy charge rate).
it will thus be able to save on fuel cost (for the energy not
generated) and retain the energy charge as net savings.
provides strong incentive to backdown generation during high
Figure 7: Present DSM Vector w.e.f 17 February.2014 frequency situations.
Figure: UI Rate
The present Deviation Settlement Mechanism in India came into force with effect from 17th
February, 2014 [3]. The salient features are as follows:
Operational Frequency Band has been tightened to 49.90 - 50.05 Hz.
Step size changed from 0.02Power System
Hz to 0.01 Hz. Operation and Control ©Ananyo Sengupta 251 / 256
Load Flow Analysis
Automatic Load Frequency Control
Short Circuit Analysis
Grid Management in India
Power System Stability
Scheduling and Dispatch Procedure
Economic Dispatch of Generation
Availability Based Tariff (ABT)
Automatic Control of Generation
Frequency < 50 Hz
1 Over Supply
UI rate ramps up.
means, if a generating station supplies more energy than schedule, it
will get back money at higher rate.
2 Under Supply
for any shortfall, the generating station will have to pay back at the
same (high) rate.
a strong commercial incentive to maximize its generation during
low frequency period.
> 50 Hz
Frequency
over drawal under drawal
< 50 Hz
2 Under Drawal
2 Under Drawal
2 Under Drawal
00
02
04
06
08
10
12
14
16
18
20
22
49.5
Tim e
48.5
Figures 6 : Frequency Profile of W estern Regional Grid (synchronously connected with Eastern and North-
47.5
00
02
04
06
08
10
12
14
16
18
20
22
eastern regions) in late 2003.
Tim e
Northern Region
Figures 6 : Frequency Profile of W estern Regional Grid (synchronously connected with Eastern and North-
Southern Region
Hz
eastern regions) in late 2003. Hz
51.5 51.5
50.5 50.5
Northern Region Southern Region
49.5 Hz 49.5 Hz
51.5 51.5
48.5 48.5
50.5 50.5
47.5 47.5
00
02
04
06
08
10
12
14
16
18
20
22
49.5
00
02
04
06
08
10
12
14
16
18
20
22
49.5
Tim e Tim e
48.5
Figures 7 & 8 : Frequency Profiles of Northern & S outhern Regional Grids in late 2003. 48.5
Power System Operation and Control ©Ananyo Sengupta 256 / 256