Ratio Rebar toward Section area = 11779 mm2/ 9100000 mm2 = 0.00173 (0.173 %)
Base SNI-03-2847-2002, minimum rebar ratio for Shrinkage Reinforcement is 0.0014 (Rebar design
supplier still OK)
SNI-03-2847-2002
REQUREMENT REINFORCEMENT BASE ON SAFE 2016 DESIGN (18-D25) FOR 2.0 M THK
But follow the regulation SNI-03-2847-2002 the Shrinkage Reinforcement should be minimum 0.0014.
Then,
DESIGN BY CCEED
DESIGN BY SUPPLIER
Based on soil investigation data in the depth 5.5-6.00 the Cu = 0.32 kg/cm2 and Ф=17.8 degree
Base Tower Crane Specification the Earth Bearing Pressure = 0.15 Mpa > 0.138 Mpa (the Bearing
Capacity still oke because our safety factor is 3 and we have additional pile to support the foundation.
If we using the safety factor 2.5 the allowable capacity = Qall = Cu.Nc/2.5 = 0.32 kg/cm2 x 12.9 / 2.5 =
1.65 kg/cm2 = 0.16 Mpa > 0.15 Mpa. (Allowable bearing capacity still enough to support Tower Crane.