DOMESTIC WATER PIPING SPECIALTIES

2. Manual drains shall be installed with a 150 mm P-trap in lieu of a gate valve for each air
handling unit, to drain the condensate from each unit
3. Manual drains shall be piped off to the closest floor drain
Y. Escutcheons shall be used where piping enters or exits finished walls, cabinets and in the
interior of cabinets, and elsewhere as noted in the specifications and drawings
3.04 TESTING
A. Field testing of the water meters for leaks and proper functioning of registers and flow rate
counters shall be performed at the time of water supply and building or facility water system
functional startup and testing
B. Installed water meters shall meet their performance specifications
3.05 FIELD QUALITY CONTROL
A. Field testing shall be performed under provisions of Division 1
B. Pressure test system with small amount of refrigerant and dry nitrogen 1378 kPa. Using
halide torch or electronic leak detector check for leaks. Perform final test at 750 mm vacuum
for a 24-hour period with no deviation. Provide a minimum of 48 hours notification prior to
test and submit written report to the Royal Commission verifying test results

END OF SECTION