You are on page 1of 1

KEY PLAN NOTES

TRUE
THE SITE 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE NOTED.
NORTH 2. ALL PANELBOARDS AND DISCONNECT SWITCHES ENCLOSURES SHALL BE
GROUNDED INTO ONE GROUNDING CONNECTION POINT OF THE GROUNDING
MAKKA
EMERGENCY
ENTRANCE & EXIT
GRID.
3. MINIMUM WIRE SIZE OF RECEPTACLE OUTLET BRANCH CIRCUITS SHALL BE
MAIN
ENTRANCE & EXIT

LAR 6427

PROPOSED
1 GUARD HOUSE BUILDING
2 4 6

N 4mm² UNLESS OTHERWISE SPECIFIED.

PROPERTY LIMIT
3 5

4. MINIMUM CONDUIT SIZE SHALL BE 20mmØ UL-LISTED, SASO APPROVED,


D D
12 12
FIRE EXIT DOOR FIRE EXIT DOOR

UNLESS OTHERWISE SPECIFIED.

COLLECTING POND
PROPOSED

RUN-OFF WATER
FINISHED PRODUCT
STORAGE BUILDING

5. FOR LOADS AND WIRE SIZE, REFER TO PANELBOARDS SCHEDULE.

SLIDING DOOR

SLIDING DOOR
D

D
13 13

6. THE LOCATION OF DISCONNECT SWITCHES IS ONLY NOTIONAL. THE


FIRE EXIT DOOR FIRE EXIT DOOR
D

12 D
12
SLIDING DOOR

ROLL UP DOOR

ROLL UP DOOR
CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL DRAWINGS FOR
PROPOSED
MAINTENANCE SERVICES BUILDING

ROLL UP DOOR

ROLL UP DOOR
LOCATION OF AC EQUIPMENT UNITS.
PROPOSED
U&OO
BUILDING 7. DO NOT SCALE FROM THIS DRAWING.
PROPOSED
RAW MTERIAL
BUILDING
8. ALL DIMENSIONS TO BE CHECKED ON SITE AND ANY DISCREPANCIES SHALL
A B C D E F G H I J BE REPORTED IMMEDIATELY TO THE ARCHITECT.
9. CONTRACTOR SHALL VERIFY ALL LEVELS AT SITE PRIOR TO EXECUTION OF
8 7

WORK AND IN CASE OF ANY DISCREPANCIES, BRING TO KNOWLEDGE OF THE


ENGINEER.
10. THE CONTRACTOR SHALL CONFIRM THE SETTING OUT OF THE BUILDING
PRIOR TO COMMENCEMENT OF WORK.
11. THE CONTRACTOR SHALL OBTAIN ALL APPROVALS AND N.O.C.'S FROM ALL
CONCERNED LOCAL STATUTORY AUTHORITIES AND SHALL INCLUDE FOR ALL
WORKS WITH RESPECT TO THE DIVERSION/PROTECTION OF THE SERVICES
DURING THE PERIOD OF CONSTRUCTION, TO THE SATISFACTION OF THE
CONCERNED AUTHORITIES AND THE ENGINEER.
12. THE CONTRACTOR TO PREPARED SHOP DRAWINGS.
SYMBOL DESCRIPTION
3 METER SUSPENDED HIGHBAY INDUSTRIAL LUMINAIRE 1X200W,
230V, 60HZ LED, GLASS DIFFUSER, IP:54, SASO APPROVED.

FULLY RECESS-MOUNTED DECORATIVE DOWN LIGHT FIXTURE ,


LED LAMP 1X18W, 230V, 60Hz, WATERPROOF IP:45, WITH GLASS
DIFFUSER, SASO APPROVED.

RECESS MOUNTED 600X600mm LED LIGHTING FIXTURE WITH,


IP:20, 230V, 60HZ ,SASO APPROVED. SAUDI LIGHTING OR EQUAL.

LPPMS PPMS
1 1 1X10W FLUORESCENT LIGHTING FIXTURE, 230V, 60HZ., ABOVE
MIRROR LUMINAIRE WITH PRISMATIC PATTERN ACRYLIC
CP-LPPMS LPPMS-1,3,5 DIFFUSER, IP:54. WITH BUILT-IN SWITCH , SASO APPROVED.
VIA CP-LPPMS SAUDI LIGHTING OR EQUAL.
1X50W EMERGENCY LIGHT WITH RECHARGEABLE BATTERY
H1 H2 H3 H4 H5 H6 H7 H8 H9 H10
PACK, 230V, 60HZ.

ROLL UP DOOR
ROLL UP DOOR

1X6W EXIT LIGHT SIGN WITH RECHARGEABLE BATTERY PACK


FOR 3 HOURS, 230V, 60HZ. ,SASO APPROVED.
WALL MOUNTED FLOOD LIGHT LUMINAIRE 1X200W, 230V, 60HZ
LED, GLASS DIFFUSER, IP:65, SASO APPROVED.
6mm² COPPER/XLPE LIGHTING WIRE IN 25mmØ EMT CONDUIT
H20 H19 H18 H17 H16 H15 H14 H13 H12 H11 UL-LISTED, SASO APPROVED, CONCEALED IN CEILING OR
EXPOSED ABOVE FALSE CEILING. 220V, NEEDS (1 PHASE, 1
NEUTRAL, 1 GROUND) "TYPICAL"

2 2 4mm² COPPER/XLPE SWITCH WIRE IN 20mmØ PVC CONDUIT


UL-LISTED, SASO APPROVED ,EMBEDDED IN FLOORS OR WALLS.
LPPG-A-3 BRANCH CIRCUIT HOMERUN, LPPG-A DENOTES PANEL NAME, 3
H30 DENOTES CIRCUIT NUMBER.
H21 H22 H23 H24 H25 H26 H27 H28 H29 Sa SINGLE POLE, ONE GANG SWITCH, RECESS MOUNTED, 20AMPS,
VIA CP-LPPMS 230V, 60HZ. LOWERCASE LETTER SIGNIFY LIGHT CONTROL.
LPPMS-7,9,11
ROLL UP DOOR

ROLL UP DOOR
LPPMS-19 ELECTRICAL PANEL BOARD 400/230 V, 3-PHASE, 60HZ, 4-WIRES :
LPPMS- LIGHTING & POWER PANEL (MS BUILDING).
PPMS-01- POWER PANEL (MS BUILDING).
PPMS-02- POWER PANEL (MS BUILDING).
PPMS-E- EX-FANS PANEL (MS BUILDING).

H31 H32 H33 H34 H35 H36 H37 H38 H39 H40

3 Sb
Sc
LPPMS-23
Sd
Sm
LPPMS-25
Sm
LPPMS-27
Su
LPPMS-29 3
SPARE u u
LPPMS-21
b
b b b
c c c c
d
PARTS e m m m m m m e u u

u
uABLUTION
STORAGE SPARE WASH
STORAGE TEA ROOM MECHANICAL ELECTRICAL u TOILET
u u
b b b b c c c c d e m m m m m m PARTS
e

Se Se u u

m m m m m e
c u u u u u
c c c m
b b b b d e

4 4
LPPMS-13,15,17
VIA CP-LPPMS

BIA
K IN
G

RA
D
M A

O
O F S A U DI

EMDAD ANTHRACITE DRYING PROJECT


CONSTRUCTION PACKAGES

TANAGHOM CONSULTING
LIC. NO. 2013,P.O BOX: 9021 / CODE: 35811-4692 JUBAIL IND. CITY -

A B C D E F G H I J OFFICE NO. 2-12, NABA COMMERCIAL CENTER, AL-FANATEER-/


TEL-/(03) 3472261 / 3473926 / 3473950 //FAX: (03) 3472259/
Website:www.tanaghomconsulting.com

Smart Projects Construction Company


(MS) BUILDING P.O. Box 1861| ZIP Code 31952 Khobar
KSA Tel.: +966 13 894 1919|Fax: +966 13 896 5511
1 GROUND FLOOR LIGHTING LAYOUT PLAN

MSB GROUND FLOOR LIGHTING LAYOUT PLAN

3 - 07 - 41J - B08A J 02 14
ANT-21-008-INK-SPCC-R.0
ANT-21-008-SD-GPP-EL-LA-0005-Rev.01
ANT-21-008-SD-GPP-EL-0094-Rev.01
1: 75M 1/7