SMOKE ALARM

FIRST FLOOR ELECTICAL NOTES:


PLAN SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING LOCATIONS:

SCALE: 1/4" = 1'-0" 1. IN EACH SLEEPING ROOM.


33'
2. OUTSIDE EACH SEPARATE SLEEPING ARE IN THE IMMEDIATE VICINITY OF THE BEDROOMS.
10'-6" 6' 10'-6" INCLUDING CRAWL SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR DWELLING
CONC. STEPS
1'-6" 1'-6" 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING BASEMENTS BUT NOT
1'-6" VARY PER GRADE 1'-6"
9'-7"

11"

11"
UNITS WITH SPLIT LEVELS AND WITHOUT INTERVENING DOOR BETWEEN THE ADJACENT
LEVELS, A SMOKE ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR THE
8"

8"

8"
ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL IS LESS THAN ONE FULL
STORY BELOW THE UPPER LEVEL.

8"
3 - 4/0 ALU.THHN
5'-4"

5'-4"
6'

WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE INSTALLED WITHIN AN


INDIVIDUAL DWELLING UNIT THE ALARM DEVICES SHALL BE INTERCONNECTED IN SUICH A
MAIN DISCONNECT MANNER THAT THE ACUATION OF ONE ALARM WILL ACTIVATE ALL OF THE ALARMS IN
COMBO METER THE INDIVIDUAL UNIT. THE ALARM SHALL BE CLEARLY AUDIBLE IN ALL BEDROOMS OVER
SQUARE D A/C
3'-0" x 5'-2" 3'-0" x 5'-2" GFI 3'-0" x 5'-2" 3'-0" x 5'-2" DISC.
BACKGROUND NOISE LEVELS WITH ALL INTERVENING DOORS CLOSED.
*FIXED *FIXED WP ENTRY DOOR *FIXED *FIXED
8"

8"
#14 AND #12 COPPER TO
3'-1" 3' 0'-4" 3' 3' 0'-7" 3' 3'-2" 3' 3' 3'-1" LIGHTS AND OUTLETS

СGFI
0'-4"
200 AMP ALL SMOKE ALARMS SHALL BE LISTED AND INSTALLED IN ACCORDANCE WITH THE
2'-3"

2'-3"
11'-4" 20'
PROVISIONS OF THIS CODE AND THE HOUSEHOLD FIRE WARNING EQUIPMENT PROVISIONS
2'-3"

2'-3"
GFI СGFI MAIN DISC. #10 COPPER TO
WATER HEATER OF NFPA 72.

3'-0" x 5'-2" 3'-0" x 5'-2"


3'-0" x 5'-2" 3'-0" x 5'-2"

#8 COPPER TO RANGE
*EGRESS

WHEN INTERIOR ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A PERMIT OCCUR, OR

4'-7"
UNDERGROUND

*EGRESS
SERVICE BY WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS,
3'

3'
3'

3'
POWER COMPANY THE INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS LOCATED AS
8'-4"

REQUIRED FOR NEW DWELLINGS: THE SMOKE ALARMS SHALL BE INTERCONNECTED AND
#4 COPPER TO 5 /8" GROUND ROD
DININIG ROOM ALSO SERVICE TO BE BONDED
HARD WIRED.
4"

4"
0'-4"

0'-4"
TO FOOTING STEEL
9'-6" CEILING
*EGRESS

EXCEPTIONS:

*EGRESS
GFI
3'
3'

3'
3'
1. SMOKE ALARMS IN EXISTING AREAS SHALL NOT BE REQUIRED TO BE INTERCONNECTED
3'-5"
UP
GROUND GROUND ROD AND HARD WIRED WHERE THE ALTERATIONS OR REPAIRS DO NOT RESULT IN THE
ROD 6' APART REMOVAL OF INTERIOR WALL FINISHES EXPOSING THE STRUCTURE, UNLESS THERE IS
6'-4"

1 AN ATTIC, CRAWL SPACE, OR BASEMENT AVAILABLE WHICH COULD PROVIDE ACCESS


2
FOR HARD WIRING AND INTERCONNECTION WITHOUT THE REMOVAL OF INTERIOR
FINISHES.
3

5'-5"
5'-5"

23'-10"
6'-2"

4
2. REPAIRS TO THE EXTERIOR SURFACES OF DWELLINGS ARE EXEMPT FROM THE

23'-10"
5 REQUIREMENTS OF THIS SECTION.

FIN. FLR.
TV 6
ELEC. RISER IN NEW CONSTRUCTION, THE REQUIRED SMOKE ALARMS SHALL RECEIVE THEIR

2'-3" x 5'-2"
7
PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING IS SERVED FROM
0'-0" A.F.F. A COMMERCIAL SOUCE, AND WHEN PRIMARY POWER IS INTERRUPPTED, SHALL

43'
43'

2'-3"
8 NOTE:
3'-0" x 5'-2" 3'-0" x 5'-2"

*TEMP
2'-3"
30'-4"

RECEIVE POWER FROM A BATTERY. WIRING SHALL BE PERMANENT AND WITHOUT


*EGRESS

9
ELECTRICAL MATERIALS AND INSTALLATIONS SHALL
COMPLY W/APPLICABLE PROVISIONS OF THE NATIONAL ELEC.CODE, A DISCONNECTING SWITCH OTHER THAN THOSE REQUIRED FOR OVERCURRENT
15'-6"

PROTECTION. SMOKE ALARMS SHALL BE PERMITTED TO BE BATTERY OPERATED


3'

3'

10 LOCAL CODES, AND THE LOCAL POWER COMPANY.

СGFI
WHEN INSTALLED IN BUILDINGS WITHOUT COMMERCIAL POWER OR IN BUILDINGS
LIVING ROOM 11 THAT UNDERGO ALTERATIONS, REPAIRS OR ADDITIONS REGULATED BY SECTION
37'

37'
9'-6" CEILING R313.1.1.
4"

12 KITCHEN
0'-4"
*EGRESS

GFI
13 9'-6" CEILING
W.M.
3'

3'

7'-8"
CARBON MONOXIDE
14

15

0'-6" 16 2'-6" 0'-2"


ALARM:
3'
3'

3'

17
СGFI СGFI
4'

4'

18 16'-7"
FL. STATUTE 553.885 CARBON MONOXIDE ALARM REQUIRED IN EVERY BUILDING FOR
6'-2"

2'-2" 4"
WHICH A BUILDING PERMIT IS ISSUED FOR NEW CONSTRUCTION. HAVING A
0'-5"

СGFI

16'-7"
FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE, OR A ATTACHED GARAGE
2'-2"
3'-0" x 5'-2"

СGFI
3'-2"

SHALL HAVE AN APPROVED CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF


2'-10"
2'-8"
*EGRESS

EACH ROOM USED FOR SLEEPING PURPOSES.


0'-2" 3'-1" 0'-2"
2'-8" 4'-7"
3'-0" x 5'-2" 3'-0" x 5'-2"
3'

3'

0'-1"
6'-6"

*EGRESS
0'-1"

5' BEDROOM 1
3'
3'

0'-2" 2'-8" 2'-2"


9'-6" CEILING
3'-4"

A/C
ELECTRICAL NOTES:
2'-3"

GFI
2'-3"

0'-4"11'-6"

4"

GFI BATH 1 EX PROVIDE ELECTRICAL


12'-2"

2'-6" 6' 2'-10"


2'-4"
CONNECTION & DISCONNECT
9'-6" CEILING
*EGRESS
8"

SWITCH FOR A/C EQUIPMENT


3'

2'-8" ALL WORK SHALL BE DONE IN STRICT ACCORDANCE WITH APPLICABLE CODES AND
8'-8"

3'
8'-4"

8'-4"

ORDINANCES. CODES AND ORDINANCES SHALL TAKE PRECEDENCE OVER THE


WP
CONSTRUCTION DOCUMENTS ONLY IN THE CASE OF CONFLICT.
FIN. FLR.
4'-8"

5'
5'-4"

0'-0" A.F.F. FIXTURE, OUTLET, AND SWITCH LOCATIONS ARE DIAGRAMMATIC. CONTRACTOR
3'-8"
3'

SHALL COORDINATE EXACT LOCATIONS WITH MINIMUM CODE REQUIREMENTS AND


LANAI СGFI СGFI
OTHER TRADES WHEN NOT SHOWN IN DETAIL.
1'-5" 2'-3" 1'-5" 2'-4" 14'-8" 12'

RECEPTACLE LOCATIONS
8"

ALL RECEPTACLES SHALL BE WIRED TO AN ARC FAULT CIRCUIT INTERRUPTER.


1. *TEMP Level 1/4" = 1'-0"
1'-6"
2'-3" x 2'-3"
PER NEC 210.52
8" 2'-6" 6' 2'-6" 8" 1'-5" 2'-3" 16'-4" 8"

ELECTRICAL PLAN
ELECTRICAL DEVICES: ABOVE FINISHED FLOOR:
ELECTRICAL KEY
5' 2'-8" SWITCHES OVER COUNTER . . . . . . . . . . 48" TO CL

SYMBOL WALL OUTLETS OVER COUNTER . . . . . . . 48" TO CL


DESCRIPTION
33'
REMAINING SWITCHES . . . . . . . . . . . . . 48" TO CL
DUPLEX CONVENIENCE OUTLET
WALL OUTLETS . . . . . . . . . . . . . . . . . . 12" TO CL
DUPLEX OUTLET ABOVE COUNTER BATH VANITY BRACKET OUTLET
1,2
GROUND FAULT INTERRUPTER DUPLEX OUTLET (1" ABOVE TOP OF MIRROR) . . . . . . 80" TO CL
GFI
WATER SOFTENER AND SUMP OUTLETS 48" TO CL
WP WATER PROOF DUPLEX OUTLET
TELEPHONE OUTLETS . . . . . . . . . . . . . . 12" TO CL
220 VOLT OUTLET
TELEVISION OUTLETS . . . . . . . . . . . . . . 12" TO CL
DUPLEX FLOOR MOUNTED OUTLET
EXTERIOR GFI OUTLETS . . . . . . . . . . . . . 12" TO CL
WALL SWITCH (D=DIMMER) GARAGE GFI (ABOVE GARAGE FLOOR) 48" TO CL
ELECTRIC PANEL BASEMENT WALL OUTLETS . . . . . . . . . . 48" TO CL

Project No.
SD SMOKE DETECTOR FRONT DOOR COACH LIGHT . . . . . . . . . 72" TO CL

TV TELEVISION CABLE OUTLET GARAGE DOOR COACH LIGHT,


(ABOVE GARAGE FLOOR) . . . . . . . 84" TO CL
TELEPHONE 64" TO BTM
EX EXHAUST FAN DINING AND BREAKFAST FIXTURE . . . . . OF FIXTURE
96" TO BTM
FLUORESCENT
WALL MOUNTED INCANDESCENT LIGHT FIXTURE FOYER AND STAIRWAY FIXTURE . . . . . . OF FIXTURE

INCANDESCENT LIGHT FIXTURE CEILING RECESSED THERMOSTAT . . . . . . . . . . . . . . . . . . . 54" TO CL


DOORBELL CHIMES . . . . . . . . . . . . . . . 84" TO CL
INCANDESCENT LIGHT FIXTURE CEILING MOUNTED
LEVEL W/
DOOR CHIME DOORBELL BUTTON . . . . . . . . . . . . . . . DR HANDLE
DOOR BELL KITCHEN HOOD FAN "WHIP" . . . . . . . . . . 66" TO CL
SOFFIT MOUNTED SPOT LIGHT WITH MOTION SENSOR KITCHEN WALL HUNG MICROWAVE
OUTLET . . . . . . . . . . . . . . . . . . . . . . 76" TO CL
AIMABLE RECESSED FIXTURE
KITCHEN DISHWASHER RECEPTACLE . . . UNDER SINK
HANGING CEILING FIXTURE (OWNER SELECT CHANDELIER)
KITCHEN RANGE . . . . . . . . . . . . . . . . . . 24" TO CL
KITCHEN REFRIGERATOR . . . . . . . . . . . 48" TO CL
WASHER/DRYER OUTLET . . . . . . . . . . . . 48" TO CL

ARCHITECT CERTIFIES, TO THE BEST OF HIS KNOWLEDGE, THAT ALL


PLANS AND SPECIFICATIONS COMPLY WITH THE MINIMUM BUILDING
E1.1
CODES.