Name of the Values volts for Core-1 Values volts for Core-2 Values volts for Core-3 Core-1

e-2 Values volts for Core-3 Core-1 Variation WRT Core-2 Variation WRT Core-3 Variation WRT
Sl No. Measurement
feeder/Bay Bus-I Bus-II Line Bus-I Bus-II Line Bus-I Bus-II Line Bus-I Bus-II Bus-I Bus-II Bus-I Bus-II
400kV Hoody-
1 Yelahanka Line R-N 64.9 65 62.5 62.3 65 64.9 62.4 -2.4 -2.5 -2.6 -2.5
Y-N 65.9 65.6 63.4 63.2 65.9 65.8 63.4 -2.5 -2.2 -2.5 -2.4
B-N 64.6 65.2 51.4 51.4 64.7 65.4 51.4 -13.2 -13.8 -13.3 -14
400kV Hoody-Nlm
1 Line R-N 64.9 65 65.5 64.4 65 64.9 65.5 0.6 0.5 0.5 0.6
Y-N 65.9 65.6 65.3 63.6 65.9 65.8 65.1 -0.6 -0.3 -0.8 -0.7
B-N 64.6 65.2 66.2 64.6 64.7 65.4 66 1.6 1 1.3 0.6
Note: Measurement to be carried out simultaneously for same phase of Bus CVTs and Line CVTs with 0.2 class multimeter. Readings to be taken from control panel. In case of discrepency, the readings should
be rechecked at switchyard
Note: Permissible limits for CVTs used for purposes other than metering. For CVTs used for commercial metering accuracy class limits to be followed
Drift in secondary
voltage (to be
measured by 0.2/0.5 Measurement
Sl No. class multimeter) Condition frequency
06 Monthly
1 Upto +/- 0.5 Volts Healthy Monitoring

To be 03 Monthly
2 0.5volts to +0.8 Volts Monitored Monitoring
Close
3 0.8Volts to +1.2Volts Monitoring Monthly
Close
4 1.2Volts to 2.0Volts Monitoring 15 days

5 Above 2Volts Alarming Replacement


Close
6 (')-0.8Volts to -4Volts Monitoring 15 Days
CAPACITIVE VOLTAGE TRANSFORMERS - 6MONTHLY ACTIVITY
Measurement of voltage
Date of Last calibration: Date: 20.11.2019
Values volts for Core-1 Values volts for Core-2 Core-1 Variation WRT Core-2 Variation WRT
Sl No. Name of the feeder/Bay Measurement
Bus-I Bus-II Line Bus-I Bus-II Line Bus-I Bus-II Bus-I Bus-II
1 220kV Hoody-HAL Line-2 R-N 62.2 62.4 61.6 62.4 62.4 61.6 -0.6 -0.8 -0.8 -0.8
Y-N 62.5 60.9 62.0 62.2 60.9 61.9 -0.5 1.1 -0.3 1
B-N 62.1 61.6 61.6 62.4 61.5 61.6 -0.5 0 -0.8 0.1
2 220kV Hoody-HAL Line-1 R-N 62.2 62.4 61.7 62.4 62.4 61.7 -0.5 -0.7 -0.7 -0.7
Y-N 62.5 60.9 62.1 62.2 60.9 62 -0.4 1.2 -0.2 1.1
B-N 62.1 61.6 61.7 62.4 61.5 61.7 -0.4 0.1 -0.7 0.2
3 220kV Hoody-HSR Line R-N 62.2 62.4 61.4 62.4 62.4 61.4 -0.8 -1 -1 -1
Y-N 62.5 60.9 59.4 62.2 60.9 59.3 -3.1 -1.5 -2.9 -1.6
B-N 62.1 61.6 62 62.4 61.5 62 -0.1 0.4 -0.4 0.5
4 220kV Hoody-EPIP Line R-N 62.2 62.4 61.5 62.4 62.4 61.5 -0.7 -0.9 -0.9 -0.9
Y-N 62.5 60.9 62.2 62.2 60.9 62.2 -0.3 1.3 0 1.3
B-N 62.1 61.6 59.2 62.4 61.5 59.2 -2.9 -2.4 -3.2 -2.3
4 220kV Hoody-ITPL UG Cable R-N 62.2 62.4 61.3 62.4 62.4 61.3 -0.9 -1.1 -1.1 -1.1
Y-N 62.5 60.9 62 62.2 60.9 62 -0.5 1.1 -0.2 1.1
B-N 62.1 61.6 61.5 62.4 61.5 62.1 -0.6 -0.1 -0.3 0.6

Note: Measurement to be carried out simultaneously for same phase of Bus CVTs and Line CVTs with 0.2 class multimeter. Readings to be taken from control panel. In case of discrepency,
the readings should be rechecked at switchyard
Note: Permissible limits for CVTs used for purposes other than metering. For CVTs used for commercial metering accuracy class limits to be followed
Drift in secondary voltage (to
be measured by 0.2/0.5 class Measurement
Sl No. multimeter) Condition frequency
06 Monthly
1 Upto +/- 0.5 Volts Healthy Monitoring
03 Monthly
2 0.5volts to +0.8 Volts To be Monitored Monitoring
3 0.8Volts to +1.2Volts Close Monitoring Monthly
4 1.2Volts to 2.0Volts Close Monitoring 15 days
5 Above 2Volts Alarming Replacement
6 (')-0.8Volts to -4Volts Close Monitoring 15 Days
Date:26.11.2019
Name of the Measureme Values volts for Core-1 Values volts for Core-2 Values volts for Core-3 Core-1 Variation WRT Core-2 Variation WRT Core-3 Variation WRT
Sl No.
feeder/Bay nt Bus-I Bus-II Line Bus-I Bus-II Line Bus-I Bus-II Line Bus-I Bus-II Bus-I Bus-II Bus-I Bus-II
400kV Hoody-
1 Yelahanka Line R-N 62.2 62.2 60 59.8 62.3 62.2 59.7 -2.2 -2.2 -2.6 -2.5
Y-N 63 62.8 60.8 60.5 63.1 63 60.6 -2.2 -2 -2.5 -2.4
B-N 61.7 62.4 49.2 49.4 61.9 62.5 49.1 -12.5 -13.2 -12.8 -13.4
400kV Hoody-Nlm
1 Line R-N 62.2 62.2 62.7 62.8 62.3 62.2 62.9 0.5 0.5 0.6 0.7
Y-N 63 62.8 62.2 61.9 63.1 63 62.2 -0.8 -0.6 -0.9 -0.8
B-N 61.7 62.4 63.1 62.9 61.9 62.5 63 1.4 0.7 1.1 0.5
Note: Measurement to be carried out simultaneously for same phase of Bus CVTs and Line CVTs with 0.2 class multimeter. Readings to be taken from control panel. In case of discrepency, the readings should
be rechecked at switchyard
Note: Permissible limits for CVTs used for purposes other than metering. For CVTs used for commercial metering accuracy class limits to be followed
Drift in secondary
voltage (to be
measured by 0.2/0.5 Measurement
Sl No. class multimeter) Condition frequency
06 Monthly
1 Upto +/- 0.5 Volts Healthy Monitoring

To be 03 Monthly
2 0.5volts to +0.8 Volts Monitored Monitoring
Close
3 0.8Volts to +1.2Volts Monitoring Monthly
Close
4 1.2Volts to 2.0Volts Monitoring 15 days

5 Above 2Volts Alarming Replacement


Close
6 (')-0.8Volts to -4Volts Monitoring 15 Days
CAPACITIVE VOLTAGE TRANSFORMERS - 6MONTHLY ACTIVIT
Measurement of voltage
Date of Last calibration:
Values volts for Core-1
Sl No. Name of the feeder/Bay Measurement
Bus-I Bus-II Line
3 220kV Hoody-HSR Line R-N 62.8 63.6 62
Y-N 63.3 61.4 60
B-N 63 62.4 62.6

Note: Measurement to be carried out simultaneously for same phase of Bus CVTs and Line CVTs with 0.2 class multimeter. R
the readings should be rechecked at switchyard
Note: Permissible limits for CVTs used for purposes other than metering. For CVTs used for commercial metering accuracy cl
Drift in secondary voltage (to
be measured by 0.2/0.5 class Measurement
Sl No. multimeter) Condition frequency
06 Monthly
1 Upto +/- 0.5 Volts Healthy Monitoring
03 Monthly
2 0.5volts to +0.8 Volts To be Monitored Monitoring
3 0.8Volts to +1.2Volts Close Monitoring Monthly
4 1.2Volts to 2.0Volts Close Monitoring 15 days
5 Above 2Volts Alarming Replacement
6 (')-0.8Volts to -4Volts Close Monitoring 15 Days
ANSFORMERS - 6MONTHLY ACTIVITY

Date: 29.11.2019
Values volts for Core-2 Core-1 Variation WRT Core-2 Variation WRT
Bus-I Bus-II Line Bus-I Bus-II Bus-I Bus-II
63.1 63.4 62.1 -0.8 -1.6 -1 -1.3
62.8 61.7 60.1 -3.3 -1.4 -2.7 -1.6
63 62.4 62.7 -0.4 0.2 -0.3 0.3

ne CVTs with 0.2 class multimeter. Readings to be taken from control panel. In case of discrepency,

or commercial metering accuracy class limits to be followed

-0.8 -1 -1 -1

-3.1 -1.5 -2.9 -1.6


-0.1 0.4 -0.4 0.5
Name of the Measureme Values volts for Core-1 Values volts for Core-2
Sl No.
feeder/Bay nt
Bus-I Bus-II Line Bus-I Bus-II Line
400kV Hoody-
1 Yelahanka Line R-N 61.9 62 59.8 0 0 59.7
Y-N 62.5 62.5 59.4 0 0 52.9
B-N 61.3 61.9 58 0 0 48.9
400kV Hoody-Nlm
1 Line R-N 61.9 62 0 0
Y-N 62.5 62.5 0 0
B-N 61.3 61.9 0 0
Note: Measurement to be carried out simultaneously for same phase of Bus CVTs and Line CVTs with 0.2 class multimeter. R
be rechecked at switchyard
Note: Permissible limits for CVTs used for purposes other than metering. For CVTs used for commercial metering accuracy cl
Drift in secondary
voltage (to be
measured by 0.2/0.5 Measurement
Sl No. class multimeter) Condition frequency
06 Monthly
1 Upto +/- 0.5 Volts Healthy Monitoring

To be 03 Monthly
2 0.5volts to +0.8 Volts Monitored Monitoring
Close
3 0.8Volts to +1.2Volts Monitoring Monthly
Close
4 1.2Volts to 2.0Volts Monitoring 15 days

5 Above 2Volts Alarming Replacement


Close
6 (')-0.8Volts to -4Volts Monitoring 15 Days
Values volts for Core-3 Core-1 Variation WRT Core-2 Variation WRT Core-3 Variation WRT
Bus-I Bus-II Line Bus-I Bus-II Bus-I Bus-II Bus-I Bus-II

62.1 61.9 59.8 -2.1 -2.2 -2.3 -2.1


62.8 62.6 59.4 -3.1 -3.1 -3.4 -3.2
61.5 62 42.2 -3.3 -3.9 -19.3 -19.8

62.1 61.9 -61.9 -62 -62.1 -61.9


62.8 62.6 -62.5 -62.5 -62.8 -62.6
61.5 62 -61.3 -61.9 -61.5 -62
VTs with 0.2 class multimeter. Readings to be taken from control panel. In case of discrepency, the readings should

ommercial metering accuracy class limits to be followed


CAPACITIVE VOLTAGE TRANSFORMERS - 6MONTHLY ACTIVIT
Measurement of voltage
Date of Last calibration:
Values volts for Core-1
Sl No. Name of the feeder/Bay Measurement
Bus-I Bus-II Line
1 220kV Hoody-HAL Line-2 R-N 62.2 62.4 61.6
Y-N 62.5 60.9 62.0
B-N 62.1 61.6 61.6
2 220kV Hoody-HAL Line-1 R-N 62.2 62.4 61.7
Y-N 62.5 60.9 62.1
B-N 62.1 61.6 61.7
3 220kV Hoody-HSR Line R-N 62.2 62.4 61.4
Y-N 62.5 60.9 59.4
B-N 62.1 61.6 62
4 220kV Hoody-EPIP Line R-N 62.2 62.4 61.5
Y-N 62.5 60.9 62.2
B-N 62.1 61.6 59.2
4 220kV Hoody-ITPL UG Cable R-N 62.2 62.4 61.3
Y-N 62.5 60.9 62
B-N 62.1 61.6 61.5

Note: Measurement to be carried out simultaneously for same phase of Bus CVTs and Line CVTs with 0.2 class multimeter. R
the readings should be rechecked at switchyard
Note: Permissible limits for CVTs used for purposes other than metering. For CVTs used for commercial metering accuracy cl
Drift in secondary voltage (to
be measured by 0.2/0.5 class Measurement
Sl No. multimeter) Condition frequency
06 Monthly
1 Upto +/- 0.5 Volts Healthy Monitoring
03 Monthly
2 0.5volts to +0.8 Volts To be Monitored Monitoring
3 0.8Volts to +1.2Volts Close Monitoring Monthly
4 1.2Volts to 2.0Volts Close Monitoring 15 days
5 Above 2Volts Alarming Replacement
6 (')-0.8Volts to -4Volts Close Monitoring 15 Days
ANSFORMERS - 6MONTHLY ACTIVITY

Date: 20.11.2019
Values volts for Core-2 Core-1 Variation WRT Core-2 Variation WRT
Bus-I Bus-II Line Bus-I Bus-II Bus-I Bus-II
62.4 62.4 61.6 -0.6 -0.8 -0.8 -0.8
62.2 60.9 61.9 -0.5 1.1 -0.3 1
62.4 61.5 61.6 -0.5 0 -0.8 0.1
62.4 62.4 61.7 -0.5 -0.7 -0.7 -0.7
62.2 60.9 62 -0.4 1.2 -0.2 1.1
62.4 61.5 61.7 -0.4 0.1 -0.7 0.2
62.4 62.4 61.4 -0.8 -1 -1 -1
62.2 60.9 59.3 -3.1 -1.5 -2.9 -1.6
62.4 61.5 62 -0.1 0.4 -0.4 0.5
62.4 62.4 61.5 -0.7 -0.9 -0.9 -0.9
62.2 60.9 62.2 -0.3 1.3 0 1.3
62.4 61.5 59.2 -2.9 -2.4 -3.2 -2.3
62.4 62.4 61.3 -0.9 -1.1 -1.1 -1.1
62.2 60.9 62 -0.5 1.1 -0.2 1.1
62.4 61.5 62.1 -0.6 -0.1 -0.3 0.6

ne CVTs with 0.2 class multimeter. Readings to be taken from control panel. In case of discrepency,

or commercial metering accuracy class limits to be followed