You are on page 1of 130

Integrated design semester project

ADVISOR APPROVAL SHEET


This is to that the students has full filled all the requirements of the program and they can
submit to the department for open defense

Jonathan K. ___________ __________


Name of principal advisor Signature date

EXAMINERS’ APPROVAL SHEET


We, the under signed members of the board of examiner of the integrated design project
defense by have read and evaluated their project entitled by G+4 hospital building and
examined the candidate oral presentation .theses therefore we certify the report has been
accepted for the fulfillment of the program objectives.

1. ______________ ________________ _____________


Examiner name signature date

2. _____________ ______________ _______________


Examiner name signature date

Structural design for G+4 hospital building Page i


Integrated design semester project

Table of Contents

CHAPTER ONE.........................................................................................................................................1

1.1. ROOF ANALYSES AND DESIGN................................................................................................1

1.1. ROOF WIND LOAD ANALYSIS..............................................................................................1

1.2. NET WIND LOAD ON DOU PICTH........................................................................................6

1.3. DOUPITCH ROOF DESIGN......................................................................................................10

1.4. ANALYSIS DESIGN OF EGA SHEET..........................................................................................10

1.3.2. ANALYSIS AND DESIGN OF PURLIN...............................................................................15

CHAPTER TWO......................................................................................................................................29

2. SLAB ANALYSIS AND DESIGN........................................................................................................29

2.1. Depth of slab for deflection requirement.............................................................................29

2.2. DESIGN LOAD DETERMINATION FOR SLAB...........................................................................34

2.3. DESIGN MOMENT DETERMINATION.....................................................................................40

2.4. REINFORCEMENT DESIGN FOR SLAB.....................................................................................53

2.5. DESIGN 0F GROUND FOOL SLAB...........................................................................................60

CHAPTER THREE...................................................................................................................................64

3. STAIRCASE ANALYSIS AND DESIGN...............................................................................................64

3.1. STAIR LOAD ANALYSIS...........................................................................................................65

CHAPTER FOUR.....................................................................................................................................75

4. FRAME ANALYSIS AND DESIGN.........................................................................................................75

4.1. BEAM DESIGN.......................................................................................................................75

4.1.1. Design of beam for flexure...........................................................................................75

4.1.2. Beam design for shear..................................................................................................87

4.1.2. Development length.....................................................................................................93

4.2. COLUMN DESIGN..................................................................................................................94

4.2.1. DESIGN FOR FLEXURE...................................................................................................95

Structural design for G+4 hospital buildingPage ii


Integrated design semester project

4.2.2. Design of column for shear...........................................................................................99

CHAPTER 5..........................................................................................................................................103

5. Footing Design............................................................................................................................103

5.1.1. LOAD CALCULATION...................................................................................................103

5.1.2. DETERIMINATION OF EFFECTIVE DEPTH.....................................................................106

5.1.3. CHECK DEPTH FOR FLEXTURE.....................................................................................108

Structural design for G+4 hospital buildingPage iii


Integrated design semester project

CHAPTER ONE

2.1. ROOF ANALYSES AND DESIGN


In the design of roof the major loads which are applied on roof are wind load and live load.
The action of wind can be of the type of suction or pressure to our structures both externally
or internally. However these effects are more magnified for structures with more openings
and large surface areas. Therefore our focus is on the most sensitive part of the building that is
the roof.

1.1. ROOF WIND LOAD ANALYSIS

The net wind pressure across a wall or an element is the difference of the pressures on each
surface taking due account of their signs. (Pressure, directed towards the surface is taken as
positive, and suction, directed away from the surface as negative). (EBCS 1, 1995 Section
3.5.4.1)

WIND PRESSURES.

A. External pressures

The wind pressure acting on the external surface of a structure shall be obtained from

We=qref. *Ce(Ze)* Cpe--------------------------------------------------EBCS1,1995 Art 3.5.2

qref = Reference mean wind velocity pressure.

Ce (Ze) = exposure coefficient accounts for the terrain and height above ground,

Ze = reference height appropriate to the relevant pressure coefficient.

Reference mean wind velocity pressure, (qref)

qref= ρ/2 * Vref2

Where:-

Vref = reference mean wind velocity

ρ = density of air at T0c (200c adopted for Ethiopia)

Reference Mean wind velocity,(Vref )

Structural design for G+4 hospital buildingPage 1


Integrated design semester project

The reference wind velocity vrei is defined as the 10 minute mean wind velocity at 10m
above

ground of terrain category II (see Table 3.2) having an annual probability of exceedence of
0.02

(commonly referred to as having a mean return period of 50 years

Vref=CDIR*CTem*CAlt*Vrefo

Where:-

Vref0 = is the basic value of the reference wind velocity to be taken as 22m/s.

CDIR = is the directional factor to be taken as 1.0.

CTem= is the temporary seasonal factor to be taken as 1.0.

CAlt= is the altitude factor to be taken as 1.0.

Vref=1.0*1.0*1.0*22m/s =22m/s

Density of air, ρ

The air density is affected by altitude and depends on the temperature and pressure to be
expected in the region during wind storms. A temperature of 20°C has been selected as
appropriate for Ethiopia and the variation of mean atmospheric pressure with altitude is given
in

Wolaita sodo is found 1600m above sea level

Structural design for G+4 hospital buildingPage 2


Integrated design semester project

ρair=0.98 Kg/m3 This value obtained by interpolation

Therefore Reference mean wind velocity pressure, (qref)

0.98 kg/m3 m 2
qref = ∗(22 2 ) =237.16N/m2
2 s

Exposure coefficient

The quasic – static gust load can be computed from Sec. 3.8.5 (EBCS 1/95)

[
C e (z )=C 2 ( z )C 2 ( z ) 1+
r t
7KT
C r ( z )C t ( z ) ]
Where:

KT= the terrain factor as defined in sect.3.8.2 EBCS 1/95

Cr (z) = is the roughness coefficient as defined in sect.3.8.3 EBCS 1/95

Ct(z) = is the topography coefficient as defined in sect.3.8.4 EBCS 1/95

Roughness coefficient

Cr (Z) = KT ln (Z/Z0).............................for Zmin≤Z≤200m

Cr (Z) = Cr (Zmin).................................for Z< Zmin

Where:

Z0 = 0.3 for Wolaita sodo case (sub-urban area) roughness length

Zmin= 8 Minimum height which depends on the terrain category

Z= 16m total height of the building

Terrain category

Wolaita sodo is the sub urban municipality. Hence, it is a train category III and the related
parameters are:

Kt =0.22,

Structural design for G+4 hospital buildingPage 3


Integrated design semester project

Z0 =0.3m

Zmin =8m ------------------------------(EBCS 1/95) Art 3.8.3

Cr(z) = 0.2ln(16/0.3) = 0.335

Topography coefficient, Ct

By assuming the zone is not affected due to topographic condition. Hence, it has to be taken
as unity. i.t

Ct=1.0 --------------- for Ø<0.05

Therefore the exposure coefficient would be

[
C e (z )=C 2 ( z )C 2 ( z ) 1+
r t
7KT
C r ( z )C t ( z ) ]
2 2
Ce (Z) = 0.335 ¿ 1 1+ ( 7∗0.22
0.14∗1 )
= 1.347

External wind pressure coefficient

The exposure coefficient is taken on the basis of the area considered

Cpe = Cpe, 1. When A <1 m2

Cpe = Cpe, 1 + (Cpe, 10 - Cpe, 1) logA When 1<A<10 m2

Cpe = Cpe, 10 When A>10 m2

The external wind pressure for different zones is tabulated as below

or different cases of θ

Roof category – Duo pitch

The code recommends the roof to be divided into zones as shown below for θ = 00

Case– І , θ = 00

e = b or 2h which so ever small

where b is cross wind direction

Structural design for G+4 hospital buildingPage 4


Integrated design semester project

External Pressure Coefficient, θ = 00

For duo pitch roofs with different pitch angle, α, External pressure coefficients has been
recommended in table A-4. Interpolations have been made between pitch angle 50 and 150.

Pitch angle calculation

α 2.5m

9.5m

opp 2.5
tanα = =
adj 9.5

2.5
α = tan-1( ) =150
9.5

Area calculation of each zone

b = 10m h = 18.5m d = 19m

Where: e = {2h=2∗18.5=37
b=10
which so ever small

Äe = 10m

e 10 e 10
= = 2.5 = =1
4 4 10 10

Area calculation for each zone

AF=2.5*1=2.5m2

Structural design for G+4 hospital buildingPage 5


Integrated design semester project

AG=5*1=5m2

AH=7*10=70m2

AI=8.5*10=85m2

AJ=1*10=10m2

Area of zone G and zone J is between 1m2 and 10m2

Zone G

Cpe (−ve )=−2+ (−0.9+2 ) log 5=−¿ 1.16

Cpe ( +ve )=0.2+ ( 0.2−0.2 ) log 5=0.2

1.2. NET WIND LOAD ON DOU PICTH

Cpi (internal pressure coefficient)

Cpi depends on

1. Building without internal partition

2. Building with internal partition

Therefore our building has partition

Cpi= +0.8

-0.5

Sample calculation for (Cpe-Cpi)

Zone F→-2+0.8=-1.2

→-2-0.5= -2.5 → is maximum value

→0.2+0.8=1

→0.2-0.5=-0.3

Wnet =We –Wi

Wnet = Ce (ze) * Cpe * qref – Ce (zi) *Cpi *qref

Wnet = Ce (ze)*qref*(Cpe-Cpi)

Structural design for G+4 hospital buildingPage 6


Integrated design semester project

The net external wind pressure for different zones is tabulated as below

or different cases of θ=00

We = 237.16*1.347* (Cpe-Cpi)

WNET = 0.32(Cpe –Cpi)KN/m2

Zone Cpe 10 Cpe 1 Cpe Cpi Cpe-Cpi Wnet


s

F -0.9 -2 -2 0.8 -2.5 -0.8

0.2 0.2 0.2 -0.5

G -0.8 -1.5 - 0.8 -1.66 -0.53


1.16

0.2 0.2 0.2 -0.5

H -0.3 -0.3 -0.3 0.8 1 0.32

0.2 0.2 0.2 -0.5

I -0.4 -0.4 -0.4 0.8 -0.9 -0.29

0 0 0 -0.5

J -1 -1.5 -1 0.8 -1.50 -0.48

0 0 0 -0.5

The governing wind pressure of case-1 on zones of doupitch roof is -0.8KN/m2

Case –II b, θ = 900

Structural design for G+4 hospital buildingPage 7


Integrated design semester project

b = 19m h = 18.5m d = 10m

Where: e = {2h=2∗18.5=37
b=19
which so ever small

Äe = 19m

e 19 e 19 e 19
= = 9.5 , = = 4.75 , = = 1.9
2 2 4 4 10 10

Area calculation

AF = 1.9*4.75 = 9.03 m2

AG = 4.75*1.9 = 9.03 m2

AH = 9.5*5 = 47.5 m2

AI = .5*9.5 = 4.75m2

The external wind pressure for different zones is tabulated as below

or different cases of θ=00

we = qref Ce (Ze) Cpe

=237.16*1.347*Cpe

we = 319.45*Cpe N/m2

Cpe=Cpe ,1 if Azone <1 m

Cpe=Cpe ,1+ ( Cpe , 10−Cpe , 1 ) logA

Cpe=Cpe ,10 ≥ 10 m

Area of zone F and zone G is between 1m2 and 10m2

Cpe=Cpe ,1+ ( Cpe , 10−Cpe , 1 ) logA

Structural design for G+4 hospital buildingPage 8


Integrated design semester project

For zone F

Cpe = -2+(-1.3+2)log9.03=-1.33

Cpe = -2+(-1.3+2)log9.03=-1.33

Cpi (internal pressure coefficient)

Cpi depends on

1. Building without internal partition

2. Building with internal partition

Therefore our building has partition

Cpi = {−0.5
+0.8

Sample calculation for (Cpe-Cpi)

Zone F→-1.33+0.8=-0.53

→-1.33-0.5=-1.83

Wnet =We –Wi

Wnet = Ce (ze) * Cpe * qref – Ce (zi) *Cpi *qref

Wnet = Ce (ze)*qref*(Cpe-Cpi)

For α=15° and Ө=90⁰

Zone Area(m2) Cpe,10 Cpe,1 Cpe Cpi Cpe-cpi Wnet

F 9.03 -1.3 -2 -1.33 -0.5 -1.83 -0.59

0 0 0.8

G 9.03 -1.3 -2 -1.33 -0.5 -1.83 -0.59

0 0 0 0.8

Structural design for G+4 hospital buildingPage 9


Integrated design semester project

H 47.5 -0.6 -1.2 -0.6 -0.5 -1.1 -0.352

0 0 0 0.8

I 4.75 -0.5 -0.5 -0.5 -0.5 -1 -0.32

0 0 0 0.8

Wnet =0.549*(Cpe –Cpi )

The maximum value of cpe-cpi=-1.83

Wnet=0.32*(-1.83)= -0.59KN/m2

The governing wind pressure of case-1 on zones of doupitch roof is -0.59KN/m2

The governing wind load of case-2 on doupitch roof zone is -1.09KN/m2

Case-1→ -1.09 KN/m2

Case-2→ -0.59 KN/m2

2.2.

2.3. DOUPITCH ROOF DESIGN

2.4. ANALYSIS DESIGN OF EGA SHEET


Use EGA sheet-500 so the relevant data from Kaliti steel manual

Structural design for G+4 hospital buildingPage 10


Integrated design semester project

Thickness=0.5mm

Width=782mm

Effective width=712mm

Weight=3.92Kg/m(for uncoated sheet)

Moment of inertia=99966m m4

Section modulus=4684m m3

Ixx =127833

Sx=5990

Purlin =1.3m

L L
Truss spacing can be taken to where L is the shorter side of the roof (EBCS 3, 1995)
5 3

10 10
=2 m¿ =3.33m
5 3

Structural design for G+4 hospital buildingPage 11


Integrated design semester project

Take c/c spacing of truss member as 2.6m

Components of load on EGA sheet

1. Dead load on EGA sheet

Note: Weight of each coated sheet (galvanized sheet) is at least 0.38Kg/m2 (max 0.76Kg/m2)
heavier than the weight of uncoated sheet. Load on EGA-sheet per meter.

3.92 Kg
∗9.81m 0.38 kg 0.76 Kg
m + m KN
Gk = 2 + m2 m
2
*9.81 2 = 0.0596 2
s s m
2
0.712 m

Live load:

Roof is not accessible for serviceability except for normal maintenance, repair, painting
&minor repair. Therefore, roof category is H. (Table 2.13, EBCS-1, 1995) and for this roof
category the live loads (Imposed load) on the sloping roofs are (from Table 2.14, EBCS-1,
1995):

KN
• LL (distributed) =0.25
m2

KN
Over a meter length of the purlin: LL (distributed) =0.25*1.3m= 0.325
m

0.325KN/m

Structural design for G+4 hospital buildingPage 12


Integrated design semester project

2.6m

0.325 KN
w l2 ∗( 2.6 m )2
M= = m =0.275KNm/m
8
8

LL (Concentrated) =1 KN Determining the governing live load:

For concentrated LL

1KN

2.6m

M=pl/4=1KN*2.6m/4= 0.65KNm

The governing live load is the concentrated live load. Thus, LL= 1 KN Therefore;

1 KN KN
Therefore:Qk= =1.279
0.782 m m

Case-I Load Perpendicular to EGA-sheet

Pitch angle α =15 °

0.058 KN
Gκ =0.0596 KN∗cos 15 ˚=
m2

Qk=1.279KN/m*cos15˚=1.235KN/m

Case-II Loads Parallel to EGA sheet

0.015 KN
Gκ =0.0596 KN∗sin 15= 2
m

Qk=1.279KN/m*Sin15=0.331KN/m

Therefore use the maximum load from the above two cases for design.

Gk=0.058KN/m2

Structural design for G+4 hospital buildingPage 13


Integrated design semester project

Qk=1.235KN/m

Load combination

Case-I: Under dead and live loads

Pd=1.3 DL+1.6≪¿

(1.3∗0.058 ) KN ( 1.6∗1.235 ) KN
Pd= + =0.075KN/m2+1.976KN/m
m 2
m

Pd= (0.075KN/m2*0.782m) + (1.976KN/m*0.782m)

Pd=0.059KN/m +1.545KN

We have purlin spacing of 1.3m

0.059 KN 2
∗( 1.3m )
w l 2 pl m 1.545 KN∗1.3 m
M= + = + =0.514 KN . m
8 4 8 4

0.059 KN
∗1.3 m
wl p m 1.545 KN
V= + = + =0.812 KN
2 2 2 2

Case-II under Dead and wind loadings

Pd=0.9 DL+1.6 Wk But Wk=-1.09KN/m 2 critical value net wind pressure.

Pd =0.9*0.059KN/m*0.782m +1.6*(-1.09KN/m)*0.782m

Pd = (0.042-1.364) KN= -1.32KN

PL −1.32∗1.3
M= = KN . m=−0.499 KNm
4 4

P 1.32 KN
V= = =−0.66 KN
2 2

Case-III under Dead, Live and Wind load

Wy=1.3 Gk+1.35 (Qk+Wk)

¿ 1.3∗0.059 KN / m+1.35∗1.235 KN +1.35∗(−1.09 KN /m)

=-1.472KN/m+1.744KN

Structural design for G+4 hospital buildingPage 14


Integrated design semester project

−1.472 KN
2 ∗( 1.3 m )2
w l pl m 1.744 KN∗1.3 m
M= + = + =0.256 KN . m
8 4 8 4

−1.472 KN
∗1.3 m
wl p m 1.744 KN
V= + = + =−0.0848 KN
2 2 2 2

Take the maximum Governing moment from three cases. Mmax=-0.514KNm

Capacity of EGA Sheet-500 from Kaliti steel manual can be

Section modulus SM=4684m m3

Allowable Stress δall=160 MPa

Moment of Inertia=99966m m4

Check Capacity of EGA sheet

Mmax 0.514∗1 06 Nmm


δ= = 3
=109.74 MPa< δall=160 MPa....ok!
SM 4684 m m

l 1300 mm
For Deflection: Δall= = =6.5 mm
200 200

5 wl 4 P l3
Δactual= + Where w+p= 0.059KN/m+1.545KN
384 EI 48 EI
3 3
1.545∗1 0 N∗( 1300 mm )
5∗0.059 N
Δactual= ∗¿ ¿+ 48∗210000 N = 3.47mm
mm 2
∗99966 mm4
mm

3.47mm¿ 6.5 mm … . ok

1.3.

1.3.1.

1.3.2. ANALYSIS AND DESIGN OF PURLIN

Purlin c/c spacing =1.3m

Truss c/c spacing =2.6m

Structural design for G+4 hospital buildingPage 15


Integrated design semester project

Height of truss=2m

Pitch angleα =15 °

There are three loads to be considered for design of a purlin:

Wind load

Wind load acting on a purlin will be a load which comes from 1.3m width; that is half from
each side of the purlin spacing.

Wind load over a meter length of the purlin will be:

WL (-ve)=1.3m*-1.09KN/m2 = -1.417KN/m.

Live load:

Roof is not accessible for serviceability except for normal maintenance, repair, painting
&minor repair. Therefore, roof category is H. (Table 2.13, EBCS-1, 1995)

And for this roof category the live loads (Imposed load) on the sloping roofs are (from Table
2.14, EBCS-1, 1995):

LL (distributed)=0.25 KN/m2

Over a meter length of the purlin: LL (distributed)=0.25*1.3=0.325KN/m

LL (Concentrated)=1 KN

Determining the governing live load:

Effective length of the purlin is taken to be the spacing of the truss, i.e. =3m.

For distributed live load:


2
w∗l 2 0.325 KN /m∗(2.6 m)
M= = = 0.275KNm
8 8

For Concentrated live load

P∗l 1 KN∗2.6 m
M= = = 0.65KNm
4 4

The governing live load is the concentrated live load. Thus, LL= 1 KN

C Dead Load:

Structural design for G+4 hospital buildingPage 16


Integrated design semester project

Dead load of the purlin:

From the Kaliti Steel manual take ST60 (Square Tube: 60 mm*60 mm*3.5mm) as the first
design trial section.

For this section we have:

weight per meter=5.96Kg/m

Area of the section=7.59c m4

I=39.56c m4

S=13.18cmc m3

R=2.28cm

Kg m KN
DL(purlin)=5.96 *9.81 2 * =0.0585 KN/m
m sec 1000 N

Structural design for G+4 hospital buildingPage 17


Integrated design semester project

Dead load of the EGA Roofing:

Type: EGA-500 with thickness of 0.5mm with a mass of 3.92Kg/m

{ }
2
3.92 Kg /m∗9.81 m/ sec
∗KN
DL(EGA roof)= 1 *1.3m=0.05KN
1000 N

To determine per meter load the weight is divided by width of the sheet

DL(EGA roof )DL= 0.05KN/0.782m=0.064 KN/m

Total DL=0.05+0.064=0.114KN/m

NB: The wind pressure acts perpendicular to the surface while the DL and LL are acting
vertically downward. DL & LL Y-AXIS

WL

Resolve the load into two components:

X-component

DLx=0.114KN/m*sin15=0.03KN/m

LLx=1KN*sin15 =0.26KN

Y-Component

DLy=0.114KN/m*cos15=0.11KN/m

LLy=1KN*cos15=0.966KN

WL (-ve) =-1.417KN/m

Load combinations & Computation of Bending moment and Shear

Safety factors for favorable and unfavorable load conditions indicated below are adopted from
section 1.9.4.3, table 1.2 of EBCS, 1/1995.

Structural design for G+4 hospital buildingPage 18


Integrated design semester project

γDL= 0.9 for favorable condition (permanent)

γDL = 1.30 for unfavorable condition (permanent)

γ LL = γ DL= 1.60 for live and wind loads

X- Direction:

w x= 1.3 DL + 1.6 LL= 1.3*0.03KN/m + 1.6*0.26 KN= 0.039KN/m + 0.416 KN

The respective bending moment and shear are:

0.039 KN 2
w∗l 2 P∗l ∗( 2.6 m) 0.416 KN∗2.6 m
Mx= + = m + = 0.3KNm
8 4 4
8

W∗l P 0.039 KN /m∗2.6 m 0.416 KN


V x= + = + = 0.259KN
2 2 2 2

Y- Direction:

Case I: Under Dead and Live loadings

Governing live load: Concentrated live loading (determined earlier)

Therefore, unfavorable condition is adopted for analysis. (γDL= 1.3 & γ LL = 1.60)

Wy= 1.3*DL + 1.6*LL= 1.3*0.11KN/m + 1.6* 0.966KN = 0.143KN/m + 1.546KN

The respective bending moment and shear are:

0.143 KN 2
2
w∗l P∗l ∗( 2.6 m) 1.546 KN ∗2.6 m
M y= + = m + = 1.126 KN.m
8 4 4
8

W∗l P 0.143 KN /m∗2.6 m 1.546 KN


V y= + = + = 0.959KN
2 2 2 2

Case II: Under Dead and Wind loadings

For negative wind load

Wy= 0.9*DL + 1.6 WL (-ve) = 0.9*0.11 + 1.6*-1.417KN/m= -2.17KN/m

The respective bending moment and shear are:

Structural design for G+4 hospital buildingPage 19


Integrated design semester project
2 2
w∗l −2.17 KN /m∗(2.6 m )
M x= = = -1.83KNm
8 8

−2.17 KN
W∗l ∗2.6 m
V y= = m = -2.82KN
2
2

The maximum values are: M max= -1.83KNm and V max=-2.82KN

Class of Cross-section (EBCS-3, 1995 Table 4.1)

Flange

c= B- 3tw = 60-3(3.5) = 49.5 mm

tf= 3.5 mm

ε = √ 235/f y

Use steel grade Fe430 and for, t<40mm, yield stress fy = 275 N/mm2 …EBCS3, 1995 Table
3.1

ε= √ 235/ 275 = 0.9244

{c/tf= 49.5/3.5= 14.14}< {26ε= 26*0.9244=24.03}

Therefore, the element is class- I.

Web with neutral axis at mid depth

d H−3 tf 60−3 (3.5)


{t = t = = 14.14}< {79 = 73.03}
w w 3.5

Therefore, the element is Class-I (plastic).

Checking the section:

1. Check for flexure:

Flexural resistance of the section:

* = 13.18*103mm3* =3.295
KNm.

Structural design for G+4 hospital buildingPage 20


Integrated design semester project

Mmax (-2.324KNm¿ mpl , Rd=3.295 KNm)……OK

2. Check for shear

Plastic shear resistance of the section (vpl,Rd)

=A (fy/ 3 )/γ = (7.59 cm2 *100/cm2 (275/ 3 ))/1.1=109.55KN

= -3.575/109.55=0.033< 0.5 ----- (OK!)

3. Check for deflection

Deflection due to uniform load:

Deflection due to concentrated load at mid-span:

Deflection in the x: wx=0.039KN/m + 0.416 KN

5 1
∗0.039∗( 2.6 ) ∗0.416∗( 2.6 )
4 3
384 48
δx= 6 −8
+ 6 −8
=¿2.08mm
210∗10 ∗39.56∗10 210∗10 ∗39.56∗10

Deflection in the y:

Case 1: wy=0.0.43KN/m + 1.546KN

1 3
4 ∗1.546∗2.6
5∗0.43∗2.6 48
δy 1= 6 −8
+ 6 −8
=9.88 mm
384∗210∗10 ∗39.56∗10 210∗10 ∗39.56∗10

Case 2: w y=-2.75KN/m

5 4
∗−2.75∗2.6
384 = -11.92mm
δy 2= 6 −8
210∗10 ∗39.56∗10

The governing deflection in the y: -11.92mm

Structural design for G+4 hospital buildingPage 21


Integrated design semester project

δ=√ δ x +δ y =√ ( 2.08 mm ) + ( 11.92 mm ) =12.1mm


2 2 2 2

Recommended limiting value for deflection as per EBCS-3/95 for roofs generally:

l 2600mm
= =13 mm
= 2 oo 200

 (OK!)The trial section is safe!

ANALYSIS OF TRUSS

Loads:

Loads on the purlin are: WL= -1.417KN/m; DL= 0.114 KN/m and LL= 1 KN Load coming
from the purlin is transferred to a truss in the form of reaction.

Critical Length of purlin= truss spacing =2.6m

Wind load transferred to intermediate truss from purlin

R WL = (-1.417 KN/m * 2.6m) = -3.68KN (shows outward direction)

This load will be resolved into components into the horizontal and vertical plane to make
computations by SAP 2000 easier. The signs are provided in accordance with global
coordinate.

Pitch angles: = 15

R WL,X= 3.68*sin15 = 0.952KN

R WL,Y= 3.68*cos15 = 3.55KN

Live load transferred to intermediate truss from purlin

Governing live load on the purlin: LL= 1 KN acting at the mid-span

RLL= 1KN

Dead load transferred to intermediate truss from purlin

R DL = (0.114KN/m * 2.6 m) = 0.296KN

There are other dead loads that act on the truss:

Structural design for G+4 hospital buildingPage 22


Integrated design semester project

Self-weight of the truss members

Weight of the chip wood ceiling and ceiling batten.

Dead load of chip wood ceiling (chip board):

Properties: Unit wt, γ=8 KN/m3; Thickness, t=2 cm=0.02 m; width=2.6m,

Length = 9.5 m (length of truss)

Wt=γ*t*(length of truss)*(truss spacing) =8*0.02 *9.5*2.6 =3.92KN

Dead load of ceiling battens:

Cross section: 40mmx50mm

Spacing c/c=60mm

Number of ceiling battens:

2.6
In the truss direction= 0.6 +1= 4.33 Use: 5 battens

9.5
In the other direction= + 1=16.83Use: 17 battens
0.6

Length of ceiling battens is =5*9.5+17*2.6 = 91.7m

Unit weight = 6KN/m3

Weight of batten=5*0.04*0.05*=0.92KN

Total load at the bottom of the truss Joints

DL of chip wood ceiling +DL of ceiling batten= 3.92+0.92 = 3.8KN

No of Joints at the bottom along truss direction= 9 (2 exterior + 7 interior)

7x+2(x/2) =3.8KN, x=0.48 and x/2=0.24

Therefore:-

Joint load (interior) = 0.48KN

Joint load (exterior) = 0.24KN

Load combinations:

Structural design for G+4 hospital buildingPage 23


Integrated design semester project

COMB1= 1.3 DL+ 1.6LL

COMB2= 0.9DL + 1.6WL

COMB3=1.3DL+1.35(LL+WL)

Summarized loads

R WL,Y= = -4.47KN(interior)(outward)

R WL,Y =- 2.235KN(exterior) (outward)

R WL,X = 1.2KN(interior) (outward)

R WL,X = 0.6KN(exterior) (outward)

R DL = 0.296KN(interior)

R DL = 0.148KN(exterior)

Joint load due to ceiling (interior) = 0.48KN(interior)

Joint load due to ceiling (exterior) = 0.24KN(exterior)

RLL= 1KN (interior)

RLL= 0.5KN(exterior)

TRUSS LAYOUT

Fig ETABS RESULT

Table. xx. Duo pitch Truss Output

Structural design for G+4 hospital buildingPage 24


Integrated design semester project

Axial forces
Bending
Elements Section Shear (KN) moments
Compression Tension
(KNm)
(KN) (KN)

(50*50*2)m
(Principal rafter ) -36.65 29.37 0.17 0.19
m

(50*50*2)m
(bottom chord) -20.44 29 0.17 0.18
m

(50*50*2)m
(strut) -9 20.97 0.11 0.1
m

(50*50*2)m
(Side Post) -12.85 21.57 0.25 0.06
m

. Checking the adequacy of the provided sections of truss

Here we take the maximum effects of load from the Doupitch and hipped roof analysis.

Section: 50 mm* 50 mm* 2mm

Maximum design axial compression (N csd)= -36.65 KN

Maximum design axial tension (N tsd)= 29.37KN

Design Moment (M sd) = -0.19 KNm

Design Shear (V sd) = 0.25KN

For axial tension with moment

Section properties:

A=3.74 cm2, I=14.15 cm4, r=1.95 cm, =5.66 cm3,

Resistance of Cross-section

Structural design for G+4 hospital buildingPage 25


Integrated design semester project

Resistance to tension:

N
374 mm2∗235 2
N pl , Rd = A∗fy mm …… (The section is adequate for
= =79.9 KN ≥ N t , sd
ᵧmo 1.1
tension!)

Resistance to pure bending:

w pl ∗f y 5.66∗10 3∗235
M pl , Rd= = = 1.209 KNm≥ M sd =0.19 (The section is adequate for
ᵧ mo 1.1
flexure!)

Resistance to shear:

fy
A v∗( )
V pl , Rd= √ 3 ; Av=(h-3tf)*tw = (80-3*3)*3= 213KN
ᵧmo

213∗235
V pl , Rd= √3 = 26.67 KN≥ Vsd ……. (The section is adequate for shear!)
1.1

Check the interaction equation:

N sd M y , sd M z , sd
+ + ≤1
N pl ,Rd M ply , Rd M plz , Rd

There is no bending moment about the minor axis. The above interaction equation is
N sd M y , sd
simplified to: + ≤1
N pl ,Rd M ply , Rd

N sd M y , sd 36.65 0.19
+ = + = 0.616≤ 1 (OK!)
N pl ,Rd M ply , Rd 79.9 1.209

For axial compression with moment

Classify the section: (Euro CODE 3 Table 5.3.1 for ST with combined action compression
and moment)

For Fe360, f y = 235 N/mm2

ε= √ 235/fy = √ 235/235=1

Structural design for G+4 hospital buildingPage 26


Integrated design semester project

b−3∗t w 50−3∗2
Flange: = =22≤ {33 ε=33}…. Class 1
tf 2

h−3 t f 50−3∗2
Web: = =22≤ {33 ε=33}…. Class 1
tw 2

The whole section is class 1 and plastic design is adopted.

Effective length:

L eff= L= 1300mm

Resistance of the cross-section:

Resistance to compression

N pl , Rd=79.9 KN ≥ N c , sd … (The section is adequate for compression!)

The adequacy of the section for bending and shear is already checked!

Stability of the member against axial force and the moment:

Buckling resistance of axially loaded compression member

The design buckling resistance of compression member shall be taken as follows

x β A∗A∗f y
N b , Rd = ………….………………… EBCS 3/1995 Article 4.5.42
rmo

βA =1 for class 1

𝒙 = reduction factor for relative bucking

Determination of 𝒙 value

λ1 = 93.9ε = 93.9*1 = 93.9

Slenderness ratio:

λ = Leff /r = 1300/19.5 = 66.67

Hence, the non-dimensional slenderness ratio can be determined as

λ= ( )
λ
λ1
∗√ βx=
66.67
93.9
∗√ 1=¿ 0.71

Structural design for G+4 hospital buildingPage 27


Integrated design semester project

From Table 4.11, EBCS-3/1995, Art 4.5.4.3


¿∗¿¿
For cold formed hollow section the appropriate buckling curve is by using fyb : curve b.

From table 4.9 the corresponding 𝒙 -values for λ = 0.71 by using interpolation

𝒙=0.778

x∗βx∗A∗fy 0.778∗1∗374∗235
N b , Rd = = =62.16 KN ≥ N c ,sd =36.65….. (OK!)
rm1 1.1

Lateral torsional buckling of a bending member

x¿∗β w∗w pl∗f y


M b, Rd= ; x ¿= func(Mcr)
ᵧmo

2 2 0.5
C1∗π ∗E∗I z I w L ∗G∗I t
M cr= *( + )
L
2
I z π 2∗E∗I z

C 1=1.0356 (for the loading condition of the truss member in accordance with EBCS-3 tables
4.12 and 4.13)

E= 210 GPa = 210*103 N/mm2

G= 80 GPa =80*103 N/mm2

I z = 14.15*104mm4

I z∗( h−t f ) 2 4
14.15∗10 ∗(50−2)
2
I w= = = 8.15*107 mm6
4 4

I t= 22.3 cm4 = 22.3*104 mm4

Substituting: M cr = 57.5KNm
2 0.5
π ∗E∗w pl π 2∗210∗10 3∗5.66∗103
λ ¿=( ) =( 6
¿0.5=451.45 mm
M cr 57.5∗10

λ ¿=
( )
λ¿
λ1
∗√ βw = (
451.45
93.9 √
) 1 = 4.81

2
Ø=0.5 (1+ ( λ¿ −0.2 ) + λ ¿ ),

For a buckling curve b: =0.34

Structural design for G+4 hospital buildingPage 28


Integrated design semester project

Ø=¿ 0.5*(1 + 0.34(4.81-0.2) + 4.812) = 12.85

1
x ¿= ≤1
Ø + √( Ø 2−λ ¿2 )

1
x ¿= = 0.04 < 1 ok!
12.85+ √ 12.85 −4.81
2 2

x¿∗β w∗w pl∗f y 0.04∗1∗5.66∗103∗235


M b, Rd= = = 0.48KN-m≥ M sd=0.19 (OK!)
ᵧmo 1.1

Combined axial force and moment

When lateral torsional buckling resistance is not a potential failure mode

N sd K y∗M y , sd K z∗M z , sd
+ + ≤1
xmin∗N pl, Rd M ply , Rd M plz, Rd

No bending about minor axis. And the above equation is modified to:

N sd K y∗M y , sd
+ ≤1
xmin∗N pl, Rd M ply , Rd

❑ y∗N sd
Where, K y= 1 - ≤ 1.5
x y∗A∗f y

w pl , y −w el , y
❑ y = λ y(2 β My - 0.4) + ≤ 0.9 (Take❑ y =0.9)
w el , y

0.9∗(−29.37∗103 )
K y= 1 – =1.386
0.778∗374∗235

Substitute for respective values into the interaction equation:

29.37∗103 1.386∗0.19∗106
= + =0.69≤1 (OK!)
0.778∗79.9∗103 1.209∗106

When lateral torsional buckling is a potential failure

N sd K ¿∗M y , sd
+ ≤1 …. (No bending on the minor axis)
x z∗N pl, Rd x LY∗M ply , Rd

Structural design for G+4 hospital buildingPage 29


Integrated design semester project

❑¿ =0.15 λ z * β MLT - 0.15 ≤ 0.9 (Take ❑¿=0.9)

❑¿∗N sd
K LT= 1 - ≤ 1.5 (K LT= K y= 1.05)
x Z∗A∗f y

0.9∗29.37∗103
K LT= 1 - =0.386
0.778∗374∗235

29.37∗103 0.386∗0.19∗106
= + =0.55 ≤1 (OK!)
0.778∗79.9∗103 0.778∗1.209∗106

DETAIL DRAWING

Cross-section of truss structure

ST-(50x50x2) mm

Structural design for G+4 hospital buildingPage 30


Integrated design semester project

CHAPTER TWO

3. SLAB ANALYSIS AND DESIGN

3.1. Depth of slab for deflection requirement


Effective slab depth for deflection requirement can be

Where

fyk -is the characteristic strength of the reinforcement (MPa)

le- is the effective span, for two-way slabs, the shorter span

βa- is the appropriate constant from table 5.1 & for slabs Carrying partition walls likely to
crack, shall be taken as βa<150/lo

lo- is the distance in meter between points of zero moments, & for

Effective depths of the panels calculated for all the floors, for demonstration purpose only the
ground floor panels done individually in this project. It is typical for others floor slab.

Type of slab

Structural design for G+4 hospital buildingPage 31


Integrated design semester project

Panel no. Support condition Ly Lx Ly Slab type


Lx
and location

P1 4m 4m 1 Two way slab

P2 4m 4m 1 Two way slab

P3 4m 4m 1 Two way slab

P4 4m 4m 1 Two way slab

P5 4m 2m 2 Two way slab

P6 4m 2m 2 Two way slab

P7 3m 2m 1.5 Two way slab

Structural design for G+4 hospital buildingPage 32


Integrated design semester project

P8 4m 2m 2 Two way slab

P9 4m 2m 2 Two way slab

P10 4m 4m 1 Two way slab

P11 4m 4m 1 Two way slab

P12 4m 3m 1.33 Two way slab

P13 4m 4m 1 Two way slab

P14 4m 4m 1 Two way slab

Minimum slab depth determination

fyk ¿
D=(0.4 +0.6 ) fyk=300N/mm2
400 ꞵ a

Structural design for G+4 hospital buildingPage 33


Integrated design semester project

Panel no. Support condition Le Ly Slab type ꞵa d min.(mm)


Lx
and location (mm
)

P1 4000 1 End span 40 85

P2 4000 1 End span 40 85

P3 4000 1 End span 40 85

P4 4000 1 End span 40 85

P5 2000 2 End span 30 72.67

Structural design for G+4 hospital buildingPage 34


Integrated design semester project

P6 2000 2 Interior span 30 72.67

P7 2000 1.5 Interior span 35 62.29

P8 2000 2 Interior span 30 72.67

P9 2000 2 End span 30 72.67

P10 4000 1 End span 40 85

P11 4000 1 End span 40 85

P12 3000 1.33 End span 34.01 75

P13 4000 1 End span 40 85

Structural design for G+4 hospital buildingPage 35


Integrated design semester project

P14 4000 1 End span 40 85

3.2. DESIGN LOAD DETERMINATION FOR SLAB


Assume ɸ12 in both directions. To satisfy requirements for durability provide adequate cover
to reinforcement. EBCS recommends 15mm thick concrete cover .

D= dmax + ɸ/2 + concrete cover

= 85+5+15

= 105 mm

Use D= 110mm

d= 110-15-5=90mm

Load calculations

The slab is loaded with both DL and LL. Dead load comes from self-weight of slab, floor
finish, cement screed, plastering and partition load. Live loads are either movable or moving
load without any acceleration or impact.

Dead and live loads are calculated depending on the service of the slabs and self-weight.
Ignoring any localized effects caused by concentrated load, the partition loads are distributed
over the area of the slab. The design loads are factored according to the following formula.

Pd =1.3DL+1.6LL

Where

Pd =total factored design load

DL = total dead load on slab

LL= total live load on slab

Cross-section of panels slab

Structural design for G+4 hospital buildingPage 36


Integrated design semester project

For panel 1

Live load

Purpose of this panel common toilet Qk= 2KN/m2

P1 4m
4m

Dead load

Slab own weight 0.11*25=2.75KN/m2

Floor finish

Cement screed =0.03*23=0.69 KN/m2

Terrazzo tile =0.02*23=0.46 KN/m2

Ceiling plaster and paint =0.02*23=0.46 KN/m2

Total DL = 8.11KN/m2

Partition wall load

Dead load from partition walls

Structural design for G+4 hospital buildingPage 37


Integrated design semester project

Material data

Thickness of HCB=100mm

Thickness of plastering on two side=20mm

Unit weight of HCB=14 KN/m3

Unit weight of plastering =23 KN/m3

Height of wall=2.85m

Unit weight of HCB for light weight aggregate range from 10-14 KN/m3 ,so we use HCB=14
KN/m3

Dead load of partition wall = Dead load of plaster+ Dead load of HCB

D.L pw= D.L pl + D.L HCB

= (Hpl * Lpl * tpl * pl ) + (HHCB * LHCB * tHCB * HCB)

= (2.85* 8.5*0.02m*23 KN/m3)+(2.85*8.5 * 0.1m *14 KN/m3)

= 45.059KN

Area of the panel = 4mx4m = 16m2

D.L. of partition wall per area of the panel

45.059
= 2.82KN/m2
16

Then, factored design load

Pd=1.3DL+1.6LL=

=1.3x(8.11+2.82) +1.6x2

=17.41KN/m2

For panel 2,

Live load

Purpose of this panel office Qk= 3KN/m2

Structural design for G+4 hospital buildingPage 38


Integrated design semester project

P2

Dead load

Slab own weight .11*25=2.75KN/m2

Floor finish

Cement screed =0.03*23=0.69 KN/m2

Terrazzo tile =0.02*23=0.46 KN/m2

Ceiling plaster and paint =0.02*23=0.46 KN/m2

Total DL = 8.11KN/m2

Then, factored design load

Then, factored design load

Pd=1.3DL+1.6LL=

=1.3x8.11+1.6x3

=15.34KN/m2

For panel P3, 4, 13, & 14

Live load

Purpose of this panel common toilet Qk= 3KN/m2

P3
.

Dead load

Slab own weight .11*25=2.75KN/m2

Floor finish

Structural design for G+4 hospital buildingPage 39


Integrated design semester project

Cement screed =0.03*23=0.69 KN/m2

Terrazzo tile =0.02*23=0.46 KN/m2

Ceiling plaster and paint =0.02*23=0.46 KN/m2

Total DL = 8.11KN/m2

Then, factored design load

Pd=1.3DL+1.6LL=

=1.3x8.11+1.6x3

=15.34KN/m2

For panel P 5, 6, 7, 8, &9

Purpose of this panel common toilet Qk= 5KN/m2

Px

Dead load

Slab own weight .11*25=2.75KN/m2

Floor finish

Cement screed =0.03*23=0.69 KN/m2

Terrazzo tile =0.02*23=0.46 KN/m2

Ceiling plaster and paint =0.02*23=0.46 KN/m2

Total DL = 8.11KN/m2

Then, factored design load

Pd=1.3DL+1.6LL=

=1.3x9.11+1.6x5

=18.54KN/m2

Structural design for G+4 hospital buildingPage 40


Integrated design semester project

For panel 10 & 11

Purpose of this panel common toilet Qk= 2KN/m2

P10&11

Dead load

Slab own weight .11*25=2.75KN/m2

Floor finish

Cement screed =0.03*23=0.69 KN/m2

Terrazzo tile =0.02*23=0.46 KN/m2

Ceiling plaster and paint =0.02*23=0.46 KN/m2

Total DL = 8.11KN/m2

Then, factored design load

Pd=1.3DL+1.6LL=

=1.3x8.11+1.6x2

=13.74KN/m2

For panel 12

Load Live

Purpose of this panel common toilet Qk= 5KN/m2

P12

Dead load

Slab own weight .11*25=2.75KN/m2

Structural design for G+4 hospital buildingPage 41


Integrated design semester project

Floor finish

Cement screed =0.03*23=0.69 KN/m2

Terrazzo tile =0.02*23=0.46 KN/m2

Ceiling plaster and paint =0.02*23=0.46 KN/m2

Total DL = 8.11KN/m2

Then, factored design load

Pd=1.3DL+1.6LL=

=1.3x8.11+1.6x5

=18.54KN/m2

3.3. DESIGN MOMENT DETERMINATION


2.3.1. SUPPORT AND FIELD MOMENT DETERMINATION

Moments for individual panels with edges either simply supported or fully fixed are
calculated as:

mi=αi (gd+qd)Lx2 ------------------------------------- [EBCS-2, 1995, Art 3.2]

Where

mi-is the design moment per unit width at the point of reference

αi-is the coefficient given in table-A-1 of EBCS-2 as function of aspect ratio Ly /Lx&

support conditions.

gd-is the uniformly distributed design permanent load

qd-is the uniformly distributed design line load

Lx -is the shortest span of the panel

Ly -is the longer span of the panel

Structural design for G+4 hospital buildingPage 42


Integrated design semester project

Support and field moment analysis computed in the following table

Support Ly Bending moment coefficient Bending moment


Lx
pa condition and Pd L
ne location x
(KN/
l 2 αxs αxf αys αyf Mxs Mx Mys Myf
m2)
f

1 1 17.41 1 0.047 0.036 0.047 0.036 14.07 10. 14.07 10.78


6 78

2 1 15.34 1 0.039 0.030 0.039 0.030 10.38 7.9 10.38 7.99


6 9

3 1 15.34 1 0.039 0.030 0.039 0.030 10.38 7.9 10.38 7.99


6 9

Structural design for G+4 hospital buildingPage 43


Integrated design semester project

4 1 15.34 1 0.047 0.036 0.047 0.036 12.51 9.5 12.51 9.58


6 8

5 2 18.54 4 0.039 0.029 0.039 0.029 3.09 2.3 3.09 2.30


0

6 2 18.54 4 0.032 0.024 0.032 0.024 2.54 1.9 2.54 1.90


0

7 1.5 18.54 4 0.053 0.040 0.032 0.024 4.21 3.1 2.54 1.90
7

8 2 18.54 4 0.063 0.048 0.032 0.024 5.00 3.8 2.54 1.90


1

9 2 18.54 4 0.067 0.050 0.039 0.029 5.32 3.9 3.09 2.30


7

10 1 13.74 1 0.047 0.036 0.047 0.036 11.31 8.6 11.31 8.66


6 6

11 1 13.74 1 0.039 0.030 0.039 0.030 9.38 7.2 9.38 7.22


6 2

Structural design for G+4 hospital buildingPage 44


Integrated design semester project

12 1.3 18.54 9 0.064 0.048 0.039 0.030 11.43 8.5 6.96 5.36
3 7

13 1 15.34 1 0.039 0.030 0.039 0.030 10.38 7.9 10.3 7.99


6 9

14 1 15.34 1 0.047 0.036 0.047 0.036 12.51 9.5 12.51 9.58


6 8

Structural design for G+4 hospital buildingPage 45


Integrated design semester project

Span & support moment before adjustment

2.3.2. BALANCING SUPPORT AND FIELD MOMENT

2.3.2.1. SUPPORT MOMENT ADJUSTMENT

Cofficient Method of Moment Distribution

If the percentage difference between moments is >20% distribute the moment

otherwise take the average value.

Panel P1& P2 Panel P6 and P11

∆Ms=14.07-10.38=3.69 KNm ∆Ms=9.38-2.54=6.84KNm

∆ Ms 3.69∗100 ∆ Ms 6.84∗100
= =26.23> 20 % = =72.92>20 %
Mmax 14.07 Mmax 9.38

Use moment distribution method

Stiffness for end support Stiffness for interior support

3 EI 3∗1
k 1= = =0.188 3 EI 3∗1
4 lx 4 x 4 k 11= = =0.188
4 lx 4 x 4
Stiffness for interior support
Use moment distribution method
EI 1
k 2= = =0.25 Stiffness for end support
lx 4

EI 1
k 6= = =0.5
Distribution factor lx 2

K1 0.188
DF 1= = =0.429 Distribution factor
K 1+ K 2 0.188+0.25

K2 0.25
DF 2= = =0.571 K1 0.188
K 1+ K 2 0.188+0.25 DF 11= = =0.273
K 1+ K 2 0.188+0.50
Adjusting using slope deflection method

Structural design for G+4 hospital buildingPage 46


Integrated design semester project

FORMULA K1 0.5
DF 6= = =0.727
K 1+ K 2 0.188+ 0.50
Md=Ms large−DFl∗∆ M
Adjusting using slope deflection method
Md=Ms small+ DFs∗∆ M
Balancing moment

P6 P11
Balancin
DF 0.273 0.727
g moment
2.54 -9.38
P1 P2
1.87 4.97
DF 0.429 0.571
Balance 4.01 -4.01
-14.07 10.38

1.583 1.583
Panel P10 & P11
Balance -12.487 12.487 ∆Ms=11.31-9.38=1.93KNm

∆ Ms 1.93∗100
= =17.1<20 %
Mmax 11.31
Panel P1&P5
Use average method
∆Ms=14.07-3.09=10.98KNm

∆ Ms 10.98∗100 -
= =78.03> 20 %
Mmax 14.07
P 10 P 11
Use moment distribution method

Stiffness for end support MOMENT 11.31 9.38

3 EI 3∗1 BALANCED -10.35 10.35


k 1= = =0.188
4 lx 4 x 4

Stiffness for interior support


Panel P11 and P12
EI 1
k 1= = =0.5
lx 2 ∆Ms=9.38-6.96=2.42KNm

Structural design for G+4 hospital buildingPage 47


Integrated design semester project

∆ Ms 2.42∗100
= =25.8> 20 %
Mmax 9.38
Distribution factor
Use moment distribution method
K1 0.188 Stiffness for end support
DF 1= = =0.273
K 1+ K 2 0.188+0.50

K1 0.50
DF 1= = =0..727 3 EI 3∗1
K 1+ K 2 0.188+0.50 k 11= = =0.188
4 lx 4 x 4
Adjusting using slope deflection method
EI 1
k 12= = =0.333
lx 3

Balancin Distribution factor

g moment K 11 0.188
DF 11= = =0.361
K 11+ K 12 0.188+0.333
P1 P5
K 12 0.333
DF 12= = =0.639
K 11+ K 12 0.188+0.333
DF 0.273 0.726
Balancing moment
-14.07 3.09
P11 P12
3.0 7.98
DF 0.361 0.639
Balance -11.07 11.07
-9.38 6.96

Panel P2& P6 1.87 1.55

∆Ms=10.38-2.54=7.84KNm
Balanced M. -8.51 8.51
∆ Ms 7.84∗100
= =75.53>20 % ,
Mmax 10.38

Stiffness for interior support Panel P7 and P12

3 EI 3∗1 ∆Ms=11.43-4.21=7.22KNm
k 2= = =0.188
4 lx 4 x 4
∆ Ms 7.22∗100
= =63.17> 20 %,
Mmax 11.43

Structural design for G+4 hospital buildingPage 48


Integrated design semester project

EI 1 Use moment distribution method


k 6= = =0.50
lx 2
Stiffness for end support
Distribution factor
3 EI 3∗1
k 12= = =0.25
K2 0.188 4 lx 4 x 3
DF 2= = =0.273
K 2+ K 6 0.188+ 0.50
EI 1
k 7= = =0.5
K6 0.50 lx 2
DF 6= = =0.727
K 2+ K 6 0.188+0.50

Adjusting using slope deflection method

Distribution factor

Balancing moment
K 12 0.25
DF 12= = =0.333
P2 P6 K 7 + K 12 0.25+0.50

K7 0.5
DF 0.273 0.727 DF 7= = =0.667
K 7+ K 12 0.25+0.50

-10.38 2.54 Adjusting using slope deflection method

2.14 5.69
Balancing
Balance -8.23 8.23
moment

P7 P12
Panel P5 & P10

∆Ms=11.31-3.09=8.22KNm DF 0.333 0.667

∆ Ms 8.22∗100 -11.43 4.21


= =72.68> 20 %,
Mmax 11.31
2.40 4.82
Use moment distribution method

Stiffness for end support Balance -9.03 9.03

3 EI 3∗1
k 10= = =0.188 Panel P7 and P8
4 lx 4 x 4

Structural design for G+4 hospital buildingPage 49


Integrated design semester project

Stiffness for interior support ∆Ms=2.54-1.90=0.64KNm

EI 1 ∆ Ms 0.64∗100
k 5= = =0.5 = =25.2>20 %
lx 2 Mmax 2.54

Distribution factor

K 10 0.188 Stiffness
DF 10= = =0.273
K 10+ K 5 0.188+ 0.50

K5 0.5 3 EI 3∗1
DF 5= = =0.727 k 7= = =0.25
K 10+ K 5 0.188+ 0.50 4 lx 4 x 3

EI 1
k 8= = =0.5
lx 2
Thus moment adjustable is required.

Distribution factor

Balancin
K1 0.25
DF 7= = =0.333
g moment K 1+ K 2 0.25+ 0.50

K1 0.5
P10 P5 DF 8= = =0.667
K 1+ K 2 0.25+ 0.50

DF 0.273 0.727 Adjusting using slope deflection method

-11.31 3.09 Balancing moment

2.24 5.96 P7 P8

Balance -9.07 9.07 DF 0.333 0.667

Panel P5 and P6 -2.54 1.90

∆Ms=3.09-2.54=0.55KNm
0.213 0.427
∆ Ms 0.55∗100
= =17.8>20 %
Mmax 3.09 Balance -2.33 2.33

Adjusting using slope deflection method


Panel P3 and P4

Balancing moment

Structural design for G+4 hospital buildingPage 50


Integrated design semester project

∆Ms=10.38-9.58=0.8KNm

∆ Ms 0.8∗100
P5 P6 = =7.7>20 %
Mmax 10.38

3.09 2.54 Adjusting using slope deflection method

Adj. M 2.82 2.82 Balancing moment

Panel P3 and P8 P3 P4

∆Ms=10.38-5.00=5.38KNm
10.38 9.58
∆ Ms 5.38∗100
= =51.83 % >20 %
Mmax 10.38 9.98 9.98

Use Average method Panel P13 and P14


Stiffness for end support ∆Ms=12.51-10.38=2.13KNm

∆ Ms 2.13∗100
= =17.03< 20 %
3 EI 3∗1 Mmax 12.51
k 3= = =0.188
4 lx 4 x 4
Use average distribution method
EI 1
k 8= = =0.50
lx 2 Balancing moment

P 13 P 14
Distribution factor
MOMENT 10.38 12.51
K3 0.188
DF 3= = =0.273
K 3+ K 8 0.188+0.50
BALANCED -11.45 11.45
K8 0.50
DF 8= = =0.727
K 3+ K 8 0.188+0.50

Balancin Panel P9 and P4

g moment ∆Ms=12.51-5.32=7.19KNm

P3 P8 ∆ Ms 7.19∗100
= =57.47 >20 %
Mmax 12.51

DF 0.727 .273 Use moment distribution method

Structural design for G+4 hospital buildingPage 51


Integrated design semester project

-10.38 5.00 Stiffness for end support

3 EI 3∗1
3.91 1.47 k 4= = =0.188
4 lx 4 x 4

Balance -6.47 6.47 3 EI 1


k 9= = =0.5
4 lx 2
Panel P8 and P13
Distribution factor
∆Ms=10.38-5.00=5.38KNm
K4 0.188
DF 4= = =0.273
∆ Ms 5.38∗100 K 4+ K 9 0.188+ 0.50
= =51.83 % >20 %
Mmax 10.38 K9 0.50
DF 9= = =0.727
Stiffness for end support K 4 + K 9 0.188+0.50

Adjusting using slope deflection method

3 EI 3∗1
k 13= = =0.188
4 lx 4 x 4 Balancing

EI 1 moment
k 8= = =0.50
lx 2
P4 P9

Distribution factor DF 0.273 0.727

K 13 0.188 -12.51 5.32


DF 13= = =0.273
K 13+ K 8 0.188+0.50

K8 0.50 1.96 5.23


DF 8= = =0.727
K 13+ K 8 0.188+0.50
Balance -10.55 10.55
Balancing
moment

P13 P8 Panel P14 and P9

∆Ms=12.51-5.32=7.19KNm
F 0.727 .273 ∆ Ms 7.19∗100
= =57.47 >20 %
Mmax 12.51
-10.38 5.00

Structural design for G+4 hospital buildingPage 52


Integrated design semester project

3.91 1.47 Use moment distribution method

Stiffness for end support


Balance -6.47 6.47
3 EI 3∗1
k 4= = =0.188
Panel P8 and P9 4 lx 4 x 4

∆Ms=3.09-1.90=1.19KNm 3 EI 1
k 9= = =0.5
4 lx 2
∆ Ms 1.19∗100
= =38.5> 20 %
Mmax 9.38 Distribution factor

K4 0.188
DF 4= = =0.273
K 4+ K 9 0.188+ 0.50
Stiffness
K9 0.50
DF 9= = =0.727
K 4 + K 9 0.188+0.50
3 EI 3∗1
k 9= = =0.188
4 lx 4 x 4 Adjusting using slope deflection method
EI 1
k 8= = =0.5
lx 2 Balancing
moment

Distribution factor
P14 P9

K1 0.188 DF 0.273 0.727


DF 9= = =0.273
K 1+ K 2 0.188+ 0.50

K1 0.5 -12.51 5.32


DF 8= = =0.727
K 1+ K 2 0.188+ 0.50
1.96 5.23
Adjusting using slope deflection method
Balance -10.55 10.55
Balancing moment

P9 P8

DF 0.273 0.727

-3.09 1.90

Structural design for G+4 hospital buildingPage 53


Integrated design semester project

.32 0.87

Balance -2.77 2.77

2.3.2.2. Field (span) moment adjustment

If the support moment is decreased, the span moments Mxf and Myf are increased allow for
the changes of support moments.

span moments are adjusted only on the direction in which support moment is decreased or
reduced, during balancing of support moment.

We adjusted the span moment by considering the adjusted support moment and its unadjusted
support moment depending on Cx & Cy from table of EBCS, 1995

NB. We are not adjust for span moment when the support moment are increased

Mxfd = Mxf +Cx1 ΔMxs +Cx2 ΔMys

Myfd = Myf +Cy1 ΔMxs +Cy2 ΔMys

Structural design for G+4 hospital buildingPage 54


Integrated design semester project

Pane 1 Panel 2

Ly/Lx=1

∆Mxf=Cx∆Mxs+CxMxs

∆Myf=Cy∆Mys+CyMys Ly/Lx=1

Cx1=0.380, Cy1=0.280, Cx2 = 0.280 , Cy2 = Cx1=0.380, Cy1=0.280, Cx2 = 0.280 , Cy2 =

0.380 0.380

∆Mxf=0.380(10.38-8.23)+.280(0)

=0.817

∆Mxf=0.280(14.07-12.487)+.380(14.07-

Structural design for G+4 hospital buildingPage 55


Integrated design semester project

11.07) Mxf=7.99+0.817=8.707 KN.m

= 1.58 ∆Myf=0.28(10.38-8.23)+.380(0)=0.714

Mxf=10.78+1.58= 12.36KN.m Myf=7.99+0.714=8.704 KN.m

∆Mxf=0.380(14.07-12.487)+.280(14.07-
11.07)

=1.44

Myf=10.78+1.44=12.22 KN.m

Panel 3 Panel 4

Ly/Lx=1 Ly/Lx=1

Cx1=0.380, Cy1=0.280, Cx2 =0.280 , Cy2 = Cx1=0.380, Cy1=0.280, Cx2 = 0.280 , Cy2 =
0.380 0.380

∆Mxf=0.380(10.38-6.47) +.280(0) ∆Mxf=0.380(12.51-10.55)+0.280(12.51-


9.96)
=0.624
=1.46
Mxf=7.99+0.624=8.959 KN.m
Mxf=9.58+1.46=11.04 KN.m
∆Myf=0.28(10.38-6.47)+.380(0)=0.458
∆Myf=0.280(12.51-10.55)+0.380(12.51-
Myf=7.99+0.458=8.704 KN.m
9.96)=1.52

Myf=7.99+1.52=9.51 KN.m

Panel 5 Panel 6

Ly/Lx=1 Ly/Lx=2

Cx1=0.238, Cy1=0.055, Cx2 = 0.484 , Cy2 = Cx1=0.238, Cy1=0.055, Cx2 = 0.484 , Cy2 =
0.248 0.248

∆Mxf=0.238(0)+0.055(3.09-2.82) ∆Mxf=0.238(0)+0.055(0) = 0

= 0.01 Mxf=1.9+0=1.90 KN.m

Structural design for G+4 hospital buildingPage 56


Integrated design semester project

Mxf=2.3+.015=2.31 KN.m ∆Myf=0.484(0)+0.248(0)=0

∆Myf=0.484(0)+0.248(3.09-2.82)=0.07 Myf=1.9+0=1.9 KN.

Myf=2.3+.07=2.37 KN.

Panel 7 Panel 8

Ly/Lx=2 Ly/Lx=2

Cx1=0.238, Cy1=0.055, Cx2 = 0.484 , Cy2 = Cx1=0.238, Cy1=0.055, Cx2 = 0.484 , Cy2 =
0.248 0.248

∆Mxf=0.238(0)+0.055(0) = 0 ∆Mxf=0.238(0)+0.055(0) = 0

Mxf=3.17+0=3.17KN.m Mxf=3.81+0=3.81 KN.m

∆Myf=0.484(0)+0.248(0)=0 ∆Myf=0.484(0)+0.248(0)=0

Myf=1.9+0=1.9 KN. Myf=1.9+0=1.9 KN.

panel 9 panel 10

Ly/Lx=2 . Ly/Lx=1

Cx1=0.238, Cy1=0.055, Cx2 = 0.484 , Cy2 = Cx1=0.380, Cy1=0.280, Cx2 = 0.280 , Cy2 =
0.248 0.380

∆Mxf=0.238(0)+0.055(3.09-2.77) = 0.02 ∆Mxf=0.380(11.31-9.07)+0.280(11.31-


10.35)
Mxf=2.30+0.02=2.32 KN.m
=1.12
∆Myf=0.484(0)+0.248(3.09-2.77)=0.08
Mxf=8.66+1.12=9.78 KN.m
Myf=3.97+0.08=4.05 KN.
∆Myf=0.280(11.31-9.07)+0.380(11.31-
10.35)=0.99

Myf=10.35+0.99=11.34 KN.m

Panel 11 Panel 12

Structural design for G+4 hospital buildingPage 57


Integrated design semester project

Cx1=0.380, Cy1=0.280, Cx2 = 0.280 , Cy2 = Ly/Lx=1.33


0.380 Cx=0.380, Cy=0.349 Cx=0.118,Cy=0.128
∆Mxf=0.380(9.38-6.96)+0.280(9.38-2.54) ∆Mxf=0.380*(11.43-9.03)+0.349*0
=2.83 =0.91
Mxf=7.22+2.83=10.05 KN.m Mxf=8.57+ 0.91=9.48KN
∆Myf=0.280(9.38-6.96)+0.380(9.38-2.54) ∆Myf=0..118(11.43-9.03)+0.128*0=0.28
=3.28 Myf=5.36+0.28=5.64KN
Myf=7.22+3.28=10.50 KN.m

Panel 13 Panel 14

Ly/Lx=1 Ly/Lx=1

Cx1=0.380, Cy1=0.280, Cx2 =0.280 , Cy2 = Cx1=0.380, Cy1=0.280, Cx2 = 0.280 , Cy2 =
0.380 0.380

∆Mxf=0.380(10.38-6.47) +.280(0) ∆Mxf=0.380(12.51-10.55)+0.280(12.51-


9.96)
=1.49
=1.46
Mxf=7.99+1.49=8.959 KN.m
Mxf=9.58+1.46=11.04 KN.m
∆Myf=0.280(10.38-6.47) +.380(0)
∆Myf=0.280(12.51-10.55)+0.380(12.51-
=1.09
9.96)=1.52
Myf = 7.99+1.0=9.08KN.m
Myf=7.99+1.52=9.51 KN.m

Structural design for G+4 hospital buildingPage 58


Integrated design semester project

Summary of adjusted span and support moment

Panel No. support moment Field moment

Mxs Mys Mxf Myf

1 12.487 11.07 12.36 8.70

2 12.487 8.23 8.71 8.70

3 11.45 6.47 8.96 8.70

4 11.45 10.45 11.04 9.51

5 2.82 11.07 2.31 2.37

6 2.82 8.23 1.9 1.9

7 2.54 9.03 3.17 1.9

8 2.82 6.47 3.81 1.9

9 2.82 10.45 2.32 4.05

10 10.35 9.03 9.78 11.34

11 10.35 4.01 10.05 10.50

12 11.45 9.03 9.48 5.64

13 11.45 6.47 8.96 9.08

14 11.45 10.45 11.04 9.51

Structural design for G+4 hospital buildingPage 59


Integrated design semester project

3.4. REINFORCEMENT DESIGN FOR SLAB


Check for adequacy of the slabs

Check depth for flexure

dmin≥
√ Mmax
0.8 bfcdρm(1−0.4 ρm)

f yd 260.87
fcd=11.33 ,fyd=260.87m= =28.78 εcu=0.0035 , εyd¿ =0.0013
0.8 f cd 200000

0.5 0.5
ρmin¿ = =0.0017
fyk 300

0.6 εcu
∗fcd
ρ=ρmax εcu+ εyd
¿ =0.019
fyd

dmin≥
√ 14.08∗1000000
0.8∗1000∗11.33∗0.019∗28.78(1−0.4∗0.¿019∗28.78)
=60.30mm------------ Ok!!

dmin =60.30mm<dused------------- ----------------Ok!!

For shear resistance

For concrete members without significant axial force, shear resistance is

Structural design for G+4 hospital buildingPage 60


Integrated design semester project

Shear acting on slab is

The Slab depth used is enough for flexure and shear.

3.6 Calculation of reinforcement for the slab

Characteristics of material

Using concrete quality (grade) C-25 and class I work

fcu = 25MPa

fck = 0.8fcu = 0.8 x 25 MPa = 20 MPa

fyk = 300 MPa

Design strength of material

μ = 0.295 γc=1.5 γs=1.15

0 . 85 f ck 0. 85∗20 300
f cd = = =11 .33 MPa f yd = =260 .87 MPa
1 . 50 1 .50 1. 15

0.5 0.5
ρmin= = = 0.00167
fyk 300

Check trial thickness for flexure

√ √
6
Mmax 12.487∗10
Dreq = = = 61.12mm
μ∗fcd∗b 0.295∗11.33∗1000

Dprov = D – Ø/2 – cc

= 110 – 5 – 15 = 90mm

dreq < provided , hence the trial thickness is adequate for flexure

Effective depth of trial section

dx = D – Ø/2 – cc = 110 – 5 – 15 = 90mm

Structural design for G+4 hospital buildingPage 61


Integrated design semester project

dy = dx – Øb = 90 – 10 = 80mm

Sample flexural reinforcement calculation for slab

Panel (P1) for 1st—4th floor

Positive (bottom) reinforcement

In short span:- Mxf = 12.36 KN-m

dx = 90mm

Mxf 12.36∗10
6
μx = 2 = = 0.135
fcd∗b∗d 11.33∗1000∗902

μx = 0.135 < μmax = 0.295

dx
zx = [ 1+ √1−2∗μx ] = 90 [ 1+ √ 1−2∗0.135 ] = 83.4
2 2

Then, rigid area of tension steel

Mxf 12.36∗106
As = = = 567.83
fyd∗Zx 260.87∗83.4

0.5∗b∗d 0.5∗1000∗90
As min = = = 150
fy 300

As >Asmin =hence it is ok to provide As calculated

Spacing of ϕ 10bars

as∗b 78.52∗1000
Sb = = = 138.3 use 138
As 567.83

Sb max = {350use
2∗t=2∗110=220
the smaller

{
20 mm
Sb min = Øb
Øagg+5

Sb min = 25mm

Sb min < Sb = 138 < Sb max = 220

Structural design for G+4 hospital buildingPage 62


Integrated design semester project

Provided ϕ 10bar at 138mm c/c placed at the bottom in short span direction

In longer span direction :- Myf = 12.22KN-m

dy = 80mm

Mxf 12.22∗10 6
μx = = = 0.169
fcd∗b∗d 2 11.33∗1000∗802

μx = 0.169 < μmax = 0.295

dx
zx = [ 1+ √1−2∗μx ] = 80 [ 1+ √ 1−2∗0.169 ] = 72.55
2 2

Then, rigid area of tension steel

Mxf 12.22∗10
6
As = = = 645.67
fyd∗Zx 260.87∗72.55

0.5∗b∗d 0.5∗1000∗80
As min = = = 133.33
fy 300

As >Asmin =hence it is ok to provide As calculated

Spacing of ϕ 10bars

as∗b 78.52∗1000
Sb = = = 121.6 use 121
As 645.67

Sb max = {350use
2∗t=2∗110=220
the smaller

{
20 mm
Sb min = Øb
Øagg+5

Sb min = 25mm

Sb min < Sb = 121 < Sb max = 220

Provided ϕ 10bar at 121mm c/c placed at the bottom in long span direction

Negative (top) reinforcement

In short span direction Mxs = 12.487KN-m

Structural design for G+4 hospital buildingPage 63


Integrated design semester project

dx = 90mm
6
Mxf 12.487∗10
μx = = = 0.136
fcd∗b∗d 2 11.33∗1000∗902

μx = 0.136 < μmax = 0.295

dx
zx = [ 1+ √1−2∗μx ] = 90 [ 1+ √ 1−2∗0.136 ] = 83.4
2 2

Then, rigid area of tension steel

Mxf 12.487∗106
As = = = 573.94
fyd∗Zx 260.87∗83.4

0.5∗b∗d 0.5∗1000∗90
As min = = = 150
fy 300

As >Asmin =hence it is ok to provide As calculated

Spacing of ϕ 10bars

as∗b 78.52∗1000
Sb = = = 136.8 use 136
As 573.94

Sb max = {350use
2∗t=2∗110=220
the smaller

{
20 mm
Sb min = Øb
Øagg+5

Sb min = 25mm

Sb min < Sb = 136 < Sb max = 220

Provided ϕ 10bar at 136mm c/c placed at the top in short span direction

In longer span direction Mys=11.07KN-m

Dy = 80mm

Mys 11.07∗106
μy = = = 0.153
fcd∗b∗d 2 11.33∗1000∗802

μy = 0.153 < μmax = 0.295

Structural design for G+4 hospital buildingPage 64


Integrated design semester project

dy
zy = [ 1+ √ 1−2∗μy ] = 80 [ 1+ √ 1−2∗0.153 ] = 73.3
2 2

Then, rigid area of tension steel

Mys 11.07∗106
As = = = 578.92
fyd∗Zy 260.87∗73.3

0.5∗b∗d 0.5∗1000∗80
As min = = = 133.33
fy 300

As >Asmin =hence it is ok to provide As calculated

Spacing of ϕ 10bars

as∗b 78.52∗1000
Sb = = = 135.63 use 135
As 578.92

Sb max = {350use
2∗t=2∗110=220
the smaller

{
20 mm
Sb min = Øb
Øagg+5

Sb min = 25mm

Sb min < Sb = 135 < Sb max = 220

Provided ϕ 10bar at 135mm c/c placed at the top in longer span direction

Provided temperature and shrinkage reinforcementϕ 10 bar at300mm c/c at the top in the long
span direction

For other panels also calculated as the above manner and tabulated below

Table 8. Reinforcement design from( 1st to 4th)

Pane Direction Moments D(mm) Ρ Asmin Ascal Asfinal S.calc S.final


l . [sq.mm [sq.mm] [mm [mm]
(KN.m) [sq.mm]
]

Structural design for G+4 hospital buildingPage 65


Integrated design semester project

1 Short 12.36 90 0.0062 150.3 558 558 140.7 140

Longer 8.70 80 0.0055 133.6 440 440 178.5 170

2 Short 8.71 90 0.0043 150.3 387 387 202.9 200

Longer 8.70 80 0.0055 133.6 440 440 178.5 170

3 Short 8.96 90 0.0044 150.3 396 396 198.3 190

Longer 8.70 80 0.0055 133.6 440 440 178.5 170

4 Short 11.04 90 0.0055 150.3 495 495 158.6 150

Longer 9.51 80 0.0061 133.6 488 488 160.9 160

5 Short 2.31 90 0.0011 150.3 99 150.3 522.4 220

Longer 2.37 80 0.0014 133.6 112 133.6 587.7 220

6 Short 1.9 90 0.0016 150.3 144 150.3 522.4 220

Longer 1.9 80 0.0016 133.6 128 133.6 587.7 220

7 Short 3.17 90 0.0016 150.3 144 150.3 522.4 220

Longer 1.9 80 0.0016 133.6 128 133.6 587.7 220

8 Short 3.81 90 0.0018 150.3 162 162 484.7 220

Longer 1.9 80 0.0016 133.6 128 133.6 587.6 220

9 Short 2.32 90 0.0016 150.3 144 150.3 522.4 220

Longer 4.05 80 0.0025 133.6 200 200 392.6 220

10 Short 9.78 90 0.0049 150.3 441 441 178 170

Structural design for G+4 hospital buildingPage 66


Integrated design semester project

Longer 11.34 80 0.0074 133.6 592 592 132.6 130

11 Short 10.50 90 0.0052 150.3 468 468 167.8 160

Longer 10.50 80 0.0068 133.6 544 544 144.3 140

12 Short 9.48 90 0.0047 150.3 423 423 185.6 180

Longer 5.64 80 0.0035 133.6 280 280 280.4 220

13 Short 8.96 90 0.0044 150.3 396 396 198.28 190

Longer 9.08 80 0.0058 133.6 464 464 169.2 160

14 Short 11.04 90 0.0055 150.3 495 495 158.6 150

Longer 9.51 80 0.0061 133.6 488 488 160.9 160

3.5. DESIGN 0F GROUND FOOL SLAB


Since the ground floor slab rests on the ground directly no bending moment is created and
therefore no structural design is required but minimum reinforcement in both directions is
provided to prevent shrinkage of the slab, stress due to temperature variation and crushing of
slab due to concentrated loads.

Use D=100mm(for slabs exposed to light moving concentrated load)…….EBCS(2/1995)

Ø8 diameter reinforcement

25mm clear cover

Structural design for G+4 hospital buildingPage 67


Integrated design semester project

Spacing between bars for main reinforcement of slab shall not exceed,

Use Ø8mm bar c/c 300mm in both directions

Table 7 panel shear force

Panel Panel type Ly/Lx Shear Lx(m) Pd(KN/ Vi( KN/m)


coefficient(βvi) m2) =Pd*Lx*β
vi

1 1 βvxc =0.4 4 17.41 27.86

βvxD =0.26 18.11

βvyc =0.40 27.86

βvyD =0.26 18.11

2 1 βvxc =0.36 4 15.34 22.09

βvxD=0.24 14.73

Structural design for G+4 hospital buildingPage 68


Integrated design semester project

βvyc =0.36 22.09

βvyD=0.00 0.00

3 1 βvxc =0.36 4 15.34 22.09

βvxD=0.24 14.73

βvyc =0.36 22.09

βvyD=0.00 0.00

4 1 βvxc =0.4 4 15.34 24.54

βvxD =0.26 15.95

βvyc =0.40 24.54

βvyD =0.26 15.95

5 2 βvxc =0.52 2 18.54 19.28

βvxD=0.0 0

βvyc =0.36 13.34

βvyD=0.24 8.90

6 2 βvxc =0.33 2 18.54 12.23

βvxD=0.00 0.00

βvyc =0.33 12.23

βvyD=0.00 0.00

7 1.5 βvxc =0.45 2 18.54 16.67

βvxD=0.00 0.00

βvyc =0.33 12.24

βvyD=0.00 0.00

Structural design for G+4 hospital buildingPage 69


Integrated design semester project

8 2 βvxc =0.33 2 18.54 12.23

βvxD=0.00 0.00

βvyc =0.33 12.23

βvyD=0.00 0.00

9 2 βvxc =0.52 2 18.54 19.28

βvxD=0.00 0

βvyc =0.36 13.34

βvyD=0.24 8.90

10 1 βvxc =0.40 4 13.74 21.98

βvxD=0.26 14.29

βvyc =0.40 21.98

βvyD =0.26 14.29

11 1 βvxc =0.36 4 13.74 23.96

βvxD=0.26 14.29

βvyc =0.36 23.96

βvyD =0.0 0

12 1.33 βvxc =0.34 3 18.54 18.91

βvxD=0.31 17.24

βvyc =0.36 20.02

βvyD =0.0 0

13 1 βvxc =0.36 4 15.34 22.09

βvxD=0.26 14.73

Structural design for G+4 hospital buildingPage 70


Integrated design semester project

βvyc =0.36 22.09

βvyD =0.0 0.00

14 1 βvxc =0.40 4 15.34 24.54

βvxD=0.26 15.95

βvyc =0.40 24.54

βvyD =0.26 15.95

CHAPTER THREE

4. STAIRCASE ANALYSIS AND DESIGN

3.1. DESIGN PROCEDURE

The purpose of stairs is to provide pedestrian access to different levels within the building.
The geometric form of the stair case depending on individual circumstances involved. These
are two main components of stair case. Stair and landing slab. The flight and landing can
arrange in different forms to get different types of stair cases. Stair case analysis and design is
similar to slabs. It involves the analysis steps followed for slabs. The inclined configuration is
analyzed by projecting the loads on a horizontal plane. The stair contains three flights with the
same configuration.

Structural design for G+4 hospital buildingPage 71


Integrated design semester project

A reinforced concrete stair-way may be considered an inclined slab with one-way


reinforcement having steps formed on its upper surface. Based on their support condition we
have Pinned to pinned support condition.

The staircase modeling and analysis

Therefore, the design of stair type is done.

The chapter includes the following:

General introduction

Modeling of staircase

Analysis of staircase

Design of staircase

Assume the stair flying from:-

- The ground floor to landing between the ground and first floor is stair-1

-The first to landing between the first and second

GENERAL

Thread - horizontal upper portion of step

Riser - vertical upper portion of step

Waist - the least thickness of a stair slab.

Flight - a series of steps provided between two landings.

For public building: Size of rise = 120 mm to 180mm

Size of thread =200 mm to 300mm

The following rules govern the selection of the size of riser (R) and thread (T):

T * R = kept between 400 to 430cm2

T + 2R = Kept about 60cm

T + R = Kept about 40 - 45cm

Let take first flight for the ground stair

Structural design for G+4 hospital buildingPage 72


Integrated design semester project

4.1. STAIR LOAD ANALYSIS


3.2.1. Determination of depth for deflection:

This is a function of design tensile strength of steel, effective span length of the shortest span
in which more load is expected to transfer and support condition.

Loading: - This determines the total load in the stair and landing

Analysis: - determines moment and shear forces based on the analyzed moment

Check depth for flexure: - this step helps to cross check the design depth as it is safe for
flexure or not, if not revise the depth determined in step 1 and also the loads.

Reinforcement provision: -using the computed moments, number and area of reinforcement
bars determined.

Detailing - the arrangement of reinforcement bars and their length are determined and drawn.

Stair case from 1st floor to 4th floor

2.2.1 Lay out

Sectional view

Structural design for G+4 hospital buildingPage 73


Integrated design semester project

Section A - A

Fig. Support system of one flight

Depth determination

150
θ=tan−1 150
( 450)
α = tan-1 400

= 20.56

Span ratio

Ly 400
= = 2.67
LX 150

⇒Oneway slab

f yk ¿
D = (0 . 4 +0 . 6 ) [EBCS-2, 1995 Art5.2.3]
400 ꞵ a

Structural design for G+4 hospital buildingPage 74


Integrated design semester project

β a =25
for simply supported [EBCS-2,1995 Table 5.1]

300 4000
d = (0 . 4 +0 . 6 )
400 25

= 136mm

Using 12 reinforcement bar and concrete cover of 20 mm

D = 136 + 20 + 6

= 161

Use D = 170 mm

d = 170 – 20 - 6 = 144 mm

2.2.3 Stair dimension

Thread = 300mm

Riser = 150mm

flight length = √ 2502 +1502 =291.54mm


3.2.2. STAIR LOAD ANALYSIS

i) Dead load on flight

a. Own weight of concrete

0 . 17∗25
= = 4.54KN/m2
cos 20 .56

b. Steps

0 .5∗. 15∗25
= = 2.00KN/m2
cos 20 .56

0 . 02∗23
c. Base mortar plaster = = 0.49
cos 20 .56

d. Mortar for thread = 0.02*23 = 0.46 KN/m2

0 .03∗1 .5∗0 . 15∗10∗23


e. mortar for riser = = 0.621KN/m2
2 .5

Structural design for G+4 hospital buildingPage 75


Integrated design semester project

0 .03∗0 . 3∗10∗27
f. Marble thread = = 0.97 KN/m2
2 .5

0 .02∗0 . 12∗10∗27
g. Marble riser = = 0.26 KN/m2
2. 5

TOTAL = 9.34 KN/m2

ii) Dead load on landing`

a. Concrete slab = 0.17 * 25 = 4.25 KN/m2

b. Cement screed = 0.03 * 23 = 0.69 KN/m2

c. Marble = 0.02 * 27 = 0.54 KN/m2

d. Plastering = 0.02 * 23 = 0.46 KN/m2

TOTAL 5.94KN/m2

iii) Live load

According to EBCS-2, 1995 stairs are classified as category A

Live load taken as 3.0KN/m2

iv) Design load

Live load on flight = 1.6 * 3.0 = 4.8KN/m2

Dead load on flight = 1.3 *9.34 = 12.142KN/m2

16.94KN/m2

Live load on landing = 1.6 * 3.0 = 4.8KN/m2

Dead load on landing = 1.3 * 5.94 = 7.72KN/m2

12.52KN/m2

3.2.3. Moment determination and steel reinforcement

i) Maximum bending moment

Structural design for G+4 hospital buildingPage 76


Integrated design semester project

16.94 KN/m 12.52KN/m

A B

RA RA

∑ M A =0

= 16 .
94∗2. 52
2
+ 12. 52∗1 . 5∗ (
1.5
2 )
+ 2. 5 −4 R=0

RB = 28.49KN

RA = 32.64

SECTION A-A (0 ≤ x ≤ 2.5)

16.94KN/m

V M

32.64

∑MX = 0 ∑Fy = 0

MX = 32.64X – 8.47X2 Vx = 32.64 – 16.94*X

At X = 0 at X = 2.5 At X = 0 at X = 2.5

Mx = 0 Mx = 60.43 Vx = 32.64 = -9.71

SECTION B- (2.5 ≤ x ≤ 4)

Structural design for G+4 hospital buildingPage 77


Integrated design semester project

16.94KN/m

12.52KN/m

2.5m

32.64 X

∑MX = 0 ∑Fy = 0

2. 5 Vx = 32.64 – 16.94*2.5 -12.52*(X-


MX=32.64X–16.94*2.5*(X– )–12.52*(X-
2
2.5)
2. 5
2.5)*(X- ) At X = 2.5 at X = 4
2

At X = 2.5 at X = 4 Vx = -9.71 = -28.49

Mx = 28.66 Mx = -37.54

When X = 1.724 shear force becomes zero and at that point the bending moment would be
maximum

Mmax = 40.81KN-m/m

ii. Check adequacy of the section for flexure

d=
√ Msd
0. 295∗fcd∗b

d=
√ 40 . 81∗10 6
0. 295∗11. 33∗1000

= 110 < 170mm OK!

iii) Reinforcement

a. longitudinal reinforcement

Mmax = 40.81KN-m/m

Structural design for G+4 hospital buildingPage 78


Integrated design semester project

0.5
ρmin =
f yk
[EBCS-2, 1995 Art 7.2.2.2]

0. 5
ρmin =
300
= 0.00167

Using general Design chart No 1, [EBCS-2, 1995 Part 2]

M us
μu , s = 6
40 . 81∗10
f cd bd 2 2
= 11. 33∗1000∗144 = 0.174

Kz = 0.911
6
Msd = 40. 81∗10
=1192.5mm2
As = Kz∗d∗fyd 0 . 911∗144∗300
1 .15

As min = ρ*b*d = 0.00167*1000*144

= 240.5mm2

Using F 12 bar

b∗as 1000∗113 . 1
S= = = 94.8mm
As 1192 .5

Spacing provided 90 mm

Use ∅ 12 bars c/c 900 mm

b. Transverse reinforcement

Transverse reinforcement must be provided to account for shrinkage. The ratio of secondary
reinforcement to the main reinforcement shall be at least equal to 0.2

A s min=0.2 A s ,main
[EBCS-2, 1995 Art 7.2.2.2]

= 0.2 *1192.5

Structural design for G+4 hospital buildingPage 79


Integrated design semester project

= 238.5mm2

Using ∅ 10 bar

b∗as 1000∗78 . 54
S= = = 329.3mm
As 238 . 5

Use ∅ 10 bar c/c 325mm

If the slab will be cast monolithically with its supporting beams, additional
reinforcement must be provided at the top of the upper and lower landings.

2.2.6 Design of landing

Considering a 1 m length of the landing along, the load on the landing is as shown below.

12.52 KN/m2

2
wl
M max =
8

2
12. 52∗3
= 14.08KN-m/m
8

Because the bars in the landing will be placed on top of the main stairs reinforcement

d = 170 – 20 – 6 – 12

= 132 mm

Using general design chart no 1, EBCS-2, 1995 part 2

M us
μu , s = 14 .08∗106
f cd bd 2 2
= 11. 33∗1000∗132 = 0.071

Kz = 0.954

Structural design for G+4 hospital buildingPage 80


Integrated design semester project
6
Msd = 14 . 08∗10
= 428.6mm2
As = Kz∗d∗fyd 0 . 954∗132∗300
1 .15

As min = ρ*b*d = 0.00167*1000*132

= 211.2mm2

Using F 12 bar

b∗as 1000∗113 . 1
S= = = 263mm
As 428 . 6

Spacing provided 260 mm

Use ∅ 12 bars c/c 260 mm

2.2.7 Shear reinforcement

Checking flexural shear at a distance d from the face of the support

Vu = 30.2

The shear force Vc carries the concrete in members with out significant axial forces shall be
taken as

V c =0.25 f ctd K 1 K 2 bw d
[EBCS-2, 1995 Art4.5.3.1]

As
ρ= = 1192 . 5
K 1 =( 1+50 ρ)≤2. 0 bd 1000∗144 = 0.0083

= (1+ 50*0.0083) = 1.42≤ 2

=1.42

K 2 =1. 6−d≥1 . 0

= 1.6 – 0.144 = 1.46 ≥ 1

= 1.46

Structural design for G+4 hospital buildingPage 81


Integrated design semester project

f ctk
f ctd =
γc
[EBCS-2, 1995 Art3.5.3.1]

f ctk =0 . 7∗f ctm


f ctm=0. 3 f 2
3
ck
[EBCS-2, 1995 Art2.4]
2
3
0 . 3∗25 ∗0 .7
f ctd =
1. 5

= 1.032 Mpa

Vc = 0.25 * 1.032 * 1.42 * 1.46 * 1000 * 144

= 77.02KN

Because Vc > Vu, no shear reinforcement is required. But it is recommended to use F 8 c/c
300 mm to hold the main reinforcement.

Structural design for G+4 hospital buildingPage 82


Integrated design semester project

CHAPTER FOUR

4. FRAME ANALYSIS AND DESIGN

5.

5.1. BEAM DESIGN


Beams should be design in such a way that they can carry their own weight in addition to
transferring the load from slabs or roofs (in top tie beams) to the column without excessive
deflection due to moment or cracks from shear force.

Plain concrete beams are inefficient as flexural members because the tensile strength in
bending is a small fraction of compressive strength. as a consequence, such beams fail on the
tension side at low loads long before the strength of the concrete on the compression side has
been fully utilized. For this reason, steel reinforcing bars are placed on the tension side as
close to the extreme tension fibers as is compatible with proper fire and corrosion protection
of the steel.

We have the following given dimensions

Top tie beam-25cm*30cm

Intermediate beam-25cm*40cm

Grade beam-25cm*30cm

Material Data

C-25, S-300 Class-I work

Structural design for G+4 hospital buildingPage 83


Integrated design semester project

2.

3.

4.

4.1.

4.1.1. Design of beam for flexure

Sample calculation of beam design

AXIS-A

Structural design for G+4 hospital buildingPage 84


Integrated design semester project

Figure 6.1 Bending moment diagram of axis-A from ETABS analysis

Sample for Design of beam

One axis (Axis A) on the beam is selected for sample calculation of beam design

Axis A

D= 400mm b = 250mm

Structural design for G+4 hospital buildingPage 85


Integrated design semester project

fcd=11.33MPa fyd= 260.87 MPa

Assume - concrete cover 25mm

-Reinforced bar Ø 20mm

-Stirrup Ø 8mm

Minimum depth requirement for serviceability i.e. deflection requirement is given by

(
d≥ 0 . 4+0 .6
400 β a)
f yk l e
, f yk =300 MPa

300 l e l
(
d≥ 0 . 4+0 .6
400 β a) =0 . 85 e
βa

First span (span 1-2) (Intermediate)

Exterior span

Le =4 m ßa = 24

d≥ 0.85 *4000/24 = 177.08mm

Overall depth, D = d + cover + Ø/2 + Øs

D= 177.08mm +25+20/2+8=220.08mm <Dused = 400 mm ok!

d= 400-(25+8+20/2) =357 mm

2) Interior span

Le =3 m ßa = 28

d≥ 0.85 *2700/28 = 81.96mm

Overall depth, D = d + cover + Ø/2 + Øs

Structural design for G+4 hospital buildingPage 86


Integrated design semester project

D= 81.96mm +25+20/2+8=124.96< Dused = 400 mm ok!

d= 400-(25+8+20/2) =357 mm

Therefore D = 400mm

d = 357mm

dc =43mm

Longitudinal Reinforcement

The geometric ratio of reinforcement and at any section of beam where positive reinforcement
required by analysis shall not be less than that given by

0.6
ρmin = =0 . 002
f yk
…………………………………….EBCS-2, 1995 Art 7.1.2

Where: -fyk = 300 Mpa

ρmax
= 0.04, for either tensile or compression reinforcement...…….EBCS-2, 1995 Art.7.1.2.
(3)

for this special case the balance steel ratio is given by

0 . 8 ε cu f cd
ρb = ∗
ε cu + ε yd f yd

0 .8∗0 . 0035 11. 33


ρb = ∗ =0 . 02
260. 87 260 .87
0 .0035+
200 ,000
53

However, for ductility purpose the steel is reduced by 25%,

ρmax =0. 75 ρb =0. 75∗0. 0253=0.0190

Calculate minimum reinforcement for beam according to EBCS 2, 1995, it is:-

0. 6 0. 6
ρmin = = =0 . 002
f yk 300
………… EBCS 2, 1995 Part 2 Section 7.2.1.1

Structural design for G+4 hospital buildingPage 87


Integrated design semester project

Asmin= ρbd = 0.002*250*357 = 178.5mm2 for intermediate beam

Asmin= ρbd = 0.002*250*259=129.5mm2 for top tie beam and grade beam

Design of member

Sample Calculation

Check T – beam analysis for Maximum Moment

For support 1, M= 108.26KNm

Check T – beam analysis

beff ≤¿ {bw +Le /5 ¿ ¿¿¿


[EBCS-2,1995Art 3.78(1)]

beff ≤¿ {250+5000/5=1250¿¿¿¿
Therefore, be = 1250mm governs. Let s use be=1250

f yd 260 . 87∗106
= =28 .77
0. 8 f cd 0 . 8∗11 . 333∗106
m=

2 . 5 2. 5
= =0 . 08688
m 28 .77
C1 =

C2 = 0.32* m2*fcd = 0.32*28.772*11.333*106 = 3002

Structural design for G+4 hospital buildingPage 88


Integrated design semester project

Md = 108.26 KN-m

ρ=
1
2 √
(C 1− C 2 −
1
4M
b e∗d 2∗C 2
)


6
1 4(108 . 26∗10 )
(0 . 08688− 0 . 007549−
2 1250∗3572∗3002
= )

= 0.00269

0.6
ρmin = =0 . 002
f yk
[EBCS-2, 1995 Art 7.1.2]

Where: -fyk = 300 Mpa

ρ>ρmin therefore, ρ=0.00269 governs.

X = ρ*m*d = 0.00269*28.77*357 =27.63mm

Y = 0.8X = 0.8*27.63= 22.1mm <hf(slab thickness)=170mm.

Therefore, the beam is rectangular.

But this checking process is used to span moment.

If the flange of the section is on the tension side when subjected to a moment flanged section
is designed as if it were a rectangular section with width equal to the width web. For support
moments flange is on the tension side. b=bw

Check the reinforcement is double or single

Step3:-Check the section whether to be designed as singly or doubly reinforced section

M sd 108 . 26∗1000
μreq= 2
= =0 .3> 0. 295
f cd bd 11 . 33∗106∗0. 25∗0 .357 2
[EBCS, 2/95]

Let M1=the moment capacity resisted by concrete and this is given by:

M1 = Msection=0.2914*bd2fcd=0.2914*250*3572*11.33=105.2KN-m

M1=105.2KN.m

Structural design for G+4 hospital buildingPage 89


Integrated design semester project

The moment from the sap output is equal to 108.26KN.m

Msd=108.26KN.m

M1=105.2KN.m

∴ M1<Msd…………….Doubly reinforced section

M2=Msd-M1

M2=108.26KN.m-105.2KN.m=3.06KN.m

Step4:- Tension Reinforcement

As=As1+As2

M2
As2=
fyd ( d −dc )

As1= ρ 1bd

√ √
6
fcd 2∗105 . 2∗10 11 .33
ρ = (1- 1− 2 M 1 ) = ρ = (1- 1− ) = 0.015>
bd 2 fcd fyd 250∗357 ∗11 .33 267 .87
2

ρmin=0. 002

∴ As1= ρ *bd=0.015*250*357=1338.75mm2

M2 3 .06∗106
As2= = =37.36mm2
fyd ( d −dc ) 260 .87∗(357−43)

∴ As=As1+As2=1338.75mm2*37.36mm2=1376.11mm2

Step5:- Number of bars and spacing

As 1376 .11
N= = =4.38 provide 5∅ 20
as 314

No of row required=> (nb+1) + ∅ comp . ¯¿*nb+2*∅ stirups

(nb+1) + ∅ comp . ¯¿*nb+2*∅ stirups …….nb =4.6 bar, →therefore provide 4 bar @ first row
and 1bar @ second row

For span moment 1, M= 85.69KNm

Structural design for G+4 hospital buildingPage 90


Integrated design semester project

M sd 85. 69∗1000
μreq= 2
= =0 .237< 0 .295
f cd bd 11 . 33∗106∗0. 25∗0 .357 2
---OK! [EBCS, 2/95]

It is singly reinforced beam

d 357
z= . ( 1 + √1−2 μ ) = ×( 1 + √1−2×0 .237 ) = 307 .96mm
2 2

Md 85 . 69 ∗106
A Steel = = =1 066 .62 mm 2
Zf yd 307 . 96∗260. 87

A Steel 1066 . 62
= =3 . 39
as 314 . 16
No of bars,

Provide 4 Ø 20 mm bars.

The other values are tabulated & shown as table below

Flexural reinforcement of the beams on axis-A

All beams are singly reinforced

Top tie beam reinforcement

Mu fcd fyd
Momen Axi As
(KNm b(m d(m) (KN/m2 (KN/m2 μ Z(mm)
t sA [mm2]
) ) ) )

1-2 25.69 0.25 0.259 11.33 260.87


0.135 240.11 410.13

span
2-3 3.45 0.25 0.259 11.33 260.87
moment 0.018 256.63 51.53

3-4 33.5 0.25 0.259 11.33 260.87


0.176 233.70 549.50

Structural design for G+4 hospital buildingPage 91


Integrated design semester project

1 23.53 0.25 0.259 11.33 260.87


0.124 241.82 372.99

3 23.13 0.25 0.259 11.33 260.87


0.122 242.14 366.18
support
moment
2 34.81 0.25 0.259 11.33 260.87
0.183 232.58 573.73

4 28.9 0.25 0.259 11.33 260.87


0.152 237.52 466.41

Top tie beam reinforcement area

No. Bars No. Bars Total As


Moment Axis A
As [mm2] as for Ø16 calc. Provided Provided

1-2 410.13 201.06 2.04 3 Ø16 603.18


span
2-3 51.53 201.06 0.26 2 Ø16 402.12
moment
3-4 549.50 201.06 2.73 3 Ø16 603.18

1 372.99 201.06 1.86 2 Ø16 402.12

2 366.18 201.06 1.82 2 Ø16 402.12


support
moment
3 573.73 201.06 2.85 3 Ø16 603.18

4 466.41 201.06 2.32 3 Ø16 603.18

Intermediate first floor beam reinforcement

Momen Axi Mu fcd fyd μ Z(mm As


t sA (KNm b(m (KN/m2 (KN/m2

Structural design for G+4 hospital buildingPage 92


Integrated design semester project

) ) d(m) ) ) ) [mm2]

0.35
1-2 75.78 0.25 11.33 260.87 0.21 314.4
7 923.77
0 6

span
0.35
momen 2-3 23 0.25 11.33 260.87 0.06 345.2
7 255.38
t 4 4

0.35
3-4 85.68 0.25 11.33 260.87 0.23 307.8 1,066.8
7
7 7 0

0.35
1 48.51 0.25 11.33 260.87 0.13 331.1
7 561.56
4 4

0.35
2 45.16 0.25 11.33 260.87 0.12 333.0
7 519.76
support 5 7
momen
t
0.35
3 80.28 0.25 11.33 260.87 0.22 311.5
7 987.90
2 1

0.35
4 56.62 0.25 11.33 260.87 0.15 326.3
7 665.01
7 8

Intermediate beam reinforcement area

Moment Axis A As [mm2] as for No. Bars No. Bars Total As

Structural design for G+4 hospital buildingPage 93


Integrated design semester project

Ø20 calc. Provided Provided

1-2
923.77 314 2.94 3 Ø20 942

span
2-3
moment 255.38 314 0.81 2 Ø20 628

3-4
1,066.80 314 3.40 4 Ø20 1256

1
561.56 314 1.79 2 Ø20 628

2
support 519.76 314 1.66 2 Ø20 628
moment

3
987.90 314 3.15 4 Ø20 1256

4 573.73 314 1.83 2 Ø20 628

Grade beam reinforcement

fcd fyd
Momen Axis Mu
d(m) (KN/m2 (KN/m2 μ Z(mm) As [mm2]
t A (KNm) b(m)
) )

span
1-2 0.25 11.33 260.87 366.18
moment 23.13 0.259 0.122 242.14

2-3 0.25 11.33 260.87 29.76

Structural design for G+4 hospital buildingPage 94


Integrated design semester project

2.00 0.259 0.011 257.63

3-4 0.25 11.33 260.87 672.41


40.00 0.259 0.211 228.04

1 0.25 11.33 260.87 301.68


19.29 0.259 0.102 245.11

2 0.25 11.33 260.87 289.77


18.57 0.259 0.098 245.66
support
moment
3 0.25 11.33 260.87 499.11
30.73 0.259 0.162 236.02
Grade beam reinforcement area

4 0.25 11.33 260.87 289.94


18.58 0.259 No. 0.098 245.65
Axis As as for No. Bars Total As
Moment Bars
A [mm2] Ø16 Provided Provided
calc.

1-2 366.1751 201 2 Ø16 402


1.822

span
2-3 29.75843 201 2 Ø16 402
moment 0.148

3-4 672.4072 201 4 Ø16 804


3.345

1 301.6833 201 2 Ø16 402


1.501

2 289.7746 201 2 Ø16 402


1.442
support
moment
3 499.1103 201 3 Ø16 603
2.483
Structural design for G+4 hospital buildingPage 95

4 289.9396 201 2 Ø16 402


1.442
Integrated design semester project

5.1.2. Beam design for shear

Structural design for G+4 hospital buildingPage 96


Integrated design semester project

Shear Reinforcement

All beams, except joists of slabs, shall be provided with at least the minimum web

Reinforcement given by:

0. 4 0 .4
= =0 . 0013
f yk 300
ρmin = ………….…..…….………..EBCS 2, 1995 Art.7.2.1.2

The maximum spacing between stirrups

Smax= 0.5d < 300mm, if Vsd<2/3VRd ………..…………….EBCS 2, 1995 Art.7.2.1.2

Structural design for G+4 hospital buildingPage 97


Integrated design semester project

Smax = 0.3d < 200mm, if Vsd>2/3 VRd

Where:- Vsd= acting shear along critical section

VRd=shear resistance of section limiting value of ultimate shear force for


prevention of diagonal compression failure in concrete, the shear resistance VRd of a section
given by the following equation shall not be less than the applied shear force, Vsd

VRd= 0.25 fcd *bw *d……………………….……………… EBCS 2, 1995 Art.4.5.2 (1)

The minimum shear resistance of concrete in beams

Vc = 0.25*fctd*k1*k2*bw*d ………………………………….EBCS 2, 1995 Art 4.5.3.1(1)

Where:- k 1=(1+50 ρ)<2. 0

k 2=1. 6−d >1 . 0 (d in meters). For members where more than 50% of the bottom
reinforcement is contained, k2= 1

As
ρ=
bd

Design of Shear Reinforcement

For longitudinal axis,

A v∗d∗f yd
S
Vs = ……………………..………………. (EBCS 2, 1995 Art. 4.5.4(4)

Where: - Av = is the area of shear resistance within the distance S.

Sample Calculation

Axis-5 First floor

For span: 1-2


2 2
(0 . 8 f cu )3 =0.21* (0 . 8∗25)3 N
f ctd=0 .21 =1 . 03
γc 1 .5 mm 2

As 3∗314
= =0 . 0106> ρ min=0 . 0013
bw d 250∗357
ρ=

Structural design for G+4 hospital buildingPage 98


Integrated design semester project

So, ρ=0.0106

k1 = (1+50ρ) <2.0

k1= (1+50*0.0106) =1.53<2.0 (OK!!)

k2 = (1.6-d) > 1.0

k2= (1.6-0.357) = 1.243>1.0 (OK!)

Concrete shear strength

Vc = 0.25*fctd*k1*k2*bw*d

= 0.25*1.03*1.53*1.243*250*357

= 43707 N=43.71KN

Diagonal compression resistance of concrete

VRd= 0.25 * fcd * bw * d

= 0.25 *11.33 *250 *357

VRd = 252800.60N = 252.8KN.

2/3 VRd= (2/3)*252.8 = 168.53KN

Critical section for shear is considered at‘d’ distance from the face of support or Critical
section

=d + column size/2

= 0.357 + 0.4/2 = 0.557 m

Vsd at critical section:

Vsd of Right
Structural design for G+4 hospital buildingPage 99
Integrated design semester project

2. 57 2. 57−0 . 482
= =
125. 62 Vsd

Vsd Right = 102.06KN>Vc= 43.71 KN, there is excess shear. Therefore shear reinforcement
is required for excess shear.

Vsd< VRD No diagonal compression failure

Vsd of Left

2 . 43 2. 43−0 . 482
= =94.91KN
118. 4 Vsd

Vsd Right= 94.91KN > Vc= 43.71KN, there is excess shear. Therefore shear reinforcement is
required for excess shear.

Maximum spacing of two leg Ø8mm bar stirrup:

S-max=0.3d= 0.3*357 =107.1 mm 200 mm, ifVsd>2/3VRd= 168.53 KN

0.5d= 0.5*357 =178.5 mm300 mm, if Vsd < 2/3VRd=168.53KN

Av∗fyd∗d
Sv=
Vsd−Vc

In this special case when Vsd > Vc

Spacing of two leg Ø8 mm vertical stirrup required by excess shear:

Av∗fyd∗d
Spacing Sv=
Vsd−Vc

Vs = Vsd – Vc = 102.06-43.71= 58.35KN

Consider `8mm stirrups with 2 legs

Av = 2 * π∗¿ 82 * /4 =100.53mm2

Av∗fyd∗d 100 .53∗260 . 87∗357


Sv= = =160 . 45 mmSmax=0.5d= 0.5*357 =178.5 mm300
Vsd−Vc ( 58 . 35 )∗1000
mm (because Vsd < 2/3VRd)

Use `8 stirrups c/c 150mm.

Structural design for G+4 hospital buildingPage 100


Integrated design semester project

Shear reinforcement of the beams on axis A

Top tie Beam

Membe Support ρ K1 Vc Vrd Vsd Smax Vs Vtot


r (KN) (KN) (KN) (mm) (KN) (KN
)

1-2 Left 0.010 1.52 47.88 290.4 104. Φ8c/c50mm 26.8 74.7
5 5 1 2 8 6

Right 0.010 1.52 47.88 290.4 100. Φ8c/c50mm 26.8 74.7


5 5 1 1 8 6

2-3 Left 0.004 1.22 38.48 290.4 50.2 Φ8c/c100mm 26.8 65.3
5 5 1 6 8 6

Right 0.006 1.30 40.83 290.4 56.4 Φ8c/c90mm 26.8 67.7


0 1 6 8 1

3-4 Left 0.006 1.30 40.83 290.4 55.5 Φ8c/c90mm 26.8 67.7
0 1 9 8 1

Right 0.004 1.22 38.48 290.4 51.3 Φ8c/c100mm 26.8 65.3


5 5 1 4 8 6

Structural design for G+4 hospital buildingPage 101


Integrated design semester project

Support As.cal As.eff. Lb. Lb.net


ember (mm2) (mm2) (mm) (mm)

1-2 Left 1238 1231.49 443.225 443.225

Right 942.66 1077.568 443.225 387.734

2-3 Left 408.01 461.814 443.225 391.586

Right 528.934 615.752 443.225 380.732

3-4 Left 507.44 615.752 443.225 365.261

Right 427.549 461.814 443.225 410.339

*** Vds<Vc; Minimum shear reinforcement is provided

Structural design for G+4 hospital buildingPage 102


Integrated design semester project

Structural design for G+4 hospital buildingPage 103


Integrated design semester project

4.1.2. Development length

The reinforcement shall be properly anchored at each end to prevent bond failure.

Basic anchorage length

The basic anchorage length lb diameter d of the bar is given as

l b =( φ /4 )
( )
f yd
f bd
[EBCS-2, 1995 Art 7.1.6.1]

f bd=2f ctd
, the design bond strength for deformed compression bar of good bond Condition

f bd=1.03∗2=2.06 Mpa
-

l b =( 20/4 ) ( 2. 06 )
260 . 87
=633 mm

Required anchorage length

A scal
lb , net =al b ≥0 .3 l b ≥¿ {10 φ ¿ ¿¿¿
A seff
[EBCS-2, 1995 Art7.1.6.2]

Where: - Ascal = theoretical area of reinforcement required by the design

Aseff = Area of reinforcement actually provided

Α=1.0 for straight bar in tension or compression zone.

First Member A-B on axis-5, @ first floor

Ascal = 923.77mm2

Aseff = 3*314.26 = 942mm2

Structural design project for G +4 hospital building page 104


Integrated design semester project

923.77
l bnet =1 . 0∗633 . 18∗ =620 . 93 mm
942
0 .3 l b =0 .3∗633. 18=189 . 95 mm

>200 OK.

Use lnet =620mm →The other members are done with the similar fashion

5.2. COLUMN DESIGN


Material Properties

Concrete - Grade C-25 Steel - Grade S300

Fck=20,000kpa [EBCS 2 Table 2.3] Fyk=300kpa

Fctk=1,500 kpa [EBCS 2 Table 2.4] PSF=1.15

PSF=1.5 [EBCS 2 Table 3.1] Fyd=261 kpa

Fcd=11333.33kpa Es= 200,000 kpa

Fctd=1,000 kpa As (min) =0.00072[EBCS-2 7.2.4.2]

Ecm=29,000 kpa [EBCS 2 Table 2.5] As (max) =0.0072[EBCS-2 7.2.4.2]

Analysis Result:

Axial (KNm) Mom. x-x (KNm) Mom y-y(KNm)

-1049.11 -8.78 -28.31

-1049.11 13.06 29.73 Dimensions


in x-x direction: Dimensions in y-y direction:

Depth Width Depth Width

B1 = 0.40 0.25 B1 =0.40 0.25

B2 = 0.40 0.25 B2 = 0.40 0.25

B3 = 0.40 0.25 B3 = 0.40 0.25

Structural design project for G +4 hospital building page 105


Integrated design semester project

C1 = 0.25 0.25 C1 = 0.25 0.25

C2 = 0.25 0.25 C2 = 0.25 0.25

C3 = 0.25 0.25 C3 = 0.25 0.25

Dimensions in x-x direction: Dimensions in y-y direction:

Lb1 = 4.0 Lb1 = 4.0

Lb2 = 2.0 Lb2 = 3.0

Lc1 = 3.00 Lc1 = 3.00

Lc2 = 3.00 Lc2 = 3.00

Lc3 = 3.00 Lc3 = 3.00

4.2.

4.3.

5.2.1. DESIGN FOR FLEXURE

Checking the column slenderness

For sway frames, the greater of

λ ≤ 25

15
√ νd
Or λ≤

For non-sway frames

25 M 1
50−
M2
λ≤

Limits of Slenderness: λ ≤ 50−25 ( MM 12 ) EBCS - 2, 4.4.6

Structural design project for G +4 hospital building page 106


Integrated design semester project

M 1 −8.78 M 1 −28.31
= =−0.67 = =−0.95
M 2 13.06 M 2 29.73

λ≤66.75 λ≤98.75

¿
But, the slenderness ratio is: λ= i

Le =Effective buckling length Ig = 0.001 EBCS-2, 4.4.5

rmin= Radius of gyration =


√ Ag
Ig
Ag= gross area of column section

Ig =moment of inertia of column section

Ag = 0.25*0.25=0.0625m2

1 3 4
Ig= ∗0.25∗0.25 =0.000325 m
12

rmin =
√ 0.000325
0.0625
=0.072

Effective Buckling Length:

KC2
About x-x direction. About y-y direction.
Kb1 Kb2
Ic1 = 0.00036 Ic1 = 0.00036 K Ic1 = 0.00036 Ic1 = 0.00036
c1

Ic2 = 0.00036 Ic3 =Kb30.00036 Kb4Ic2 = 0.00036 Ic3 = 0.00036

Ib1 = 0.00107 Ib3 = 0.00107 KC3 Ib1 = 0.00107 Ib3 = 0.00000

Ib2 = 0.00107 Ib4 = 0.00107 Ib2 = 0.00107 Ib4 = 0.00107

a1 = 0.393 a2 = 0.45 a1 = 0.393 a2 = 0.45

α mean= 0.423 αmean = 0.423

The effective buckling length:

Structural design project for G +4 hospital building page 107


Integrated design semester project

0.423+0.4
Le = *3=2.02m ≥ 0.7*3=2.1m , not ok! Take Le=2.1m
0.423+0.8

Slenderness Ratio:

¿ 2.1
λ= rmin = =29.17
0.072

λ=29.17≤66.75 Not Slender that means it is a short column. Ignore Secondary Effects

Reinforcement calculation

The minimum lateral dimension of column shall be at least 150 mm.

The area of longitudinal reinforcement shall not be less than 0.008*Ac and not more than 0.08*Ac. The
upper Limit shall be observed even where bars overlap.

The minimum number of longitudinal reinforcement bars shall be 6 for bars in a circular arrangement
and 4 bars in a rectangular arrangement.

The diameter of longitudinal bars shall not be less than 12 mm.

The column is reinforced according to EBCS-2 1995 part 2 design charts for biaxially bending
columns.

Design moments:

After determining amplified moments and made an allowance for imperfection (Ma), the total design
moment Mtot is calculated as

etot = ee + ea + e2 or Mtot =M1+Ma+M2‘

Mtot = Ma+M2 ...................................................................... *

Where: M1=1st order (computed) moment

Ma =moment due to imperfection

M2’ =moment due to lateral displacement

M2 is obtained by amplifying the first order moment

Therefore, M1+M2’ is equal to M2

Structural design project for G +4 hospital building page 108


Integrated design semester project

As per EBCS -2, 1995 Art 4.4.10.2(4), for different eccentricity at the ends, the critical end section
shall be checked for first order moments.

etot = eo2 + ea

Mtot = ML + Ma ………………………………………... **

2100
ea = =7mm≥ 20 mm not ok! Take ea =20mm=0.02m
300

ee(x-x) = max of 0.6e02 + 0.4e01 & 0.4e02 ee(y-y) =max of 0.6 e02 + 0.4e01
& 0.4e02

Axial (KNm) Mom. x-x (KNm) Mom y-y(KNm)

-1049.11 -8.78 =M1 -28.31=M1

-1049.11 13.06=M2 29.73=M2

Md −8.78
e01 = - = =-0.0084 e01 = -28.31/1049.11=-0.027
Nd 1049.11

13.06
e02 = =0.0124 e02 = 29.73/1049.11=0.0283
1049.11

ee = 0.0041 &0.00496 ee= 0.0062 & 0.0113

ee(x-x) =max of (0.0041 & 0.00496)=0.00496m

ee(y-y)= max of (0.0062 &0.0113) =0.0113m

etot(x-x) =ee + ea =0.00496+0.02= 0.025m

etot(y-y)= ee+ea=0.0113+0.02 = 0.0313m

Msd x-x = etot(x-x)*Nd = 0.025*1049.11= 26.23KN-m

Msd y-y = etot(y-y)*Nd= 0.0313*1049.11=32.84KN-m

Reinforcement Calculation:

Structural design project for G +4 hospital building page 109


Integrated design semester project

ϕl
Column x-section=b x h = 250x250mm and b’=h’=c.cover+ϕtie+ =25+8+20/2=43mm
2

b' h' 43 mm
Cover ratio = = but b= =0.17
b h 250 mm

Nsd=1049.11KN=1049.11*10^3N

fcd =11.33*10^6N/mm2 & Ac =250*250=6.25*10^4

N sd M sd ,x  x M sd ,y  y
 sd   sd ,x  x   sd,y  y 
fcd Ac fcd Ac h fcd Ac b

3N
1049.11∗10
υsd = 11.33 N 2 =1.48 but use 1.4
2
∗250∗250 mm
mm

26.23∗106 Nmm 32.84∗106 Nmm


μsd,x-x= =-0.15 and μsd,y-y= =0.19
11.33∗250∗250∗250 11.33∗250∗250∗250

h'/h=b'/b ω

0.1 0.5

0.17 ω=0.64

0.2 0.7

w = 0.64 by interpolating EBCS 2 - 1995: Part 2 Biaxial Chart No. 10

ω∗fcd∗Ac 0.64∗11.33∗250∗250
As, tot = = =1737.26mm2
fyd 260.87

AS, tot/4 = 1737.62/4=434.32mm

Number of bars →area of single ϕ20 bar =314.12mm2

Structural design project for G +4 hospital building page 110


Integrated design semester project

1737.62
N= =5.53
314.12

Therefore provide 6 ϕ20 bar

5.2.2. Design of column for shear

Lateral reinforcement

(EBCS-2 1995 Art 7.2.4.3 (2))

The diameter of ties or spirals shall not be less than 6mm or 1/4th of diameter of longitudinal bars. The
centre to centre spacing of lateral reinforcement shall not exceed:-

12 times the minimum diameter of longitudinal bars

Least dimension of columns

300mm

Ties shall be arranged such that every bar or groups of bars in a corner and alternate longitudinal bars
shall have provided by the corner of a tie with an included angle of not more than 1350 and for no bars
shall be further 150mm clear on each side along the tie from such a laterally supported bar.

Up to five longitudinal bars in each corner may be secured against lateral buckling by means of the
main ties. The centre to centre distance between the outer most of these bars and the corner bar shall
not exceed 15 times the diameter of the tie.

The shear force Vc carried by the concrete in member without significant axial forces shall be taken as:

Vc = 0.25*fctd*k1*k2*bw*d

k 1 =(1 .5+50 ρ)≤2 . 0


Where

k 2 =1 .6−d ¿ 1. 0
(d in meters)For members where more than 50% of the bottom of
Reinforcement is curtailed, K2 =1.0

As
ρ=
bw d

Structural design project for G +4 hospital building page 111


Integrated design semester project

As – the area of tensile reinforcement anchored beyond the intersection of the steel and the line of a
possible 45o crack starting from the edge of the section.

And for member subjected to axial compression the following equation may be used to compute the
additional shear force Vcn carried by the concrete.

0 . 1×b w ×d
V cn = N sd
Ac
----------------------------------------------------EBCS-2, 1995, Art. 4.5.3.2

Where, Nsd is the design axial force.

Therefore the total shear force,Vtot, resisted by the concrete becomes

Vtot = Vc + Vcn

0. 1×b w ×d
N sd
Ac
Vtotal= 0.25*fctd*k1*k2*bw*d+

Check for shear (selected column for sample in above reinforcement calculation)

Max shear force =8.28 KN, it occurs at the foundation column with Nsd=1049.11KN

The shear reinforcement is calculated by taking the cross section of column and the axial load of the
columns on each story. Comparing our result with the maximum shear on the columns:

Dimension 25*25cm

Limiting value of ultimate shear force:

v RD =0.25 f ctd b w d

= 0.25*11.33*250*250

= 177 KN > 8.28KN


2
6∗3.14∗20
Shear resistance of cross-section: As= =1884mm2
4

1884
ρ= = 0.03
250∗250

Structural design project for G +4 hospital building page 112


Integrated design semester project

Vc = 0.25*fctd*k1*k2*bw*d

k1= (1+50*0.03) = 2.5<2.0 ;K2=2

k2= 1.6-d, (deff =D-cover-Ø/2- Øb =250-25-20/2-8=207mm

= 1.6 – 0.207 = 1.393 >1 ………………………….safe! For members where more than 50% of the
bottom of Reinforcement is curtailed, K2 =1.0

Vc = 0.25*1.03*2*1.393*250*250= 44.84KN

Additional shear capacity of concrete:

0 . 1×b w ×d
V cn = N sd
Ac

250∗250¿
V cn=0.1×207∗207×1049.11¿ ¿
¿
= 71.93KN

Vtot = Vc + Vcn

Vtot=44.84+71.93=116.77KN>8.28KN (max. shear) ……………Safe!!

Nominal shear reinforcement is to be provided

For reinforcing the cross section to resist shear force ties are used as lateral reinforcement.

Hence, the centre to centre spacing between the ties is smaller of

12Фmin = 12 x 20 = 240 mm

C/C≤ Least dimension of columns (in our case) = 250 mm

300 mm

è Provide ϕ8 c/c 240mm.

Structural design project for G +4 hospital building page 113


Integrated design semester project

Structural design project for G +4 hospital building page 114


Integrated design semester project

CHAPTER 5

6. Footing Design
Selection of type of footing depends majorly on bearing capacity of supporting soil & cost. Starting by
trying isolated footing (as always the case) we can see that the load coming from the building can
efficiently be transmitted to the supporting soil. This is resulted from moderate load and good bearing
capacity of the soil. Hence isolated footing is designed.

Since we are using ultimate limit state design method, the allowable soil stress is multiplied by a factor
of average factor of dead load and live load (which is normally employed) and factored loads are taken
for analysis and design.

As in the case of column, design of footing started by grouping similar loading condition. One sample
footing design is done following formal procedure as shown below.

Not assume the length to breadth of footing is kept the same as that of column.

5.

5.1.

5.1.1. LOAD CALCULATION

I. Maximum factored loading from super structure(Pmax)-highly axial load

Pmax =1454.97 KN

Mx = -3.63KN-m

My = -0.58 KN-m

Depth of footing below the NGL=3m

Thickness of footing pad D=0.5m

Unit weight of selected soil is rsoil=16KN/m3

Unit weight of concrete rcr=25KN/m3

For cohesive silt soil =280KN/m2………………EBCS-7/1995-------------- table 6.3

Structural design project for G +4 hospital building page 115


Integrated design semester project

Concrete cover =50mm …………….EBCS-7/1995--------------table 10.2

Reinforced bar øb 20mm

Since the load from super structure is factored therefore, the allowable bearing capacity of the soil must
be factored by an average

Psoil= Load from the soil weight =

Pf= load from footing pad = (BL*0.5*rcr)

Ptotal = Pcl + 1.3 (Psoil+ Pf)

To be save use maximum value

Structural design project for G +4 hospital building page 116


Integrated design semester project

Provide 1.7m and 2.3m isolated footing

Calculation of bearing stress

x=2.3/2=1.15

1.70m a=0.4

b=0.4
bw y=1.7/2=0.85

Pmax = 2.30m

Pmax = 23.4*1.72 + 1448.73 = 1516.356KN

Structural design project for G +4 hospital building page 117


Integrated design semester project

For structural design difficult to design each stress so, average

5.1.2. DETERIMINATION OF EFFECTIVE DEPTH

In the structural design of footings adequacy of the thickness of the footing and provide the necessary
reinforcement to withstand punching shear and shear diagonal tension (wide beam shear) moment and
bond stress should be checked. For the structural design a simplifying assumption is made in which the
contact pressure distribution is assumed uniform and it magnitude is taken as the average of the each
side contact pressure

WIDE BEAM CRATERIA

Note conceder in longer direction because to get large Vd value

Structural design project for G +4 hospital building page 118


Integrated design semester project

Applied pressure from soil and self weight

Up-lift pressure from bottom

Resultant value is 659.28KPa – 132.6KPa = 526.68

Critical section for Vd is at ‘d’ distance from the face of the column because crack is propagate at 450

Material:-

Concrete grade(fcu) C-25

fck =0.8fcuk =0.8*25=20MPa

Structural design project for G +4 hospital building page 119


Integrated design semester project

5.1.3. CHECK DEPTH FOR FLEXTURE

For actual design it is better to use actual value

Structural design project for G +4 hospital building page 120


Integrated design semester project

Take

CHACK DEPTH FOR PUNCHING SHEAR

Critical section for punching shear is at 0.5d distance from face of column

Structural design project for G +4 hospital building page 121


Integrated design semester project

Structural design project for G +4 hospital building page 122


Integrated design semester project

Revised ‘d’ value

Structural design project for G +4 hospital building page 123


Integrated design semester project

Calculation flexural reinforcement

Step 5 CALCULAT FLAXTURAL REAINFORCEMENT

5.1 IN THE LONGER DIRECTION

Critical section for bending moment is at the face of the support

by interpolation Ks=3.97

Structural design project for G +4 hospital building page 124


Integrated design semester project

PROVIDE ø20mmC/C300mm

Calculate required bond length

Need of bending moment of bar‼

5.2 IN SHORT DIRECTION

Critical section of bending moment is face of the column

Structural design project for G +4 hospital building page 125


Integrated design semester project

In the Km table minimum value is Km=19 since our Km-value is les than the minimum use use Km=19

Corresponding Ks value are 3.95

PROVIDE ø20mmC/C350mm

5.2.2 BOND LENGTH

Need of bending moment of bar‼

Structural design project for G +4 hospital building page 126


Integrated design semester project

Step-6 detail drawing

x=2.7/2=1.35

4 3 bw
d

2.70m a=0.4

b=0.4
bw y=2.7/2=1.35
1 2

2.70m

Structural design project for G +4 hospital building page 127

You might also like