Area/Building

Inside Design Condition Dry Bulb Temperature 22


Outside Design Condition Dry Bulb Temperature 32
Location Butuan City Coordinates 8.944144812, 125.53278260

Ground Floor No. Occupant

Supply Room 4
Planning Office 5
Planning Office Comfort Room 1
Finance Office 10
Finance Filing Storage 2
Finance Office Comfort Room 1
Cashier Filing Storage 2
Cashier Window 2
TOTAL 27

Room Number of Lights

6
Supply Room
3
2
Planning Office
3
Planning Office Comfort Room 1
8
Finance Office
2
Finance Filing Storage 1
Finance Office Comfort Room 1
Cashier Filing Storage 1
Cashier Window 1
TOTAL 29

Room Number of change per hour

Supply Room 0.48


Planning Office 0.48
Planning Office Comfort Room 0.34
Finance Office 0.48
Finance Filing Storage 0.48
Finance Office Comfort Room 0.34
Cashier Filing Storage 0.48
Cashier Window 0.48
TOTAL

Heat
Opaque Surface (Concrete Wall/Roof/Floor)
Dimension
Exposure (N, NE, E, SE, SW,W)
L W
N 8 2.7
E 18 2.7
FLOOR 4 18
TOTAL

Opaque Surface (Window)


Dimension
Exposure (N, NE, E, SE, SW,W)
L W
N 0.5 1
N 1.6 1.2
N 1.6 1.2
E 1.25 2.5
E 1.6 2.5
TOTAL

Opaque Surface (Door)


Dimension
Exposure (N, NE, E, SE, SW,W)
L W
E 2.1 0.8
E 2.1 0.8
E 2.15 1.6
TOTAL

Hea
Opaque Surface (Concrete Wall/Roof/Floor)
Dimension
Exposure (N, NE, E, SE, SW,W)
L W
W 18 2.7
S 8 2.7
TOTAL

Opaque Surface (Window)


Dimension
Exposure (N, NE, E, SE, SW,W)
L W
W 1.6 1.2
W 1.6 1.2
W 1.6 1.2
W 1.6 1.2
W 1.6 2.5
W 0.5 1
W 0.5 1
S 1.6 1.2
S 1.6 1.2
S 0.5 1
S 0.5 1
TOTAL

Room Items

3
Supply Room
1
6
Planning Office 6
1
11
11
Finance Office
1
1
1
Finance Filing Storage
1
2
Cashier Filing Storage 2
Cashier Filing Storage
2
Cashier Window 2
TOTAL
DOTC Caraga Regional Office - Annex
22 Relative Humidity
32 Relative Humidity
44144812, 125.53278260 Month May

Occupant
Heat Per Occupant
Occupant Activity
Sensible Latent
4 Moderately active office work 75 55
5 Seated, very light work 70 45
1 Seated, very light work 70 45
10 Seated, very light work 70 45
2 Moderately active office work 75 55
1 Seated, very light work 70 45
2 Moderately active office work 75 55
2 Moderately active office work 75 55
27

Lightning
Wattage Instantaneous Load
Type of Bulb Hours On
Ratting Sensible Latent
LED Light Bulb 12 10 86.4
Circular LED 20 10 72
LED Light Bulb 12 10 28.8
Circular LED 20 10 72
LED Light Bulb 9 10 10.8
LED Light Bulb 12 10 115.2
Circular LED 20 10 48
Circular LED 20 10 24
LED Light Bulb 9 10 10.8
Circular LED 20 10 24
LED Light Bulb 12 10 14.4
0

Air Infiltration
Wall Dimension Instantaneous Load
change per hour
L W H Sensible Latent
0.48 8 4.5 2.7 529.415062855 2106
0.48 8 4.5 2.7 529.415062855 2106
0.34 1.5 2.5 2.7 39.062743353 155
0.48 9 8 2.7 1058.83012571 4213
0.48 2 4.85 2.7 142.647947491 568
0.34 1.5 2.5 2.7 39.062743353 155
0.48 3 4 2.7 176.471687618 702
0.48 3 1.5 2.7 66.1768828568 263

Heat Transmission through Unsunlit Building Structure

Heat Instantaneous Load


Unsunlit Area ΔT
Coefficient Sensible Latent
21.6000000 1.222 10 263.952
48.6000000 1.222 10 593.892
72.0000000 1.222 10 879.84

Heat Instantaneous Load


Unsunlit Area ΔT
Coefficient Sensible Latent
0.500000 4.6 10 23
1.920000 4.6 10 88.32
1.920000 4.6 10 88.32
3.125000 4.6 10 143.75
4.000000 4.6 10 184

Heat Instantaneous Load


Unsunlit Area ΔT
Coefficient Sensible Latent
1.680000 0.44 10 7.392
1.680000 0.44 10 7.392
3.440000 0.44 10 15.136

Heat Transmission through Sunlit Building Structure


Heat Instantaneous Load
Sunlit Area ETD
Coefficient Sensible Latent
48.600000 1.222 16.06 953.790552
21.600000 1.222 16.06 423.906912

Instantaneous Load
Sunlit Area SHGF SC
Sensible Latent
1.920000 132 1.00 253.44
1.920000 132 1.00 253.44
1.920000 132 1.00 253.44
1.920000 132 1.00 253.44
4.000000 132 1.00 528
0.500000 132 1.00 66
0.500000 132 1.00 66
1.920000 129 1.00 247.68
1.920000 129 1.00 247.68
0.500000 129 1.00 64.5
0.500000 129 1.00 64.5

Miscellaneous Load
Instantaneous Load
Description
Sensible Latent
Computer 511
Multifunction Large, multiuser, office printer (copy,print,scan) 30max printing speed 990
Computer 511
Printer: Desktop Small Office type 56
LED Screen 65in 265
Computer 511
Printer: Desktop Small Office type 56
LED Screen 65in 265
Fridge 430
Computer 511
Printer: Desktop Small Office type 56
Computer 511
Printer: Desktop Small Office type 56
Cash Register 139.9
Computer 511
50
81.6
Time 1:00 PM

Cooling Load Factor, CLF Design Cooling Load


Sensible Latent Sensible Latent
0.91 0.91 273 200.2
0.91 0.91 318.5 204.75
0.63 0.63 44.1 28.35
0.91 0.91 637 409.5
0.91 0.91 136.5 100.1
0.63 0.63 44.1 28.35
0.91 0.91 136.5 100.1
0.91 0.91 136.5 100.1
1726.2 1171.45

Cooling Load Factor, CLF Design Cooling Load


Sensible Latent Sensible Latent
0.93 80.352
0.93 66.96
0.93 26.784
0.93 66.96
0.73 7.884
0.93 107.136
0.93 44.64
0.93 22.32
0.73 7.884
0.93 22.32
0.93 13.392
466.632

Cooling Load Factor, CLF Design Cooling Load


Sensible Latent Sensible Latent
1.00 1.00 529.415062855 2106.3463401
1.00 1.00 529.415062855 2106.3463401
1.00 1.00 39.062743353 155.416179608
1.00 1.00 1058.83012571 4212.69268021
1.00 1.00 142.647947491 567.543319417
1.00 1.00 39.062743353 155.416179608
1.00 1.00 176.471687618 702.115446702
1.00 1.00 66.1768828568 263.293292513
2581.08225609 10269.1697783

Room 1st Floor


Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 263.952
1.00 593.892
1.00 879.84
1737.684

Room 1st Floor


Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 23
1.00 88.32
1.00 88.32
1.00 143.75
1.00 184
527.39

Room 1st Floor


Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 7.392
1.00 7.392
1.00 15.136
29.92
Room 1st Floor
Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 953.790552
1.00 423.906912
1377.697464

Room 1st Floor


Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
0.58 146.9952
0.58 146.9952
0.58 146.9952
0.58 146.9952
0.58 306.24
0.58 38.28
0.58 38.28
0.58 143.6544
0.58 143.6544
0.58 37.41
0.58 37.41
1332.9096

1st floor
Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 1533
1.00 990
1.00 3066
1.00 336
1.00 265
1.00 5621
1.00 616
1.00 265
1.00 430
1.00 511
1.00 56
1.00 1022
1.00 112
1.00 279.8
1.00 1022
16124.8

SENSIBLE LATENT TOTAL


25,904.32 11,440.62 37,344.94
Specific Volume (Outside) 0.8989
Humidity Ratio (Outside) 0.0248
Humidity Ratio (Inside) 0.0082
Area/Building
Inside Design Condition Dry Bulb Temperature 22
Outside Design Condition Dry Bulb Temperature 32
Location Butuan City Coordinates 8.944144812, 125.53278260

2nd Floor No. Occupant

Operation Office 14
Operation Office Comfort Room 1
Room 1 3
Room 1 Comfort Room 1
Room 2 3
Room 2 Comfort Room 1
Room 3 4
Room 3 Comfort Room 1
Room 4 4
Room 4 Comfort Room 1
TOTAL 33

Room Number of Lights

11
Operation Office
6
Operation Office Comfort Room 1
4
Room 1
1
Room 1 Comfort Room 1
4
Room 2
1
Room 2 Comfort Room 1
4
Room 3
1
Room 3 Comfort Room 1
4
Room 4
1
Room 4 Comfort Room 1
TOTAL
Room Number of change per hour

Operation Office 0.48


Operation Office Comfort Room 0.34
Room 1 0.48
Room 1 Comfort Room 0.34
Room 2 0.48
Room 2 Comfort Room 0.34
Room 3 0.48
Room 3 Comfort Room 0.34
Room 4 0.48
Room 4 Comfort Room 0.34
TOTAL

Opaque Surface (Concrete Wall/Roof/Floor)


Dimension
Exposure (N, NE, E, SE, SW,W)
L W
N 8 2.6
E 18 2.6
FLOOR 4 18
TOTAL

Opaque Surface (Window)


Dimension
Exposure (N, NE, E, SE, SW,W)
L W
N 0.5 2.5
N 0.5 2.5
E 1.6 1.2
E 1.6 1.2
TOTAL

Opaque Surface (Door)


Dimension
Exposure (N, NE, E, SE, SW,W)
L W
E 2.1 0.8
E 2.15 1.6
TOTAL
Opaque Surface (Concrete Wall/Roof/Floor)
Dimension
Exposure (N, NE, E, SE, SW,W)
L W
W 18 2.6
S 8 2.6
TOTAL

Opaque Surface (Window)


Dimension
Exposure (N, NE, E, SE, SW,W)
L W
W 1.6 2.5
W 1.6 1.2
W 0.5 1
W 0.5 1
W 1.6 1.2
W 1.6 1.2
W 1.6 1.2
W 1.6 1.2
S 0.5 1
S 0.5 1
S 1.6 1.2
TOTAL

Room Items

15
15
Operation Office
1
1
4
Room 1
4
4
Room 2
4
5
Room 3
Room 3
5
5
Room 4
5
TOTAL 68
DOTC Caraga Regional Office - Annex
22 Relative Humidity
32 Relative Humidity
44144812, 125.53278260 Month May

Occupant
Heat Per Occupant
Occupant Activity
Sensible Latent
14 Moderately active office work 75 55
1 Seated, very light work 70 45
3 Moderately active office work 75 55
1 Seated, very light work 70 45
3 Moderately active office work 75 55
1 Seated, very light work 70 45
4 Moderately active office work 75 55
1 Seated, very light work 70 45
4 Moderately active office work 75 55
1 Seated, very light work 70 45
33

Lightning
Wattage Instantaneous Load
Type of Bulb Hours On
Ratting Sensible Latent
LED Light Bulb 12 10 158.4
Circular LED 20 10 144
LED Light Bulb 9 10 10.8
LED Light Bulb 12 10 57.6
Circular LED 20 10 24
LED Light Bulb 9 10 10.8
LED Light Bulb 12 10 57.6
Circular LED 20 10 24
LED Light Bulb 9 10 10.8
LED Light Bulb 12 10 57.6
Circular LED 20 10 24
LED Light Bulb 9 10 10.8
LED Light Bulb 12 10 57.6
Circular LED 20 10 24
LED Light Bulb 9 10 10.8
Air Infiltration
Wall Dimension Instantaneous Load
change per hour
L W H Sensible Latent
0.48 9 8 2.6 1019.61419513 4056.66702539
0.34 1.5 2.5 2.6 37.6159750807 149.660024808
0.48 3.3 3.75 2.6 175.246189788 697.239644988
0.34 1.5 2.6 2.6 39.1206140839 155.6464258
0.48 3 5.1 2.6 216.668016465 862.041742895
0.34 1.5 2.5 2.6 37.6159750807 149.660024808
0.48 3 5.1 2.6 216.668016465 862.041742895
0.34 1.5 2.5 2.6 37.6159750807 149.660024808
0.48 4.5 3.65 2.6 232.599488263 925.427165166
0.34 1.5 2.7 2.6 40.6252530871 161.632826793

Heat Transmission through Unsunlit Building Structure

Heat Instantaneous Load


Unsunlit Area ΔT
Coefficient Sensible Latent
20.8000000 1.222 10 254.176
46.8000000 1.222 10 571.896
72.0000000 1.222 10 879.84

Heat Instantaneous Load


Unsunlit Area ΔT
Coefficient Sensible Latent
1.25000 4.6 10 57.5
1.25000 4.6 10 57.5
1.92000 4.6 10 88.32
1.92000 4.6 10 88.32

Heat Instantaneous Load


Unsunlit Area ΔT
Coefficient Sensible Latent
1.68000 0.44 10 7.392
3.44000 0.44 10 15.136
Heat Transmission through Sunlit Building Structure

Heat Instantaneous Load


Sunlit Area ETD
Coefficient Sensible Latent
46.800000 1.222 16.06 918.464976
20.800000 1.222 16.06 408.206656

Instantaneous Load
Sunlit Area SHGF SC
Sensible Latent
4.00000 132 1 528
1.92000 132 1 253.44
0.50000 132 1 66
0.50000 132 1 66
1.92000 132 1 253.44
1.92000 132 1 253.44
1.92000 132 1 253.44
1.92000 132 1 253.44
0.50000 129 1 64.5
0.50000 129 1 64.5
1.92000 129 1 247.68

Miscellaneous Load
Instantaneous Load
Description
Sensible Latent
Computer 511
Printer: Desktop Small Office type 56
Fridge 430
LED Screen 65in 265
Computer 511
Printer: Desktop Small Office type 56
Computer 511
Printer: Desktop Small Office type 56
Computer 511
Printer: Desktop Small Office type 56
Computer 511
Printer: Desktop Small Office type 56
50
81.6
Time 1:00 PM

Cooling Load Factor, CLF Design Cooling Load


Sensible Latent Sensible Latent
0.91 0.91 955.5 700.7
0.63 0.63 44.1 28.35
0.91 0.91 204.75 150.15
0.63 0.63 44.1 28.35
0.91 0.91 204.75 150.15
0.63 0.63 44.1 28.35
0.91 0.91 273 200.2
0.63 0.63 44.1 28.35
0.91 0.91 273 200.2
0.63 0.63 44.1 28.35
2131.5 1543.15

Cooling Load Factor, CLF Design Cooling Load


Sensible Latent Sensible Latent
0.93 147.312
0.93 133.92
0.73 7.884
0.93 53.568
0.93 22.32
0.73 7.884
0.93 53.568
0.93 22.32
0.73 7.884
0.93 53.568
0.93 22.32
0.73 7.884
0.93 53.568
0.93 22.32
0.73 7.884
624.204
Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 1.00 1019.61419513 4056.66702539
1.00 1.00 37.6159750807 149.660024808
1.00 1.00 175.246189788 697.239644988
1.00 1.00 39.1206140839 155.6464258
1.00 1.00 216.668016465 862.041742895
1.00 1.00 37.6159750807 149.660024808
1.00 1.00 216.668016465 862.041742895
1.00 1.00 37.6159750807 149.660024808
1.00 1.00 232.599488263 925.427165166
1.00 1.00 40.6252530871 161.632826793
2053.38969852 8169.67664835

Room 2nd Floor


Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 254.176
1.00 571.896
1.00 879.84
1705.912

Room 2nd Floor


Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 57.5
1.00 57.5
1.00 88.32
1.00 88.32
291.64

Room 2nd Floor


Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 7.392
1.00 15.136
22.528
Room 2nd Floor
Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 918.464976
1.00 408.206656
1326.671632

Room 2nd Floor


Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
0.58 306.24
0.58 146.9952
0.58 38.28
0.58 38.28
0.58 146.9952
0.58 146.9952
0.58 146.9952
0.58 146.9952
0.58 37.41
0.58 37.41
0.58 143.6544
1336.2504

2nd Floor
Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 7665
1.00 840
1.00 430
1.00 265
1.00 2044
1.00 224
1.00 2044
1.00 224
1.00 2555
1.00 280
1.00 2555
1.00 280
19406

SENSIBLE LATENT TOTAL


28,898.10 9,712.83 38,610.92
Specific Volume (Outside) 0.8989
Humidity Ratio (Outside) 0.0248
Humidity Ratio (Inside) 0.0082
Area/Building
Inside Design Condition Dry Bulb Temperature 22
Outside Design Condition Dry Bulb Temperature 32
Location Butuan City Coordinates 8.944144812, 125.53278260

3rd Floor No. Occupant

Multipurpose Hall 43
Multipurpose Hall Male Comfort Room 1
Multipurpose Hall Female Comfort Room 1
TOTAL 45

Room Number of Lights

5
Multipurpose Hall
12
2
Multipurpose Hall Male Comfort Room
1
2
Multipurpose Hall Female Comfort Room
1
TOTAL 23

Room Number of change per hour

Multipurpose Hall 0.48


Multipurpose Hall Male Comfort Room 0.34
Multipurpose Hall Female Comfort Room 0.34
TOTAL

Opaque Surface (Concrete Wall/Roof/Floor)


Dimension
Exposure (N, NE, E, SE, SW,W)
L W
N 8 3
E 18 3
TOTAL

Opaque Surface (Window)


Dimension
Exposure (N, NE, E, SE, SW,W)
L W
N 0.5 1
N 0.5 1
E 1.6 2.5
E 1.6 2.5
E 1.6 2.5
TOTAL

Opaque Surface (Concrete Wall/Roof/Floor)


Dimension
Exposure (N, NE, E, SE, SW,W)
L W
W 18 3
S 8 3
ROOF 14.15 20.2
TOTAL

Opaque Surface (Window)


Dimension
Exposure (N, NE, E, SE, SW,W)
L W
S 1.6 2.5
S 1.6 2.5
TOTAL

Room Items

5
Multipurpose Hall 3
2
TOTAL
DOTC Caraga Regional Office - Annex
22 Relative Humidity
32 Relative Humidity
44144812, 125.53278260 Month May

Occupant
Heat Per Occupant
Occupant Activity
Sensible Latent
43 Seated 65 30
1 Seated 65 30
1 Seated 65 30
45

Lightning
Wattage Instantaneous Load
Type of Bulb Hours On
Ratting Sensible Latent
LED Light Bulb 12 10 72
Circular LED 20 10 288
LED Light Bulb 9 10 21.6
Circular LED 20 10 24
LED Light Bulb 9 10 21.6
Circular LED 20 10 24

Air Infiltration
Wall Dimension Instantaneous Load
change per hour
L W H Sensible Latent
0.48 15.955 12 3 3067.1086884 12447
0.34 2.045 4 3 92.820113472 377
0.34 2.045 4 3 92.820113472 377

Heat Transmission through Unsunlit Building Structure

Heat Instantaneous Load


Unsunlit Area ΔT
Coefficient Sensible Latent
24.0000000 1.222 10 293.28
54.0000000 1.222 10 659.88

Heat Instantaneous Load


Unsunlit Area ΔT
Coefficient Sensible Latent
0.500000 4.6 10 23
0.500000 4.6 10 23
4.000000 4.6 10 184
4.000000 4.6 10 184
4.000000 4.6 10 184

Heat Transmission through Sunlit Building Structure

Heat Instantaneous Load


Sunlit Area ETD
Coefficient Sensible Latent
54.000000 1.222 16.06 1059.76728
24.000000 1.222 16.06 471.00768
285.830000 1.222 16.06 5609.5052156

Instantaneous Load
Sunlit Area SHGF SC
Sensible Latent
4.000000 129 1.00 516
4.000000 129 1.00 516

Miscellaneous Load
Instantaneous Load
Description
Sensible Latent
Computer 511
Projector Resolution 1024X768 240
Speakers 5000
50
81.6
Time 1:00 PM

Cooling Load Factor, CLF Design Cooling Load


Sensible Latent Sensible Latent
0.91 0.91 2543.45 1173.9
0.91 0.91 59.15 27.3
0.91 0.91 59.15 27.3
2661.75 1228.5

Cooling Load Factor, CLF Design Cooling Load


Sensible Latent Sensible Latent
0.93 66.96
0.93 267.84
0.63 13.608
0.63 15.12
0.63 13.608
0.63 15.12
392.256

Cooling Load Factor, CLF Design Cooling Load


Sensible Latent Sensible Latent
1.00 1.00 3067.1086884 12446.9466135
1.00 1.00 92.820113472 376.682770132
1.00 1.00 92.820113472 376.682770132
3252.74891534 13200.3121537

Room 3rd Floor


Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 293.28
1.00 659.88
953.16

Room 3rd Floor


Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 23
1.00 23
1.00 184
1.00 184
1.00 184
598

Room 3rd Floor


Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 1059.76728
1.00 471.00768
1.00 5609.5052156
7140.280176

Room 3rd Floor


Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
0.58 299.28
0.58 299.28
598.56

3rd Floor
Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 2555
1.00 720
1.00 10000
13275
SENSIBLE LATENT TOTAL
28,871.76 14,428.81 43,300.57
Specific Volume (Outside) 0.8989
Humidity Ratio (Outside) 0.0248
Humidity Ratio (Inside) 0.0082
FLOOR SENSIBLE LATENT TOTAL
First 25,904.32 11,440.62 37,344.94
Second 28,898.10 9,712.83 38,610.92
Third 28,871.76 14,428.81 43,300.57
TOTAL 83,674.17 35,582.26 119,256.42

SHR 0.7016323551