Supply Room 4
Planning Office 5
Planning Office Comfort Room 1
Finance Office 10
Finance Filing Storage 2
Finance Office Comfort Room 1
Cashier Filing Storage 2
Cashier Window 2
TOTAL 27
6
Supply Room
3
2
Planning Office
3
Planning Office Comfort Room 1
8
Finance Office
2
Finance Filing Storage 1
Finance Office Comfort Room 1
Cashier Filing Storage 1
Cashier Window 1
TOTAL 29
Heat
Opaque Surface (Concrete Wall/Roof/Floor)
Dimension
Exposure (N, NE, E, SE, SW,W)
L W
N 8 2.7
E 18 2.7
FLOOR 4 18
TOTAL
Hea
Opaque Surface (Concrete Wall/Roof/Floor)
Dimension
Exposure (N, NE, E, SE, SW,W)
L W
W 18 2.7
S 8 2.7
TOTAL
Room Items
3
Supply Room
1
6
Planning Office 6
1
11
11
Finance Office
1
1
1
Finance Filing Storage
1
2
Cashier Filing Storage 2
Cashier Filing Storage
2
Cashier Window 2
TOTAL
DOTC Caraga Regional Office - Annex
22 Relative Humidity
32 Relative Humidity
44144812, 125.53278260 Month May
Occupant
Heat Per Occupant
Occupant Activity
Sensible Latent
4 Moderately active office work 75 55
5 Seated, very light work 70 45
1 Seated, very light work 70 45
10 Seated, very light work 70 45
2 Moderately active office work 75 55
1 Seated, very light work 70 45
2 Moderately active office work 75 55
2 Moderately active office work 75 55
27
Lightning
Wattage Instantaneous Load
Type of Bulb Hours On
Ratting Sensible Latent
LED Light Bulb 12 10 86.4
Circular LED 20 10 72
LED Light Bulb 12 10 28.8
Circular LED 20 10 72
LED Light Bulb 9 10 10.8
LED Light Bulb 12 10 115.2
Circular LED 20 10 48
Circular LED 20 10 24
LED Light Bulb 9 10 10.8
Circular LED 20 10 24
LED Light Bulb 12 10 14.4
0
Air Infiltration
Wall Dimension Instantaneous Load
change per hour
L W H Sensible Latent
0.48 8 4.5 2.7 529.415062855 2106
0.48 8 4.5 2.7 529.415062855 2106
0.34 1.5 2.5 2.7 39.062743353 155
0.48 9 8 2.7 1058.83012571 4213
0.48 2 4.85 2.7 142.647947491 568
0.34 1.5 2.5 2.7 39.062743353 155
0.48 3 4 2.7 176.471687618 702
0.48 3 1.5 2.7 66.1768828568 263
Instantaneous Load
Sunlit Area SHGF SC
Sensible Latent
1.920000 132 1.00 253.44
1.920000 132 1.00 253.44
1.920000 132 1.00 253.44
1.920000 132 1.00 253.44
4.000000 132 1.00 528
0.500000 132 1.00 66
0.500000 132 1.00 66
1.920000 129 1.00 247.68
1.920000 129 1.00 247.68
0.500000 129 1.00 64.5
0.500000 129 1.00 64.5
Miscellaneous Load
Instantaneous Load
Description
Sensible Latent
Computer 511
Multifunction Large, multiuser, office printer (copy,print,scan) 30max printing speed 990
Computer 511
Printer: Desktop Small Office type 56
LED Screen 65in 265
Computer 511
Printer: Desktop Small Office type 56
LED Screen 65in 265
Fridge 430
Computer 511
Printer: Desktop Small Office type 56
Computer 511
Printer: Desktop Small Office type 56
Cash Register 139.9
Computer 511
50
81.6
Time 1:00 PM
1st floor
Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 1533
1.00 990
1.00 3066
1.00 336
1.00 265
1.00 5621
1.00 616
1.00 265
1.00 430
1.00 511
1.00 56
1.00 1022
1.00 112
1.00 279.8
1.00 1022
16124.8
Operation Office 14
Operation Office Comfort Room 1
Room 1 3
Room 1 Comfort Room 1
Room 2 3
Room 2 Comfort Room 1
Room 3 4
Room 3 Comfort Room 1
Room 4 4
Room 4 Comfort Room 1
TOTAL 33
11
Operation Office
6
Operation Office Comfort Room 1
4
Room 1
1
Room 1 Comfort Room 1
4
Room 2
1
Room 2 Comfort Room 1
4
Room 3
1
Room 3 Comfort Room 1
4
Room 4
1
Room 4 Comfort Room 1
TOTAL
Room Number of change per hour
Room Items
15
15
Operation Office
1
1
4
Room 1
4
4
Room 2
4
5
Room 3
Room 3
5
5
Room 4
5
TOTAL 68
DOTC Caraga Regional Office - Annex
22 Relative Humidity
32 Relative Humidity
44144812, 125.53278260 Month May
Occupant
Heat Per Occupant
Occupant Activity
Sensible Latent
14 Moderately active office work 75 55
1 Seated, very light work 70 45
3 Moderately active office work 75 55
1 Seated, very light work 70 45
3 Moderately active office work 75 55
1 Seated, very light work 70 45
4 Moderately active office work 75 55
1 Seated, very light work 70 45
4 Moderately active office work 75 55
1 Seated, very light work 70 45
33
Lightning
Wattage Instantaneous Load
Type of Bulb Hours On
Ratting Sensible Latent
LED Light Bulb 12 10 158.4
Circular LED 20 10 144
LED Light Bulb 9 10 10.8
LED Light Bulb 12 10 57.6
Circular LED 20 10 24
LED Light Bulb 9 10 10.8
LED Light Bulb 12 10 57.6
Circular LED 20 10 24
LED Light Bulb 9 10 10.8
LED Light Bulb 12 10 57.6
Circular LED 20 10 24
LED Light Bulb 9 10 10.8
LED Light Bulb 12 10 57.6
Circular LED 20 10 24
LED Light Bulb 9 10 10.8
Air Infiltration
Wall Dimension Instantaneous Load
change per hour
L W H Sensible Latent
0.48 9 8 2.6 1019.61419513 4056.66702539
0.34 1.5 2.5 2.6 37.6159750807 149.660024808
0.48 3.3 3.75 2.6 175.246189788 697.239644988
0.34 1.5 2.6 2.6 39.1206140839 155.6464258
0.48 3 5.1 2.6 216.668016465 862.041742895
0.34 1.5 2.5 2.6 37.6159750807 149.660024808
0.48 3 5.1 2.6 216.668016465 862.041742895
0.34 1.5 2.5 2.6 37.6159750807 149.660024808
0.48 4.5 3.65 2.6 232.599488263 925.427165166
0.34 1.5 2.7 2.6 40.6252530871 161.632826793
Instantaneous Load
Sunlit Area SHGF SC
Sensible Latent
4.00000 132 1 528
1.92000 132 1 253.44
0.50000 132 1 66
0.50000 132 1 66
1.92000 132 1 253.44
1.92000 132 1 253.44
1.92000 132 1 253.44
1.92000 132 1 253.44
0.50000 129 1 64.5
0.50000 129 1 64.5
1.92000 129 1 247.68
Miscellaneous Load
Instantaneous Load
Description
Sensible Latent
Computer 511
Printer: Desktop Small Office type 56
Fridge 430
LED Screen 65in 265
Computer 511
Printer: Desktop Small Office type 56
Computer 511
Printer: Desktop Small Office type 56
Computer 511
Printer: Desktop Small Office type 56
Computer 511
Printer: Desktop Small Office type 56
50
81.6
Time 1:00 PM
2nd Floor
Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 7665
1.00 840
1.00 430
1.00 265
1.00 2044
1.00 224
1.00 2044
1.00 224
1.00 2555
1.00 280
1.00 2555
1.00 280
19406
Multipurpose Hall 43
Multipurpose Hall Male Comfort Room 1
Multipurpose Hall Female Comfort Room 1
TOTAL 45
5
Multipurpose Hall
12
2
Multipurpose Hall Male Comfort Room
1
2
Multipurpose Hall Female Comfort Room
1
TOTAL 23
Room Items
5
Multipurpose Hall 3
2
TOTAL
DOTC Caraga Regional Office - Annex
22 Relative Humidity
32 Relative Humidity
44144812, 125.53278260 Month May
Occupant
Heat Per Occupant
Occupant Activity
Sensible Latent
43 Seated 65 30
1 Seated 65 30
1 Seated 65 30
45
Lightning
Wattage Instantaneous Load
Type of Bulb Hours On
Ratting Sensible Latent
LED Light Bulb 12 10 72
Circular LED 20 10 288
LED Light Bulb 9 10 21.6
Circular LED 20 10 24
LED Light Bulb 9 10 21.6
Circular LED 20 10 24
Air Infiltration
Wall Dimension Instantaneous Load
change per hour
L W H Sensible Latent
0.48 15.955 12 3 3067.1086884 12447
0.34 2.045 4 3 92.820113472 377
0.34 2.045 4 3 92.820113472 377
Instantaneous Load
Sunlit Area SHGF SC
Sensible Latent
4.000000 129 1.00 516
4.000000 129 1.00 516
Miscellaneous Load
Instantaneous Load
Description
Sensible Latent
Computer 511
Projector Resolution 1024X768 240
Speakers 5000
50
81.6
Time 1:00 PM
3rd Floor
Cooling Load Factor, CLF Design Cooling Load
Sensible Latent Sensible Latent
1.00 2555
1.00 720
1.00 10000
13275
SENSIBLE LATENT TOTAL
28,871.76 14,428.81 43,300.57
Specific Volume (Outside) 0.8989
Humidity Ratio (Outside) 0.0248
Humidity Ratio (Inside) 0.0082
FLOOR SENSIBLE LATENT TOTAL
First 25,904.32 11,440.62 37,344.94
Second 28,898.10 9,712.83 38,610.92
Third 28,871.76 14,428.81 43,300.57
TOTAL 83,674.17 35,582.26 119,256.42
SHR 0.7016323551