You are on page 1of 65

AIR HANDLING UNIT TEST DATA

Description Submitted data Actual Test Data Remarks Date


Unit Designation AHU 1
Quantity 2
Location 2F Utility Area
Manufacturer
Model Number
Model Type Horizontal Draw Thru
Area Served Auto Assy
Total Heat (TR) 85 TR
Sensible Heat (TR)
Max Face Velocity (FPM) 500 FPM
Entering Air Temperature (DB)
Entering Air Temperature (WB)
Leaving Air Temperature (DB)
Leaving Air Temperature (WB)
Supply Air Flow (CFM) 7514 CFM
Free Air Flow (CFM) 7514 LPS
Total Static Pressure( Pa) 622 Pa
Water Flow (GPM) 12.87 LPS
Mid Filter 35%
Final Filter 85%
Power 20HP
Voltage 460V

AIR HANDLING UNIT TEST DATA


Description Submitted data Actual Test Data Remarks Date
Unit Designation AHU 1
Quantity 3
Location 2F Utility Area
Manufacturer
Model Number
Model Type Horizontal Draw Thru
Area Served Plating
Total Heat (TR) 85 TR
Sensible Heat (TR)
Max Face Velocity (FPM) 500 FPM
Entering Air Temperature (DB)
Entering Air Temperature (WB)
Leaving Air Temperature (DB)
Leaving Air Temperature (WB)
Supply Air Flow (LPS) 7514 LPS
Free Air Flow (CFM) 7514 LPS
Total Static Pressure( Pa) 622 Pa
Water Flow (GPM) 12.87 LPS
Mid Filter 35%
Final Filter 85%
Power 20HP
Voltage 460V

AIR HANDLING UNIT TEST DATA


Description Submitted data Actual Test Data Remarks Date
Unit Designation AHU 2
Quantity 3
Location Molding & Stamping
Manufacturer
Model Number
Model Type Horizontal Draw Thru
Area Served Plating
Total Heat (TR) 70 TR
Sensible Heat (TR)
Max Face Velocity (FPM) 500 FPM
Entering Air Temperature (DB)
Entering Air Temperature (WB)
Leaving Air Temperature (DB)
Leaving Air Temperature (WB)
Supply Air Flow (LPS) 11056 LPS
Free Air Flow (CFM) 11056 LPS
Total Static Pressure( Pa) 622 Pa
Water Flow (GPM) 10.6 LPS
Mid Filter 35%
Final Filter 85%
Power 30HP
Voltage 460V

PRE-COOL AIR HANDLING UNIT TEST DATA


Description Submitted data Actual Test Data Remarks Date
Unit Designation PAU 1
Quantity 4
Location LEVEL 1 &2
Manufacturer
Model Number
Model Type Horizontal draw thru
Area Served HALLWAY, OFFICES
Total Heat (TR) 4.2 TR
Sensible Heat (TR) 3.1 TR
Max Face Velocity (FPM) 500 FPM
Entering Air Temperature (DB) 35C
Entering Air Temperature (WB) 28C
Leaving Air Temperature (DB) 32C
Leaving Air Temperature (WB) 25.8C
Supply Air Flow (LPS) 354 LPS
Free Air Flow (CFM) 250 Pa
Total Static Pressure( Pa) 622 Pa
Water Flow (GPM) .66 LPS
Mid Filter 85%
Final Filter 85%
Power .75HP
Voltage 230V
FAN TEST DATA
Description Submitted data Actual Test Data
Unit Designation EF 1
Quantity 2
Location TBD
Manufacturer
Serial Number
Service Plating Area
Capacity 6187 LPS
ESP 375 Pa
Fan Motor Power 5.6 kW
Fan Motor Voltage 460V
Fan Motor Phase 3

FAN TEST DATA


Description Submitted data Actual Test Data
Unit Designation EF 2
Quantity 2
Location TBD
Manufacturer
Serial Number
Service Molding Area
Capacity 14158 LPS
ESP 375 Pa
Fan Motor Power 11.2 kW
Fan Motor Voltage 460V
Fan Motor Phase 3

FAN TEST DATA


Description Submitted data Actual Test Data
Unit Designation EF 3
Quantity 2
Location TBD
Manufacturer
Serial Number
Service Warehouse (Raws)
Capacity 5899 LPS
ESP 375 Pa
Fan Motor Power 5.6 kW
Fan Motor Voltage 460V
Fan Motor Phase 3
FAN TEST DATA
Description Submitted data Actual Test Data
Unit Designation EF 4
Quantity 2
Location TBD
Manufacturer
Serial Number
Service Warehouse (Finished)
Capacity 4719 LPS
ESP 375 Pa
Fan Motor Power 3.72kW
Fan Motor Voltage 460V
Fan Motor Phase 3

FAN TEST DATA


Description Submitted data Actual Test Data
Unit Designation EF 5
Quantity 1
Location Level 1
Manufacturer
Serial Number
Service Lvl 1 Female toilet
Capacity 165 LPS
ESP 250 Pa
Fan Motor Power .1 kW
Fan Motor Voltage 230 V
Fan Motor Phase 1

FAN TEST DATA


Description Submitted data Actual Test Data
Unit Designation EF 6
Quantity 3
Location Level 1 & 2
Manufacturer
Serial Number
Service Male toilet
Capacity 142 LPS
ESP 230 Pa
Fan Motor Power .1 kW
Fan Motor Voltage 230 V
Fan Motor Phase 1
FAN TEST DATA
Description Submitted data Actual Test Data
Unit Designation EF 7
Quantity 6
Location Level 1 & 2
Manufacturer
Serial Number
Service Male & Female toilet
Capacity 94.4 LPS
ESP 230 Pa
Fan Motor Power .1 kW
Fan Motor Voltage 230 V
Fan Motor Phase 1

FAN TEST DATA


Description Submitted data Actual Test Data
Unit Designation EF 8
Quantity 1
Location Level 1
Manufacturer
Serial Number
Service Clinic toilet
Capacity 47.19 LPS
ESP 230 Pa
Fan Motor Power .05 kW
Fan Motor Voltage 230 V
Fan Motor Phase 1

FAN TEST DATA


Description Submitted data Actual Test Data
Unit Designation EF 9
Quantity 4
Location Level 1
Manufacturer
Serial Number
Service Janitor & toilet
Capacity 23.6 LPS
ESP 230 Pa
Fan Motor Power .05 kW
Fan Motor Voltage 230 V
Fan Motor Phase 1
FAN TEST DATA
Description Submitted data Actual Test Data
Unit Designation EF 10
Quantity 1
Location Level 1
Manufacturer
Serial Number
Service Cafeteria / Food Prep
Capacity 708 LPS
ESP 350 Pa
Fan Motor Power .746 kW
Fan Motor Voltage 230 V
Fan Motor Phase 1

FAN TEST DATA


Description Submitted data Actual Test Data
Unit Designation EF 11
Quantity 1
Location Level 1
Manufacturer
Serial Number
Service Alkaline & Acid Storage
Capacity 1188 LPS
ESP 250 Pa
Fan Motor Power .746 kW
Fan Motor Voltage 230 V
Fan Motor Phase 1
Remarks

Remarks

Remarks
Remarks

Remarks

Remarks
Remarks

Remarks

Remarks
Remarks

Remarks
WATER COOLED CHILLER TEST DATA
Description Submitted data Actual Test Data
Unit Designation CH 1
Quantity 1
Location 2F utility area
Manufacturer
Model Number
Model Type
Unit Capacity 2110 kW
Motor Power 325 kW
Motor Volts 460 V
Motor Phase 3

EVAPORATOR TEST DATA


Description Submitted data Actual Test Data
Total LPS 90.84 LPS
Entering Temperature (˚C) 12.22 ˚C
LeavingTemperature (˚C) 6.67 ˚C
Numberof Pass 2
Max Pressure Drop (kPa) 53.8 kPa
Fouling factor 0.0001
CONDENSER TEST DATA
Description Submitted data Actual Test Data
Total LPS 113.6 LPS
Entering Temperature (˚C) 29.4 ˚C
LeavingTemperature (˚C) 35 ˚C
Numberof Pass 2
Max Pressure Drop (kPa) 53.8 KpA
Fouling factor 0.00025
ST DATA
Remarks Date

TA
Remarks Date

TA
Remarks Date
COOLING TOWER UNIT TEST DATA
Description Submitted data Actual Test Data
Unit Designation CT 1
Quantity 1
Location 2F UTILITY AREA
Manufacturer
Model Number
Model Type INDUCED TYPE
Units Served Chiller units
Heat Dissipation Capacity (LPS) 113.6 LPS
Water Entering Temperature (˚C) 35(˚C)
Water Leaving Temperature (˚C) 29.4 (˚C)
Max Pressure Drop (kPa) 35.87 kPa
Design wet bulb temperature (˚C) 27.78 (˚C)
Motor Power 30 kW
Motor Voltage 460V
Motor Phase 3
Remarks
PUMPS TEST DATA
Description Submitted data Actual Test Data
Unit Designation CHWP 1
Quantity 2
Manufacturer
Model Number
Horizontal Split
Model Type Case,Double Suction,
Centrifugal Pump
Service Chilled Water
Capacity 90.8 LPS
Total Dynamic Head 672 kPa
Motor Speed 1800 rpm
Motor Power 93.2 kW
Motor Voltage 460 V
Motor Phase 3
Motor Poles 4
Seal Gland Mechanical Seal

PUMPS TEST DATA


Description Submitted data Actual Test Data
Unit Designation CWP1
Quantity 2
Manufacturer
Model Number
Horizontal Split
Model Type Case,Double Suction,
Centrifugal Pump
Service Condenser Water
Capacity 113.5 LPS
Total Dynamic Head 389.55 kPa
Motor Speed 1800 rpm
Motor Power 74.6 kW
Motor Voltage 460 V
Motor Phase 3
Motor Poles 4
Seal Gland Mechanical Seal
Remarks

Remarks
FAN COIL UNIT (CHILLED WATER TYPE) TEST DATA
Description Submitted data Actual Test Data
Unit Designation FCU 1
Quantity 6
Manufacturer
Serial Number
Type 4-way ceiling cassette
Automation, Reception,
Area Served Store, MGR, Equip
Storage
COOLING DATA
Total Heat (kW) 5.9 kW
Air Flow (LPS) 306.7 LPS
Water Flow (LPS) 0.285 LPS
Entering Water Temp. (˚C) 6.67 (˚C)
Leaving Water Temp. (˚C) 12.22 (˚C)
ELECTRICAL DATA
Power 37 watts
Voltage 230 V
Motor Phase 1
Weight (kg) 30 kg

FAN COIL UNIT (CHILLED WATER TYPE) TEST DATA


Description Submitted data Actual Test Data
Unit Designation FCU 2
Quantity 7
Manufacturer
Serial Number
Type 4-way ceiling cassette

Mech Storage,Board
Room, Presence Room,
Area Served
BMS Room, Vault,
Facilities Office

COOLING DATA
Total Heat (kW) 8.8 kW
Air Flow (LPS) 420 LPS
Water Flow (LPS) 0.425 LPS
Entering Water Temp. (˚C) 6.67 (˚C)
Leaving Water Temp. (˚C) 12.22 (˚C)
ELECTRICAL DATA
Power 90 watts
Voltage 230 V
Motor Phase 1
Weight (kg) 32 kg

FAN COIL UNIT (CHILLED WATER TYPE) TEST DATA


Description Submitted data Actual Test Data
Unit Designation FCU 3
Quantity 7
Manufacturer
Serial Number
Type 4-way ceiling cassette

Inward QA, PQA, Spare


Parts, Clinic, Main
Lobby, Cafeteria, Food
Area Served Prep, Training Room, L1
Office, L2 Office, Tooling,
Prod Office, Inspection
Office, Wet Lab

COOLING DATA
Total Heat (kW) 11.75 kW
Air Flow (LPS) 500 LPS
Water Flow (LPS) .57 LPS
Entering Water Temp. (˚C) 6.67 (˚C)
Leaving Water Temp. (˚C) 12.22 (˚C)
ELECTRICAL DATA
Power 120 watts
Voltage 230 V
Motor Phase 1
Weight (kg) 36 kg

FAN COIL UNIT (CHILLED WATER TYPE) TEST DATA


Description Submitted data Actual Test Data
Unit Designation FCU 4
Quantity 14
Manufacturer
Serial Number
Type Wall Mounted
Location, DN,DR, MGR1-
Area Served 10, Docs Room
COOLING DATA
Total Heat (kW) 2.7 kW
Air Flow (LPS) 132 LPS
Water Flow (LPS) 0.13 LPS
Entering Water Temp. (˚C) 6.67 (˚C)
Leaving Water Temp. (˚C) 12.22 (˚C)
ELECTRICAL DATA
Power 9 watts
Voltage 230 V
Motor Phase 1
Weight (kg) 30 kg

FAN COIL UNIT (CHILLED WATER TYPE) TEST DATA


Description Submitted data Actual Test Data
Unit Designation FCU 5
Quantity 4
Manufacturer
Serial Number
Type Wall Mounted
Area Served MT1-3, VP Room
COOLING DATA
Total Heat (kW) 3.5 kW
Air Flow (LPS) 175 LPS
Water Flow (LPS) 0.16 LPS
Entering Water Temp. (˚C) 6.67 (˚C)
Leaving Water Temp. (˚C) 12.22 (˚C)
ELECTRICAL DATA
Power 9 watts
Voltage 230 V
Motor Phase 1
Weight (kg) 30 kg

FAN COIL UNIT (CHILLED WATER TYPE) TEST DATA


Description Submitted data Actual Test Data
Unit Designation FCU 6
Quantity 3
Manufacturer
Serial Number
Type Ceiling Mounted
Server Room, IT Server,
Area Served Hub Room
COOLING DATA
Total Heat (kW) 13.19 kW
Air Flow (LPS) 175 LPS
Water Flow (LPS) 0.16 LPS
Entering Water Temp. (˚C) 6.67 (˚C)
Leaving Water Temp. (˚C) 12.22 (˚C)
ELECTRICAL DATA
Power 9 watts
Voltage 230 V
Motor Phase 1
Weight (kg) 30 kg
DATA
Remarks

DATA
Remarks
DATA
Remarks

DATA
Remarks
DATA
Remarks

DATA
Remarks
SPLIT TYPE AC UNIT TEST DATA
Description Submitted data Actual Test Data

Unit Designation DX 1 for Indoor & ACCU


1 for outdoor
Server, IT Server, Hub
Service
room
Cooling Capacity 13.19 kW
Fan Coil Unit
Quantity 3
Type Ceiling Suspended
Supply Air 635 CFM
External Static Pressure (Pa)
Air Cooled Condensing Unit
Quantity 3
Cooling Capacity 13.19 kW
Power Consumption 5400 watts
Refrigerant Suction Ø 22.3
Refrigerant Liquid Ø 9.5
Voltage 230
Phase 3
Remarks
SCRUBBER EXHAUST TEST DATA
Description Submitted data Actual Test Data
Unit Designation SCR 1
Quantity 1
Location
Service Plating Machine
capacity 1668 LPS
External Static Pressure
Motor Power
Motor Voltage 460
Motor Phase 3
Motor Frequency 60
Remarks
MIST ELIMINATOR TEST DATA
Description Submitted data Actual Test Data
Unit Designation ME 1
Quantity 1
Location TBD
Service Plating Machine
Capacity 4719 LPS
External Static Pressure -
Motor Power -
Motor Voltage 460 V
Motor Phase 3
Motor Frequency 60 hz
Remarks
Air Compressor TEST DATA
Description Submitted data Actual Test Data
Unit Designation AC 1
Quantity 1
Service Production Area
Capacity Free Air (LPS) 392 LPS
Capacity Working Pressure 8.6 Bar
Power 144 kW
Voltage 460 V
Phase 3
Frequency 60 Hz

Air Compressor TEST DATA


Description Submitted data Actual Test Data
Unit Designation AC 2
Quantity 1
Service Production Area
Capacity Free Air (LPS) 283 LPS
Capacity Working Pressure 8.6 Bar
Power 122 kW
Voltage 460 V
Phase 3
Frequency 60 Hz
Remarks

Remarks
Air Dryer TEST DATA
Description Submitted data Actual Test Data
Unit Designation AD 1
Quantity 1
Capacity 392 LPS
Pressure Drop (Bar) .12 Bar
Power 10.7 kW
Voltage 460 V
Phase 3
Frequency 60 Hz

Air Dryer TEST DATA


Description Submitted data Actual Test Data
Unit Designation AD 2
Quantity 1
Capacity 283 LPS
Pressure Drop (Bar) .12 Bar
Power 8.6 kW
Voltage 460 V
Phase 3
Frequency 60 Hz
Remarks

Remarks
Air Receiver Tank TEST DATA
Description Submitted data Actual Test Data
Unit Designation AR 1
Quantity 1
Capacity 2000 L

Air Receiver Tank TEST DATA


Description Submitted data Actual Test Data
Unit Designation AR 2
Quantity 1
Capacity
Remarks

Remarks
Hot Water Boiler TEST DATA
Description Submitted data Actual Test Data
Unit Designation AR 2
Service Hot Water
Number of Units 1
Water flow rate (LPS) 12.66 LPS
Heating Capacity 275 kW
Fuel Electric
Power 275 kW
Voltage 460 V
Phase 3
Frequency 60 Hz
Remarks
PROCESS HOT WATER PUMP TEST DATA
Description Submitted data Actual Test Data
Unit Designation PHWP 1
Type End-Suction (C.P.)
Number of Units 1
Capacity 12.66 LPS
Total Dynamic Head (kPa) 275 kW
Drive Electric
Motor Speed 1800 rpm
Motor Power 15 HP
Motor Voltage 460 V
Motor Phase 3
Motor Frequency 60 Hz
A
Remarks
PROCESS COOLING WATER PUMP TEST DATA
Description Submitted data Actual Test Data
Unit Designation PCWP 1
Type End-Suction (C.P.)
Number of Units 1
Capacity 14.5 LPS
Total Dynamic Head (kPa) 690 Kpa
Drive Flanged Coupled
Motor Speed 1800 rpm
Motor Power 20 HP
Motor Voltage 460 V
Motor Phase 3
Motor Frequency 60 Hz
ATA
Remarks
EXPANSION TANK TEST DATA
Description Submitted data Actual Test Data
Unit Designation ET - 1
Location Equipment Room
Service Chilled Water
Number of Units 1
Unit Capacity 90 L
Type Bladder

EXPANSION TANK TEST DATA


Description Submitted data Actual Test Data
Unit Designation ET - 2
Location Equipment room
Service PCW
Number of Units 1
Unit Capacity 90 L
Type Bladder

EXPANSION TANK TEST DATA


Description Submitted data Actual Test Data
Unit Designation ET - 3
Location Boiler room
Service PHW
Number of Units 1
Unit Capacity 90 L
Type Bladder
Remarks

Remarks

Remarks
AIR SEPARATOR TEST DATA
Description Submitted data Actual Test Data
Unit Designation AS - 1
Location Equipment room
Service Chilled Water
Number of Units 1
Unit Capacity 2880 GPM
Type In line

AIR SEPARATOR TEST DATA


Description Submitted data Actual Test Data
Unit Designation AS - 2
Location Equipment room
Service PCW
Number of Units 1
Unit Capacity 460
Type In line

AIR SEPARATOR TEST DATA


Description Submitted data Actual Test Data
Unit Designation AS - 3
Location Boiler room
Service PHW
Number of Units 1
Unit Capacity 460
Type In line
Remarks

Remarks

Remarks
PRE FILTER TEST DATA
Description Submitted data Actual Test Data
Unit Designation PF - 1
Quantity 1
Capacity 392 LPS
Efficiency 1 micron

PRE FILTER TEST DATA


Description Submitted data Actual Test Data
Unit Designation PF - 2
Quantity 1
Capacity 283 LPS
Efficiency 1 micron
Remarks

Remarks
AIR FILTER TEST DATA
Description Submitted data Actual Test Data
Unit Designation AF - 1
Quantity 1
Capacity 392 LPS
Efficiency 1 micron

AIR FILTER TEST DATA


Description Submitted data Actual Test Data
Unit Designation AF - 2
Quantity 1
Capacity 283 LPS
Efficiency 1 micron
Remarks

Remarks
HEAT EXCHANGER TEST DATA
Description Submitted data Actual Test Data
Unit Designation HX - 1
Number of units 1
Cold Side
Flow rate 14.5 LPS
Temperature IN 5.5 ˚C
Temperature OUT 12 ˚C
Hot Side
Flow rate 14.5 LPS
Temperature IN 22 ˚C
Temperature OUT 28.5 ˚C
Remarks
PRE - COMMISSIONING CHECKLIST

Ready Ready
1. HVAC Units & Build-Up Units Date
Yes No Yes No
a. GENERAL d. COILS (ELECTRIC)
Louvers Installed Sizes and construction
Manual dampers adjusted & locked Airflow Direction
Automatic dampers operating Duct connection
Housing complete Safety switches
Access door closed Contractors and disconnect switches
Condensate drain piping & pan Electrical service and connections
Free from debris and dirt Obstruction &debris
b. FILTERS e. FANS
Type and size Rotation
Number Wheel clearance and balance
Clean Bearing and Motor lubrication
Frame - clean Drive alignment
Temporary Belt tension
c. COILS (HYDRONIC) Drive set screw tight
Size and rows Belt guard in place
Fin spacing and condition Flexible duct connector alignment
Obstruction & debris Starters and disconnect switches
Airflow and Direction Electrical service and connections
Piping leakage VFD set up for correct frequency
Correct piping connections f. VIBRATION ISOLATION
Valves open or set Springs and compression
Air vents or steam traps Base level and free
Provisions for TAB measurement

Ready Ready
2. DUCT SYSTEMS Date 3. PUMPS
Yes No Yes No
a. GENERAL a. MOTORS
Manual dampers adjusted & locked Rotation
Doors closed as required Lubrication
Fire dampers open and accessible Alignment
Terminal units open or set Set screws tight
Registers and diffusers open & set Guards in place
Turning vanes in square elbows Starters and disconnect switches
Provisions made for Tab Requirements Electrical servce and connections
Duct work sealed as required b. PIPING
Correct flow and connections
Leakage
Valves open or set
Strainer clean
Air vented
Flexible connections
Cavitation possibilities
c. BASES
Vibration Isolation
Grouting
Leveling

Ready Ready
4. HYDRONIC EQUIPMENT Date 5. HYDRONIC PIPING SYSTEM
Yes No Yes No
a. BOILERS Leak tested and flushed
Operating controls & devices Fluid levels and make up
Safety controls & devices Relief or safety valve setting
Lubricatio of pumps andfans Compression tanks / Air vented
Draft controls and Devices Steam traps and connections
Piping connection and flow Strainers clean
Valves open or set Valves open or set
Water make-up provisions Provisions made for TAB measurements
Blow down provisions
6. CONTROL SYSTEM
Electrical connections
b. HEAT EXCHANGERS Data centers operating
Correct flow and connection Outdoor/return damper set
Valves open or set Economizer control set
Air vensts or steam traps Static pressure control set
c. COOLING TOWERS AND CONDENSERS Space controls operating
Correct flow and proctecton Complete system operating
Valves open or set Valves open or set
Leakage
7. OTHER CHECKS
sump waterr level
Spray nozzle a. Other trade or personel notified of Tab
Fan / Pump rotation work requirements.
Drives and alignment b. Preliminary data complete
Guards in place c. Test report forms prepared
Starters and Disconnect switches
Electrical connections
Date

Date
Date
To be completed by design engineer To be completed by test and air
Design CFM VAV Min/Max Actual CFM VAV min/max

Space Pressure
Location Supply Return Exhaust Relationship Supply Return Exhaust
Volume
+0-

Plating Area

Molding &
Stamping
Area

Raw Materials
Warehouse

Finished
Goods
Warehouse

Level 1
female toilet

Level 1 & 2
Male toilet
Level 1 & 2
toilet

clinic toilet

Janitor &
toilet
Tooling
Production

Level 1 Office

Level 2 Office

To be completed by design engineer To be completed by test and air


Design CFM VAV Min/Max Actual CFM VAV min/max
Pressure
Space
Location Supply Return Exhaust Relationship Supply Return Exhaust
Volume
+0-
Inspection
Office
Documents
room

Server Room

Cafeteria /
Food Prep

Training room

Alkaline
Storage / Acid
Storage &
Mezzanine

HUB room

Main Lobby

Facilities
Office

BMS room
pleted by test and air balance technician
Percent of Design

Actual # air
Suppy Return Exhaust changes per
hour

pleted by test and air balance technician


Percent of Design
Actual # air
Suppy Return Exhaust changes per
hour
PUNCHLIST FORM
Equipment: Water - CooledChiller
Site: 1st Philippine Industrial Park (Sto tomas, Batangas)
System ID: CH1
Location: 2F Utility Area
Project: TE Connectivity
Date:
Category Raised by On
Item No. Punchlist Details
A B Name Date

Category A, Major Punchlist items must be resolved prior to tetsing & commissioning activities commencing.
Category B, Minor Punchlist not impacting on commissioning, Must be resolved for final Handover.

Punchlist Raised by:


Signature Date
PL Cleared By:
Signature Date
Verified By:
Signature Date
REMARKS:
PUNCHLIST FORM
Equipment: Water - CooledChiller
Site: 1st Philippine Industrial Park (Sto tomas, Batangas)
System ID: CH1
Location: 2F Utility Area
Project: TE Connectivity
Date:
Category Raised by On
Item No. Punchlist Details
A B Name Date

Category A, Major Punchlist items must be resolved prior to tetsing & commissioning activities commencing.
Category B, Minor Punchlist not impacting on commissioning, Must be resolved for final Handover.

Punchlist Raised by:


Signature Date
PL Cleared By:
Signature Date
Verified By:
Signature Date
REMARKS:
ater - CooledChiller
CH1
2F Utility Area

Cleared
Date

vities commencing.
andover.

Date

Date

Date
ater - CooledChiller
CH1
2F Utility Area

Cleared
Date

vities commencing.
andover.

Date

Date

Date