Stored energy motor operator for SACE S6-S7 circuit-breakers

S6-S7

Rated voltage, Un AC DC
[V] – 24
[V] – 48
[V] – 60
[V] 110 110
[V] 120-127 120-127
[V] 220-250 220-250
[V] 380 –
[V] – –
Operating voltage 85 ... 110% Un 85 ... 110% Un
Inrush power absorption, Ps 660 [VA] 600 [W]
Service power absorption, Pc 180 [VA] 180 [W]
Operating frequency [Hz] 50-60
Time constant [ms] 22
Duration closing 0.09
opening 1.2
resetting 2
Mechanical life [no. operations] 10000 (S6) / 5000 (S7)
Degree of protection, on the front IP 30
Minimum duration of the opening
and closing command impulse [ms] > 100