SUMP AT PALLIKUTTUMMA
Water demand of Zone Kainakari Zone - I &II, Nedumudi
Zone - I&II, Chambakkulam Zone - I&II, Pulinkunnu and
Kavalm = 15.070 mld
So provide a 400 mm DI K9 pipe from Mambuzhakkri to Pallikuttumma sump - 3200 m and a 400
mm DI K9 from Mabuchakkari to Ramankari - 1400 m and 350 mm DI K9 pipe thereafter up to
Pallikuttumma -1800 m
Page
CLEAR WATER PUMPING MAIN FROM PALLIKUTTUMMA SUMP TO MANKOMBU JN IN
AC ROAD (CHAMBAKKULAM ZONE - II AND NEDUMUDI ZONE - II)
Length of common Pumping Main 3075 m
Demand 2.640 mld
Hours of pumping 20 hrs
Rate of pumping in lps 36.67 say 40 lps
Diameter required assuming velocity of 1m/s 225.73 say 250 mm
Page