You are on page 1of 7

1 Single phase loads connected on the load side of a phase all of the choices

converter shall be permitted to be connected to ______.

2 To measure the area of a dwelling to determine the The floor area


lighting load, the following dimensions are used: computed from
the outside
dimensions
3 Overhead service conductors, when not in excess of 600 15 feet
volts, that pass over residential property, driveways, and
those commercial areas not subject to truck traffic must
have a minimum clearance of:

4 In a balanced three-phase, 4-wire system, the current in Will not flow


the neutral conductor: when all loads
are exactly
balanced
5 In the installation of power resistors, a thermal barrier 300 mm
shall be required if the space between the resistors and
any combustible materials is less than ______ mm.

6 Which of the following shall not be used in wet or damp AC armored


locations? cable

7 In all case where there are energized parts on the front of 1,000 mm
the switchboard or motor control centers, the working
space in front of such equipment shall NOT be less than
_____.

8 Edges that are invisible in an electrical drawing should be broken lines


represented ______.

9 A restaurant with five pieces of kitchen equipment would 70 percent


have a feeder demand factor of _______.
10 Where the voltage between conductors does not exceed 18 inches
300, and not more than 6 feet of service conductors pass
over not more than 4 feet of the overhang portion of the
roof, and the conductors terminate in a through-the-roof
raceway or other approved support, the clearance of
service conductors above the roof is reduced to not less
than:

11 The antenna for a satellite system must be grounded to an accessible


_______. means external
to the building

12 Feeders that contain a common neutral are permitted to all of the above
supply _______.

13 The ampacity of a conductor must be derated where the 86 degrees F


ambient temperature exceeds ________.

14 Resistors and reactors shall not be installed in close 300 mm


proximity to combustible materials such that it
constitutes a fire hazard. What minimum clearance is
required by the code?

15 Which of the following statements is TRUE? A 3-phase AC


unit must be
directly
connected to a
recognized
wiring method
and may not
include a cord
connection.
16 When computing ampacity, a fraction of an ampere is 0.5 or larger
considered only when it is ______.

17 The minimum size of wire used in electrical wiring is the 1.6 mm


former number 14 AWG. Under the metric system shown
in the PEC, the diameter is ______.

18 Wooden plugs shall not be used to mount electrical All of the choices
equipment to which of the following types of material:

19 Under no conditions shall a receptacle be permitted to All of the choices


be installed within ______ from the inside wall of a pool.

20 Overhead service conductors, when not in excess of 150 10 feet


volts to ground, that pass over residential sidewalks,
finished grade (the ground), or over any platform or any
projection from which the conductors may be reached,
must have a minimum clearance of:

21 Overhead service conductors, when not in excess of 300 12 feet


volts, that pass over residential driveways and
commercial areas such as parking lots and drive-in
establishments not subject to truck traffic must have a
clearance of at least:

22 The maximum size of liquid tight flexible metal conduit 100 mm


shall be ______ trade size.

23 Each kitchen in a two-family dwelling unit requires a two 20 amp


minimum of ________ in order to meet the small circuits
appliance load.
24 The code requires that all energized parts of electrical 50 volts
equipment operating at _____ or more shall be guarded
against accidental contacts by approved enclosures.

25 A building has two sets of service drop conductors from a 12


utility pole where Drop A is 120/240 volt for lighting and
receptacle loads and Drop B is a 480 volt motor load
supply, which means that this building is required to
have how many disconnecting means?

26 When a single-family dwelling has an initial load of 10 kVA 100 amperes


or above, the minimum service rating is:

27 A conductor must be sized in accordance with which of the No less than 100
following requirements: percent of the
noncontinuous
load, plus 125
percent of the
continuous load
28 Taps and splices shall not be located within ______. stems and arms

29 What is the smallest copper wire size allowed for service- No. 12 AWG
entrance conductors supplying loads consisting of
limited loads of a single branch circuit?
30 Flexible cords are not allowed for use: To replace fixed
wiring of a
structure
31 Festoon lighting is a string of outdoor lights suspended 4,5000 mm
between two points more than _______ apart.
32 If a transformer vault is not protected by an automatic 3 hours
sprinkler system, then it must have a minimum fire
resistance and structural strength of which of the
following periods of time ______.

33 Equipment connected to a 40 amp circuit requires that #10


the minimum size of the copper equipment grounding
conductor be no less than ______.

34 Give the minimum vertical clearance from finish grade of 4,600 mm


a service drop conductor installed between buildings on
residential properties and driveways?

35 The demand factor percent for the portion of a lighting None of the
load greater than 120,000 VA is _______. choices

36 Solid dielectric insulated conductors in permanent both be shielded


installations operating over 2000 volts shall _______. and have ozone-
resistant
insulation
37 Overhead service conductors, when not in excess of 600 18 feet
volts, that pass over public streets, alleys, roads, parking
lots, agricultural, or other areas subject to truck traffic
must have a minimum clearance of:

38 Article 1.10.2 of PEC 1 requires working spaces for 1100 mm


equipment operating 600 V nominal or less to ground.
This is required for live parts on the other side, like
concrete, brick or tile walls and shall be considered as
grounded. What is this minimum distance for condition
2?
39 Conductors that supply a fire pump motor must have a 125, 100
rating not less than ____ percent of the sum of the fire
pump motor’s full load current and ____ percent of any
associated fire pump accessory equipment.

40 Disregarding any exceptions, a copper-clad aluminum #6


conductor used for overhead services must be at least
______ in size.

41 Branch circuits must have ground-fault circuit 15 volts


interrupters if the branch circuit supplies a swimming
pool light fixture that exceeds ______.

42 In a switchboard there shall be an air space of at least 25 mm


______ between the energized metal part and the door of
the cabinet.

43 All wiring must be installed so that when complete the Is free of shorts
installation: and
unintentional
grounds
44 Class II locations are considered hazardous because combustible
_______ is present in quantities sufficient to create the dust
potential for combustion.

45 What percentage of fill is allowed in a conduit with three 40 %


conductors?

46 The minimum service load for each individual mobile none of the
home in a mobile home park is _______. choices
47 A fire-resistant room or enclosure must surround a 112 1//2 kVA
transformer with a rating greater than _______.

48 Which of the following statement is FALSE? Type MV cable is


rated for 2000
volts or less.
49 Which of the following shall be used to connect the An equipment
grounding terminal of a grounding receptacle to a bonding jumper
grounded box?

50 Which of the following statements is FALSE? A #14 grounded


conductor in a
circuit must be
either a white or
gray color.