3 Heavy duty lamps are used on which of the following circuit sizes? 25 amps or larger
4 If a bare live conductor is touched accidentally, the severity of electric The contact resistance between the bare
shock is determined primarily by: wire and the person at the point of contact
5 Which of the following must be provided when a No. 4 AWG or larger An insulated bushing
conductor enters a panelboard?
6 How many overcurrent device spaces are counted when using one 3- 3
pole circuit breaker?
7 What is the maximum number of main circuit breakers that may be used 2
to protect a lighting and appliance panelboard on the supply side?
8 A multiwire branch circuit protected by fuses may supply only ______. line to neutral loads
9 One receptacle on a single branch circuit must have which of the 100 percent of the branch circuit rating
following ratings?