Professional Documents
Culture Documents
TS2022 - 013 Electrical Tests Report Sofidel
TS2022 - 013 Electrical Tests Report Sofidel
Witnessed by:
Marud Somasundaram - HVSS
Comments:
Test Condition: HV vs LV
First Terminals: 1U – 1V – 1W
Second Terminals: 2U – 2V – 2W – 2N
Phase Displacement 330 °
Corr. temperature 18 °C
Corr. factor 1.04
* Reference voltage 10.0 kV
No. Meas. Test mode Freq. V out * I out * Watt losses DF meas DF corr Cap. meas Assessment
1 ICH+ICHL GST 50.00 Hz 10.00 kV 38.49 mA 1250.85 mW 0.3250 % 0.3380 % 12247.4 pF Pass
2 ICH GSTg-A 50.00 Hz 10.00 kV 8.56 mA 161.22 mW 0.1883 % 0.1958 % 2722.2 pF Pass
3 ICHL UST-A 50.00 Hz 10.00 kV 29.93 mA 1090.49 mW 0.3644 % 0.3790 % 9525.4 pF Pass
Cross check: calculated ICHL 29.92 mA 1089.64 mW 0.3641 % 9525.3 pF Pass
No. Meas. Test mode Freq. V out * I out * Watt losses DF meas DF corr Cap. meas Assessment
4 ICL+ICLH GST 50.00 Hz 6.00 kV 68.53 mA 2523.88 mW 0.3683 % 0.3830 % 21810.1 pF Pass
5 ICL GSTg-A 50.00 Hz 6.00 kV 38.60 mA 1437.55 mW 0.3724 % 0.3873 % 12284.3 pF Pass
6 ICLH UST-A 50.00 Hz 6.00 kV 29.93 mA 1088.46 mW 0.3637 % 0.3783 % 9525.6 pF Pass
Cross check: calculated ICLH 29.93 mA 1086.34 mW 0.3630 % 9525.8 pF Pass