You are on page 1of 8

Report No.

TEST REPORT TS2022_013


Table Of Contents Page 1 of 8

Serial No.: 1LTR0052398

Customer: Test Object: Serial No.: 1LTR0052398


SOFIDEL
Highest Rated Power: 15 MVA
Customer Ref.: Voltage: 33 +5 -5 x 2 % / 11 kV
TX 2 Highest Rated Current: 291 / 787 A
Customer Specification: BIL: 75 / 28 kV
Connection: Dyn11
Phase Displacement: 330
Frequency: 50Hz
Cooling Condition(s): ONAF
Oil: 5.3 Ton
Winding Temp. Rise: 65°C
HITACHI Reference:
Product Reference:
Order No.: 9902035
Name Plate No.:
Inspection and Test Plan: IEC 60076
Performed and Approved Tests: Applied Standards:
Transformer Turn Ratio and Excitation Currents IEC 60076
Windings resistance
Capacitance and Power Factor of Windings
Excitation Current
Insulation resistance

Witnessed by:
Marud Somasundaram - HVSS

Comments:

Test Department: TRES-GBHITACHI Test Date: 08th of June 2022


Date of Issue
Approved by: Stephen Curry
Issued by: Mauricio Potes
Signature: ________________
Signature TRES Operation Manager
Commissioning Engineer
This report faithfully records the results obtained during the tests, and may not be reproduced in whole or in part without
Written permission from the laboratory that emits it.
Report No.
TEST REPORT TS2022_013
Table Of Contents Page 2 of 8

Serial No.: 1LTR0052398

Transformer turns ratio .................................................................................................................. 3


Windings Resistance...................................................................................................................... 4
Excitation Current ......................................................................................................................... 6
Insulation Resistance ..................................................................................................................... 7
Capacitance and power factor ........................................................................................................ 8

Test Date: Test Engineer: Test Department:


08/06/2022 Mauricio Potes TRES-GBHITACHI
Report No.
TEST REPORT TS2022_013
Transformer turns ratio Page 3 of 8

Serial No.: 1LTR0052398

Test Condition: HV vs LV
First Terminals: 1U – 1V – 1W
Second Terminals: 2U – 2V – 2W – 2N
Phase Displacement 330 °

Tap Position Rated Voltage (V) Measured Ratio Calculated


Maximum
Ratio Difference
First Second First Second 1U – 1V 1V – 1W 1W – 1U
(with (%)
Terminals Terminals Terminals Terminals 2U- 2N 2V- 2N 2W- 2N
Multiplier)
1 - 29700 11000 4.6832 4.6833 4.6835 4.6765 0.15 %
2 - 30360 11000 4.7865 4.7864 4.7867 4.7805 0.13 %
3 - 31020 11000 4.8897 4.8896 4.8899 4.8844 0.11 %
4 - 31680 11000 4.9930 4.9928 4.9931 4.9883 0.10 %
5 - 32340 11000 5.0961 5.0961 5.0963 5.0922 0.08 %
6 - 33000 11000 5.1993 5.1992 5.1995 5.1962 0.06 %
7 - 33660 11000 5.3026 5.3024 5.3027 5.3001 0.05 %
8 - 34320 11000 5.4058 5.4056 5.4059 5.4040 0.04 %
9 - 34980 11000 5.5089 5.5088 5.5092 5.5079 0.02 %
10 - 35640 11000 5.6122 5.6120 5.6123 5.6118 0.01 %
11 - 36300 11000 5.7154 5.7151 5.7156 5.7158 0.00 %

Remarks: The polarity and phase deviation were checked.


Equipment: TESTRANO 600
Brand: Omicron
Serial Number: DM326X
Tested by : Mauricio Potes
Date last calibrated: 10/05/2022
Date next calibration: 10/05/2023
Acceptance criteria: Maximum Deviation accepted ± 0.5%
Test Results: Satisfactory

Test Date: Test Engineer: Test Department:


08/06/2022 Mauricio Potes TRES-GBHITACHI
Report No.
TEST REPORT TS2022_013
Windings resistance Page 4 of 8

Serial No.: 1LTR0052398

Test Condition: LV Winding, 50A injected


Reference Temperature: 75.0 °C
Tested Terminal Names: 2U – 2V– 2W – 2N
Average Oil Temperature: 16 °C Correction Factor: 1.245

Resistance Between Terminals (µΩ) Average Resistance at


Tap
Max Resistance Reference Temp.
Positions 2u – 2v 2v – 2w 2w – 2u
Deviation (µΩ /Phase) (µΩ /Phase)
- 27.434 27.497 27.479 0.07% 27.470 34.200

Test Condition: HV Winding, 10A injected


Reference Temperature: 75°C
Tested Terminal Names: 1U – 1V – 1W
Average Oil Temperature: 16 °C Correction Factor: 1.245

Resistance Between Terminals (m) Average Resistance at


Tap
Resistance Reference Temp.
Positions 1U – 1V 1V – 1W 1W – 1U Variation%
(m/Phase) (m/Phase)
1 282.029 282.201 282.486 0.10% 282.239 351.387
2 288.927 289.087 289.365 0.10% 289.126 359.962
3 295.711 295.886 296.162 0.09% 295.920 368.420
4 302.526 302.735 302.960 0.07% 302.740 376.912
5 309.276 309.129 309.709 0.19% 309.371 385.167
6 316.179 316.314 316.483 0.05% 316.325 393.825
7 323.034 322.902 323.243 0.11% 323.060 402.209
8 330.197 329.958 330.289 0.10% 330.148 411.034
9 336.961 336.857 337.201 0.10% 337.006 419.573
10 343.898 343.874 344.106 0.07% 343.959 428.229
11 350.551 350.859 351.294 0.12% 350.901 436.872

Graphs for HV Winding DC Resistance

Test Date: Test Engineer: Test Department:


08/06/2022 Mauricio Potes TRES-GBHITACHI
Report No.
TEST REPORT TS2022_013
Windings resistance Page 5 of 8

Serial No.: 1LTR0052398

Remarks: Equipment: TESTRANO 600


Brand: Omicron
Serial Number: DM326X
Tested by: Mauricio Potes
Date last calibrated: 10/05/2022
Date next calibration: 10/05/2023
Acceptance criteria: Maximum Deviation accepted ± 2.0%
Test Results: Satisfactory.

Test Date: Test Engineer: Test Department:


08/06/2022 Mauricio Potes TRES-GBHITACHI
Report No.
TEST REPORT TS2022_013
Excitation Current Page 6 of 8

Serial No.: 1LTR0052398

Test Condition: Windings Capacitances @ 10 kV


Applied Voltage: 10 kV to HV winding
Equipment Type: Without temperature correction
Test temperature 10°C

Tap Phase V out I out * I phase Watt losses * Reactance

1 A 10.00 kV 42.856 mA -48.47 ° 284.140 W 174.671 kΩ


1 B 10.00 kV 16.920 mA -43.29 ° 123.157 W 405.253 kΩ
1 C 10.00 kV 43.121 mA -48.00 ° 288.558 W 172.323 kΩ
6 A 10.00 kV 35.743 mA -49.07 ° 234.167 W 211.366 kΩ
6 B 10.00 kV 14.097 mA -44.06 ° 101.304 W 493.268 kΩ
6 C 10.00 kV 35.677 mA -48.45 ° 236.633 W 209.766 kΩ
11 A 10.10 kV 29.881 mA -49.14 ° 195.474 W 253.161 kΩ
11 B 10.00 kV 11.807 mA -44.11 ° 84.769 W 589.555 kΩ
11 C 10.00 kV 29.873 mA -48.67 ° 197.273 W 251.382 kΩ

Remarks: Equipment: TESTRANO 600


Brand: Omicron
Serial Number: DM326X
Tested by: Mauricio Potes
Date last calibrated: 10/05/2022
Date next calibration: 10/05/2023
Tested by: Mauricio Potes
Acceptance criteria: If the excitation current is less than 50 mA, the difference between the two
higher currents for a three-phase transformer should be less than 10 %. If the excitation
current is greater than 50 mA, the difference should be less than 5 %.
Test Results – Satisfactory

Test Date: Test Engineer: Test Department:


08/06/2022 Mauricio Potes TRES-GBHITACHI
Report No.
TEST REPORT TS2022_013
Insulation Resistance Page 7 of 8

Serial No.: 1LTR0052398

Test Condition: Windings


Applied Voltage: 5,0 kV to HV - LV

Terminals Temp. Time @60s


Tested Grounded Guard (C) 15s 30s 45s 60s 20ºC
HV LV-Tank - 17 5.0 9.3 10.1 10.7 8.8
LV HV-Tank - 17 5.1 7.7 9.4 10.7 8.8
HV-LV Tank - 17 4.7 6.2 7.0 7.7 6.3

Remarks: The measurement unit is G-Ohms.


Brand: Megger
Serial number: 1005325
Tested by: Mauricio Potes
Date last calibrated: 03/02/2022
Date next calibration: 03/02/2023
Ambient temperature: 15°C
Humidity: 60%
Acceptance criteria:
Minimum allowed Absorption Index 1.2%
Minimum allowed resistances @ 60 sec 20° C
LV to Ground > 75.0 M
HV to Ground > 215 M
HV to LV > 215` M
Test Results – Satisfactory

Test Date: Test Engineer: Test Department:


08/06/2022 Mauricio Potes TRES-GBHITACHI
Report No.
TEST REPORT TS2022_013
Capacitance and power factor Page 8 of 8

Serial No.: 1LTR0052398

Test Condition: Windings Capacitances @ 10 kV


Applied Voltage: 10 kV to HV winding
Equipment Type: Without temperature correction
Test temperature 10°C

Block 1: injection at Pri

Corr. temperature 18 °C
Corr. factor 1.04
* Reference voltage 10.0 kV

No. Meas. Test mode Freq. V out * I out * Watt losses DF meas DF corr Cap. meas Assessment

1 ICH+ICHL GST 50.00 Hz 10.00 kV 38.49 mA 1250.85 mW 0.3250 % 0.3380 % 12247.4 pF Pass
2 ICH GSTg-A 50.00 Hz 10.00 kV 8.56 mA 161.22 mW 0.1883 % 0.1958 % 2722.2 pF Pass
3 ICHL UST-A 50.00 Hz 10.00 kV 29.93 mA 1090.49 mW 0.3644 % 0.3790 % 9525.4 pF Pass
Cross check: calculated ICHL 29.92 mA 1089.64 mW 0.3641 % 9525.3 pF Pass

Block 2: injection at Sec


Corr. temperature 18 °C
Corr. factor 1.04
* Reference voltage 10.0 kV

No. Meas. Test mode Freq. V out * I out * Watt losses DF meas DF corr Cap. meas Assessment

4 ICL+ICLH GST 50.00 Hz 6.00 kV 68.53 mA 2523.88 mW 0.3683 % 0.3830 % 21810.1 pF Pass
5 ICL GSTg-A 50.00 Hz 6.00 kV 38.60 mA 1437.55 mW 0.3724 % 0.3873 % 12284.3 pF Pass
6 ICLH UST-A 50.00 Hz 6.00 kV 29.93 mA 1088.46 mW 0.3637 % 0.3783 % 9525.6 pF Pass
Cross check: calculated ICLH 29.93 mA 1086.34 mW 0.3630 % 9525.8 pF Pass

Remarks: Equipment: TESTRANO 600


Brand: Omicron
Serial Number: DM326X
Tested by: Mauricio Potes
Date last calibrated: 10/05/2022
Date next calibration: 10/05/2023
Acceptance criteria: P.F.  0.5 Good (G)
0.5 < P.F.  0.7 Deteriorated (D)
0.7 < P.F.  1.0 (& Increasing) Investigate (I)
P.F. > 1.0 Bad (B)
Test Results: Satisfactory

Test Date: Test Engineer: Test Department:


08/06/2022 Mauricio Potes TRES-GBHITACHI